Susol VCB is full line-up new VCB which has the high
interrupting capacity, large current(~50kA, ~4000A), and
maximized compatibility with existing products through the
dual phases and compact sized models.
Contents
External structure
26
28
31
32
42
Ratings
46
Accessories
56
87
Dimensions
210
Technical data
212
91
Interrupting current
Rated current
7.2kV
8/12.5/20/25/31.5/40/50kA
400/630/1250/2000/3150/4000A
12/17.5kV
20/25/31.5/40/50kA
630/1000/1250/2000/3150/4000A
24kV
12.5/25/31.5/40kA
630/1250/2000/2500/3150A
36kV
25/31.5/40kA
1250/2000/3150A
40.5kV
25/31.5kA
1250/2000/3150A
accessories.
CB compartment structure: Metal isolation structures to prevent the
accident spread and ensure safety. And the convenience of switchgear
building is extended by its module style.
A variety of accessories: UVT, Locking Magnet, Plug Interlock, Key lock,
Temperature Sensor, MOC, TOC, Earthing S/W.
Maximizing compatibility with existing products through the dualistic
deployment of phases and compact models.
Type testing is complete for all models according to latest standard,
IEC62271-100 (2008) [M2, E2 (List1 or 3), C2].
7.2kV (VL-06)
Rated short-time (for withstand current ): 3sec.
Rated operating sequence: O-0.3s-CO-15s-CO
Type test level: M2, E2 (List1), C2
100% Compatibility
- with existing fixed type breakers
- with existing drawout type breakers
Various cradle: E, F and G type
A variety of control power
- DC 24~30V, DC 48~60V, DC 110V, DC 125V, DC 220V
- AC 48V, AC 100~130V, AC 220~250V
A variety of accessories
- Charge switch, UVT, Secondary trip Coil, Current trip coil,
Trip Latch Checking S/W, Position S/W
- Key-lock, Button lock, Button cover, Padlock, UVT, Time Delay
Controller, Lifting hook, CTD
TEST/SERVICE Automatic Position Indicator
Standards and certification
- IEC62271-100 (2008) [M2, C2, E2 (List1)]
- Tested in enclosure
- KERI type tested, V-check (KESCO) certification
Ur
(kV)
Isc
(kA)
Ir
(A)
7.2
8
12.5
400
630
up & Compact
Full line
<<
Susol VCBSeries
7.2/12/17.5/24/25.8kV (VL-06/12/17/20/25)
7.2/12/17.5/24/25.8/36/40.5kV (VH-06/12/17/20/25/36/40)
25
31.5
17.5
20
25
31.5
24, 25.8
12.5
16
25
2000
630
1000
1250
2000
630
1250
2000
2500
630
1250
2000
630
1250
2000
630
1250
2000
2500
630
1250
630
1250
630
1250
2000
2500
17.5
50
24
25
31.5
40
25.8
25
36
25
31.5
40
40.5
25
31.5
3150
4000
1250
2000
2500
3150
2500
1250
2000
3150
1250
2000
3150
1200
2000
1250
2000
3150
1250
2000
3150
1250
2000
3150
1250
2000
3150
1250
2000
3150
E type
F type
H type
Susol
VCB
Breaker
Insulation rod
Lower terminal
Shunt
Vacuum interrupter
Upper terminal
Tulip contactor
Contacts
Fixed
electrode
Fixed
seal cup
Arc shield
Bellows
shield
The vacuum rate within the VI is very high the contacts are made of special alloy (copper(approximately 5x10-5 Torr) and the spacing chromium) and the interior is completely sealed
Ceramic
Bellows
Movable
electrode
Vacuum Interrupter, VI
Movable
seal cup
voltage.
The contacts are in a structure that arc can arc energy by overvoltage or switching can be
easily be extinguished and the surfaces of reduced effectively.
<<
Convenience and
Variety
Maximizing the durability and reliability of
the main circuit contactors
(Stego Tulip contactor)
Strong structure for the temperature rise
(Natural cooling system)
Stego Tulip
Main circuit structure with high reliability
Maximizing the durability and reliability of the main circuit contactors (Stego Tulip contactor)
Strong structure for the temperature rise (Natural cooling system)
Tulip finger
Tulip spring
Plate understar :
Securing freedom of Tulip
Plate star: Supporting Tulip for position maintaing and torsional flow prevention
10
<<
7.2/12/17.5/24/25.8/36/40kV...
(VH-06/12/17/20/25/36/40)
11
CB Compartment
Convenience in building switchgears
CB compartment structure: H type cradle
Metal isolation structure to prevent the accident spread and ensure safety
Convenience of switchgear building
7.2/12/17.5/24/25.8/36/40.5kV 20/25/31.5/40/50kA
Metal isolation structure to prevent the accident spread and ensure safety
Convenience of operation by Truck
- Drawable in the closed position of the switchgear door
- Racking-in/out positions indicated mechanically
Equipped with safety devices and accessories
- Control power connected Interlock
- Earthing S/W and interlock, MOC/TOC (ANSI)
Convenience in building switchgears
- Module assembly with CB compartment
12
<<
LV
Compartment
CB
Compartment
Busbar & Cable
Compartment
Accessories of CB compartment
(H type cradle)
MOC (Mechanism Operated Cell S/W)
PT
Compartment
13
Cradles
E, F, G, K and H type... Variety of the Cradles
F type
E type
E type
14
F type
E type
F type
H type
<<
H type
K type
G type
H type
K type
G type
Premium style cradle with
safety shutter and bushings
For MESG
Applies VL type VCB
VL type
VL type
VL, VH type
15
Convenience
Convenience in building switchgears
- Maximizing compatibility with existing products through the dualistic deployment of phases and compact models.
210
150
150
210
VCB rating
Ur (kV)
Isc (kA)
Ir (A)
12
20/25
31.5
17.5
20/25
31.5
630
1000
1250
630
1250
P150
(distance between phases: 150mm)
150
150
P210
(distance between phases: 210mm)
210
210
VCB rating
Ur (kV)
Isc (kA)
Ir (A)
12
20/25
2000
17.5
20/25
2000
P150
(distance between phases: 150mm)
275
275
VCB rating
Ur (kV)
Isc (kA)
Ir (A)
17.5
31.5
2500
P275
(distance between phases: 275mm)
16
P210
(distance between phases: 210mm)
<<
210
VCB rating
Ur (kV)
Isc (kA)
Ir (A)
24
12.5
630
1250
630
1250
2000
2500 *
630
1250
630
1250
2000
2500 *
16/25
25
25.8
12.5
16/25
25
P210
(distance between phases: 210mm)
275
210
275
P275
(distance between phases: 275mm)
VCB rating
Ur (kV)
Isc (kA)
Ir (A)
24
31.5/40
2000
25.8
31.5/40
2000
P210
(distance between phases: 210mm)
P275
(distance between phases: 275mm)
17
Accessories
A variety of accessories for VL-06
Breaker
Motor
Closing coil
Trip coil
Counter
Auxiliary contacts
UVT coil
18
<<
Cradle
Handle for Racking-in and out
UVT time delay controller
Condenser trip device
19
Accessories
A variety of accessories for VL-06/12/17/20/25
Breaker
Motor
Closing coil
Trip coil
Counter
Auxiliary contacts
UVT coil
Key lock
Button padlock
Button cover
20
Position switch
Handle for Racking-in/out
UVT time delay controller
Condenser trip device (CTD)
MOC
Padlock (H type Door Interlock)
Locking magnet
Plug Interlock
<<
Cradle (H type)
TOC (Truck operated cell s/w)
MOC (Mechanical operated cell s/w)
Temperature sensor
Door
Door interlock
Shutter padlock
21
Accessories
A variety of accessories for VH-06/12/17/20/25/36/40
Breaker
Motor
AC/DC coil rectifier
Trip coil/Closing coil
Secondary trip coil
AC/DC UVT coil rectifier
UVT coil
Latch checking switch
22
<<
Cradle (H type)
MOC (Mechanism operated cell switch)
TOC (Truck operated cell switch)
Shutter padlock
Temperature sensor
Door
Emergency ON/OFF button
23
IEC62271-100 (2002)
274
268
260
274
IEC62271-100 (2008)
130
116
104
72
66
36
15
268
260
130
116
104
72
66
36
15
3
10
30
60 100(sym) 100(asym)
10
Test current
(A, %Short-circuit current)
30
60 100(sym) 100(asym)
Test current
(A, %Short-circuit current)
Arc Energy: List 1 (100%) < List 2 (125%) < List 3 (134%)
134%
125%
100%
E2 List1
E2 List2
E2 List3
E1
24
<<
M2, C2
IEC standards to verify the relibilty of the product allows to select the quality level for the product to be tested
according to its real performance and practical usage. The highest quality level of M2, C2 has been applied to
Susol VCB.
M2
Control Voltage
Number of operations
C-O
85%
500
C-O
100%
500
C-O
110%
500
O - CO - C
100%
250
10,000
10,000
operations
operations
M1
2,000
operations
2,000
operations
C1, C2: Capacitive current breaking test is to verify the probability of restriking and C2 class is secured for all Susol VCB.
C1
C2
25
ON/OFF Indicator
Manual Charging Handle
Back side
26
Key Lock
Operation Counter
TEST/SERVICE
Position Indicator
ON/OFF Indicator
Manual Charging Handle
Key Lock
Operation Counter
TEST/SERVICE
Position Indicator
Back side
27
Manual operation
Manual Charge
a) VL type: operate the charge handle 7-8 times as a fully stroke.
b) VH type: Insert the charge handle into the handle slot first. Rotate the handle clockwise 40 times more and then
charge will be complete with a click sound.
- When the closing spring is charged fully "CHARGED" is displayed at the charge indicator.
Manual closing
a) Pressing the ON button the breaker is closed.
b) With the closing of the breaker "ON" is displayed at Close/Trip indicator and "DISCHARGED" at the charge
indicator.
Manual trip
a) Pressing the OFF button the breaker is opened.
b) "OFF" is displayed at Close/Trip indicator.
Electric operation
Electric charge
The breaker is remotely closing with charging of closing spring.
If the breaker trips the closing spring is automatically charged by gear motors.
Electric closing
Remote closing is operated by the closing coil.
Electric trip
Remote trip can be operated by the trip coil or UVT coil.
Main contacts are operated by the energy of the spring mechanism and closing spring is charged by the motor in the
mechanism.
Breaker is closed by closing coil and tripped by trip coil.
These operations are repeated in VCB as shown in the below sequence chart.
Start closing
Closing signal
Control power ON
Complete closing
Trip(Open) signal
Start opening
Complete
opening
Motor
Closing spring
Opening spring
Closing coil
Opening coil
Main contact
Closing time
28
Opening time
Fixed electrode
Fixed shield
Contacts
Arc shield
Ceramic
Bellows shield
Bellows
An example of oscillogram obtained through the interrupting test using LC resonant circuit
29
Direction of
rotating arc
Columnar arc
Current
30
Susol VCB has been type tested and obtained certifications according to the latest IEC standard at international testing
laboratory and can be installed and applied at the environment and conditions in accordance with the standard.
Standard
- IEC 62271-1 (2007.10)
High-voltage switchgear and controlgear - Part 1: Common specifications.
- IEC 62271-100 (2008.04)
High-voltage switchgear and controlgear - Part 2: Alternating-current circuit breakers.
Test and certification
Test report (KERI)
Test report (KEMA)
31
VL
06
08
04
Version
Phase distance/Compatibility
VL
Susol VCB
06
7.2
Fixed
08
E type drawout
13
12.5
F type drawout
G type drawout
Standard
04
400
Compatible with
06
630
A
B
M1
VL-06E08A04
C1
T1
SA1
U1
UVT
Note5)
M1
DC 110V
T1
DC 110V
U0
Without UVT
M2
DC 220V
T2
DC 220V
U1
DC 110V
M3
DC 125V
T3
DC 125V
U2
DC 220V
M4
DC 24V~30V
T4
DC 24V~30V
U3
DC 125V
M5
DC 48V~60V
T5
DC 48V~60V
U4
DC 24V~30V
M6
AC 48V
T6
AC 48V
U5
DC 48V~60V
M7
AC 100V~130V
T7
AC 100V~130V
U6
AC 48V
M8
AC 200V~250V
T8
AC 200V~250V
U7
AC 100V~130V
T9
U8
AC 200V~250V
C1
DC 110V
SA1
C2
DC 220V
C3
DC 125V
SA3
C4
DC 24V~30V
SA5
C5
DC 48V~60V
SA6
C6
AC 48V
SA7
C7
AC 100V~130V
C8
AC 200V~250V
14 7
3
A type connector, 6a6b
Note5)
Position S/W
Flame
4
A type connector, 4a4b
retardant
A type connector, 6a6b
Position S/W
Note5)
5
(Test: 1a1b, Service: 1a1b)
7
Key lock
Button Padlock
Button cover
Lead wire
Optional
LH
Note)
1. In the case of selecting accessories such as A1(Secondary trip coil), A4(Position S/W
2a2a)and A7(Key lock), A147 is type name in the ordering.
2. Unable to select A1(Secondary Trip coil), U1~U8(UVT)and T9(Current trip coil)
simultaneously.
3. A4(Position S/W 2a2a) and A5(Position S/W 2a2b) can not be selected simultaneously.
4. A8 (Button Padlock) and A9 (Button Cover) can not be selected simultaneously.
5. Maximum number of Auxiliary Contacts available are 5a5b, 5a6b in the case of selecting
A1(Secondary trip coil), U1~U8(UVT).
6. In case of using the existing old type cradle and replacing breaker only please order type
B (Compatible with existing breaker). Compatibille busbars are required for fixed version.
7. If T9(CTC) is selected, in case of adding Secondary trip coil, CTC is also added.
32
Lifting Hook
Cradle
VCL
06
08
06
Version
Phase distance/Compatibility
E type drawout
08
F type drawout
13
12.5
G type drawout
Susol VCB
VCL
Cradle
06
7.2
Standard
04
400
Compatible with
06
630
B
existing cradle Note)
Note) In case of replacing the existing old type VCB with Susol VCB please order type B for cradle and A for breaker.
33
06
VL
Basic model name
VL
Susol VCB
06
12
17
Version
7.2
12
17.5
Fixed
20
Phase distance/Compatibility
20
25
32
20
25
31.5
C1
T1
SB1
U1
DC 110V
T1
DC 110V
U0
Without UVT
M2
DC 220V
T2
DC 220V
U1
DC 110V
M3
DC 125V
T3
DC 125V
U2
DC 220V
M4
DC 24V~30V
T4
DC 24V~30V
U3
DC 125V
M5
DC 48V~60V
T5
DC 48V~60V
U4
DC 24V~30V
M6
AC 48V
T6
AC 48V
U5
DC 48V~60V
M7
AC 100V~130V
T7
AC 100V~130V
U6
AC 48V
M8
AC 200V~250V
T8
AC 200V~250V
U7
AC 100V~130V
T9
U8
AC 200V~250V
Note)
1. If A2 (UVT), A4 (Position S/W 2a2b) and A7 (Keylock) are
C2 DC 220V
selected, A147 is the type name in the ordering.
C3 DC 125V
2. Unable to select A1(Secondary trip coil), U1~U8(UVT)
simultaneously.
C4 DC 24V~30V
3. A3(Position S/W 1a3b), A4(Position S/W 2a2a),
C5 DC 48V~60V
A5(Position S/W 2a2b)can not be selected simultaneously.
4. A8 (Button Padlock) and A9 (Button Cover) can not be
C6 AC 48V
selected simultaneously.
C7 AC 100V~130V
5. When A1 (Secondary Trip coil) is selected the maximum
available auxiliary contacts are 9a9b.
C8 AC 200V~250V
6. When A2(Secondary trip coil with TCS Contact) is
selected the maximum available auxiliary contacts are 4a3b, 9a8b.
7. AC (Plug interlock), AD (H type Door interlock), AE (MOC) and AF (Locking magnet) are
available only for H type.
8. In case of B-type connector the flame retardant wire is applicable to auxiliary contacts
4a4b, not to 10a10b.
9. A/B-type connector is applicable to P/E/F/G/K type and B-type connector to H type.
10. Lead wire special color (blue) is applicable to A-type connector.
11. When the position switch is selected from accessories, auxiliary contacts and wiring assy
can be selected as option A/B-type (P/E/F/G/K-type) or B-type(H-type) connector
12. Locking magnet of H type breaker use the same control power supply as motor.
13. Flame retardant type blue wire is not available.
14. When current Trip Coil AV(CTC 1A) or AW(CTC 5A) is selected, A1(Secondary Trip Coil),
U1~U8(UVT) cannot be selected simultaneously and the maximum auxiliary contact is 4a4b.
