Chapter SM 7: Evaporators and Condensers

SM 7.1 Introduction
Evaporators and condensers are sensible heat exchangers in which one of the fluids, the
refrigerant, changes phase. They are constructed similar to the sensible heat exchangers described
in Chapter 13. An evaporator in a chilled water system would typically be a shell and tube
exchanger with refrigerant contained in the shell and outside the tubes. Water would flow through
the tubes and be cooled by the evaporation of the refrigerant. The liquid refrigerant from the
condenser passes through the expansion valve and then enters the evaporator as a low temperature
mixture of vapor and liquid. The vapor is usually slightly superheated before it leaves the
evaporator and enters the compressor. Most of the heat transfer occurs during the change of phase.
Direct expansion coils (DX) are used in systems in which air is cooled and dehumidified. The
refrigerant flows inside the tubes of the coil and evaporates while air flows over the surfaces. As
this refrigerant stream passes through the coil, the liquid portion evaporates and the vapor fraction
progressively increases so that the leaving stream is entirely vapor. In most DX coil applications
the air is dehumidified. Direct expansion coils are common in appliances such as refrigerators, airconditioners, and the air handlers found in typical HVAC distribution systems.
As with evaporators, there are two basic types of condensers. In water-cooled condensers,
constructed as shell and tube exchangers, relatively cool water flows through the tubes. Refrigerant
condenses on the outside of the tubes and then drains from the bottom of the exchanger. Air-cooled
condensers are similar to cooling coils, with the refrigerant condensing inside tubes and transferring
heat to the relatively cool air stream flowing over the outside of the tubes. In evaporative
condensers liquid water is sprayed over the outside of the tubes and then evaporates into the air
stream flowing over the tubes. The performance of these heat and mass exchangers is covered in
Chapter SM 4.
The refrigerant typically enters a condenser from the compressor as superheated vapor. The
vapor is cooled to saturation, condensed and then subcooled slightly. In the desuperheating section
both the refrigerant and cooling fluid change in temperature, while during the phase change the
temperature of the refrigerant is constant as it condenses. Although the majority of the heat transfer
is from the refrigerant during the phase section, a significant portion does occur during desuperheating.

SM 7.2 Thermal Performance of Shell-and-Tube Evaporators


Flooded evaporators are common in chilled water circuits where heat is transferred from water
flowing through tubes to a refrigerant evaporating on the outside of the tubes. A flooded shell and
tube evaporator is shown in Figure 7.1. The tubes are relatively small diameter (1 inch or 2 cm)
and closely spaced, and only a few tubes are shown in Figure 7.1.

7.1

Figure 7.1 Shell and tube flooded evaporator


The tubes are submerged in a pool of liquid refrigerant with a pump used to circulate the liquid
refrigerant so that it continually flows over the heat transfer surfaces. In some applications the twophase mixture leaving the expansion valve is separated into liquid and vapor components with only
the liquid is sent to the evaporator. This reduces the flow through the evaporator. As the liquid
evaporates the vapor leaves, usually with a small amount of superheat, and is sent to the
compressor. The chilled water is then circulated to coils where it cools and dehumidifies and air
stream.
Direct expansion evaporators are also used to cool liquids. The exchanger is a shell and tube
type similar to that shown in Figure 7.1. However, in a direct expansion liquid evaporator the
refrigerantisinsidethetubesandevaporatesasitflows.
Although the detailed fluid flow and heat transfer characteristics of these two types of
evaporators are different, the same basic ideas apply. In the section where the refrigerant
evaporates the refrigerant temperature is constant and the capacity rate ratio is zero. In the
superheating section the refrigerant temperature changes and the capacitance rate ratio is finite.
Different effectiveness relations would apply to these two sections. However, since most of the
heat is transferred during the evaporation process, the approximation that C* is zero for the entire
evaporator is usually sufficiently for the design or evaluation of an evaporator.
Example 7.1 illustrates the calculation of the performance of an evaporator and shows the
degree of error in assuming that the capacitance rate ratio is zero throughout. Although this
example is for a cooling a liquid the same ideas would apply for sensible cooling of an air or
another gas stream.
"Example 7.1 An evaporator is used to chill a liquid water flow rate of 150 gpm that
enters at 45 F. The refrigerant is a flow of 7550 lbm/hr of R-22 that enters at a quality
of 0.1 and a temperature of 30 F. The evaporator has an overall heat transfer
conductance of 60,000 Btu/hr-F. Determine heat transfer rate, the refrigerant outlet
state, and the water outlet temperature."
"The performance will first be calculated assuming that the evaporator is a single
heat exchanger with a capacitance rate ratio of zero. Then, the evaporator will be

7.2

evaluated as two exchangers: an exchanger in which the refrigerant evaporates and


one in which the refrigerant vapor is superheated. The relations in Section 7.3 will be
used to find the thermal performance."
"Problem specifications"
T_w_i = 45 "F"
V_dot_w = 150 "gpm"
T_r = 30 "F"
x_i = 0.1
m_dot_r = 7750 "lbm/hr"
UA = 60000 "Btu/hr-F"

"Temperature"
"Volume flow rate"
"Temperature"
"Quality"
"Mass flow rate"
"Overall UA"

"Refrigerant properties"
h_r_i = enthalpy(R22,T=T_r,x=x_i) "Btu/lbm"
p_r = pressure(R22,T=T_r,x=1) "psia"

"Enthalpy"
"Pressure"

"Water properties"
rho_f = density(water,T=T_w_i, x = 0) "lbm/ft3" "Density"
cp_f = specheat(water, T =T_w_i, x = 0) "Btu/lbm-F"
"Specific heat"
m_dot_w = rho_f*V_dot_w*convert(gpm,ft^3/hr) "lbm/hr"
"Mass flow rate"
C_w = m_dot_w*cp_f "Btu/hr-F"
"Capacitance rate"
"The evaporator is analyzed as a single exchanger with C_star = 0 for entire
exchanger. The effectiveness is taken from Table 13.1."
Ntu_0 =UA/C_w
"Ntu"
epsilon_0 = 1-exp(-Ntu_0)
"Effectiveness"
epsilon_0 = Q_0/Q_max_0
"Effectiveness"
Q_max_0 = C_w*(T_w_i - T_r) "Btu/hr"
"Maximum heat flow"
"Energy balances are used to determine the outlet state of the water T_w_0_o and
refrigerant h_r_0_o "
Q_0= C_w*(T_w_i - T_w_0_o) "Btu/hr"
"Heat flow"
Q_0 = m_dot_r*(h_r_0_o - h_r_i) "Btu/hr"
"Heat flow"
h_r_0_o = enthalpy(R22,T=T_r_0_o,p=p_r) "Btu/lbm"
"Enthalpy"

Results
Treating the evaporator as a single heat exchanger results in a heat transfer rate of 620,100
Btu/hr. The refrigerant outlet temperature is 35.1 F, corresponding to 5.1F of superheat. The
outlet water temperature is 36.8 F. These results will serve as a reference for the performance
calculated assuming that the evaporator has two sections.
"The second performance calculations will treat the exchanger as two evaporators.
The first section will be where the refrigerant evaporates and the second section will
be where it is superheated."
"For the evaporating section the value of C_star is zero and the effectiveness is from
Table 13.1. The overall conductance for this section will be expressed as UA_e =
F*UA where F is the fraction of the UA in the evaporation section. At the end of this
section the refrigerant is saturated vapor at 30 F and the enthalpy h_r_x at the end of
this section is known (174.0 Btu/lbm).

7.3

The temperature of the water at the end of the evaporation section, T_w_x, is not
known because the water has been cooled in the superheating section. As a result
the performance of this section cannot be obtained directly. The solution for this
section is coupled to that for the superheating section and obtained through iteration.
For the evaporation section:"
h_r_x = enthalpy(R22,T=T_r,x=1) "Btu/lbm"
Ntu_e = F*UA/C_w
epsilon_e = 1-exp(-Ntu_e)
epsilon_e = Q_e/Q_max_e
Q_max_e = C_w*(T_w_x - T_r) "Btu/hr"
Q_e = m_dot_r*(h_r_x - h_r_i) "Btu/hr"
Q_e = C_w*(T_w_x - T_w_o) "Btu/hr"

"Enthalpy"
"Ntu"
"Effectiveness"
"Effectiveness"
"Maximum heat flow"
"Heat flow"
"Heat flow"

"For the superheating section the value of C_star is finite. The geometry is assumed
to be counterflow and the effectiveness is from Table 13.1. The overall conductance
of this exchanger is the remaining fraction of the entire exchanger, or UA_s = (1F)*UA.
The unknown water temperature T_w_x couples the solution for the superheater to
that for the evaporation section.
The capacitance rate of the refrigerant vapor is determined using the specific heat
of the vapor and the mass flow rate, and the minimum capacitance is smaller of the
water and refrigerant capacitance rates.
For the superheating section
C_r_s = m_dot_r*cp_r "Btu/hr-F"
"Capacitance rate"
cp_r = specheat(R22,T=T_r,x=1) "Btu/lbm-F"
"Specific heat"
C_min_s = min(C_w,C_r_s) "Btu/hr-F"
"Capacitance rate"
C_max_s = max(C_w,C_r_s) "Btu/hr-F"
"Capacitance rate"
C_star_s =C_min_s/C_max_s
"Capacitance rate ratio"
Ntu_s = (1-F)*UA/C_min_s
"Ntu"
epsilon_s= (1-exp(-Ntu_s*(1-C_star_s)))/(1-C_star_s*exp(-Ntu_s*(1-C_star_s)))
"Effectiveness"
epsilon_s = Q_s/Q_max_s
"Effectiveness"
Q_max_s = C_min_s*(T_w_i - T_r) "Btu/hr"
"Maximum heat flow"
Q_s = m_dot_r*(h_r_o_s - h_r_x) "Btu/hr"
"Heat flow"
h_r_o_s = enthalpy(R22,T=T_r_o_s,p=p_r) "Btu/lbm"
"Enthalpy"
Q_s = C_w*(T_w_i - T_w_x) "Btu/hr"
"Heat flow"
"The total heat transfer equals the sum of the evaporation and superheat sections."
Q_ss = Q_e + Q_s "Btu/hr"
"Heat flow"

Results and Discussion


For the superheating section the refrigerant has a capacitance rate of 1370 Btu/hr-F and it is
the minimum capacitance rate. The capacitance rate ratio is 0.0182. Solving the set of equations
simultaneously yields a fraction of the evaporating section of 0.9925. This shows that
superheater section comprises only 0.75 percent of the surface area. The refrigerant and water
outlet temperatures are 34.7 F and 36.8 F respectively. The refrigerant is superheated 4.7 F,
which is only slightly less than the 5.1 F computed using the capacitance rate ratio of zero
throughout.

7.4

Treating the evaporator as having the two sections yields a heat transfer rate of 619,700
Btu/hr, which is 0.4 % lower than that obtained by treating the evaporator as a single exchanger.
For situations in which the amount of superheat is low (less than about 20 F or 10 C), the
treatment of an evaporator as an exchanger in which one side has a phase change only is valid.

