Sunteți pe pagina 1din 12

37

3. GENERATOR STATOR WATER COOLING SYSTEM-STAGE-II


DESCRIPTION AND OPERATION
3.1 INTRODUCTION
One of the efficient ways of taking away the losses from the windings of
any electrical machines is by direct cooling using water. The optimum design of
large capacity turbo generator, as a rule envisages water-cooling of stator
windings. The 200MW / 210MW / 235MW Turbo generators employ a closed loop
circulation of high quality demineralised water through the stator windings made
of hollow and solid conductors.
The generator is capable of delivering its rated load only when the stator
water-cooling system is functioning properly. Therefore it is necessary that
highest attention is paid for proper operation and maintenance of all the
equipments in this system.
This section deals with the principles of working, constructional features
and the operation and maintenance procedures of various elements of stator
water-cooling system.
This manual is prepared keeping in mind that the operating personnel have
the necessary basic knowledge of the equipment. Though in this manual, it has
been attempted to deal with all the important aspects of operation and
maintenance, it should be kept in mind that the final responsibility for operating
the unit lies with the operating company personnel and it is advisable to consult
BHEL whenever necessary. BHEL reserves the right to change or modify these
instructions, in part or full, at a later date, based on the experience gained on
similar units in course of time.

3.2 GENERAL DESCRIPTION


The heat losses arising in the stator winding, main terminal bushings and
phase connectors are removed by demineralised water coming into direct contact
with high voltage winding. The cooling water must have an electrical conductivity
of less than 2.5 micro mho/Cm. The Demineralised (DM) water supply system
comprises of following main components:
Centrifugal pumps 2 X 100 % duty
Distilled water cooler 2 X 100 % duty
Polishing Unit

38
Mechanical filters 2 X 100 % duty
Magnetic filter 1 X 100 % duty
Other components employed in the system are gas trap device, expansion
tank, water jet ejector, valves and associated instrumentation. Together with the
connecting pipe work these components form the external circuit for the supply
of cooling water to generator windings. Refer stator water system diagram. The
cooling circuit makes use of either of the following water supplies, free from
oxygen.
(a) Distilled Water.
(b) Fully demineralised water from boiler feed water treatment plant.
(c) Condensate.
Fully demineralised water from the boiler feed water treatment plant and
condensate may only be used if no chemicals, such as ammonia, hydrazine,
phosphates etc. are present in the water or condensate. A part of water is
bypassed, and is treated in mixed bed ion exchanger, connected in parallel to the
stator winding, magnetic filter and expansion tank and returned into suction side
of the water pump, thus maintaining conductivity of closed loop circulating water
within permissible limit. The DM water pumps are of single stage type with spiral
casing and overhung impeller. The pump is connected to a three phase AC Motor.
Failure of the working pump due to fault or power supply failure results in an
automatic changeover to standby pump; the criterion for such a changeover is
the falling water pressures downstream the pumps. This falling pressure is sensed
by means of a pressure switch. The heat absorbed by the DM water in the
generator is dissipated to the secondary coolant in the primary water cooler. The
water treatment plant (polishing unit) provided across the stator winding,
essentially comprises an exchanger tank filled with anion and cation resins in the
form of a mixed bed ion exchanger.
The base substances of the exchanger resins are normally polymers
containing groups of diverse character featuring exchange activity. In this way
the synthetic resins are capable of cation and anion exchange. The cation
exchanger contains highly acidic groups, while the anion exchanger comprises
highly basic groups. The exchanger resins are thus capable of accepting ions
from the DM water, while releasing equivalent amounts of other ions (hydrogen