SA4
SB4
SA6
SA8
SB6
Flame
retardant
14 7
630
1250
2000
2500
UVT
M1
C1
06
13
20
25
M1
150mm
210mm
275mm
Compatible with
existing products
compatible with K
Pro-MEC G/T(T)
VL-06H20A06
A
B
D
06
Optional
CTD1 Condenser Trip Device (AC 110V)
CTD2 Condenser Trip Device (AC 220V)
UDC1 UVT Time Delay Controller (AC/DC 110V)
UDC2 UVT Time Delay Controller (AC/DC 220V)
UDC3 UVT Time Delay Controller (AC/DC 48V)
CTU Coil Test Unit
1
2
3
4
5
7
8
9
A
B
C
D
E
F
G
J
O
V
W
34
Cradle
06
VCL
Basic model name
20
06
7.2
20
20
06
630
Cradle
12
12
25
25
13
1250
17
17.5
32
31.5
20
2000
25
2500
Version
P
Fixed
K
H
Phase distance/Compatibility
A
B
D
F
K
14 7
Susol VCB
06
VCL
150mm
210mm
275mm
Compatible with
existing products
compatible with K
Pro-MEC G/T(T)
Other accessories
1
2
Shutter padlock
Door
Door Interlock
M
Note) 1.These accessories for cradle and TM can be applied only to H type.
2. AJ and AK can not be selected without door (AH).
3. TM (Temperature Monitoring) should be used with AL (Temperature Sensor).
4. H type lead wire - one of AM, AN or AO is required for cradle in case of H type breaker.
5. Unable to select AK at the cradle in the case of selecting A8(Button Padlock), A9(Button Cover) for body of H-type.
6. When Earthing Switch(A1) is selected, Keylock(A5) is included as standard.
N
X
Optional
TM
Temperature Monitoring
35
20
VL
Basic model name
VL
Susol VCB
Version
13
Phase distance/Compatibility
20
24
Fixed
13
12.5
25
25.8
16
16
25
25
630
265mm
13
1250
275mm
20
2000
25
2500
Enclosed type,
Tulip Contact
M1
VL-20H13A06
210mm
C1
T1
SB1
U1
14 7
UVT
M1
DC 110V
T1
DC 110V
U0
Without UVT
M2
DC 220V
T2
DC 220V
U1
DC 110V
M3
DC 125V
T3
DC 125V
U2
DC 220V
M4
DC 24V~30V
T4
DC 24V~30V
U3
DC 125V
M5
DC 48V~60V
T5
DC 48V~60V
U4
DC 24V~30V
M6
AC 48V
T6
AC 48V
U5
DC 48V~60V
M7
AC 100V~130V
T7
AC 100V~130V
U6
AC 48V
M8
AC 200V~250V
T8
AC 200V~250V
U7
AC 100V~130V
T9
U8
AC 200V~250V
06
C1
DC 110V
SA2
C2
DC 220V
SA4
Note)
1. If A2 (UVT), A4 (Position S/W 2a2b) and A7 (Keylock) are
C3 DC 125V
selected, A147 is the type name in the ordering.
C4 DC 24V~30V
2. Unable to select A1(Secondary trip coil), U1~U8(UVT)
simultaneously.
C5 DC 48V~60V
3. A3(Position S/W 1a3b), A4(Position S/W 2a2a),
A5(Position S/W 2a2b)can not be selected simultaneously.
C6 AC 48V
4. A8 (Button Padlock) and A9 (Button Cover) can not be
selected simultaneously.
C7 AC 100V~130V
5. When A1 (Secondary Trip coil) is selected the maximum
C8 AC 200V~250V
available auxiliary contacts are 9a9b.
6. When A2(Secondary trip coil with TCS Contact) is
selected the maximum available auxiliary contacts are 4a3b, 9a8b.
7. AC (Plug interlock), AD (H type Door interlock), AE (MOC) and AF (Locking magnet) are
available only for H type.
8. In case of B-type connector the flame retardant wire is applicable to auxiliary contacts
4a4b, not to 10a10b.
9. A/B-type connector is applicable to P/E/F/G type and B-type connector to H type.
10. Lead wire special color (blue) is applicable to A-type connector.
11. When the position switch is selected from accessories, auxiliary contacts and wiring assy
can be selected as option A/B-type (P/E/F/G/K-type) or B-type(H-type) connector
12. Locking magnet of H type breaker use the same control power supply as motor.
13. Flame retardant type blue wire is not available.
14. When current Trip Coil AV(CTC 1A) or AW(CTC 5A) is selected, A1(Secondary Trip Coil),
U1~U8(UVT) cannot be selected simultaneously and the maximum auxiliary contact is 4a4b.
Standard
SB2
SB4
SA6
SA8
SB6
Optional
CTD1 Condenser Trip Device (AC 110V)
CTD2 Condenser Trip Device (AC 220V)
Key lock
Button Padlock
Button Cover
Lead Wire
Plug Interlock
Locking Magnet
CT operated coil 1A
CT operated coil 5A
36
Cradle
VCL
20
13
20
24
13
12.5
06
630
Cradle
25
25.8
16
16
13
1250
25
25
20
2000
25
2500
Version
E type drawout
210mm
F type drawout
265mm
G type drawout
275mm
Phase distance/Compatibility
14 7
Susol VCB
VCL
06
Enclosed type,
Tulip Contact
Note) 1.These accessories for cradle and TM can be applied only to H type.
2. AJ and AK can not be selected without door (AH).
3. TM (Temperature Monitoring) should be used with AL (Temperature Sensor).
4. H type lead wire - one of AM, AN or AO is required for cradle in case of H type breaker.
5. Accessary A2~AQ is available to H-type. Exceptionally K-type is available to A1.
(Position S/W 4a4b is basic option of A1)
6. Unable to select AK at the cradle in the case of selecting A8(Button Padlock), A9(Button
Cover) for body of H-type.
7. When Earthing Switch(A1) is selected, Keylock(A5) is included as standard.
Shutter padlock
Door
Door Interlock
M
(Flame retardant wire)
H type Lead wire 10a10b
N
(Flame retardant wire)
H type Lead wire 4a4b
O
(Rated short time current)
Optional
TM
Temperature Monitoring
37
06
LVB
Susol VCB
7.2
12
40
40
12
40
20
2000A
2E
3150A
2G
2H
00
Dummy VCB
32
Susol
Control voltage
1A
DC110V
B1
E type drawout
1B
DC220V
F type drawout
1C
DC48V
B2
B6
User
s Plug(Part)
C1
Button Padlock(ON)
C2
Button Padlock(OFF)
G type drawout
1E
DC125V
1L
AC220V
(for MESG)+T2
1M
AC110V
C3
Button Padlock(ON,OFF)
1N
AC48V
D1
Button Cover(ON)
00
Dummy VCB
D2
Button Cover(OFF)
D3
Note)
1. H(Secondary trip coil) and V(UVT) can not be selected simultaneously.
2. B(Position S/W 2a2a), B1(Position S/W 2a2b) and B2(Position S/W 1a3b) can not be
selected simultaneously.
However, only B(Position S/W 2a2a) is available for G/T type(MCSG drawable type)
3. If V(UVT) is selected , additional K(Latch checking S/W) is not allowed.
(Because if UVT is slected a latch checking S/W is included as standard for electrical
interlocking )
4. One out of T and T2 should be selected for G/T type(MCSG drawable type).
T2 is the standard and T (Product before Earthing S/W interlock change) is suitable for
compatibility with existing products.
5. In case of T(Tulip contact, closed type) 3150A is available only for open type housing .
6. Only G/T type is available for 12kV.
38
BB6GT2
1250A
2B
1A
12
Model version
Version
Fixed
12
31.5
Keylock
P1
P2
Padlock
T2
UVT
Cradle
06
LCL
Pro-MEC
06
7.2
Cradle
12
12
LCL
40
BCDT2
12
31.5
12
1250A
40
40
20
2000A
32
3150A
Model version
Version
D
Pro-MEC
Fixed
E type drawout
F type drawout
G type drawout
T2
(for MESG)+T2
T3
U1
Note1)
Note) 1. One out of T, T2 and T3 should be selected for G/T type(MCSG drawable type).
T2 is the standard and T (Product before Earthing S/W interlock change)
is suitable for compatibility with existing products.
T3 is available only for 1250/2000A.
2. U1(Reduced height type) and B(Earthing S/W) can not be selected simultaneously.
39
VH
06
50
13
Version
Phase distance/Compatibility
VH
Susol VCB
06
7.2
Fixed
25
25
150mm
12
1200A
12
12
32
31.5
210mm
13
1250A
17
17.5
40
40
275mm
20
2000A
20
24
50
50
300mm
25
2500A
25
25.8
30
3000A
36
36
32
3150A
40
40.5
40
4000A
M1
VH-06H50B32
C1
Note)
Note)
1. 25kA is for 24/36/40.5kV
2. 31.5kA is for 24/36/40.5kV
3. 40kA is for
7.2/12/17.5/24/36kV
4. 50kA is for 7.2/12/17.5kV
T1
SB2
U1
14 7
UVT
M1
DC 110V
T1
DC110V
U0
Without UVT
M2
DC 220V
T2
DC220V
U1
DC 110V
M3
DC 125V
T3
DC125V
U2
DC 220V
M5
DC 48V
T5
DC48V
U3
DC 125V
M6
AC 48V
T6
AC 48V
U5
DC 48V
M7
AC 110V
T7
AC 110V
U6
AC 48V
M8
AC 220V
T8
AC 220V
U7
AC 110V
U8
AC 220
C1
DC 110V
SA2
C2
DC 220V
SA4
SB2
SB4
SA6
Keylock
Button Padlock
Note)
C3 DC 125V
1. If A1(Secondary trip coil), A4(Position S/W 2a2a),
A7(Keylock)are selected, A147 is the type name in the
C5 DC 48V
ordering.
2. A1(Secondary trip coil), U1~U8(UVT) can not be selected
C6 AC 48V
simultaneously.
C7 AC 110V
3. A3(Position S/W 1a3b), A4(Position S/W 2a2a),
A5(Position S/W 2a2b) can not be selected simultaneously.
C8 AC 220V
4. A8 (Button Padlock) and A9 (Button Cover) can not be
selected simultaneously.
5. AC (Plug interlock), AD (H type Door interlock), AE (MOC) and AF (Locking magnet) are
available only for H type.
6. In case of B-type connector the flame retardant wire is applicable to auxiliary contacts
4a4b, not to 10a10b.
7. A-type connector is applicable to P/E/F/G type and B-type connector to H type.
8. Lead Wire Special Color(blue) is available only for A type connector and the flame
retardant is not applicable to it.
9. Locking magnet can be applied only to H type VCB - breaker and cradle.
10. Locking magnet of H type breaker use the same control power supply as motor.
11. In case of selecting UVT A6 (Latch checking S/W) is not allowed. A6 (Latch checking
S/W) is installed by default to make electrical interlock with UVT.
12. Lead wire is enclosed in the breaker in case of ordering fixed type or H type
breaker without cradle, installed of cradle in case of ordering the breaker with
cradle. If user plug is selected it will be enclosed in the breaker.
13. AG(ANSI type Charge interlock) is available only for H type and the cradle option AQ
should be selected accordingly.
14. 7.2/12kV 31.5kA type: VL Series available
Standard
SA8
SB6
Flame
retardant
Optional
CTD1 Condenser Trip Device(AC 110V)
CTD2 Condenser Trip Device(AC 220V)
UDC1 UVT Time Delay Controller(AC/DC 110V)
Button Cover
Lead Wire
User Plug(Part)
Plug Interlock
Locking Magnet
40
Cradle
06
VCL
Basic model name
25
13
Rated current (A)
Susol VCB
06
7.2
25
25
12
1200A
Cradle
12
12
32
31.5
13
1250A
17
17.5
40
40
20
2000A
20
24
50
50
25
2500A
25
25.8
30
3000A
36
36
32
3150A
40
40.5
40
4000A
VCL
Version
E
Phase distance/Compatibility
A
150mm
210mm
275mm
300mm
14 7
Rotated bushing
F
type
(210mm)
Note) 1. Cradle accessories and the option TM are available only for H type(MCSG drawable type)
A1 for K type. (If A1 is selected, Position S/W 4a4b is included as standard)
2. AJ and AK can not be selected without door (AH).
3. TM (Temperature Monitoring) should be used with AL (Temperature Sensor).
4. H type lead wire - one of AM, AN or AO is required for cradle in case of H type breaker.
5. If AQ(ANSI type Charge interlock) is selected, the breaker option AG should be selected
accordingly.
6. If the H type breaker options A8(Button Padlock) and A9(Button Cover) are slected, the
cradle option AK(Door Emergency Push Button) is not available.