SM 7.3 Thermal Performance of Direct Expansion Cooling Coils


In a direct expansion cooling coil, the refrigerant enters from the expansion valve as a low
quality mixture of vapor and liquid. The liquid fraction evaporates during its passage through the
coil and leaves at a slightly superheated condition. The temperature of the refrigerant is constant
during the phase change process and, as discussed in Section 13.2, the capacitance of the
refrigerant is infinite. Because the amount of superheat is small (5 10 F or 2- 5 C), a DX coil
can be analyzed as an exchanger with a capacity rate ratio of zero.
On the air side of a DX coil there is usually both cooling and dehumidification. The design
or analysis of a DX coil then brings in performance relations both for sensible heat exchanger and
for heat and mass transfer. As discussed in Section 15.3, the performance of a cooling coil can be
determined assuming two different conditions. The first is that the coil is completely wet and the
second is that the coil is completely dry. The maximum of the heat transfer rates from these to
determinations is quite close to the actual heat transfer rate for a coil that is partially wet. The
analysis for the heat transfer only section can be treated using the sensible heat exchanger
relations of Section 13.3 and illustrated for a shell and tube evaporator in Section 13.2. The
analogy method for a chilled water coil was discussed in Section 15.4 and can be extended to a
DX coil.
In a DX coil the refrigerant has an infinite sensible capacity rate, and by extension an infinite
mass capacity rate. The parameter m* corresponds to the sensible capacity rate ratio C*, and is
then zero for a DX coil. The Number of Transfer Units for mass transfer, Ntu*, is determined as
presented in Section 13.6:
(7.1)
where U* is the overall mass transfer conductance based on the air-side area, A a is the area on the
&a istheairmassflowrate.The overall mass transfer conductance is given as
air side, and m
where cp is the specific heat of air,

*o

(7.2)
is the overall air-side surface efficiency for mass transfer,

hc is the air-side convection coefficient, cs is the effective specific heat, Ur is the conductance on
the refrigerant side, and Ar is the refrigerant-side area. The resistance of the surface separating
the air and refrigerant is assumed negligible. The effective specific heat is estimated using a
finite difference approximation around the temperature of refrigerant:
h a,sat h a,sat Tr T / 2 h a,sat Tr T / 2
cs

(7.3)
T
T
The effectiveness for the DX coil is then computed using the analogous relation for a sensible
heat exchanger with a capacity rate ratio of zero

7.5


With the effectiveness, the heat transfer can be determined using the relation

(7.4)

(7.5)
where ha,in is the enthalpy of saturated air at the inlet conditions and h r, sat is the enthalpy of
saturated air at the refrigerant temperature. The air outlet humidity ratio is then determined from
an energy balance on the air flow
(7.6)
As with the chilled water coil, the analogy method yields only the outlet air enthalpy. The outlet
temperature and humidity are determined using the relations presented in Section SM 2.2.
Example 7.2 shows the determination of performance for DX coil.
"Example 7.2 Determine the performance of a DX coil. The air enters the coil at a dry
bulb temperature of 75 F and a wet bulb temperature of 60 F with a volume flow rate
of 5000 cfm. The refrigerant is R-22 at a temperature of 40 F that enters with a
quality of 0.1 and leaves with 5 F superheat. On the airside the heat transfer
conductance Ua is 50 Btu/hr-ft2 and the surface area is 360 ft2. On the waterside the
heat transfer conductance Uw is 1000 Btu/hr-ft2 and the area is 18 ft2"
"Problem specifications
Air side
p_atm = 14.7 "psia"
T_a_i = 75 "F"
Twb_a_i = 60 "F"
V_dot_a = 5000 "cfm"
Refrigerant side
T_r = 40 "F"
DT_sh = 5 "F"

"Atmospheric pressure"
"Dry-bulb temperature"
"Wet-bulb temperature"
"Volume flow rate"
"Refrigerant temperature"
"Temp. difference"

"Heat Exchanger Parameters"


U_a = 50 "Btu/hr-ft2-F"
A_a = 360 "ft2"
U_r = 1000"Btu/hr-ft2-F"
A_r = 18 "ft2"

"Conductance"
"Area"
"Conductance"
"Area"

"Air properties
Determine the properties of air, the mass flow rate, and the sensible capacitance rate
for the air flow through the coil."
w_a_i = HumRat(AirH2O,T=T_a_i, p=p_atm,B=Twb_a_i ) "lbmw/lbma"
"Humidity ratio"
h_a_i= Enthalpy(AirH2O,T=T_a_i,p=p_atm,B=Twb_a_i ) "Btu/lbm"
"Enthalpy"
rho_a_i= density(AirH2O,T=T_a_i,p=p_atm,B=Twb_a_i ) "lbm/ft3"
"Density"
m_dot_a = rho_a_i*V_dot_a*convert(1/min,1/hr) "lbm/hr"
"Mass flow rate"
cp_a = SpecHeat(AirH2O,T=T_a_i,p=p_atm,B=Twb_a_i ) "Btu/lbm-F"
"Specific heat"
C_a = m_dot_a*cp_a "Btu/hr-F"
"Capacitance rate"
"The performance of the DX coil will be determined following the analogy approach of
Section 13.6. It will be assumed first that the coil is completely wet and second that
the coil is completely dry. The maximum of the two heat transfer rates approximates

7.6

actual heat transfer rate for a coil that is partially wet. It will also be assumed that
DX coil can be treated as a single exchanger with the capacitance rate of the
refrigerant infinite. As shown in Example 7.1, because the amount of superheat is
small this is a good assumption"
"In the analogy method the refrigerant is treated as an equivalent saturated air
stream with an effective specific heat c_s. The enthalpy of saturated air at the
refrigerant temperature is"
h_r_sat= Enthalpy(AirH2O,T=T_r,p=p_atm,R=1) "Btu/lbm"
"Enthalpy"
"The effective specific heat c_s is aproximated using finite differences around the
refrigerant temperature and a temperature increment of 2 F"
c_s = Dh_r/DT_r "Btu/lbm-F"
"Specific heat"
Dh_r = Enthalpy(AirH2O,T=T_r+DT_r/2,p=p_atm,R=1)-Enthalpy(AirH2O,T=T_rDT_r/2,p=p_atm,R=1) "Btu/lbm"
"Enthalpy"
DT_r = 2 "F"
"Temperature"
"Totally Wet Coil
The mass transfer resistances and the mass transfer Ntu_star are determined using
the relations in Section 13.6 The overall surface efficiency is included the heat
transfer conductance on the air side U_a "
U_star*A_a = 1/R_wet "lbm/hr"
"Mass transfer cond."
R_wet = cp_a/(U_a*A_a) + c_s/(U_r*A_r) "hr/lbm" "Mass transfer resist."
Ntu_Star = U_star*A_a/m_dot_a
"Mass transfer Ntu"
"The value of m* is zero and therefore the energy effectiveness for the totally wet coil
is given by the expression for a sensible heat exchanger with C*=0 (Table 13.1)."
eff_wet = (1 - exp(-Ntu_Star))
"Wet coil effectiveness"
"The heat transfer and the air outlet enthalpy for the totally wet coil are determined
using the expression for heat transfer in terms of effectiveness and an energy
balance on the air side."
Q_dot_wet = eff_wet*m_dot_a*(h_a_i - h_r_sat) "Btu/hr"
"Heat transfer rate"
Q_dot_wet =m_dot_a*(h_a_i- h_a_o) "Btu/hr"
"Heat transfer rate"
"The analogy method directly determines the outlet air enthalpy. The air outlet
temperature is determined using the approximation that the heat transfer is to a
uniform temperature surface and the energy transfer is to a surface with a uniform
enthalpy of saturated air that gives the actual heat transfer. The outlet temperature
and enthalpy are used to determine the humidity ratio (Section SM 2.2)"
Ntu_a = U_a*A_a/(C_a)
h_s_eff = h_a_i +(h_a_o - h_a_i )/(1 - exp(-Ntu_a)) "Btu/lbm"
"Enthalpy"
T_s_eff = Temperature(AirH2O,h=h_s_eff,p=p_atm,R=1) "F"
"Temperature"
T_a_o = T_s_eff +(T_a_i - T_s_eff)*exp(-Ntu_a) "F" "Temperature"
w_a_o = Humrat(AirH2O,T=T_a_o,p=p_atm,h=h_a_o) "lbmw/lbma"
"Humidity ratio"
"The rate of condensation is determined from a mass balance on the air stream"
m_dot_cond = m_dot_a*(w_a_i - w_a_o) "lbm/hr" "Condensate flow rate"

Results
For the totally wet coil assumption, the Ntu is 1.158, the effectiveness is 0.686, and the heat
transfer rate is 167,719 Btu/hr. The condensation rate is 19.0 lbm/hr.

7.7

"The heat transfer for a totally dry coil is determined using the relations for a sensible
heat exchanger with a capacitance rate ratio of zero. The heat transfer resistances
and the Ntu_dry are determined."
U_a_dry*A_a = 1/R_dry "Btu/hr-F"
"Heat transfer cond."
R_dry = 1/(U_a*A_a)+1/(U_r*A_r) "hr-F/Btu"
"Heat transfer resist."
Ntu_dry = U_a_dry*A_a/C_a
"Heat transfer Ntu"
"The effectiveness for C* = 0 is (Table 13.1)"
eff_dry = (1 - exp(-Ntu_dry))

"Dry coil effectiveness."

"The heat transfer and the air outlet temperature for the totally dry coil are
determined from the expression for effectiveness and an energy balance on the air
stream."
Q_dot_dry = eff_dry*C_a*(T_a_i - T_r) "Btu/hr"
"Heat transfer rate"
Q_dot_dry =C_a*(T_a_i- T_a_o_dry) "Btu/hr"
"Heat transfer rate"
"The higher of the totally wet or totally dry calculation is determined and used to
approximate the actual heat transfer."
Q_dot_coil = max(Q_dot_wet, Q_dot_dry) "Btu/hr" "Heat transfer rate"
Results

For the totally dry coil assumption, the Ntu is 1.678, the effectiveness is 0.813, and the heat
transfer rate is 152,654 Btu/hr. The heat transfer for the totally dry assumption is lower than that
for the totally wet assumption and the totally wet calculation is closer to the actual heat transfer.
"The refrigerant entering and exiting enthalpies are determined from the entering
condition of a quality of 0.1 and an outlet condition of 5 F superheat. The refrigerant
mass flow rate is determined from an energy balance on the refrigerant.
h_r_i = enthalpy(R22,T = T_r, x = 0.1) "Btu/lbm" "Enthalpy"
p_r = pressure(R22,T = T_r, x = 0.1) "psia"
"Pressure"
h_r_o= enthalpy(R22,T = T_r+DT_sh,p=p_r) "Btu/lbm"
"Enthalpy"
Q_dot_coil = m_dot_r*(h_r_o - h_r_i) "Btu/hr"
"Heat transfer rate"

Results and Discussion


Even though the Ntu and effectiveness are larger for the totally dry assumption than for the totally
wet coil assumption, the heat transfer rate is less. The maximum sensible heat transfer
&a h a,i h r,sat . Because the wet
Ca Ta,i Tr is less than the maximum latent transfer rate m
coil assumption yields the higher heat transfer rate it is closer to the partially wet coil case, and is
taken as the coil heat transfer (Section SM 2.2)
The air outlet state is a dry-bulb temperature of 47.6 F, a humidity ratio of 0.006726
lbmw/lbma, and an enthalpy of 18.7 Btu/lbm. The refrigerant mass flow rate is to be 2142
lbm/hr.

