Sunteți pe pagina 1din 6

ME 354 Tutorial, Week#11

Non-Reacting Mixtures Psychrometrics Applied to a Cooling


Tower
Water exiting the condenser of a power plant at 45C enters a cooling tower with
a mass flow rate of 15000 kg/s. A stream of cooled water is returned to the
condenser from the cooling tower with the same flow rate. Make-up water is
added in a separate stream at 20C. Atmospheric air enters the cooling tower at
30C and a wet bulb temperature of 20C. The volumetric flow rate of air into the
cooling tower is 8000 m3/s. Moist air exits the tower at 40C and 90% relative
humidity. Assume an atmospheric pressure of 101.3 kPa.
Determine:
a) the mass flow rate of dry air,
b) the mass flow rate of make-up water, and
c) the temperature of the cooled liquid water exiting the cooling tower.
Step 1: Draw a diagram to represent the system

Exhaust Air

Warm Condenser
Water

Inlet Air

mw,1=15000 kgw/s
T1 =45 C

Va,3=8000 m /s
Tdb,3=30 C
Twb,3=20 C

Cooled
Condenser Water
mw,2 = mw,1
T2 =? C

Make-up Water

mmw =? kgw/s
T5 =20 C

Step 2: Prepare a property table

H2 0
1 (sat. liq)
2 (sat. liq)
5 (sat. liq)

T (C)
45

m (kg/s)
15000
15000

h (kJ/kg)

20

Air

T db (C)

Twb (C)

Step 3: State your assumptions


Assumptions:
1) The cooling tower operates under steady conditions
2) KE, PE 0
3) Cooling tower is rigid and adiabatic Wcv = 0 & Qcv = 0 .
4) Assume all liquid water is saturated
5) The pressure is constant throughout the cooling tower at 101.3 kPa.
Step 4: Calculations
Part a)
The mass flow rate of dry air can be determined using the volumetric flow rate of
air into the cooling tower (given in the problem as 8000 m 3/s) and the specific
volume of this air as shown in Eq1.

ma ,3

V a ,3

v a ,3

(Eq1)

We can determine the specific volume of the air entering the cooling tower by
determining the state point of location 3 on the psychrometric chart using T db,3 =
30C and Twb,3 = 20C.
From the psychrometric chart,
va,3 = 0.873 m3/kga
Substituting this value and the given volumetric flow rate into Eq1 we can
determine the mass flow rate of dry air.

ma ,3

V a ,3
v a ,3

m 3
8000
s

= 9163.8
m3
0.873

kg a

kga/s

Answer a)

Part b)

To determine the mass flow rate of the make-up water, denoted as m mw , we can
perform a mass balance on the water entering/exiting our cooling tower control
volume. At location 1 we have the stream of water entering the cooling tower

from the condenser, which we will denote as m w,1 . At location 2 we have the
stream of water exiting the cooling tower to be returned to the condenser, which

we will denote as m w, 2 . We are told in the problem statement that m w,1 = m w, 2

= m w . At location 3, we have the moisture entering the cooling tower control

volume carried in by the incoming air. We will denote this as m v , 3 . At location 4,


we have the moisture leaving the cooling tower control volume carried out by the

exiting air. We will denote this as m v , 4 . The mass balance on the water is
performed in Eq2.

m w m w m v ,3 m v , 4 m mw 0 m mw m v , 4 m v ,3

(Eq2)

Note: We could have developed Eq2 immediately by reasoning that the amount
of water that needs to be made-up for will be equal to the amount of moisture
that is picked up in the cooling tower by the air and exhausted.

We can express m v , 3 & m v , 4 in terms of the corresponding mass flow rates of


dry air at location 3 & 4 and their respective humidity ratios w 3 & w4 as shown in
Eq3 and Eq4.