7. When Earthing Switch(A1) is selected, Keylock(A5) is included as standard.
Shutter padlock
Door
Door Interlock
Temperature Sensor
H type Lead wire 4a4b
M
(Flame retardant wire)
H type Lead wire 10a10b
N
(Flame retardant wire)
H type Lead wire 4a4b
O
(Rated short time current)
Q
Optional
TM
Temperature Monitoring
41
Isc
[kA]
p=130
400
12.5
7.2
p=150
Ir[A]
p=210
VCB
p=275
630
630
1250
2000
630
1250
2000
630
1250
2000
630
1250
2000
20
25
31.5
630
1250
2000
630
1250
20
630
1250
2000
12
630
1250
2000
630
1250
25
630
1250
630
1250
31.5
2000
2000
2500
2500
630
1250
2000
630
1250
2000
630
1250
20
17.5
630
1250
2000
25
630
1250
2000
630
1250
42
CRADLE
Connector
Type
Version
Type
Version
VL-0608A04
P,E,F,G
VCL-0608A04
E,F,G
VL-0608B04
P,E,F,G
VCL-0608B04
E,F,G
VL-0613A06
P,E,F,G
VCL-0613A06
E,F,G
VL-0613B06
VL-0620A06
VL-0620A13
VL-0620A20
VL-0625A06
VL-0625A13
VL-0625A20
VL-0632A06
VL-0632A13
VL-0632A20
VL-12H20A06
VL-12H20A13
VL-12H20A20
VL-1220B06
VL-1220B13
VL-1220B20
VL-1220F06
VL-1220F13
VL-12H25A06
VL-12H25A13
VL-12H25A20
VL-1225B06
VL-1225B13
VL-1225B20
VL-1225F06
VL-1225F13
VL-1232A06
VL-1232A13
VL-1232B06
VL-1232B13
VL-1232A20
VL-1232B20
VL-1232B25
VL-1232D25
VL-17H20A06
VL-17H20A13
VL-17H20A20
VL-1720B06
VL-1720B13
VL-1720B20
VL-1720F06
VL-1720F13
VL-17H25A06
VL-17H25A13
VL-17H25A20
VL-1725B06
VL-1725B13
VL-1725B20
VL-1725F06
VL-1725F13
P,E,F,G
P,E,F,G,H
P,E,F,G,H
P,E,F,G,H
P,E,F,G,H
P,E,F,G,H
P,E,F,G,H
P,H
P,E,F,G,K,H
P,E,F,G,K,H
P,H
P,H
P,H
P,E,F,H
P,E,F,H
P,E,F,H
E,F
E,F
P,H
P,H
P,H
P,E,F,H
P,E,F,H
P,E,F,H
E,F
E,F
P,H
P,K,H
P,H
P,H
K,H
P,H
P,H
P,H
H
H
H
P,E,F,H
P,E,F,H
P,E,F,H
E,F
E,F
H
H
H
P,E,F,H
P,E,F,H
P,E,F,H
E,F
E,F
VCL-0613B06
VCL-0620A06
VCL-0620A13
VCL-0620A20
VCL-0625A06
VCL-0625A13
VCL-0625A20
VCL-06H32A06
VCL-0632A13
VCL-0632A20
VCL-12H20A06
VCL-12H20A13
VCL-12H20A20
VCL-1220B06
VCL-1220B13
VCL-1220B20
VCL-1220F06
VCL-1220F13
VCL-12H25A06
VCL-12H25A13
VCL-12H25A20
VCL-1225B06
VCL-1225B13
VCL-1225B20
VCL-1225F06
VCL-1225F13
VCL-12H32A06
VCL-1232A13
VCL-12H32B06
VCL-12H32B13
VCL-1232A20
VCL-12H32B20
VCL-12H32B25
VCL-12H32D25
VCL-17H20A06
VCL-17H20A13
VCL-17H20A20
VCL-1720B06
VCL-1720B13
VCL-1720B20
VCL-1720F06
VCL-1720F13
VCL-17H25A06
VCL-17H25A13
VCL-17H25A20
VCL-1725B06
VCL-1725B13
VCL-1725B20
VCL-1725F06
VCL-1725F13
E,F,G
E,F,G,H
E,F,G,H
E,F,G,H
E,F,G,H
E,F,G,H
E,F,G,H
H
E,F,G,K,H
E,F,G,K,H
H
H
H
E,F,H
E,F,H
E,F,H
E,F
E,F
H
H
H
E,F,H
E,F,H
E,F,H
E,F
E,F
H
K,H
H
H
K,H
H
H
H
H
H
H
E,F,H
E,F,H
E,F,H
E,F
E,F
H
H
H
E,F,H
E,F,H
E,F,H
E,F
E,F
P,E,F,G:A/B, H:B
B
A,B
A,B
B
B
B
P,E,F:A/B, H:B
A
A
B
B
B
P,E,F:A/B, H:B
A
A
B
B
B
B
A,B
B
B
B
B
B
B
P,E,F:A/B, H:B
A
A
B
B
B
P,E,F:A/B, H:B
A
A
Ur
[kV]
17.5
Isc
[kA]
31.5
p=150
p=210
630
1250
Ir[A]
p=265
p=275
2000
2000
2500
2500
630
630
12.5
630
1250
1250
1250
630
630
16
630
1250
24
1250
1250
630
630
630
1250
25
1250
1250
2000
2000
2500
630
630
12.5
630
1250
1250
1250
630
630
16
630
1250
25.8
1250
1250
630
630
630
1250
25
1250
1250
2000
2000
2500
VCB
Type
VL-1732B06
VL-1732B13
VL-1732A20
VL-1732B20
VL-1732B25
VL-1732D25
VL-2013B06
VL-2013F06
VL-20H13D06
VL-2013B13
VL-2013F13
VL-20H13D13
VL-2016B06
VL-2016F06
VL-20H16D06
VL-2016B13
VL-2016F13
VL-20H16D13
VL-2025B06
VL-2025F06
VL-20H25D06
VL-2025B13
VL-2025F13
VL-20H25D13
VL-2025F20
VL-20H25D20
VL-20H25D25
VL-2513B06
VL-2513F06
VL-25H13D06
VL-2513B13
VL-2513F13
VL-25H13D13
VL-2516B06
VL-2516F06
VL-25H16D06
VL-2516B13
VL-2516F13
VL-25H16D13
VL-2525B06
VL-2525F06
VL-25H25D06
VL-2525B13
VL-2525F13
VL-25H25D13
VL-2525F20
VL-25H25D20
VL-25H25D25
Version
P,H
P,H
H
P,H
P,H
P,H
K,H
P,E,F,G,K
H
K,H
P,E,F,G,K
H
K,H
P,E,F,G,K
H
K,H
P,E,F,G,K
H
K,H
P,E,F,G,K
H
K,H
P,E,F,G,K
H
P,E,F,G,K
H
H
K,H
P,E,F,G,K
H
K,H
P,E,F,G,K
H
K,H
P,E,F,G,K
H
K,H
P,E,F,G,K
H
K,H
P,E,F,G,K
H
K,H
P,E,F,G,K
H
P,E,F,G,K
H
H
CRADLE
Type
VCL-17H32B06
VCL-17H32B13
VCL-17H32A20
VCL-17H32B20
VCL-17H32B25
VCL-17H32D25
VCL-2013B06
VCL-2013F06
VCL-20H13D06
VCL-2013B13
VCL-2013F13
VCL-20H13D13
VCL-2016B06
VCL-2016F06
VCL-20H16D06
VCL-2016B13
VCL-2016F13
VCL-20H16D13
VCL-2025B06
VCL-2025F06
VCL-20H25D06
VCL-2025B13
VCL-2025F13
VCL-20H25D13
VCL-2025F20
VCL-20H25D20
VCL-20H25D25-AS
VCL-2513B06
VCL-2513F06
VCL-25H13D06
VCL-2513B13
VCL-2513F13
VCL-25H13D13
VCL-2516B06
VCL-2516F06
VCL-25H16D06
VCL-2516B13
VCL-2516F13
VCL-25H16D13
VCL-2525B06
VCL-2525F06
VCL-25H25D06
VCL-2525B13
VCL-2525F13
VCL-25H25D13
VCL-2525F20
VCL-25H25D20
VCL-25H25D25-AS
Version
H
H
H
H
H
H
K,H
E,F,G,K
H
K,H
E,F,G,K
H
K,H
E,F,G,K
H
K,H
E,F,G,K
H
K,H
E,F,G,K
H
K,H
E,F,G,K
H
E,F,G,K
H
H
K,H
E,F,G,K
H
K,H
E,F,G,K
H
K,H
E,F,G,K
H
K,H
E,F,G,K
H
K,H
E,F,G,K
H
K,H
E,F,G,K
H
E,F,G,K
H
H
Connector
B
B
B
B
B
B
A,B
A,B
B
A,B
A,B
B
A,B
A,B
B
A,B
A,B
B
A,B
A,B
B
A,B
A,B
B
A,B
B
B
A,B
A,B
B
A,B
A,B
B
A,B
A,B
B
A,B
A,B
B
A,B
A,B
B
A,B
A,B
B
A,B
B
B
43
Isc
[kV]
[kA]
Ir[A]
p=150
31.5
p=210
p=275
3150
1250
40
2000
3150
7.2
4000
1250
2000
50
31.5
40
VCL-0632B32
E,F,G
LCL-06G-32D/30-T2
G/T
LVB-06-40L/12
P,E,F,G,G/T
LCL-06G-40D/12-T2
G/T
A,B
LVB-06-40L/20
P,E,F,G,G/T
LCL-06G-40D/20-T2
G/T
A,B
LVB-06-40L/30
P,E,F,G/T
LCL-06G-40D/30-T2
G/T
A,B
VH-0640D40
P,H
VCL-06K40D40
VH-0650B13
P,H
VCL-06H50B13
A,B
VCL-06H50B20
3150
VH-0650D32
P,H
VCL-06H50D32
4000
VH-0650D40
P,H
VCL-06K50D40
LVB-12G-32L/30-T2
G/T
LCL-12G-32D/30-T2
G/T
A,B
LVB-12G-40L/12-T2
G/T
LCL-12G-40D/12-T2
G/T
A,B
2000
LVB-12G-40L/20-T2
G/T
LCL-12G-40D/20-T2
G/T
A,B
LVB-12G-40L/30-T2
G/T
LCL-12G-40D/30-T2
G/T
A,B
3150
VH-1240D40
P,H
VCL-12K40D40
VH-1250B13
P,H
VCL-12H50B13
VH-1250B20
P,H
VCL-12H50B20
2500
VH-1250D25
P,H
VCL-12H50D25
3150
VH-1250D32
P,H
VCL-12H50D32
4000
VH-1250D40
P,H
VCL-12K50D40
VH-1750B13
P,H
VCL-17H50B13
2000
VH-1750B20
P,H
VCL-17H50B20
VH-1750D25
P,H
VCL-17H50D25
3150
VH-1750D32
P,H
VCL-17H50D32
2500
VH-2025D25
P,H
VCL-20H25D25
VCL-20H32B13
B
B
2500
VH-2032B13
2000
24
P,H
VH-2032B20
P,H
VCL-20H32F13
VCL-20H32B20
VCL-20H32F20
1250
VH-2032D13
P,H
VCL-20H32D13
2000
VH-2032D20
P,H
VCL-20H32D20
3150
VH-2032D32
P,H
VCL-20H32D32
VCL-20H40B13
VCL-20H40F13
1250
VH-2040B13
P,H
2000
VH-2040B20
P,H
VCL-20H40B20
VCL-20H40F20
1250
VH-2040D13
P,H
VCL-20H40D13
2000
VH-2040D20
P,H
VCL-20H40D20
3150
VH-2040D32
P,H
VCL-20H40D32
2500
VH-2525D25
P,H
VCL-25H25D25
1250
VH-2532B13
P,H
2000
VH-2532B20
P,H
25
44
P,E,F,G
P,E,F,G/T
VCL-06H50D25
1250
31.5
VH-0632B32
LVB-06-32L/30
P,H
3150
25
25.8
Connector
P,H
1250
40
Version
VH-0650B20
2000
31.5
Type
VH-0650D25
1250
50
CRADLE
Version
1250
50
17.5
Type
2500
4000
12
VCB
p=300
VCL-25H32B13
VCL-25H32F13
VCL-25H32B20
VCL-25H32F20
1250
VH-2532D13
P,H
VCL-25H32D13
2000
VH-2532D20
P,H
VCL-25H32D20
3150
VH-2532D32
P,H
VCL-25H32D32
Ur
Isc
[kV]
[kA]
25.8
27
40
25
25
36
31.5
40
25
40.5
31.5
Ir[A]
p=150
p=210
VCB
p=275
p=300
CRADLE
Type
Version
1250
VH-2540B13
P,H
2000
VH-2540B20
P,H
1250
VH-2540D13
2000
VH-2540D20
3150
Type
Connector
Version
VCL-25H40B13
VCL-25H40F13
VCL-25H40B20
VCL-25H40F20
P,H
VCL-25H40D13
P,H
VCL-25H40D20
VH-2540D32
P,H
VCL-25H40D32
1200
VH-2725E12
P,H
VCL-27H25E12
2000
VH-2725E20
P,H
VCL-27H25E20
1250
VH-3625E13
P,H
VCL-36H25E13
2000
VH-3625E20
P,H
VCL-36H25E20
3150
VH-3625E32
P,H
VCL-36H25E32
1250
VH-3632E13
P,H
VCL-36H32E13
2000
VH-3632E20
P,H
VCL-36H32E20
3150
VH-3632E32
P,H
VCL-36H32E32
1250
VH-3640E13
P,H
VCL-36H40E13
2000
VH-3640E20
P,H
VCL-36H40E20
3150
VH-3640E32
P,H
VCL-36H40E32
1250
VH-4025E13
P,H
2000
VH-4025E20
P,H
3150
VH-4025E32
P,H
1250
VH-4032E13
P,H
2000
VH-4032E20
P,H
3150
VH-4032E32
P,H
45
VL-06 0804
Item
Rated voltage
Ur (kV)
Ir (A)
Rated frequency
7.2
400
fr (Hz)
Isc (kA)
VL-0613 06
630
50/60
12.5
Ik/tk (kA/s)
8/3
12.5/3
(MVA)
100
160
Ip (kA)
(cycle)
Rated withstand
Ud (kV)
20
voltage
Impulse (1.250)
Up (kV)
60
O-0.3s-CO-15s-CO
Closing coil
(V)
Trip coil
(V)
Auxiliary contacts
(sec)
0.04
(sec)
0.06
Mechanical
M2
Electrical
E2 (List1)
C2
Fixed
P type
Drawout
Phase distance
Weight
Dimensions
Standards
46
130
(kg)
37
37
(kg)
18, 25, 32
19, 26, 33
Page 91~92
Page 92~93
IEC 62271-100 (2008), KS C 4611, JEC 2300/JIS C 4603, V-check (KESCO)
Item
Rated voltage
Ur (kV)
Ir (A)
Rated frequency
Rated short-circuit current
Rated short-time withstand current
7.2
630
1250
12
2000
630
17.5
1250
fr (Hz)
50/60
Isc (kA)
20, 25
Ik/tk (kA/s)
2000
630
1250
20/3, 25/3
(MVA)
Ip (kA)
(cycle)
250/310
410/520
600/750
Rated withstand
Ud (kV)
20
28 (42) Note1)
38
voltage
Impulse (1.250)
Up (kV)
60
75 (82) Note1)
95
O-0.3s-CO-15s-CO
Closing coil
(V)
Trip coil
(V)
Auxiliary contacts
4a4b, 10a10b
(sec)
0.04
(sec)
0.06
Mechanical
M2
Electrical
E2 (List3)
C2
Fixed
P type
Drawout
Phase distance **
Weight
Dimensions
2000
150
150 (210)
150 (210)
(kg)
100
100
130
115 (120)
115 (120)
130 (140)
115 (120)
115 (120)
130 (140)
(kg)
170
170
180
170 (200)
170 (200)
180 (200)
170 (200)
170 (200)
180 (200)
Page 94~103
Page 94~103
Page 94~103
Page 94~103
Page 94~103
Page 94~103
Cradle (H type)
Page 94~103
Page 94~103
Page 94~103
Standards
47
VL-063206/13/20
Item
Rated voltage
Ur (kV)
Ir (A)
Rated frequency
630
1250
2000
630
Isc (kA)
(MVA)
Ip (kA)
1250
2000
393
655
(cycle)
2500
955
voltage
Impulse (1.250)
Up (kV)
60
28 (42) Note2)
38
75
95
O-0.3s-CO-3min-CO
Closing coil
(V)
Trip coil
(V)
Auxiliary contacts
4a4b, 10a10b
(sec)
0.04
(sec)
0.06
Mechanical
M2
Electrical
E2 (List 3)
C2
Fixed
P type
Drawout
Phase distance **
150
H type
(for MCSG)
210 (275)
150 (210)
210 (275)
Breaker (H type)
(kg)
100
100
130
160/175 115/120
Cradle (H type)
(kg)
170
170
200
260/290 170/200
(kg)
85
85
100
85/100
120/135
85/100
Standards
* H type is a box type cradle with CB compartment style structure.
** ( ) displays option of phase distance.
Note1) For Icw 4s, please contact us.
2) Contact us.
48
2000
3
20
Dimensions
1250
Ud (kV)
Weight
630
31.5
Installation version *
2500
31.5/3 (4Note1))
Rated withstand
17.5
50/60
Ik/tk (kA/s)
VL-173206/13/20/25
12
fr (Hz)
Control voltage
VL-123206/13/20/25
7.2
85/100
100/115
85/100
Page 135~148
Page 135~148
IEC 62271-100 (2008), KERI, V-check (KESCO)
100/115 120/135
VL-20,251306/13 VL-20,251606/13
Item
Rated voltage
Ur (kV)
Ir (A)
Rated frequency
630
1250
630
1250
630
fr (Hz)
Isc (kA)
(MVA)
Ip (kA)
12.5
16
12.5/3 Note1)
520/560
665/715
1040/1120
(cycle)
Ud (kV)
50/60
voltage
Impulse (1.250)
Up (kV)
125
O-0.3s-CO-3min-CO
Closing coil
(V)
Trip coil
(V)
Auxiliary contacts
4a4b, 10a10b
(sec)
0.04
(sec)
0.06
Mechanical
M2
Electrical
E2 (List 3)
C2
Fixed
P type
Drawout
Phase distance **
Weight
Dimensions
2500
25/3 Note1)
2000
25
16/3 Note1)
Rated withstand
Control voltage
1250
50/60
Ik/tk (kA/s)
VL-20,252506/13/20/25
24/25.8
(mm)
Breaker (H type)
H type
(for MCSG)
(kg)
Cradle (H type)
(kg)
(kg)
120 (130)
200 (220)
110
275
130 (140)
150 (160)
200 (220)
115
120
200 (220)
135
Page 149~158
Page 159~165
Page 165~169
Page 170~172
Page 170~172
Page 170~172
Cradle (H type)
Page 173~177
Page 173~177
Page 173~177
Standards
49
LVB-06/12
-32
32 LVB-06
-40
12, 20, 32 LVB-12
-32
32 LVB-12
-40
12, 20, 32
LVB-06
Item
Rated voltage
Ur (kV)
Ir (A)
Rated frequency
7.2
7.2
3150 *
1250
12
3150 *
2000
fr (Hz)
Isc (kA)
Ik/tk (kA/s)
(MVA)
Ip (kA)
(Cycle)
12
3150 *
1250
40
31.5
40
31.5/3
40/3
31.5/3
40/3
393
499
393
499
Ud (kV)
20
28
voltage
Impulse (1.250)
Up (kV)
60
75
O-0.3s-CO-3min-CO
Closing coil
(V)
Trip coil
(V)
Auxiliary contacts
4a4b, 10a10b
(sec)
0.04
(sec)
0.06
Mechanical
M2
Electrical
E2 (List1)
C2
Fixed
P type
Drawout *
Phase distance
Weight
Dimensions
Standards
MCSG Cradle
(mm)
210
210
(kg)
210, 220
135, 160
135, 160
210, 220
220
164
165
220
(kg)
135, 155
55, 110
63, 117
135, 155
155
110
117
155
210
150
210
Page 182~183
Page 178~179
Page 182~183
Page 182~183
Page 178~179
Page 182~183
Page 184~185
Page 180~181
Page 184~185
Page 184~186
Page 180~181
Page 184~186
* MCSG style drawable type provide a cradle for builting in the switchgear, not a box type for CB compartment. Ordering type is LVB.