SM 7.4 Heat Transfer Coefficients for Evaporators


The heat transfer coefficients for evaporation are different than the conventional convection
relations described in Chapter 4. The process by which the refrigerant changes from liquid to
vapor is a combination of boiling and evaporation, although a clear distinction between the two is
usually not made. For both mechanisms, the surface temperature is higher than the saturation
7.8

temperature. In boiling, vapor is produced at the solid surface and bubbles up through the liquid
to the surrounding vapor, while in evaporation the liquid changes phase at the interface between
the liquid and the vapor.
There are different types of evaporators with different geometries for the heat transfer
process. In flooded evaporators, which are common in chilled water systems, refrigerant
evaporates from the outside of tubes that are submerged in a pool of refrigerant and is collected at
the top of the evaporator. Water or another heat transfer fluid flows on the inside of the tubes. In
the direct expansion (DX) coils common in air systems, warm air flows over the outside of the
tubes and evaporation of the refrigerant takes place inside the tubes.
The process of evaporation on the outside of tubes is often described as nucleate pool boiling.
The term pool boiling refers to boiling from the hot tubes submerged in a pool of liquid, and
nucleate refers to the boiling regime in which steady streams of small vapor bubbles are produced
along the tubes. The bubbles rise to the surface of the refrigerant agitating the fluid and allowing
cold liquid to flow to the tube surface and evaporate. The phase change occurs where the liquid
is in contact with the surface, yielding high transfer rates.
Film boiling occurs when the tubes are so hot that all of the liquid at the surface boils and a
layer of vapor forms around the tubes. The phase change occurs at the interface between vapor
and liquid away from the tube surface. Heat is transferred from the tube surface by radiation and
conduction through the vapor layer to the interface. The thermal resistance of the vapor layer is
high and the heat transfer coefficients for film boiling are much lower than for nucleate boiling.
In film boiling, the temperature differences between the fluid and surface are several of orders of
magnitude higher than for nucleate boiling, which would be detrimental to the performance of a
refrigeration system. Evaporators are therefore designed so that nucleate boiling occurs.
No really universal method is available to correlate and predict boiling heat transfer
coefficients. The actual fluid temperature has little effect on the heat transfer, and the proposed
equations can all be put in a form that relates the heat transfer coefficient to the difference
between the surface temperature and saturation temperature of the fluid at that pressure. The
correlations reduce to the basic form:
n
(7.7)
h c C Ts Tsat
where Ts is the surface temperature and Tsat is the saturation temperature of the refrigerant. The
proportionality constant C is a function of fluid thermodynamic and transport properties,
including surface tension, and the characteristics of the surface, such as the roughness. The
exponent n is about 3, but also depends on the fluid properties and surface characteristics. One of
the earliest correlations that contains the relevant fluid properties is (Handbook of Phase Change:
Boiling and Condensation, 1999):
(7.8)
"
&
where Q is the average heat flux, f is the liquid viscosity, hfg is the latent heat of vaporization,
Cs is an empirically determined coefficient, g is the acceleration due to gravity, is the surface
tension for the fluid, f and g are the densities of the liquid and vapor phases, T s is the surface
temperature and Tsat is the saturation temperature at the fluid pressure, c p,f is the specific heat of
7.9

the liquid, kf is the thermal conductivity of the liquid. The correlation is in terms of the heat flux
rather than a heat transfer coefficient since the flux is not linearly proportional to a temperature
difference.
On the right-hand side are a number of non-dimensional groups of properties. In the first
term in brackets, the difference in density between liquid and vapor multiplied by gravity reflects
the buoyancy force that allows the bubbles to rise, and indicates that evaporation is a natural
convection phenomenon. The liquid surface tension () relates to the force that is necessary for
vapor bubbles to form in the liquid phase.
The relevant temperature difference is contained in the second term in brackets. Fluid and
surface temperatures are equal at a surface. If the surface temperature is higher than the
saturation temperature, boiling will occur at the surface independent of the bulk fluid
temperature. The relevant driving force is then the difference between the surface and saturation
temperatures. The specific heat times the temperature difference represents the energy required to
heat the liquid and the latent heat of vaporization reflects the energy required to change phase.
The last term in brackets is the liquid Prandtl number, which is an important fluid properties
group.
The constant Cs is empirically determined. It is a strong function of surface conditions such
as roughness, the surface composition such the type of metal, and the refrigerant. Equation 7.2 is
useful for estimating the heat transfer when the constant C s has been established. The original
correlation was developed for non-refrigerants.
A more recent correlation was developed by Gorenflo (1993) (ASHRAE Handbook of
Fundamentals, Chapter 4, 2005). The correlation was developed for a reduced pressure (the ratio
of the pressure to the critical pressure for the fluid) of 0.1 and specified reference conditions. The
correlation is
0.133
&" n R p
Q
(7.9)
h c,TP h c,o FPF "
& R

Q
po
o

where hc,TP is the heat transfer coefficient for two-phase boiling, h c,o is a reference value for the
&" is a reference heat flux, n is an exponent
heat transfer coefficient that depends on the fluid, Q
o
that depends on the reduced pressure, R p is the surface roughness, and R po is a reference
roughness. The coefficient FPF is a correlated function of the reduced pressure.
Equations 7.8 and 7.9 can only approximate the heat transfer coefficients for evaporators.
One reason is that the evaporation of the refrigerant can produce strong convection currents that
augment the natural convection flow significantly. Another is that the flow over the tubes is very
non-uniform and the coefficients are not equal throughout the evaporator. Equation 7.9 is useful,
though, for extending measurements on a given evaporator under one condition to another
condition.
Boiling inside tubes is more complicated than the boiling on the outside. The fluid enters a
tube as a liquid and, as it is heated, becomes a saturated mixture of liquid and vapor. The
evaporation process and flow regimes are shown schematically in Figure 7.2.

7.10

Figure 7.2 Flow regimes during evaporation or boiling


Initially, there is nucleate boiling at the wall that creates small bubbles that flow through the
liquid layer to the core. Large bubbles of vapor then form in the core that grow and move along
with the flow. Eventually, these large vapor bubbles coalesce and form a continuous core of
vapor with the liquid flowing in an annular film along the wall. At high values of the mass flux,
the annular flow pattern occurs over most of the tube length, whereas at low values the flow may
become stratified with liquid moving along the bottom of the tube and vapor along the top. As
the flow progresses down the tube, the liquid film on the walls becomes thinner and eventually
disappears as all of the liquid evaporates.
There are two interacting mechanisms for boiling inside tubes. Forced convection dominates
when the flow rates are high. Heat is transferred from the wall to the flowing liquid and
evaporation occurs at the liquid vapor interface. The second mechanism is nucleate boiling at the
wall surface, and this mechanism dominates when the heat flux is high or flow rate is low. The
relations for heat transfer over the entire boiling range are based on a combination of these two
mechanisms.
A correlation for the heat transfer coefficient for evaporation/boiling in tubes has been
developed to predict the ratio of the two-phase heat transfer coefficient to that for a single-phase
liquid flow (Kandlikar, Shoji, and Dhir, 1999). This ratio depends on the relative magnitudes of
the flow rate and heat flux, and can be represented in terms of two non-dimensional parameters.
One is the ratio of the density of the liquid phase to that of the vapor phase (fg = *). The
second parameter is a boiling number Bo* that is defined in terms of the wall heat flux,
refrigerant mass flux, latent heat of vaporization, and a surface parameter F Fl:
&" (1/ 0.7)
Q
Bo*
FFL
G h fg

(7.10)

where G is the mass flux (mass flow rate per unit cross sectional area). The fluid-surface
parameter FFL reflects the interaction of the fluid and the surface, and depends on the specific
refrigerant and the tube material. Values for F Fl for refrigerants flowing inside copper tubes are
given in Table 7.1. For stainless steel tubes the value of F Fl is unity.
Table 7.1 Values of FFL for copper tubes.
Refrigerant
FFL
Refrigerant

FFL

R-11
R-12

1.30
1.24

1.30
1.50

R-113
R-114

7.11

R-13B4
1.31
R-134a
1.63
R-22
2.30
R-152
1.10
From Chapter 15, Handbook of Phase Change: Boiling and Condensation, 1999.
The ratio of the heat transfer coefficient for two-phase (h TP) to that for single phase (h SP) is
plotted in Figure 7.3 as a function of vapor quality for different values of the modified boiling
number and the ratio of the liquid and vapor densities. The three curves for * of 10, 100, and
1000 for a Bo* of 0.0001 are indicated at the left of Figure 7.3, and the corresponding curves for
Bo* of 0.oo1 are indicated on the right. The local two-phase heat transfer coefficient varies with
distance along the tube in that it depends on the local value of the quality, and it needs to be
integrated over the tube length to compute the heat transfer.
It can be seen that the two-phase heat transfer coefficient can be up to twenty times larger
than that for a single-phase liquid flow. The coefficient is highest for situations in which the
liquid density is much larger than the vapor density (large values of * = fg). The two-phase
heat transfer coefficient is also larger when the boiling number is large, which occurs with large
heat fluxes or low mass flow rates. At a high value of the mass fraction of the vapor phase (high
value of quality) the heat transfer coefficient is high when the vapor phase is much less dense
than the liquid phase, but otherwise, quality has a relatively small effect.

Figure 7.3 Boiling heat transfer coefficients as a function of vapor quality.


