LIST OF CONTENTS
SECTION TITLE
1. Introduction
4 Equipment Catalogs
1
OPERATION AND MAINTENANCE MANUAL
CITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266
(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0
IN CASE OF FIRE
a) When the Fire Alarm bell rings, note the zone light “On”.
f) DO NOT switch off panel or reset the alarm bells before investigating the 'Fire' affected zone.
g) When situation is back to normal, refer to instruction manual housed in the cabinet for resetting system.
a) Bila loceng kebakaran berbunyi, lihat lampu daerah mana yang bernyala.
f) JANGAN tutupkan suis panel atau memulihkan system sebelum tamat siasatan.
2
OPERATION AND MAINTENANCE MANUAL
CITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266
(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0
Introduction
1. INTRODUCTION
The City Mall is protected with the following Fire Protection System.
An Automatic Sprinkler installation is a device contrived for the detection and by the application of water,
extinguisher a fore in its initial stages. It is designed to carry out those functions automatically and its operation
simultaneously causes an alarm bell to sound.
The method of its application is by the action of the Sprinkler head inserted into the system of pipework fitted
throughout the building.
At normal temperatures, the sprinkler glass bulb contains the fluid in both liquid and gaseous phase. As heat is
applied, the liquid expands forcing it to push out against the bulb, causing the glass to shatter, opening the water way
and allowing the deflector to distribute the discharging water.
Hose Reel provides one of the most effective non-automatic means of extinguishing a fire in its early stage or
containing a large fire pending the arrival of the the fire brigade. It is able to scope with larger fire than portable
extinguisher, and is simple and convenient to handle. The floor distance coverage using Hose Reel usually ranging
from 100 ft. The water pressure is 30 psi at which pressure of 30 ft. jet is produced. In principle, Hose Reel are
strategically located in a building. They are normally housed in cabinets with a graphic board symbol 'HOSE REEL'
conspicuously displayed.
Portable Fire Extinguishers is useful when initial Fire-Fighting is called. Various type of Fire Extinguishers are
available for different purposes. Among all Dry Powder extinguisher is commonly used as it is effective for class A
(carbonaceous), B (flammable liquid) and C (flammable gas ) fires. CO2 Fire Extinguishers are used to kill fires
involving flammable liquids and gases. It is non-conductive and therefore particularly effective against fires in
electrical plant and equipment.
3
OPERATION AND MAINTENANCE MANUAL
CITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266
(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0
Introduction
This system mainly consists of detectors, control panel battery and charger. Audible and visual alarm and electrical
power supply which will automatically raise an alarm in the event of the fire, and simultaneously transmit an alarm
signal to the fire control station.
Generally the location of the breakglass manual call point together with 6" Alarm Bell are installed at the passage
way leading to lobby and corridor of the building. The Smoke Detectors are located in the lift lobby area, lift motor
room and air handling unit room. Heat Detectors are normally installed in places where Smoke Detectors are
discouraged e.g. Diesel Generator room and workshop.
This system consists of a Master Handset in the main panel control room which is linked to other remote handsets
located at every floor of the building. The purpose of this system is to enable the Fireman to communicate at
different floor level and control station while fighting a fire within the building.
CO2 (carbon dioxide) is an odourless and colourless gas. The particular characteristics of this gas make it the
cleanest fire extinguishing method known to date. Carbon dioxide is electrically non-conductive. It is neither caustic,
corrosive nor contaminating. It evaporates without any chemical influence and leaves no residues. The extinguishing
effect is based on the fact that the oxygen content of the air is reduced, thus, choking the fire. This system is installed
in the substation.
4
OPERATION AND MAINTENANCE MANUAL
CITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266
(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0
Description &Operation
This automatic sprinkler system is designed / installed in accordance with the Rules and Regulations of the Uniform
Building By-Laws 1976, Rules of the loss Prevention Council for Automatic Sprinkler Installation BS 5306 Part 2
1990 and subsequents and Jabatan Perkhidmatan Bomba Malaysia.
