Sunteți pe pagina 1din 24

GB

Technical Data
T013D202A00 Issue 08/2006

a-eberle

Voltage Control System


REGSys
(REG-D, PAN-D)
* in wall-mounting
housing
* in panel-mounting
housing
* as plug-in module
The PAN-D monitoring unit can be used
as an additional safety device.

Application
Both simple and demanding measurement, control and regulation tasks can be carried out using the new RegSys voltage-control system.
The REG-D voltage regulator (basic device), PAN-D and
PAN-A1/A2 voltage monitoring units as well as interface modules with binary inputs and outputs and analogue inputs
and outputs are used as an optimal solution for these varied
tasks.
Every REG-D regulator can be used as a regulator and at the
same time as a transformer monitor, measurement transducer,
recorder, statistical unit and ParaGramer. All important network
measurement quantities are displayed in measurement transducer mode. Changes in the regulated voltage and additional
selectable measurement quantities are recorded in recorder
mode. The statistical unit for the tap-changer position offers a
clear display of all switching operations of the tap-changer. The
ParaGramer provides a complete busbar simulation.
It is particularly useful for the parallel connection of several
transformers.
The REG-DA regulator features a world innovation as it can be
equipped with a high-capacity transformer-monitoring function in accordance with CEI IEC 354 (VDE 0536). This function
allows the operator to call up information about the hot-spot
temperature and the lifetime consumption of the transformer at
any time. If required, the regulator can activate up to six cooling levels. The oil temperature can either be recorded directly
(PT 100) or via a mA input.
The connection of multiple independent voltage control systems in a network via a bus line enables a central monitoring
of the transformers and a mutual exchange of data over large
distances via various transfer methods. In particular, the parallel
connections of several transformers can be very easily implemented this way.
The PAN-D voltage-monitoring unit is used for redundant voltage monitoring.
Both the tap-changer and the regulator can be monitored with
the aid of monitoring units.
The PAN-D unit supplies a range of signals which enable secure

and concise operation of a transformer.


These are output via LEDs and relay contacts and include the
following: voltage limits <U1, >U2, <<U3, >>U4, tap-changer
in operation lamp and the signals Regulator fault and TapChanger fault, etc.
Application-specific tasks can also be implemented via freely
programmable inputs and outputs.
REGSys is able to communicate with a central control unit
via all common protocols.
The following protocols are available:
IEC 60870 - 5 - 101 / 103 / 104
IEC 61850
LON
DNP 3.0
Profibus DP
MODBUS RTU
SPABUS

Characteristics of the voltage


regulation system
Large backlit LCD (128 x 128) with all
Important information (tap-change position, voltage, etc.)
Measuring functions (U, I, P, Q, S, cos , , I sin , f )
Recorder functions (multichannel line recorder)
Statistics functions (total number of switching operations,
switching operations per tap)
Event recorder (log book)
Transformer-monitoring functions for recording of
the hot-spot temperature and lifetime consumption
14 (16) freely programmable binary inputs
7 freely programmable binary outputs
Freely programmable analogue inputs or outputs (mA)
PT 100 direct input
Input for tap-change potentiometer (200 ... 20 k
total resistance)
Control of triple-wound transformers
Control of phase-shifting transformers
A. Eberle GmbH & Co. KG

Technical Data

REG-D

Limit value monitoring for all measurement quantities


4 freely programmable set-point values
Rated values of U and I can be programmed
Implementation of control tasks through ability to freely
program
RS485 peripheral bus (COM3) for additional interface
modules (ANA-D, BIN-D)
ParaGramer function for the display and automation
of any parallel connections with up to ten transformers
WinREG parameterisation software for parameterisation,
programming and visualisation as well as for a PC-based
archiving and evaluation of the recorder data
REGSim simulation software for the simulation of
any parallel operation, network and load situations

Regulator mode
The actual value and a fixed or load-dependent setpoint value
are compared in the regulator. The comparison determines
the correcting variable for the tap-changer of the transformer,
dependent on the regulative deviation. The parameters of the
regulator can be optimally adjusted according to the dynamic
time behaviour of the network voltage in order to obtain high
control performance at a low number of switching operations.
Parallel connection of transformers
Every regulator can be used with other regulators from the
REGSys family to regulate up to 10 transformers connected
in parallel without additional components.

REG-D

a-eberle

Status

Description

F1

<U
Display

>U

F2

X = 81,15
y = 76,95

>I

F3

B = 67,818 mm
H = 67,818 mm

F4

P
F5

LCD
AUTO

LED

RAM
4

ROM
CLOCK

E-LAN
RS485

RS232 10
RS232 11

COM 1

RS485 12
Status 13

COM 3

COM 2

ESC

MENU

2x current and 2x voltage transformers


Analogue mA inputs, Pt 100
Binary inputs
Input for tap-changer display (tap-change potentiometer)
Power supply
Display and processing unit
Analogue outputs (optional)
Binary outputs
E-LAN connection (2 x RS485 with repeater function)
COM 1, RS232
COM 2, RS232
COM 3, RS485 (optional)
Status signal (life contact)

Case
differentiation

REG-D
Program

Boundary conditions

Parallel operation
on one
(several)
busbar(s)

I sin

Identical transformers,
identical or different
tap changes

I sin (S)

Transformers with
different performances,
different or equal
tap changes

Master
slave

Identical transformers,
identical tap changes

Free infeed

cos

Any transformers,
any tap changes

Emergency program during bus


error

cos

Any transformers,
any tap changes for the
I sin and I sin (S)
programs

Table 1 Parallel operation of transformers

A. Eberle GmbH & Co. KG

COM1

Various processes are available to control the transformers and


they are listed in Table 1 according to those that operate in
parallel on a busbar and those that are simply freely switched
in parallel.
An essential factor in this context is that no additional components are required as all function units required for parallel
operation are accommodated within the regulators.

Functions of the REG-DTM regulator


1
2
3
4
5
6
7
8
9
10
11
12
13

local
remote

Technical Data

REG-D
Additionally, a record is kept for every single tap in tabular form.
How many tap changes have been carried out during which
time period and how often each tap has been selected can
be checked using these data. This information can be used to
optimise the regulator settings.
The saved statistics values can be selected using the keyboard
or loaded and printed using WinREG.

Measurement transducer mode


The values of all relevant variables of an equally or arbitrarily loaded three-conductor three-phase supply network are calculated
and displayed on the basis of the sampling values.
In addition, a selection of up to seven measurement values can
be output as a DC signal via the analogue outputs.

REG-D

a-eberle

Status

REG-D

a-eberle

F1
Status

F1

<U
Display

>U

Display

>U

X = 81,15
y = 76,95

>I

<U

F2

F3

B = 67,818 mm
H = 67,818 mm

F2

X = 81,15
y = 76,95

>I

F3

B = 67,818 mm
H = 67,818 mm

F4

F4

F5
F5

AUTO

local
remote

ESC

MENU

COM1
AUTO

Furthermore, measurement values which are transferred to the


regulator as mA signals from external sources can be displayed.
displayed

ESC

COM1

MENU

ParaGramer mode
The PARAGRAMER is a support tool for the automatic preparation of parallel connections and the online display of the
switching statuses.
The artificial word PARAGRAMER is a combination of the two
terms parallel and one-line diagram.
The PARAGRAMER shows the switching status of the individual
transformers in a one-line diagram.
The function is activated by feeding each regulator with a complete busbar replica (position of circuit breakers, disconnectors,
bus ties and bus couplings).
Based on the switching states of all regulators involved in the
parallel connection, the system autonomously detects which
transformer is to work with which other transformer(s) in parallel
connection on a busbar.
Busbars that are connected via bus coupling(s) are treated as
one single busbar by the system.