Correlations have been developed for the curves shown on Figure 7.3 and are available in
Kandlikar, Shoji, and Dhir (1999). Example 7.2 illustrates the use of this map in determining the
heat transfer coefficient.
"Example 7.3 Determine the boiling heat flux and heat transfer coefficient inside the
0.5-inch diameter tubes of a DX coil at a location where the quality is 0.5. The

7.12

refrigerant is R-22, the saturation temperature is 35 F, the wall temperature is 45 F,


the tubes are copper, and the mass flow rate through each tube is 100 lb/hr."
Problem specifications
T_sat = 35 "F"
"Temperature"
T_w = 45 "F"
"Temperature"
x=0.5
"Quality"
D = 0.5*convert(in,ft) "ft"
"Tube diameter"
m_dot = 100 "lbm/hr"
"Mass flow rate"
"Surface finish factor for copper tubes (Table 7.1)"
F_Fl = 2.3
"Surface finish factor"
"Determine the liquid and vapor properties of the refrigerant "
rho_f = density(R22,x=0, T=T_sat) "lbm/ft3"
"Density"
rho_g = density(R22,x=1, T=T_sat) "lbm/ft3"
"Density"
h_f = Enthalpy(R22,x=0, T=T_sat) "Btu/lbm"
"Enthalpy"
h_g = Enthalpy(R22, x=1, T=T_sat) "Btu/lbm"
"Enthalpy"
h_fg = h_g - h_f "Btu/lbm"
"Enthalpy"
mu_f = Viscosity(R22, x=0, T=T_sat) "lbm/hr-ft" "Viscosity"
k_f = Conductivity(R22,x=0, T=T_sat) "Btu/hr-ft-F"
"Thermal conductivity"
Pr = Prandtl(R22,x=0, T=T_sat)
"Prandtl number"
"Determine the single phase heat transfer coefficient using an appropriate relation
from Table 4.3 in Section 4.3. A simple relation is used because the evaluation of the
boiling coefficient is not that precise.
N_u = 0.023*Re^0.8*Pr^0.4
"Nusselt number"
Re = 4*m_dot/(Pi*D*mu_f)
"Reynolds number"
N_u = h_SP*D/k_f
"Nusselt number"
Results

The Reynolds for a single phase flow of liquid refrigerant is 6286. The flow is turbulent and with
a Prandtl number of 2.52 the heat transfer coefficient is found to be 47.4 Btu/hr-ft 2-F. The value
of the heat transfer coefficient will be the base for determining the boiling heat transfer
coefficient.
"The calculation for the two phase heat transfer coefficient uses the correlation
presented in Figure 7.3. The ratio of the liquid to vapor density rho_star is
determined. The mass flux G is used in calculating the modified boiling number
Bo_star. The boiling number depends on the heat flux which is not known at the start
of the solution. The equation set is solved simultaneously with an estimate of the
ratio of two-phase to single-phase heat transfer coefficients alpha from Figure 7.3 to
find the modified boiling number, and then iterated until convergence is obtained.
Surface finish factor for copper tubes is from Table 7.1"
rho_star = rho_f/rho_g
"Density ratio"
G = m_dot/(Pi*D^2/4) "lbm/hr-ft2"
"Mass flux"
Bo_star = (q``/(h_fg*G))*F_Fl^(1/0.7)
"Boiling number"
alpha = 7
"h_TP/h_SP"
h_TP=alpha*h_SP "Btu/hr-ft2-F"
"Two-phase coefficient"
q`` = h_TP*(T_w - T_sat) "Btu/hr-ft2"
"Two-phase heat flux"

Results and Discussion

7.13

With the value for quality (0.5) and density ratio (57.0), the ratio of the two phase to single
phase heat transfer coefficient is read from Figure 7.3 to be about 7. By iteration, the modified
boiling number is found to be 0.0017. Using the correlations available would allow a more
precise determination of the ratio to be obtained. The heat transfer coefficient for boiling is then
332 Btu/hr-ft2-F and the heat flux 3320 Btu/hr-ft 2. The evaporation heat transfer coefficient is
high compared to that for single-phase flows.

SM 7.5 Thermal Performance of Condensers


Condensers in air conditioning and refrigeration systems are air-cooled, water-cooled, or
evaporatively cooled. Water-cooled condensers are generally shell and tube exchangers and are
very similar to a chilled water evaporator. A two-pass water cooled condenser is shown
schematically in Figure 7.4. Refrigerant vapor leaving the compressor enters at the top of the shell
and flows downward. The vapor condenses on the outside of the tubes and drains by gravity out the
bottom.
Air-cooled condensers are constructed similar to cooling coils, and, similar to water-cooled
condensers, refrigerant vapor enters at the top and liquid refrigerant leaves at the bottom. In an aircooled condenser the refrigerant is condensed inside tubes and air flows over the outside.
Evaporative condensers, discussed in Chapter SM 4, are constructed similar to coils, but use
evaporation of water from the heat transfer surfaces and into the air stream to condense the
refrigerant.

Figure 7.4 Schematic of a water-cooled condenser


The refrigerant enters the condenser from the compressor, usually with a significant amount of
superheat. The refrigerant vapor is cooled in the upper section of the condenser to the saturation
temperature before condensation occurs. The heat transfer from the superheated vapor is in the
range of 10 to 30 percent of the total heat transfer. The condensed refrigerant leaves at the bottom
of the condenser. There is some subcooling by the lowest incoming water but the amount of heat
transfer is much less than that for desuperheating.

7.14

In the condensing section the specific heat of the condensing fluid is infinite since the enthalpy
changes without a corresponding temperature change. In this section the condensing fluid has an
infinite capacitance rate and the capacitance rate ratio (C*) is zero. In the sections in which
desuperheating and subcooling occur the capacitance rate ratio has a finite value. However, since
most of the heat is transferred during the condensation process, the approximation that C* is
essentially zero for the entire condenser is usually sufficiently accurate for design or evaluation.
The condensing temperature is then used as the inlet temperature in determining the effectiveness.
In some circumstances it might be desirable to separately analyze the desuperheating and
subcooling sections. The heat transfer coefficients on the refrigerant side are quite different in
these sections. The heat transfer coefficient for the vapor in the desuperheating section is low and
that for the subcooling section is high, although less than that for section in which condensation
occurs. An accurate determination of the performance would involve dividing the exchanger up
into three separate, but coupled exchangers. Each would have a different value for the number of
transfer units and capacitance rate ratio. The solution would involve interation to find the outlet
conditions. Example 7.3 illustrates the contribution that the desuperheating and subcooling
sections make to the overall heat transfer in a condenser.
"Example 7.4 A water-cooled condenser is to be designed for a flow of 0.2 kg/s of R-22
that enters at a temperature of 125 C and a pressure of 1200 kPa and leaves at 25 C.
The water enters at a temperature of 17 C and has a temperature rise of 10 C.
Determine the required overall heat transfer coefficient for the condenser."
Problem specifications
m_dot_r = 0.2 kg/s
p_sat = 1200 kPa
T_r_i = 125 C
T_r_o = 25 C
T_w_i = 17 C
T_w_o = 27 C

Mass flow rate


Pressure
Temperature
Temperature
Temperature
Temperature

"Refrigerant properties"
T_sat = temperature(R22, p = p_sat, x = 1) C
Temperature
h_g = enthalpy(R22, p = p_sat, x=1) kJ/kg
Enthalpy
h_f = enthalpy(R22, p = p_sat, x=0) kJ/kg
Enthalpy
h_fg = h_g - h_f kJ/kg
Enthalpy
h_r_i = enthalpy(R22, p = p_sat, T = T_r_i) kJ/kg
Enthalpy
h_r_o = enthalpy(R22, p = p_sat, T =T_r_o) kJ/kg
Enthalpy
"The heat flow rate is determined from an energy balance using the refrigerant flow
and enthalpy change"
q = m_dot_r*(h_r_i - h_r_o) kW
Heat flow rate
"Water properties"
cp_w = specheat(water,T=T_w_i, x=0) kJ/kg-C
Specific heat
"An energy balance on condenser that relates the heat transfer from the refrigerant
to the evaporator is performed. This yields the water flow rate needed to condense
the refrigerant and the corresponding capacitance rate"
q = m_dot_w*cp_w*(T_w_o - T_w_i) kW
Heat flow rate
C_w = m_dot_w*cp_w kW/C
Capacitance rate

7.15

"The condenser is first treated as a single heat exchanger. The effectiveness is


determined from the ratio of the heat transfer to the water to the maximum heat
transfer and then equated to the effectiveness relation for a C* of zero with the water
flow as the minimum capacitance fluid. The resulting Ntu is then used to find the
UA_s for the single heat exchanger approximation. "
epsilon = C_w*(T_w_o - T_w_i)/(C_w*(T_sat - T_w_i))
Effectiveness
epsilon = 1 - exp(-Ntu)
Effectiveness
"The overall heat transfer coefficient for a single heat exchanger"
Ntu = UA_s/C_w
Ntu

Results
The heat transfer based on the refrigerant mass flow rate and enthalpy difference is 52.4 kW,
yielding a required water flow rate for the 10 C rise of 1.252 kg/s.
In treating the condenser as a single exchanger with a capacitance rate ratio of unity, it is
assumed that all of the heat is transferred from the refrigerant at the constant saturation
temperature of 30.25 C. The effectiveness for this assumption is 0.755, yielding an Ntu of 1.406
and a UA of 7.37 kW/C. This result will be compared to the more realistic design using two
exchangers.
"The condenser is treated as being composed of two heat exchangers. One is the
desuperheater (ds) and the other is the condenser and subcooler (cond). The
solution is iterative in that the water temperature entering the desuperheater is
unknown. For the desuperheater, the refrigerant leaves as saturated vapor. The
heat flow is determined from the refrigerant mass flow rate and enthalpy difference."
q_ds = m_dot_r*(h_r_i - h_g) kW
Heat flow rate
cp_r = (h_r_i - h_g)/(T_r_i - T_sat) kJ/kg-C
Specific heat
"The desuperheater is a sensible heat exchanger with a finite capacitance rate ratio"
C_r = m_dot_r*cp_rkW/C
Capacitance rate
C_star = C_r/C_w
Capacity rate ratio
"The effectiveness of the desuperheater is based on the refrigerant as the minimum
capacitance fluid. The water temperature entering the desuperheater T_w_ds is
unknown. The effectiveness relation for a counter flow exchanger from Table 13.1 is
used. The overall heat transfer coefficient for the desuperheater is determined from
the Ntu."
epsilon_ds = q_ds/(C_r*(T_r_i - T_w_ds))
Effectiveness
epsilon_ds = (1 - exp(-Ntu_ds*(1-C_star)))/(1 - C_star*exp(-Ntu_ds*(1-C_star)))
Effectiveness
Ntu_ds = UA_ds/C_r
Ntu
"For the condenser and subcooler, the heat flow for the condensing and subcooling
sections is based on the refrigerant mass flow rate and enthalpy difference. The heat
flow to the water is used to find the temperature of the water entering the
desuperheater."
q_cond = m_dot_r*(h_g - h_r_o) kW
Heat flow rate
q_cond = C_w*(T_w_ds - T_w_i) kW
Heat flow rate
"The effectiveness is based on the heat flow to the water and the water as the
minimum capacitance fluid. The effectiveness for the condenser and subcooler is for
a C* = 0 exchanger. The overall heat transfer coefficient is determined from the
Ntu.
epsilon_cond = q_cond/(C_w*(T_sat - T_w_i))
Effectiveness
epsilon_cond = 1 - exp(-Ntu_cond)
Effectiveness
Ntu_cond = UA_cond/C_w
Ntu

7.16

"The total overall transfer coefficient for the treatment of the condenser as two
exchangers is the sum of that for the condenser and desuperheater."
UA_overall = UA_cond + UA_ds kW/C
Overall UA
"The relative heat transfer rates for the single heat exchanger and for the two
exchanger analysis are indicated by the relative temperature differences."
Deltah_single = h_r_i - h_r_o kJ/kg
Enthalpy
Deltah_ds = h_r_i - h_g kJ/kg
Enthalpy
Deltah_cond = h_g- h_f kJ/kg
Enthalpy
Deltah_sc = h_f - h_r_o kJ/kg

Enthalpy

ResultsandDiscussion:
For the design treating the condenser as a single exchanger the heat transfer rate is 62.4 kW and
the overall thermal conductance is 7.37 kW/C. The heat transfer rate is the same for both
treatments.
Forcondensing/subcoolingsectiontheheattransferrateis36.8kW. Thewatertemperature
increases from 17C to24.0 Cin this section. The capacitance rate ratioC* is zeroandthe
effectiveness is 0.531, yielding an Ntu_cond of 0.757 and a UA_cond of 3.96 kW/C.
For the desuperheater section the heat transfer rate is 15.6 kW. The capacitance rate of the
refrigerant is 0.164 kW/C, and for the desuperheater the refrigerant capacitance rate is the
minimum. For this sensible heat exchanger the effectiveness is 0.938, the Ntu is 2.85, and the UA
is 0.47 kW/C.
The overall heat transfer coefficient for the two-exchanger design is the sum of the component
UA values, or 4.43 kW/C. This value is significantly less than the 7.37 kW/C determined assuming
that all of the heat was transferred at the saturation temperature. The assumption that the condenser
can be treated as a single exchanger with a capacitance rate ratio of zero does not account for the
fact that the vapor enters at a high temperature. The large temperature difference in the
desuperheater means that the UA needs to be smaller. For the conditions of this condenser it is
necessary to design the unit as two exchangers.
The enthalpy changes of the refrigerant in the heat exchanger for the three processes indicate
the relative heat transfer:
Desuperheating to saturation vapor: 77.8 kJ/kg
Condensation at saturation:
176.3 kJ/kg
Subcooling from saturated liquid;
7.9 kJ/kg
Total enthalpy change
262 kJ/kg
About 30 % of the heat transfer occurs during the de-superheating process, but only 3 % during
the subcooling. Thus it is reasonable to combine the subcooling and condensing sections in the
design of the condenser, but to treat the desuperheating section separately.

