Documente Academic
Documente Profesional
Documente Cultură
ACKLOWLEDGMENTS
This academic report on the Post Occupancy Evaluation of the John Payne Building could not have been produced
without the support and valuable knowledge of the John Payne in-situ staff and the Oxford Brookes Universitys
POE 2011 academia. I would like to thank all those involved in the survey and data collection, in particular:
OBU Energy and Carbon Manager, Gavin Hodson: for the guided site visit and all data assistance;
OBU Operations and Maintenance, Gareth Eddy: for the systems walk through and knowledgeable insights into the
system workings;
Capital Projects Manager, Andrew Moore: for the invaluable as-designed data;
OBU CAD Officer, Harj Dharwar: for all the drawings provided.
And most importantly, Prof. Rajat Gupta and Matthew Gregg: for their time, guidance and support with the Post
Occupancy Evaluation methodology and workflow.
TABLE OF CONTENTS
ACKLOWLEDGMENTS ................................................................................................................................................ i
LIST OF TABLES ........................................................................................................................................................ iii
LIST OF FIGURES ...................................................................................................................................................... iv
1
1.1
INTRODUCTION ................................................................................................................................................ 1
Objectives .................................................................................................................................................... 1
METHODOLOGY ............................................................................................................................................... 2
4.1
4.2
4.3
4.4
4.5
4.6
5.1
5.2
5.3
OCCUPANT FEEDBACK.................................................................................................................................... 20
6.1
6.2
Interviews .................................................................................................................................................. 24
CONCLUSION ................................................................................................................................................. 25
RECCOMENDATIONS ...................................................................................................................................... 26
8.1
8.2
8.3
10
REFERENCES ................................................................................................................................................... 28
11
APPENDIXES ................................................................................................................................................... 29
12
ATTACHMENTS .............................................................................................................................................. 43
ii
LIST OF TABLES
iii
LIST OF FIGURES
iv
INTRODUCTION
This Post-occupancy evaluation study is undertaken within the POE Module 30405 of the MSc Sustainable Building: Performance
& Design course at Oxford Brookes University. This course module, under Professor Rajat Gupta, is pioneering in POE training
and research in the UK.
Assessing Building Performance defines Post-occupancy evaluation (POE)
...as the act of evaluating buildings in a systematic and rigorous manner after they have been built and
occupied for some time. (Prieser & Vischer 2005, p8).
The subject of this POE study is the John Payne Building on Oxford Brookes Headington Campus, completed and occupied
during 2010. In some respects this building is a prototype where much of the building method and technology to be deployed
on the on-going reconstruction of the campus can be road-tested. In this context, the timing of this POE study, though
comparatively early in its occupation, may be of significant value for specific feedback to the buildings currently on site.
The three story John Payne building houses the main Headington campus workshops on the ground floor, including the
Technology Lab and Architectural Workshops, with two floors of office, open-plan around a single core, above. This is the new
home of the Universitys Estates and Facilities Management department, along with Capital Projects, Hospitality, Property
Services, CAD and the OBU Sustainability team.
1.1
Objectives
The POE brief is defined by Probe (Post-occupancy review of buildings and their engineering) team to answer four broad
questions:
How is this building working?, Is it intended?, How can it be improved?
and How can future buildings be improved? (Bordass & Leaman 2005, p72).
One of the key findings established by the Probe process and other POE studies is the divergence between design forecast and
actual energy use [Figure 1]. A large contingent of this is likely to be from unregulated energy, outside that regulated by Part L
of the Building Regulations.
METHODOLOGY
The format for POE in the UK, as pragmatically developed for the Probe process (1995-2002), consists of three interrelated
study areas: the audit, survey and analysis of pre-existing energy use data, site survey and in-use monitoring of environmental
data, and occupant feedback surveys through questionnaires and interviews.
The POE workflow for this study is illustrated below in Figure 2:
This study sets out to evaluate how the John Payne Building is actually performing, whether this accords with the design intent,
if there is scope for immediate, short or long term improvements (relative to cost) and whether any conclusions can be fedforward to future build. The process consists of following the Energy [Figure 3] and Environmental Audit [Figure 4] workflows,
which in sum is the evaluation of all data, services and environmental conditions, and finally the Occupant Survey [Figure 5]
workflow.
Results of this analysis can then be benchmarked against equivalent buildings and appropriate standards, conclusions drawn
whether the building is performing as intended, whether immediate, short term or long term interventions can be
recommended and whether these outcomes can be fed-forward to future build.
BUILDING DATA
PROJECT DETAILS
INPUT DATA
Name:
Completion Date:
2010
2
1,380
1,282
Location:
Thames Valley
2,205
Naturally-ventilated
ENERGY DETAILS
(without any weather, exposure, occupancy correction) Areas refer to treated floor area.