39
ions from the cation exchanger and hydroxyl ions from the anion exchanger) to
the DM water at the same time. This exchange can only take place between
equally charged ions. Therefore, cation exchanger exchange cation and anion
exchanger exchange anion. This process takes place within a very short time
while the DM water is passed through the ion exchanger. A combination of highly
acidic cation exchanger and highly basic anion exchanger constitutes a multitude
of small demineralization units, resulting in a high purity deionite.
The mechanical filter eliminates any foreign particles in the water, which
may choke, erode the hollow conductors. Difference of pressure at inlet and
outlet of the filter is indicative of the degree of choking. The choked filter may be
cleaned after using the standby without affecting the system corking. The
magnetic filter prevents any magnetic particles from entering the generator. Any
accidental leakage of hydrogen into the main distilled water stream is detected
by gas trap device (see description of gas trap device). The water from the outlet
of stator winding collects in an overhead expansion tank, which provides a
constant level of water during normal running of the system. The hot water
enters the tank through perforated pipe in the form of spray thus releasing any
entrapped gas. A water jet ejector is connected to expansion tank for creating
vacuum for the purpose of removing any traces of Oxygen/Hydrogen Gas which
may be present as a result of hydrogen leakage into the DM water stream. Level
signaling device provided in the expansion tank monitors the high and low level
of distilled water and initiates a tripping command for stator water pump at low
level in the expansion tank. Make up DM water to the system is provided at
expansion tank through a float operated level regulator.
The quantity of DM water flowing through the windings is measured by a
system of orifice plate, flow transducers, and flow indicator and recorder.
Signalling contacts are available in flow switch/the indicator/recorder, which are
set to annunciate at low flow through the windings, and initiates tripping of the
machine at emergency flow on the principle of two out of three. Conductivity cell
and suitable indicator and recorder do continuous monitoring of the conductivity
of water, which annunciate alarm at conductivity high set value. At very high
conductivity the unit is tripped automatically. In addition to above, the system
also provides for necessary instrumentation for indicating/Signalling of the

40
temperatures and pressures at various points of the system. Pressure interlocking
of the pumps is also provided.

3.3 STATOR WATER PUMP DESCRIPTION


01. DESIGN FEATURE
Stator water for cooling the stator winding is circulated in a closed loop. To
ensure the continuous generator operation, without any interruption two full
capacity pumps are provided. The pumps have equal priority and are
alternatively brought into operation, a changeover being possible at any time
without interruption. The standby pump is kept ready for service and is
automatically started in the event of the failure of stator water supply, which
results in fall of the pressure below the set value in pressure switch installed in
the circuit. Stator water pumps are of single stage centrifugal type with spiral
casing and overhung impeller. The pumps suction is arranged in the axial
direction, while the discharge is directed radially upward. The spiral casing of the
pump is joined to the bearing housing through a flange. The pump impeller and
the spiral are of the stainless steel construction. The point casing is sealed by
means of mechanical seals. The pump shaft is supported in oil lubricated
antifriction bearing. The pump is connected to a 3 phase 415 Volt A.C. motor by a
coupling covered by the coupling guard spacer. Normally the pump-motor set is
installed at the zero meter level of the power station.

3.4 WATER COOLER DESCRIPTION


The stator water cooler is shell and tube type heat exchanger suitable for
vertical mounting, in which the D.M. water flows through the shell. Shell is made
of non-magnetic stainless steel. Cooling water flows through the tubes. Tubes are
made of stainless steel. The general arrangement of the cooler along with
different nozzle connections is shown in the diagram. To have effective heat
transfer between the coolent and cooled water, baffles made of brass are
provided across the tube nest to guide the water to be cooled in a zigzag fashion.
The cooling water is led in and out of the cooler from the flanges provided at the
bottom of the cooler. Four numbers of dial type thermometers have been
provided for the following purpose:
(i)

One thermometer each at inlet and outlet of primary water to


measure inlet and outlet temperatures.

41
(ii)

One thermometer each at inlet and outlet of secondary cooling


water to measure the inlet and outlet temperature.

3.5 STATOR WATER FILTER DESCRIPTION


The filter consists of cylindrical body having separate inlet and outlet
chambers. An assembly of 45 filter elements surrounds a perforated cylindrical
body having holes all along its length and periphery. The filter elements are kept
in position by helical spring, which is kept pressed by the cover. The filter
elements consist of sound corrugated brass sheet with a central hole and two
sizes of wire mesh aperture, 0.224 mm and 0.5 mm held in one assembly by the
inner and outer brass rings. The material of construction of body, cover, and
perforated cylinder is stainless steel whereas that of filtering element is brass.
The water enters the filters as shown in the drawing. The water after
passing through the filtering elements enters the perforated cylinder from where
it flows to the outlet chamber. Mechanical impurities get collected on the wire
meshes as the liquid passes through the mesh holes from the inlet chamber to
the delivery chamber through the perforated cylinder. The filter is provided with
vent and drain plugs.