Note 1) H type that is a box type cradle for enabling a CB compartment in MCSG is under development. Consult us for ordering.
2) Some LVB is the ordering name of the switchboard for export
50
3150 *
50/60
31.5
Rated withstand
Control voltage
2000
VH-065013/20/25/32
Item
Rated voltage
Ur (kV)
Ir (A)
Rated frequency
Rated short-circuit current
Rated short-time withstand current
VH-125013/20/25/32
7.2
1250
2000
12
2500
3150
1250
2000
fr (Hz)
60
50
Ik/tk (kA/s)
(MVA)
Ip (kA)
(cycle)
17.5
2500
Isc (kA)
VH-175013/20/25/32
3150
1250
2000
2500
50/3
623
1039
1515
2.6Isc (60Hz)
3
Rated withstand
Ud (kV)
20
28 (42) Note1)
38
voltage
Impulse (1.250)
Up (kV)
60
75 (82) Note1)
95
O-0.3s-CO-3min-CO
Closing coil
(V)
Trip coil
(V)
Auxiliary contacts
4a4b, 10a10b
(sec)
0.04
(sec)
0.06
Mechanical
M2
Electrical
E2 (List3)
C2
Fixed
P type
Drawout
Phase distance
Weight
Dimensions
3150
210
275
210
275
210
275
Breaker (H type)
(kg)
230
287
290
230
287
290
230
287
290
(kg)
175
320
320
175
320
320
175
320
320
Breaker (H type)
Page 187
Page 189
Page 187
Page 189
Page 187
Page 189
Page 188
Page 190
Page 188
Page 190
Page 188
Page 190
Standards
51
40, 50
40
VH-06
Item
Rated voltage
Ur (kV)
Ir (A)
Rated frequency
Rated short-circuit current
Rated short-time withstand current
Rated short-circuit breaking capacity
40, 50
40
VH-12
7.2
12
4000
4000
fr (Hz)
50/60
Isc (kA)
40, 50
Ik/tk (kA/s)
(MVA)
Ip (kA)
(Cycle)
40/3, 50/3
499, 623
831, 1039
2.5Isc (50)/2.6Isc (60)
3
Rated withstand
Ud (kV)
20
28
voltage
Impulse (1.250)
Up (kV)
60
75
O-0.3s-CO-3min-CO
Closing coil
(V)
Trip coil
(V)
Auxiliary contacts
4a4b, 10a10b
(sec)
0.04
(sec)
0.06
Mechanical
M2
Electrical
E2 (List1)
C2
Fixed
P type
Drawout *
Phase distance
Weight
Dimensions
Standards
275
(kg)
270, 318
Cradle (K type)
(kg)
315
Page 191
Cradle (K type)
Page 192
IEC 62271-100, KERI/KEMA, V-check(KESCO)
* K type cradle drawable type provide a cradle for builting in the switchgear, not a box type for CB compartment. Ordering type is LVB.
Note 1) 40kA : IEC62271-100, KERI/CESI, V-check(KESCO)
50kA : IEC62271-100, KERI/KEMA, V-check(KESCO)
52
VH-20,252525
Item
Rated voltage
Ur (kV)
Ir (A)
Rated frequency
24/25.8
2500
1250
2000
fr (Hz)
Isc (kA)
Ik/tk (kA/s)
25/3
31.5/3
40/3
1309/1407
1662/1787
Ip (kA)
2.6Isc (60Hz)
(cycle)
voltage
Impulse (1.250)
Up (kV)
50 (65) Note1)
125
O-0.3s-CO-3min-CO
Closing coil
(V)
Trip coil
(V)
Auxiliary contacts
4a4b, 10a10b
(sec)
0.04
(sec)
0.06
Mechanical
M2
Electrical
E2 (List3)
C2
Fixed
P type
Drawout
Phase distance **
Weight
Dimensions
3150
40
1039/1117
Ud (kV)
2000
31.5
(MVA)
1250
60
25
Rated withstand
3150
275
210 (275)
210 (275)
275
210 (275)
210 (275)
275
Breaker (H type)
(kg)
295
256 (273)
256 (273)
318
256 (273)
256 (273)
318
Cradle (H type)
(kg)
316
257 (284)
257 (284)
316
257 (284)
257 (284)
316
Breaker (H type)
Page 193
Page 195~198
Page 200
Page 195~198
Page 200
Cradle (H type)
Page 194
Page 201
Page 201
Standards
53
VH-362513/20/32
Item
Rated voltage
VH-363213/20/32
Ur (kV)
Ir (A)
Rated frequency
1250
2000
3150
1250
2000
fr (Hz)
VH-364013/20/32
36
3150
1250
2000
25
31.5
40
Ik/tk (kA/s)
25/3
31.5/3
40/3
(MVA)
1559
1964
2494
Ip (kA)
Isc (kA)
(cycle)
Rated withstand
Ud (kV)
70 (95) Note1)
voltage
Impulse (1.250)
Up (kV)
170
O-0.3s-CO-3min-CO
Closing coil
(V)
Trip coil
(V)
Auxiliary contacts
4a4b, 10a10b
(sec)
0.04
(sec)
0.06
Mechanical
M2
Electrical
E2 (List3)
3150
50/60
C2
Fixed
P type
Drawout
Phase distance
300
Weight
Breaker (H type)
(kg)
Cradle (H type)
(kg)
700
750
750
700
750
Dimensions
Breaker (H type)
Page 202
Page 204
Page 202
Page 204
Page 202
Page 204
Cradle (H type)
Page 203
Page 205
Page 203
Page 205
Page 203
Page 205
Standards
* H type is a box type cradle with CB compartment style structure.
Note1) Contact us.
54
400
490
400
700
490
400
490
VH-402513/20/32
Item
Rated voltage
VH-403213/20/32
Ur (kV)
Ir (A)
Rated frequency
40.5
1250
2000
3150
1250
fr (Hz)
2000
25
31.5
Ik/tk (kA/s)
25/4
31.5/4
(MVA)
1754
Ip (kA)
Isc (kA)
2210
2.5Isc (50Hz)
(cycle)
Rated withstand
Ud (kV)
95
voltage
Impulse (1.250)
Up (kV)
180
O-0.3s-CO-3min-CO
Closing coil
(V)
Trip coil
(V)
Auxiliary contacts
4a4b, 10a10b
(sec)
0.04
(sec)
0.06
Mechanical
M2
Electrical
C2
Fixed
Phase distance
P type
(mm)
Weight
Breaker (H type)
Dimensions
Breaker (H type)
Standards
3150
50
(kg)
300
400
490
400
490
Page 206
Page 207
Page 206
Page 207
GB1984
55
Accessory
Supplied as
Mounting
Type
Accessory
Position
VL: 7.2kV
8/12.5kA
VL: 20/25kA
VH
Remarks
page
Breaker
Motor
58
(Internal)
CC
Closing Coil
59
TC
Trip Coil
60
A1
Option
Option
Option
61
T9
Option
Option
62
63
Option
(SB)
Option
Option
Option
Option
Option
Option
64
A3
Option
Option
Option
65
A4
Option
Option
Option
65
A5
Option
Option
Option
65
A6
Option
66
Counter
66
A7
Keylock
Option
Option
Option
67
A8
Button Padlock
Option
Option
Option
68
A9
Button cover
Option
Option
Option
69
AA
Option
Option
Option
70
AB
Option
Option
Option
70
AC
Plug Interlock
Option
Option
71
AD
Padlock (H type)
Option
Option
71
AE
Option
Option
72
AF
Locking Magnet
Option
Option
73
AJ
Door Interlock
Option
Option
83
AO
Option
85
74
CTD1
Option
Option
Option
76
(External)
CTD2
Option
Option
Option
76
UDC1
Option
Option
Option
77
UDC2
Option
Option
Option
77
UDC3
Option
Option
Option
77
CTU
Option
Option
Option
75
TM
Temperature Monitoring
Option
Option
78
* : Basic Installation
56
Supplied as
Mounting
Type
Accessory
Position
Cradle
A1
A2
Remarks
page
Option
79
Option
Option
79
Option
Option
79
Option
Option
80
Option
Option
80
Option
Option
80
Option
Option
80
Option
Option
80
Option
Option
80
Option
Option
80
Option
Option
80
Option
Option
80
VL: 7.2kV
8/12.5kA
VL: 20/25kA
VH
Option
ES(Earthing Switch)
with Position Switch(6a6b)
A5
A6
A7
ES(Earthing Switch)
with Locking magnet: DC220V
A8
ES(Earthing Switch)
with Locking magnet: DC125V
A9
ES(Earthing Switch)
with Locking magnet: DC24V
AA
ES(Earthing Switch)
with Locking magnet: DC48V
AB
ES(Earthing Switch)
with Locking magnet: AC48V
AC
ES(Earthing Switch)
with Locking magnet: AC110V
AD
ES(Earthing Switch)
with Locking magnet: AC220V
AE
Shutter padlock
Option
Option
81
AF
Option
Option
81
AG
Option
Option
82
AH
Door
Option
Option
82
AJ
Door Interlock
Option
Option
83
AK
Option
Option
83
AL
Temperature Sensor
Option
Option
84
AM
Option
Option
85
Option
Option
85
Option
Option
85
Option
Option
85
57
Accessory
Motor: M
VL type
Charge the closing spring of a circuit breaker by
the external power source. When the charging
is complete, control power of the motor will be
"OFF" by the built-in Limit S/W. Without the
external power source, charge manually.
Motor
Gear
Main
shaft
Charge completion
contact
Motor
VL type
Input voltage (Vn)
Load current (A)
DC 24~
DC 48~
30V
60V
DC 110V
DC 125V
DC 220V
AC 48V
0.5
AC 100~
AC 200~
130
250V
0.5
Charge time
Within 5 sec.
Note) Rated operation and control voltage range, see page 62.
VH type
Motor
VH Type
Input voltage (Vn)
DC 48V
DC 110V
DC 125V
DC 220V
AC 48V
AC 110V
AC 220V
2.6
2.6
30
20
20
17
30
20
17
Charge time
Note) Rated operation and control voltage range, see page 62.
58
Within 12 sec.
Closing Coil: C
VL type
It is a control device which closes a circuit
breaker, when applying voltage continuously or
instantaneously over 200ms to the coil control
terminals.
Closing coil
VL type
Input voltage (Vn)
DC 24~
DC 48~
30V
60V
DC 110V
DC 125V
200
DC 220V
AC 48V
AC 100~
AC 200~
130
250V
Note) Rated operation and control voltage range, see page 62.
VH type
It is a control device which closes a circuit
breaker, when applying voltage continuously
about 45ms to the coil control terminals.
Electrical pumping preventing circuit is built in.
Closing coil
VH Type
Input voltage (Vn)
DC 48V
DC 110V
DC 125V
DC 220V
AC 48V
AC 110V
AC 220V
2.5
2.5
Note) Rated operation and control voltage range, see page 62.
59
Accessory
Trip Coil: T
VL type
It is a control device which trips a circuit breaker
from remote place, when applying voltage
continuously or instantaneously over 35ms to
coil control terminals.
When UVT coil is installed, its location is
changed.
Trip coil
VL type
Input voltage (Vn)
DC 24~
DC 48~
30V
60V
DC 110V
DC 125V
200
DC 220V
AC 48V
AC 100~
AC 200~
130
250V
Note) Rated operation and control voltage range, see page 62.
VH type
It is a control device which trips a circuit
breaker, when applying voltage continuously or
instantaneausly over 35ms to the coil control
terminals.
Trip coil
VH Type
Input voltage (Vn)
DC 48V
DC 110V
DC 125V
DC 220V
AC 48V
AC 110V
AC 220V
2.5
2.5
Note) Rated operation and control voltage range, see page 62.
60
VL type
It is a control device which trips a circuit breaker
doubly from the outside. If the trip coil (T ) fails,
it can trip a circuit breaker safely.
Trip coil: Install it at existing location.
Secondary trip coil: Install it on the right side of
the trip coil.
It is not available with UVT coil when installing
secondary trip coil.
Secondary
Trip coil
VL type
Input voltage (Vn)
DC 24~
DC 48~
30V
60V
DC 110V
DC 125V
200
DC 220V
AC 48V
AC 100~
AC 200~
130
250V
VH type
It is a control device which trips a circuit breaker
doubly from the outside. If the trip coil (T) fails, it
can trip a circuit breaker safely.
It is not available with UVT coil when installing
secondary trip coil.
Secondary
Trip coil
VH Type
Input voltage (Vn)
DC 48V
DC 110V
DC 125V
DC 220V
AC 48V
AC 110V
AC 220V
2.5
2.5
61
Accessory
Rated operation and control voltage range
Susol VCB
Item
Motor
Closing
Trip
Remarks
VL: 7.2kV 8/12.5kA
VL: 20/25kA
VH
AC
85~110%
85~110%
85~110%
DC
75~110%
85~110%
85~110%
AC
85~110%
85~110%
85~110%
DC
75~125%
85~110%
85~110%
AC
60~125%
85~110%
85~110%
60~125%
70~110%
70~110%
IEC62271-100 (2008)
IEC62271-100 (2008)
DC
Applied standards
IEC62271-100 (2008)
KSC4611
VL type : T9
Current Trip Coil
VL type : AV, AW
Current Trip Coil
62
Auxiliary Contact: SA
VL type
It is a contact used to monitor ON/OFF status of
a breaker from remote place.
Auxiliary contact
VL: 7.2kV
Item
VL: 20/25kA,
8/12.5kA
VH
Standard
2a2b
4a4b
Optional
4a4b, 6a6b
10a10b
VH type
Auxiliary contact
VL/VH Type
Item
AC
250V
10
125V
10
250V
10
125V
10
30V
10
Remarks
Contact
For all models
configuration
DC
63
Accessory
Under Voltage Trip Coil: U
VL type
VH type
VL type
Under Voltage
Trip Coil
Under Voltage
Trip Coil
It is installed inside of a breaker to trip when the main power or control power voltage drops below certain value.
Instantaneous type is only available with UVT coil and Time delay type is available by connecting UVT coil and UVT
time delay controller.
The closing of a circuit breaker is impossible mechanically or electrically if control power is not supplied to UVT.
To close the circuit breaker, 65~85% of rated voltage should be applied.
UVT and secondary trip coil will not be selected together.
VH type
DC 24~
DC 48~
30V
60V
DC 110V
DC 125V
200
DC 220V
AC 48V
AC 100~
AC 200~
130
250V
VH Type
Input voltage (Vn)
64
DC 48V
DC 110V
DC 125V
DC 220V
350
10
AC 48V
AC 110V
AC 220V
VL: 20/25kA
Position switch
This switch is used to indicate the breaker position (SERVICE, TEST), and contact configuration is 2a2a or 2a2b.
VH
Position
switch
Position
switch
Contact configuration
1
1a1b(TEST)
2b(SERVICE)
2a(TEST)
2a(SERVICE)
1a1b(TEST)
6
8
1a1b(SERVICE)
65
Accessory
Latch checking switch: A6
VH type
This switch works in conjunction with the
mechanism of the breaker. It checks if the
breaker is ready to be closed.
When the mechanism is OFF and the closing
spring is at charged status the switch becomes
"ON", which means the mechanism is ready to
be closed.
If the latch is not in a proper position the switch
prevents the breaker from closing.
In case of VH type it is connected internally in
series with the closing coil.
Latch checking
switch
Counter: C
VL/VH type
It displays the total number of ON/OFF
operations of a breaker.
66
Keylock: A7
VL type
The key is to unlock the locking device first to
close the breaker electrically and mechanically.
*How to operate
- It is not possible to pull out the key in the
unlocked position, possible only in locked
status.
- Pushing "OFF" switch of a breaker turn the key
counter-clockwise to the locked position and pull
it out.
- It is not possible to close the breaker electrically
and mechanically in the locked position.
- Insert the key and turn clockwise and then the
breaker can be closed electrically and
mechanically.
Keylock
VH type
*How to operate
- It is not possible to pull out the key in the
unlocked position, possible only in locked status.
