AUTOMATIC TRANSFER SWITCH

ATyS 3e, 6s, 6e


Notice dutilisation - Operating Instructions
F

GB

SOCOMEC GROUP SWITCHING PROTECTION & UPS

MAKE YOUR BUSINESS SAFE

Systmes de Coupure et de Protection


Industrial Switching and Protection Systems

531_848_b-1

10/02/05

11:42

Page 2

F
LA GAMME ATyS ____________________________3
PRSENTATION GNRALE __________________4
Prsentation des produits ___________________4
Identification _______________________________5
Environnement_____________________________6
Accessoires disponibles en montage client _____7
Accessoires disponibles en montage usine _____7
INSTALLATION ______________________________8
Dimensions _______________________________8
Sens de montage _________________________10
Montage des accessoires client _____________10
Accessoires usine _________________________13
RACCORDEMENTS _________________________14
Circuits de puissance ______________________14
Circuits de commande ATyS 3e _____________16
Circuits de commande ATyS 6s _____________18
Circuits de commande ATyS 6e _____________20
Kit de prise de tension et dalimentation ______22
UTILISATION _______________________________28
Commande manuelle ______________________28
Commande lectrique _____________________29
FONCTIONNEMENT ATyS 3e ________________30
Prsentation______________________________30
Modes dutilisation ________________________31
Programmation ___________________________31
Visualisation ______________________________34
FONCTIONNEMENT ATyS 6s et 6e ___________35
Prsentation______________________________35
Modes dutilisation ________________________36
Programmation ___________________________37
Exploitation ______________________________46
Visualisation ______________________________49
Squences automatiques __________________51
OPTIONS __________________________________54
Module de communication _________________54
AIDE AU DPANNAGE ______________________61
PICES DE RECHANGE _____________________62
ANNEXES _________________________________63
Typologie des rseaux _____________________63
Programmation et cblage ATyS 6 ___________64

Summary

Sommaire

GB
THE ATYS RANGE __________________________67
GENERAL PRESENTATION __________________68
Product introduction _______________________68
Identification______________________________69
Environment______________________________70
Customer mounted accessories _____________71
Factory fitted accessories __________________71
INSTALLATION _____________________________72
Dimensions ______________________________72
Mounting orientation_______________________74
Customer mounted accessories _____________74
Factory fitted accessories____________________77
CONNECTIONS ____________________________78
Power circuits ____________________________78
Control circuits ATyS 3e ____________________80
Control circuits ATyS 6s ____________________82
Control circuits ATyS 6e ____________________84
Voltage sensing and power supply kit ________86
OPERATION _______________________________92
Manual operation _________________________92
Electrical operation ________________________93
OPERATION ATyS 3e________________________94
Presentation______________________________94
Operational modes ________________________95
Programming _____________________________95
Visualisation ______________________________98
OPERATION ATyS 6s & 6e ___________________99
Presentation______________________________99
Operational modes _______________________100
Programming____________________________101
Operation _______________________________110
Visualisation _____________________________113
Automatic sequences_____________________115
OPTIONS _________________________________118
Communication module___________________118
TROUBLESHOOTING GUIDE _______________125
SPARE PARTS ____________________________126
ANNEXES ________________________________127
Networks analysis________________________127
Programming and connection on ATyS 6s ___128

SOCOMEC - Rf. : 531 848 B

531_848_b-3

10/02/05

11:37

Page 67

Automatic Transfer Switch

ATyS

THE ATyS RANGE

The ATyS family proposes a complete motorised


changeover range including electrical and mechanical
interlocking. Manual operation is always possible on all
the products in case of emergency.
The electric command is realised via a motorised
module, electronically driven by 2 types of logic:
Remote controlled: ATyS 3 products are controlled by
volt free contacts allowing the switch to be driven in 1,
0 or 2 position. These contacts can come from an
external control logic.

ATyS 3s

ATyS 3e

ATyS 6s

Automatic control: AtyS 6 products integrate all


controls, timers and relays required to realise a
Normal / Emergency application.
ATyS 6e and 6m versions also integrate the remote
controlled feature.
The motorised and control modules can easily be
replaced without disconnecting the power cables.

ATyS 6e

ATyS 6m

ATyS C30

MOTORISED CHANGEOVER
Dual power supply
Control relay for
changeover

Integrated control relay


Metering
Com option

Communication option

2 I/2 O option

2 inputs / 2 outputs option


Remote interfaces ATyS D10 & D20

> This instruction manual applies to following


products:
Range from 125 to 1 600 A 230 Vac three or four poles:
ATyS 3e
ATyS 6s
ATyS 6e

SOCOMEC - Rf.: 531 848 B

> Following products are delivered with their own


instruction manual:
ATyS 3s
ATyS 6m
Remote interfaces ATyS D10 & D20
Control relay ATyS C30

67

531_848_b-3

10/02/05

11:37

Page 68

Automatic Transfer Switch

ATyS

Product introduction
Identification
Environment
Customer mounted accessories
Factory fitted accessories

GENERAL PRESENTATION
ATyS 3e, 6s, 6e

Product introduction

Power supply and


control module

Optional modules slots

Switch II
Switch I
Changeover
switch
Changeover
switch position
indication

ATYS 097 A NB

Motorized
module

Manual operation handle housing

Auxiliary contacts terminals


Auto / manu (AUT / ) selector
(key on ATyS 3e and 6e)

Padlocking mechanism

Handle support

ATYS 110 A NB

Handle for manual operation

68

SOCOMEC - Rf.: 531 848 B

531_848_b-3

10/02/05

11:37

Page 69

Automatic Transfer Switch ATyS

GENERAL PRESENTATION

Identification

Rating and
changeover switch identification

Electrical characteristics
according to standards
Switch I & II
identification

Complete product
serial number

SOCOMEC - Rf.: 531 848 B

ATyS
model and rating

ATyS model

Serial number and


characteristics of the
power supply and
control module

69

531_848_b-3

10/02/05

11:37

Page 70

Automatic Transfer Switch

ATyS

Product introduction
Identification
Environment
Customer mounted accessories
Factory fitted accessories

GENERAL PRESENTATION
ATyS 3e, 6s, 6e

Environment
The complete product meets the following environmental
requirements.

IP-RATING
IP2 and class II for the front face.

OPERATION
> Temperature

> Altitude

-10 +40 C without de-rating


-20 +70 C with de-rating (refer to catalogue)

Maximum altitude without de-rating = 2 000 metres

> Hygrometry
80 % humidity without condensation at 55 C
95 % humidity with condensation at 40 C

STORAGE
> Temperature
-20 to +70 C
SVRMO 029 A

> Period
Storage period = maximum 1 year.
It is recommended not to stock the products in a
corrosive or salty atmosphere.

630 A

800 A

WEIGHTS
Ratings (A)

125

160

250

400

630

800

Nb of poles

Weight (kg)

4.1

4.1

4.2

4.5

4.6

5.5

6.5

1 000
4

1 250
3

1 600
3

20.4 23.9 23.9 25.4 25.4 30.4 36.9 42.9

STANDARDS AND DIRECTIVES


> The product meets the applicable european directive
CE.

> The product also meets applicable international


directives IEC:
- IEC 60947-3: low voltage devices, disconnection
switches (the whole range)
- IEC 60947-6-1: low voltage devices, automatic transfer
and connection material (ATyS 6s & 6e).

70

SOCOMEC - Rf.: 531 848 B

531_848_b-3

10/02/05

11:37

Page 71

Automatic Transfer Switch ATyS

GENERAL PRESENTATION

Customer mounted accessories


BRIDGING BARS

3e 6s 6e

To connect switch I & II load terminals together.

VOLTAGE SENSING AND


POWER SUPPLY KIT

3e 6s 6e

Incoming and outgoing protection against direct contact


with the connection terminals or parts.

3e 6s 6e

Allows voltage sensing and power supply connections


from switch terminals to power supply and control
module. Secure cables tray, no specific cable protection required (fuse type).

OPTIONAL MODULES

TERMINAL SCREENS

3e 6s 6e

CONTROL VOLTAGE
TRANSFORMER

3e 6s 6e

Allows a standard 230 V AC device to be supplied with


400 V AC.

MOUNTING SPACERS
(125 TO 630 A)

3e 6s 6e

Raises the devices terminals 10 mm away from the


backplate or frame on which the device is mounted.

> N 1- communication module


Control and state feedback of the changeover switch via
a 2 or 3-wire RS485 link with protocol JBUS/MODBUS
and transmission speed up to 38400 bauds.

> N 2 - 2 Inputs/2 Outputs

REMOTE INTERFACES
ATYS D10 OR D20

3e 6s 6e

> ATyS D10


TERMINAL SHROUDS
(125 TO 630 A)

3e 6s 6e

Incoming and outgoing protection against direct contact


with the connection terminals or parts.
Cannot be mounted in the rear position at the same time
as the voltage sensing and power outlet kit or the bridging bars.
Can be mounted top or bottom, in front or in rear
position.

Allows the state of the source and switch position to be


displayed remotely.

> ATyS D20


Allows sources state and switch position to be
displayed remotely
Allows configuration, control and metering remotely
(from front panel).

Factory fitted accessories


SUPPLEMENTARY AUXILIARY
CONTACT (AC)

3e 6s 6e

Pre-breaking and signalling of positions I and II: 1 additional NO / NC auxiliary contacts in each position.
Low level AC: please consult us.

PADLOCKING IN 3 POSITIONS

3e 6s 6e

HANDLE KEY INTERLOCKING


ACCESSORIES

3e 6s 6e

Locking of the electrical and the manual operation by


means of a RONIS EL11AP lock.
Possibility of locking in another position, if the
Padlocking in the 3 positions option is ordered.
Not compatible with flush mounting.

Allows locking of the operation in the 3 positions I, 0


and II.

SOCOMEC - Rf.: 531 848 B

71

531_848_b-3

10/02/05

11:37

Page 72

Automatic Transfer Switch

ATyS

Dimensions
Mounting orientation
Customer mounted accessories
Factory fitted accessories

INSTALLATION
ATyS 3e, 6s, 6e

Dimensions
125 to 630 A
J
M

J1

U
4

119

223

101

140

CA

120

Fix. 180

Fix. 195

AA

BA

AC

270

CA

10.5

48

Y
3

2
10

11
3

85

Z1
5

Z2

H
C
1

CA

Fix. 180

Fix. 195

138
20

1. Locking bracket with 3 padocks max


2. Maximum handle radius, operating angle 2 x 90
3. Connection zone
4. Mounting spacer (accessory)
Rating
(A)
125
160
250
400
630

72

50.5

Consider space required for handle operation


and cables connection.