The normal pressure drop, across the filter corresponding

to the rated flow is of the order of 0.1 0.2 kg/Cm 2 (g). As the particles get
deposited on the wire meshes, the resistance to flow increases and consequently
pressure drop across the water filter increases. When the pressure drop increases
to 0.4 kg/Cm2 (gauge) cleaning is recommended.

3.6 TECHNICAL PARTICULARS


1. Type

: Wire mesh Disc Type

2. Rated discharge

: 30 M3/hr.

3. Maximum pressure rating

: 12 kg/Cm2

4. Minimum size of particles that can be filtered

: 0.224mm.

5. Pressure drop across filter during normal running : 0.1-0.2kh/Cm2(g)


6. Pressure drop across filter at which cleaning is recommended: 0.4 kg/Cm2 (g)
7. Material of body and perforated cylinder

: Stainless Steel

8. Material of filtering elements

: Brass

9. Weight (Kg)
10.Size of wire mesh (Aperture) mm
0.5

: 71.5
: 0.224 and

42
: 38 kg/Cm2 (G) for 15
minutes.

11.Hydraulic test pressure

3.7 MAGNETIC FILTER DESCRIPTION

The magnetic filter is of permanent magnet type designed to trap


ferromagnetic (strong and average magnetic) particles, if present in the water
system. The capacity of the magnetic filter is 36 M 3/hr. Maximum strength of
magnetic field in the circular air gap is of the order of 4000 gauss. The filter
mainly consists of an upper and a lower body, housing the permanent magnet
system, comprising of the magnets, pole shoes and pole ring as shown in the
figure. The demineralised water before entering the winding passes through the
magnetic filter, where it successively passes through two annular air gaps in
which ferromagnetic particles are filtered out because the later are attracted to
the pole shoes and pole ring points in the zone of high magnetic field strength.
The filter is installed to the vertical position and is connected to the
corresponding piping flanges by means of bolts.

3.8 TECHNICAL PARTICULARS


1.

Magnetic filter type

: Y 36

2.

Magnet type

: Permanent magnet

3.

Maximum induction density

: 4000 Gauss

4.

Capacity

: 36 M3/hr.

5.

Weight

: 113 kg

6.

Pressure rating (kg/Cm2)

7.

Type of particles which can be filtered

: Highly & medium magnetic

8.

Hydraulic test pressure

: 16 kg/Cm2 for 10 minutes.

9.

Pressure drop

: Negligible

: Not more than 10

3.9 EXPANSION TANK DESCRIPTION


The expansion tank is a hermetically sealed container made of stainless
steel (see diagram). The DM water from the stator winding outlet header
discharges into a section of the tank through a perforated pipe. The tank is under
vacuum of 250-300 mm of mercury under the influence of water jet ejector. In the
proce4ss of spraying under vacuum, the entrapped air/gas in DM water, entering
the tank, if any, gets liberated and ejected out. The tank is provided with a make
up connection from the power station DM water source. The inlet of make up
water in to the tank is controlled by means of a float operated level regulator,

43
which opens or closes depending on the level in the tank. The stator water pump
draws water from the bottom of the tank for recirculation. The tank is provided
with the following instruments/components.
(i)

A gauge glass to indicate the level of the water in the tank.

(ii)

Two nos. of transducers for level signalling device to give high and
low level alarm signals.

(iii)

A vacuum gauge level regulator vacuum inside the tank.

(iv)

A float operated level regulator to regulate the make up water.

(v)

A drain valve to facilitate draining of the complete tank in case of


necessary.

