N o v e m b e r /2 0 0 7
T W C 77- 0 7
SOFT-STARTER SSW-07
SSW07 parameter programming via DIP-Switch
Dear Sirs,
It has been incorporated to the SSW07 a programming mode via DIP-Switch, i.e. without using the
keypad. The purpose of this programming mode is to allow to the SSW07 user to make some
modifications in the standard product, like choosing 2 or 3 -wire command, using a contactor/circuit
breaker with minimum voltage coil in the SSW07 input, and loading the fac tory parameters.
NOTE: The RESET button must be held during the whole operation.
To leave the programming mode, the RESET button just has to be released.
To use an input contactor, parameter P277 = 1 must be adjusted, allowing to the relay output RL1
the Running function. To enable parameter P277, please follow the instructions below:
Step 1 Enter in programming mode (see 1)
Step 2 Check the OVERLOAD LED
OFF: Running (P277 = 1) End of programming
ON: No Fault (P277 = 6) Continue through steps 3 and 4
Step 3 Change the OVERLOAD DIP-Switch
Step 4 Check if the OVERLOAD LED is OFF
3.2
To use an input circuit breaker with minimum voltage coil, parameter P277 = 6 must be adjusted,
allowing to the relay output RL1 the No Fault function . To enable parameter P277, please follo w
the instructions below:
Step 1 Enter in programming mode (see 1)
Step 2 Check the OVERLOAD LED
OFF: Running (P277 = 1) Continue through steps 3 and
ON: No Fault (P277 = 6) End of p rogramming
Step 3 Change the OVERLOAD DIP-Switch
Step 4 Check if the OVERLOAD LED is ON
If you need any further information, please feel free to contact us (fabiogg@weg.net).
Best regards,
Mauro Tusset