SM 7.6 Heat Transfer Coefficients for Condensers


When refrigerant vapor comes into contact with a surface that is at a temperature below the
dew point, vapor starts to condense. The condensing liquid is heavier than the vapor and flows

7.17

downward under the influence of gravity. Depending on the condition of the surface on which
the condensation occurs, the process may be either dropwise or filmwise condensation. In
dropwise condensation, drops of condensate form on the surface and flow downward, leaving the
surface essentially bare except for the areas on which the drops are forming. The rates of heat
transfer are high since most of the condensing vapor is in intimate contact with the surface. In
filmwise condensation, a film of condensate forms that covers the surface and continually drains.
Condensation takes place at the film-vapor interface and the heat of condensation is transferred
through the liquid film to the surface. The heat transfer rates for filmwise condensation are less
than those for dropwise condensation due to the added thermal resistance of the condensate film.
It is difficult to maintain a surface so that the drops do not coalesce and thus filmwise
condensation usually occurs.
Condensation can occur on either the outside or the inside of the tubes of a refrigerant
condenser, as shown schematically in Figure 7.5. In most water-cooled condensers the refrigerant
condenses on the outside of the tubes. The condensate drips from the tubes and is removed from
the shell of the condenser at the bottom. In air-cooled condensers, the refrigerant flows inside the
tubes and condensate drains from the tube at the condenser headers. Although the geometries are
quite different the mechanisms are similar and the same fluid properties govern the heat transfer.

Figure 7.5 Condensation on the outside and inside of tubes


For the relatively small diameter tubes found in refrigeration condensers the condensate flow
on the outside of tubes is laminar rather than turbulent, and only the laminar relations will be
presented. The laminar heat transfer coefficient for condensation on the outside of a horizontal
tube can be represented by equation 7.11, and is often termed a falling film correlation. The
important parameter is the density difference between the liquid and vapor that creates the
buoyancy force that causes the fluid to flow, similar to that for natural convection. The term
inside the brackets is analogous to a Rayleigh number and the exponent on the grouping of
properties is 0.25, which is the same as for laminar natural convection. The Nusselt number
based on the tube diameter D is given by:
(7.11)
where kf is the liquid thermal conductivity, g the acceleration due to gravity, f and g are the
liquid and vapor densities, respectively, f is the liquid viscosity, Tsat and Ts are the saturation and
surface temperature, respectively. The term h 'fg is a modified heat of vaporization that includes

7.18

the thermal effect of subcooling the vapor from the saturation temperature to the surface
temperature, and is given by:
h 'fg h fg 0.68 c p,f Tsat Ts
(7.12)
where hfg is the heat of vaporization at the saturation temperature and c p,f is the specific heat of the
liquid. The film of condensate on a tube is quite thin, and is determined as:
(7.13)
These relations include the important properties that govern condensation heat transfer. The
downward flow of the condensate is driven by gravity. With an increasing difference the film
thickness is thinner and the heat transfer coefficient higher. Increased viscosity results in a
thicker film and less heat transfer. Increased conductivity, which is in both the Nusselt number
definition and the correlation parameter, increases the heat transfer coefficient. An increased
latent heat of vaporization increases the heat transfer per unit mass, and results in an increased
coefficient. An increased difference between the surface and saturation temperatures increases
the film thickness since the rate of condensation is increased, which reduces the heat transfer
coefficient. The heat flow, though, which is the product of the heat transfer coefficient and the
temperature difference between the fluid and surface, increases. Equation 7.11 has been found to
underpredict the heat transfer by 15 to 20 % and so it provides a conservative estimate of the heat
transfer coefficient.
In many condensers, tubes are placed above each other. The condensate from one tube drips
onto the tube below, which increases the thickness of the film and reduces the heat transfer
coefficient. Equation 7.11 has been modified to account for a tube bank that is N tubes high by
dividing the term in brackets by the number of tubes in the vertical direction:
(7.14)
Condenser fins are often added to increase the area and the overall heat transfer coefficient.
A schematic of a typical finned horizontal tube is shown in Figure 7.6. Cold water flows inside
the tubes and refrigerant vapor flows horizontally over the tubes. Refrigerant condensate forms
on both the fins and the bare tubing and flows downward.

Figure 7.6 Condensation on finned tubes

7.19

For the finned tube geometry, the heat transfer coefficient is given by a relation similar to
equation 7.5. An equivalent diameter is employed that accounts for the added heights of the fins.
The following relation is recommended (ASHRAE, 2005).
(7.15)
where the characteristic dimension in equation 7.15 is an equivalent fin diameter defined as:
(7.16)
and the effective area is a function of the fin area, prime area, and the fin efficiency. The
effective area is
(7.17)
and the effective fin length is the ratio of the area on one side of the fin to the tube diameter.
(7.18)
This rather complicated set of relations for the equivalent diameter of finned tubes has been
determined experimentally. In general, the heat transfer coefficients for condensation on finned
tubes are somewhat higher than those for bare tubes because the fins are vertical surfaces and the
liquid drains better than around a circular tube. However, the main effect of fins is the addition of
more surface area. Equations 7.11, 7.14, and 7.15 are general relations that apply to situations in
which the condensate drains from the tubes. If the fin spacing is too small, surface tension may
cause the liquid to collect and the fluid will not drain and the heat transfer rate will be reduced.
Air and other non-condensables can adversely affect the heat transfer coefficients. Heat
transfer coefficients for condensation are generally much higher than for single-phase convective
heat transfer, and this usually makes accurate determination of the coefficients less critical.
Example 7.4 illustrates the calculation of the condensation heat transfer coefficient for bare and
for finned tubes.
"Example 7.5 Determine the heat transfer coefficients and thermal resistances for R22 condensing on horizontal one-inch diameter tubes for the case of plain and finned
tubes. The fins are of copper with a diameter of 1.35 inches, a thickness of 0.004
inches, and a pitch of 10 fins/inch. The saturation temperature of the refrigerant is
85 F and the surface is 80 F."
Problem specifications
T_s = 80 F
temperature
T_sat = 85 F
DT = T_sat - T_s F

Surface
Saturation temp.
Temp. difference

Determine the properties of refrigerant for the liquid and vapor phases.
p_sat = Pressure(R22,x=0, T=T_sat) psia
Saturation
pressure
rho_f = 1/Volume(R22,x=0, T=T_sat) lbm/ft3
Density
rho_g = 1/Volume(R22,x=1, T=T_sat) lbm/ft3
Density
cp_f = specheat(R22,T=T_sat, x = 0) Btu/lbm-F
Specific heat
k_f = Conductivity(R22,x=0, P=P_sat) Btu/hr-ft-F
Thermal
conductivity
mu_f = Viscosity(R22, x=0, P=P_sat) lbm/hr-ft
Viscosity
h_f = Enthalpy(R22,x=0, T=T_sat) Btu/lbm
Enthalpy

7.20

h_g = Enthalpy(R22, x=1, T=T_sat) Btu/lbm


h_fg = h_g - h_f Btu/lbm
vapor.

Enthalpy
Latent heat of

Determine the effective latent heat of vaporization from equation 7.12


h_fg_prime = h_fg+ 0.68*cp_f*DT Btu/lbm
Effective latent
heat
To determine the unit resistances use one foot as the length of the tube.
L = 1 ft
Length
D = 1*convert(in,ft) ft
Diameter
Convert gravitational attraction from a per second to a per hour basis
g = 32.2*convert(ft/s^2, ft/hr^2) ft/hr2
Gravity
"Determine the thermal resistance of the bare tube. The Nusselt number is
calculated using equation 7.14"
N_u_bare = 0.728*(g*rho_f*(rho_f - rho_g)*d^3*h_fg_prime/
(k_f*mu_f*DT))^0.25Nusselt number
N_u_bare =h_tube*D/k_f
Nusselt number
A_tube = pi*D*L ft2
Area
R_tube = 1/(h_tube*A_tube) hr-F/Btu
Thermal resistance

Results
The modified heat of vaporization accounts for cooling the vapor from 82 F to 80 F, and is 77.2
Btu/lbm. The Nusselt number for the bare tubes is 743 and the heat transfer coefficient is 420
Btu/hr-ft2-F. The area of the tube per foot of length is 0.26 ft 2, yielding a resistance per foot of
length of 0.00910 hr-F/Btu.
"Determine the thermal resistance of finned tubes. The Nusselt number is
determined using equation 7.15"
N_u_fin = 0.689*(rho_f^2*g*D_eq^3*h_fg_prime/(k_f*mu_f*DT))^0.25
Nusselt number
N_u_fin = h_fin*D_eq/k_f
Nusselt number
The effective diameter and area is found using equations 7.16, 7.17, and 7.18
1/D_eq^0.25 = 1.3*A_allfins*eta_fin/(A_eff*L_mf^0.25) + A_p/(A_eff*D^0.25)
Equivalent D
A_eff = A_allfins*eta_fin + A_p ft2
Area
The fin parameters are needed in order to find fin efficiency from Figure 13.8 The
thermal conductivity of the fins is that for copper. The equations are not coupled and
can be solved sequentially.
k_fin = 230 Btu/hr-ft-F
Thermal
conductivity
Parameter_fin = m_fin*(r_2c - r_1)
Fin parameter
m_fin = sqrt(2*h_fin/(k_fin*t_fin)) 1/ft
Fin parameter
r_2c = D_fin/2 ft
Radius
r_1 = D/2 ft
Radius
D_ratio = r_2c/r_1
Diameter ratio
From Figure 7.8, the fin efficiency for this diameter ratio and fin parameter is found
eta_fin = 0.67
Fin efficiency
Determine the effective length and area of the fins. The pitch is 10 fins/inch.
L_mf =(A_fin/2)/Dft
Effective length
D_fin = 1.35*convert(in,ft) ft
Fin diameter
A_p = pi*D*(L - 10*12*t_fin) ft2
Area
t_fin = 0.01*convert(in,ft) ft
Fin thickness