ATYS 018 C

165

5. terminal shrouds (accessory)


6. Cut out dimension
7. Removable handle

Overall
Terminal
Switch body
Switch
dimensions shrouds
mounting
A 3p. A 4p. C
AC F 3p. F 4p. H J 3p. J 4p. J 1 M 3p. M 4p.
304 340 244 235 286.5 322.5 151 154 184 34 120 150
304 340 244 235 286.5 322.5 151 154 184 34 120 150
345 395 244.5 280 328 378 153 195 245 35 160 210
345 395 244.5 280 328 378 153 195 245 35 160 210
394 459 320.5 400 377 437 221 244 304 34 210 270

Connection terminals
T
36
36
50
50
65

U
20
20
25
35
45

V
25
25
30
35
50

W X 3p.
9
28
9
28
11 33
11 33
13 42.5

X 4p.
22
22
33
33
37.5

Y
3.5
3.5
3.5
3.5
5

Z1
38
38
39.5
39.5
53

Z2
134
134
134.5
134.5
190

AA
135
135
160
170
260

BA CA
115 10
115 10
130 15
140 15
220 20

SOCOMEC - Rf.: 531 848 B

531_848_b-3

10/02/05

11:37

Page 73

Automatic Transfer Switch ATyS

INSTALLATION

Dimensions
800 to 1 600 A
J

51.5

12.5

166

2
3

12.5

280
166

207

AA

250

AC

169

250

48
3

Z1

253.5

94

293

391.5

1250 A

1600 A

16 x 11

12,5
5

8.5

33

15.75

28.5

138
6

15

12,5

20

25 25
30
30
45
45
90

15.75

60

50.5

ATYS 019 C

214

50

8.5

SVR 078 B

10 33

15

SVR 077 A

15 28.5

SVR 098 A

800 to 1000 A

Consider space required for handle operation


and cables connection.
1. Locking bracket with 3 padocks max
2. Maximum handle radius, operating angle 2 x 90
3. Connection zone
4. Protection screen (accessory)
Rating
(A)
800
1000
1250
1600

Overall Terminal
dimensions shrouds
B
AC
370
461
370
461
370
461
380
481

SOCOMEC - Rf.: 531 848 B

5. terminal shrouds
6. Cut out dimension
7. Removable handle

Switch body
F 3p.
504
504
504
596

F 4p.
584
584
584
716

J 3p.
306.5
306.5
306.5
398.5

Switch mounting
J 4p.
386.5
386.5
386.5
518.5

M 3p.
255
255
255
347

M 4p.
335
335
335
467

Connection terminals
T
80
80
80
120

U
50
50
60
90

V
60.5
60.5
65
44

X
60
60
60
66

Y
7
7
7
8

Z1
66.5
66.5
66.5
67.5

AA
321
321
330
288

73

531_848_b-3

10/02/05

11:37

Page 74

Automatic Transfer Switch

ATyS

Dimensions
Mounting orientation
Customer mounted accessories
Factory fitted accessories

INSTALLATION
ATyS 3e, 6s, 6e

ATYS 165 A

Mounting orientation

630 A
800 A

X
O




O
X

X
X

X: forbidden
O: possible
: recommended
Always mount the product on a vertical surface.

Customer mounted accessories


BRIDGING BARS
> 800 to 1250 A

ATYS 162 A

ATYS 120 A

> 125 to 630 A

Recommended tightning
torque

Maximum tightning torque

M6: 4.5 N.m


M8: 8.3 N.m
M10: 20 N.m
M12: 40 N.m

M6: 5.4 N.m


M8: 13 N.m
M10: 26 N.m
M12: 45 N.m

Possible to mount the bridging bars on either side of


the switch.
74

SOCOMEC - Rf.: 531 848 B

531_848_b-3

10/02/05

11:37

Page 75

Automatic Transfer Switch ATyS

INSTALLATION

Customer mounted accessories


3e 6s 6e

OPTIONAL MODULES
> Presentation
Connectors are dedicated to optional modules:
2 slots on ATyS 3e
4 slots on ATyS 6e
Modules can be mounted on any slots. Following
procedure should nevertheless be followed:
--> 2nd option on slot 2
--> 3rd option on slot 3
--> 4th slot 4 not used

> Installation

ATYS 154 A

1st option on slot 1

x1

Installation

ATYS 159 A

Connect modules power off.

A 3 minutes power off action is


necessary to allow module recognition
(only on ATyS 6e).

SOCOMEC - Rf.: 531 848 B

Verify options are correctly tightened.

75

531_848_b-3

10/02/05

11:37

Page 76

Automatic Transfer Switch

ATyS

Dimensions
Mounting orientation
Customer mounted accessories
Factory fitted accessories

INSTALLATION
ATyS 3e, 6s, 6e

Customer mounted accessories


3e 6s 6e

Example: identification In1 to In 4 and Ou1 to Ou4


Outputs

Inputs

In3

In4

In2

I I I I
14 13 24 23

2I/2O

2I/2O

O O O O
24 23 14 13

O O O O
24 23 14 13

Ou4
4

In1

I I I I
14 13 24 23

Ou3

Ou2

C
O
M

Ou1
2

ATYS 247 A GB

For ATyS 6e, up to two 2 Inputs / 2 Outputs can be


mounted. Terminals identification depends on modules
location. 2I / 2O terminals identification is chronological
from first module, not taking into account communication module.

ATYS 114 A

> Inputs/outputs identification

VOLTAGE SENSING AND POWER SUPPLY KIT


Refer to connections paragraph for kit mounting and
connection.
To be mounted before power cables connection.

TERMINAL SHROUDS
(AVAILABLE FROM 125 TO 630 A)

PROTECTION SCREENS

76

ATYS 164 A

ATYS 163 A

Upstream, downstream, front or back mounting


Only possible to mount front terminal shroud in case
of bridging bars.

SOCOMEC - Rf.: 531 848 B

531_848_b-3

10/02/05

11:37

Page 77

Automatic Transfer Switch ATyS

INSTALLATION

Customer mounted accessories


POWER TRANSFORMER

400 Vac

400 Vac

230 Vac
ATYS 191 A

201 202

230 Vac

102 101

Source 2

Power 230 Vac

Source 1

Power 230 Vac

ATYS 188 A

For 400 Vac application (Phase to Phase voltage) without


neutral.
One transformer is necessary for each supply.

MOUNTING SPACERS
(AVAILABLE FOR 125 A TO 630 A)

Allows screws head isolation

Factory fitted accessories


2nd CUSTOMER AUXILIARY CONTACT

ATYS 400 A

ATYS 266 A

HANDLE KEY INTERLOCKING ACCESSORY

SOCOMEC - Rf.: 531 848 B

77

531_848_b-3

10/02/05

11:37

Page 78

Automatic Transfer Switch

ATyS

Power circuits
Control circuits
Voltage sensing and
power supply kit

CONNECTIONS
ATyS 3e, 6s, 6e

Power circuits
3e 6s 6e

STANDARD CONNECTION PRIORITY SOURCE ON SWITCH I


The product is delivered from the factory with the following
configuration:
the source 1 on control module (connectors 101 to
106) is linked to switch I
the source 2 on the control module (connectors 201
to 206) is linked to switch II.

In case of voltage sensing and power supply


kit mounting on ATyS 6, mount the kit before
power cables connections.

Load

II

Source
1

ATYS 167 A

ATYS 200 A GB

Source
2

CONNECTIONS
Take into account connection cables length for section selection.
125 A

160 A

250 A

400 A

630 A

800 A

1 000 A

1 250 A

1 600 A

35

50

95

185

2 x 150

2 x 185

Maximum cables section Cu (mm )

50

95

150

240

2x300

2x300

4x185

4x185

6x185

Maximum bars width Cu (mm) at Ith

20

20

32

32

50

63

63

63

100

Minimum cables section Cu (mm ) at Ith


2

Minimum bars section Cu (mm ) at Ith

ATYS 166 A

78

2x30x5 2x40x5 2x60x5 2x60x5 2 x80x5

Recommended tightning
torque

Maximum tightning torque

M6: 4.5 N.m


M8: 8.3 N.m
M10: 20 N.m
M12: 40 N.m

M6: 5.4 N.m


M8: 13 N.m
M10: 26 N.m
M12: 45 N.m
SOCOMEC - Rf.: 531 848 B

531_848_b-3

10/02/05

11:37

Page 79

Automatic Transfer Switch ATyS

CONNECTIONS

Power circuits
3e 6s 6e

SPECIFIC CONNECTION PRIORITY SOURCE ON SWITCH II


Load

Some applications may require source 1 to be


connected to switch II.
A software modification is then required to change internal link between sources 1 et 2 and switches I & II.

ATYS 201 A GB

Source
2
Source
1

II

ATYS 267 A

> Configurations summary and modifications required


Configuration

Modification required
(refer to programming, Setup, variable Sce)

Source 1 connected to switch I


Source 2 connected to switch II

Standard
(factory)

Configure source 1 on switch I


Variable Sce = I

Source 1 connected to switch II


Source 2 connected to switch I

Specific

Configure source 1 on switch II


Variable Sce = II

Refer to Programming, chapter Setup, to


modify Sce variable.

SOCOMEC - Rf.: 531 848 B

79

531_848_b-3

10/02/05

11:37

Page 80

Automatic Transfer Switch

ATyS

Power circuits
Control circuits
Voltage sensing and
power supply kit

CONNECTIONS
ATyS 3e

Control circuits
EXAMPLE: 400 Vac (P-P) APPLICATION WITH NEUTRAL CONDUCTOR

L1
L2
L3
N

L1
L2
L3
N

F1
Power supply 1
F1, F2
Fuse protection
230 Vac 5 A

COMMAND

Power 230 V~

201202

Power supply 2

Power 230 V~

F2

102 101

POWER

Switch I is linked to source 1 information.

ATYS 092 A GB

317 316 315 314 313


64 63

II

AUT

13 14 24 34 43 44 53 54

Verify power supply terminals 101-102 and


201-202: 230 Vac nominal.

80

2
O O O O
24 23 14 13

II
I
0

RJ

SIGNALISATION

317 316 315 314 313

C
O
M

Opt 1

I I I I
14 13 24 23

Opt 2

64

10 to 30 Vdc

63

inhibition

II

81 82 84

91 92 94

Maximum control cables length = 10 m. In


case of longer distance, insert control relays.