Year of electricity and gas data:
04.2010 03.2011
Actual unadjusted electricity use (kWh/year):
2
66,205
52
7,729
6
None
95 (typical TM46)
20.36C
21.57C
21.99C
49.6 RH
49.88 RH
49.33RH
70.9 lux
294.36 lux
10.3C
4.1
ENERGY AUDIT
Pre-Survey Calculations
During this stage available existing data is collected and analyzed, quantifying known energy use and identifying anomalies. This
serves to establish the research parameters for the following walk around survey and in-use monitoring. Pre-existing data is
then assessed and evident patterns of energy consumption or potential wastage are established.
Electricity Consumption
Table 2 Sankey Diagram showing Electricity use in percentages from the total energy consumption.
The main energy consumption pattern in the John Payne building comes from electricity consumption, mainly for ICT and
lighting use, as is clearly demonstrated on Table 2 above. This will be further analyzed in the upcoming sections.
Gas Consumption
Table 3 Sankey Diagram showing Gas consumption in percentages from the total energy consumption
The gas consumption amounting to a very small proportion, relative to hot water and space heating, , as can be seen on Table 3.
These two Sankey diagrams relate to one another in proportion, with electricity taking up 93% of the total energy consumption
and gas only 7% of the total.
T = C
500
400
Degree Days
(DD)
Heating
kWh
2,500
2,000
300
1,500
200
1,000
100
500
0
APR MAY JUN JUL AUG SEP OCT NOV DEC JAN FEB MAR
Table 4 Heating Requirements versus Degree Day Data (APR 2010 - MAR 2011). Degree Day Data by Carbon Trust 2011
The comparison illustrates how the internal temperature heating requirement follows the degree days consistently throughout
the year. This implies that in general, the John Payne building follows the UK standard heating requirements and no major
discrepancies can be observed.
Compiling comparative scatter plots and control charts of monthly space heating consumption against Degree Days will show
the seasonal variations of energy use patterns. The statistical cumulative sum (CUSUM) chart will illustrate consumption
patterns highlighting where the building performs best or worst.
Heating kWh
2,500
R2 0.85 = EXCELLENT
y = 4.9809x - 264.53
R = 0.93981
2,000
1,500
1,000
500
0
-500
50
100
150
200
250
300
350
400
450
Degree Days
Table 5 Regression Analysis (APR 2010 - MAR 2011)
The trend line [y = mx + c] implies when DD = 0 the Internal space Gas hearing requirement is a minus value, or is not required.
This does not mean however, that there is a surplus of heating/kWh when the y axis reaches negative. According to the
performance indicator (R2), the John Payne building performs at an excellent rate, in terms of heating/kWh versus heating
Degree Days.
6
300
200
100
kWh 0
-100
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
DEC
JAN
FEB
MAR
-200
-300
Table 6 Control Chart (actual versus predicted) gas consumption (Apr 2010 - Mar 2011)
On Table 6, the rise of kWh/use in July implies that summer months perform badly, despite energy consumption at a minimum
0, this is because the constant (y=mx+C) is negative (- 264.53 kWh). The negative areas of the graph highlight the most energy
efficient months within John Payne, which are May and November (marked in green).
200
FEB
100
kWh 0
-100
-200
AUG
APR
JUL
-300
-400
JUN
JAN
OCT
MAR
DEC
SEP
NOV
MAY
-500
Table 7 CUSUM Chart (Apr 2010 - Mar 2011)
This graph would be flatter compared other building performance. This is due to the y scale being relatively small; the good and
bad performance is exaggerated. Downward trends imply energy efficient months, while upward trends expose less energy
efficiency. It is not possible for John Payne to perform any better during summer months as its Gas requirement is already
minimal 0.
4.2
Building Fabric
The building fabric (roof/ground floor/glazing/walls) and corresponding U-values are used for the design heat loss calculations
and thermal loads. These calculations will also be checked with reference to available construction drawings and related to
other factors such as orientation and internal layout.
Since there was no data available on the exact U-values for the Fabric of the John Payne Building, estimates were made using UK
manufactures standard specifications [Table 8]. Through these findings, the building fabric heat loss can be calculated.
SOURCE
IES Modeling from available info
IES Modeling from available info
IES Modeling from available info
MagHansen Fenster/Fasad
MagHansen Fenster/Fasad
MagHansen Fenster/Fasad
Assumed worst case Part L 2006
Worst case from available construction info
MATERIAL
External Walls
Ground Floor
Roof
Glazing
External Doors
Roof Lights
Roller Doors
external upper floor
W/m2 oC
0.198
0.132
0.177
1.300
1.300
1.300
1.500
0.200
The most relevant of these values were then benchmarked against Max Fordhams Sustainability Matrix for Green Office
AJ/2010 for a better insight on their efficiency value, as Table 8 through to Table 11 illustrate.
