Detailed Performance Summary For EFR-1

Project: HOTEL DANN BUCARAMANGA


Prepared By:

01/07/2016
04:21PM

PackagedChillerReport:DoNotEdit;

Unit Information
EFR-1
Tag Name:
30RB090
Model Number:
Air Cooled
Condenser Type:
Scroll
Compressor Type:
208/230-3-60
Nameplate Voltage:
2
Quantity:
Manufacturing Source: Charlotte, NC USA
R410A
Refrigerant:
4
Capacity Control Steps:
22.0
Minimum Capacity:
6590
Shipping Weight:
6855
Operating Weight:
142
Unit Length:
89
Unit Width:
90
Unit Height:
32
Minimum Outdoor Operating Temp:
11.6
Chiller Pressure Drop:
Performance Information
Cooling Capacity:
Total Compressor Power:
Total Fan Motor Power:
Pump Power:
Total Unit Power (without pump):
Total Unit Power (with pump):
Efficiency (without pump):
Evaporator Information
Fluid Type:
Fouling Factor:
Leaving Temperature:
Entering Temperature:
Fluid Flow:

90.8
80.7
13.8
8.79
94.5
103.3
11.52

Fresh Water
0.00010
44.0
54.0
217.1

Condenser Information
Altitude:
Number of Fans:
Total Condenser Fan Air Flow:
Entering Air Temperature:

Packaged Chiller Builder NACO 3.49m

Accessories and Installed Options


Al Fin/Cu Tube, Pre-Coat
Dual Pump, 15 HP w/ VFD
Single Point
Coil Trim Panels
V-Ph-Hz

%
lb
lb
in
in
in
F
ft wg

Electrical Information
Unit Voltage:
Connection Type:
Minimum Voltage:
Maximum Voltage:

Amps
MCA
MOCP
ICF
Rec Fuse Size

208/230-3-60 V-Ph-Hz
Single Point
187 Volts
253 Volts
Electrical
Circuit 1
470.3
500.0
925.7
500.0

Electrical
Circuit 2
---------

Tons
kW
kW
kW
kW
kW
EER

(hr-sqft-F)/BTU
F
F
gpm

3116 ft
6
74400 CFM
86.0 F

Page 1 of 16

Detailed Performance Summary For EFR-1


Project: HOTEL DANN BUCARAMANGA
Prepared By:
Integrated Pump Information
Dynamic Head At Pump:
Dynamic Head External To Chiller:

Packaged Chiller Builder NACO 3.49m

01/07/2016
04:21PM

131.0 ft
119.5 ft

Page 2 of 16

Detailed Performance Summary For EFR-1


Project: HOTEL DANN BUCARAMANGA
Prepared By:
Integrated Part Load Value (AHRI)
IPLV:

Unit Performance
Percent of Full Load Capacity, %
Percent of Full Load Power, %
Unloading Sequence
Cooling Capacity, Tons
Total Unit Power, kW
Efficiency, EER
Evaporator Data
Fluid Entering Temperature, F
Fluid Leaving Temperature, F
Fluid Flow Rate, gpm
Fouling Factor, (hr-sqft-F)/BTU
Condenser Data
Entering Air Temperature, F

01/07/2016
04:21PM

13.68 EER

100
100.0
B
86.3
101.1
10.25

75
61.3
B
64.7
62.0
12.54

50
35.9
B
43.2
36.3
14.28

25
16.4
B
21.6
16.5
15.67

54.0
44.0
207.2
0.0001

51.5
44.0
207.2
0.0001

49.0
44.0
207.2
0.0001

46.5
44.0
207.2
0.0001

95.0

80.0

65.0

55.0

All performance efficiency data are without pump.


Sound power measured in accordance with ANSI/AHRI 370-2001.
Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Using Vapor Compression Cycle Certification
Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI
Directory at www.ahridirectory.org.