- Trip the breaker first and then turn the key
counter-clockwise to the locked position and pull
it out.
- It is not possible to close the breaker electrically
and mechanically in the locked position.
Keylock
67
Accessory
Button Padlock: A8
VL type
It is to prevent manual operation of ON/OFF
button due to users wrong handling.
It is not possible to handle ON/OFF operation
under the Button lock status.
* Key lock is not supplied.
Button Padlock
VH type
Button Padlock
68
Button Cover: A9
VL type
It is a protection cover to prevent an accident
due to unintended operation of ON/OFF button.
Use the push-bar to operate the ON/OFF
button.
Push Bar
Button Cover
VH type
Push Bar
Button Cover
69
Accessory
Lead wire: AA
VL/VH type
It is to connect with the control circuit of a
breaker from outside. (supply wire length: 2m)
Lead wire
A type connector
VCB model
VL
VH
VL/VH type
A type connector
B type connector
It is connector to connect with the connector installed in the breaker. (supply connectors and terminal only for lead wire)
Type of connector is depends on the type of connector installed in the breaker- A or B.
70
Plug interlock: AC
Plug interlock
Door interlock
71
Accessory
MOC drive device: AE
MOC
VH type
MOC
72
Locking magnet: AF
VL type
It allows the drawing-in of the breaker in the
TEST position under the condition that the
control power connector on the cradle (H type)
is connected with the connecting terminal of the
breaker and the power is supplied.
During the drawing-in or in the SERVICE
position draw-in/out is allowed without supplying
power.
* Control power rating is the same as that of a motor.
Locking
magnet
VH type
Locking magnet
73
Accessory
Trip coil monitoring contact: AP
VL type
Device for monitoring the functions of the trip
coils.
Supplied as standard for VL model and optional
for VH model.
To monitor the trip coils connect its terminals
with the trip coil monitoring relay as shown on
the circuit diagram.
- If the trip coil is normal: closed-circuit
consisting
- If the trip coil is damaged: open circuit
1) Terminals A5 and A6 monitor the trip coils in
closed position of the breaker.
2) Terminal A6 and aux. contact terminal 34
monitor the trip coils in trip position of the
breaker.
Coil Test Unit is opional, which enable
monitoring the coils by connecting in parallel
with the trip coil operation switch.
VH type
74
When no current flows through the coil it gives the test current which does not cause the coil to operate to check
whether the coil is disconnected or not.
- If the test current flows normally: coil normal
- If the test current does not flow through: coil disconnected
As it is connected in parallel with the control part of the coil the normal operation of the coil is not affected.
Monitoring of the running coils is not possible.
One test unit can monitor up to two coils.
1. Input voltage: AC/DC 75V~264V
2. Contact output
1) 2a contacts for Fail indication and 2a contacts for Alarm
2) 250Vac/10A Resistive, 30Vdc/10A Resistive
3. Disconnection test cycle is 12 seconds (Test LED blinks)
4. The default operation
If Fail happens (coil disconnected), Fail LED turns on and the Fail contacts become short state.
If Fail happens three times in series, Alarm LED turns on and the Alarm contacts become short state.
In order to clear the Alarm status push up DIP switch on the front and then push down it (Off On Off)
Input voltage
AC/DC 75~264V
Fail 1
24~250V
(AC/DC)
Alarm 1
Shunt 1
Coil
Test
Unit
24~250V
(AC/DC)
Fail 2
Alarm 2
Shunt 2
CTU
CTU
Input voltage Input voltage
(+)
(+)
Coil
Coil test current
Coil drive power(-)
1
5
Fail (LED)
Fail (RELAY)
Alarm (LED)
Alarm (RELAY)
75
Accessory
Condenser trip device: CTD
Ratings
Ratings
Specification
Model
CB - T1
CB - T2
AC 100/110
AC 200/220
Frequency (Hz)
50/60
50/60
140/155
280/310
Charging time
Within 10sec.
Within 10sec.
Within 30sec.
Within 30sec.
85%~110%
85%~110%
Condenser capacity (
F)
1,000
560
Terminal arrangement
External dimension
(Mounting hole)
Circuit diagram
76
UVT time delay, UDC is to delay the trip signal from UVT.
Without UDC the breaker will be tripped instantaneously by the trip signal from UVT installed inside of the breaker
even in the the momentary power failure.
UDC can delay the trip time to avoid this unintended instantaneous trip in the event of such power failure.
It can be installed on the cradle or inside of the switchgear.
UDC provides output contacts for indication of trip status due to the UVT coil inside of the breaker.
b contact is closed at normal state and a contact is closed at trip.
1. Characteristics
Rated voltage (Vn)
DC (V)
AC (V)
48~60
48
100~130
100~130
200~250
200~250
Consumption (VA or W)
Time delay
Pick up
Drop out
Inrush
Steady - state
(ms)
0.65~0.85 Vn
0.4~0.65 Vn
200
0.5, 1, 1.5, 3
- Operating voltage ranges are based on the minimum value of each rated voltage (Vn)
24V DC
12
120V AC
12
250V AC
10
110V DC
250V AC
15
3. Wiring diagram
Delayed
trip signal
14 16
18(a)
Operating
output 19(c)
contact 20(b)
UVT
18 19 20
a c b
0.5
UVT Delay
Controllor
Signal for
tripping
1.5
14
16
DC48~60V
AC48
[sec]
5 7
Instantaneous
trip signal
77
Accessory
Temperature sensor and
monitoring unit: TM
Temperature
Sensor
78
Earthing Switch: A1
Earthing
Switch
Circuit diagram
E1
E3
E5
E7
E9
E2
E4
E6
E8
79
Accessory
Keylock for Earthing Switch: A5
80
Shutter padlock: AE
Shutter
padlock
VL type
Circuit diagram
VH Type
121 122
124
125
127 128
126
129
130
131
TOC
123
132
81
Accessory
Mechanical Operated Cell Switch
(MOC: AG)
VL type
Circuit diagram
102 101
105
104
108 107
106
109
111
110
MOC
103
112
VH Type
a Contact: 101-103, 104-106, 107-109, 110-112,
b Contact: 102-103, 105-106, 108-109, 111-112
Door: AH
Door
82
Door Interlock: AJ
Door
Emergency
Push button
83
Accessory
Temperature Sensor: AC
Temperature
Sensor
Cradle
E
VL-06 08,13
Charging handle
Not required
Not required
55223171101
F
G
E
VL-06 20,25
55213143005
F
G
55223172407
A
VL-06 20,25
Not required
55223172403
B
H
K
55223172405
55213143006
C
VH-06,12,17,
24,35,36
55223172406
D
B
C
84
Lead
Wire
Door Padlock
Door
Padlock
85
Accessory
Auxiliary guide frame
550
Width : 550mm
Min. height:90mm
Bottom
<Fig 1>
86
If dimension A in Fig. 1 is
less than 120mm B type
pallet can be used.
In case of more than 120mm
C type must be applied.
A2
LS2
A1
10
CS
14
A4
A3
52a
11
D2
UVT
12
TC1
Note3) Note4)
D1
A6
TC
52a
A5
TEST : 1a1b
SERVICE : 2b
A3
Close at TEST position
OPEN at TEST position
OPEN at SERVICE position
OPEN at SERVICE position
25
24
27
26
29
28
42
41 43
40
TEST : 2a
SERVICE : 2a
A4
Close at TEST position
Close at TEST position
Close at SERVICE position
Close at SERVICE position
Option
D1
14
D2
CTC2 CTC3
13
Auxiliary switch
TEST : 1a1b
SERVICE : 1a1b
A5
Close at TEST position
OPEN at TEST position
Close at SERVICE position
OPEN at SERVICE position
23 25 27 29 41 (43)
23
22
22 24 26 28 40 (42)
2a
4a
LS4
LS5
LS6
LS7
S/W
No.
CTC2
Note1)
13
Note5)
6a(5a)
Note5)
35
34
39
52
51 53
38 50
55
54
57
56
A3
A4
A2
A1
A3
A4
A3
A4
A1
A2
A1
A2
A5
A6
A5
A6
A5
A6
37 39 51 53 55 (57)
37
36
34 36 38 50 52 54 (56)
2b
4b
6b(5b)
10
10
10
3
LS4
TEST
5
LS5
7
LS6
SERVICE
LS7
3*
4*
LS4
14
/57
14
13
/56
D2/12
/43
D1/11
/42
13
/56
/42
/57
D2/12
D1/11
/43
13
14
/42
/57
/56
D1/11
/43
D2/12
13
14
/57
/56
/42
/43
D2/12
D1/11
4
6
23
22
23
22
23
22
(5a5b)
(5a6b)
(4a4b)
(2a2b)
25
24
25
24
25
24
27
26
27
26
LS5
7*
8*
LS6
LS7
4*
LS4
3*
28
29
28
29
41
40
34
34
34
36
37
36
37
36
37
38
39
38
5*
6*
39
38
39
LS5
51
50
51
50
52
53
52
53
8*
LS6
7*
54
55
LS7
Position switch
<1a1b(TEST), 2b(SERVICE)>
Position switch
<1a1b(TEST),1a1b(SERVICE)>
VL-06
87
88
A2
LS2
A1
10
CS
52a
11
D2
UVT
12
TC1
Note3) Note4)
D1
A4
A3
A6
TC
52a
A5
23 25
23 25
43 45 47 49
Note4)
27 29 41
61
61
48 60
48 60
43 45 47 49
40 42 44 46
40 42 44 46
27 29 41
22 24 26 28
22 24 26 28
4a
10b (9b)
Note4)
D1
14
D2
CTC2 CTC3
13
5
LS5
7
LS6
12
11
D2 D1
10
9 16 15 14 13
LM
16
Note5)
LS7
15
3*
4*
LS4
LS5
7*
8*
LS6
LS7
4*
LS4
3*
LS5
6*
5*
8*
LS6
7*
LS7
Position switch
<1a1b(TEST), 2b(SERVICE)>
53 52 51 50
A
B
C
D
12
11
D2 D1
10
9 16 15 14 13
75 74 73 72 71 70 59 58 57 56 55 54 53 52 51 50
41 40 29 28 27 26 25 24 23 22 A6 A5 A4 A3 A2 A1
39 38 37 36
34 61 60 49 48 47 46 45 44 43 42
16 15 14 13 12 11 10 9
Position switch
<1a1b(TEST),1a1b(SERVICE)>
SERVICE
29 28 27 26 25 24 23 22 A6 A5 A4 A3 A2 A1
39 38 37 36
34
16 15 14 13 12 11 10 9
B type
A type
37 39 51 53 55 57 59 71 73 75
35 37 39 51 53 55 57 59 71 73 75
3
LS4
TEST
34 36 38 50 52 54 56 58 70 72 74
34 36 38 50 52 54 56 58 70 72 74
4b
TEST : 1a1b
TEST : 2a
TEST : 1a1b
SERVICE : 2b
SERVICE : 2a
SERVICE : 1a1b
A3
A4
A5
Close at TEST position
Close at TEST position
Close at TEST position
OPEN at TEST position
Close at TEST position
OPEN at TEST position
OPEN at SERVICE position Close at SERVICE position Close at SERVICE position
OPEN at SERVICE position Close at SERVICE position OPEN at SERVICE position
LS4
LS5
LS6
LS7
S/W
No.
14
CTC2
Note1)
13
10a (9a)
Auxiliary switch
A
B
C
D
VL-06/12/17/20/25
10
A2
LS2
A1
Yb
31
30
5
1
A4
LS1
52b
LCS1
Note1)
LS3
A3
CS
83
82
11
12
TC1
Note4)
UVT
D2
Note3)
52a
A6
TC
6'
A5
CS
Ya
D1
16
LM
Note5)
15
25
24
27
26
29
28
42
41 43
40
45
44
47
46
49
48
61
60
Option
10b
35
34
39
52
51 53
38 50
55
54
57
56
59
58
72
71 73
70
75
74
5
7
34
36 37
B
28 29
26 27
12
D2
11
D1
24 25
36 37
34
28 29
26 27
24 25
12
D2
56 57
11
D1
46 47
54 55
10
10
22 23
44 45
52 53
A5 A6
52 53
A5 A6
74 75
72 73
70 71
60 61
58 59
48 49
42 43
50 51
A3 A4
50 51
40 41
A3 A4
38 39
A1 A2
38 39
A1 A2
22 23
Note2)
3
LS4
TEST
5
LS5
7
LS6
SERVICE
LS7
Position switch
<2a(TEST),2a(SERVICE)>
3*
4*
LS4
LS5
7*
8*
LS6
3*
4*
LS4
LS5
6*
5*
7*
8*
LS6
9 16 15
12
11
D2 D1
10
9 16 15
75 74 73 72 71 70 59 58 57 56 55 54 53 52 51 50
41 40 29 28 27 26 25 24 23 22 A6 A5 A4 A3 A2 A1
39 38 37 36
34 61 60 49 48 47 46 45 44 43 42
16 15 14 13 12 11 10 9
10
53 52 51 50
29 28 27 26 25 24 23 22 A6 A5 A4 A3 A2 A1
39 38 37 36
34
16 15 14 13 12 11 10 9
B type connector
12
11
D2 D1
LS7
A
B
C
D
A
B
C
D
LS7
Position switch
<1a1b(TEST), 2b(SERVICE)>
Position switch
<1a1b(TEST),1a1b(SERVICE)>
37 39 51 53 55 57 59 71 73 75
37
36
34 36 38 50 52 54 56 58 70 72 74
4b
A type connector
23 25 27 29 41 43 45 47 49 61
23
22
22 24 26 28 40 42 44 46 48 60
4a
10a
VH-06/12/17/20/25//36/40
89
90
E4
17
P
Note2)
103
106
109
112
MOC
* Above circuit diagram is based on the status that the earthing S/W is Open and the breaker is at Test or
between Test and Service position. MOC indicates the Open of the breaker. If the breaker is Closed from
Service, the contacts configuration is displayed on the contrary.
Note) 1. LM - If it is energized with the rated power the earthing switch can be closed or opened (for H type cradle)
2. MOC - This auxiliary switch is used to indicate the Close/Open of VCB (for H type cradle)
It is composed of 4 cell switches with 4 changeover contacts.
3. TOC - This auxiliary switch is used to indicate the 'SERVICE' position of VCB (for H type cradle)
It is composed of 4 cell switches with 4 changeover contacts.
4. TM - Temperature Alarm Unit displays the input temperature detected through the temperature sensor installed
in H-type cradle. Temperature sensor can be installed in each phase and can be connected with the
temperature module.
