LED indicators, Wires, Auxiliary Input and Output


C3-200 Installation Guide
Vision: 1 . 0 . 1

Notes:

Date: Oct. 2010

1.Cautions
Please note the following cautions.Mis-operation may lead to personal injury or equipment failure:

1)Meaning of LED indicators:

2)Recommended use of wires

LINK indicator(green): always(green) indicates TCP/IP


communication is proper;

A Use 2-conducotor power cord

ACT indicator(yellow):its flashing indicates data is in transmitting


through TCP/IP communication.

B Use 6-conductor wire between wiegand reader and control panal


(RVVP 6*0.5mm) (To choose the proper cord according to the
interface you connect, such as 6,8,10 cord.)

TX indicator(yellow):its flashing indicates it is sending data through


RS485 communication.

C Use 4-conducotor lock power cord (RVV 4*0.75mm)

RX indicator(green):its flashing indicates it is receiving data through


RS485 communication.

1 Do not energize the system before installation is complete; never carry out installation activities when the system is energized.

Auxiliary output indicator(green):always(green) indicates it is in use.

2 All peripheral devices must be grounded.

Lock indicator(green):always(green) indicates lock is open.

3 It is preferred that all wires run through PVC or galvanized pipes.

POWER indicator(red): always(red) indicates control panel is power


on.

4 It is strongly recommended that the length of exposed part of any connection cable should not be longer than 4 mm. Professional
clamping tools may be used to avoid unintentional contact of exposed wires to avoid short-circuit or communication failure.

D Use 2-conducotor switch power cordRVV 2*0.5mm)


3)The auxiliary input may be connnected to infrared body detectors,
alam switches,etc.
4)The auxiliary output may be connected to door bells,alarms,etc.

RUN indicator(green):its flashing indicates the system works normally.


CARD indicator(yellow):its flashing indicates card is punched on reader.

5 It is recommended that card readers and buttons should be installed at height of 1.4m-1.5m above ground.
6 It is recommended to use the power supply in case for control panel, and external power supply for each lock.
LINK

IN
GND
GND
485485+

EXT

IN

BUTTON1

5 6 7 8

Backup battery Power supply Control panel

Advanced Access Control

TX
RX

Appearance of case

Auxiliary output2

A
A
Power of Control panel

1
Get through the thread hole

2
Fixed case

LOCK POWER

Power of lock

V+
V+12V
GND

Door2

LOCK2

Thread hole

SEN
GND
NO
COM
NC

BEEP
GLED
WD1
WD0
GND
+12V
BEEP
GLED
WD1
WD0
GND
POWER
RUN CARD +12V

READER4

{
{

IN
GND

READER3

3.Get through the thread hole

BEEP
GLED
WD1
WD0
GND
+12V

BUTTON2

Door1

SEN
GND
NO
COM
NC

NO
COM
NC

LOCK1

Auxiliary output1
Thread hole

NO
COM
NC

AUXOUT2

{
{

AUXOUT1

Heat
dissipation
hole

GND
BEEP
GLED
WD1
WD0
GND
+12V

READER2

PC

PC RS485 interface

TX
RX

485+
485GND

READER1

Key hole

Extended
RS485 output

1# Door Button

1#Door
wiegand reader

1#Door
wiegand reader

ON

1 2 3 4

2.Components

Dip switch

{
{
{
{

+12V
ACT

Auxiliary input2

(green) flashes.

GND

Auxiliary input1

Ethernet interface

{
{

LAN

Connect the system to the power supply.If the system works properly,the POWER indicator(red) is lit constantly and the RUN indicator

AUX2

IN

SD card

AUX1

Description of normal working state:

2# Door Button

2#Door
wiegand reader

2#Door
wiegand reader

5.RS485 address setting, Restore factory setting, Terminal resistance setting

7.Equipment communication

Set RS485 address through DIP switch:


The background PC software is able to communicate with the system according to two protocols(RS485 and TCP/IP) for data exchange and
remote management. The communication cable should be away from high-voltage lines as far as possible. Do not keep the communication cable
in parallel with power cords or bind them together.

1) Place 1-6 on DIP switch are for setting the number of control panel when communicating through RS485, it is adopted for binary coding,
and little endian, the address represented by place 1-6 are shown as figurue(5-1).
2) Before setting the address, please keep the system is power off, Jump place 1-6 to desired status, and the address number shall not be the
same as another one in the network. For example: to set the device number as 39 (39=1+2+4+32), the corresponding RS485 code is 111001,
then Jump place 1,2,3 and 6 at ON status.
ON

1.TCP/IP Communication

PC

3) Place 7 is for restoring factory default settings, Jump it for three times within 10 seconds and restart the system, then all information in
RAM of control panel will be cleared and the system restores factory default settings.