ROOF
U-Value
0.05
0.1
0.15
0.2
0.25
0.3
Series1, 0.177
GROUND FLOOR
U-Value
0.05
0.1
0.15
0.2
0.25
0.3
2.5
Series1, 0.1324
GLAZING U-Value
0.5
1.5
Series1, 1.3
WALLS
U-Value
0.05
0.1
0.15
0.2
0.25
0.3
0.35
0.4
Series1, 0.1981
U-value = W/m2C
V = m3
13%
12%
1%
floor
10%
susp. floor
building
fabric
external walls
15%
28%
glazing/doors
ventilation
roller doors
5%
roof
26%
90%
rooflights
Heat loss through building fabric: using the [Qf formula] findings were reached showing a high percentage of heat loss through
the external walls (10,249 kWh/annum at 28%), and the glazing (9,683 kWh/annum at 26%). The remaining values from highest
to lowest are, respectively, from the roof (5,551 kWh/annum at 15%), the roof lights (4,917 kWh/annum at 13%), the ground
floor (4,438 kWh/annum at 12%), the roller doors (2,050 at 5%), and finally, the suspended floor with green-roof sedum cover
(326 kWh/annum at 1%). The green roof could account for an added insulation for the suspended roof, but which could not
benefit from a negative value, or lower than 0% [Table 13].
Heat loss through ventilation: using the [Qinf. Formula] and the air change for typical naturally ventilated office at 3m3/h/m3 (as
advised by Prof. R Gupta), the heat loss through building fabric amounts to 37,215 kWh/annum, which corresponds to 10% of
the total, where heat loss through ventilation amounts to an astounding 351,838 kWh/annum, which corresponds the
remaining 90% of the total [Table 14].
4.3
The Normalized Performance Indicator (NPI) for John Payne Building is calculated to allow objective comparison of this building
against benchmarks, whilst taking into account energy use data, the weather exposure and occupancy. A bottom-up approach
(CIBSE, 2004) for detailed end-use building benchmarking standards is then used and specific elements are evaluated, as
appropriate, with reference to:
1282
2250
m2
per annum
7729
66205
73934
kWh/annum
kWh/annum
kWh/annum
2189
Weather correction
9693
kWh/ annum
Exposure correction
Weather corrected total
9562
75767
kWh/ annum
kWh/ annum
82467
kWh/ annum
gas
kWh/m2/annum
electricity
NPI total
56
64
kWh/m2/annum
kWh/m2/annum
gas
electricity
Unadjusted total
6
52
58
kWh/m2/annum
kWh/m2/annum
kWh/m2/annum
Benchmarks
0
50
100
150
200
250
gas
John Payne
(unadjusted)
6
John Payne
(normalized)
8
52
56
54
95
electricity
Table 15 JP Benchmarks against CIBSE TM46 Typical Office 2006, and Good Practice Guide F 2004
Against the established CIBSE benchmarks, the John Payne performs well [Table 15]. However these benchmarks are set against
a general typical office. Against current and future projected benchmarking (relative to current and anticipated Part L
2010/13/16/19), John Payne achieves only minimum standard [Table 16], but it also only required to reach the Part L 2006
benchmark.
0
5
10
15
20
25
30
35
kgCO2/m2/year
minimum standard (2010)
30
21
8
zero carbon
31
28
Table 16 Benchmark against Sustainability Matrix - Green offices [Max Fordham/AJ 2010]
tonnes CO2/annum
tonnes CO2/annum
tonnes CO2/annum
kgCO2/m2/annum
typical office
10
20
30
40
50
60
70
80
heating & h/w
other electricty
good practice
John Payne (re-adjusted*)
Table 18 benchmark against Econ19 (*normalized electric h/w CO2 added to normalized gas heating CO2)
actual use
7,729
design estimate
10,800
66,205
91,800
design brief
actual occupancy
90
41
Table 20 Design brief versus actual occupancy
4.4
Building Operation
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]
Maintenance Workshop possible fire hazard due to impromptu bicycle and clothes storage
Entrance hall improper bike storage under stairwell
Boiler Room detail of electrical fittings
Maintenance Workshop lights on unnecessarily: no users
Maintenance Workshop detail of light fittings
Hall excessive heating of unoccupied and small area
Maintenance Workshop wide window area with high daylight permeability under-used
Boiler Room detail of properly installed (perceived) and organized heating and electric systems
Lounge adapted lounge, adjacent to Maintenance Workshop, users have no outside views, natural light or ventilation.