5
OPERATION AND MAINTENANCE MANUAL
CITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266
(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0
Description &Operation
2) Pump On 'Manual-AC/Operated
a. Turn pump isolator knob to 'ON' position.
b. Select AUTO/MANUAL switch to "MANUAL" position.
c. Push 'START' button to operate pump.
d. Push 'STOP' button to stop the pump.
6
OPERATION AND MAINTENANCE MANUAL
CITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266
(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0
Description &Operation
This system has been installed, tested and commissioned according to the specification of the Local Fire Authorities.
The Hose Reel system covers the whole building and is installed along the sideway of the building.
1. HOSE REEL
The Hose Reel is of the swing type. Each Reel is complete with 1" x 50 ft. long non-link rubber hose. The
Hose Reel is finished in black colour which can be easily identified.
2. SHUT-OFF NOZZLE
The shut-off nozzle assembly is constructed from a non-corrosive resistant material conforming to BS336.
3. SYSTEM OPERATION
Opening of any of the Hose Reel nozzle results in a pressure drop in the system. This, in turn, starts the
electric duty pumpset. Should the duty pumpset fails to start, a further pressure drop will operate the
standby pumpset.
Care should be taken to ensure that no Hose Reel can be permitted to be operated for any other purposes. Should the
Hose Reel be used freely, the duty electric pumpset will start and stop frequently thereby increasing maintenance
costs, not to mention the frequent false alarms.
7
OPERATION AND MAINTENANCE MANUAL
CITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266
(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0
Description &Operation
Generally, the hose reel serves as an initial general fire fighting aid. In order for the user to operate the system
efficiently, the following instructions should be followed :
GENERAL INFORMATION
The basic function of the Fire Pump Starter Panel for electric motor driven fire pumpsets is to automatically start &
run the motor upon a drop in pressure in the water line.
When water pressure drops below a level which is preset on the internal pressure switch. the pressure switch will
open. The preset pressure switch will trigger the starter panel to start the duty pumpset. Should the duty pumpset
fails to start, a further pressure drop will operate the standby pump. At any time, only one pumpset shall operate. To
stop the pumpset, place the selector switch to 'OFF' position and press the red button 'STOP'. Therefore, the selector
switch must always be restored to 'AUTO' position.
FUNCTION
Note : The standby Hose Reel pump will operate automatically only when the duty pump is 'OFF' or fail to start.
8
OPERATION AND MAINTENANCE MANUAL
CITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266
(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0
Description &Operation
This extinguisher is free flowing powder with a composition based on ammonium phosphate and
ammonium sulphates with special additive to improve fluidity and storage.
When discharge, the heat from the fire is greatly reduced. Firstly, because a cloud of powder provides an
effective heat-shield. Secondly, there is an immediately knockdown of the flames. Hence, the flames are
suffocated and any embers are extinguished by a layer of melted powder.
Carbon Dioxide gas is an efficient Fire Extinguishing agent which offers unique properties to user. The
colourless and odourless gas is heavier than air and works by smothering the flames and reducing the
oxygen content of the air around the fire.
Carbon Dioxide is the ideal agent for use on Class B (flammable liquids) and Class C (flammable gas) fire.
It is non-conductive and therefore particularly effective against fires in electrical plant and equipment.
Carbon Dioxide Extinguisher are used throughout industry as a protection against complex industrial fires
where dangerous chemicals and gases are involved. Carbon Dioxide does not deteriorate with storage or
freeze in the container.
After use carbon dioxide disperses without leaving any contamination or corrosive residue but if used in a
confined area normal ventilation procedure should be followed.
Statistic proves that more and more fire are being detected too late for the fire fighting action to be innate in
time. It is the function of the fire alarm system to detect a fire, if possible in its incipient stage and
automatically alert an emergency service to isolate the source of a fire by means of fire protection and local
extinguishing facility.
Quick and reliable automatic alerting depends on the detection element of the automatic fire detectors. To
ensure the proper functioning of fire detectors, the response criterion must be based on the expected
characteristic of an incipient fire.
9
OPERATION AND MAINTENANCE MANUAL
CITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266
(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0
Description &Operation
Minimum Maintenance required. It is a closed supervisory type of system. Therefore, whenever fault occurred
automatic self detection will sound the buzzer with light indication.