Recorder mode
The change in the voltage over time and a second selectable
measurement quantity are continuously shown on the display
in the form of a line chart. The time grid for the recording is
adjustable. The present tap position, time and date are recorded in addition to the measurement quantity. Therefore, it is
possible to display the present voltage and the time-correlated
tap position at any time. The average storage time for voltages
and tap changes is approximately six weeks.
The stored values can be displayed by using the keyboard or
the WinREG operating software.

REG-D

local
remote

a-eberle

Status

REG-D

F1

a-eberle

<U
Display

>U

F2

X = 81,15
y = 76,95

>I

Status
F3

B = 67,818 mm
H = 67,818 mm

F1

<U
Display

>U
F4

F5

AUTO

local
remote

ESC

MENU

F2

X = 81,15
y = 76,95

>I

F3

B = 67,818 mm
H = 67,818 mm

F4

F5

COM1

AUTO

local
remote

ESC

MENU

COM1

Statistics mode
In the statistics mode, all switching operations of the tap-changer are registered. A differentiation is made between switching
operations under load and switching operations without load.

As shown in the graphic, both transformers T1 and T3 are


working on busbar a, whereas transformer T2 is feeding into
busbar b.
3

A. Eberle GmbH & Co. KG

Technical Data

REG-D
lator. The PAN-D unit can function without a bus connection
in normal operation and works as a totally independent and
additional monitoring unit.

Transformer monitoring mode TMM


The essential characteristic quantities of the transformer are
monitored in the monitoring mode. The oil temperature can
also be recorded in addition to the tap-changer statistics. In
accordance with IEC 354 (VDE 0536/3.77), the hot-spot temperature is determined on the basis of the oil temperature and
the winding current and subsequently extrapolated to determine
the residual lifetime of the transformer.
Fans can be set to one of six levels and an oil pump can be
used to regulate the temperature. Furthermore, the oil levels
can be monitored and the operating hours of the fans and the
pumps can be counted.

REG-D

LED
RAM

ROM

a-eberle

Status

P
E-LAN
RS485

COM1
RS232

Status

Functions of the PAN-D monitoring unit

F1

<U
Display

>U

F2

X = 81,15
y = 76,95

>I

1
2
3
4
5
6
7
8

F3

B = 67,818 mm
H = 67,818 mm

F4

F5

AUTO

local
remote

ESC

MENU

COM1

The regulator can be optionally supplied with a PT100 module


or a mA input for measuring the oil temperature.
In total, three connection points are available. This means that
several temperatures can be recorded via mA inputs or the
PT 100 if required.
The possible combinations can be found in Feature Group E
in the ordering information.

PAN-D Voltage Monitoring Unit


The PAN-D monitoring unit is assigned to a regulator and can
be switched to this regulator via bus (E-LAN).

PAN-D

a-eberle

Betrieb

Lauflampe

Strung

Phasenfall

Strung
Stufenschalter

< U1

Strung
Regler

Auslsung
Leistungsschalter

> U2

NOT-AUS
Stufenschalter

U3
U4

AUTO

local
remote

ESC

MENU

COM1

The PAN-D monitoring unit is parameterized either directly via


the unit interface or via the keyboard and display of the reguA. Eberle GmbH & Co. KG

Voltage transformer
Binary inputs
Power supply
Display and processing unit
Binary outputs
E-LAN connection (2 x RS485 with repeater)
COM 1, RS232
Status signal (life contact)

Technical Data

REG-D

Technical Characteristics
TM

*) Data is valid for both REG-D

and PAN-D

Analogue outputs (AO)

only for REG-DTM

Number
Output range Y1...Y2

See ordering information


-20 mA...0...20 mA
Y1 and Y2 programmable
Optocoupler
0 R 8 V / Y2
< 0.5 % from Y2

Regulations and standards *)


IEC 1010/ EN61010 (VDE 0411)
CAN / CSA - C 22.2 No. 1010.1 - 92
VDE 0110
IEC 255 - 4
EN 55011 : 1991
EN 50082 - 2 : 1995
IEC 688 - 1
IEC 529
EN 50178 / VDE 0160 / 11.94
VDE0106 part 100

Electrical isolation
Load range
Alternating component

AC voltage input (UE)

Number

Measurement voltage UE

The outputs can be continuously short-circuited or operated


open. All output connections are galvanically isolated from all
other circuits.

Temperature input PT 100

*)

Curve shape
Frequency range

60 ... 140 V
(software selectable)
Sinusoidal
16....50....60....65 Hz

Internal consumption
Overload capacity

U2 / 100 k
300 V continuous

Connection
Current through sensor
Line compensation
Transmission behaviour

Resistance input for


tap-change potentiometer
If the tap-changer position is supplied as a resistance value
(tap-change potentiometer), then an appropriate module can
also be connected (see Feature Group E or Accessories).
In this case the resistance measurement transducer is no longer
required.
Resistance ranges from 200 Ohm to 20 kOhm can be converted
into tap changes.
The specified resistances correspond to the total resistance in
the resistance chain.
The number of Ohms per tap-change (e.g. 10 Ohm/tap-change)
can be specified using the keyboard.

AC current inputs (IE) only for REG-DTM


Measurement current In

Curve shape
Frequency range
Internal consumption
Overload capacity

Analogue inputs (AI)


Number
Input range X1...X2
X1 and X2 programmable
Control limit
Voltage drop
Electrical isolation
Common mode rejection
Series mode rejection
Overload capacity
Error limit

Up to three PT 100 inputs are possible


3-conductor circuit
<8 mA
No compensation required
Linear

1A/5A
(hardware and software
selectable)
Sinusoidal
16....50....60....65 Hz
0.5 VA
10 A continuous
100 In for 1 sec (max.
300 A)
30 In for 10 sec
500 A for 5 ms

Resistance measurement is normally carried out for a 3-conductor circuit. If a 4-conductor measurement circuit is required,
this can also be configured.
The resistance-measurement equipment consists of a programmable current source to feed the measurement resistance and
a voltage-measurement device to measure the voltage at the
resistance.
The measurement result is output with a resolution of 12 bits
and a refresh rate of approx. 10 Hz (0.1 s).

only for REG-DTM


See ordering information
-20 mA...0...20 mA
1.2 X2
1.5 V
Optocoupler
> 80 db
> 60 db / order of
magnitude from 10 Hz
50 mA continuous
0.5 %

The measurement device has a broken-wire detection system.


The parameters are input in an application menu using the
keyboard.

The inputs can be continuously short-circuited or operated


open. All inputs are galvanically isolated from all other circuits.