If the lounge space (where users can rest their eyes and minds by looking into the landscape) was switched with the
maintenance workshop (where users need controlled lighting levels and are looking into the desk to concentrate) the
psychological benefits to the users could improve their work performance.
Lounge materials and layout of the kitchen in the lounge is non-appealing, non-functional (odour/heat), and possibly
dangerous: due to the light fittings right above and proximity to the boiler room.
[01]
[02]
[03]
[04]
[05]
[06]
[07]
[08]
[09]
West Office adaptation: blinds have been installed due to outside glare
West Office dominant south west wind has been known to gust thorough the window, re-organizing nearby desktops
West Office the passive ventilation system works by convection causing nearby users to feel the outside weather as-is and
causing discomfort. Lighting controls are motion automated and not always sense a lone user.
West Office nearby construction site is a major source of unwelcome noise and dust in the office.
Although the offices are under populated (41/90), the layout does not always benefit the user: positioning them in locations
where noise/wind/insolation can reach them.
Connecting Hall adaptation: lights installed have no functional use (aside from aesthetics) and appear to be non-energy
efficient.
Connecting Hall panoramic detail of passive ventilation and light fittings
East Office automated windows near desktops may create unwanted environment interactions with users. The lighting
scheme sometimes lights areas with much higher intensity than needed.
Kitchen the materials chosen for the kitchen seem to be more for aesthetics than for functionality (user-friendly/cleaning)
[1]
[2]
[3]
[4]
[5]
[6]
[7]
West Office windows and building structure have clear ventilation and temperature infiltration issues (respectively)
Shower detail, seems to be routinely used
West Office anything said on these leisure and meeting spaces is echoed and reverberated to the lower floor
West Office throughout the building the controls are not user-friendly or intuitive
West Office lighting controls do not notice that there is a user working away on her desk
East Office detail of structural versus fabric dislocation, creating infiltration (also, the metallic structure brings cold in
from the base of the building by conduction)
East Office to close the manually controlled windows, users risk their fingers in a design-unintended manoeuvre. This
photograph is actually located at its mirrored location, on the west office.
4.5
The building management system (BMS) generally provides control and monitoring of the building services, consisting of:
Boiler plant providing LPHW to a constant temperature and a variable temperature circuit
Zone control of radiator heating and fan convector heating
Two extract fan systems
Natural ventilation systems
Figure 12 Ground floor - John Payne AES System Monitor - AES Control Systems 2011
Figure 13 First floor - John Payne AES System Monitor - AES Control Systems 2011
Figure 14 Second floor - John Payne AES System Monitor - AES Control Systems 2011
BMS Supervisor
Controls heating zones temperature set points and automated natural ventilation CO2 levels set points. It has two modes:
summer and winter. The automated window opening may be triggered by high temperatures or high CO2 levels; therefore, in
winter the windows may open for air flow quality, regardless of temperature. The heating system is then activated,
counteracting the heat loss, and created a spiral of unbalance in the system. There is minimal (time-limited) occupant manual
over-ride, which can cause frustration due to the external noise/winter draughts (ref. occupant feedback).
Ventilation system (see Appendix IV)
Advanced Natural Ventilation (ANV) system has been adopted to reduce the requirement for comfort cooling and mechanical
Ventilation; BMS controlled automated windows (CO2 & temperature sensors) offer the opportunity for night time cooling to
reduce peak daytime temperatures., record settings and variability, vent outlets: area & location, fans: quantity, power rating
(Watts), duration of use. The table below highlights the opening control for the identified areas. (Decant Workshop 2011)
Heating Systems
A condensing gas boiler: Potterton WH50 (not listed Sedbuk/SAP, 87.5-107.5% from trade lit). Twin boilers [Figure 16 through to
Figure 18]: single sufficient for most conditions, therefore running at efficient level/back-up. Zoning flexibility: two main circuits
each with 3 zones: rads & trenches circuit, zoned for each ent. Lobby, 1st and 2nd floor offices and fan convector circuit, zoned
for each gnd. fl. Workshop/lab.
Figure 16 AES System Control - BOILERS - 28th November 2011, via Gareth Eddie
Figure 17 AES System Control - HEATING ZONE VALVES - 28th November 2011, via Gareth Eddie
Figure 18 Boiler-room: well insulated fittings and with easy access. Photos by Author
4.6
Appliance Audit
x32
x10
x60
x144
x39
11%
14%
3%
Recessed
Compact
Florescent
21%
Suspended
Fluorescent
Laserline
Luminaire
51%
The only ambient lighting is the Spot Halogens and they have the largest potential of 90% saving per fitting. The task
lighting also saves a fraction per fitting but has a far larger number of fittings.