5. Please make sure that keep the direction of P, N on this circuit diagram.
18
LM
6b
E4
E2
E2
E3
E3
2b
E5
E5
6a
E1
E1
2a
Note3)
123
126
Option
129
132
TOC
12(R-)
TM
8(R+)
12(S-)
TM
9(S+)
TM
12(T-)
TM
10(T+)
Note4)
Compartment
VL-06
Dimensions - VL type
7.2kV, 8/12.5kA, 400/630A
Fixed (P type)
(Mounting hole)
91
Dimensions - VL type
7.2kV, 8/12.5kA, 400/630A
Withdrawable (Compatible with existing breaker E/F/G type)
(Earthing hole)
Racking in/out
Stroke:150
92
VL-06
(Earthing hole)
Racking in/out
Stroke:150
(Earthing hole)
Racking in/out
Stroke:150
93
Dimensions - VL type
7.2kV, 20/25kA, 630/1250A
Fixed (P type, phase distance 150mm)
91.5
96.5
6(10)
281
M12
(Earthing hole)
94
VL-06/12/17/20/25
95
Dimensions - VL type
7.2kV, 20/25kA, 630/1250A
Withdrawable (E type cradle, phase distance 150mm)
5- 12(Mounting hole)
Rating
A
B
C
630A
6
55
95
1250A
10
60
90
96
630A
6
55
95
1250A
10
60
90
12(Earthing hole)
VL-06/12/17/20/25
(Mounting hole)
Rating
A
630A
6
(Mounting hole)
(Earthing hole)
1250A
10
273.5
194
110
112
Racking in/out
Stroke:200
97
Dimensions - VL type
7.2kV, 20/25kA, 630/1250A
Withdrawable (H type cradle, phase distance 150mm)
323.4
317
(For assembly of
lifting hook and LV
compartment
mounting hole)
42.3
(Mounting hole)
150 150
M12 (DP:25)
(Mounting hole)
725
183.7
1017.7
(Mounting hole)
(Mounting hole)
65
285
20
550
8- 11
(Mounting hole)
87.3
20
TUBE
Detail A
30
30
TUBE
10.0
87.3
Detail A
87.3
20
43.4
2-M8 (DP:18)
See Detail A
98
Detail A
VL-06/12/17/20/25
96.5
46.8
M12(Earthing hole)
99
Dimensions - VL type
7.2kV, 20/25kA, 2000A
Withdrawable (F/G type unit, phase distance 150mm)
110
125
(Mounting hole)
273.5
100
(Earthing hole)
VL-06/12/17/20/25
110
125
(Mounting hole)
(Mounting hole)
110
125
(Earthing hole)
273.5
101
Dimensions - VL type
7.2kV, 20/25kA, 2000A
Withdrawable (H type unit, phase distance 150mm)
194
110
112
Racking in/out
Stroke:220
102
VL-06/12/17/20/25
317
42.3
25
150 150
(Mounting hole)
550.4
(For assembly of
lifting hook and LV
compartment
mounting hole)
(Mounting hole)
725
1017.7
202.7
(Mounting hole)
465
310
(Mounting hole)
285
550
65
(Mounting hole)
20
30
TUBE
10.0
68.3
25
Detail A
68.3
20
43.4
2-M8 (DP:18)
See Detail A
Detail A
103
Dimensions - VL type
7.2kV, 31.5kA, 630A
Fixed (P type, phase distance 150mm)
553
2- 14
150
40
40
150
Earthing position
10
152
212
178
4- 13
96.5
450
46.8
281
509
M12
(Earthing hole)
320
10
650
670
295
212
470
589
315
523.5
156
150
194
110
607
660
440
112
Stroke: 200
319
503
104
13
53
320
358
383
469
25
4
21.5
19.5
76
154
280
623.5
688
35
310
492
VL-06/12/17/20/25
(Mounting hole)
(Mounting hole)
(Mounting hole)
(Mounting hole)
(Mounting hole)
105
Dimensions - VL type
7.2kV, 31.5kA, 1250A
Fixed (P type, phase distance 150mm)
553
150
150
2- 14
60
10
152
212
178
4- 13
40
Earthing position
46.8
281
509
M12
(Earthing hole)
96.5
450
320
10
650
670
295
212
470
589
315
523.5
106
156
VL-06/12/17/20/25
62.4
80.2
(Mounting hole)
107
Dimensions - VL type
7.2kV, 31.5kA, 1250A
Withdrawable (F type cradle , phase distance 150mm)
(Earthing hole)
62.4
80.2
(Mounting hole)
62.4
80.2
(Mounting hole)
108
(Earthing hole)
VL-06/12/17/20/25
350
616
669
150
328
Stroke:225
53
32
12.5
288
351
383
436
13
522
332.5
104.5
230.5
48
676
692.5
295
450
350
616
669
150
328
Stroke:225
13
522
53
288
351
383
436
32
32.5
104.5
230.5
332.5
676
692.5
48
295
450
109
Dimensions - VL type
7.2kV, 31.5kA, 1250A
26
295
83
(Mounting
hole)
560
VIEW "C"
150 150
26
(Mounting hole)
660
100
ST: 225
VIEW
"C"
285
1250A: 12t
2000A: 25t
345
1235
295
48
ST: 225
12
600
100
156
660
731.5
946
150
60
150
150
600
560
83
26
26
100
662
630
1235
295
1250A:12t
2000A:25t
731.5
946
110
VL-06/12/17/20/25
150
194
110
607
660
440
112
Stroke: 200
319
503
13
53
320
358
383
469
25
4
21.5
19.5
76
154
280
623.5
688
35
310
492
111
Dimensions - VL type
7.2kV, 31.5kA, 1250A
Withdrawable (H type cradle, phase distance 150mm)
(For assembly of
lifting hook and LV
compartment
mounting hole)
(Mounting hole)
(Mounting hole)
(Mounting hole)
(Mounting hole)
(Mounting hole)
112
VL-06/12/17/20/25
96.5
46.8
M12(Earthing hole)
113
Dimensions - VL type
7.2kV, 31.5A, 2000A
Withdrawable (F/G type unit, phase distance 150mm)
62.4
80.2
(Mounting hole)
114
(Earthing hole)
VL-06/12/17/20/25
62.4
80.2
(Mounting hole)
(Earthing hole)
62.4
80.2
(Mounting hole)
115
Dimensions - VL type
7.2kV, 31.5kA, 2000A
Withdrawable (K type unit T type, phase distance 150mm)
516
150
350
616
669
150
328
Stroke:225
522
53
32
12.5
288
351
383
436
13
332.5
104.5
230.5
48
676
692.5
295
450
350
616
669
150
328
Stroke:225
13
522
116
53
288
351
383
436
32
32.5
104.5
230.5
332.5
676
692.5
48
295
450
VL-06/12/17/20/25
26
295
83
(Mounting
hole)
560
VIEW "C"
150 150
26
(Mounting hole)
660
100
ST: 225
VIEW
"C"
285
1250A: 12t
2000A: 25t
345
1235
295
48
ST: 225
12
600
100
156
660
731.5
946
150
600
560
150
26
26
662
295
1250A:12t
2000A:25t
1235
100
630
83
150
731.5
946
117
Dimensions - VL type
7.2kV, 31.5kA, 2000A
Withdrawable (H type unit, phase distance 150mm)
194
110
112
Racking in/out
Stroke:220
118
VL-06/12/17/20/25
323.4
42.3
25
150 150
(Mounting hole)
550.4
(For assembly of
lifting hook and LV
compartment
mounting hole)
(Mounting hole)
725
1017.7
202.7
(Mounting hole)
465
310
(Mounting hole)
285
550
65
(Mounting hole)
20
30
TUBE
10.0
68.3
25
Detail A
68.3
20
43.4
2-M8 (DP:18)
See Detail A
Detail A
119
Dimensions - VL type
12/17.5kV, 20/25kA, 630/1250A
Fixed (P type, phase distance 150mm)
96.5
46.8
M12(Earthing hole)
96.5
120
46.8
M12(Earthing hole)
VL-06/12/17/20/25
311.5
613.5
210
670
310
650
670
295
302
103
670
715
286
78
94.5
483
315
655.5
311.5
613.5
210
670
169.5
310
650
670
295
302
103
670
715
286
78
94.5
483
315
655.5
121
Dimensions - VL type
12/17.5kV, 20/25kA, 630/1250A
Withdrawable (E type unit, phase distance 210mm)
122
VL-06/12/17/20/25
Racking in/out
Stroke:182
2-M6 TAP
40
20
50
210
766.4
725
690
139
210
11.8
(Earthing hole)
440
340
326
87.2
720.2
295
270
278.5
800
860
1050
40
(Earthing hole)
60
210
766.4
725
690
139
210
11.8
2-M6 TAP
164
70
440
340
800
10
326
87.2
720.2
295
270
278.5
860
1050
40
123
Dimensions - VL type
12/17.5kV, 20/25kA, 630A
Withdrawable (Compatible with existing F cradle, phase distance 210mm)
Racking in/out
Stroke:182
164
70
2-M6 TAP
11.8
40
20
50
210
766.4
725
690
210
(Earthing hole)
440
340
326.2
87.2
720.2
295
270
278.5
800
55
860
1050
(Earthing hole)
60
210
766.4
725
690
139
210
11.8
2-M6 TAP
164
70
440
340
800
124
326.2
87.2
10
295
720.2
270
278.5
860
1050
40
VL-06/12/17/20/25
(Earthing hole)
(Mounting hole)
278.5
(Earthing hole)
(Mounting hole)
278.5
125
Dimensions - VL type
12/17.5kV, 20/25kA, 630/1250A
Withdrawable (H type unit, phase distance 150mm)
194
110
112
Racking in/out
Stroke:200
110
112
Racking in/out
Stroke: 220
126
VL-06/12/17/20/25
42.3
323.4
(For assembly of
lifting hook and LV
compartment
mounting hole)
M12 (DP:25)
550
150 150
(Mounting hole)
(Mounting hole)
183.7
1017.7
725
600
560
650
(Mounting hole)
65
285
150 150
400
212.5
445
400
258.7
550
(Mounting hole)
20
212.5
205
1120
400
400
(Mounting hole)
20
87.3
30
TUBE
30
TUBE
10.0
87.3
Detail A
Detail A
87.3
20
43.4
2-M8 (DP:18)
See Detail A
Detail A
127
Dimensions - VL type
12/17.5kV, 20/25kA, 1250A
Withdrawable (H type cradle, phase distance 210mm)
317
323.4
42.3
M12 (DP:25)
(Mounting hole)
210
700
210
(For assembly of
lifting hook and LV
compartment
mounting hole)
725
1017.7
(Mounting hole)
183.7
(Mounting hole)
65 285
700
(Mounting hole)
20
(Mounting hole)
20
87.3
30
TUBE
30
TUBE
10.0
87.3
Detail A
Detail A
87.3
20
63.4
2-M8(DP:18)
See Detail A
128
Detail A
VL-06/12/17/20/25
96.5
46.8
M12(Earthing hole)
129
Dimensions - VL type
12/17.5kV, 20/25kA, 2000A
Withdrawable (F type unit, phase distance 210mm)
(Earthing hole)
(Mounting hole)
278.5
130
VL-06/12/17/20/25
(Earthing hole)
(Mounting hole)
131
Dimensions - VL type
12/17.5kV, 20/25kA, 2000A
Withdrawable (H type unit, phase distance 150mm)
194
110
112
Racking in/out
Stroke:220
110
112
Racking in/out
Stroke:220
132
VL-06/12/17/20/25
317
42.3
25
150 150
(Mounting hole)
550
(For assembly of
lifting hook and LV
compartment
mounting hole)
2-M12 (DP:25)
(Mounting hole)
725
202.7
1017.7
(Mounting hole)
550
65 285
(Mounting hole)
(Mounting hole)
20
25
30
TUBE
10.0
68.3
Detail A
68.3
20
43.4
2-M8 (DP:18)
See Detail A
Detail A
133
Dimensions - VL type
12/17.5kV, 20/25kA, 2000A
Withdrawable (H type cradle, phase distance 210mm)
317
42.3
(Mounting hole)
2-M12 (DP:25)
725
1017.7
25
210 210
700
(For assembly of
lifting hook and LV
compartment
mounting hole)
323.4
(Mounting hole)
183.7
(Mounting hole)
(Mounting hole)
700
(Mounting hole)
20
30
25
TUBE
10.0
87.3
Detail A
87.3
20
63.4
2-M8(DP:18)
See Detail A
134
Detail A
VL-06/12/17/20/25
96.5
46.8
M12(Earthing hole)
96.5
46.8
M12(Earthing hole)
135
Dimensions - VL type
12kV, 31.5kA, 1250A
Withdrawable (K type unit T type, phase distance 150mm)
516
150
350
616
669
150
328
Stroke:225
522
53
32
12.5
288
351
383
436
13
332.5
104.5
230.5
48
676
692.5
295
450
350
616
669
150
328
Stroke:225
13
522
136
53
288
351
383
436
32
32.5
104.5
230.5
332.5
676
692.5
48
295
450
VL-06/12/17/20/25
26
295
83
(Mounting
hole)
560
VIEW "C"
150 150
26
(Mounting hole)
660
100
ST: 225
VIEW
"C"
285
1250A: 12t
2000A: 25t
345
1235
295
48
ST: 225
12
600
100
156
660
731.5
946
150
600
560
150
26
26
662
295
1250A:12t
2000A:25t
1235
100
630
83
150
731.5
946
137
Dimensions - VL type
12kV, 31.5kA, 2000A
Withdrawable (K type unit T type, phase distance 150mm)
516
150
350
616
669
150
328
Stroke:225
522
53
32
12.5
288
351
383
436
13
332.5
104.5
230.5
48
676
692.5
295
450
350
616
669
150
328
Stroke:225
13
522
138
53
288
351
383
436
32
32.5
104.5
230.5
332.5
676
692.5
48
295
450
VL-06/12/17/20/25
26
295
83
(Mounting
hole)
560
VIEW "C"
150 150
26
(Mounting hole)
660
100
ST: 225
VIEW
"C"
285
1250A: 12t
2000A: 25t
345
1235
295
48
ST: 225
12
600
100
156
660
731.5
946
150
600
560
150
26
26
662
295
1250A:12t
2000A:25t
1235
100
630
83
150
731.5
946
139
Dimensions - VL type
12/17.5kV, 31.5kA, 630/1250A
Withdrawable (H type unit, phase distance 150mm)
490
150
150
194
607
660
440
110
112
Stroke: 200
319
503
13
53
320
358
383
469
25
4
21.5
19.5
76
154
280
623.5
688
35
310
492
110
112
Racking in/out
Stroke: 220
140
VL-06/12/17/20/25
(Mounting hole)
(Mounting hole)
(Mounting hole)
(Mounting hole)
(Mounting hole)
141
Dimensions - VL type
12/17.5kV, 31.5kA, 630/1250A
Withdrawable (H type cradle, phase distance 210mm)
317
323.4
42.3
M12(DP:25)
(For assembly of
lifting hook and LV
compartment
mounting hole)
210
210
(Mounting hole)
(Mounting hole)
725
183.7
1112.7
650
750
37.5
710
(Mounting hole)
65 285
400
212.5
465
400
212.5
1120
310
400
400
(Mounting hole)
700
(Mounting hole)
20
20
87.3
30
30
10.0
87.3
87.3
2-M8(DP:18)
63.4
20
DETAIL A
SCALE 2/15
SEE DETAIL A
142
VL-06/12/17/20/25
96.5
46.8
M12(Earthing hole)
194
110
112
Racking in/out
Stroke:220
143
Dimensions - VL type
12/17.5kV, 31.5kA, 2000A
Withdrawable (H type unit, phase distance 210mm)
194
110
112
Racking in/out
Stroke:220
144
VL-06/12/17/20/25
323.4
42.3
25
(For assembly of
lifting hook and LV
compartment
mounting hole)
550.4
150 150
(Mounting hole)
14(Mounting hole)
725
202.7
1112.7
600
650
560
37.5
(Mounting hole)
285
400
212.5
465
400
150 150 277.2
550
65
212.5
1120
310
400
400
(Mounting hole)
(Mounting hole)
20
30
10.0
68.3
25
DETAIL A
43.4
68.3
20
2-M8(DP:18)
DETAIL B
SCALE 2/15
SECTION A-A
SEE DETAIL B
145
Dimensions - VL type
12/17.5kV, 31.5kA, 2000A
Withdrawable (H type cradle, phase distance 210mm)
317
323.4
(For assembly of
lifting hook and LV
compartment
mounting hole)
42.3
M12(DP:25)
210
25
210
(Mounting hole)
14(Mounting hole)
725
183.7
1112.7
650
750
37.5
710
(Mounting hole)
65 285
400
212.5
465
400
212.5
1120
310
400
400
(Mounting hole)
700
(Mounting hole)
20
30
10.0
87.3
DETAIL A
87.3
20
63.4
2-M8(DP:18)
SEE DETAIL A
146
DETAIL A
SCALE 1/6
VL-06/12/17/20/25
210
6- 14
60
100
40
M12(Earthing hole)
96.5
46.8
10
281
523.5
152
212
178
4- 13
455
212
650
690
320
670
20
295
600
315
523.5
606.5
670
789
156
275
100
60
Earthing position
281
523.5
M12
(Earthing hole)
96.5
800
46.8
10
152
212
178
4- 13
650
320
670
20
295
212
800
919.5
315
523.5
156
147
Dimensions - VL type
12/17.5kV, 31.5A, 2500A
Withdrawable (H type unit, phase distance 210mm)
640
210
210
194
589
642
110
112
359.5
301
Stroke:220
13
653
53
320
358
383
469