A. Eberle GmbH & Co. KG

Technical Data
Binary inputs (BI)

REG-D
*)

Feature D1
Inputs E1 ... E8
Control signals Ust
Curve shape, permissible
H level
L level
Signal frequency
Switching delay
Input resistance
Electrical isolation

Inputs E9 ... E16


Control signals Ust
Curve shape, permissible
H level
L level
Signal frequency
Input resistance
Electrical isolation

Within the 48 V...250 V


AC/DC range
Rectangular, sinusoidal
48 V
< 10 V
DC ... 50 Hz
Selectable from 1..999 s
108 k
Optocoupler; all
inputs are galvanically
isolated from each other

Example circuit diagram of a binary input

Binary outputs (BO)


Status Relays 1 ... 9,

Within the AC/DC range


10 V...50 V
Rectangular, sinusoidal
10 V
<5V
DC ... 50 Hz
6.8 k
Optocoupler; all
inputs are galvanically
isolated from each other.

Contact load

No. of switching operations

Limit value monitoring

Inputs E1 ... E16


Curve shape, permissible
H level
L level
Signal frequency
Switching delay
Input resistance
Electrical isolation

PAN-D Relays 7 ... 14

Max. switching frequency


Electrical isolation

Feature D2
Control signals Ust

*)

Limit values
Response time
Alarm display

Within the 48 V...250 V


AC/DC range
Rectangular, sinusoidal
48 V
< 10 V
DC ... 50 Hz
Selectable from 1..999s
108 k
Optocoupler; all
inputs are galvanically
isolated from each other.

1 Hz
Isolated from all deviceinternal potentials
AC: 250 V, 5 A (cos = 1.0)
AC: 250 V, 3 A (cos = 0.4)
DC: 220 V, 150 W switching
capacity
5105 electrical

*)
Programmable
Programmable
Programmable LEDs

Measurement quantities
Voltages
TRMS
Current
TRMS
Active power
Reactive power
Apparent power
Power factor
Reactive current
Frequency

U12, (U23, U31 )( 0.25 %)


I1 (I2 ; I3) ( 0.25 %)
P ( 0.5 %)
Q ( 0.5 %)
S ( 0.5 %)
cos ( 0.5 %)
I sin ( 1 %)
f ( 0.05 %)

Feature D3
Inputs E1 ... E16

Reference conditions
Control signals Ust
Curve shape, permissible
H level
L level
Signal frequency
Input resistance
Electrical isolation

A. Eberle GmbH & Co. KG

Within the AC/DC range


10 V...50 V
Rectangular, sinusoidal
10 V
<5V
DC ... 50 Hz
6.8 k
Optocoupler; all
inputs are galvanically
isolated from each other.

Reference temperature
Input quantity
Frequency
Curve shape
Auxiliary voltage
Load (only for features E91...E900)
Other

*)
23 C 1 K
UE = 60 ... 140 V
IE = 0 ... 1A / 0 ... 5 A
50 Hz...60 Hz
Sine, form factor 1.1107
H = Hn 1%
Rn = 5 V / Y2 1%
IEC 688 - part 1

Technical Data

REG-D

Transmission behaviour

*)
0.05% / 0.5 % / 1%
All error data compared
to Y2 (see Measurement
Quantities)
10 ms
1 kHz

Error limit

Measurement cycle time


Sampling rate

Electrical safety

Emitted
interference

Group 1 limit class A


according to EN 55011:1991

Immunity to
interference

Electrostatic discharges
according to EN 61000-4-2:1995
Air discharge: 8 kV
Contact discharge: 8 kV
Electromagnetic fields
according to ENV 50140:1993
and/or ENV 50204:1995
80 - 1000 MHz: 10 V/m
900 5 MHz: 10 V/m pulsemodulated
Fast transient interferences (bursts)
according to EN 61000-4-4:1995
Supply voltage: AC 230 V: 2 kV;
Data cables: 1 kV
Conducted interferences according to
ENV 50141:1993
0.15 - 80 MHz: 10 Veff
50 Hz-magnetic fields acc. to
EN 61000-4-8:1993 30 A/m

*)

Safety class
Degree of pollution
Overvoltage category

I
2
II, III

III

II

Input circuits of the current


and voltage transformers
Auxiliary voltage

Control circuits, analogue


inputs, analogue outputs
COMs, E-LAN

Operating voltages
50 V

150 V

E-LAN,
COM 1...COM 3,
analogue inputs,
analogue outputs,
inputs 10...50 V

230 V

Voltage input,
current input

Moun
t.*

Uh*

COMs*

BO*

BI*

BI*
50 V

AI

AO

UE*

IE

Mount.*

2.2

0.35

1.35

1.35

0.35

0.35

0.35

1.35

1.35

Uh*

2.2

3.7

2.9

2.9

3.7

3.7

3.7

2.6

2.6

Test voltages
Mounting rack
Auxiliary voltage
COMs

Auxiliary voltage,
binary inputs,
relay outputs,
status

COMs*

0.35

3.7

2.3

2.3

0.5

0.5

0.5

2.8

2.8

Binary outputs

BO*

1.35

2.9

2.3

2.0

2.3

2.3

2.3

2.6

2.6

Binary inputs (250 V)

BI*

1.35

2.9

2.3

2.0

2.3

2.3

2.3

2.6

2.6

Binary inputs (50 V)

BI 50V*

0.35

3.7

0.5

2.3

2.3

0.5

0.5

2.8

2.8

AI

0.35

3.7

0.5

2.3

2.3

0.5

0.5

2.8

2.8

Analogue inputs
Analoge outputs

AO

0.35

3.7

0.5

2.3

2.3

0.5

0.5

2.8

2.8

Input voltage

UE*

1.35

2.6

2.8

2.6

2.6

2.8

2.8

2.8

2.2

Input current

IE

1.35

2.6

2.8

2.6

2.6

2.8

2.8

2.8

2.2

Note:

All test voltages are AC voltages in kV, which may be applied for 1 minute.
COM1, COM2, COM3 are tested against each other with 0.5 kV.
* Also valid for PAN-D

Power supply
Feature

Climatic stability *)
Temperature range
Function (housing)
Function (plug-in module)
Transport und storage

*)
H0

H1

H2

AC (internal)

75 V...185 V

AC

85...264 V

18 ...72 V

88...280 V

18 ...72 V

DC
Power cons.

15 VA

15 VA

10 Watt

Frequency

45...400 Hz

45...400 Hz

Microfuse

T2 250 V

T2 250 V

T2 250 V

Display
LCD display
Lighting

only for REG-DTM


128 x 128 graphics-capable
Programmable switch on/off

Data storage
Device settings

The following applies to all features:


Voltage dips lasting < 80 ms cause neither loss of data nor
malfunction.

-10 C...+50 C
-10 C...+60 C
-25 C...+65 C

RAM data

Serial EEPROM with 1000 k


read/write cycles
Li battery laser-welded

(recorder function Feature S1)

A. Eberle GmbH & Co. KG

Technical Data

REG-D

Mechanical design

Installation in the mounting rack

*)

The mounting rack has 84 sections and therefore 84 n place


numbers. A specific place number is the reference point for the
installation of the guide and the connection elements on the rear
of the mounting rack.