SOCOMEC - Rf.: 531 848 B

531_848_b-3

10/02/05

11:37

Page 81

Automatic Transfer Switch ATyS

CONNECTIONS

Control circuits ATyS 3e


Denomination Terminals Description
Source 1

Power supply 101


102
201
202
Control
313
(impulse mode
contactor
314
mode to
315
change
316
programming) 317
13
14
24
34
Auxiliary
43
contact
44
/ AUT &
53
padlock
54
Fault relay
63
64
Second
81
auxiliary
82
contacts
84
(option)
91
92
94
Option
0
Communication +
Option
I13
2 Inputs /
I14
2 Outputs
I23
I24
O13
O14
023
024

Characteristics
220 to 240 Vac 20 %

Recommended
section
1.5 mm2

Source 2
Control inhibition
if closed 317
Position II order if closed with 317
Position I order if closed with 317
Position 0 order if closed with 317
Specific voltage supply
Common control terminals 313 to 316
Common I - 0 - II
AC position I NO
AC position II NO
AC position 0 NO
Auto / manu selector position
Closed in automatic position
Padlocked information
Closed if padlock is in place
Relay closed when product is faulty
(if product is powered)
Commun AC position I
AC position I NC
AC position I NO
Commun AC position II
AC position II NC
AC position II NO
Connection RS485

Position
auxiliary
contact

+
+
-

Input
Transfer control
Input
Source 2 available
Output Relay EJP

1.5 mm2

do not connect to any


power supply
5A AC1 / 250 V

1.5 mm2

5A AC1 / 250 V

1.5 mm2

5A AC1 / 250 V

1.5 mm2

5A AC1 / 250 V

1.5 mm2

to power from 10 to 30 Vdc 1.5 mm2


to power from 10 to 30 Vdc 1.5 mm2
5A AC1 / 250 V

1.5 mm2

Fault Output relay

SOCOMEC - Rf.: 531 848 B

81

531_848_b-3

10/02/05

11:37

Page 82

Automatic Transfer Switch

ATyS

Power circuits
Control circuits
Voltage sensing and
power supply kit

CONNECTIONS
ATyS 6s

Control circuits

F1, F2
Fuse protection
230 Vac 5 A

103
105
106

207 208 209 210

207 208 209 210

73 74

73 74

* internal link between terminals

II

13 14 24 34

II

81 82 84

91 92 94

Verify power supply terminals 101-102 and


201-202: 230 Vac nominal.

82

SOCOMEC - Rf.: 531 848 B

ATYS 093 A GB

L3

L3

Voltage sensing

L2

206

Voltage sensing

205

104

L1

204

COMMAND

102 101

Power 230 V~

2
203

SIGNALISATION

F1

201202

Power 230 V~

F2

L2

L1
L2
L3
N

L1
L2
L3
N

L1

POWER

EXAMPLE: 400 Vac (P-P) APPLICATION WITH NEUTRAL CONDUCTOR

531_848_b-3

10/02/05

11:37

Page 83

Automatic Transfer Switch ATyS

CONNECTIONS

Control circuits ATyS 6s


Denomination Terminals Description
Power supply Power 101
1
230 V~102
Power supply Power 201
2
230 V~202
Sensing inputs N (103)
source 1
L3 (104)
L2 (105)
L1 (106)
Sensing inputs L1 (203)
source 2
L2 (204)
L3 (205)
N (206)
Commands
207
208
209
210
Genset
73
start signal** 74
Position
13
auxiliary
14
contacts
24
34
Options
81
Second
82
position
84
auxiliary
91
contacts
92
94

Source 1

Characteristics
220 to 240 Vac 20 %

Recommended
section
1.5 mm2

Source 2
Neutral
Phase 3
Phase 2
Phase 1
Phase 1
Not connected
Phase 3
Not connected
Commands inputs Common terminal
Backup source transfer control input
Remote test on load input
Not connected
Genset start / stop relay - 2 stable positions
Programmable state - factory setting = NO, close to start
Common I - 0 - II
AC position I NO
AC position II NO
AC position 0 NO
Common AC position I
AC position I NC
AC position I NO
Common AC position II
AC position II NC
AC position II NO

500 Vac (phase-phase)


maximum
288 Vac (phase-neutral)
maximum
500 Vac (phase-phase)
maximum

1.5 mm2

1.5 mm2

1.5 mm2
Do not connect
to any power supply
Dry contact
5A AC1 / 250 V
5A AC1 / 250 V

4 mm2

5A AC1 / 250 V

1.5 mm2

1.5 mm2

Voltage sensing precision: 1 %

* Terminal numbers can be different in the case of voltage sensing and power supply kit connection (refer to kit specific
configurations).
** Refer to programming, setup, to change output relay state.

SOCOMEC - Rf.: 531 848 B

83

531_848_b-3

10/02/05

11:37

Page 84

Automatic Transfer Switch

ATyS

Power circuits
Control circuits
Voltage sensing and
power supply kit

CONNECTIONS
ATyS 6e

Control circuits

II

AUT

13 14 24 34 43 44 53 54

102 101
103
105
106
317 316 315 314 313
64 63
RJ

104

L2

L3

Voltage sensing

RJ

73 74

Opt 1

207 208 209 210

Opt 2

73 74

Opt 3

L3

207 208 209 210

Opt 4

L2

206

Voltage sensing

205

COMMAND

L1

204

SIGNALISATION

F1, F2
Fuse protection
230 Vac 5 A

2
203

F1

L1

201202

Power 230 V~

F2

Power 230 V~

L1
L2
L3
N

317 316 315 314 313

L1
L2
L3
N

64 63

POWER

EXAMPLE: 400 Vac (P-P) APPLICATION WITH NEUTRAL CONDUCTOR

Inhibition
2
1
0

RJ45 8/8 link


I

II

81 82 84

91 92 94

Remote Interface
ATyS D10 or D20

ATYS 094 A GB

+
I I I I
14 13 24 23

I I I I
14 13 24 23

O O O O
24 23 14 13

O O O O
24 23 14 13

C
O
M
0

Verify power supply terminals 101-102 and


201-202: 230 Vac nominal.

Maximum control cables length = 10 m. In


case of longer distance, insert control relays.
Remote interfaces maximum connection
cable (RJ45) = 3 m.

84

SOCOMEC - Rf.: 531 848 B

531_848_b-3

10/02/05

11:37

Page 85

Automatic Transfer Switch ATyS

CONNECTIONS

Control circuits ATyS 6e


Denomination Terminals(1) Description
Power supply Power 101
1
230 V~102
Power supply Power 201
2
230 V~202
Sensing inputs N (103)
source 1
L3 (104)
L2 (105)
L1 (106)
Sensing inputs L1 (203)
source 2
L2 (204)
L3 (205)
N (206)
Commands
207
208
209
210
Genset
73
start signal(2) 74
Control
313
(Impulse /
contactor
314
mode to
315
change
316
programming) 317
Remote interface
conection
Position
auxiliary
contacts

RJ

13
14
24
34
Auxiliary
43
contacts
44
/ AUT &
53
Padlock
54
Fault
63
relay
64
Second
81
auxiliary
82
contact
84
(option)
91
92
94
Option
0
Communication +
Option
I13 +
2 Inputs /
I14 2 Outputs
I23 +
I24 O13
O14
O23
O24

Source 1

Characteristics
220 to 240 Vac 20 %

Recommended
section
1.5 mm2

Source 2
Neutral
Phase 3
Phase 2
Phase 1
Phase 1
Not connected
Phase 3
Not connected
Commands inputs Common terminal
Backup source transfer control input (CTS)
Remote test on load input
DC power supply for 2I / 2O
Genset start / stop relay - 2 stable positions
Programmable state - factory setting = NO, close to start
Control activation
if closed with 317
Position 2 order if closed with 317
Position 1 order if closed with 317
Position 0 order if closed with 317
Specific voltage supply
Common control terminals 313 to 316
ATyS D10 or D20 connection
Common I - 0 - II
AC position I NO
AC position II NO
AC position 0 NO
Auto / manu selector position
Closed in automatic position
Padlocked information
Closed if padlock is in place
Relay closed when product is faulty
(if product is powered)
Common AC position I
AC position I NC
AC position I NO
Common AC position II
AC position II NC
AC position II NO
Connection RS485

Input
Function according to programming
Input
Function according to programming
Output Relay
Function according to programming
Output Relay
Function according to programming

500 Vac (phase-phase)


maximum
288 Vac (phase-neutral)
maximum
500 Vac (phase-phase)
maximum
288 Vac (phase-neutral)
maximum

1.5 mm2

1.5 mm2

1.5 mm2
Do not connect to any
power supply
Dry contact
5A AC1 / 250 V

4 mm2
1.5 mm2

Do not connect to any


power supply
Maximum distance 3 m.

RJ45 8 / 8

5A AC1 / 250 V

1.5 mm2

5A AC1 / 250 V

1.5 mm2

5A AC1 / 250 V

1.5 mm2

5A AC1 / 250 V

1.5 mm2

To power from 10 to 30 Vdc(3) 1.5 mm2


To power from 10 to 30 Vdc(3) 1.5 mm2
5A AC1 / 250 V

Voltage and frequency sensing precision: 1 %


(1) Terminal numbers can differ depending on voltage sensing and power supply kit configuration.
(2) Refer to programming, Setup, to modify relay state.
(3) It is recommended to power 2I / 2O modules from terminals 207-210 (refer to connection diagram).
SOCOMEC - Rf.: 531 848 B

1.5 mm2

85

531_848_b-3

10/02/05

11:37

Page 86

Automatic Transfer Switch

ATyS

Power circuits
Control circuits
Voltage sensing and
power supply kit

CONNECTIONS
ATyS 6s, 6e

Voltage sensing and power supply kit

3e 6s 6e

Only for ATyS 6. All sensing and power connections


required to make the product work are included.
ATYS 012 A

Mount the kit before power cables


connection.
Load

STANDARD CONFIGURATION

230 V

The kit is delivered from factory with the following configuration:


3 phases network 400 / 230 Vac 4 wires or 230 Vac
3 wires
bottom cables entry
neutral conductor on the right (in case of 4 wires
configuration)
source 1 connected to switch I.

400 V

The kit can be adapted to other configurations, but


then requires, connections and / or programming
modifications.

ATYS 202 A GB

N
Source 1
Source 2

KIT INSTALLATION (FOR STANDARD 4 WIRES CONFIGURATION)


Load

ATYS 203 A GB

Be careful not to damage contacts during kit


mounting and power cables connections
(tighten cables carefully).

800 A
Specific strips
to fixe cables tray

Sources

ATYS193 A

ATYS 206 A

630 A

Bottom view
86

Cables tray positionned FAST ON plug


on the specific supports connections
Bottom view
SOCOMEC - Rf.: 531 848 B

531_848_b-3

10/02/05

11:37

Page 87

Automatic Transfer Switch ATyS

CONNECTIONS

Voltage sensing and power supply kit


CONNECTION KIT DIAGRAM
> Standard configuration

> Wires numbers

Black wires: switch I


Red wires: switch II

Wires numbers have been determined in accordance


to power switches terminals
Example: black and red wires 1-2 always connected to
terminals 1 or 2 from switch I or II.