The Genset Room, MSB Room, Transformer Room & Switchgear Room are protected with CO2 Extinguishing
System.
CO2 (carbon dioxide) is an odourless and colourless gas. The particular characteristics of this gas make it the
cleanest fire extinguishing method known to date. Carbon dioxide is electrically non-conductive. It is neither caustic,
corrosive nor contaminating. It evaporates without any chemical influence and leaves no residues. The extinguishing
effect is based on the fact that the oxygen content of the air is reduced, thus choking the fire. The liquified gas is
stored in high pressure gas cylinder. This cylinder is equipped with an electrical Solenoid actuator control from CO2
control panel. This actuator open the cylinder valve and the CO2 is discharge into the common manifold as well as
into the control piping from which the desired number of follow-up cylinders are pneumatically opened. The CO2
nozzles are open at all times.
10
OPERATION AND MAINTENANCE MANUAL
CITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266
(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0
Description &Operation
A. DESIGN SPECIFICATION
1. The installation is designed for extinguishing of fire involving electrical / electronic equipment
hazards and complied to the requirements of Malaysian Fire Protection Association.
2. The quantity of extinguishing agent is carefully predetermined to ensure the fastest possible
extinction of any fire in the protected area.
3. The protected area is provided with normally 50% @ 70 °F concentration of agent in the space of
protected area.
4. Normally a time delay of 25-30 seconds is set for discharge of gas after both two detector zones
receive alarm.
5. The system comprises the following features : -
a) CO2 containers charged with the required quantity of gas.
b) Automatic electric solenoid actuator, manual keyswitch box and manual pull box.
c) Automatic detectors, Alarm bells, Flashing lights & by pass switch.
d) CO2 control panel with 24V Dry Cell batteries and charger.
e) Discharge nozzles, piping and conduit wiring.
f) Discharge warning signboard.
6. The system is installed with 2.27 KG pilot cylinder used to activate all the slave cylinder when the
pilot cylinder is actuated.
B. SYSTEM OPERATION
The installation is operated from automatic mode using smoke/heat detectors under dual mode operation
and manual mode using electric keyswitch. The system is operated by an input voltage of 240V AC 50Hz
supplied to a power charger module within the panel. The AC voltage is transformed and rectified to 24V
DC. A set of Dry Cell batteries is provided as secondary supply in case of AC failure. These batteries will
automatically and instantaneously be switched into use as soon as the mains supply fails. Such a failure is
shown both visually and audibly at the panel. The batteries is trickled charged during normal operating
conditions. The hazard area is protected by two detectors i.e. one smoke and one heat detector. When one of
these detectors receive an alarm condition, a visual and audible warning bell will be given at the control
panel. In order to discharge the extinguishing agent automatically, both detectors must receive alarm
condition. This mode of operation is called 'Double Knock' system with a time delay of 30 seconds preset in
the control panel to discharge the extinguishing agent. This obviates the possibility of false discharge due to
one detector operating.
The facility to discharge the CO2 agent manually is also been provided via manual keyswitch. Also, in the
event of total failure of the control panel, the CO2 agent can still be discharged through mechanical manual
pull station by double action breakglass and follow by pulling the level. The detectors are continuously
supervised by zone supervisory module of the panel for line fault. Any break of wires, the module will both
visually and audibly inform by a fault lamp and buzzer.
11
OPERATION AND MAINTENANCE MANUAL
CITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266
(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0
Description &Operation
C. SYSTEM CONTROL PANEL
The CO2 control panel is located normally beside the hazard area is complete with the following facilities: -
The audible warning and indicators are used to indicate the operations and conditions of the system. The
alarm is provided to give a warning of a discharge or pending to discharge of extinguishing agent where a
hazard to personnel may exist.
The audible buzzer indicating, failure of supervised devices or equipment are provided with prompt and
indication of any failure to warn the personnel that the system is not in proper and require immediate
rectification.