3.10 VACUUM PUMP DESCRIPTION


Liquid Ring Vacuum Pump is used to create vacuum in expansion tank. It
also builds up vacuum in stator water-cooling system during starting. The pump
consists of a SHAFT mounted multibladed impeller located eccentrically in the
STATOR. Process gas is sucked through in the INLET CONTROL DISC via other
INLET PUMO CASING compressed in stator and expelled through a groove in
OUTLET CONTROL DISC into the OUTLET PUMP CASING to the atmosphere.
Service liquid is inserted into the pump by means of a control value provided.
Due to rotation of the eccentrically mounted multibladed impeller, service liquid
is thrown towards the periphery of the stator thus forming a sealant. Process gas
is trapped in the space between the impeller blades, compressed and expelled.
Thus a continuous suction cycle is initiated. The service liquid functions as a
sealant as well as coolant.

3.11 TECHNICAL DATA


01. MATERIAL OF CONSTRUCTION
*

PUMP CASING

SS316

SHAFT

IMPELLER

SS316

STATOR

SS316

CONTROL DISCS

INTERMEDIATE DISC

SS316

BEARING HOUSING

CAST IRON

SHAFT SEAL

SS

N/B FLANGE (TABLE D) BS 10

SS316

SS316

44
SERVICE LIQUID CONNECTION
COUPLING

:
:

SERVICE LIQUID USED

BSP

FLEXIBLE
:

8 LPM AT 10 Psig

0.2 PUMP DETAILS


MODEL

2T 30

VACUUM

720 mm Hg Col. (Max.)

DISPLACEMENT

51 M3/HR

R.P.M
SEALANT REQD.

:
:

3HP AT 415V 3 50 C/S

8 LPM

03. MOTOR DETAILS


MAKE

BHARAT BIJLEE

TYPE

TEFC SQUIRREL CAGE

H.P.

R.P.M
VOLTAGE

:
:

2850

415 VOLTS

3.12 POLISHING UNIT DESCRIPTION


The polishing unit serves to maintain a low electrical conductivity of
the primary water. The water treatment system is connected in parallel to
the main circuit and contains a mixed-bed ion exchanger with series
connected fine filter, an integrating flow meter and a conductivity
transmitter.

3.13 MIXED-BED ION EXCHANGER


The mixed-bed ion exchanger consists of a tank filled with anion and
cation exchanger resins. Nozzle trays in the upper and lower part of heat
exchanger tank prevent the escape of the resins into the piping system. A
fine filter after the ion exchanger retains any resins particles. An alarm is
initiated when the filter is contaminated. The water flow passing through the
ion exchanger is measured by means of an integrating flow meter after the
filter. After the ion exchanger part of the flow is passed through a
conductivity transmitter for checking the resin activity.

3.14 ION EXCHANGER RESINS


The ion exchangers consist of chemically durable and highly active
synthetic resins. The base substances of the exchanger resins are polymers.

45
The polymer in the cation exchanger contains highly acid groups, while the
polymer in the anion exchanger is composed of highly basic groups. The
exchanger resins are thus capable of accepting ions from the primary water,
while simultaneously releasing equivalent amounts of other ions (hydrogen
ions from the cation exchanger and hydroxyl ions from the anion exchanger)
to the primary water. This process takes place within a very short time while
the primary water is passed through the ion exchanger. The combination of
highly acid cation exchangers and highly basic cation exchangers forms a
multitude of small demineralization units, resulting in a high-purity de-ionate.
The number of ions it can exchange limits the capacity of the mixed-bed of
the ion exchange. This capacity is primarily determined by the type of
exchanger used, but also depends on the quantity of reactivating agent, the
rate of flow and the water temperature. When the resins are exhausted, new
resins must replace them. After removal from the primary water treatment
system, the resins can be reactivated.

3.15 SUPERVISION OF STATOR WATER COOLING SYSTEM


The most essential measuring and supervisory devices in the primary
water supply system are: (1)Specific Resistivity / Conductivity measuring device
(2)Level meter Device
(3)Flow measuring device
(4)Pressure gauges/Pressure switches.
(5)Temperature detectors and Indicators or Recorders.