30000
Spot Domotec Halogen
25000
20000
Strip Fluorescent
Luminaire
15000
10000
Suspended Fluorescent
Luminaire
5000
Suspended Fluorescent
Laserline Luminaire
Recessed Compact
Florescent
0
Standard fitting
Low-e fitting
The majority of the lighting is task lighting due to this it acts as a base-load for electricity consumption despite this there are
savings to be made.
Typical ( electricity) CIBSE TM46 (2008)
Typical Guide F (2004)
Good Practice Guide F (2004)
JOHN PAYNE
0
JOHN PAYNE
kWh/m2/yr
21
Table 23
10
20
30
40
50
60
70
80
90
100
Lighting Benchmark - CIBSE TM46 typical office & Guide F open plan naturally ventilated
John Paynes energy consumption against Guide F only office Good Practice performs well enough but this benchmark is 7years
out of date. Its lighting, electrical energy consumption against CIBSE TM46 typical office is clear to see it performs well but it is
difficult to tell accurately how well the building performs as it is a total electrical typical office load and JP data is just lighting.
Standard fitting
7.0
Low-e fitting
kWh
1.8
0.8
1.1
7.8
5.9
7.1
2.0
0.7
0.2
Task lighting
Task lighting
Task lighting
Task lighting
Ambient lighting
Recessed Compact
Florescent
Suspended Fluorescent
Laserline Luminaire
Suspended Fluorescent
Luminaire
Strip Fluorescent
Luminaire
1%
Recessed Compact
Florescent
4%
5%
Suspended Fluorescent
Laserline Luminaire
51%
39%
Suspended Fluorescent
Luminaire
Strip Fluorescent Luminaire
0% 3%
3%
Recessed Compact
Florescent
Suspended Fluorescent
Laserline Luminaire
39%
55%
Suspended Fluorescent
Luminaire
Strip Fluorescent
Luminaire
Spot Domotec Halogen
10
TYPE
FLOOR
Heatrae Sadia
Multipoint 30
LOCATION
POWER RATE
kW
AV.
hrs/day
hrs/annum
kWh/annum
3.00
3.00
756
2268
3.00
1.00
252
756
3.00
3.00
756
2268
3.00
1.00
252
756
3.00
4.50
1134
3402
3.00
3.00
756
2268
9.80
1.50
378
3704
Sub-Total
(Hot
Water)
15422
Hot Water
Point Of Use
Hot Water
0
0
0
1
2
Instantaneous
Shower
Water Boilers
(For Hot Drinks)
ICT
PCs Inc. VDU
Rada/Mira
Advance Atl
Heatrae Sadia
Supreme 170
Kitchen
2.50
6.00
1512
3780
Kitchen
2.50
6.00
1512
3780
0.20
4.00
1008
1411
0.20
5.00
1260
1260
0.20
3.00
756
302
1
1
2
1
2
Lab
Architectural
Workshop
Elect/Systems
Workshop
Office
Office (BMS)
Office
Office
Office
19
7
25
10
8
0.20
0.20
0.20
0.18
0.18
6.50
24.00
6.50
5.50
5.50
1638
8760
1638
1386
1386
6224
12264
8190
2495
1996
Office
0.02
8.00
2016
202
Office
0.02
8.00
2016
40
Office
0.05
8.00
2016
202
2
1
Office
Office
3
1
0.05
0.03
8.00
8.00
2016
2016
302
60
Sub-Total
(ICT)
34949
Printer/Scanner
s (Small)
Printer/Copiers
(Large)
Plotter
Shower Room
Laptops
Cleaners Cpd. (3 X
WCs)
Rest Room
Architectural
Workshop
Lab
Kitchen (Sink + 3 X
WCs)
Kitchen (Sink + 2 X
WCs)
ENVIRONMENTAL AUDIT
Assessment of the John Payne Buildings immediate external environment will need to address the short and medium term (the
current site works and how they are proposed to evolve) and the long term (the implemented Brookes masterplan).
5.1
Figure 22 Location and Accessibility. Original photos by Google Maps; Photomontage by Author (2011)
Site environment: As existing/as proposed: hard/soft landscape/ green roof, bio-diversity, site works: extent, duration.
Access: Pedestrian/goods access, egress (inc. green roof space) - as existing/as proposed.