Packaged Chiller Builder NACO 3.49m

Page 3 of 16

Detailed Performance Summary For EFR-1


Project: HOTEL DANN BUCARAMANGA
Prepared By:
Unit Parameters
Tag Name:
Model Number:
Condenser Type:
Compressor Type:
Chiller Nameplate Voltage:
Quantity:
Manufacturing Source:
Refrigerant:
Shipping Weight:
Operating Weight:
Unit Length:
Unit Width:
Unit Height:

EFR-1
30RB090
Air Cooled
Scroll
208/230-3-60
2
Charlotte, NC USA
R410A
6590
6855
142
89
90

01/07/2016
04:21PM

V-Ph-Hz

lb
lb
in
in
in

1 - Chiller Height Above Ground


2 - Horizontal Distance From Chiller to Receiver
3 - Receiver Height Above Ground
(See Note 3)

Accessories and Installed Options


Al Fin/Cu Tube, Pre-Coat
Dual Pump, 15 HP w/ VFD

Single Point
Coil Trim Panels

Acoustic Information
Table 1. A-Weighted Sound Power Levels (dB re 1 picowatt). See note #1.
Octave Band Center Frequency, Hz
100% Load
75% Load
50% Load
25% Load

31
37
36
37
31

63
68
72
68
64

125
80
80
80
75

250
87
87
87
81

500
93
93
93
87

1k
97
97
97
90

2k
93
92
92
87

4k
89
89
88
83

8k
80
80
79
72

Overall
100
100
100
94

Table 2. A-Weighted Sound Pressure Levels (dB re 20 micropascals) calculated based upon user defined input for
dimensions 1, 2 and 3 as shown in above diagram. See note #2 and #3.
Octave Band Center Frequency, Hz
100% Load
75% Load
50% Load
25% Load

31
9
8
9
3

63
40
44
40
36

125
52
52
52
47

250
59
59
58
53

500
65
65
64
58

1k
69
69
69
62

2k
65
64
64
59

4k
61
61
60
54

8k
52
51
51
44

Overall
72
72
72
65

Notes: (1) Measurements performed in accordance with AHRI Standard 370 for air cooled Chillers.
(2) Chiller is assumed to be a point source on a reflecting plane.
(3) Without user defined input, the default dimensions used to construct Table 2 are as follows:
1 - Chiller Height Above Ground = 0.0 ft
2 - Horizontal Distance From Chiller to Receiver = 30.0 ft
3 - Receiver Height Above Ground = 3.0 ft

Packaged Chiller Builder NACO 3.49m

Page 4 of 16

Detailed Performance Summary For EFR-1 OP MCHX


Project: HOTEL DANN BUCARAMANGA
Prepared By:

01/07/2016
04:21PM

PackagedChillerReport:DoNotEdit;

Unit Information
EFR-1 OP MCHX
Tag Name:
30RB090
Model Number:
Air Cooled
Condenser Type:
Scroll
Compressor Type:
208/230-3-60
Nameplate Voltage:
2
Quantity:
Manufacturing Source: Charlotte, NC USA
R410A
Refrigerant:
4
Capacity Control Steps:
22.0
Minimum Capacity:
6107
Shipping Weight:
6372
Operating Weight:
142
Unit Length:
89
Unit Width:
90
Unit Height:
32
Minimum Outdoor Operating Temp:
11.6
Chiller Pressure Drop:
Performance Information
Cooling Capacity:
Total Compressor Power:
Total Fan Motor Power:
Pump Power:
Total Unit Power (without pump):
Total Unit Power (with pump):
Efficiency (without pump):
Evaporator Information
Fluid Type:
Fouling Factor:
Leaving Temperature:
Entering Temperature:
Fluid Flow:

91.1
80.2
13.8
8.80
94.1
102.9
11.61

Fresh Water
0.00010
44.0
54.0
217.8

Condenser Information
Altitude:
Number of Fans:
Total Condenser Fan Air Flow:
Entering Air Temperature:

Packaged Chiller Builder NACO 3.49m

Accessories and Installed Options


Micro Channel
Dual Pump, 15 HP w/ VFD
Single Point
Coil Trim Panels
V-Ph-Hz

%
lb
lb
in
in
in
F
ft wg

Electrical Information
Unit Voltage:
Connection Type:
Minimum Voltage:
Maximum Voltage:

Amps
MCA
MOCP
ICF
Rec Fuse Size

208/230-3-60 V-Ph-Hz
Single Point
187 Volts
253 Volts
Electrical
Circuit 1
470.3
500.0
925.7
500.0

Electrical
Circuit 2
---------

Tons
kW
kW
kW
kW
kW
EER

(hr-sqft-F)/BTU
F
F
gpm

3116 ft
6
74400 CFM
86.0 F

Page 5 of 16

Detailed Performance Summary For EFR-1 OP MCHX


Project: HOTEL DANN BUCARAMANGA
Prepared By:
Integrated Pump Information
Dynamic Head At Pump:
Dynamic Head External To Chiller:

Packaged Chiller Builder NACO 3.49m

01/07/2016
04:21PM

131.0 ft
119.3 ft

Page 6 of 16

Detailed Performance Summary For EFR-1 OP MCHX


Project: HOTEL DANN BUCARAMANGA
Prepared By:
Integrated Part Load Value (AHRI)
IPLV:

Unit Performance
Percent of Full Load Capacity, %
Percent of Full Load Power, %
Unloading Sequence
Cooling Capacity, Tons
Total Unit Power, kW
Efficiency, EER
Evaporator Data
Fluid Entering Temperature, F
Fluid Leaving Temperature, F
Fluid Flow Rate, gpm
Fouling Factor, (hr-sqft-F)/BTU
Condenser Data
Entering Air Temperature, F

01/07/2016
04:21PM

13.73 EER

100
100.0
B
86.6
100.7
10.32

75
61.4
B
64.9
61.8
12.60

50
36.0
B
43.3
36.3
14.32

25
16.4
B
21.6
16.5
15.74

54.0
44.0
207.8
0.0001

51.5
44.0
207.8
0.0001

49.0
44.0
207.8
0.0001

46.5
44.0
207.8
0.0001

95.0

80.0

65.0

55.0

All performance efficiency data are without pump.


An uncoated Novation condenser coil was selected for this product. This is based on an installed location that must be analyzed and
guidance provided by applications engineering and a non-corrosive localized environment.
Sound power measured in accordance with ANSI/AHRI 370-2001.
Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Using Vapor Compression Cycle Certification
Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI
Directory at www.ahridirectory.org.

Packaged Chiller Builder NACO 3.49m

Page 7 of 16

Detailed Performance Summary For EFR-1 OP MCHX


Project: HOTEL DANN BUCARAMANGA
Prepared By:
Unit Parameters
Tag Name:
Model Number:
Condenser Type:
Compressor Type:
Chiller Nameplate Voltage:
Quantity:
Manufacturing Source:
Refrigerant:
Shipping Weight:
Operating Weight:
Unit Length:
Unit Width:
Unit Height:

EFR-1 OP MCHX
30RB090
Air Cooled
Scroll
208/230-3-60
2
Charlotte, NC USA
R410A
6107
6372
142
89
90

01/07/2016
04:21PM

V-Ph-Hz

lb
lb
in
in
in

1 - Chiller Height Above Ground


2 - Horizontal Distance From Chiller to Receiver
3 - Receiver Height Above Ground
(See Note 3)

Accessories and Installed Options


Micro Channel
Dual Pump, 15 HP w/ VFD

Single Point
Coil Trim Panels

Acoustic Information
Table 1. A-Weighted Sound Power Levels (dB re 1 picowatt). See note #1.
Octave Band Center Frequency, Hz
100% Load
75% Load
50% Load
25% Load

31
37
36
37
31

63
68
72
68
64

125
80
80
80
75

250
87
87
87
81

500
93
93
93
87

1k
97
97
97
90

2k
93
92
92
87

4k
89
89
88
83

8k
80
80
79
72

Overall
100
100
100
94

Table 2. A-Weighted Sound Pressure Levels (dB re 20 micropascals) calculated based upon user defined input for
dimensions 1, 2 and 3 as shown in above diagram. See note #2 and #3.
Octave Band Center Frequency, Hz
100% Load
75% Load
50% Load
25% Load

31
9
8
9
3

63
40
44
40
36

125
52
52
52
47

250
59
59
58
53

500
65
65
64
58

1k
69
69
69
62

2k
65
64
64
59

4k
61
61
60
54

8k
52
51
51
44

Overall
72
72
72
65

Notes: (1) Measurements performed in accordance with AHRI Standard 370 for air cooled Chillers.
(2) Chiller is assumed to be a point source on a reflecting plane.
(3) Without user defined input, the default dimensions used to construct Table 2 are as follows:
1 - Chiller Height Above Ground = 0.0 ft
2 - Horizontal Distance From Chiller to Receiver = 30.0 ft
3 - Receiver Height Above Ground = 3.0 ft

Packaged Chiller Builder NACO 3.49m

Page 8 of 16

Detailed Performance Summary For EFR-1 OP 30RAP


Project: HOTEL DANN BUCARAMANGA
Prepared By:

01/07/2016
04:21PM

PackagedChillerReport:DoNotEdit;