Plug-in module
Front panel

Plastic, RAL 7035 grey


on aluminium support
3 U (132.5 mm)
28 T (142.2 mm)
160 mm x 100 mm
1.5 kg

Height
Width
Circuit board
Weight
Degree of protection
Plug-in module
Socket connector
Mounting
Plug-in connectors

IP 00
IP 00
Acc. to DIN 41494 part 5
DIN 41612

Place numbers

Guide

n+26

Screws

n+4

Socket connector

z
2

n+8 n+11 n+16 n+25

32

32

4
16
3

16

20

20

22

22
24

24

26

26
28
30
32

32

32

32

CP - 6

CP - 1

CP - 2

Position of the PAN-D socket connectors

CP - 4

CP - 3

CP - 5

CP - 6

Position of the REG-D socket connectors

32

32

CP - 1

32

CP - 3

32

28

30

CP - 5

CP - 2

45.72

40.64

15.24
20.32

20.32
7.62

45.72

Position of the REG-D blade connectors


A. Eberle GmbH & Co. KG

40.64

Position of the PAN-D blade connectors


8

20.32 20.32
7.62

Technical Data

REG-D

Contact assignment

CB-5 can be supplied either with a protocol card (XW1) or an


additional binary input or output card if required.

for REG-DTM

Socket connector 1; (binary outputs BO)


Raise (2 contact pairs)
1 NC contact and 1
NO contact

R1

Lower (2 contact pairs)


1 NC contact + 1 NO
contact

R2

Pole b8
Pole b10

NC z8
NO z10

Freely programmable

R3

Pole b14

NO z14

Freely programmable

R4

Pole b16

NO z16

Freely programmable

Pole
Pole

NC z2
NO z4

Socket connector 6; (analogue inputs / outputs; interfaces)

R5

Manual/Automatic
(Switch)

1.1 + b2

1.2 + z2

1.1 - b4

1.2 - z4

Left EA + b6

Right EA + z6

Left EA - b8

Right EA - z8
Right E + z10

Analogue module 1

E-LAN

Pole b20

NO z20

Left E + b10

Pole b22

Automatic z22

Left E - b12

Right E - z12

2.1 + b14

2.2 + z14

z24

2.1 - b16

2.2 - z16

GND R6...9 z28

TxD b20

RTS z20

RxD b22

CTS z22

GND b24

+12 V z24

3.1 + b26

3.2 + z26

3.1 - b28

3.3 - z28

Tx + b30

Rx + z30

TX - b32

Rx - z32

Manual b24

Status
Binary outputs (BO)
4 relays
Freely programmable

b2
b4

Pole b26

Analogue module 2
NO/NC

NO R6

b30

NO R8

z30

NO R7

b32

NO R9

z32

COM 2

Analogue module 3

Socket connector 2; (binary inputs BI) Features D1...D3


Raise

E1

+ b2

- z2

Lower

E2

+ b4

- z4

Standstill

E3

+ b6

- z6

High-speed switching

E4

+ b8

- z8

COM 3

Contact assignment

for PAN-DTM

Manual / Automatic

E5

+ b10

- z10

Socket connector 1; (binary outputs 230V)

Manual

E6

+ b12

- z12

E7

+ b14

- z14

Tripping
Circuit breaker

R1

Freely programmable

Pole
Pole

b2
b4

NO z2
NO z4

Freely programmable

E8

+ b16

- z16

R2

BCD 1

E9

+ b18

- z18

EMERGENCY OFF
Tap-changer drive

Pole b8
Pole b10

NO z8
NO z10

BCD 2

E10

+ b20

- z20

BCD 4

E11

+ b22

- z22

BCD 8

E12

+ b24

- z24

BCD 10

E13

+ b26

- z26

BCD 20

E14

+ b28

- z28

BCD -

E15

+ b30

- z30

Freely programmable

E16

+ b32

- z32

Pole b14

NO z14

R4

Pole b16

NO z16

Freely programmable

R5

Pole b20

NO z20

Freely programmable

R6

Pole b22

NO z22

Pole b22
Fault b24 Operation

z22

Socket connector 2; (binary inputs BI)

Socket connector 3; (input voltage, auxiliary voltage)


Auxiliary voltage

R3

Lower

Status

Note:
All of the inputs are freely programmable, with the exception
of the inputs E5 and E6. Table 2 shows an example for assigment.

Input voltage

Raise

Tap-changer in operation

E1

+ b2

- z2

Freely programmable

E2

+ b4

- z4

Freely programmable

E3

+ b6

- z6

Freely programmable

E4

+ b8

- z8

Freely programmable

E5

+ b10

- z10

20

22

24

Freely programmable

E6

+ b12

- z12

L(+)

28

N(-)

30

GND

32

Freely programmable

E7

+ b14

- z14

Freely programmable

E8

+ b16

- z16

Socket connector 4; (Input for alternating current)


Input current IE1

Input current IE2

A. Eberle GmbH & Co. KG

Technical Data

REG-D
Nr.
1
Auxiliary voltage
UH AC / DC
2
3
4
Input voltage
UE
5
6
7 k
Current input
8 l
Open during fault
9
Status
Closed during fault
10
11 Input 1
Raise
12 Input 2
Lower
13 Input 3
Standstill
14 Input 4
High-speed switching
15 Input 5
AUTO (M / A)
16 Input 6
MANUAL
17 Input 7
Freely programmable
18 Input 8
Freely programmable
19 Ground for input terminals 11...18
20
21
22
23 EA+
24 EAE-LAN (L)
25 E+
26 E27
28
Raise
R1
29
30
31
32
Lower
R2
33
34
35
Freely programmable R3
36
37
Freely programmable R4
38
39
Freely programmable R5
40
41
42
43
BCD 1
44
BCD 2
45
BCD 4
46
BCD 8
47
BCD 10
48
BCD 20
49
VZ
(-)
50
51
Freely programmable R9
52
Freely programmable R8
53
Freely programmable R7
54
Freely programmable R6
55
GND
56
MANUAL
57
AUTO
58
Pin assignment for types B05, B06 and B07
**) See Figures 12 to 16 for position of the terminal strip

Socket connector 6; (analogue inputs / outputs; interfaces)


Pole b2

Tap-changer
fault

NO contact z2

NC contact b4
NO contact z6

I **

Pole b6

Regulator
fault

NC contact b8
Pole b10

<U1

NO contact z10

NC contact b12
Pole b14

>U2

NO contact z14

NC contact b16
Pole b18

U3

NO contact z18

NC contact b20
Pole b22

U4

NO contact z22

NC contact b24
NO contact z26

II **

Pole b26

High-speed switching

NC contact b28
Pole b30

Freely programmable

NO contact z30

NC contact b32

Socket connector 3; (input voltage, auxiliary voltage)


Input voltage

L1

20

L2

22

L3

24

Auxiliary voltage

L(+)

28

N(-)

30

GND

32

Socket connector 6; (interfaces)


Right EA + z6

Left EA - b8

Right EA - z8

Left E + b10

Right E + z10

Left E - b12

Right E - z12

III **

E-LAN

Left EA + b6

Housing

*)

REGSys is also very flexible with regards to its housing system. The following are just some of the housing option available.
The standard versions are those described by features B05
and B07.
Since the number of inputs, outputs, COMs, etc. in a B01 regulator plug-in module (basic module for all regulation systems
in the housing!) is much larger than the number of terminals
available on the housing, the pin assignment can be individually
suited for all other housing types.
Further housing types can be found in the
brochure Designs.