> In top cable entry configuration (sources


connected from the top)
Black wires: switch II
Red wires: switch I
1
1

II
I
2
2

Example: 4 wires kit (4 poles)


630 A

800 A

Kit connection on
power switches terminals

1-2

3-4

5-6

7-8

1-2

3-4

5-6

7-8

1-2

3-4

5-6

7-8

1-2

3-4

5-6

7-8

Red wires

7-8

5-6

3-4

Black wires

1-2

7-8

ATYS 204 A GB

206

205

SOCOMEC - Rf.: 531 848 B

204

203

202201

mechanical cables
support

5-6

3-4

1-2

101 102

103

104

105

106

Connection on power supply and control module


87

531_848_b-3

10/02/05

11:37

Page 88

Automatic Transfer Switch

ATyS

Power circuits
Control circuits
Voltage sensing and
power supply kit

CONNECTIONS
ATyS 6s, 6e

Voltage sensing and power supply kit


OTHER CONFIGURATIONS
The kit can be adapted to other configurations but
requires connections or programming modification.

> Voltage sensing and power supply kit mounting


procedure

> STEP 1

Neutral on the right

Neutral position

Neutral on the left

> No action
> Wires permutation on terminals
103 to 206 & 203 to 206

> STEP 2
Network

> STEP 3

Bottom entry

> No action
> A & B wires position modification
> Kit to mount downstream

Top entry

> Kit to mount upstream

Priority network
connected to switch I

> Connectors to plug in (on control module)


according to sources entry

Priority network
connected to switch II

> Connectors to plug in (on control module)


according to sources entry

Network 230 / 400 Vac


Network 127 / 230 Vac

Sources (cables) entry

> STEP 4
Sources / Switches cabling
and connectors plugging

Refer to following paragraphs for steps description

88

SOCOMEC - Rf.: 531 848 B

531_848_b-3

10/02/05

11:37

Page 89

Automatic Transfer Switch ATyS

CONNECTIONS

Voltage sensing and power supply kit


> STEP 1: Neutral position
3 wires kit: only to use on 3 x 230 Vac network
without neutral conductor.
The kit is delivered from factory for neutral on the right
configuration. For neutral on the left configuration, it is

necessary to modify the kit cabling (terminals 103 to


106 and 203 to 206.

Standard kit: neutral on the right

Kit modification for neutral on the left configuration:


circular permutation on terminals 103-106 and
203-206
N

ATYS 097 A

ATYS 097 A

Red wires

ATYS 296 A GB

7-8

5-6

3-4

1-2

7-8

206

205

204

Red wires

Black wires

203

202201

mechanical cables
support

5-6

3-4

1-2

1-2

7-8

5-6

Black wires

3-4

101 102

1-2

103

104

105

106

206

205

204

203

202201

mechanical cables
support

7-8

5-6

3-4
ATYS 297 A GB

101 102

103

104

105

106

> STEP 2: Network


3 wires kit: only to use on 3 x 230 Vac network
without neutral conductor.

Verify power supply on terminals 101-102 &


201-202: 230 Vac nominal 20 %.

Power inputs (terminals 101-102 & 201-202) are 220/240


Vac 20%. It is necessary to adapt power input cables
connection according to network configuration (Power

supply to take between phase to phase or between


phase and neutral).

Standard kit:
Network 380 / 415 Vac 20 % with neutral
conductor (no kit modification required) :

Kit Modification:
For network 220 / 240 Vac 20 %, power supply
cables A-B to connect between phases

206

205

204

Red wires

Black wires

203

202201

mechanical cables
support

SOCOMEC - Rf.: 531 848 B

Black wires

101 102

103

104

105

106

206

205

204

203

202201

mechanical cables
support

101 102

103

104

105

106

ATYS 295 A GB

ATYS 294 A GB

Red wires

89

531_848_b-3

10/02/05

11:37

Page 90

Automatic Transfer Switch

ATyS

Power circuits
Control circuits
Voltage sensing and
power supply kit

CONNECTIONS
ATyS 6s, 6e

Voltage sensing and power supply kit


> STEP 3: Sources (cables) entry
The standard kit is delivered from factory for sources
bottom entry (bridging bars on the top).
Bottom sources (cables) entry

Top sources (cables) entry

Load

ATYS 170 A GB

Sources

ATYS 171 A GB

Sources

Load

Black wires on switch I


Red wires on switch II

Black wires on switch II


Red wires on switch I

Verify kit orientation before kit mounting:


kit output cables always on the right
(control module side).

90

SOCOMEC - Rf.: 531 848 B

531_848_b-3

10/02/05

11:37

Page 91

Automatic Transfer Switch ATyS

CONNECTIONS

Voltage sensing and power supply kit


> STEP 4: Sources cabling and connectors plugging
Standard configuration: source 1 on switch I

Source 1 on switch II

II

II
I

ATYS 172 A

ATYS 167 A

Refer to programming paragraph (Setup)


for Sce variable configuration
Sce = II.

201 202

Power 230 V~
1

206
N

204

205

L2

203

L3

Voltage sensing

L1

102 101
103

Power 230 V~
1

Black
wires

105
106

104

N
L3
L2

ATYS 292 A GB

204
203

Voltage sensing

ATYS 290 A GB

201 202
206
205

L2

206

L1

Voltage sensing

L3

205

L2

L3

103

204

L2

104

Voltage sensing

105

L1

102 101
103

105

L3
L2

106

104

Voltage sensing

L1

Power 230 V~
1

2
L1

Red
wires

Red
wires

Switch II

203

L1

Red
wires

Switch II

TOP SOURCES
(CABLES) ENTRY

Power 230 V~

Switch I

201 202

Power 230 V~

106
L3

L3

103

102 101

Voltage sensing

L2

104

L3

Switch I

Voltage sensing

L2

206

ATYS 291 A GB

L1

Black
wires

Black
wires

105

Voltage sensing

205

ATYS 293 A GB

BOTTOM SOURCES
(CABLES) ENTRY

106

L1

204

TOP SOURCES
(CABLES) ENTRY

SOCOMEC - Rf.: 531 848 B

Switch I

Power 230 V~

203

Switch II

Black
wires

Switch I

102 101

Power 230 V~

201 202

Red
wires

Power 230 V~

BOTTOM SOURCES
(CABLES) ENTRY

Switch II

91

531_848_b-3

10/02/05

11:37

Page 92

Automatic Transfer Switch

ATyS

Manual operation
Electrical operation

OPERATION
ATyS 3e, 6s, 6e

Manual operation
MODE

selector
key selector

/ AUT

3e 6s 6e
3e 6s 6e

Two operational modes, manual or automatic, depending


on the front selector position.
AUT MODE
The front selector is on AUT

MODE
The front selector is on
POS 0

AUT

ATYS 195 A

AUT
ATYS 196 A

ATYS 194 A

AUT

for ATyS 3e, I, 0 and II commands are active for all versions, electrical commands
for ATyS 6, AUT mode is active
are inhibited

for all versions, electrical commands


are inhibited

it is not possible to insert the handle it is possible to insert the handle


it is not possible to pull the padlocking if handle is in, it is not possible to
mechanism
padlock or to switch to AUT

it is not possible to insert the handle


the product is padlocked (standard
product only in 0 position)

EMERGENCY OPERATION

Verify product position before any manual


operation.

ATYS 196 A NB

ATYS 194 A NB

All ATyS products can be manually operated (emergency


or maintenance operation).
Turn the front selector on manual position and insert the
handle in the specific hole.

Position

Remove the handle from the product before


changing the selector position to AUT.

It is possible to padlock the standard product in 0 position. Padlocking in position I or II is optional. Turn the
front selector on manual position and pull the padlocking mechanism to insert up to 3 padlocks (8 mm
maximum).
Padlocking only possible in manual mode,
handle not in place.

92

ATYS 008 A

PADLOCKING

SOCOMEC - Rf.: 531 848 B

531_848_b-3

10/02/05

11:37

Page 93

Automatic Transfer Switch ATyS

OPERATION

Electrical operation
3e 6s 6e

ATyS 3e, 6s and 6e integrate 2 power inputs (101-102,


201-202), and consider the available source to keep the
product operational.

AUT position
SVRMO 077 B GB

POWER SUPPLY

priority power source

backup power source

switching operation possibility

1 : terminals 101-102

CONTROL LOGIC

2 : terminals 201-202

3e 6s 6e

ATyS 3e and 6e products are electrically driven by external volt free contacts between terminals 314 and 317.
This command can be inhibited:
On ATyS 3e: terminals 313-317 closed
On ATyS 6e: terminals 313-317 opened.

> Impulse logic (standard configuration)


The switching command is a pulsed dry contact lasting
at least 30 ms.
When the order disappears, the product remains in
position
The impulse can be of infinite duration without causing
any disturbance.

Two types of control logic are possible: impulse or


contactor. The choice of the control logic is made via
programming (refer to programming chapter ATyS 3e
and 6e).

command I
command O

SVRMO 079 B

command II
position I
position O
position II

> Contactor logic


The transfer command is a maintained dry contact
If command I or II disappears, the device returns to
zero position
A 0 command drives the device into zero position,
irrespective of the status of the I and II commands ( 1
or 2 ).
command I
command O
command II

ATYS 024 A GB

position I

SOCOMEC - Rf.: 531 848 B

position O
position II

93

531_848_b-3

10/02/05

11:37

Page 94

Automatic Transfer Switch

ATyS

Presentation
Operationnal modes
Programming
Visualisation

OPERATION
ATyS 3e

Presentation
The product can be remotely driven in 0, I or II positions.
It is equipped with two power supplies to allow self
supply from sources.

CONTROL
- CONTROL led is on AUTO mode,
command not inhibited
- Leds 1 , O and 2 depend
on commands.

The power supply and control module allows:


product state and commands display,
optional modules connection,
parameters configuration.

LCD
Displays:
- local/remote modes
- number of permutations
- communication activation
- source concerned by displayed information.

FAULT led
Led is on when product
is faulty.
Disconnect power supplies
to reset.

Switch state
2 green leds:
- switch I state
- switch II state
Led is on when switch
is closed
Yellow led (O) is on when
both switches are opened.

POWER led
Green led is on when
product is powered.
Keypad

Padlock
Yellow led is on when product
is padlocked.

Navigation

LCD & leds test


Validation

Escape

Changeover switch position indication


Position O, I or II.

ATYS 205 A GB

Manual operation
Insert handle
Only possible in
not padlocked.

Key switch (selector)


Insert key
Turn right for AUT mod
Turn left for mod.
Padlock
Only possible in 0 position (I and II optional)
Remove handle
Pull padlocking mechanism to allow
padlock insertion.

mode,

94

{
{

Displayed after reset.

ATI 069 B GB

SOFTWARE VERSION

Product Version
number

SOCOMEC - Rf.: 531 848 B

531_848_b-3

10/02/05

11:37

Page 95

Automatic Transfer Switch ATyS

OPERATION ATyS 3e

Operationnal modes
VISUALISATION

PROGRAMMING

Parameters and values display.


No password required.