7.21

A_fin = 2* pi*((D_fin+t_fin)^2 - D^2)/4 ft2


Area
A_allfins = A_fin*FPI*L ft2
Area
FPI = 10*convert(1/in,1/ft) 1/ft
Pitch
R_fin = 1/(h_fin*A_eff) hr-F/Btu
Thermal resistance
eta_overall = 1 - (A_allfins/(A_allfins + A_p))*(1 - eta_fin)
Overall efficiency
R_finnedtube = 1/(h_fin*eta_overall*(A_allfins + A_p)) hr-F/Btu Thermal resistance

Results and Discussion:


The total fin area per foot of tube length is 1.112 ft 2. The area not covered by the fins, which
is the tube surface area less that covered by the base of 120 fins, is 0.236 ft 2 per foot of length.
The effective area per foot of length is 0.981 ft 2, the effective fin length is 0.0556 ft, and the
equivalent diameter is 0.0264 ft. The Nusselt number for the finned tubes is 300, yielding a
condensing heat transfer coefficient of 535 Btu/hr-ft 2-F. The fin and overall efficiencies are
determined to be 0.670 and 0.727 respectively. The thermal resistance per foot of length for the
finned tubes is 0.00190 hr-F/Btu.
The heat transfer coefficient is increased by about 25 % by the addition of the fins. However,
the main effect of the added fin surface area is to reduce the thermal resistance by a factor of
almost five. Fins have a significant effect on the resistance during condensation.
Although the above solution is not iterative the surface temperature is generally not known.
It would be determined through a heat transfer analysis that would include the heat transfer
coefficient calculations and would involve iterative calculations.
Condensation inside horizontal tube is more complicated than that for condensation outside
the tubes. The formation of the condensate is affected by the flow of fluid through the tube. A
different set of flow regimes exist depending on the flow rate of the fluid through the tube.
Typical two-phase flow patterns for flow in horizontal tubes for low and high mass velocity (flow
rate per unit area) are shown in Figure 7.7.

7.22

Figure 7.7 Flow regimes for condensation in horizontal tubes


When the mass velocity of the flow is low, there is initially a region where the superheated
vapor is cooled to the dew point. Condensation then forms around the periphery of the tube and,
due to the shear at the liquid and vapor interface, flows axially down the tube. The liquid at the
top of the tube also drains downward due to gravity, creating an annular flow pattern, and the
cross-sectional pattern is as shown in Figure 7.8. The angle q represents the fraction of the tube
wall on which condensation occurs. All vapor eventually condenses and the liquid flows axially
out of the tubes. When the mass flux is high, the superheated section is relatively longer. The
liquid condensate fills the tube with bubbles of vapor entrained in the liquid that eventually
condense. The liquid becomes subcooled and flows from the tube.

Figure 7.8 Annular flow pattern for condensation in horizontal tube

7.23

The heat transfer during condensation involves two types of mechanisms. One is film
condensation similar to that which occurs on the outside of a horizontal cylinder, discussed
above. The other mechanism is convective condensation, which is due to the axial flow of
condensate along the channel and is similar to that for forced convection in tubes, discussed in
Section 4.3. The heat transfer coefficients for film and axial flow condensation are applied to
their respective areas. Flow pattern maps have been developed by Hajal, et al. (2003) and Thome
et al. (2003) that show the transition boundaries for different flow regimes such as wavy,
stratified, and mist. Only a brief summary of the basic ideas will be given in this text.
For the upper portion of the tube where film condensation occurs, the film is very thin and the
heat transfer coefficients are high. The thickness of the falling film is given by
D 1
(7.19)
ff
4
where D is the tube diameter and is the void fraction (the vapor fraction of the mixture by
volume). The void fraction is directly related to the quality x and the densities of the two phases.

g

f

1 x
1

(7.20)

The falling film condensation coefficient is given by equation 7.11, repeated here
(7.21)
The convection flow heat transfer coefficient is given by a relation similar to that for forced
convection in tubes
h
Nu L L 0.003Re0.74
Prf0.5 f i
(7.22)
L
kf
where L is the thickness of the liquid at the bottom of the tube and f i is an interfacial roughness
factor that accounts for the shear between the vapor and liquid. The Reynolds number is
determined using the thickness of the liquid layer as the characteristic dimension
4G 1 x L
ReL
(7.23)
1 f
where G is the mass flux. The Prandtl number is defined using the properties of the liquid:
cp,f f
Prf
(7.24)
kf
The interfacial roughness factor f i is about unity for thin films and increases as the ratio of the
vapor velocity to liquid velocity increases. It has been correlated as

1/ 4

2
Vg f g g

(7.25)
f i 1

Vf

where is the surface tension and accounts for the damping effect of surface tension on surface

waves created by the movement of vapor over the liquid.


For stratified flow, such as shown in Figure 7.8, the thickness of the layer depends on the
relative amounts of vapor and liquid. A correlation for the angle of the condensing vapor

7.24

fraction as a function of the quality has been obtained, and is shown in Figure 7.9. Even at a low
value of quality the angle of the condensing layer is greater than 180 degrees and the fraction of
the tube exposed to the condensing layer is over 50 %.

Figure 7.9 Angle of condensing layer for stratified flow


The thickness of the liquid layer is related to the angle of the condensing vapor fraction
through the geometry shown in Figure 7.8. The geometric relation for height of the liquid layer
as a function of the angle for the film condensation portion is
2
D
L 1 cos
(7.26)

2
2

The expression for the thickness of the liquid layer allows the convective heat transfer coefficient
to be determined. The overall heat transfer coefficient is then a sum of the condensing and
convective heat transfer coefficients weight by the respective heat transfer areas.
The basic ideas behind the mechanisms of condensation in tubes have been presented in this
section. Although the heat transfer coefficients can be estimated using these relations, it is
recommended that the original references (Hajal, et al., 2003; Thome et al., 2003) be consulted.
These references describe flow pattern maps that describe the different flow regimes in a tube at
different axial positions and lead to a more accurate evaluation of the local heat transfer
coefficient as a function of axial position. The condensation phenomenon is obviously very
complicated and the calculation process yields local values at an axial position that must then be
integrated over the length of the tube. The modern design of condensers is based on these ideas.
Example 7.6 illustrates the calculation procedure when a number of the parameters are known.
"Example 7.6 Estimate the heat transfer coefficients for R-134a condensing inside
the tubes of an air-cooled condenser at a position where the quality is 60 %. The flow
rate per tube is 0.0025 kg/s, the tube diameter is 8 mm, the saturation temperature
is 40 C, the surface temperature is 35 C, and the interface roughness factor is 1.2. "
"Problem specifications"
T_s = 38 C

Temperature

7.25

T_sat = 40 C
DT = T_sat - T_s C
p_sat = Pressure(R134a,x=0, T=T_sat) kPa
x = 0.6
D = 8*convert(mm,m) m
m_dot = 0.0025 kg/s
f_i = 1.2
roughness
g = 9.8 m/s2

Temperature
Temp. difference
Pressure
Quality
Tube diameter
Mass flow rate
Interfacial
Gravity

"Determine the refrigerant properties for both the liquid and vapor phases"
rho_f = density(R134a,x=0, T=T_sat) kg/m3
Density
rho_g = density(R134a,x=1, T=T_sat) kg/m3
Density
h_f = Enthalpy(R134a,x=0, T=T_sat) kJ/kg
Enthalpy
h_g = Enthalpy(R134a, x=1, T=T_sat) kJ/kg
Enthalpy
h_fg = h_g - h_f kJ/kg
Latent heat
cp_f = specheat(R134a,T=T_sat, x = 0) kJ/kg-C
Specific heat
k_f = Conductivity(R134a,T=T_sat, x=0) W/m_C
Thermal
conductivity
mu_f = Viscosity(R134a, T=T_sat , x=0) kg/m-s
Viscosity
Determine the effective latent heat of vaporization from equation 7.12
h_fg_prime = h_fg+ 0.68*cp_f*DT kJ/kg
Effective latent
heat
"The void fraction is given by equation 7.20"
Void = 1/(1+((1-x)/x)*(rho_g/rho_f))
Void fraction
"The heat transfer coefficient is needed for both the falling film condensation and the
convective flow along the bottom of the tube. The condensation coefficient is
computed first. The Nusselt number for the film condensation portion is given by
equation 7.21. The equations are not coupled and can be solved sequentially."
N_u_film = 0.728*(g*rho_f*(rho_f - rho_g)*d^3*h_fg*convert(kJ,J)/
(k_f*mu_f*DT))^0.25 Nusselt
N_u_film =h_film*D/k_f
Nusselt number
"The thickness of the falling film is given by equation 7.19"
delta_ff = D*(1-void)/4 m
Falling film
thickness
"The convective condensation coefficient and angle of contact of the condensate
layer are determined next. The angle of the condensate layer is taken from Figure
7.9."
Theta = 300* convert(deg,rad) rad
Layer angle
delta_L = D*0.5*(1-cos((2*Pi-theta)/2)) m
Layer thickness
D_ratio = delta_L/D
Relative thickness
The Reynolds number is given by equation 7.23, with the mass flux determined from
the mass flow rate and cross-sectional area. The Nusselt number is then given by
equation 7.22 and the convection coefficient is computed using the Nusselt number
and the thickness of the layer. "
G_flow = m_dot/A kg/m2-s
Mass flux
A = Pi*D^2/4 m2
Cross-sectional
area
Re = 4*G_flow*(1-x)*delta_L/((1-void)*mu_f)
Reynolds number
Pr = cp_f*convert(kJ,J)*mu_f/k_f
Prandtl number
N_u_conv = C*Re^n*Pr^m*f_i
Nusselt number
C=0.003
Coefficient
n = 0.74
Exponent

7.26

m = 0.5
N_u_conv = h_conv*delta_L/k_f

Exponent
Nusselt number

"The overall condensation coefficient is the sum of the falling film and convective
coefficients weighted by the area of the tube (represented by the angle) for each
mechanism"
h_overall=h_film*(Theta/(2*Pi))+h_conv*(2*Pi-Theta)/(2*Pi) W/m2-C
Overall coefficient

Results and Discussion


For the falling film section of the tube, the Nusselt number is 330 and the heat transfer
coefficient is 3122 W/m2-C. The thickness of the falling film depends on the void fraction, which
is 0.972, which means that the volume of the refrigerant vapor is 97 % of the tube volume at this
location. The film thickness is 0.000057 m. The falling film is very thin and the thickness is
about 0.6% of the tube diameter.
The Reynolds number for the convective flow is a function of the thickness of the liquid layer
which in turn depends on the angle of the condensation layer as shown in Figures 7.8 and 7.9.
For a quality of 0.6 the angle is 300 degrees or 5.24 radians. The liquid layer thickness is
0.000546 m, which is about 7 % the thickness of the tube diameter. The mass flux is 49.7 kg/m 2-s
and the Reynolds number is 9350. The Nusselt number is 5.58 and the convective heat transfer
coefficient for the layer at the bottom of the tube is 788 W/m2-C.
The convective coefficient is about one-quarter as large as the falling film coefficient.
However, the surface area for convection is very small, as indicated by the large void volume and
large angle of the condensing flow. The overall heat transfer coefficient is the area weighted
average of the falling film and liquid layer heat transfer coefficients and is 2733 W/m2-C. At this
position the heat transfer coefficient is close to that for the film that condenses on the tube walls.

