SPECIAL MATERIAL DATA SHEET

FLAME ARRESTOR

PROJECT NO.
PROJECT TITLE

TAG:
DOC NO

CLIENT

DATE

LOCATION

SHEET NO.

Item

Rev

Title

Notes Units

Design Data

GENERAL DESIGN CONDITIONS


101

Description/Type

text

Detonation Flame Arrestor (DFA)

102

Inlet Nozzle N1

mm

150 NB

103

Oulet Nozzle N2

mm

150 NB

104

Drain

mm

3/4"

105

Instrument Nozzle

mm

ASTM A105 ,RF CL150, Refer NL693507/M.02/003


Rev P

106

Quantity

No

107

Location

text

Engineering Flow Diagram Vent Stack Dwg No :188066P

108

Design Code

text

ASME B31.3 / ASTM F1273

109

ASME Rating

text

CL150

110

End Connection / Facing

111

Dimension (face-to-face)

112

Installation
Installation Distance from
Potential Ignition Source

113

text

Flanged-RF, As per ASME B16.5

mm

Vendor to Specify

Text

Horizontal / Vertical /Other

MTR

Piping to provide

MATERIALS
201

Body (Housing)

text

ASTM A105 / ASTM A234 WPB

202

Internal Elements

text

SS316

203

Lifting Lugs

text

Required

204

Bolting

text

As per Mfg. Std. ASTM A193 Gr B7 and 2 Heavy Hex


Nuts to ASTM A194 Gr 2H to ASME B18.2.1/ B18.2.2

PROCESS CONDITIONS
301

Gas / Vapor

Text

Gas

302

Composition

Text

Paraxylen Vapors / HC Vapors

303

Operating Pressure (Min)

Bar(g) 0

304

Operating Pressure (Max)

Bar(g) 0

305

Operating Pressure
(Normal)

Bar(g) 0.012

306

Design Pressure (Upper)

Bar(g) 14.8

307

Design Pressure (Lower)


Operating Temperature
(Min)

Bar(g) 0

308
309

Operating Temperature
(Max)

20

35

311

Operating Temperature
(Normal)
Design Temperature(Upper)

312
313
314

Flowrate (Max)

M3/Hr 1200

315

Flowrate (Operating)

M3/Hr 450

316

Gas Group Rating

Text

IIA

310

20

70

Design Temperature(Lower)

-15

Pressure Drop (Allowable)

Bar

OPTIONS
401

Pressure Tap

Text

402

Temperature Probe Fitting

Text

Required , Refer Refer NL693507/M.02/003 Rev P

403

Drain Plug

Text

Required , Refer Refer NL693507/M.02/003 Rev P

404

Coating

Text

Required , Refer Refer NL693507/M.02/003 Rev P

405

Other

Text

1 of 2

Supplier Data
(Note B)

1 OF 1

Operation Data

Item

Rev

Title

Notes Units

Design Data

Supplier Data
(Note B)

Operation Data

TESTING
501

Testing

text

As per ASTM F1273

502

NDE

text

as per Manufacturing

503

Applicable Test Protocols

text

UL / FM /CEN /USCG /Others

504

Listing Requirement

text

UL Listed / FM Approved

505

Material Certification

text

BS EN 10204 Type 3.1

text

MSS SP-25

SPECIAL REQUIREMENTS
601

Marking

602

Painting

603

Intrument Connection

604

Insulation

605

Electrical Tracing

606

Supplementary
Requirements

text

Refer NL693507/M.02/003 Rev P


Refer NL693507/M.02/003 Rev P
Yes
Yes

text

Refer NL693507/M.02/003 Rev P

MANUFACTURER DELIVERABLES
701

Certified Drawings

702

Certified Flow Curve

text

Required

703

Weight

704

Calculations

Required

705

Catalogue

Required

706

Installation & Maintenance


Manual

Required

Required
kg

Required

REFERENCE
601

Fluid Service

text

Paraxylen Vapors / HC Vapors

602

Manufacturer(s)

text

603

Piping Material Class


Specifications

text

G1A-41 & G1K-3

604

P&ID

text

Engineering Flow Diagram Vent Stack Dwg No :188066P

NOTES
A

Refer doc :Refer NL693507/M.02/003 Rev P for all process requirements.

"Supplier Data" fields to be completed by the Supplier. The Supplier shall note any non compliance in the "Supplier Data" column.

Flame Arrestor to have a non-corrosive metal tag wired, indicating size & Tag number

Vendor to provide material certificate, inspection and testing certificate

Flanges shall be as per ASME B16.5

Flame arrester housing shall be gas tight to prevent the escape of vapors.

The net free area through flame arrester elements shall be at least 1.5 times the cross-sectional area of the arrester inlet.

DETONATION FLAME ARRESTER MAY BE EXPOSED TO INSTANTANEOUS PRESSURE SPIKES IN EXCESS OF 1000 PSIG. ANY INSTRUMENTATION
ATTACHED TO THE ARRESTER MUST BE CAPABLE OF CONTINUED OPERATION IN THIS ENVIRONMENT

2 of 2