Material
Degree of protection
Weight
Dimensions
Connection elements
Feature B02
Features B03, B05, B06
B07, B91, B92

A. Eberle GmbH & Co. KG

IV **

Note:

Plastic
IP 65
1.5 kg
See Figure 8
2.8 x 0.8
6.3 x 0.8 Fast-on
Phoenix
Screw/clamp terminals

10

Technical Data

REG-D
REG-D

a-eberle

Status

F1

<U
Display

>U

3 HE

128.5

F2

X = 81,15
y = 76,95

>I

F3

B = 67,818 mm
H = 67,818 mm

F4

F5

local
remote

AUTO

ESC

COM1

MENU

173.5
28 TE

12

REG-D / PAN-D plug-in module 28 TE - Feature B01

287

224

138

52

REG-D

a-eberle

Status

280

F1

<U
Display

>U

F2

X = 81,15
y = 76,95

>I

F3

B = 67,818 mm
H = 67,818 mm

REG-D

F4

a-eberle

F5
Status

F1

<U
local
remote

AUTO

COM1

MENU

ESC

Display

>U

F2

X = 81,15
y = 76,95

>I

F3

B = 67,818 mm
H = 67,818 mm

OVR

<U1

>U2

F4

MODE
F5

288
local
remote

AUTO

))

)))

ESC

CAL

COM1

MENU

)6

0!. !

E1...E12
hher

27

43

BCD 1

12
13

11
1

tiefer

28

44

BCD 2

45

BCD 4

30

46

15

Stillsetzung
Schnellschaltung
Auto
(A/H)

29

31

47

BCD 10

16

Hand

32

48

BCD 20

17

progr.

33

49

VZ

18

progr.

34

50

(-)

144

14

UE
5

19

6
7
8

1A/5A
k

I E1

37

22

38

23

EA+

24

EA-

25
NO
Status
NC

R8

52

R7

53
progr.

Status

10

R9

progr.

36

21

26

E+
E-

39

R6

54
55

progr.

56

40

57

41

58

42

COM2

BCD 8

51

35

(-)

20

E-LAN (L)

UH AC/DC
2

GND
Hand/Auto
H
A

Note:
The housing can be supplied with additional equipment as well as applicationspecific pin assignment according to
agreement

a-eberle

View of fixing in
control panel

A:REG-D

12:34:00

Regler-Modus

MANUELL

1. Sollwert
Istwert
zul. Regelabw.

100.0 %
100.0 V
101.0 V
2.0 %

Stufenstellung

12

-10 %

&

)))

&

&

&

27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42

10

)6
))

27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42

27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42

+10 %
&

Control panel cutout:

310

280.5 +0.2 mm x 138.3 +0.2 mm

Wall mounting housing 49 TE - Feature B91

Panel mounting housing 49 TE - Features B06/B91


11

A. Eberle GmbH & Co. KG

Technical Data

REG-D
287

224

138

52

REG-D

a-eberle

Status

280

F1

<U
Display

>U

F2

X = 81,15
y = 76,95

>I

F3

B = 67,818 mm
H = 67,818 mm

F4

REG-D

a-eberle

F5

Status
local
remote

AUTO

COM1

MENU

ESC

F1

<U
Display

>U

F2

X = 81,15
y = 76,95

>I

F3

B = 67,818 mm
H = 67,818 mm

F4

F5

192

))

local
remote

AUTO

)))

ESC

COM1

MENU

)6

E1...E12

11
1

UH AC/DC
2

UE

28

44

BCD 2

Stillsetzung
Schnellschaltung
Auto
(A/H)

29

45

BCD 4

30

46

BCD 8

31

47

BCD 10

16

Hand

32

48

BCD 20

17

progr.

33

49

VZ

18

progr.

34

50

(-)

19

6
7

1A/5A

I E1

BCD 1

tiefer

15

35

(-)

36

21

37

R8

52

R7

53
progr.

22

23

EA+

24

EA-

25

E+

26

E-

Status

10
NO
Status
NC

38

54

39

55

progr.

40

56

41

57

42

58

COM2

R9

51
progr.

20

E-LAN (L)

144

43

12
13
14

27

hher

R6
GND
Hand/Auto
H
A

Note:
The housing can be supplied with additional equipment as well as applicationspecific pin assignment according to
agreement

COM2

View of fixing in
control panel

a-eberle

A:REG-D

12:34:00

Regler-Modus

MANUELL

1. Sollwert
Istwert
zul. Regelabw.

100.0 %
100.0 V
101.0 V
2.0 %

Stufenstellung

12

-10 %

&

)))

27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42

)6

27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42

&

&

10

))

27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42

&

+10 %
&

310

Control panel cutout:

184.5 +0.2 mm x 138.3 +0.2 mm

Panel mounting housing 30 TE - Feature B05


(Panel mounting housing as standard)

245

Wall mounting housing 49 TE - Feature B07


(Wall mounting housing as standard)

mm

REG-D

a-eberle

Status

a-eberle

Note:
The housing can be
supplied with additional
equipment as well as
application-specific pin
assignment according to
agreement

F1

<U
Display

3 HE

>U

F2

X = 81,15
y = 76,95

>I

F3

B = 67,818 mm
H = 67,818 mm

F4

F5

AUTO

local
remote

ESC

MENU

COM1

84 TE

Mounting rack 84 TE - Feature B92


A. Eberle GmbH & Co. KG

a-eberle

12

Technical Data

REG-D

Fibre-optic cable output as


ST or FSMA connection
Mounting rack 84 TE Rear view with terminals - Feature B92

13

A. Eberle GmbH & Co. KG

Technical Data

REG-D

Network / parallel connection

RS485 interface

The networking of several regulators to a system is particularly


required with transformers connected in parallel. The I sin,
I sin (S) and Master-Slave parallel connection programs can
only be implemented by the system bus (E-LAN). This enables
the individual group members of a parallel connection to communicate with each other easily without the need for additional
components.
The stations do not need to be connected for the operation of a
parallel connection which works in accordance with the cos
procedure. Due to the large distances, such a connection is not
normally possible anyway

Every REG-D regulator is provided with a double E-LAN


interface as standard. It provides the bus connection of individual regulators and monitoring units to a form a voltage
control system.
E-LAN (Energy - Local Area Network)
Features
255 bus stations can be addressed
Multimaster structure
Integrated repeater function
Open ring, bus or combination of bus and ring possible
possible
Log based on SDLC/HDLC framework
Transfer rates of 62.5 or 125 kbit/s
Telegram length 15.6... 375 kbits/s
Average throughput approx. 100 telegrams / sec at 62.5k

Serial interfaces
RS232 interfaces
Connection elements
COM1

Sub Min D on the front of


the device, pin assignment
as on PC
Pin connection
Terminal strip
(Circuit board VI)

COM2

Connection possibilities

PC, terminal, modem, PLC

Number of data bits/ protocol


Transfer rate bit / s

Parity 8, even, off, odd


1200, 2400, 4800, 9600,
19200, 38400, 57600,
76800, 115200
76800, 115200

HANDSHAKE

RTS / CTS or XON / XOFF

COM3
For connection of 15 interface modules (BIN-D, ANA-D) in any
combination to any REG-D regulator.