Unit Information
EFR-1 OP 30RAP
Tag Name:
30RAP090
Model Number:
Air Cooled
Condenser Type:
Scroll
Compressor Type:
208/230-3-60 V-Ph-Hz
Nameplate Voltage:
1
Quantity:
Manufacturing Source: Charlotte, NC USA
R410A
Refrigerant:
6
Capacity Control Steps:
17.0 %
Minimum Capacity:
4663 lb
Shipping Weight:
4763 lb
Operating Weight:
151 in
Unit Length:
88 in
Unit Width:
78 in
Unit Height:
32 F
Minimum Outdoor Operating Temp:
26.5 ft wg
Chiller Pressure Drop*:
*Use Chiller Pressure Drop for sizing pumps. This value
includes losses due to chiller piping, fittings, 40 mesh factory
supplied strainer and BPHX.
Performance Information
Cooling Capacity:
Total Compressor Power:
Total Fan Motor Power:
Pump Power:
Total Unit Power (without pump):
Total Unit Power (with pump):
Efficiency (without pump):

87.8
84.2
8.61
8.71
92.8
101.5
11.35

Accessories and Installed Options


Al Fin/Cu Tube, Pre-Coat
Value Sound
Dual Pump, 15 HP w/ VFD
Single Point
Electrical Information
Unit Voltage:
Connection Type:

Amps
MCA
MOCP
ICF
Rec Fuse Size

208/230-3-60 V-Ph-Hz
Single Point
Electrical
Circuit 1
425.1
450.0
695.3
450.0

Electrical
Circuit 2
---------

Tons
kW
kW
kW
kW
kW
EER

Evaporator Information
Fresh Water
Fluid Type:
0.00010 (hr-sqft-F)/BTU
Fouling Factor:
44.0 F
Leaving Temperature:
54.0 F
Entering Temperature:
209.9 gpm
Fluid Flow:
12.2 ft wg
Evaporator Pressure Drop*:
*Refer to Chiller Pressure Drop for sizing pumps.
Condenser Information
Altitude:
Number of Fans:
Total Condenser Fan Air Flow:
Entering Air Temperature:

Packaged Chiller Builder NACO 3.49m

3116 ft
6
61500 CFM
86.0 F

Page 9 of 16

Detailed Performance Summary For EFR-1 OP 30RAP


Project: HOTEL DANN BUCARAMANGA
Prepared By:
Integrated Pump Information
Dynamic Head At Pump:
Dynamic Head External To Chiller:

Packaged Chiller Builder NACO 3.49m

01/07/2016
04:21PM

132.0 ft
105.6 ft

Page 10 of 16

Detailed Performance Summary For EFR-1 OP 30RAP


Project: HOTEL DANN BUCARAMANGA
Prepared By:
Integrated Part Load Value (AHRI)
IPLV:

Unit Performance
Percent of Full Load Capacity, %
Percent of Full Load Power, %
Unloading Sequence
Cooling Capacity, Tons
Total Unit Power, kW
Efficiency, EER
Evaporator Data
Fluid Entering Temperature, F
Fluid Leaving Temperature, F
Fluid Flow Rate, gpm
Fouling Factor, (hr-sqft-F)/BTU
Condenser Data
Entering Air Temperature, F

01/07/2016
04:21PM

15.07 EER

100
100.0
A
84.0
99.8
10.09

75
54.4
A
63.0
54.3
13.91

50
32.8
A
42.0
32.8
15.38

25
13.8
A
21.0
13.7
18.34

54.0
44.0
201.5
0.0001

51.5
44.0
201.5
0.0001

49.0
44.0
201.5
0.0001

46.5
44.0
201.5
0.0001

95.0

80.0

65.0

55.0

For some 75% operating points, the efficiency may be calculated at a condenser inlet air operating temperature as much as 0.8
degrees higher.

All performance efficiency data are without pump.


Sound power measured in accordance with ANSI/AHRI 370-2001.
Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Using Vapor Compression Cycle Certification
Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI
Directory at www.ahridirectory.org.