Switch

4) Place 8 is for setting terminal resistance when communicating through RS485. Jump it at ON status, then it is equivalent to have a
terminal resistance of 120 ohm between 485+ and 485-.
1# control panel

n# control panel

2# control panel

Diagram of places of DIP switch.


LINK

LINK

LINK

AUX2

AUXOUT1

NO
COM
NC

IN
GND

READER4

GND
POWER
RUN CARD +12V

GND

READER3

LOCK POWER

BEEP
GLED
WD1
WD0

V+
V+12V

BUTTON2

LOCK2

BEEP
GLED
WD1
WD0
GND
+12V

BEEP
GLED
WD1
WD0
GND
+12V

LOCK1

SEN
GND
NO
COM
NC

AUXOUT2

READER4

NO
COM
NC
SEN
GND
NO
COM
NC

IN
GND
BEEP
GLED
WD1
WD0
GND
+12V

READER2

PC

485+
485GND

GND
485485+

READER1

TX
RX

BUTTON1

Advanced Access Control

EXT

5 6 7 8

BEEP
GLED
WD1
WD0
GND
POWER
RUN CARD +12V

ON

READER3

GND

ACT

TX
RX

BUTTON2

LOCK POWER

READER4

V+
V+12V

1 2 3 4

READER2

IN
GND

AUX1

LAN

BEEP
GLED
WD1
WD0
GND
+12V

BEEP
GLED
WD1
WD0
GND
+12V

LOCK2

SEN
GND
NO
COM
NC

LOCK1

SEN
GND
NO
COM
NC

BEEP
GLED
WD1
WD0
GND
+12V

READER1

AUXOUT2

NO
COM
NC

BUTTON1

AUXOUT1

NO
COM
NC

EXT

ON

GND

TX
RX

485+
485GND

PC

READER3

GND
POWER
RUN CARD +12V

GND

IN

Advanced Access Control

TX
RX

BUTTON2

BEEP
GLED
WD1
WD0

V+
V+12V

5 6 7 8

READER2

GND
BEEP
GLED
WD1
WD0
GND
+12V

1 2 3 4

BEEP
GLED
WD1
WD0
GND
+12V
IN

GND
POWER
RUN CARD +12V

GND

BEEP
GLED
WD1
WD0
GND
+12V

GND
485485+

ACT

READER4

LOCK POWER

BEEP
GLED
WD1
WD0

V+
V+12V

LOCK POWER

BEEP
GLED
WD1
WD0
GND
+12V

SEN
GND
NO
COM
NC

IN
GND

GND
IN
GND
+12V

READER3

LOCK2

Restore factory setting

IN
GND

BUTTON2

LOCK1

SEN
GND
NO
COM
NC

GND
+12V

NO
COM
NC
SEN
GND
NO
COM
NC

AUXOUT2

RS485 terminal resistance

BEEP
GLED
WD1
WD0

READER2

AUXOUT1

32
16
8
4
2
1

NO
COM
NC

SEN
GND
NO
COM
NC

LOCK2

TX
RX

NO
COM
NC

LOCK1

NO
COM
NC

AUXOUT2

AUXOUT1

BEEP
GLED
WD1
WD0
GND
+12V

READER1

PC

TX
RX

485+
485GND

GND

BUTTON1

5 6 7 8

Advanced Access Control

IN

EXT

ON

1 2 3 4

GND
485485+

GND
485485+

READER1

TX
RX

+12V
ACT

TX
RX

485+
485GND

BUTTON1

Advanced Access Control


PC

IN
GND

AUX2

LAN

GND

AUX1

IN

SD card

ACT

5 6 7 8

LINK

IN

SD card

+12V
EXT

ON

1 2 3 4

ON

GND
IN
GND

AUX2

+12V

AUX1

IN

SD card
LAN

IN
GND

AUX2

LAN

GND

AUX1

IN

SD card

2.RS485 Communication

figure(5-1)

GND
485-

6.Connection of lock
5

485+

485

serial line

Converter

1) Control panel provides lock control output interfaces. For NO lock ,it is open when power is on, and closed when power is off, so COM and

NO interfaces should be used; For NC lock, it is open when power is off, and closed when power is on, so COM and NC interfaces should be

485+

485+

485+

used.

485-

485-

485-

GND

GND

GND

PC

2
3
4
5

2) Control panel supports dry mode and wet mode by setting the jumper, it is wet mode when connecting V+ V- Input interfaces to
supply power for locks, please shorten 2-3 and 4-5

. Equipment factory default setting is dry mode. For setting dry mode and

1# control panel

2# control panel
8# control panel

wet mode, please refer to <<C3-100/200/400 access control panel installation instructions>>.