Parameters configuration.
Password access (1000 from factory).
POSITION

Programming
code

Programming

Handle removed
from housing

Visualisation

Padlocking

Manual operation

AUT POSITION
Programming
code

Programming

Command
not inhibited

Visualisation

Commands

Position I

Position O

Position II

Programming
Accessible in
or AUT modes.
Modified values are considered after mode exit.

> Navigation
or

Access parameters: press up, down left or right push buttons

Modify parameter value: press right


to access parameter to modify
Press up and down to modify parameter and validate

Home return: press ESC


If modified value it not validated, new parameters wont be taken into account

SOCOMEC - Rf.: 531 848 B

95

531_848_b-3

10/02/05

11:37

Page 96

Automatic Transfer Switch

ATyS

Presentation
Operationnal modes
Programming
Visualisation

OPERATION
ATyS 3e

Programming
> Exit programming mode

> Enter programming mode


Step 1: press and hold 5 seconds
validation

Press and hold 5 seconds


validation

Step 2: enter code using keypad


(1000 for factory)
Step 3:
validate

> Programming mode allows following parameters modifications:


Control logic: contactor or impulse
Programming code modification
Optional modules configuration
- Option2 I / 2O: load shedding timer
- Option COM: JBUS / MODBUS.

PROGRAMMING ARCHITECTURE MODE


1

ESC

SETUP
1

LCD
1

Definition

Setting range

Default values

Control logic (cf electrical operation)

CON (contactor)
IMP (impulse)

IMP

Programming code

0000 to 9 999

1000

Load shedding timer

1 to 60 s

5s

* Menu activated in case of optional modules recognition (refer to options).

96

SOCOMEC - Rf.: 531 848 B

531_848_b-3

10/02/05

11:37

Page 97

Automatic Transfer Switch ATyS

OPERATION ATyS 3e

Programming
COMMUNICATION (OPTION)
1

Activated in case of option recognition.


LCD
1

Refer to Communication chapter.

Definition

Setting range

Default values

Address

1 to 247

Speed

2400, 4800, 9 600


19200, 38 400

9 600

Stop bit

0, 1, 2

Parity bit

No, odd, even

No

2 INPUTS / 2 OUTPUTS
Denomination

Terminals

Type / rating

Description

Outputs

O13 - O14

Dry contact output

Load shedding output

O23 - O24

230 VA - 5 A - 1 150 VA
Operation max 105
Galvanic insulation 2,5 kV (1 min 50 Hz)

Fault output

I13 - I14

Optocoupled input

Transfer 1 -> 2

I23 - I24

10 to 30 Vdc

Source 2 available

Inputs

> Transfer Control (EJP) (I13-I14 terminals)


Possibility to control the transfer from network 1 to
network 2 if network 2 is available (terminals I23-I24)
As long as transfer control input is active and network 2
available, the changeover switch stays in position 2 .
If network 2 disappears, the load will be transfered
back on network 1 . As soon as transfer control is inactive, the now position depends on order commands on
terminals 313 to 317.

> Emergency source

available

(I23-I24 terminals)
Allows transfer from priority source 1 to emergency
source 2 . This information can be: genset ready to
take the load.
Power off action allows reset in case of fault
disappearance.

SOCOMEC - Rf.: 531 848 B

EJP is displayed on LCD when transfer control is active.


It has priority over order commands 1 and 2 .

> Load shedding output (O13-O14 terminals)


This output is a dry contact activated as soon as transfer
control input is active. Allows transfer on emergency
source 2 after t-ejp timer count down. The contact
opens after transfer back on priority source 1 and tejp timer count-down.

> Fault output (O23-O24 terminals)


Activated when product is faulty.

97

531_848_b-3

10/02/05

11:37

Page 98

Automatic Transfer Switch

ATyS

Presentation
Operationnal modes
Programming
Visualisation

OPERATION
ATyS 3e

Transfer sequence source 2

Transfer back sequence source 1


Transfer switch in AUT mode
Position II
EJP command active
Load shedding output active

Transfer switch in AUT mode


Position I or O

No

No

EJP activation
(I13 -I14 terminals
closed)

EJP
command lost
(I13-I14)

loss of source 2
(terminals I23 I24)

Yes

No

Yes

Yes

Load shedding output


(O13-O14 terminals activation)

No

Transfer to position I

Countdown
t-ejp

Source 2
available
(I23-I24)

t-ejp = 0

Yes
Load shedding output opened
(O13-O14 teminals)

ATYS 248 A GB

t-ejp count down

EJP control sequence exit

No
t-ejp = 0

T-ejp can be set from 1 to 60 s (default = 5 s).

Yes

ATYS 248 A GB

Transfer to position II

The output is de-activated in case of loss of


power. It may then be required to put in
parrallel with the load shedding ouptut relay,
position 2 auxiliary contact. This would avoid
taking back the load in case of loss of emergency
source in emergency position.

Main return sequence


(source 1 )

Visualisation
Allows operation display
Active mode:
if selector is on
1

if selector is on AUT position

If product is padlocked
1

98

position

Product state display:


if product is faulty, fault led is on
1

if more than 15 commands have been


required in less than 30 seconds
if power supply is not sufficient to operate
(230 Vac nominal)

SOCOMEC - Rf.: 531 848 B

531_848_b-3

10/02/05

11:37

Page 99

Automatic Transfer Switch

ATyS

Presentation
Operationnal modes
Programming
Operation
Visualisation
Automatic sequences

OPERATION
ATyS 6s et 6e

Presentation
The product allows:
sources control,
automatic transfer control in AUT mode,
parameters configuration,

voltage and frequency (6e) metering,


system state display,
alarm or fault indication,

AUT

LCD

FAULT led

Led is on when automatic mode is active

7 digits + 14 pointers

Led is on where product is faulty.


Disconnect power supplies to
reset.

Sources state
- Led is on : source = OK
- Led is off : source is not available

Operational modes
- Automatic sequence simulator
(test on load)
- Genset remote start (test off load)
- Changeover switch position
control (local or remote)
POWER led
Green led is on when product is
powered.

Padlock
Yellow led is on when
product is padlocked.

Keypad
Switch state

LCD & leds test


Validation

Escape

Changeover switch position indication


Position O, I or II.
Manual operation
Insert handle
Only possible in
not padlocked

Navigation

Operations

2 green leds:
- switch I state
- switch II state
Led is on when switch is closed
Yellow led (O) is on when both switches are
opened.

Key switch (selector)


Insert key
Turn right for AUT mod
Turn left for mod.

mode,

ATYS 153 A GB

Padlock
Only possible in O position (1 and 2 as option)
Remove handle
Pull padlocking mechanism to allow
padlock insertion.

Displayed after reset.


(3 minutes power off action to allow the reset).

SOCOMEC - Rf.: 531 848 B

ATYS 300 A GB

SOFTWARE VERSION

Product Version
number

Product Version
number

99

531_848_b-4

10/02/05

11:33

Page 100

Automatic Transfer Switch

ATyS

Presentation
Operational modes
Programming
Operation
Visualisation
Automatic sequences

OPERATION
ATyS 6s & 6e

Operational modes
VISUALISATION

OPERATION

Measured values & parametered timers display. Always


accessible without code.

Test sequences or electrical control of the position.


Password access (code 4000).

PROGRAMMING
Parameters configuration. Password access (code 1000
from factory).
POSITION
Programming
Code

Programming

Operation
Code

Visualisation

Handle not
in place

Phases
rotation
control

Operation

Padlocking

Manual
emergency
operation

Loss of main
source
sequence

Mains return
sequence

Test off load

POSITION AUT
Programming
Code

Programming

Operation
Code

Visualisation

Operation

Control I, O, II*

Test off load

Test on load

Position Position Position


I
O
II

* only on ATyS 6e

PHASES ROTATION CONTROL


This feature allows in manual mode, to verify phases
rotation before commisionning.
V1

V1

V3

V2

PROT
ATYS 220 A

OK
ATYS 219 A

Only source 1 phases rotation control on ATyS 6s & on


sources 1 and 2 on ATyS 6e.

V2

V3

Function available on both sources (ATyS 6e) in


case of 4NBL or 3NBL type of network and only
on source 1 in case of 41NBL ou 42NBL
network (refer to annexes).

or
displayed according to faulty
source (source 1 or source 2 ).
1

100

SOCOMEC - Rf.: 531 848 B

531_848_b-4

10/02/05

11:34

Page 101

Automatic Transfer Switch ATyS

OPERATION
ATyS 6s & 6e

Programming
This mode allows product parameters configuration
Always accessible in
position
Always accessible in AUT position, changeover switch
on priority source, priority source being available
Not accessible when test off load, test on load and
control functions are active or during automatic
sequence.
Parameters requiring programming before
use:
type of network
nominal voltage
and nominal frequency on ATyS 6e.

> Navigation in the menus


or

Parameters access: Press up, down, left & right push buttons

Parametermodification: press right push button to access the parameter to modify


Press up and down push buttons to modify the parameter
and validate

Return to main menu: press ESC pushbotton


Value is only modified after validation

> Programming access


Step 1: press and hold for 5 s
validation push button

> Programming exit


Press and hold for 5 s
validation push button

Step 2: enter code (factory code = 1000)


using navigation push buttons
Step 3: press validation
push button

SOCOMEC - Rf.: 531 848 B

101

Presentation
Operational modes
Programming
Operation
Visualisation
Automatic sequences

ATyS
Automatic Transfer Switch

OPERATION
ATyS 6s & 6e

Setup
ESC
Type of network

Phase-Phase
nominal voltage

Nominal**
frequency
Source 1 Switch I or II
configuration
Genset start
signal state

Network priority
selection:

1 or 2
Manuel
retransfer

Impulse** or
contactor logic

Number of
permutation
counter Reset
Programming
code
modification

Voltage
ESC
Network 1 over
voltage
threshold
Network 1 over
voltage
threshold
hysteresis
Network 1
under voltage
threshold
Network 1
under voltage
threshold
hysteresis
Network 2 over
voltage
threshold
Network 2 over
voltage
threshold
hysteresis
Network 2
under voltage
threshold
Network 2
under voltage
threshold
hysteresis

Frequency**
ESC
Network 1 over
frequency
threshold
Network 1 over
frequency
threshold
hysteresis
Network 1
under frequency
threshold
Network 1
under frequency
threshold
hysteresis
Network 2 over
frequency
threshold
Network 2 over
frequency
threshold
hysteresis
Network 2
under frequency
threshold
Network 2
under frequency
threshold
hysteresis

Timer
ESC
Main Failure
Timer

Delay on
Transfer
Timer
O main failure
Timer

Main Return
Timer

O main Return
Timer

Cool Down
Timer

Option Com.*
ESC

Adress

Speed

Stop Bit

Parity

OPTIONS

* Menus only available in case of optional module connection on ATyS 6e, up to 2 modules (In1, In2, In3, In4, Ou1, Ou2, Ou3, Ou4).
** Only on ATyS 6e.
*** Displayed if LS variable has been selected

