Documente Academic
Documente Profesional
Documente Cultură
Conductors in parallel
Short-circuit current
Overcurrent protection
principles
Contents
[hide]
Earthing system
TN-S
Tripping unit
Micrologic 2.3
Neutral distributed
No
510
Voltage (V)
400
Short-delay trip Im /
Isd (A)
5100
Frequency (Hz)
50
Cable C3
500
Length
20
Resistance of MV
network (m)
0.0351
Maximum load
current (A)
509
Reactance of MV
network (m)
0.351
Type of insulation
PVC
Ambient temperature 30
(C)
Transformer T1
Rating (kVA)
630
Conductor material
Copper
Short-circuit
impedance voltage
(%)
Transformer
resistance RT (m)
3.472
Installation method
Transformer
reactance XT (m)
10.64
Phase conductor
selected csa (mm2)
2 x 95
3-phase short-circuit
current Ik3 (kA)
21.54
Neutral conductor
selected csa (mm2)
2 x 95
PE conductor
selected csa (mm2)
1 x 95
Cable C1
Length (m)
0.53
Maximum load
current (A)
860
0.65
Type of insulation
PVC
3-phase short-circuit
current Ik3 (kA)
19.1
Ambient temperature 30
(C)
Conductor material
Copper
Switchboard B6
Single
Reference
Linergy 800
Installation method
750
Number of layers
Circuit-breaker Q7
Phase conductor
selected csa (mm2)
2 x 240
255
Neutral conductor
selected csa (mm2)
2 x 240
Type
Compact
PE conductor
selected csa (mm2)
1 x 120
Reference
NSX400F
400
3-phase short-circuit
current Ik3 (kA)
21.5
Courant de dfaut
phase-terre Id (kA)
15.9
Tripping unit
Micrologic 2.3
258
2576
Circuit-breaker Q1
860
Short-delay trip Im /
Isd (A)
Type
Compact
Cable C7
Reference
NS1000N
Length
1000
Maximum load
current (A)
255
4P4d
Type of insulation
PVC
Tripping unit
Micrologic
5.0
Ambient temperature 30
(C)
900
Conductor material
Short-delay trip Im /
Isd (A)
9000
Tripping time tm
(ms)
50
Installation method
Phase conductor
selected csa (mm2)
1 x 95
Switchboard B2
Copper
Reference
Linergy
1250
Neutral conductor
selected csa (mm2)
1050
PE conductor
selected csa (mm2)
1 x 50
0.14
Circuit breaker Q3
509
0.79
Type
Compact
3-phase short-circuit
current Ik3 (kA)
18.0
Reference
NSX630F
630
Fig. G66: Partial results of calculation carried out with Ecodial software (Schneider Electric)
The same calculation using the simplified method recommended in this guide
Dimensioning circuit C1
The MV/LV 630 kVA transformer has a rated no-load voltage of 420 V. Circuit C1 must be suitable for a current
of:
per phase
Two single-core PVC-insulated copper cables in parallel will be used for each phase.These cables will be laid on cable trays according to method F.
Each conductor will therefore carry 433A. Figure G21a indicates that for 3 loaded conductors with PVC isolation, the required c.s.a. is 240mm.
The resistance and the inductive reactance, for the two conductors in parallel, and for a length of 5 metres,
are:
X = 0,08 x 5 = 0,4 m (cable reactance: 0.08 m/m)
Dimensioning circuit C3
Circuit C3 supplies two 150kW loads with cos = 0.85, so the total load current is:
Two single-core PVC-insulated copper cables in parallel will be used for each phase. These cables will be laid on cable trays according to method F.
Each conductor will therefore carry 255A. Figure G21a indicates that for 3 loaded conductors with PVC isolation, the required c.s.a. is 95mm 2.
The resistance and the inductive reactance, for the two conductors in parallel, and for a length of 20 metres, are:
Dimensioning circuit C7
Circuit C7 supplies one 150kW load with cos = 0.85, so the total load current is:
One single-core PVC-insulated copper cable will be used for each phase. The cables will be laid on cable trays according to method F.
Each conductor will therefore carry 255A. Figure G21a indicates that for 3 loaded conductors with PVC isolation, the required c.s.a. is 95mm 2.
The resistance and the inductive reactance for a length of 20 metres is:
Calculation of short-circuit currents for the selection of circuit-breakers Q1, Q3, Q7 (see Fig. G67)
Circuit components
R
(m)
X
(m)
Z
(m)
Ikmax
(kA)
0,035
0,351
2.9
10.8
Cable C1
0.23
0.4
Sub-total
3.16
11.55
Cable C3
2.37
1.6
Sub-total
5.53
13.15
Cable C7
1.18
0.4
Sub-total
6.71
13.55
11.97
20.2
14.26
17
15.12
16
G58:
This gives:
A single 120 mm2 conductor is therefore largely sufficient, provided that it also satisfies the requirements for indirect contact protection (i.e. that its
impedance is sufficiently low).
Generally, for circuits with phase conductor c.s.a. Sph 50 mm2, the PE conductor minimum c.s.a. will be Sph / 2. Then, for circuit C3, the PE
conductor will be 95mm2, and for circuit C7, the PE conductor will be 50mm 2.
For circuit C3 of Figure G65, Figures F41 and F40, or the formula given page F25 may be used for a 3-phase 4-wire circuit.
(The value in the denominator 630 x 11 is the maximum current level at which the instantaneous short-circuit magnetic trip of the 630 A circuit-breaker
operates).
The length of 20 metres is therefore fully protected by instantaneous over-current devices.
Voltage drop
The voltage drop is calculated using the data given in Figure G28, for balanced three-phase circuits, motor power normal service (cos = 0.8).
The results are summarized on figure G68:
c.s.a.
C1
C3
C7
2 x 240mm
2 x 95mm
1 x 95mm
U per conductor
(V/A/km) see Fig.
G28
0.21
0.42
0.42
866
509
255
Length (m)
20
0.45
2.1
0.53
0.11
0.53
0.13