Transport: Public transport accessibility/proximity, car parking, cycle parking (ref. facilities, showers etc.)
percentage %
20
15
10
5
0
journey to work
car
bike
bus
walk
lift
17
5.2
Site Analysis
Figure 23 Original images: Google Maps, Sun Path Diagram (http://www.gaisma.com), Wind Rose for Heathrow
(http://www.metoffice.gov.uk); Photomontage by Author (2011)
5.3
In Use Monitoring
Daylight
The external lighting for the day measured was 4700lux on a semi-cloudy day. It is possible to see a stronger influx of daylight
near the areas with windows/roof lights/openings. The levels, however, change very drastically from the lit areas to the one in
the shade, possibly resulting in glare, if the internal artificial units do not activate.
Studies (H Mahone 1999) have shown better improved pupil performance in schools associated with higher daylight levels.
http://www.virtualdaylight.com. Daylight, and the users ability to interact visually with the surrounding environment is an
important factor for creating psychological user comfort in architecture. It has also been known to increase productivity and
improve overall building health status.
Lux
600
1st Floor
400
2nd Floor
200
12 November 2007
11 November 2007
10 November 2007
09 November 2007
08 November 2007
07 November 2007
06 November 2007
Lux levels monitored within the open-plan offices show how 2nd floor lighting reaches much higher lighting levels thank the 1st
floor. This is not due to natural light from the roof light as it does not happen over the weekend.
Indoor Temperature
The recorded internal temperatures are on average much higher than necessary. This is possibly due to the fact that these are
dry-bulb temperature readings, which do not take into account the environmental perception of the analysed areas. By
considering the humidity [Figure 30] and air change rate levels [Table 14], one will find that the perceived temperature for these
spaces is in actuality much cooler than the actual dry-bulb temperature readings.
2nd Floor
15
1st Floor
10
Gnd Floor
5
0
oC
External
MAX
AVG
Week 1
MIN
MAX
AVG
Week 2
MIN
MAX
AVG
MIN
Week 3
MAX
AVG
MIN
Week 4
25
20
15
External
Temp
10
5
0
MAX
AVG
MIN
MAX
Week 1
oC
AVG
MIN
MAX
Week 2
AVG
MIN
MAX
Week 3
AVG
MIN
Internal
Temp
Week 4
Internal temperature on all floors stays within a consistent tolerance creating a consistent environment. Internal temperature
fluctuates with the External temperature but to a lesser extent.
25
20
External
Gnd Floor W
15
1st Floor E
1st Floor W
10
2nd Floor S
5
2nd Floor W
2nd Floor E
19 November 2007
18 November 2007
17 November 2007
16 November 2007
15 November 2007
14 November 2007
13 November 2007
oC 0
Humidity Levels
From the UK Statutory Instruments, 2005 No.1643 HEALTH AND SAFETY, The Control of Noise at Work Regulations 2005.
10
OCCUPANT FEEDBACK
Figure 32 John Payne Building Occupants. Photo by EFM - Estates and Facilities Management (2010)
As academic research the module has been allowed to use the copyrighted Building Use Studies (BUS) occupant questionnaire,
with the advantage of benchmarking against a wide data-set of surveyed buildings (including all the Probe studies). The
questionnaire has been refined over a long period to precise and pragmatic need to know notnice to have content. This
covers:
overall comfort, including thermal
occupancy
perceived productivity
management responsivity
transport to work
Numeric results and commentary have been fed back to BUS director Adrian Leaman via excel pro-forma spreadsheet, analysed,
benchmarked and returned graphically. This enables access to the comfort, satisfaction and perceived productivity of JPs
occupants relative to equivalent buildings, gauge its success as a workplace and conclude whether there are issues that might
need to be addressed.
6.1
20
Based on the overall summary as illustrated on Figure 33, some conclusions can already be drawn, respectively from top to
bottom:
Figure 33 BUS overall summary John Payne (BUS Methodology Ltd 2011)
i.
Despite nearly universal concerns over excessive air movement in winter, overall ambient comfort is still perceived as
good.
ii.
Good lighting quality was let down by universal frustration with poor sensoring.
iii.
External noise through automated open windows gained the worst responses.
iv.
v.
Typically no effect on health at all (or the users did not understand the question).
vi.
The image to visitors is perceived as good, but perhaps not as good as it could for a new building.
vii.
20
Figure 34 Overall Comfort Map - BUS comfort scores on the John Payne building
21
John Payne scored very well for BUS overall comfort [Table 32]. Nevertheless, a significant proportion complained of excessive
air movement, particularly cold draughts in winter. The control over cooling diagram [Table 33] shows another side of that
problem, that users are at the mercy of a non-intuitive computerized system control. West facing windows are noticeably the
worst affected by prevailing wind.