In case of fire alarm, quickly evacuate hazard area and close the doors. The CO2 gas can be released by
smashing the glass of manual keyswitch and to turn it in clockwise position. In case of false alarm or minor
fire hazards, which can be easily extinguished by using portable lire extinguisher, quickly run to CO2
control panel and switch the C02 isolate switch to 'Isolate CO2' so as to prevent the CO2 from discharging,.
1. Ventilate the affected area to disperse all smoke or heat that would reinitiate the fire alarm system.
12
OPERATION AND MAINTENANCE MANUAL
CITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266
(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0
Description &Operation
F. FUNCTION OF CO2 PANEL
MAINS ON When the “MAINS ON” switch is on, the LED indicator will light.
“CHARGER ON” and “DC ON” will also on.
DC ON This indicator is on all the time whenever there is supply (either AC or Battery
Supply).
ALARM The “ALARM RESET” push-button switch is incorporated for
RESET resetting the alarm condition and set the system back to normal.
BATTERY “BATTERY FAIL” indicator will light and the buzzer sounds when
FAIL the battery fuse is removed or in fuse condition.
TEST LED To check that all the LED's are good, switch on the “TEST LED” switch and all
the LED's will light and buzzer sounds restore switch back to normal.
CHARGER “CHARGER FAIL” indicator will light and the buzzer sounds when there is no
FAIL AC supply.
MAINS FAIL “MAINS FAIL” indicator will light and the buzzer sounds when either one of
the following conditions exists :(i) The AC Supply is switched off, (ii) AC Fuse
has been removed or in fused condition.
BUZZER When the Bell switch inside the CO2 panel is switched to “OFF” position, the
SILENCE “BUZZER SILENCE” green indicator will light, indicating that the buzzer has
been cut-off.
BELL When the Bell Silence switch inside the CO2 panel is switched to “OFF”
SILENCE position, the “BELL SILENCE” green indicator will light and the buzzer
sounds. All the bells will not sound. This allow test alarm to carry out without
causing any inconvenience to the public.
BELL LINE When the bell is removed or disconnected, "BELL LINE OPEN" indicator will
OPEN light and the buzzer sound.
VOLTAGE The Voltmeter will indicate the system's voltage, it should be 25V.
CURRENT The Ammeter will indicate the system's current consumption.
13
OPERATION AND MAINTENANCE MANUAL
CITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266
(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0
Description &Operation
ALARM When alarm signal from sensors is received, the two red LED alarm light for
that particular zone will flash. Further alarm signal for the adjacent zone will
cause the adjacent zone indicator to flash again. Since the signal is latched, the
indication will remain until the signal is cleared and the panel “RESET”.
FAULT When the external zone detector wiring is open or the end-of-line resistor is
removed, this yellow indicator will light and buzzer sounds. The “Fault”
indicator will automatically clear when the fault condition is cleared.
ISOLATE This green indicator will light and buzzer sounds when the rotary switch is set to
“ISOLATE” (ISO) position. This will cause the flashing “ALARM” indicator to
become steady and the bells to stop ringing.
T/F (TEST When the rotary switch is set to “FAULT” (T/F) position, it simulated an open
FAULT) circuit on the detected line. The yellow “FAULT” indicator of that particular
zone will light and buzzer sound. The “FAULT” will automatically clear when
the rotary switch is turn to “NORMAL” (NOR) position.
T/A (TEST Alarm condition can be tested from the panel by turning the rotary switch to
ALARM) “ALARM” position. That particular zone's ALARM indicator will flash and it
will remain flashing until the rotary switch turns back to “NORMAL” (NOR)
position and depressing the “MASTER RESET” switch once. Be careful, by
activating two zones simultaneously, will cause the system to activate &
discharge of CO2 agent.
Note:
● Under normal condition, the “Bell Silence” and “Buzzer Silence” switches outside the CO2 panel should
not be “OFF”.
● When doing Test Alarm, always isolate the CO2 Gas or disconnect Electrical Actuator wire at the CO2
panel. This is to avoid accidentally discharging the gas.