SM 7.7 Pressure Drops in Two-Phase Flows


The pressure drop due to a single phase flow of a fluid through a pipe is due to wall friction
and to fittings, and relations for determining the pressure drop are presented in Chapter 3. In twophase flow there are additional mechanisms that come into play and that need to be accounted for
in the pressure drop evaluation. The wall friction relations are different since both liquid and
vapor flow through the pipe and the flow patterns are different from those of single phase flows.
For example, in annular condensation flow there is a thin layer of liquid between the wall and the
vapor that affects the wall friction. The second mechanism is the change in momentum of the
flow due to evaporation or condensation, even if the cross-sectional area of the pipe is constant.
For example, in the tubes of an evaporator the entering fluid is mostly liquid phase and has a
relatively low velocity and, consequently, momentum. As the liquid evaporates into vapor the
density decreases significantly and the velocity increases. The corresponding momentum
increase is a result of the pressure forces on the fluid, and so the momentum of the vapor leaving
the tube is relatively high and the pressure is low. Similarly, for condensation, the momentum of
the flow decreases in the flow direction and the pressure rises.

7.27

One approach to estimating the pressure drops in two-phase flows is to modify the
relationships for single phase flows. In some of the approaches a multiplier for the single phase
pressure drop is employed. Other relationships are based on a set of empirical relations that add
to the single phase relation. For all of the correlations, the differences between the calculated and
measured pressure drops can be as high as 50 %. The Muller-Steinhagen and Heck correlation
(ASHRAE, 2005) has been found to work quite well with a database consisting of flows of
refrigerants and steam as well as mixtures of air, water, and/or oil in horizontal tubes, and is
presented here.
The correlations are presented as the pressure gradient rather than the pressure difference
over the flow length. The properties of the flow such as quality and void fraction change as the
fluid flows through a pipe and so the local value of the pressure gradient needs to be integrated to
obtain the total pressure drop. The Muller-Steinhagen and Heck correlation is give as
dp
1/ 3
dp
1 x x3
(7.27)
dz
dz lo
where p is the pressure, z is the coordinate along the flow length, x is the quality, and the
subscript lo denotes the liquid phase only. The term is a combination of the liquid and vapor
phase pressure gradients and given as
dp
dp

dp
2 x
(7.28)
dz lo dz

dz lo
vo
The liquid and vapor only pressure gradients are determined using the conventional relations with
friction factor, mass flux, and fluid properties (Chapter 3).
2G T2
dp

f
lo
dz
D f
lo

(7.29)

2G T2
dp

f
vo
dz
D g
vo

(7.30)

and

where flo and fvo are the friction factors for liquid only and vapor only flows, respectively, at the
total mass flux GT and l and v are the liquid and vapor densities at the local pressure and
temperature, respectively. The friction factors are computed using the relation (Chapter 3) of
f 0.079 Re D0.25
H

(7.31)

where the Reynolds number is defined using the total mass flux and the liquid or vapor viscosity,
as appropriate.
Re DH

GT DH
f

(7.32)

The estimation of the pressure gradient is given in Example 7.7 for the condensation
conditions described in Example 7.6.

7.28

"Example 7.7 Estimate the pressure gradient for R-134a condensing inside the tubes
of an air-cooled condenser at a position where the quality is 60 %. The flow rate per
tube is 0.0025 kg/s, the tube diameter is 8 mm, the saturation temperature is 40 C,
and the surface temperature is 35 C.
The equations are not coupled and can be solved sequentially. "
Problem specifications
T_sat = 40 C
x = 0.6
D = 8*convert(mm,m) m
m_dot = 0.0025 kg/s

Temperature
Quality
Tube diameter
Mass flow rate

Determine the refrigerant properties for both the liquid and vapor phases.
rho_f = density(R134a,x=0, T=T_sat) kg/m3
Density
rho_g = density(R134a,x=1, T=T_sat) kg/m3
Density
mu_f = Viscosity(R134a, T=T_sat , x=0) kg/m-s
Viscosity
mu_g = Viscosity(R134a, T=T_sat , x=1) kg/m-s
Viscosity
Determine the mass flux based on the mass flow rate and cross-sectional area
G_tot = m_dot/A_c kg/m2-s
Mass flux
A_c = pi*D^2/4 m2
Cross-sectional
area
"The liquid phase pressure gradient is from equation 7.29 with the friction factor from
equation 7.31. The Reynolds number is based on the total mass flux and the liquid
viscosity."
Re_l = G_tot*D/mu_f
Reynolds number
f_l = 0.079*Re_l^(-0.25)
Friction factor
dpdz_l = -f_l*2*G_tot^2/(d*rho_f) Pa/m
Pressure gradient
"The vapor phase pressure gradient is from equation 7.30 with the friction factor from
equation 7.31. The Reynolds number is based on the total mass flux and the vapor
viscosity."
Re_v = G_tot*D/mu_g
Reynolds number
f_v = 0.079*Re_v^(-0.25)
Friction factor
dpdz_v =- f_v*2*G_tot^2/(d*rho_g) Pa/m
Pressure gradient
"The total pressure gradient is form equation 7.27 with Lambda calculated from
equation 7.28"
Lambda = dpdz_l + 2* (dpdz_v - dpdz_l)*x
dpdz = lambda*(1-x)^(1/3)+dpdz_l*x^3 Pa/m
Pressure gradient

Results and Discussion


The fluid properties and mass flux are the same as in Problem 7.6. For the liquid only
pressure gradient, the Reynolds number is 2469 and the friction factor is 0.0112. The
corresponding pressure gradient is 6.04 Pa/m. The Reynolds number for the vapor only
calculation is 31,320, the friction factor 0.00594, and the pressure gradient -73.3 Pa/m.
The pressure gradient depends on the parameter which is 86.8 Pa/m. The pressure
gradient at the location where the quality is 0.6 is then 65.2 Pa/m.

7.29

Example 7.7 shows how the local pressure gradient is estimated. To determine the overall
pressure drop, the pressure gradient needs to be integrated over the tube length. This involves
evaluating the quality along the tube length. Determining the quality as a function of length
requires an energy balance on the flow. The quality at a position depends on the total heat
transfer to or from the flow which depends on the heat transfer coefficient. Although the process
is involved, the heat transfer and pressure gradient relations presented here will allow the total
pressure drop to be estimated.

SM 7.8 Summary
Condensers and evaporators are sensible heat exchangers in which the refrigerant changes
phase. The capacitance rate during a phase change is effectively infinite since the fluid energy
changes without a corresponding change in temperature. However, the refrigerant is often
superheated or subcooled, and the overall capacitance rate ratio is not zero. For evaporators,
treating the exchanger as one with a capacity rate ratio of zero is usually sufficiently accurate. In a
condenser, there is usually significant desuperheating of the vapor prior to condensation. Dividing
the exchanger into two sections, one with a finite capacitance ratio and the other zero, improves the
estimation of performance.
In the evaporation and condensation of refrigerants additional mechanisms over those in single
phase heat transfer are present. The process of changing phase from liquid to vapor in evaporators
and vapor to liquid in condensers affects the flow patterns and, consequently, the heat transfer and
pressure drop for the flow. In evaporation on the outside of tubes the phase change takes place at
the surface and the rising bubbles create secondary flow patterns in the fluid. For evaporation
inside tubes, bubbles forming at the wall surface move to the center of the flow, also causing
mixing and secondary current. Condensation on the outside of tubes creates a downward flow of
condensate over the surfaces that promotes mixing. For condensation inside tubes there is a layer
of condensing liquid along the wall surface and a flow of vapor down the center of the tube,
creating a complex flow pattern. The heat transfer coefficient and pressure drop correlations for
evaporation and condensation are empirical and bring in the important parameters. They can be
used as guides to estimate the heat transfer and pressure drop for these heat transfer situations.

SM 7.9 Nomenclature
A
Bo*
cp
cs
C
C*
Cs
D
f
fi

area
modified boiling number
specific heat
equivalent specific heat
capacitance rate, coefficient
capacitance rate ratio
surface coefficient
diameter
friction factor
interfacial roughness factor

F
FFL
FPF
g
G
GT
hc
hfg
hfg
hSP

7.30

fraction of heat exchanger surface


fluid surface parameter
reduced pressure function
gravitational attraction
mass flux
total mass flux
convection heat transfer coefficient
latent heat of vaporization
modified latent heat of vaporization
single phase heat transfer coefficient

hTP
k
Leff
&
m
n
N
Ntu
Ntu*
p
Pr
&
Q

Re
Rp
T
U
U*
V
x
z

two phase heat transfer coefficient


thermal conductivity
effective fin length
mass flow rate
exponent
number of tubes
number of transfer units for heat
transfer
number of transfer units for mass
transfer
pressure
Prandtl number
heat flow rate

L
p

f
*o

thickness of the liquid layer


pressure drop
effectiveness, void fraction
fin efficiency
overall surface mass transfer

efficiency
pressure drop parameter
angle
fluid viscosity
density
ratio of liquid to vapor density
surface tension

heat flux (heat flow rate per unit


area)
Reynolds number based on
hydraulic diameter
roughness
temperature
overall unit thermal conductance
overall unit mass transfer
conductance
velocity
quality
coordinate in flow direction,
location where refrigerant is
saturated

Subscripts
a
air side
D
diameter
DH
hydraulic diameter
eff
effective
eq
equivalent
f
liquid phase, fin
ff
falling film
g
vapor phase
i
inside, inlet
lo
liquid only
o
outside, outlet, reference value
r
refrigerant, refrigerant side
s
surface
sat
saturated conditions
vo
vapor only

film thickness

SM 7.10 References
El Hajal, J,, J. R. Thome, and A. Cavallini, Condensation in Horizontal Tubes, part 1: TwoPhase Flow Pattern Map, International Journal of Heat and Mass Transfer, Vol 46, p33493363, 2003.
Rohsenow, W. M., J. P. Hartnett, and E. N. Ganic', Editors "Handbook of Heat Transfer
Fundamentals", Chapters 11 and 12, McGraw Hill, 1985
Thome, J. R., J. El Hajal, and A. Cavallini, Condensation in Horizontal Tubes, part 2: New Heat
Transfer Model based on Flow Regimes, International Journal of Heat and Mass Transfer,
Vol 46, p3365-3387, 2003.