Table 33 BUS - control over cooling diagram (BUS Methodology Ltd 2011)
External noise is the next significant discomfort. High sound levels coming from adjacent construction; frustration at the lack of
control over window automation; over-ride potential is very time limited; temporary condition: end in sight mentality; CO2
threshold for automated opening raised to 1000 ppm; improved but not resolvable until construction completion.
Table 34 BUS - control over noise diagram (BUS Methodology Ltd 2011)
Lighting overall was perceived as reasonably satisfactory. However, frustration with the lighting sensors was commented on by
nearly every occupant.
productivity is affected by having to get up and walk under the sensor.
Lighting goes off after no motion detected for short period. A short term option is to increase the period to its max. Unit, at
40min (currently it is at 20min). This may defeat the object of energy conservation, but may increase productivity. The PIR
sensors actually have an effective radius of only 2.5m, whereas following the manufactures specifications, it should have from 5
to 7m [Figure 35].
22
Figure 36 Detail - motion sensors on the east office area of the first floor of the John Payne building
Aside from that, there seem to be less sensors than required installed throughout the building [Figure 36]. Because of the open
floor plan layout, they are not strategically positioned for the sensors to be effective without a fixed layout plan; they need to
be installed on a 5x5m grid throughout the desk space floor area.
Some of the good indicators showed user satisfaction with the meets and needs [Table 36] of the building, as well as the
temperature in summer (when the cold drafts actually play the correct role of passively cooling the environment) in Table 37.
Some of the other results include dissatisfaction with the air quality and quantity of the meeting rooms, insufficient or over
ventilation due to gusts of wind through openings being a problem. The forgiveness factor rating is just above average [Table
38], showing that despite its shortcomings, the users like the building overall, as shown by Table 39.
23
6.2
Interviews
24
CONCLUSION
The post occupancy evaluation of the John Payne Building has shown that the building is generally eco-friendly as it has a good
rating when benchmarked for energy use against CIBSE (2004) Guide F: Energy Efficiency in buildings, Max Fordham
Sustainability Matrix - Green Offices (see Appendix II), the RIBA CIBSE platform (nd) CarbonBuzz, Probe (1995-2002) POE case
studies and the Building Use Studies (1995-present) Occupant survey studies (courtesy of Adrian Leaman, BUS), as can be
verified throughout the report.
The John Payne performs well in terms of general energy consumption. And although it is within the benchmarks established, it
has high electricity consumption and considerations must be made to the fact that the building is only 46% is full capacity of
occupants, resulting in correspondingly less total energy consumption per square meter than its real potential. System controls
do not work as efficiently as the design intent was, but another consideration has to be made about the influence of the
adjacent construction site, which interacts with John Payne by influencing its non-intuitive pre-set ventilation and lighting
systems. Occupant feedback shows that users are in general satisfied with the John Payne building, with some complaints about
the pre-set control systems that are not interacting with the users, nor can be guided by the users, to satisfaction.
There is always scope for improvement, therefore some immediate, short or long term recommendations (relative to cost) can
be found on the next page.
25
RECCOMENDATIONS
8.1
8.2
Increase energy efficiency by installing more energy efficient light bulbs starting at the worst case scenarios, as can be
verified on Figure 19 through to Figure 21.
Address lack of the acoustic absorbent surfaces within the open-plan environment with available artwork from OBU
Improve quiet/sensitive office task areas, without adding partitions (which negatively impact other issues).
Provide communal areas with natural light, such as altering the office layouts to allow for easy circulation and rest
spaces near wide-window areas: such as overlooking the green roof on the second floor, and switching the lounge with
the maintenance workshop on the ground floor thus also avoiding wind tunnels versus desktop.
Improve working conditions in relation to temperature versus passive ventilation, by positioning all file cabinets and
storage spaces directly below the roof light on the first floor. This will better control the air flow rate, but not so much
that it will compromise its functionality. Be sure to keep drawers closed in case it rains suddenly (rain drops from rooflight openings).
Fulfill the building occupancy potential, consider hot-desk usage or smaller desks, as noted by occupants through BUS
Increase daylight propagation and decrease glare by installing semi-opaque screens on roof lights and selected
windows
Set ambient lighting to the minimal required (BREEAM Office minimal requirements are 350lux) and proportion
desktop lights individually to the users.
Separate the temperature and the CO2 monitors, so that one does not influence the other resulting in off readings. Or
have a series of them in the same space (3 max) to only activate after going through a comparative analysis.
Allow for user control after educating the users about working in a high tech building environment.
Short Term (medium cost)
8.3
Improve lighting sensors capacity and or quantity, ideally at 5x5m grid intervals.
Address lack of the acoustic absorbent surfaces within the open-plan environment with available artwork from OBU
students or even the John Payne staff themselves. The artwork can also improve the buildings attractiveness to users.