14
OPERATION AND MAINTENANCE MANUAL
CITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266
(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0
Description &Operation
SPECIFICATION
15
OPERATION AND MAINTENANCE MANUAL
CITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266
(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0
Testing,Services&Maintenance
This automatic sprinkler system is designed / installed in accordance with the Rules and Regulations of the Uniform
Building By-Laws 1976, Rules of the loss Prevention Council for Automatic Sprinkler Installation BS 5306 Part 2
1990 and subsequents and Jabatan Perkhidmatan Bomba Malaysia.
This automatic sprinkler system is using a deluge system with wet pilot actuation utilizes the deluge valve in
conjunction with open sprinkler nozzles. The system piping contains no water under normal conditions. Water is
held back by the deluge valve. With "wet pilot” actuation, a network of ½” or ¾" piping with closed ½" orifice
sprinklers is spaced throughout the area of coverage. This "pilot" piping is under water pressure and is connected to
the "wet pilot" (basic) trim of the deluge valve. When the "wet pilot” piping is pressurized / filled with water, the
diaphragm chamber of the deluge valve is also pressurized. This pressure in the diaphragm chamber is exerted to a
piston which forces the clapper lever against the clapper, holding it closed. When a fire activates a pilot sprinkler
detector, water pressure is released through the pilot sprinkler faster than it can be restored due to the restricted
orifice located at the inlet of the diaphragm chamber. This drop in pressure in the diaphragm chamber releases the
lever, allowing the valve to trip. Water enters the system piping and discharges from all of the sprinklers.
It is possible to isolate the sprinkler system via the insolation Rate value.
16
OPERATION AND MAINTENANCE MANUAL
CITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266
(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0
Testing,Services&Maintenance
a. Check the sprinkler heads and sprinkler spanner are on hand. Every 6 months
2. Piping
17
OPERATION AND MAINTENANCE MANUAL
CITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266
(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0
Testing,Services&Maintenance
18
OPERATION AND MAINTENANCE MANUAL
CITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266
(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0
Testing,Services&Maintenance
G – detect and remove the Inter-turn short-circuit or the short-circuit to casing (if any).
19
OPERATION AND MAINTENANCE MANUAL
CITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266
(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0
Testing,Services&Maintenance
VISUAL INSPECTION
1. Check all hoses fully charged with water-monthly.
2. Check swivel joint of drum of leakage and ease of movement-monthly
3. Check all stop valves in fully 'open'-weekly.
4. Check for air lock in the system and rectify accordingly.
TESTING PROCEDURES
The Hose Reel system is pressurized by means of pumpsets. Opening of the Hose Reel nozzle result in a
pressure drop in the system. This in turn starts the electric Pumpset.
In order for the user to operate the system efficiently, the following step must be followed:
Each Hose Reel has a minimum flow rate of 6 igpm at 13 psi. Normally 2 sets of Hose Reel are tested at
one time for this specified duty.
A test valve is connected to each of the Hose Reel system in the pump room. Testing of pumpset operation
sequences can be carried out as follow:
1. Operating the test valve slowly and note the system pressure drops.
2. Check the electric Pumpset cut in pressure against the pressure switch setting.
3. Drop the system pressure further until Pumpset cut in.
4. Check the standby Pumpset cut in pressure against the pressure switch setting.
5. Check cut out pressure by closing the test valve while duty or standby pumpset is running.
At any time, only one pumpset shall operate. To stop the pumpset. place the selector switch to "OFF"
position and then press the red button "STOP'. Thereafter the selector switch must always be restored to
'AUTO' position.
20
OPERATION AND MAINTENANCE MANUAL
CITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266
(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0
Testing,Services&Maintenance
C. PORTABLE EXTINGUISHERS
The purpose of well planned and well executed maintenance program is to enable the maximum probability
of an extinguisher.
a)Properly operate between the time intervals established for maintenance examination in the environment
to which it is exposed.
b)Will not constitute a potential hazard to person in its vicinity or to operate or recharge extinguisher.
Frequency of extinguisher inspection should be on the need of the area in which extinguishers are located.
The monthly inspection should be more frequent if any of the following exists:-
INSPECTION PROCEDURE
Extinguisher that is out of service should be replaced by spare extinguisher having the same classification
and capacity.