SM 7.11 Problems
Problems in English Units
7.1 An evaporator is used to chill a liquid water flow rate of 200 gpm that enters at 55 F and
leaves at 45 F. The refrigerant is R-22 that enters at a quality of 0.1 and a temperature of 30
7.31

7.2

7.3

7.4

7.5

7.6

7.7

7.8

F and leaves with 5 F superheat. Determine heat transfer rate, the required overall
conductance, and the refrigerant mass flow rate. Draw some conclusions from your results.
Determine the heat flux and heat transfer coefficient for evaporation from the outside of
tubes in a flooded R-22 evaporator over a range of saturation temperatures between 10 and
50 F using equation 7.8. The surface temperature is always 10 F higher than the saturation
temperature. The surface coefficient Cs is 0.02. Draw some conclusions from your results.
A flooded R-22 evaporator is designed with tubes that are 10 feet long, have an OD of 0.75
inch and an ID of 0.65 inch.. The water flow rate is 1 gpm per tube and the water enters at
60 F. The refrigerant temperature is 30 F. Determine the heat transfer coefficient for the
water side of the evaporator, the heat transfer coefficient for the refrigerant side of the
evaporator, the exchanger effectiveness, and the water outlet temperature. Determine how
many tubes are needed for a cooling capacity of 10 tons. Draw some conclusions from
your results.
Determine the heat transfer coefficient, heat flux, and pressure gradient inside the 0.5-inch
diameter tubes of a DX coil at a location where the quality is 0.4. The refrigerant is R134a, the saturation pressure is 45 psia, the wall temperature is 50 F, the tubes are
aluminum, and the mass flow rate through each tube is 200 lb/hr. Draw some conclusions
from your results.
Determine the heat transfer coefficient, heat flux, and pressure gradient inside the 0.5-inch
diameter copper tubes of a DX coil as a function of quality over the range of 0 to 0.8. The
refrigerant is R-134a, the saturation pressure is 45 psia, the wall temperature is 50 F and the
mass flow rate through each tube is 200 lb/hr. Draw some conclusions from your results.
Estimate the boiling heat flux and heat transfer coefficient inside the 0.5-inch diameter
copper tubes of a DX coil from the entrance (saturated liquid) to the exit (saturated vapor)
at a mass flow rate of 100 lb/hr.. The refrigerant is R-113, the saturation temperature is 35
F, and the wall temperature is 45 F. Estimate the length of tube needed to achieve the
complete phase change and the velocities at the entrance and exit of the tube. Plot the
quality and heat transfer coefficient as functions of distance along the tube. Draw some
conclusions from your results.
A water-cooled R-134a condenser is designed to transfer 200,000 Btu/hr of heat at a
condensing temperature of 105 F. The water flow is designed for an entering temperature
of 90 F and a temperature rise of 10 F. The surface has an overall conductance of 500
Btu/hr-ft2-F. Determine the refrigerant condensing temperature, the water flow rate and the
heat transfer area for the condenser. Draw some conclusions from your results.
A water cooled R-22 condenser is made of 60 unfinned horizontal copper tubes that are 10
feet long. The heat transfer rate is 120,000 Btu/hr. The tube OD is 0.75 inch and the ID is
0.65 inch. The water flow rate is 0.5 gpm per tube and the water enters at 85 F. Determine
the refrigerant saturation temperature, heat transfer coefficient for the water side of the
condenser, heat transfer coefficient for the refrigerant side of the condenser, the condenser

7.32

7.9

7.10

7.11

7.12

7.13

7.14

effectiveness, the water outlet temperature, and the refrigerant flow rate. Draw some
conclusions from your results.
Design a water cooled R-22 condenser with a heat rejection rate of 50,000 Btu/hr made of
unfinned horizontal copper tubes that have an OD of 0.75 inch and an ID of 0.65 inch. The
refrigerant saturation temperature is 95 F and the inlet water temperature is 80 F. Select a
water flow rate, tube length, and number of tubes that will meet the design specifications.
The water flow rate should be between 0.1 and 2 gpm per tube and the tube length should
be between 4 and 10 feet. Draw some conclusions from your results.
For a R-134a condenser made of bare horizontal tubes determine and plot the heat
transfer coefficient duct and the hA product per unit length over the range of saturation
temperatures from 70 to 120 F C for tubes that range in diameter between 0.5 inch and 2
inch in diameter. The surface temperature is always 5 F lower than the saturation
temperature. Draw some conclusions from your results.
Determine the heat transfer coefficient and heat transfer per unit length for R-134a
condensing on horizontal 0.75 in. diameter tubes for bare and finned tubes. The fins are
made of aluminum, are 1.5 in. in diameter and 0.050 in. thick, and have a pitch of 10 fpi.
The saturation temperature of the refrigerant is 95 F and the surface is 90 F. Draw some
conclusions from your results.
Estimate the heat transfer coefficient and pressure gradient for R-134a condensing inside
the tubes of an air-cooled condenser at a position where the quality is 0.5. The flow rate is
20 lbm/hr, the tube diameter is 0.4 inch, the saturation temperature is 100 F, the surface
temperature is 90 F and the interface roughness factor is 1.2. Draw some conclusions from
your results.
Estimate the heat transfer coefficient and pressure gradient for R-134a condensing inside
the tubes of an air-cooled condenser at a position over the range of quality of 1.0 to 0. The
flow rate is 20 lbm/hr, the tube diameter is 0.4 inch, the saturation temperature is 100 F, the
surface temperature is 90 F and the interface roughness factor is 1.2. Draw some
conclusions from your results.
Estimate the tube length required to condense R-134a entering as a vapor and leaving as
liquid. The flow rate is 20 lbm/hr, the tube diameter is 0.4 inch, the saturation temperature
is 100 F, the surface temperature is 90 F and the interface roughness factor is 1.2. Draw
some conclusions from your results.

ProblemsinSIunits
7.15

An evaporator is used to chill a liquid water flow rate of 10 kg/s that enters at 13 C and
leaves at 8 C. The refrigerant is R-22 that enters at a quality of 0.1 and a temperature of 4
C and leaves with 3 C superheat. Determine heat transfer rate, the required overall
conductance, and the refrigerant flow rate. Draw some conclusions from your results.
7.16
Determine the heat flux and heat transfer coefficient for evaporation from the outside of
tubes in a flooded R-22 evaporator over a range of saturation temperatures between 0 and

7.33

7.17

7.18

7.19

7.20

7.21

7.22

7.23

30 C using equation 7.8. The surface temperature is always 5 C higher than the saturation
temperature. The surface coefficient Cs is 0.02. Draw some conclusions from your results.
A flooded R-22 evaporator is designed with tubes that are 2 m long, have an OD of 20
mm and an ID of 17 mm. The water flow rate is 0.05 kg/s per tube and the water enters at
20 C. The refrigerant temperature is 5 C. Determine the heat transfer coefficient for the
water side of the evaporator, the heat transfer coefficient for the refrigerant side of the
evaporator, the exchanger effectiveness, and the water outlet temperature. Determine how
many tubes are needed for a cooling capacity of 30 kW. Draw some conclusions from your
results.
Determine the heat transfer coefficient and pressure gradient inside the 1 cm diameter
copper tubes of a DX coil at a location where the quality is 0.4. The refrigerant is R-134a,
the saturation pressure is 300 kPa, the wall temperature is 10 C, and the mass flow rate
through each tube is 0.03 kg/s. Draw some conclusions from your results.
Determine the heat flux, heat transfer coefficient and pressure gradient inside the 1 cm
diameter copper tubes of a DX coil as a function of location over the range of quality
between 0 and 0.8. The refrigerant is R-134a, the saturation pressure is 300 kPa, the wall
temperature is 10 C, and the mass flow rate through each tube is 0.03 kg/s. Draw some
conclusions from your results.
Estimate the boiling heat flux and heat transfer coefficient inside the 1 cm diameter
copper tubes of a DX coil from the entrance (saturated liquid) to the exit (saturated vapor)
at a mass flow rate of 0.1 kg/s.. The refrigerant is R-113, the saturation temperature is 5 C,
and the wall temperature is 8 C. Estimate the length of tube needed to achieve the
complete phase change and the velocities at the entrance and exit of the tube. Plot the
quality and heat transfer coefficient as functions of distance along the tube. Draw some
conclusions from your results.
A water-cooled R-22 condenser is designed to transfer 50 kW of heat at a condensing
temperature of 45 C. The water flow is designed for an entering temperature of 30 C and a
temperature rise of 5 C. The surface has an overall conductance of 2500 W/m 2-C.
Determine the refrigerant condensing temperature, the water flow rate and the heat transfer
area for the condenser. Draw some conclusions from your results.
A water cooled R-22 condenser is made of 60 unfinned horizontal copper tubes that are 3
m long. The heat transfer rate is 40 kW. The tube OD is 22 mm and the ID is 20 mm. The
water flow rate is 0.05 kg/s per tube and the water enters at 30 C. Determine the refrigerant
saturation temperature, heat transfer coefficient for the water side of the condenser, heat
transfer coefficient for the refrigerant side of the condenser, the condenser effectiveness, the
water outlet temperature, and the refrigerant flow rate. Draw some conclusions from your
results.
Design a water cooled R-22 condenser with a heat rejection rate of 20 kW made of
unfinned horizontal copper tubes that have an OD of 22 mm and an ID of 20 mm. The
refrigerant saturation temperature is 35 C and the inlet water temperature is 20 C. Select a

7.34

7.24

7.25

7.26

7.27

7.28

water flow rate, tube length, and number of tubes that will meet the design specifications.
The water flow rate should be between 0.5 and 5 kg/s per tube and the tube length should
be between 1 and 3 m. Draw some conclusions from your results.
For a R-134a condenser made of bare horizontal tubes determine and plot the heat
transfer coefficient duct and the hA product per unit length over the range of saturation
temperatures from 20 to 60 C for tubes that range in diameter between 10 mm and 5 mm
diameter. The surface temperature is always 3 C lower than the saturation temperature.
Determine the heat transfer coefficient and heat transfer per unit length for R-134a
condensing on horizontal 20 mm diameter tubes for bare and finned tubes. The fins are
made of aluminum, are 40 mm in diameter, 1.5 mm. thick, and have a pitch of 25 fins/cm.
The saturation temperature of the refrigerant is 35 C and the surface is 32 C. Draw some
conclusions from your results.
Estimate the heat transfer coefficient and pressure gradient for R-134a condensing inside
the tubes of an air-cooled condenser at a position where the quality is 0.5. The flow rate is
0.0025 kg/s, the tube diameter is 8 mm, the saturation temperature is 40 C, the surface
temperature is 35 C, and the interface roughness factor is 1.2. Draw some conclusions
from your results.
Estimate the heat transfer coefficient and pressure gradient for R-134a condensing inside
the tubes of an air-cooled condenser at a position over the range of quality of 1.0 to 0. The
flow rate tube is 0.0025 kg/s, the tube diameter is 8 mm, the saturation temperature is 40 C,
the surface temperature is 35 C and the interface roughness factor is 1.2. Draw some
conclusions from your results.
Estimate the tube length required to condense R-134a entering as a vapor and leaving as
liquid. The tube diameter is 8 mm, the flow rate is 0.0025 kg/s, the saturation temperature
is 40 C, the surface temperature is 35 C and the interface roughness factor is 1.2. Draw
some conclusions from your results.

7.35