2I / 2O*

ESC

Optional module 1
Input 1 (variable
selection)

Optional module 1
Input 1 (contact
state selection)

Optional module 2
Input 2 (variable
selection)

Optional module 2
Input 2 (contact
state selection)

Optional module 3
Input 3 (variable
selection)

Optional module 3
Input 3 (contact
state selection)

Optional module 4
Input 4 (variable
selection)

Optional module 4
Input 4 (contact
state selection)

Optional module 1
Output 1

Optional module 2
Output 2

Optional module 3
Output 3

Optional module 4
Output 4

Load shedding
timer***

SOCOMEC - Rf.: 531 848 B

102

Page 102
11:34
10/02/05
531_848_b-4

Programming

PROGRAMMING MENU ARCHITECTURE

531_848_b-4

10/02/05

11:34

Page 103

Automatic Transfer Switch ATyS

OPERATION
ATyS 6s & 6e

Programming
PARAMETER MODIFICATION
> Example:
Modify network 1 nominal voltage from 400 to 230 V.

to access first digit (blinking)

Press 2X

to display 2 (blinking)

Press

to access second digit (blinking)

Press 3X

to display 3 (blinking)

Press

to validate

ATI 074 A

Press

SOCOMEC - Rf.: 531 848 B

103

531_848_b-4

10/02/05

11:34

Page 104

Automatic Transfer Switch

ATyS

OPERATION
ATyS 6s & 6e

Presentation
Operational modes
Programming
Operation
Visualisation
Automatic sequences

Programming
PARAMETERS CHARACTERISTICS
> Menu Setup
LCD

Denomination

Definition

Setting
range

Default
values

Type of
network*

Number of active conductors of controlled network


(refer to annexes)

1BL, 2BL,
2NBL, 3NBL,
4NBL, 41 NBL,
42 NBL
from 110 V to
480 V

4NBL

Network
Phase-Neutral voltage for 1BL & 41NBL
nominal voltage Phase-Phase voltage for others
Network**
nominal
frequency

Network nominal frequency

400 V

50 Hz or 60 Hz

50 Hz

I, II

NO or NC

NO

Network priority Keypad selection (1 or 2)


selection
Also possible via external contact
Using option

1 or 2
( 1 or 2 )

1(1)

Manual
Retransfer

Yes or No

No

Type of control Impulse or contactor


logic selection**

Imp, con

Imp

Number of
permutation
counter Reset

Allows source 1 -> source 2 automatic sequences


counter reset

Yes or No

No

Programming
code
modification

Possible to change the programming code

from 0001 to
9999

1000

Source 1 - Switch I Source 1 (controlled and displayed) linked to switch I or II


or II configuration (depending on cabling)
Genset start
Normally opened or closed
signal state

Activation of the feature

* refer to annexes
** on ATyS 6e only.

104

SOCOMEC - Rf.: 531 848 B

531_848_b-4

10/02/05

11:34

Page 105

Automatic Transfer Switch ATyS

OPERATION
ATyS 6s & 6e

Programming
> Volt Menu

Threshold detection starts from the loss of source


or source return sequence

Controlled value (voltages)


Over voltage threshold (oU)
Over voltage hysteresys
threshold (oUh)
Available source
t

100

ATYS 243 A GB

Under voltage hysteresys


threshold (uUh)

LCD

Under voltage threshold (uU)

Denomination / Definition

Setting
range

Default
values

Network 1 over voltage threshold

from 102 to
120 %

115 %

Network 1 over voltage threshold hysteresis

from 101 to
119 % (<oU)

110 %

Network 1 under voltage threshold

from 80 to 98 % 85 %

Network 1 under voltage threshold hysteresis

from 81 to 99 % 95 %
(>uO)

Network 2 over voltage threshold

from 102 to
120 %

115 %

Network 2 over voltage threshold hysteresis

from 101 to
119 % (<oU)

110 %

Network 2 under voltage threshold

from 80 to 98 % 85 %

Network 2 under voltage threshold hysteresis

from 81 to 99 % 95 %
(>uU)

Values definition: % of nominal values


Hysteresis values range is limited by thresholds values.

SOCOMEC - Rf.: 531 848 B

105

531_848_b-4

10/02/05

11:34

Page 106

Automatic Transfer Switch

ATyS

OPERATION
ATyS 6e

Presentation
Operational modes
Programming
Operation
Visualisation
Automatic sequences

Programming
> Frequency Menu

6s 6e

Threshold detection starts from the loss of source


or source return sequence
%

Controlled value (frequency)


Over frequency threshold (oU)
Over frequency hysteresys
threshold (oUh)
Available source
t

100

ATYS 286 A GB

Under frequency hysteresys


threshold (uUh)

LCD

Under frequency threshold (uU)

Denomination / Definition

Setting
range

Default
values

Network 1 over frequency threshold

from 101 to
120 %

105 %

Network 1 over frequency threshold hysteresis

from 100.5 to
119.5 % (< oF)

103 %

Network 1 under frequency threshold

from 80 to 99 % 95 %

Network 1 under frequency threshold hysteresis

from 80.5 to
99.5 % (> uF)

97 %

Network 2 over frequency threshold

from 101 to
120 %

105 %

Network 2 over frequency threshold hysteresis

from 100.5 to
119.5 % (< oF)

103 %

Network 2 under frequency threshold

from 80 to 99 % 95 %

Network 2 under frequency threshold hysteresis

from 80.5 to
99.5 % (> uF)

97 %

Values definition: % of nominal values


Hysteresis values range is limited by thresholds values.

106

SOCOMEC - Rf.: 531 848 B

531_848_b-4

10/02/05

11:34

Page 107

Automatic Transfer Switch ATyS

OPERATION
ATyS 6s & 6e

Programming
> Menu Timer
LCD

6s 6e

Denomination

Definition

Setting
range

Default
values

Main Failure
Timer

Delays priority network failure detection

from 0 to 60 s

5s

Delay on
transfer Timer

Standby network stability validation before transfer

from 0 to 60 s

5s

O Main failure
Timer

Rest in O position when transferring


from main network to secondary network

from 0 to 20 s

5s

Main return
Timer

Main network stability validation before re-transfer

from 0 to 30 min 1 min

O main return
Timer

Rest in O position when re-transferring from standby


network to main network

from 0 to 20 s

Cool down
Timer

Allows generator cooling down period after loads


retransfer from standby source (generator) to Main source

from 0 to 30 min 4 min

>Communication Menu

5s

6s 6e

Menu only activated in case of optional


communication module connection
(refer to Options chapter).
LCD

Denomination

Definition

Setting
range

Default
values

Address

Address of the device

1 to 247

Speed

Communication speed

2400, 4800,
9600, 19 200,
38 400

9 600

Stop bit

1, 2

Parity bit

No, odd, even

No

SOCOMEC - Rf.: 531 848 B

107

531_848_b-4

10/02/05

11:34

Page 108

Automatic Transfer Switch

ATyS

Presentation
Operational modes
Programming
Operation
Visualisation
Automatic sequences

OPERATION
ATyS 6s & 6e

Programming
>Inputs/Outputs Menu

6s 6e

Menu activated in case of 2I / 2O optional module


connection (up to 2 modules).
Refer to accessories mounting for Input &
Output terminals identification.

In case of option re-plug or de-plug action,


inspect Inputs / Outputs identification and
programming.
Output relays are NO type (construction) and
can not be configured as NC.

Input state can be configured: NC or NO.


LCD
1

Denomination / Definition

Setting range

Default values

Input 1

Ft1, Ft2, Pri, Mtf, S2A, /

State input 1

NO, NC

NO

Input 2

Ft1, Ft2, Pri, Mtf, S2A, /

State input 2

NO, NC

NO

Input 3

Ft1, Ft2, Pri, Mtf, S2A, /

State input 3

NO, NC

NO

Input 4

Ft1, Ft2, Pri, Mtf, S2A, /

State input 4

NO, NC

NO

Output 1

S1A, S2A, LS, /

Output 2

S1A, S2A, LS, /

Output 3

S1A, S2A, LS, /

Output 4

S1A, S2A, LS, /

Inputs:
Ft1, Ft2: External Fault 1or 2. The fault led is blinking as
soon as the input is active and Ft1or Ft2 is displayed
on LCD. Reset when the input is de-activated
PRI: Priority network selection. Network 1 has priority
when input is not activated. Network 2 has priority if
input is active.
This information is the only considered in case
of option configuration. Programming variable
Pri is then inhibited.

Mtf: Remote manual re-transfer. Feature identical to


manual re transfert on keypad. Re-transfer from priority network to backup network is allowed from input
activation (1s front). The Mtf variable in the setup menu
must be selected (Yes) to allow input recognition.
Refer to priority source return sequence.
S2A: Information source 2 available (Genset) used instead
of voltage/frequency measurement from ATyS (inhibited
when S2A is selected).
Refer to loss of priority source sequence.

108

SOCOMEC - Rf.: 531 848 B

531_848_b-4

10/02/05

11:34

Page 109

Automatic Transfer Switch ATyS

OPERATION
ATyS 6s & 6e

Programming
>Inputs/Outputs Menu

Sorties:
S1A, S2A: Source 1 or source 2 available. Output activated as soon as source 1 or 2 is considered available
(similar to front led source 1 & 2 ).
LS: Load shedding relay. LS timer corresponds to time
available to disconnect the shed loads. The relay is activated before permutation on standby network according
to LS timer. The relay is de-activated after retransfer on
mains network and LS timer countdown.
In case of LS function selection, it is required to configure associated LS timer.
Output
1

Function

Default Value

Setting range

S1A, S2A, LS

0 to 60 s ( DTT)*

3s

* In case of DTT variable configuration below LS, LS will be automatically set to DTT value.

Example: LS configuration (output relay Ou1, 3 seconds):

ATYS 269 A

Sources priority can not be modified when LS


is affected to any output.

Load shedding feature can not be selected


when priority source = source 2 .
1

Load shedding cycle


DTT timer

LS timer

Priority source emergency source


transfer

Emergency source priority source


transfer

LS timer

Position II (emergency) AC activation

ATYS 334 A GB

LS relay Activation

LS

AC II

Load shedding output

SOCOMEC - Rf.: 531 848 B

The output is de-activated in case of loss of power.


It may then be required to put in parrallel with the
load shedding ouptut relay, position 2 auxiliary contact.
This would avoid taking back the load in case of loss of
emergency source in emergency position.