21
OPERATION AND MAINTENANCE MANUAL
CITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266
(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0
Testing,Services&Maintenance
1. When there is alarm, rush to the main panel and see which indicator is on.
2. Rush to that particular area to check which alarm comes from and check that area to see if there is fire or
false alarm.
3. If there is a fire, please leave the alarm on till the Fire Brigade arrives, meanwhile you can call for help and
fight for fire by using the system installed.
4. If this is a false alarm, isolate the corresponding isolating switch and then reset to silence the alarm.
5. Main panel should also be reset.
6. When the alarm is off, ring Fire Brigade about the false alarm.
7. Investigate the cause of false alarm.
8. When you are sure all the breakglass & detectors are in their original position, put the isolator back to its
original position.
Testing
Procedure
22
OPERATION AND MAINTENANCE MANUAL
CITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266
(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0
Testing,Services&Maintenance
Maintenance
General Introduction
The indicating panel is available for use in open or closed circuit system, and in either case continually
supervise external wiring to associate alarm initiating devices and alarm sounders.
Control and indicating panel allows the system to be tailored to meet particular requirements by the
addition of standard modules.
Panel interconnection diagram is supplied with each panel and shows panel interconnections and also
typical external wiring to bells, detectors, remote indicators, etc.
NOTE
When installation is completed, the system must be checked by qualified personnel before power is
supplied.
The following text and illustrations explain the operation of a representative control. Though individual
system may differ, all standard features are describe in this publication.
Normal Condition
"Power On" LED illuminated. Should the "Power On" becomes extinguished at any time, this will indicate
a failure of the power supply to the panel or a failure of the LED itself.
Alarm Condition
When an alarm initiating device is operated, the following signal will be given by the control panel.
1. The external alarm sounders will operate.
2. The built in supervisory buzzer will operate.
3. The red LED associated with the zone in which the alarm originated will light.
4. Any ancillary equipment required to be operated for an alarm in that zone will operate e.g. fire
station link. Fan shutdown staircase pressurization, door closed, etc.
23
OPERATION AND MAINTENANCE MANUAL
CITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266
(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0
Testing,Services&Maintenance
Alarm Control
c) Reset Switch
Operation of this switch resets the control panel after an alarm providing that the alarm initiating
device has been restored to normal.
NOTE
In case of smoke detectors or ionisation type detectors it is important to ensure that all smoke or
product of combustion are purged from the detector before the "Reset Alarm" switch is operated.
d) Trouble Condition
When any one of variety of faults occurs, signals given by the control panel, either singly or
combination, assist in tracing the nature of the fault. These indications are as follow:-
Battery Test
To assist anticipation possible battery deterioration, a battery test facility is provided. If operation
of the "Test Battery" voltage switch produces a battery trouble indication, an inspection of the
battery should be carried out.
e) Possible Causes
1. Open or short circuit on warning to alarm sounders.
2. Low insulations resistance between system wiring and earth.
3. Main supply to charger disconnected or charger faulty.
4. Condition of battery requires investigating.
NOTE
All above visual warning indications are accompanied by an audible warning from the built-in supervisory buzzer.
24
OPERATION AND MAINTENANCE MANUAL
CITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266
(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0
Testing,Services&Maintenance
Inform the fire Brigade Station Authority and the Building Personnel in-Charge that the system is back to normal
operation. Record all your testing in 'Record Book'.
25
OPERATION AND MAINTENANCE MANUAL
CITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266
(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0
Testing,Services&Maintenance
Testing,Services&Maintenance
MODES OF OPERATION
The fireman intercom system installed supports several modes of operation. They are as follow:-
Any remote handset is addressed by the operator at Master control Panel via selector switches. A call to any
remote handset can be made simply by the following procedure.
1. Lift up the master handset.
2. Press the selector switch that correspond to the remote handset to be called.
3. The respective 'call' LED will then be flashing.
4. The buzzer at the remote handset will sound continuously and the LED at the remote.
5. When the remote handset is lifted, the CALL LED lights steadily and the buzzer stops sounding.
6. Communication between master and slave handset is then established.
7. Once conversation ends and the handset is put back in position the processor will cut off the line
automatically.