AUX1
AUX2

AUXOUT1

NO
COM
NC

7 8

READER4

BEEP
GLED
WD1
WD0
GND
POWER
RUN CARD +12V

READER3

LOCK POWER

GND

IN

BEEP
GLED
WD1
WD0
GND
+12V

BUTTON2

LOCK2

V+
V+12V

BEEP
GLED
WD1
WD0
GND
+12V

GND

LOCK1

SEN
GND
NO
COM
NC

AUXOUT2

NO
COM
NC
SEN
GND
NO
COM
NC

READER2

TX
RX

IN
GND
BEEP
GLED
WD1
WD0
GND
+12V

READER1

485+
485GND

GND
485485+

BUTTON1

TX
RX

EXT

Advanced Access Control


PC

READER4

BEEP
GLED
WD1
WD0
GND
POWER
RUN CARD +12V

READER3

GND

BEEP
GLED
WD1
WD0
GND
+12V

BUTTON2

LOCK POWER

V+
V+12V

IN
GND

LOCK2

SEN
GND
NO
COM
NC

LOCK1

SEN
GND
NO
COM
NC

BEEP
GLED
WD1
WD0
GND
+12V

ACT

5 6 7 8

AUXOUT2

NO
COM
NC

ON

AUXOUT1

NO
COM
NC

READER2

PC

TX
RX

BEEP
GLED
WD1
WD0
GND
+12V

READER1

TX
RX

485+
485GND

IN
GND

BUTTON1

5 6 7 8

Advanced Access Control

1 2 3 4

GND
485485+

ACT

GND
IN
GND
+12V

EXT

ON

GND
POWER
RUN CARD +12V

READER4

GND

READER3

BEEP
GLED
WD1
WD0

V+
V+12V

BUTTON2

LOCK POWER

GND
BEEP
GLED
WD1
WD0
GND
+12V

LOCK2

READER3
READER4

BEEP
GLED
WD1
WD0
GND
POWER
RUN CARD +12V

BUTTON2

BEEP
GLED
WD1
WD0
GND
+12V

READER2

IN

IN

LOCK1

GND
BEEP
GLED
WD1
WD0
GND
+12V

BEEP
GLED
WD1
WD0
GND
+12V

1 2 3 4

AUXOUT2

SEN
GND
NO
COM
NC

READER1

GND

BUTTON1

V+
V+12V

EXT

SEN
GND
NO
COM
NC

IN

GND

+
Lock power
input

NO
COM
NC

GND
485485+

BEEP
GLED
WD1
WD0
GND
+12V
1

FR107

SEN
GND
NO
COM
NC

LOCK POWER

NC Lock

NC

SEN
GND
NO
COM
NC

LOCK2

Diode

NO
COM
NC

LOCK1

NO
COM
NC

AUXOUT2

COM

AUXOUT1

GND
NO

LOCK

TX
RX

485+
485GND
TX
RX

SEN

Advanced Access Control


PC

ACT

5 6 7 8

Enlarged diagram
of lock ports

Diode

ON

LOCK

1 2 3 4

FR107

NO Lock

AUXOUT1

+12V

NO
COM
NC

BEEP
GLED
WD1
WD0
GND
+12V

READER2

TX
RX

IN
GND

READER1

PC

IN
GND

AUX2

LAN

GND

AUX1

IN

SD card

TX
RX

485+
485GND

GND
485485+

BUTTON1

5 6 7 8

LINK

Advanced Access Control

IN

SD card

+12V
EXT

ON

1 2 3 4

ACT

GND
IN
GND

LAN

+12V

AUX2

SD card
LAN

IN
GND

AUX2

LAN

GND

AUX1

SD card

IN

ON

LINK

LINK
IN

1 2 3 4 5 6

LINK

AUX1

3) When the Electrical Lock is connected to the Access Control System, you need to parallel one FR107 diode (equipped in the package) to
prevent the self-inductance EMF affecting the system, do not reverse the polarities.

DIP switch

LED
1

2
3
4
5
Jumper
terminal

Notes
1) Internationally accepted RVSP(shielded twisted-pair) wires should be used for communication to effectively avoid interference. RS485
communication wires should be connected by means of bus cascade connection.
2)Considering stability of communication, it is recommended the length of RS485 bus is less than 600m
3) One RS485 BUS may hold 63 units of control panel, but it is not recommended to connect with more than 32 units access control panels..
4)When the bus is longer than 300m, to enhance the stability of communication, it is necessary to keep place 8 of DIP switches of
the first and the last control panel at ON status. As shown in the figure above, place 8 of the DIP switches of units 1# and 8#