Packaged Chiller Builder NACO 3.49m

Page 11 of 16

Detailed Performance Summary For EFR-1 OP 30RAP


Project: HOTEL DANN BUCARAMANGA
Prepared By:
Unit Parameters
Tag Name:
Model Number:
Condenser Type:
Compressor Type:
Chiller Nameplate Voltage:
Quantity:
Manufacturing Source:
Refrigerant:
Shipping Weight:
Operating Weight:
Unit Length:
Unit Width:
Unit Height:

EFR-1 OP 30RAP
30RAP090
Air Cooled
Scroll
208/230-3-60
1
Charlotte, NC USA
R410A
4663
4763
151
88
78

01/07/2016
04:21PM

V-Ph-Hz

lb
lb
in
in
in

1 - Chiller Height Above Ground


2 - Horizontal Distance From Chiller to Receiver
3 - Receiver Height Above Ground
(See Note 3)

Accessories and Installed Options


Al Fin/Cu Tube, Pre-Coat
Value Sound
Dual Pump, 15 HP w/ VFD
Single Point

Acoustic Information
Table 1. A-Weighted Sound Power Levels (dB re 1 picowatt). See note #1.
Octave Band Center Frequency, Hz
100% Load
75% Load
50% Load
25% Load

31
42
42
41
40

63
75
75
74
73

125
82
82
81
80

250
88
88
88
87

500
94
94
93
92

1k
95
95
94
93

2k
93
92
91
90

4k
89
89
88
87

8k
84
84
83
82

Overall
100
100
99
98

Table 2. A-Weighted Sound Pressure Levels (dB re 20 micropascals) calculated based upon user defined input for
dimensions 1, 2 and 3 as shown in above diagram. See note #2 and #3.
Octave Band Center Frequency, Hz
100% Load
75% Load
50% Load
25% Load

31
14
14
13
12

63
47
47
46
45

125
54
54
53
52

250
60
60
59
58

500
66
66
65
64

1k
67
66
66
65

2k
64
64
63
62

4k
61
61
60
59

8k
56
56
55
54

Overall
72
72
71
70

Notes: (1) Measurements performed in accordance with AHRI Standard 370 for air cooled Chillers.
(2) Chiller is assumed to be a point source on a reflecting plane.
(3) Without user defined input, the default dimensions used to construct Table 2 are as follows:
1 - Chiller Height Above Ground = 0.0 ft
2 - Horizontal Distance From Chiller to Receiver = 30.0 ft
3 - Receiver Height Above Ground = 3.0 ft

Packaged Chiller Builder NACO 3.49m

Page 12 of 16

Detailed Performance Summary For EFR-1 OP 30RAP MCHX


Project: HOTEL DANN BUCARAMANGA
Prepared By:

01/07/2016
04:21PM

PackagedChillerReport:DoNotEdit;

Unit Information
EFR-1 OP 30RAP MCHX
Tag Name:
30RAP090
Model Number:
Air Cooled
Condenser Type:
Scroll
Compressor Type:
208/230-3-60 V-Ph-Hz
Nameplate Voltage:
1
Quantity:
Manufacturing Source: Charlotte, NC USA
R410A
Refrigerant:
6
Capacity Control Steps:
17.0 %
Minimum Capacity:
4310 lb
Shipping Weight:
4411 lb
Operating Weight:
151 in
Unit Length:
88 in
Unit Width:
78 in
Unit Height:
32 F
Minimum Outdoor Operating Temp:
26.6 ft wg
Chiller Pressure Drop*:
*Use Chiller Pressure Drop for sizing pumps. This value
includes losses due to chiller piping, fittings, 40 mesh factory
supplied strainer and BPHX.
Performance Information
Cooling Capacity:
Total Compressor Power:
Total Fan Motor Power:
Pump Power:
Total Unit Power (without pump):
Total Unit Power (with pump):
Efficiency (without pump):

88.1
83.7
8.54
8.72
92.2
101.0
11.46

Accessories and Installed Options


Micro Channel
Value Sound
Dual Pump, 15 HP w/ VFD
Single Point
Electrical Information
Unit Voltage:
Connection Type:

Amps
MCA
MOCP
ICF
Rec Fuse Size

208/230-3-60 V-Ph-Hz
Single Point
Electrical
Circuit 1
425.1
450.0
695.3
450.0

Electrical
Circuit 2
---------

Tons
kW
kW
kW
kW
kW
EER

Evaporator Information
Fresh Water
Fluid Type:
0.00010 (hr-sqft-F)/BTU
Fouling Factor:
44.0 F
Leaving Temperature:
54.0 F
Entering Temperature:
210.6 gpm
Fluid Flow:
12.3 ft wg
Evaporator Pressure Drop*:
*Refer to Chiller Pressure Drop for sizing pumps.
Condenser Information
Altitude:
Number of Fans:
Total Condenser Fan Air Flow:
Entering Air Temperature:

Packaged Chiller Builder NACO 3.49m

3116 ft
6
61500 CFM
86.0 F

Page 13 of 16

Detailed Performance Summary For EFR-1 OP 30RAP MCHX


Project: HOTEL DANN BUCARAMANGA
Prepared By:
Integrated Pump Information
Dynamic Head At Pump:
Dynamic Head External To Chiller:

Packaged Chiller Builder NACO 3.49m

01/07/2016
04:21PM

131.9 ft
105.3 ft

Page 14 of 16

Detailed Performance Summary For EFR-1 OP 30RAP MCHX


Project: HOTEL DANN BUCARAMANGA
Prepared By:
Integrated Part Load Value (AHRI)
IPLV:

Unit Performance
Percent of Full Load Capacity, %
Percent of Full Load Power, %
Unloading Sequence
Cooling Capacity, Tons
Total Unit Power, kW
Efficiency, EER
Evaporator Data
Fluid Entering Temperature, F
Fluid Leaving Temperature, F
Fluid Flow Rate, gpm
Fouling Factor, (hr-sqft-F)/BTU
Condenser Data
Entering Air Temperature, F

01/07/2016
04:21PM

15.14 EER

100
100.0
A
84.2
99.4
10.17

75
54.5
A
63.1
54.2
13.99

50
32.9
A
42.1
32.7
15.45

25
13.8
A
21.0
13.7
18.40

54.0
44.0
202.1
0.0001

51.5
44.0
202.1
0.0001

49.0
44.0
202.1
0.0001

46.5
44.0
202.1
0.0001

95.0

80.0

65.0

55.0

For some 75% operating points, the efficiency may be calculated at a condenser inlet air operating temperature as much as 0.8
degrees higher.

All performance efficiency data are without pump.


An uncoated Novation condenser coil was selected for this product. This is based on an installed location that must be analyzed and
guidance provided by applications engineering and a non-corrosive localized environment.
Sound power measured in accordance with ANSI/AHRI 370-2001.
Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Using Vapor Compression Cycle Certification
Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI
Directory at www.ahridirectory.org.

Packaged Chiller Builder NACO 3.49m

Page 15 of 16

Detailed Performance Summary For EFR-1 OP 30RAP MCHX


Project: HOTEL DANN BUCARAMANGA
Prepared By:
Unit Parameters
EFR-1 OP 30RAP MCHX
Tag Name:
30RAP090
Model Number:
Air Cooled
Condenser Type:
Scroll
Compressor Type:
208/230-3-60
Chiller Nameplate Voltage:
1
Quantity:
Charlotte, NC USA
Manufacturing Source:
R410A
Refrigerant:
4310
Shipping Weight:
4411
Operating Weight:
151
Unit Length:
88
Unit Width:
78
Unit Height:

01/07/2016
04:21PM

V-Ph-Hz

lb
lb
in
in
in

1 - Chiller Height Above Ground


2 - Horizontal Distance From Chiller to Receiver
3 - Receiver Height Above Ground
(See Note 3)

Accessories and Installed Options


Micro Channel
Value Sound
Dual Pump, 15 HP w/ VFD
Single Point

Acoustic Information
Table 1. A-Weighted Sound Power Levels (dB re 1 picowatt). See note #1.
Octave Band Center Frequency, Hz
100% Load
75% Load
50% Load
25% Load

31
42
42
41
40

63
75
75
74
73

125
82
82
81
80

250
88
88
88
87

500
94
94
93
92

1k
95
95
94
93

2k
93
92
91
90

4k
89
89
88
87

8k
84
84
83
82

Overall
100
100
99
98

Table 2. A-Weighted Sound Pressure Levels (dB re 20 micropascals) calculated based upon user defined input for
dimensions 1, 2 and 3 as shown in above diagram. See note #2 and #3.
Octave Band Center Frequency, Hz
100% Load
75% Load
50% Load
25% Load

31
14
14
13
12

63
47
47
46
45

125
54
54
53
52

250
60
60
59
58

500
66
66
65
64

1k
67
66
66
65

2k
64
64
63
62

4k
61
61
60
59

8k
56
56
55
54

Overall
72
72
71
70

Notes: (1) Measurements performed in accordance with AHRI Standard 370 for air cooled Chillers.
(2) Chiller is assumed to be a point source on a reflecting plane.
(3) Without user defined input, the default dimensions used to construct Table 2 are as follows:
1 - Chiller Height Above Ground = 0.0 ft
2 - Horizontal Distance From Chiller to Receiver = 30.0 ft
3 - Receiver Height Above Ground = 3.0 ft

Packaged Chiller Builder NACO 3.49m

Page 16 of 16