Any communication between two slaves handsets must be patched by the master handset. Just perform
operation B and request the operator to perform GROUPCALL on the other Slave handset.
To GROUPCALL:
1. Press the GROUPCALL selector switch followed by the selector switch that corresponds to the
slave handsets.
2. The LED will be flashing and remote handset buzzer sounds.
3. Once the remote handset is lifted, the communication is established.
D. CONFERENCE LINE
By similar operation as in C, a conference line of not more than 5 handset can be achieved. After
GROUPCALL has been used, it must be cancelled by CANCEL command. TO CANCEL:Press the
CANCEL selector switch.
26
OPERATION AND MAINTENANCE MANUAL
CITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266
(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0
Testing,Services&Maintenance
The C02 cylinder to be installed is calculated to cover the volume of the protected space. The room is under
surveillance of the Heat/Smoke Detection devices which work on a double knob basic.
Only with the activation of the two zones, would the CO2 gas be discharged.
If only zone one activates, 'ALARM' would be indicated and the bell will ring. When zone two activates the
CO2 agent will be discharged after 25-30 seconds (preset timing) through the balanced distribution piping
and nozzles.
In the case when the Heat/Smoke detectors is not functioning, use the manual electric keyswitch which is
enclosed in the metal box installed below the CO2 panel to actuate the CO2 gas or through mechanical
manual pull station by double action breakglass and followed by pulling the level to discharge CO2 agent.
DAILY MAINTENANCE
WARNING:Precise execution of each step is necessary to avoid discharge of the gas and to prevent danger to
personnel.
A-1 Safety requirement : Arrangements must be made to ensure rapid and safe evacuation of any area into
which CO2 agent may be discharge accidentally.
A-2 Before carrying out any test, check the system supervising lamps : A.C on indicator, D.C on indicator,
and charger on indicator. Other indicators are off.
A-3 Lamp test; to check that bulbs are healthy for servicing, depress the lamp Test Switch (Non-locking
type), this will light up all the bulbs of the indicators, simultaneously bring in the fault warning device
for sound check.
A-4 Visually check the flashing light, the 'GREEN' light must be on.
A-5 Visually check the manual release mechanical device and electrical actuator.
A-6 Nozzle of proper type in place and properly arm.
MONTHLY MAINTENANCE
B-1 Repeat daily check.
B-2 Check all the wires are in place and intact.
B-3 Check for mechanical damage or tampering.
B-4 Check that nozzle blow-off cap if required are in place.
B-5 Piping securely bracketed or hung.
B-6 All pipes and tubing connecting are tight.
B-7 Check all components supporting hardware and tighten or repair as required.
B-8 Visually check all components for evidence of physical abuse and take whatever action that is
indicated. Replace the components if in doubt of its ability to perform properly.
27
OPERATION AND MAINTENANCE MANUAL
CITY MALL COMMERCIAL DEVELOPMENT ON CL.015011266
(NEW DRAFT TITLE CL.015580355) AT JALAN LINTAS, KOTA KINABALU FPS O&M CITY MALL version 1.0
1. Check the system with DAILY MAINTENANCE. If the system checked normal, then proceed with the
following test procedure.
2. Disconnect the electrical actuator wire at the CO2 panel.
3. Automatic detector gas release : Activate a detector in accordance with procedures recommended. This will
bring in an alert alarm bell sounding (one second on : one second off), and zone alarm indicator lit up
flashing.
4. Activate another detector in the next zone, this will operate the alarm lamp to pulsate and the' Fire
confirmation' circuit and discharge time start to operate and fire extinguishing gas is discharged after the
preset time and an evacuate alarm is given in the area.
5. Check the gas discharge LED Bulb is lit up and the gas discharge flashing warning lamp (RED COLOUR)
is ON and the blanket tripped.
6. Return detector / alarm control system to normal supervisory operation.
7. Remote manual key operated gas release : Open the remote key switch box cover.
8. Discharge flashing lamp (RED COLOUR) will light and warning signaling device will operate, also
actuating end terminals to enclose the protected area (Blanked etc.) and fire extinguishing gas will be
discharged immediately. Check the gas discharge LED Bulb operated.
28