3.16 SPECIFIC RESISTIVITY/CONDUCTIVITY MEASURING


DEVICE:
Within the primary water system the conductivity of the primary water
is supervised on:
(a) Down stream of the ion exchanger and
(b)Upstream of generator inlet.
The measuring point downstream of the ion exchanger serves for
checking the ion exchange for proper performance. The measuring point on
the primary water inlet to the generator permits the conductivity of the
entire cooling circuit to be assessed. Both measuring devices are equipped
for indication and alarm.

46

3.17 LEVEL METER DEVICE:


A level-signalling device senses the water level in the expansion tank,
with a high or low water level initiating an alarm. A local water level gauge is
arranged in parallel to the electrical meter system.

3.18 FLOW MEASURING SYSTEM:


The amount of water flowing through the stator winding is measured
by flow measuring system.

3.19 PRESSURE GAUGE/PRESSURE SWITCHES:


Pressures are sensed at the following measuring points in the stator
water-cooling circuit.
(1)Pressure downstream of stator water pump A.
(2)Pressure downstream of stator water pumps B.
(3)Pressure before and after water filters.
(4)Pressure switches and pressure gauge at the inlet of stator winding.
(5)Pressure gauge at the outlet of stator winding.
(6)Vacuum pressure gauge at the expansion tank.

3.20 TEMPERATURE DETECTORS/INDICATORS OR


RECORDER:
The following temperatures are measured locally by means of
thermometers.
(a) Temperature of inlet and outlet of water coolers
(b)Temperature of the water at the inlet and outlet of stator winding with
alarm contacts.
(c) Resistance thermometers at the inlet and outlet of the stator windings.
These resistance thermometers are connected to the indicators or
temperature recorder on UCB.

3.21 CONTROL PANEL DESCRIPTION


There are three control cabinets for stator water-cooling system
namely:
i)

Stator water-cooling system instrumentation cabinet.

ii)

Starting cabinet for stator water-cooling pump motors.

iii)

Annunciation cabinet.

47

3.22 GENERAL DESCRIPTION


The control cabinets are freestanding sheet steel enclosures; dust and
vermin proof, provided with mesh covered louvers on front and rear doors for
natural ventilation. The control panels are provided with:

Earthing point.

Adequate terminal station to facilitate interconnections (external).

Removable bottom cover which can be suitably drilled for fixing of


cable glands and pipe entry.

Lockable servicing door(s).

Lifting arrangement through eye bolts at the top.

3.23 EQUIPMENTS MOUNTED IN CONTROL CABINETS


The following components are mounted in the stator water-cooling
systems signalling cabinet:

Conductivity measuring indicators.

Flow indicator.

Audio-visual annunciation system equipment.

Multiplier relays, control devices etc.

Power supply units.

Alarm units.

Level switches.

D.O.L starter and control equipments for both working and standby
pump motors.

3.24 GAS TRAP DEVICE DESCRIPTION


Gas trap device is used for detecting the presence of hydrogen gas in
the water employed for cooling stator windings. Appearance of hydrogen in
the water stream is possible due to loose/leak of joints, as the water pressure
in the winding is kept lower than the hydrogen pressure in the generator
casing. This device is to be used continuously.
The main features of this device are illustrated in figure 1. It consists of
a lower cover (1), which has two drain tubes and three inlet connections
along with valves. The drain tube (2) is push fitted in disc (3) positioned
180mm from the lower cover. The sealing between tube and disc and
between disc and the transparent cylinder (4) is attained by 0-rings. This

48
drainpipe consists of a plug (5), which has a central hole and a slot, which
connects the space at the upper chamber. The hole at the centre in the plug
faces a small hole in the drainpipe, which is having small loop at the bottom.
The loop remains filled with water during normal operation thus isolating the
atmospheric gases/air from the upper chamber. The cylinder is kept in
position by four bolts (7) between upper and lower covers. Two sampling
points are provided along with valves in the upper chamber of cylinder for
gas sampling.
*-*-*-*-*-*-*-*-*-*-*-*-*-*-*-*
*-*-*-*-*-*-*-*-*-*-*-*-*

S-ar putea să vă placă și