(Eq3)
m v ,3 w3 m a ,3

(Eq4)

m v , 4 w4 m a , 4

Substituting Eq3 and Eq4 into Eq2 we obtain Eq5.

m mw m v , 4 m v ,3 w4 m a , 4 w3 m a , 3

(Eq5)

From our assumption that the cooling tower operates in a steady manner, the

mass flow rate of air will be constant i.e. m a ,3 = m a , 4 = m a . Eq5 can be


rewritten as Eq6.

m mw m a ( w4 w3 )

(Eq6)

Recall that we determined the mass flow rate of dry air in part a). We can
determine the humidity ratio of the air entering the cooling tower by using state
point 3 on the psychrometric chart.
From the psychrometric chart,
w3 = 10.6 gv/kga = 0.0106 kgv/kga

Unfortunately, state point 4 (T db,4 = 40C & =90%) is off the psychrometric chart
so we will have to calculate the value of w 4 using equation 13-11b from Cengel
and Boles as shown below.
From Table A-4 @ T= 40C, Pg = 7.384 kPa.
w4

0.622 4 Pg
P 4 Pg

kg
0.622(0.9)(7.384)
0.0437 v
101.3 0.9(7.384)
kg a

Substituting these values into Eq6, we can determine the mass flow rate of the
make-up water.

kg
kg
m mw m a ( w4 w3 ) 9163.8 a 0.0437 0.0106 v
s
kg a

= 303.3 kgv/s

Answer b)

Part c)
We can determine the temperature of the cooled liquid water exiting the cooling
tower by first determining its enthalpy. Since we are assuming it is a saturated
liquid we can use the enthalpy to interpolate in Table A-4 to determine its
temperature. To find the enthalpy of the water exiting the cooling tower we must
perform an energy balance on the cooling tower control volume. At location 1, the
rate of energy entering the control volume carried in by the stream of water

coming from the condenser is m w hw,1 , where h is used to denote enthalpy. At


location 2 we have the stream of water leaving the cooling tower carrying away

energy at a rate of m w hw, 2 . At location 3, the moist air carries energy at a rate of

m a h3 into the control volume. At location 4, we have moist air leaving the cooling

tower control volume carrying energy out at a rate of m a h4 . The make-up water

carries energy into the control volume at a rate of m mw hmw . Combining all of
these statements into one expression we obtain Eq7. Note: We have made use
of our list of assumptions in developing Eq7.

,1 , 2 3 4 0

(Eq7)

We can isolate the enthalpy of the water at location 2 by rearranging Eq7 as


shown in Eq8.

hw hw

m a h h m mw hmw

(Eq8)

mw

We have previously determined m a and m mw , and we are given m w in the


problem statement.
hw,1
Since we have assumed saturated liquid water at location 1 we can determine
hw,1 from Table A-4 using T1 = 45C.
kJ

kg w

hw,1 188.45

h3
Using state point 3 on the psychrometric chart we can determine h 3.
kJ

kg a

h3 58

h4
As stated previously, state point 4 is off the psychrometric chart so we must
calculate h4. Using equation 13-1a from Cengel and Boles, we can calculate the
enthalpy of DRY AIR alone.

kJ

kJ

( 40 oC ) 40.2
1.005
ha , 4

kg

C
kg a
a

We can calculate the enthalpy of the MOISTURE in the air using Table A-4 for h g
@ T = 40C.
kJ

kg v

hg , 4 2574.3

To combine the dry air and moisture enthalpies at location 4 into one term, h 4, we
need to convert the enthalpy of the moisture to be on a per kg of dry air basis
by multiplying it by the humidity ratio, w4.

kJ
kg v
kJ
kJ

0
.
0437
2574
.
3
h4 ha , 4 w4 hg , 4 40.2

152.7

kg a
kg a
kg v
kg a
hmw
Since we have assumed saturated liquid water at location 5 we can determine
hmw from Table A-4 using T5=20C.

kJ

kg w

hmw 83.96

Substituting these values into Eq8, we can determine the enthalpy of the water at
location 2.

hw , 2

kJ

kg
kg
(303.3) w (83.96) kJ
9163.8 a (58 152.7)

kJ
s

kg a
kg w
188.45

kg
kg w
15000 w
s
kJ
kJ
kJ
56.16
132.3

kg w
kg w
kg w

hw, 2 188.45

As stated previously, since we have assumed saturated liquid water at location 2


we can use hw,2 to find the corresponding temperature in Table A-4. From Table A4 we find that hw,2 lies in between the enthalpies corresponding to temperatures
of 30C and 35C. We can interpolate in between them to find the temperature of
the water exiting the cooling tower.
T2 30oC
132.3 125.79

146.68 125.79 35oC 30oC

T2 = 31.6C

Answer c)

Step 5: Summary
a) the mass flow rate of dry air is 9163.8 kga/s
b) the mass flow rate of make-up water is 303.3 kgw/s, and
c) the temperature of the cooled liquid water exiting the cooling tower is
31.6C.

S-ar putea să vă placă și