109

531_848_b-4

10/02/05

11:34

Page 110

ATyS

Automatic Transfer Switch

Presentation
Operational modes
Programming
Operation
Visualisation
Automatic sequences

OPERATION
ATyS 6s & 6e

Operation
PRESENTATION
This mode allows in manual position (not padlocked) to
start a test off load. In the automatic position, it allows
the starting of a test, on or off load and to control electricaly the position of the changeover switch on ATyS 6e.
Enter operation mode:

Exit operation mode:

Step 1: press and hold


the mode push button for 5 s

Press and hold for 5 s


mode push button

Step 2: enter the operation code (CE) using


navigation push buttons (code 4000)

Navigate in operation mode:


Press mode push button to access
different features

Step 3: press validation


push button

Press validation push button to activate


required function

OPERATION MODE ARCHITECTURE


Enter: press 5 seconds

Led test on load


is blinking

Yes, press
validation
1

Led TEST ON LOAD


is fixed

TEST ON LOAD
Lod of priority
source sequence

Led TEST OFF LOAD


is fixed

TEST OFF LOAD


Genset start
sequence

Led CONTROL 1 O 2
is fixed

Changeover
Led contrle
switch
position control
fixe 1 O 2
(PS1, PS 0, PS2)

Non, appuyer
sur mode

Led test off load


is blinking

Yes, press
validation
1

Non, appuyer
sur mode

Led control
is blinking

Yes, press
validation
1

ATYS 156 A GB

No,
press mode

Exit: press 5 seconds

* only on ATyS 6e.


110

SOCOMEC - Rf.: 531 848 B

531_848_b-4

10/02/05

11:34

Page 111

Automatic Transfer Switch ATyS

OPERATION
ATyS 6s & 6e

Operation
TEST OFF LOAD (ACCESSIBLE IN AUT /

MODES)

It can be activated from:


operation mode
communication option (ATyS 6e)
ATyS D20 interface (ATyS 6e).
This test is made for applications where emergency
source 2 is typically a genset (priority source must be
source 1 ). This test can only be activated, in automatic
mode, changeover switch in position 1 , source 1
available.

start Gen

Gen ?
1

No

Yes

> Description

Validate

This mode will start and stop remote by genset operation without load transfer
The test is not possible during an automatic sequence

Stop Gen ?
1

After operation mode access, press mode mushbutton


to make a test with the load led blinking and validate to
start the sequence.

TEST ON LOAD (ACCESSIBLE IN AUT MODE)


It is activated from:
operation mode
external dry contacts (terminals 207-209)
communication option (ATyS 6e)
ATyS D20 interface (ATyS 6e).

ATI 087 B GB

> Keypad activation

Gen stopped

Automatic cycle keeps priority.

> Description:

> Remote activation via specific input

This test simulates a loss of priority source situation.


The sequence generates load transfer from priority
souce to emergency source after backup source start
up operation (in case of genset). The return sequence
always keeps manual re transfer feature activated (from
priority source availability). All timers are counted down
according to their programmed settings.
The product automatically returns to Visualisation
mode after complete test sequence.
The test is only possible in automatic mode, the changeover switch in a priority source position, priority
source being available.

It is also possible to start a test on load remotely closing


terminals 207 & 209.
The cycle is started from contacts closure.
The re-transfer is initiated from contacts opening.

The re-transfer from emergency source to


priority source is blocked and only authorized
after manuel retransfer validation (keypad
activation) or terminals 207-209 opening.

> Keypad activation


After operation mode access, press mode mushbutton
to make test on load led blinking and validate to start a
cycle.
Manual retransfer to validate on keypad.

SOCOMEC - Rf.: 531 848 B

111

531_848_b-4

10/02/05

11:34

Page 112

Automatic Transfer Switch

ATyS

Presentation
Operational modes
Programming
Operation
Visualisation
Automatic sequences

OPERATION
ATyS 6e

Operation
CONTROL

, 0,

6s 6e

(ACCESSIBLE IN AUT MODE)

It can be activated from:


- operation mode. It is possible to select the position of
the changeover switch ( 1 , O, 2 ) from keypad,
- dry contacts. It is the possible to select the position
of the changeover switch ( 1 , O, 2 ) from specific
inputs (terminals 313 to 317),
- communication optional module
- interface ATyS D20.

> Description
Electrical operation of the changeover switch to reach
position: PS1, PSO, PS2 ( 1 , O ou 2 ) according to switches configuration (source 1 connected to switch I or
II).
The remote control has priority in automatic
mode. The product keeps in control mode
after transfer sequence.

> Remote activation


This mode is activated closing terminals 313 and 317.
Changeover switch position depends on orders present
between terminal 317 and terminals 314-315-316.

> Keypad activation


Select required position PS1, PSO or PS2:
Press mode push button
Yes is displayed on the screen for active position

ATYS 246 A

Select a new position (from 1 to 0):

112

SOCOMEC - Rf.: 531 848 B

531_848_b-4

10/02/05

11:34

Page 113

Automatic Transfer Switch ATyS

OPERATION
ATyS 6s & 6e

Visualisation
PRESENTATION
This mode allows parameters to be displayed independently from the selector / AUT switch position
No code required to access parameters visualisation
Without any action during 5 minutes on the keypad,
the LCD displays voltage available on active network.
In case of changeover switch on 0 position, priority
network voltage is displayed.
Navigation in visualisation mode:

Press up and bottom push buttons to access required parameter


Press left and right push buttons to navigate in the different menus

SOCOMEC - Rf.: 531 848 B

113

531_848_b-4

10/02/05

11:35

Page 114

Automatic Transfer Switch

ATyS

Presentation
Operational modes
Programming
Operation
Visualisation
Automatic sequences

OPERATION
ATyS 6s & 6e

Visualisation
VISUALISATION MODE ARCHITECTURE
MENUS
Metering

Timers
Phase-neutral voltage V1
network 1
Phase-neutral voltage V2
network 1
Phase-neutral voltage V3
network 1
Phase-phase U12
network 1
Phase-phase U23
network 1
Phase-phase U31
network 1

Counter
Main Failure Timer

Priority source ->


Emergency source counter
commutation counter

Delay on Transfer Timer

O Main Failure Timer

Main Return Timer

O Main Return Timer

Cool Down Timer

Network 1 * frequency

Load shedding**

Phase-neutral voltage V1
network 2 *
Phase-neutral voltage V2
network 2 *
Phase-neutral voltage V3
network 2 *
Phase-phase U12
network 2 *
Phase-phase U23
network 2 *
Phase-phase U31
network 2
Network 2 * frequency

* Only on ATyS 6e.

** If option selected and timer active on ATyS 6e.

All values indicated might not be available according to programmed network. Refer to annexes.
114

SOCOMEC - Rf.: 531 848 B

531_848_b-4

10/02/05

11:35

Page 115

Automatic Transfer Switch ATyS

OPERATION
ATyS 6s & 6e

Automatic sequences
MANUAL MODE / AUTOMATIC MODE
> Manual mode - Automatic mode
permutation/power supply reappearance
As soon as the selector switch is switched to automatic, the automatic mode is active
Voltages (and frequencies on ATyS 6e) are verified to
define new stable position of the changeover switch
The same table can be taken into account after
complete power supply loss (the product must be
completely discharged to reset = 3 minutes.)

Refer to timer menus for MFT, MRT or DTT timers


definition.

> New stable position of the chaneover swicth


Changeover switch Sources availability
initial position

New position

Priority source

Priority source available,


emergency source available or unavailable

Priority source

Priority source

Priority source unavailable for MFT time period,


emergency source available or unavailable

Emergency source. If emergency source


unavailable start emergency source first and wait
for DTT timer period before transfer

Emergency source

Emergency source available,


priority source unavailable

Emergency source

Emergency source

Emergency source available,


priority source available for MRT time period

Priority source

Position 0

Priority source available,


emergency source unavailable

Available source to count down MRT before


transfer to priority source

Position 0

Priority source available,


emergency source unavailable

Priority source

Position 0

Priority source unavailable,


emergency source available

Emergency source

Position 0

Priority source unavailable,


emergency source unavailable

No action (because no supply).


When supply becomes available change to priority
source or emergency source

The switch immediately transfers to new stable position as soon as the keyswitch is turned from
Manual to Automatic mode or as soon as Power comes back.

LOSS OF PRIORITY SOURCE AUTOMATIC SEQUENCE


This sequence is started as soon as the switch is in
automatic mode and in priority position (position I source 1 ).
source 1 is available
transfer switch is in position I
source 2 is available or unavailable

> Specific feature: remote transfer control


It is possible to transfer from main source to emergency
source before DTT finishes up. If it is setup to its maximum values (60s), it is possible to allow transfer closing
terminals 207-208 (CTS).

> Available source


Source being within programmed voltage and frequency
settings, phases rotation being correct.

SOCOMEC - Rf.: 531 848 B

115

531_848_b-4

10/02/05

11:35

Page 116

Automatic Transfer Switch

ATyS

Presentation
Operational modes
Programming
Operation
Visualisation
Automatic sequences

OPERATION
ATyS 6s & 6e

Automatic sequences
> Sequence description
Example:
position I = priority source ( 1 )
position II = emergency source type Genset ( 2 )
Automatic mode

Loss of
mains?

No
Loss of main?

Count down
MFT

MFT = 0

Genset
start up

Main comes back


before MFT ends?

Start Genset

Reset MFT
Yes

Emergency
source
available ?
No
Yes
Stop gen

No

Priority
source ?

Yes
DTT = DTTmax ?

No

Reset DTT

Count down
DTT

CTS = 1 ?
Gen fails
Count down DTT

Yes

DTT = 0

DTT = 0

Yes

No
OMF 0 ?

Transfer I

>0

Count down OMF

OMF = 0

Transfer 0

> II

Transfer I

ATYS 154 A GB

Transfer I

116

> II

> II

Go to priority source
return automatic
sequence

SOCOMEC - Rf.: 531 848 B

531_848_b-4

10/02/05

11:35

Page 117

Automatic Transfer Switch ATyS

OPERATION
ATyS 6s & 6e

Automatic sequences
RETURN TO PRIORITY SOURCE
This sequence is activated as soon as the changeover
switch is in automatic mode and in emergency position
(position II):
the priority source 1 is not available

the changeover switch is in emergency position (ex:


genset)
the emergency source 2 is available.

> Specific feature: manual re-transfer

> Sequence description

Manual re-transfert
= validation press
Or
optional input activation, feature Mtf
ATYS 143 A

When priority source comes back, it can be required


not to automatically retransfer and wait for an more
adequate timing.
It is possible, validating manual retransfer feature (refer
to programming), to block the re-transfer.
It is initiated from:
validation push button localy or on ATyS D20
via an input on optional module 2I / 2O on ATyS 6e,
Mtf feature.
Priority source unavailable
Generator running (emergency source) &
Switch in position II

Mains
return

Priority
source
return?

No
Yes

Manual re-transfer
Loss of
priority source ?

Yes

Count down
MRT

No

MRT = 0

Priority source
lost again
before MRT
times out?

Mode
semi-auto
activated ?
(Mtf)

Reset MRT

No

Yes

Yes
Validation

OMR 0?