REGSimTM simulation software


REGSim was designed as a PC-based program for the
simulation of parallel connections of several transformers with
any possible combinations of network and load.
The transformers, the network and the load are simulated in
a mathematically exact manner to ensure that the REG-D
regulators operate in the same way in the simulation as they
do in the network.
The authenticity of the simulation is guaranteed because
REGSimTM uses the original algorithm of the REG-D regulator.
All the setting options correspond to those in the real regulator
and the simulation runs in real time.

REGSys - Overview
L
LW

R
S4
85

R
S2
32

REGSim

Et

WinREG

he

rn
e

E-LAN
IEC 61850
IEC 60850-5-101/103/104
MODBUS, SPABUS,
LONMark, DNP 3.00

CPR-D

a-eberle

EOR-D

Status

Windows 95
Windows 98
Windows NT
Windows 2000
Windows XP

a-eberle

Status

Reset

a-eberle

EOR-D

Status

Reset

COM1

EOR-D

COM1

CPR-D

a-eberle

Status

EOR-D

a-eberle

Status

Reset

Reset

Reset

COM1

COM1

COM1

EOR-D

E-LAN
E-LAN
COM3
RS485

PQI-D
a-eberle

a-eberle

a-eberle
Status

Reset

REG-D

BIN-D

a-eberle

Status

ANA-D

PQI-D

ANA-D

<

F1

km

REG-BO

ELA
N

COM1

BIN-D

<U
Display

>U

F2

X = 81,15
y = 76,95

>I

REG-D

B = 67,818 mm
H = 67,818 mm

F3

E-LAN

F4

RS485

PAN-D

REG-D

a-eberle

Betrieb

Lauflampe

Strung

Phasenfall

Strung

< U1

F1

R e g le r

local
remote

ESC

MENU

REG-DP

a-eberle

a-eberle

Status

F1

<U
Display

>U

Auslsung

F2

X = 81,15
y = 76,95

>I

NOT-AUS

Display

>U

U3

F4

U4

F5

F2

X = 81,15
y = 76,95

>I
F3

B = 67,818 mm
H = 67,818 mm

St u fe ns c h a lt e r

AUTO

a-eberle

Status

<U

Strung
Lei st u ng s s c ha l t e r

> U2

MMU-D

a-eberle

Status

St u fe ns c h a lt e r

F5

F3

B = 67,818 mm
H = 67,818 mm

F4

Reset

F5

COM1
AUTO

local
remote

ESC

MENU

COM1

AUTO

local
remote

ESC

MENU

COM1

COM1

AUTO

local
remote

ESC

MENU

COM1

REG-PC

REG/ST

REG-D

PAN-D

MMU-D

REG-ST

REG-DP

REG-BO

COM1
RS232

RS232

BCD-CODE (Tap position)


Remote control unit
BCD-CODE
a-eberle

REG-S

REG-S

A. Eberle GmbH & Co. KG

a-eberle

REG-F

REG-F(X)

14

Technical Data

REG-D

WinREG parameterisation and


configuration software

PAN-D - Parameters

WinREG was designed for the parameterisation and programming of the system. WinREG can be operated in three different
modes.
In the Panel mode, up to six regulators can be simultaneously
displayed and operated via the mouse.
All settings that can be carried out directly on the regulator via
the membrane keyboard can also be carried out centrally via
WinREG. However, all the regulators need to be connected
together via E-LAN to be able to do this.
This operating mode provides a considerably simplified and
more transparent operation, particularly when the transformers
are operated in parallel.
If WinREG is used to change all the regulators of the transformers that are operating in parallel into the measurement
transformer mode, all the circulating reactive currents of the
transformers can be displayed on a PC monitor in real time.
The Parameter mode allows for an easy parameterisation of
the individual components. The individual parameters can be
entered, stored for future use or transferred to a station using
the clear tabbed structure.
The Terminal mode provides the possibility of direct communication with the system.
Therefore, the WinREG terminal is far easier to use than traditional terminal programs and considerably simplifies the system
programming.
WinREG runs under Windows 95, 98, Windows 2000, NT
or Windows XP and is also available in a modem-enabled
version.

Undervoltage <U1

0 ... -25 %

Undervoltage >U2

0 ... 25 %

Undervoltage U3

0 ... -35 %

Undervoltage U4

0 ... 35 %

Tripping

100 ... 135 V

Switching delay for


<U1, >U2, U3, U4
The standstill can be set separately

1 ... 999s

Lauflampe - Maximalzeit

3 ... 40s

Recorder Mode
Tme grid YT

14 s,
1, 5, 10, 30, min / divisions
All measurement values are stored in seconds, independent of
the selected YT time grid (feed speed).
The value every second represents the arithmetic average of
the previous 10 measurement values generated in intervals of
100 ms.
Memory response
at overflow

Stop or overwrite;
FIFO with overwrite
(First in First out)

Storage time
(Voltage plus tap-change)

> 18.7 days in worst case


On average > 1 month

Parametrierung
Measurement transducer mode

REG-D - Parameters (selection)


Parameter
Permissible regulative deviation
Time factor
1st setpoint value
2nd setpoint value
3rd setpoint value
4th setpoint value
Time behaviour

Current influence
Apparent current / Active current
Gradient
Limitation
LDC
(Line Drop Compensation)
Undervoltage <U
Overvoltage >U
Overcurrent
>I
Tripping
High-speed forward switching
High-speed backwards switching
Standstill
Switching delay for
<U, >U, <I, tripping,
high-speed switching
The standstill can be set separately

Setting range
0.1 ... 10%
0.1 ... 30
60.0 ... 140.0 V
60.0 ... 140.0 V
60.0 ... 140.0 V
60.0 ... 140.0 V
U t = const
REG 5A/E
LINEAR
CONST
Apparent current
Active current
Reactive curren
LDC
0 ... 40 %
0 ... 40 %
R : 0 ... 30
X : 0 ... 30
-25 % ... +10 %
0 ... 25 %
0 ... 210 % (1 A / 5 A)
60 V ... 160 V
0 ... -35 %
0 ... 35 %
-75 % ... 0 %

Measurement quantities
in the display

Voltage Ueff
Current Ieff
Active power P
Reactive power Q
Apparent power S
cos

Circulating reactive current I sin


Frequency f

Analogue output

Max. 6 mA output
(2.5, 5, 10, 20 mA bipolar)

Characteristic curve

Linear, with corner

Max. load RAmax


RA
IAN

RA = 8 V/IAN
Load
Nominal value of the
output current

1 ... 999 s
(High-speed forward
switching 2...999 s)
15

A. Eberle GmbH & Co. KG

A. Eberle GmbH & Co. KG

REG-D block diagram

16

24

Option
M2

-20 ... 0 ... +20 mA

b
b

z
z

Automatic

-20 ... 0 ... +20 mA

-20 ... 0 ... +20 mA

-20 ... 0 ... +20 mA

L(-)

L(+)
z

E9
+

E10 E11 E12 E13 E14 E15 E16

8 10 10 12 12 14 14 16 16 18 18 20 20 22 22 24 24 26 26 28 28 30 30 32 32

Freely configurable

E8
+

Freely configurable

E7

Freely configurable

E6

Freely configurable

E5

Freely configurable

E4

Freely configurable

E3

Freely configurable

E2

Freely configurable

E1

Freely configurable

4 14 16 14 16 26 28 26 28

Freely configurable

26 24

NC contact /
NO contact

z 14

b 10

z 10

b 14

Row

-20 ... 0 ... +20 mA

lower

R2

z 16
b 16

Socket connector no.