25
4
21.5
19.5
76
165
280
688
79
310
640
275
194
359.5
110
589
642
112
301
Stroke:220
853
148
13
53
320
358
383
469
25
4
21.5
19.5
76
165
280
646.5
688
79
310
890
VL-06/12/17/20/25
323.4
(For assembly of
lifting hook and LV
compartment
mounting hole)
42.3
35
M12(DP:25)
210
210
35
(Mounting hole)
14(Mounting hole)
725
1017.2
750
650
197.2
37.5
710
(Mounting hole)
65 285
400
212.5
465
400
212.5
1120
310
400
400
(Mounting hole)
700
(Mounting hole)
20
73.8
35
35
35
10.0
32.5
73.8
20
63.4
2-M8(DP:18)
DETAIL A
SCALE 2/15
SEE DETAIL A
149
Dimensions - VL type
12/17.5kV, 31.5A, 2500A
Withdrawable (H type cradle, phase distance 275mm)
317
323.4
(For assembly of
lifting hook and LV
compartment
mounting hole)
35
42.3
4-M12 (DP:25)
275
950.4
275
35
(Mounting hole)
(Mounting hole)
725
1017.2
1000
197.2
650
960
37.5
(Mounting hole)
65
285
465
212.5
212.5
400
400
1120
310
400
400
(Mounting hole)
950
(Mounting hole)
20
73.8
35
35
35
10.0
32.5
73.8
20
63.4
2-M8(DP:18)
SEE DETAIL A
150
DETAIL A
VL-06/12/17/20/25
(Earthing hole)
151
Dimensions - VL type
24/25.8kV 12.5kA 630A
Withdrawable (F type unit Visible, Clip contact, phase distance 265mm)
830
265
38
311.5
617.5
265
306
126.5
400
805
805
10
340
700
103
700
745
72
94.5
312
493
335
659.5
311.5
576
265
400
29
805
805
120
340
264.5
700
103
700
745
152
72
94.5
312
443
451.5
335
618
VL-06/12/17/20/25
311.5
576
265
126.5
400
29
805
805
120
340
264.5
700
103
700
745
72
94.5
312
443
451.5
335
618
311.5
671.5
265
700
103
700
745
72
94.5
312
547
335
713.5
126.5
400
805
805
29
340
360
153
Dimensions - VL type
24/25.8kV 12.5kA 630A
Withdrawable (K type unit, phase distance 210mm)
656
437
820
210
767
210
Stroke: 310
479.5
13
350
437
463
53
653
50
301.5
422.5
12.5
185.5
827.5
827.5
29
340
600
437
767
820
265
479.5
Stroke: 310
154
53
350
437
463
50
12.5
13
886
422.5
185.5
301.5
827.5
827.5
29
340
600
VL-06/12/17/20/25
210
194
746
799
110
112
458
458
Stroke: 300
13
653
53
35
365
403
438
524
21.5
19.5
72
198
325
756
770
35
310
636
275
194
458
746
799
110
112
836
Stroke: 300
13
53
365
403
438
524
35
21.5
19.5
853
72
198
325
756
770
35
310
458
155
Dimensions - VL type
24/25.8kV 12.5kA 1250A
Fixed (P type, phase distance 265mm)
(Earthing hole)
156
VL-06/12/17/20/25
311.5
617.5
265
306
126.5
400
805
805
10
340
700
103
700
745
72
94.5
312
493
335
659.5
311.5
576
265
400
29
805
805
120
340
264.5
700
103
700
745
72
94.5
312
443
451.5
335
618
157
Dimensions - VL type
24/25.8kV 12.5kA 1250A
Withdrawable (F type unit Enclosed, Tulip contact, phase distance 265mm)
830
265
311.5
576
265
264.5
103
700
745
72
94.5
126.5
400
29
805
805
120
340
700
312
443
451.5
335
618
311.5
671.5
265
360
103
700
745
158
312
72
94.5
547
335
713.5
126.5
400
805
805
29
340
700
VL-06/12/17/20/25
437
767
820
210
479.5
Stroke: 310
653
13
53
350
437
463
50
12.5
185.5
301.5
422.5
827.5
827.5
29
340
600
479.5
53
350
437
463
50
422.5
12.5
185.5
301.5
840
29
340
Stroke: 310
159
Dimensions - VL type
24/25.8kV 12.5kA 1250A
Withdrawable (H type unit, phase distance 210mm)
640
210
210
194
746
799
110
112
458
458
Stroke: 300
72
198
325
756
770
35
310
636
53
35
365
438
471
524
21.5
19.5
13
653
275
194
458
746
799
110
112
836
Stroke: 300
853
13
53
160
365
403
438
524
35
21.5
19.5
72
198
325
756
770
35
310
458
VL-06/12/17/20/25
(Earthing hole)
311.5
617.5
265
306
400
805
805
10
340
700
103
700
745
72
94.5
312
493
335
659.5
161
Dimensions - VL type
24/25.8kV 16kA 630A
Withdrawable (F type unit Visible, Clip contact, phase distance 265mm)
830
265
38
311.5
617.5
265
306
126.5
400
805
805
10
340
700
103
700
745
72
312
493
335
659.5
(Earthing hole)
162
VL-06/12/17/20/25
311.5
617.5
265
306
126.5
400
805
805
10
340
700
103
700
745
72
94.5
312
493
335
659.5
163
Dimensions - VL type
24/25.8kV 16/25kA 630/1250A
Withdrawable (E type unit Enclosed, Tulip contact, phase distance 265mm)
265
311.5
576
265
400
29
805
805
120
340
264.5
700
103
72
94.5
700
745
312
443
451.5
335
618
311.5
576
265
264.5
103
700
745
164
72
94.5
312
443
451.5
335
618
126.5
400
29
805
805
120
340
700
VL-06/12/17/20/25
311.5
671.5
265
360
126.5
400
805
805
29
340
700
312
103
700
745
72
94.5
547
335
713.5
437
767
820
210
479.5
Stroke: 310
653
13
53
350
437
463
50
12.5
185.5
301.5
422.5
827.5
827.5
29
340
600
165
Dimensions - VL type
24/25.8kV 16/25kA 630/1250A
Withdrawable (K type unit, phase distance 265mm)
Stroke: 310
50
350
437
463
53
422.5
12.5
185.5
301.5
840
29
340
479.5
210
194
458
746
799
110
112
458
Stroke: 300
13
653
53
166
365
438
471
524
35
21.5
19.5
72
198
325
756
770
35
310
636
VL-06/12/17/20/25
275
194
458
746
799
110
112
836
Stroke: 300
853
13
53
365
403
438
524
35
21.5
19.5
72
198
325
756
770
35
310
458
(Earthing hole)
167
Dimensions - VL type
24/25.8kV 25kA 2000A
Withdrawable (E type unit Visible, Clip contact, phase distance 265mm)
265
78
311.5
617.5
265
306
400
805
805
10
340
700
312
103
700
745
72
94.5
493
335
659.5
311.5
617.5
265
306
126.5
400
805
805
20
340
700
103
700
745
168
72
94.5
312
493
335
659.5
VL-06/12/17/20/25
311.5
576
265
264.5
400
48
805
805
120
340
700
103
700
745
72
94.5
312
443
451.5
335
618
311.5
576
265
264.5
126.5
400
48
805
805
120
340
700
103
700
745
72
94.5
312
443
451.5
335
618
169
Dimensions - VL type
24/25.8kV 25kA 2000A
Withdrawable (K type unit, phase distance 265mm)
825
265
437
767
820
265
50
350
437
463
516
13
886
53
12.5
185.5
301.5
422.5
827.5
827.5
48
340
Stroke: 310
479.5
840
210
194
447.5
746
799
110
112
636
Stroke: 300
653
13
53
170
365
403
438
524
35
21.5
19.5
89
181
345
756
770
48
310
458
VL-06/12/17/20/25
275
194
447.5
746
799
110
112
458
Stroke: 300
13
853
53
365
403
438
524
35
21.5
19.5
89
181
345
756
770
48
310
836
275
194
447.5
746
799
110
112
836
Stroke: 300
853
13
53
365
403
438
524
35
21.5
19.5
89
181
345
756
770
79
310
458
171
Dimensions - VL type
24/25.8kV 12.5/16/25kA 630/1250/2000A
Withdrawable (E type cradle Visible, Clip contact, phase distance 265mm)
Rating
A
B
630, 1250A 768 190.5
2000A
778 185.5
<Terminal conductor>
Insulation Barrier
T
10
20
<Earthing terminal>
(Earthing hole)
(Earthing hole)
(Mounting hole)
172
VL-06/12/17/20/25
Insulation
Barrier
Rating
A
B
630, 1250A 768 190.5
2000A
778 185.5
<Terminal conductor>
Insulation Barrier
T
10
20
<Earthing terminal>
(Earthing hole)
(Earthing hole)
(Mounting hole)
173
Dimensions - VL type
24/25.8kV 12.5/16/25kA 630/1250A
Withdrawable (G type cradle Tulip contact, phase distance 265mm)
174
Note) In case of phase distance 210mm ( ) means dimensions and 630A, 1250A areavailable only
Items : VCL-20K13B06, VCL-20K13B13, (G-type closed Tulip way, 630A, 1250A)
VL-06/12/17/20/25
(For assembly of
lifting hook and LV
compartment
mounting hole)
(Mounting hole)
(Mounting hole)
(Mounting hole)
(Mounting hole)
(Mounting hole)
DETAIL A
DETAIL A
SEE DETAIL A
DETAIL A
175
Dimensions - VL type
24kV25.8kV 12.5/16/25kA 630/1250A
Withdrawable (H type cradle, phase distance 275mm)
367
(For assembly of
lifting hook and LV
compartment
mounting hole)
413.4
42.3
(Mounting hole)
865
1239.5
(Mounting hole)
275.5
790
1000
35
275
275
M12(DP: 25)
960
37.5
(Mounting hole)
65
285
220 220
455
212.5
510
455
212.5
1230
310
455
455
(Mounting hole)
350.5
950
(Mounting hole)
12
20
12
Connecting busbar method
(with earthing switch)
Busbar : 10t40 (2 sheets) <1250A>
87.3
14
20
87.3
14
2- 12
30
30
10.0
2- 12
DETAIL A
DETAIL A
87.3
20
63.4
2-M8(DP: 18)
SEE DETAIL A
176
DETAIL A
VL-06/12/17/20/25
413.4
(For assembly of
lifting hook and LV
compartment
mounting hole)
42.3
M12(DP: 25)
865
1239.5
800
790
25
49
750.4
210 210
(Mounting hole)
(Mounting hole)
275.5
37.5
760
(Mounting hole)
65
285
220 220
455
212.5
530
455
212.5
1230
310
455
455
(Mounting hole)
350.5
750
(Mounting hole)
12
20
87.3
30
25
2- 12
10.0
14
DETAIL A
87.3
20
63.4
2-M8(DP: 18)
SEE DETAIL A
DETAIL A
177
Dimensions - VL type
24/25.8kV 25kA 2000A
Withdrawable (H type cradle, phase distance 275mm)
367
413.4
(For assembly of
lifting hook and LV
compartment
mounting hole)
42.3
(Mounting hole)
25
49
275
950.4
275
865
1239.5
1000
(Mounting hole)
275.5
790
37.5
960
(Mounting hole)
65
285
220 220
455
212.5
530
455
212.5
1230
310
455
455
(Mounting hole)
350.5
950
(Mounting hole)
12
20
87.3
30
25
2- 12
10.0
14
DETAIL A
87.3
20
63.4
2-M8(DP: 18)
SEE DETAIL A
178
DETAIL A
VL-06/12/17/20/25
413.4
(For assembly of
lifting hook and LV
compartment
mounting hole)
42.3
4-M 12(DP: 25)
50
79
275
950.4
275
50
(Mounting hole)
865
1239.5
790
1000
(Mounting hole)
275.5
37.5
960
(Mounting hole)
65
285
220 220
530
455
212.5
212.5
455
1230
310
455
455
(Mounting hole)
350.5
950
(Mounting hole)
12
20
25
87.3
14
25
25
30
2- 12
10.0
25
DETAIL A
87.3
20
63.1
2-M8(DP: 18)
SEE DETAIL A
DETAIL A
179
4- 14
40
20
2- 14
1250A(E, F type)
2000A(E, F type)
271
118
2-M12(Earthing hole)
60
20
150
40
150
125.5
553
4- 13
670
320
286.6
20
670
130
295
20
478
115.5
515
589
400.6
547
117
B type connector
A type connector
150
468.5
60
80
1250A
(E, F type)
2000A
(E, F type)
60
1250A
(G type)
80
2000A
(G type)
125.5
670
310
169.5
286.6
670
130
295
478
115.5
515
A type connector
180
582.5
B type connector
LVB-06/12
689
150
528
15
702.5
342.5
115.5
501
350.7
388.5
A type connector
B type connector
47
114.5 126
319.1
702.5
705.5
130
295
516
478
618
668
689
150
528
15
715.5
115.5
496
A type connector
B type connector
350.7
388.5
618
668
60
10
332.1
127.5 126
355.5
715.5
725.5
130
295
516
478
181
50
4- 14
2- 14
1250A
2000A
7- 12
(Mounting hole)
260
Rating
A
150
410
1250A
10
210
2000A
20
23.2 A
326.2
720.2
295
150
Only for
3 position type
139
87.5 90 80 90 87.5
180
180
20
525
40
20
70 105 70 105 70
180
180
40
600
790
820
940
15
2- 14
1250A
50
2- 14
7- 12
(Mounting hole)
260
Rating
A
410
1250A
10
210
2000A
20
23.2 A
326.2
720.2
295
150
50
4- 14
2000A
150
Only for
3 position type
139
20
525
40
87.5 90 80 90 87.5
180
180
20
70 105 70 105 70
180
180
40
600
182
790
820
940
15
LVB-06/12
150
150
600
560
4- 14
( )
662
295
1250A:12t
2000A:25t
1235
100
630
26
26
60
83
150
731.5
946
183
6- 14
330
69 4040
M-12(Earthing hole)
20
210
4- 13
(Mounting hole)
125.5
703
750.5
286.6
40
328.5
130
750.5
40
350
620
115.5
665
739
463.6
597
A type connector
104
M-12
(Earthing hole)
B type connector
436.5
507.5
210
125.5
750.5
303.5
129
286.6
130
750.5
360
620
115.5
665
680
A type connector
184
507.5
630
B type connector
LVB-06/12
693
210
714
16.5
348.5
115.5
687
A type connector
B type connector
321.7
450.6
624.7
674.4
60
10
331.6
140.2 135.6
130
795.5
805.5
795.5
360
690
620
693
210
714
16.5
795.5
348.5
115.5
687
A type connector
B type connector
321.7
450.6
624.7
674.4
60
10
331.6
140.2 135.6
130
795.5
805.5
360
690
620
185
50
50
80
139
675
50
(Earthing hole)
50
4-M12 DP25
7- 12
(Mounting hole)
210
265
530
135
23.4
309.7
360
940.2
210
750
825
877
930
15
Withdrawable (F cradle)
Only for
3 position type
50
50
80
139
50
(Earthing hole)
4-M12 DP25
210
7- 12
(Mounting hole)
265
530
135
23.4
309.7
940.2
210
750
186
825
877
930
15
LVB-06/12
Stroke:240
(Earthing hole)
187
LVB-06/12
210
800
760
210
145
120
70
35
230
Mounting hole
724
12
439
360
12
764
1014
188
1100
100
Dimensions - VH type
VH-06/12/17/20/25/36/40
25
2-M12 (DP:25)
816
130
862.5
610
M12
108
285
(Earthing hole)
94
144
115.5
360
602
695
137
653
Racking in/out
Stroke:220
725
12
353
72
447
53
380
193.5
42
412
3.5
89
335
130
48
340
644
656
189
Dimensions - VH type
7.2/12/17.5kV, 50kA, 1250/2000A
Withdrawable (H cradle, phase distance 210mm)
317
378.4
2-M12 (DP:25)
49
210
210
(For assembly of
lifting hook and LV
compartment
mounting hole)
25
42.3
187
780
1073
750
705
710
37.5
(Mounting hole)
65
285
200
200
212.5
212.5
565
450
450
1325
340
450
450
(Mounting hole)
217
(Mounting hole)
12
30
12
20
60
84.3
Connecting busbar method
(with earthing switch)
Busbar : 12t60 (1 sheet) <1250A>
TUBE
30
20
60
84.3
TUBE
84.3
20
63.3
2-M8 (DP:18)
See Detail A
190
Detail A
VH-06/12/17/20/25/36/40
50
4-M12 (DP:25)
79
50
130
862.5
750
M12
108
285
(Earthing hole)
115.5
786
864
94
114
360
602
695
142
12
Racking in/out
Stroke:220
725
353
89
193.5
380
869.5
335
130
340
844
53
3.5
42
400
447
656
191
Dimensions - VH type
7.2/12/17.5kV, 50kA, 2500/3150A
Withdrawable (H cradle, phase distance 275mm)
352
413
30
4-M12 (DP:25)
(Mounting hole)
50
4-M12
(For assembly of
lifting hook and LV
compartment
mounting hole)
50
(Mounting hole)
239.5
825
1167
1000
750
950
37.5
(Mounting hole)
212.5
212.5
565
450
450
1325
340
450
450
(Mounting hole)
60
