Vaisala HUMICAP Humidity and Temperature Transmitters HMD60 and HMD70 are
designed for use in air conditioning applications where accurate and stable control
of relative humidity and temperature are required.
Resistant to Chemicals
and Dust
Temperature compensated
NIST traceable
(certificate included)
Accuracy up to 2 %RH
True two-wire transmitters
with 4 ... 20 mA loop powered
output (HMD60)
Technical Data
60 Series: 2-wire, 4 to 20 mA Output
Duct mount
General - 60 Series
RH only
RH & T
T only
HMD60U
HMD60Y
HMD60T
Supply voltage
Output signal
General - 70 Series
Duct mount
RH only
RH & T
T only
HMD70U
HMD70Y
HMD70T
Relative Humidity
Measurement range
duct mount
Accuracy at +20 C
%RH
3
2
1
0
-1
10
20
30
40
50
60
70
80
90
100 %RH
-2
-3
Temperature dependence
%RH
2.0
-20 C, + 1,5 %
1.5
1.0
0.5
0
-20
-10 0
10
-0.5
-1.0
-1.5
-2.0
+80 C, + 1,3 %
20
30
40
50
60
70
80
C
0.8
0.6
0.2
0
11 ... 24 V
17 ... 24 V
10 mA typical
12 mA typical
General
Operating temperature range
electronics
-5 ... +55 C (+23 ... +131 F)
probe
-20 ... +80 C (-4 ... +176 F)
Storage temperature range
-40 ... +80 C (-40 ... +176 F)
Maximum flow speed
50 m/s
Current module
part no. 18945 HM
Housing
probe
stainless steel
electronics
cast aluminum
Connections
screw terminals 0.5 ... 1.5 mm2
Sensor protection
standard
membrane filter (part no. DRW010525)
optional
stainless steel sintered filter (part no. HM46670SP)
Cable thread-through
bushing for 7 ... 10 mm (PG9)
cable housing IP65 (NEMA 4)
part no. 18941HM
armoured cable glands
part no. 10528HM
(must be ordered separately)
Complies with EMC standard EN61326 and EN55022
Dimensions
0.4
-0.2
-20
-10
10
20
30
40
50
60
70
80 C
Dimensions in mm (inches)
62 (2.44)
250 (9.84)
100 (3.94)
82 (3.23)
-0.6
-0.8
12 (0.47)
100 (3.94)
-0.4
Please contact us at