Pin assignment

Socket connector no.

Socket connector no.


MANUAL

Pin assignment

128 x 128
DOTS

freely

R3

raise

freely

R1

b 24

z 22

z 28

b 30

b 32

z 30

z 32

Manual / b 22
Auto.
z 20
freely
b 20

GND

BA1

BA2

BA3

BA4

R4

R5

R6

R7

R8

R9

Status

Pol

Row

LCD

Binary inputs

RS232

COM 1

Display

Module 3

6 7 8 9

1 2 3 4 5

front side

D-Sub pin strip

LED

Module 1

Input or output
Module 2

Rx-

CLOCK RAM/ROM

TxD

Analogue - channels (Option E9x)

Keyboard

RS232

COM 2

Power supply
AC or DC

Binary outputs 230 V

Pin assignment 28 32 30

L3

L2

Option
M2

22

E-

L1

E-

20

EA+
E+

EAE+

I E1

Tx+

Tx-

CTS

+12V

Rx+

RS485
(Option R1)

RxD

COM3

20 22 24 20 22 24

Binary outputs
230 V

I E2

GND

E-LAN
R

30 32 30 32

RTS

E-LAN
L

6
b

GND
RI
DTR
CTS
TXD
RTS
RXD
DSR
DCD

8 10 12

8 10 12

EA+

Pin assignment

b
z

EA-

Row

Socket connector no.

Technical Data
REG-D

Freely configurable

Freely configurable

Freely configurable

Freely configurable

-20 ... 0 ... +20 mA

17

Pin assignment

Socket connector no.

48 ... 230 V AC/DC

Binary inputs

R10

Meldungen

R11

R9

z
b

8 10 10 12 12 14 14 16 16

z
6

z
4

z
2

R7

z
2

b
2

b
4

z
b

R1

22 24 22

E-LAN
R

z
8 10 12

z
6

b
4 10 8

z
b

z
b

R6

R5

R4

RS232

R3

8 9

3 4

COM1

8 10 14 14 16 16 20 20 26 24

R2

Binary outputs 230 V

RAM/ROM

Status

E-LAN
L

b
8 10 12

b
6

Keyboard

CLOCK

R8

z
2

Row
Pin assignment 28 32 30
Socket connector no.
3

R12

Display

1
2
3
4
5
6
7
8
+ - + - + - + - + - + - + - + -

R13

Power supply
AC or DC

R14

LED

Designation

>U2

24

U3
z

<U1

22

Regulator
fault

L3

Tapchanger
fault

20

U4
z

EA+

E+

EA-

L1

E-

Highspeed
switching

EA+

6 7

1 2

front side

D-Sub pin strip

z
32

z
30

BA3

b
32

BA2

BA4

28 30

Binary outputs
230 V

GND
RI
DTR
CTS
TXD
RTS
RXD
DSR
DCD

L2

Freely

EA-

E-

32 30 30 28 26 26 24 22 22 20 18 18 16 14 14 12 10 10 8

E+

Row
Pin assignment

Socket connector no.

Designation

Technical Data
REG-D

GND

BA1

Freely
configurable

Freely
configurable

Lower

Raise

EMERGENCY
OFF
Tap-changer
drive

Tripping
of circuit
breaker

in operation

malfunktion

Pol

Freely
configurable

Freely
configurable

Freely
configurable

Freely
configurable

Freely
configurable

Freely
configurable

Freely
configurable

Tap-changer
in operation

L(-)

L(+)

Designation

PAN-D block diagram

A. Eberle GmbH & Co. KG

Technical Data

REG-D

Ordering information
When ordering please note:
Only one code with the same capital letter is possible
If the capital letter is followed by the number 9, additional details in plain text are required
If capital letters are followed by 0, the code can be omitted.

Feature

CODE
REG-D

PAN-D

REG-D

REG-D voltage regulator, 28TE, 3HE plug-in module


Standard version, with double E-LAN interface, COM 1, COM 2,
16 binary inputs, 10 relay outputs plus status relays and
WinREG parameterisation and programming software incl. connection cable

PAN-D

PAN-D monitoring unit, 28TE, 3HE plug-in module


Standard version, with double E-LAN interface, COM 1, COM 2,
8 binary inputs, 14 relay outputs plus status relays

Design
19 plug-in module
Wall-mounting housing (30TE) - without wiring
Wall-mounting housing (30TE) - with wiring
(Terminals compatible with REG 5A)
Wall-mounting housing (30TE) - with wiring
(Terminals compatible with Pantavolt 2)
Panel-mounting housing (30TE) with wiring
Panel-mounting housing (49TE) with wiring
Wall-mounting housing (49TE) with wiring
Wall-mounting or panel-mounting housing (30/49TE) on request
19 mounting rack according on request

B01
B02
B03

B01
B02
-

B03

B05
B06
B07
B91
B92

B05
B06
B07
B91
B92

From monitoring network 80 V ... 110 V ... 185 V AC


External 85 V ... 110 V ... 264 V AC / 88 V ... 220 V ... 280 DCV
External 18 V ... 60 V ... 72 V DC

H0
H1
H2

H0
H1
H2

IEN 1 A
IEN 5 A

F1
F2

Measurement transducer display functions for network quantities


Three-phase current with equal load
Three-phase current with unequal load
U measurement for overvoltage, U and I measurements for undervoltage
Other uses of the transformer ( 2 x I, 2 x U, e.g. triple-wound transformer)

M1
M2
M3
M9

Recorder functions for network quantities


Incl. evaluation software

Without
With

S0
S1

without firmware for parallel operation


with firmware for parallel operation

K0
K1

Power supply

Input current

Parallel operation

Continued on next page


A. Eberle GmbH & Co. KG

18

Technical Data

REG-D

Feature

CODE
REG-D

PAN-D

E00
E91
E92
E93
E94
E95
E96
E97
E98
E99
E900

D1
D2
D3

R0
R1

XW0
XW1
XW9

XL1
XL9

XV10
XV11

Fibre optic cable with FSMA connection


Glass fibre (wavelength 800...900 nm, range 2000 m)
Plastic (wavelength 620...680 nm, range 50 m)

XV13
XV15

Fibre optic cable with ST connection


Glass fibre (wavelength 800...900 nm, range 2000 m)
Plastic (wavelength 620...680 nm, range 50 m)

XV17
XV19

Analogue inputs and outputs


Note:
Please specify the scale if known!:
Example:
Channel 1: -100 ... 0 ... + 100 MW
- 20 ... 0 ... + 20 MW
Channel 2:
0 ... 80 ... 100 V
4 ... 16 ... 20 mA
Channel 3: 1 ... 19 tap-change positions
0 ... 20 mA
Note:
A total of 3 modules may be used. Pay attention to the TMM particularly with use of the
transformer monitoring module!