Increase covered bike storage/lockers and create incentives for public transport.
Green roof access for maintenance purposes (although this is medium cost, it should be considered as a immediate
priority recommendation)
Improve usability of temperature, lighting and CO2 window controls
Set up sub-meters in zones of different purpose in the building to allow greater energy consumption understanding
Remove dimmers and replace all ambient light bulbs with limited lux intensity (BREEAM Office minimal requirements
are 350lux) as well as energy saving (eco-friendly) bulbs.
Long Term (high cost)
Green roof versus Photovoltaic Panels: since the green roof presently does not provide any insulation benefits, nor
rainwater storage capacities without retrofit, as other benefits for the immediate surrounding environment (as biodiversity), it would be strongly advised to consider the installation of PV panels, which would benefit John Payne and
OBU in the long term by providing considerable electricity savings: which is one of the major energy consumer and CO2
contributor in John Payne [Table 17].
Increase daylight propagation and decrease glare by installing semi-opaque glazing in the roof light and selected
windows.
Hire an Architect to supervise changing layout floor plans in order to increase productivity and user well-being, as well
as other adaptations.
Invest in a professional POE assessment, as predicted in John Paynes building log, every few years.
26
FEED FORWARD
Energy Consumption Monitoring and a Building Managers Manual, along with increased user awareness and
responsibility through a seminar or workshop and an appointed building manager.
Consider all aspects of orientation and environmental influences and interactions from inside and outside of the
building fabric. So that if the building has to breathe to circulate air, then the air cant be too cold, otherwise it will
get a flu.
Improve user-friendliness and user controls empower the user and they will react accordingly by taking care of
their environment.
27
10
REFERENCES
ACCESS The Advanced Student Scheme For Energy Savings in Schools, Best practice programme Energy Efficiency BRE 2000
Bordass et al, Assessing building performance in use, Building Research & Information (2001) 29(2) 144-157
Building Use Studies Ltd 42-44 Newman Street, London W1T 1QD
Carbonbuzz website: http://www.carbonbuzz.org/
CIBSE Applications Manual AM5:1991 Energy Audits and Surveys, The Chartered Institution of Building Services Engineers,
London.
CIBSE Guide F 2004, Energy Efficiency in Buildings, The Chartered Institution of Building Services Engineers, London.
CIBSE TM 46 2008, Energy Benchmarks, The Chartered Institution of Building Services Engineers, London.
Degree days (International resource): www.degreedays.net
Gupta R, Chandiwala S, A Student-Centred Approach to Provide Evidence-Based Feedback on the Sustainability Performance of
Buildings, PLEA 2009, Quebec City, Canada, 22-24 June 2009
SMEasure: Building Energy Management http://www.smeasure.org.uk/about
The Carbon Trust, How and why to use degree day information, GIL 135 www.thecarbontrust.co.uk
28
KEY
WEEK
WEEK DAYS
Submission Deadlines
Group Meetings
Site Visits
General
Project Introduction
Building Background Data
Group Meeting - Establish Pre Survey
1st Contact - Gavin Hodgson
Site Survey & Data Request to Gavin Hodgson
Site and Photographic Survey
Study of Site Survey
Site Survey Presentation
Group Meeting
Establish Group Programme
Equipment - from Matt Gregg
Study of Equipment Position
Equipment Position Review by Matt Gregg
2nd Site Visit - Setup of Data Monitoring
BUS Questionaire - Dr Bill Bordass
Group Meeting
POE Methodologies
Occupant Questionaire
Energy Analysis and related calculations
Systems Analysis
3rd Site Visit
Occupant Interviews
Retrieve Monitors
Download Data
Group Meeting - Tutorials
Analysis of Data Collected
Compare Data (to Benchmarks)
Report Scope and Coordination
Final Report and Presentation
Post Presentation Gathering
Individual Study
Individual Report Submission
DESCRIPTION
7h Nov - Wk4
M T W T F
This issue will be proposed by our group before/after class, on the 16th of November, so a poll can be taken concerning this matter.
Chloe Oades
Paula Baptista
Andy Baylis
NOTES
! Subject to Building Manager confirmation (Gavin Hodgson)
! This is the formal established date for the final presentations - although we hope to present a week earlier, in order to have more time to elaborate and submit a more throrough final individual report.
GROUP 01
11
APPENDIXES
29
Appendix II Max Fordham, Green Office Sustainability Matrix versus John Payne Building.
30
31
nd
III.a BUS Questionnaire Ltd 2 page
32
rd
page
33
34
35
36
37
38
39
40
41
42
12
ATTACHMENTS
43