300
210
230 264.5
(Mounting hole)
12
25
25
30
TUBE
25
TUBE
25
25
25
12
20
100
30
90.8
20
80
90.8
90.8
20
49.4
2-M8 (DP:18)
See Detail A
192
Detail A
VH-06/12/17/20/25/36/40
2-M12
Earth TAP
330
44
30.5
179.5
275
923
4- 13
Mounting Hole
286.5
906
65
859
959
147
341
134
286.6
130
400
65
4-M12
Busbar TAP
120
Terminal Diameter
113.5
615.1
193
Dimensions - VH type
7.2/12kV, 40/50kA, 4000A
Withdrawable (K cradle, phase distance 275mm)
(Earthing hole)
(Mounting hole)
194
VH-06/12/17/20/25/36/40
320
214
4-M12 (DP:25)
834
130
750
110.5
287.5
M12
(Earthing hole)
118
174
115.5
786
864
142
853
12
Racking in/out
Stroke:310
857
850
53
497
535
788
3.5
41.5
335
80
225
440
130
340
445
195
Dimensions - VH type
24kV, 25kA, 2500A
Withdrawable (H cradle, phase distance 275mm)
352
558
30
(Mounting hole)
275
275
50
4-M12 (DP:25)
4-M12
(For assembly of
lifting hook and LV
compartment
mounting hole)
1000
970
(Mounting hole)
240
1312
895
37.5
50
950
212.5
212.5
625
500
500
1380
340
500
(Mounting hole)
500
(Mounting hole)
60
300
280
300
270
(Mounting hole)
90.3
20
25
25
30
12
80
25
TUBE
90.3
20
49.4
2-M8 (DP:18)
See Detail A
196
Detail A
VH-06/12/17/20/25/36/40
2-M12 (DP:25)
130
610
115.5
110.5
287.5
M12
(Earthing hole)
118
174
137
653
12
Racking in/out
Stroke:310
857
652
497
535
53
788
3.5
41.5
335
80
225
440
130
340
445
197
Dimensions - VH type
24kV, 31.5/40kA, 1250/2000A
Withdrawable (H cradle, phase distance 210mm)
352
558
30
210 210
4-M12
(For assembly of
lifting hook and LV
compartment
mounting hole)
25
(Mounting hole)
800
970
(Mounting hole)
239.5
1302
895
37.5
2-M12 (DP:25)
750
(Mounting hole)
60
300
280
300
212.5
212.5
625
500
500
1380
340
500
500
(Mounting hole)
269.5
(Mounting hole)
85.8
Connecting busbar method
(with earthing switch)
Busbar : 12t60 (1 sheets) <1250A>
20
Connecting busbar method
(with earthing switch)
Busbar : 12t60 (2 sheets) <2000A>
30
30
12
12
20
60
60
85.8
TUBE
TUBE
85.8
20
49.4
2-M8 (DP:16)
See Detail A
198
Detail A
VH-06/12/17/20/25/36/40
970
25
210 210
2-M12 (DP:25)
239.5
1302
800
895
37.5
750
(Mounting hole)
500
212.5
625
500
212.5
1380
340
500
500
(Mounting hole)
60
300
280
300
269.5
(Mounting hole)
199
Dimensions - VH type
24kV, 31.5/40kA, 1250/2000A
Fixed (P type, phase distance 275mm)
2-M12 (DP:25)
130
750
110.5
287.5
M12
(Earthing hole)
115.5
118
174
142
853
12
Racking in/out
Stroke:310
857
850
497
535
53
200
788
3.5
41.5
335
80
225
440
130
340
445
VH-06/12/17/20/25/36/40
558
30
(Mounting hole)
275
25
4-M12
(For assembly of
lifting hook and LV
compartment
mounting hole)
275
2-M12 (DP:25)
1000
970
(Mounting hole)
239.5
1302
895
37.5
950
(Mounting hole)
60
300
280
300
212.5
212.5
625
500
500
1380
340
500
500
(Mounting hole)
269.5
(Mounting hole)
85.8
20
30
12
60
TUBE
85.8
20
49.4
2-M8 (DP:18)
See Detail A
Detail A
201
Dimensions - VH type
24kV, 31.5/40kA, 3150A
Fixed (P type, phase distance 275mm)
4-M12 (DP:25)
(Mounting hole)
130
750
110.5
287.5
M12
(Earthing hole)
115.5
118
174
786
864
142
853
12
Racking in/out
Stroke:310
857
850
497
535
53
202
788
3.5
41.5
335
80
225
440
130
340
445
VH-06/12/17/20/25/36/40
558
30
(Mounting hole)
275
275
50
4-M12 (DP:25)
4-M12
(For assembly of
lifting hook and LV
compartment
mounting hole)
1000
970
(Mounting hole)
240
1312
895
37.5
50
950
212.5
212.5
625
500
500
1380
340
500
(Mounting hole)
500
(Mounting hole)
60
300
280
300
270
(Mounting hole)
90.3
20
25
25
30
12
100
25
TUBE
90.3
20
49.4
2-M8 (DP:18)
See Detail A
Detail A
203
Dimensions - VH type
36kV, 25/31.5/40kA, 1250/2000A
Fixed (P type, phase distance 300mm)
M12
551.5
(Earthing hole)
115.5
220.1
294.1
1042.5
(Mounting hole)
204
8.5
8.5
Racking in/out
Stroke:440
VH-06/12/17/20/25/36/40
466
43
11-M8
20
Mounting hole
221.5 221.5
300
1150
1100
900
570
300
300
Mounting TAP
300
61
402
300
180 255
24
300
40
6-M5
288
1200
1100
300 300
A
Mounting TAP
270
270
(symmetrically)
23.5
Mounting hole
9-M8
7
40
485
216.5
216.5
400
53.5
104
604
15
901
649
360.5
25
608
1194
66
127.5 30
300
300
300
24-M8
Mounting TAP
53.5
300
40
365
30
300 300
1160
290
285
285
488
300
Mounting hole
290
203.8
734
Mounting hole
2140
52
14
30 40
See Detail A
140
140
480
600
480
600
2200
A
740
846
60
2165
2150
480
288
480
Mounting TAP
60
Mounting hole
45
65
14
6-M8
Mounting TAP
205
Dimensions - VH type
36kV, 25/31.5/40kA, 3150A
Fixed (P type, phase distance 300mm)
M12
551.5
(Earthing hole)
115.5
220.1
294.1
1042.5
(Mounting hole)
206
8.5
8.5
Racking in/out
Stroke:440
VH-06/12/17/20/25/36/40
466
300
14
40
25
40
1200
221.5
12
10
300
296.5
201.5
505
A
61
140.5
563
127.5
30
463
25
Remove both side of shrink tube
for bolting busbar when using Cu PIPE
14
110
40
30 40
203.8
855
10
STS HEX M8X70 BOLT
7
BUSBAR: 110 X 12t
19
28.5
1226.7
120
46
56.12
740
846
873.4
290
50.5
1520
400
2200
8.5
25
1194
568
66
14(Earthing hole)
203.8
104
604
28.5
See Detail A
185 300
563
300
207
Dimensions - VH type
40.5kV, 25/31.5kA, 1250/2000A
Fixed (P type, phase distance 300mm)
300
157
247
300
50
914
50
420
M12
(Mounting hole)
830
551.5
(Earthing hole)
115.5
1.5
220.1
294.1
130
136.5 107
1042.5
400
392
866
944
500
837
157
207
570
Racking in/out
Stroke:440
208
52
65
104
463.6
487.4
1015
8.5
844
866
910
965
623.6
140
403
115.5
8.5
697.6
955
1446
130
136.5 107
400
830
300
VH-06/12/17/20/25/36/40
300
247
300
80
914
80
420
M12
(Mounting hole)
830
551.5
(Earthing hole)
115.5
1.5
294.1
130
1042.5
400
392
866
944
500
837
157
207
570
Racking in/out
Stroke:440
463.6
487.4
1015
8.5
52
65
104
623.6
403
844
866
910
965
8.5
697.6
955
1446
130
136.5 107
400
830
300
209
VL-25 16B 06
Item
Rated voltage
Rated normal current
Rated frequency
Rated short-circuit breaking current
Ur (kV)
25.8
Ir (A)
630
fr (Hz)
50/60
Isc (kA)
16
Ik (kA)
16
(MVA)
665/715
Ip (kA)
40/41.6
(cycle)
Rated withstand
Ud (kV)
60
voltage
Impulse (1.250)
Up (kV)
125
O-0.3s-CO-3min-CO
Closing coil
(V)
Trip coil
(V)
Auxiliary contact
5a5b
(sec)
0.04
(sec)
0.06
Mechanical
M1
Electrical
E1
C1
Lifetime *
Mechanical
(time)
Electrical
(time)
2,000
Installation
Fixed
Right
R type
Left
L type
(mm)
CB
Standards
* Lifetime with maintenance
210
(kg)
2,000
210
95
IEC 62271-100
CS
M
C
A2
A3
LS2
P
D1
A4
10
A5
52a
Note1)
A6
D2
C : Closing coil(CC)
UVT : Under Voltage Trip
52a : Auxiliary switch (a)
52b : Auxiliary switch (b)
TC
UVT
Auxiliary switch
5a
22 24 26 28 40
22
24
26
28
40
36
38 50
23
25
27
29
41
37
39
23 25 27 29 41
5b
36 38 50 52 54
52
54
51 53
55
37 39 51 53 55
A6 10 D2
A1 A3
A5
23
25
27 29 41
37 39 51
53
55
22
24
26 28 40
36 38 50
52
54
B
D1
(5a5b)
210
210
210
145
Dimension
210
600
605
120
212.5
M10-DP 25
100
38.5
355.5
818
873
169
300
1000
M10-DP 20
Ordering information
25
VL
Basic model name
e-VCB
25
Installation type
25.8
VL-2516B06
Motor control voltage
M1
C1
M0
Without Motor
C0
T0
M1
DC 110V
C1
DC 110V
T1
DC 110V
M2
DC 220V
C2
DC 220V
T2
DC 220V
M3
DC 125V
C3
DC 125V
T3
M4
DC 24V~30V
C4
DC 24V~30V
T4
M5
DC 48V~60V
C5
DC 48V~60V
M6
AC 48V
C6
AC 48V
M7
AC 100V~130V
C7
M8
AC 200V~250V
C8
16
Breaking
Phase distance/Compatibility
16
16
T1
210mm
SA5
06
06
680
AAB
U1
Other accessories
UVT
A type connector,
U0
Without UVT
AA
Lead Wire
5a5b
U1
DC 110V
AB
User Plug(Part)
U2
DC 220V
DC 125V
U3
DC 125V
DC 24V~30V
U4
DC 24V~30V
T5
DC 48V~60V
U5
DC 48V~60V
T6
AC 48V
U6
AC 48V
AC 100V~130V
T7
AC 100V~130V
U7
AC 100V~130V
AC 200V~250V
T8
AC 200V~250V
U8
AC 200V~250V
SA5
211
Technical data
Number[ops.]
Number[ops.]
Number[ops.]
Number[ops.]
N : Operation numbers
I : Interrupting current
212
Number[ops.]
Number[ops.]
Number[ops.]
N : Operation numbers
I : Interrupting current
Note) 1. Above graphs represent the characteristics of the electrical life of LS Susol VCB.
2. Life characteristics of each model in each rating represents the LOG-LOG graphs.
213
Technical data
214
The circuit breaker is designed for use in standard use environment specified in Section 2. 1 of IEC62271-1.
Concerning the special use environments as below the special use conditions are
required to be considered, thus please contact us in advance.
- where altitude and ambient temperature are out of standard use environment.(-40)
- where a strong sea breeze blows
- when usually used in a humid place
- where a lot of steam or oil steam exists
- where explosive, flammable and other harmful gases might permeate the breaker
- In a dusty place
- where abnormal vibration or shock exists
- where a lot of ice and snow exist
- other special conditions
70
36
50(65)
24
38
170
125
17.5
95
28(42)
12
75(82)
20
7.2
60
Ud [kV/1min]
Power Frequency
Withstand Voltage
Ur[kV]
Up [kV/1.2
50
215
Technical data
Special Use Environment
Correction parameter 1
1500
2000
2500
3000
3500
4000
Altitude (m)
Correction parameter 2
<Fig.1 > withstand voltage correction parameter 1 by altitude (based on a required withstand voltage)
1
0.95
0.9
0.85
0.8
0.75
0.7
0.65
0.6
0.55
0.5
1000
1500
2000
2500
3000
3500
4000
Altitude (m)
<Fig.2 > withstand voltage correction parameter 2 by altitude (based on a applicable withstand voltage)
Ex) Selecting a breaker to be used in a place of 2500m above sea level with a rated voltage 7.2kV
(correction parameter 1 applied)
- correction parameter at 2500m is 1.2
- criteria of withstand voltage by rated voltage:
Power Frequency Withstand Voltage (Ud) = 20kV, Impulse Withstand Voltage (Up) = 60kV
- requirements withstand voltage criteria:
Power Frequency Withstand Voltage (Ud) = 201.2 = 24kV, Impulse Withstand Voltage (Up) = 72kV
Therefore rated voltage 12kV breaker shall apply to satisfy the required withstand voltage.
Ex) To apply a breaker with a rated voltage 12kV to the place of 2,500m above sea level
(correction parameter 2 applied)
- correction parameter at 2500m is 0.825
- dielectric strength of VCB : Power Frequency Withstand Voltage (Ud) = 280.825 = 23.1kV,
Impulse Withstand Voltage (Up) = 750.825 = 62kV/1.250
Therefore above breaker with rated voltage 12kV shall apply to rated voltage system 7.2kV at the altitude.
216
Ambient temperature ()
Rated current (A)
20
25
30
35
40
45
50
55
60
4000
4000
4000
4000
4000
4000
3843
3679
3508
3328
3150
3150
3150
3150
3150
3150
3026
2898
2763
2621
2000
2000
2000
2000
2000
2000
1922
1840
1754
1664
1250
1250
1250
1250
1250
1250
1201
1150
1096
1040
630
630
630
630
630
630
605
580
553
524
4500
4000A
4000
3500
3150A
3000
2500
2000A
2000
1250A
1500
1000
630A
500
0
20
25
30
35
40
45
50
55
60
Ambient temperature()
217
Technical data
Comparison of GCB & VCB
In the system of medium voltage lines VCB uses a vacuum which is an eco friendly medium for arc extinguishing.
It also offers excellent interrupting properties and ease of maintenance and has expanded the area to the scope of the
GCB as the overlap increases.
Items
GCB
VCB
Comparison
results
Remarks
Images
VI
Arc extinguish
medium and
characteristics
SF6 gas
- Greenhouse gas that causes
global warming.
- The toxic gas generated by chemical
Vacuum
- Green clean medium.
- 510-5 Torr vacuum rate to
maintain.
VCB is
better than
GCB
of the
arc media
better than
When an accident occurs the
trip-first feature
GCB
range (kV)
3.6~550
3.6~36
better than
VCB
Applicable rate
VCB is
of transient
Low
High
recovery voltage
better than
GCB
(RRRV)
Development
and trends
Decline
- Company M discontinued producing GCB.
- Company A manufactures
VCB in medium voltage GCB
production factory.
- GCB Maker S started the
production of VCB.
218
Increasing
- Companies A and S have
developed new VCBs.
- Development trend that the voltage
coverage of VCB expands.
- VI increased coverage.
(GIS, DAIS, SIS, etc.)
VCB is
better than
GCB
For your safety, please read user's manual thoroughly before operating.
Contact the nearest authorized service facility for examination, repair, or adjustment.
Please contact qualified service technician when you need maintenance.
Do not disassemble or repair by yourself!
Safety Instructions
Any maintenance and inspection shall be performed by the personnel having expertise concerned.
HEAD OFFICE
LS-ro 127 (Hogye-dong) Dongan-gu Anyang-si
Gyeonggi-do Korea
Tel. (82-2)2034-4840, 4911, 4914
Fax. (82-2)2034-4648
www.lsis.com
Global Network
LSIS USA Inc.
Chicago, America
Address: 2000 Millbrook Drive, Lincolnshire, Chicago, IL 60069, United States of America
Tel: 847-941-8240 Fax: 847-941-8259 e-mail: seungheonc@lsis.com
CHEONG-JU PLANT
Cheong-Ju Plant #1, 95 Baekbong-ro Heungdeok-gu
Cheongju-si Chungcheongbuk-do 361-720 Korea
2014. 04