without
with 2 inputs
with 4 inputs
with 6 inputs
with 2 outputs
with 4 outputs
with 6 outputs
with 2 inputs and 2 outputs
with 2 inputs and 4 outputs
with 4 inputs and 2 outputs
Any combination on request
each with 2 analogue inputs and outputs
PT 100 direct input
Tap-change potentiometer input

Binary inputs (freely programmable)


E1...E8: 48..250 V AC/DC, E9...E16: 10 ... 50 V AC/DC (can also be used as a BCD input)
E1...E16: 48 ...250 V AC/DC (can also be used as a BCD input)
E1...E16: 10 ...50 V AC/DC (can also be used as a BCD input)

RS485 interface (COM 3)


Note:
COM 3 is only required for ANA-D and BIN-D!

without
with

Control system connection: Internal or external:


without (more in Feature Group Y))
with integrated connection (more in Feature Group XL)
with ext. connection (REG-P/PE/PM) more in Feature Group Y)

Integrated protocol interface card


for control connection of REG-D system
for control connection of multiple systems
Note: XL9 can only be combined with XZ15..XZ19 and XZ91

Type of connection:
Copper
RS 232
RS 485 only for 2-wire operation
Note: XV13 .. XV 19 can only be selected in combination with B02B92.
In all other case, select the appropriate fibre optic cable module!

Continued on next page


19

A. Eberle GmbH & Co. KG

Technical Data

REG-D

Feature

CODE
REG-D

PAN-D

IEC60870-5-103 for ABB


IEC60870-5-103 for Areva
IEC60870-5-103 for SAT
IEC60870-5-103 for Siemens (LSA/SAS)
IEC60870-5-103 for Sprecher Automation
IEC60870-5-103 for others

XZ10
XZ11
XZ12
XZ13
XZ14
XZ90

IEC60870-5-101 for ABB


IEC60870-5-101 for IDS
IEC60870-5-101 for SAT
IEC60870-5-101 for Siemens (LSA/SAS)
IEC60870-5-101 for others

XZ15
XZ17
XZ18
XZ19
XZ91

DNP 3.00

XZ20

LONMark

XZ21

MODBUS RTU

XZ22
XZ23

without
with

Y0
Y1

closes during fault


opens during fault

U0
U1

German
English
French
Spanish
Italian
Russian

G1
G2
G3
G4
G5
G8

G1
G2
G3
G4
G5
-

Same as operating manual


German
English
French
Spanish
Italian
Dutch
Czech
Russian

A0
A1
A2
A3
A4
A5
A6
A7
A8

Log

Local/remote switching using the keyboard

Status output

Operating manual

Display text

A. Eberle GmbH & Co. KG

20

Technical Data

REG-D

REG-D accessories

IDENT No.

Socket connector 1

(Electronic connector design F, wire wrap)

582.0197

Socket connector 1

(Electronic connector design F, 2.8 faston)

582.0213.01

Socket connector 2

(Current inputs with leading contacts, 2-pole)

582.0258.10

Socket connector 3

(Hybrid connector designs F24 + H7, wire wrap)

582.0215

Socket connector 3

(Hybrid connector designs F24 + H7, 6.3/2.8


faston)

582.0214

Socket connector 4

Current input with leading contacts, 6-pole

582.0258.20

Blanking plate 14TE

566.0014

Blanking plate 7TE

566.0007

Blanking plate 8TE

566.0008

1 pack of T2 L 250 V microfuses

582.1019

Cable for PC connection (null modem cable)

582.020B

Cable for modem connection

582.2040

Fibre optic cable coupler (E-LAN)

111.9030.10

DCF 77 radio clock

111.9024

USB adapter for null modem cable

111.9046

Modem for REG-Dx/EOR-D/PQI-D/MMU-D (standard version Uh: AC 230 V)

111.9030.02

Modem for PC (industrial version Uh: AC 230 V)

111.9030

Analogue input module (2 inputs)

320.0004

Analogue output module (2 outputs)

320.0003

Input module for tap-change potentiometer total resistance 200 Ohm...2 kOhm

320.0002.01

Input module for tap-change potentiometer total resistance >2 kOhm...20 kOhm

320.0002.03

Input module for PT 100 according to DIN 43760 in 3-conductor circuit.

320.0005

E-LAN Y-connection with booster

REG-ST

E-LAN PC adapter with booster

REG-PC

E-LAN PC adapter, Y-connection with booster

REG-ST3

E-LAN booster (wide-range network)

REG-BO

Additonal operating manuals for REG-D plus PAN-D

GX

Additonal operating manuals for REG-D (please state language)

GX

21

A. Eberle GmbH & Co. KG

Technical Data

REG-D

Additions to REG-D

IDENT. No.

Transformer monitoring module TMM


Consisting of:

TMM

Firmware- Update (2.X)


Analogue module with two inputs for temp. measurement transducer
Input for PT 100 according to DIN 43760 in 3-conductor circuit
Operating manual and Windows user interface
via WinREG

A1
A2

Additional analogue input module (2 inputs)

320.0004

Additional analogue output module (2 outputs)

320.0003

Additional input module for PT 100 according to DIN 43760 in 3-conductor circuit

320.0005

Profibus-DP interface module


Incl. RS 485 interface and connection cable

Profi-DP

Design:
can be installed on standard mounting rails (120 x 75 x 27) mm, with ext. 24 V
power supply
Plug-in module: 12TE/3HE
TCP/IP Adapter (10MB/s)
can be installed on standard mounting rails with power supply for Uh 230 V AC

REG-COM
A01

as 8TE plug-in module, 3HE with power supply:


85 V ... 110 V ... 264 V AC / 88 V ... 220 V ... 280 V DC

A02

as 8TE plug-in module, 3HE with power supply:


18 V ... 60 V ... 72 V DC

A03

100MB/s TCP/IP adapter)

A90

Fibre optic cable module


with ST connection (glass or plastic))
with FSMA connection (glass or plastic)

A. Eberle GmbH & Co. KG

B0
B1

22

Module 1
A90
A91

Technical Data

REG-D

Notes: .....................................................................................................................
................................................................................................................................
................................................................................................................................
................................................................................................................................
................................................................................................................................
................................................................................................................................
................................................................................................................................
................................................................................................................................
................................................................................................................................
................................................................................................................................
................................................................................................................................
................................................................................................................................
................................................................................................................................
................................................................................................................................
................................................................................................................................
................................................................................................................................
................................................................................................................................
................................................................................................................................
................................................................................................................................
................................................................................................................................
................................................................................................................................
................................................................................................................................
................................................................................................................................
................................................................................................................................
................................................................................................................................
................................................................................................................................
................................................................................................................................
................................................................................................................................
................................................................................................................................
................................................................................................................................
................................................................................................................................
................................................................................................................................
23

A. Eberle GmbH & Co. KG

Technical Data

REG-D

A.Eberle GmbH & Co. KG

presented by:

Aalener Str. 30/32


D-90441 Nrnberg
Phone: +49 (0) 911 / 62 81 08-0
Fax:
+49 (0) 911 / 62 81 08 96
http://www.a-eberle.de
info@a-eberle.de
A. Eberle GmbH & Co. KG

24