Yes

Transfer II

No

>0

Count Down OMR


OMR = 0

Transfer 0

To loss of priority
source sequence

Reset CDT

>I

Transfer II

Count Down CDT

Transfer II

>I

>I

Loss of priority source

Stop generator
position 1
Back to priority source control

SOCOMEC - Rf.: 531 848 B

ATYS 155 A GB

CDT = 0

117

531_848_b-4

10/02/05

11:35

Page 118

Automatic Transfer Switch

ATyS

Communication module

OPTIONS
ATyS 3e, 6e

Communication module
Refer to Accessories Mounting to know modules mounting
instructions. This module allows RS485 communication
connection via JBUS/MODBUS protocol.
RS485

2 or 3 wires half duplex

Protocol

JBUS / MODBUS in RTU mode

Speed

2400, 4800, 9600, 19 200, 38 400 Bauds

Galvanic insulation

4 kV (1 min 50 Hz)

GENERAL POINTS
An RS 485 link is used to connect up to 31 ATyS with a
PC or a PLC over a distance of 1500 meters, using
JBUS / MODBUS protocol.

1500 M

> Recommendations

R = 120

N 1

N 2

N n
R = 120

Programmable PLCs

DIRIS 109 B GB

You should use a shielded twisted pair (LIYCY type). In


an interfearence environment or large network (in terms
of length) we recommend the use of 2 shielded pairs
(type LIYCY-CY). In this case, one pair is used for the
+ and the , and another pair, where the 2 wires are
short-circuited, for the 0 V.
A repeater (1 channel) or an arrestor (4 channels) should
be used if you intend to exceed the distance (1500 m)
and / or maximum number (31) of ATyS. Please contact
us for more information.

Other systems

1500 M

R = 120

N 1

1500 M

0+- -+0
rpteur

N n

RS485

R = 120
DIRIS 110 B GB

Programmable PLCs
Other systems

A 120 ohm resistance (found on the RS485


optional module) must be fixed at both ends of
the link.

118

SOCOMEC - Rf.: 531 848 B

531_848_b-4

10/02/05

11:35

Page 119

Automatic Transfer Switch ATyS

OPTIONS

Communication module
PROTOCOL JBUS / MODBUS
The JBUS / MODBUS used by the ATyS involves a
dialogue using a master-slave hierarchical structure.
There are two possible dialogues:
the master communicates with a slave (ATyS) and waits
for its reply
the master communicates with all the slaves (ATyS)
without waiting for their reply.
The mode of communication is the RTU (Remote
Terminal Unit) using hexadecimal characters of at least
8 bits.
According to the JBUS / MODBUS protocol, transmission time must be less than 3 silences, i.e. the emission
time of 3 characters so that the message is processed
by the ATyS.
The standard communications frame consists of:
Slave address

Function code

Address

Slave address: communicating device address (Add,


menu Comm parameters)
Function codes:
3: to read n words (maximum 128).
6: to write one word.
8: to diagnose exchanges between the master and the
slave via meters 1, 3, 4, 5 and 6.
16: to write n words (maximum 128).

Data

CRC 16

NB:
When selecting slave address 0, a message is sent to all
the instruments present on the network (only for functions 6 and 16).
Comment:
The response time (time out question/answer) is 250 ms
maximum.

Address: concerned variable address (refer to following


tables)
Values: parameters linked to function (number of
words, value).

SOCOMEC - Rf.: 531 848 B

119

531_848_b-4

10/02/05

11:35

Page 120

Automatic Transfer Switch

ATyS

Communication module

OPTIONS
ATyS 3e, 6e

Communication module
LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)
> Table of values on 2 words
Decimal
address
776
778
780
782
784
786
788
884
892
894
895
896
897
898
899

Hexa.
address
308
30A
30C
30E
310
312
314
374
37C
37E
37F
380
381
382
383

Number
of words
2
2
2
2
2
2
2
2
2
1
1
1
1
1
1

Text

Unit

U12 Source 1
U23 Source 1
U31 Source 1
V1 Source 1
V2 Source 1
V3 Source 1
Frequency Source 1
U31 Source 2
Frequency Source 2
MRT
MFT
DTT
OMF
CDT
OMR

V / 100
V / 100
V / 100
V / 100
V / 100
V / 100
Hz / 100
V / 100
Hz / 100
s
s
s
s
s
s

Example:
To read U31 GEN = 228.89, the following message
should be sent:
Slave

Function

High-order
address

Low-order
address

High-order
word n

Low-order
word n

CRC 16

05

03

03

74

00

02

85D1

Slave

Function

Number
of bytes

Value
high-order

Value
low-order

CRC 16

05

03

04

0000

5969

458D

ATyS reply:

Hex.

Decimal value = 22 889 (/100)

120

SOCOMEC - Rf.: 531 848 B

531_848_b-4

10/02/05

11:35

Page 121

Automatic Transfer Switch ATyS

OPTIONS

Communication module
> Table of values on 1 word
Decimal
address
1792
1793
1794
1795
1796
1797
1798
1801
1805
1806
1807
1808
1809
1810
1811

Hexa.
address
700
701
702
703
704
705
706
709
70D
70E
70F
710
711
712
713

Number
of words
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Text

Unit

U12 source 1
U23 source 1
U31 source 1
V1 source 1
V2 source 1
V3 source 1
Frequency source 1
U31 source 2
Frequency source 2
Timer MRT
Timer MFT
Timer DTT
Timer OMF
Timer CDT
Timer OMR

V / 10
V / 10
V / 10
V / 10
V / 10
V / 10
Hz / 100
V / 10
Hz / 100
s
s
s
s
s
s

> Diagnostic zone


Decimal
address
257

Hexa.
address
101

Number Text
of words
1
product identification

258

102

Option 1

259
260
261
262
263
265
278

103
104
105
106
107
109
116

1
1
1
1
2
17
1

Option 2
Option 3
Option 4
Version
Serial number
/
Operational mode

282

11A

Changeover state

283
285

11B
11D

2
1

286

11E

/
Source 1 --> source 2
permutations counter
Start gen relay state

SOCOMEC - Rf.: 531 848 B

ATyS 3e value 1237


ATyS 6e value 1242
Without option: FF
Option COM: 00
Option 2I / 2I: 20
refer to option 1
refer to option 1
refer to option 1
Software version

Available on
ATyS 3e
X

ATyS 6e
X

X
X
X
X
X

X
X

3 stables states
X
Bit3 Bit2 Bit1 Bit0
1
0
1
0 Auto.
0
1
0
1 Padlocked
0
1
1
0 Manu.
3 stables states
X
Bit2 Bit1 Bit0
0
0
1 Position 1
0
1
0 Position 0
1
0
0 Position 2
X
2 stables states
Bit5 Bit4
0
1
relay not active
1
0
relay active

X
X

121

531_848_b-4

10/02/05

11:35

Page 122

Automatic Transfer Switch

ATyS

Communication module

OPTIONS
ATyS 3e, 6e

Communication module
LISTE DES PARAMTRES CONFIGURER (FONCTION 3, 6, 16)
Decimal
address
512

Hexa.
address
200

Number
of words
1

513
518
519
520

201
206
207
208

5
1
1
1

521

209

522
523
524
525
526
527
528
529
530
531
532
533
534
535
536
537
538
539
540
541
542
543
544
545

20A
20B
20C
20D
20E
20F
210
211
212
213
214
215
216
217
218
219
21A
21B
21C
21D
21E
21F
220
221

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

546
547
548

222
223
224

1
1
1

549

225

550

226

551

227

552

228

122

Text

Unit

Type of network 0 = 4NBL - 1 = 2NBL - 2 = 2BL


3 = 3NBL - 4 = 41NBL - 5 = 1BL
6 = 42NBL
/
VNominal
FNominal - 50 or 60
Connection source 1
1 = inter I - 2 = inter II
Retransfer
0 = not active - 1 = active
oU 1 from 102 to 120
oUh 1 from 101 to 119
uU 1 from 88 to 98
uUh 1 from 81 to 99
oU 2 from 102 to 120
oUh 2 from 101 to 119
uU 2 from 80 to 98
uUh 2 from 81 to 99
oF 1 from 101 to 120
oFh 1 from 100.5 to 119.5
uF 1 from 80 99
uFh 1 from 80.5 99.5
oF 2 from 101 120
oFh 2 from 100.5 119.5
uF 2 from 80 99
uFh 2 from 80.5 99.5
Timer MRT
Timer MFT
Timer DTT
Timer OMF
Timer CDD
Timer OMR
Priority network (1 = R1; 2 = R2)

A
V
Hz

%
%
%
%
%
%
%
%
% / 10
% / 10
% / 10
% / 10
% / 10
% / 10
% / 10
% / 10
min / 10
s
s
s
min / 10
s
s

Type of control logic


(0 = IMP; 1 = CON)

Load shedding LS
s
Start gen 0 = NO - 1 = NC
Input 1
0:/
3: Pri
1: Ft1
4: S2A
2: Ft2
5: MtF
Input In1 state
0 = NO - 1 = NC
Input 2
0:/
3: Pri
1: Ft1
4: S2A
2: Ft2
5: MtF
Input In2 state
0 = NO - 1 = NC
Output Ou1
0 = S1A - 1 = S2A
2 = LS - 3 = /

SOCOMEC - Rf.: 531 848 B

531_848_b-4

10/02/05

11:35

Page 123

Automatic Transfer Switch ATyS

OPTIONS

Communication module
Decimal
address
553

Hexa.
address
229

Number
of words
1

Text

Unit

554

22A

555

22B

556

22C

557

22D

558

22E

559

22F

Decimal
address
545

Hexa.
address
221

Number
of words
1

Text

546

222

Timer EJP

Output Ou2
0 = S1A - 1 = S2A
2 = LS - 3 = /
Input In3
0 = / - 1 = Ft1 - 2 = Ft2
3 = Pri - 4 = S2A - 5 = MtF
Input In3 state
0 = NO - 1 = NC
Input In4
0 = / - 1 = Ft1 - 2 = Ft2
3 = Pri - 4 = S2A - 5 = MtF
Input In4 state
0 = NO - 1 = NC
Output Ou3
0 = S1A - 1 = S2A
2 = LS - 3 = /
Output Ou4
0 = S1A - 1 = S2A
2 = LS - 3 = /

> ATyS 3e

3e 6e
Unit

Type of control logic


(0 = IMP; 1 = CON)

> Example
Nominal voltage (233 V) configuration on ATyS n 5.
Slave
Hex

05

Function

High-order Low-order
Word n
address
address

10

Dc.

02

06

00

Number
of bytes

01

02

First word First word


high order low order
00

E9

16

CRC 16
76B8

233

ATyS answer:

Hex

Slave

Function

Value
high-order

Value
low-order

05

10

02

06

SOCOMEC - Rf.: 531 848 B

Word n
00

01

CRC 16
E1F4

123

531_848_b-4

10/02/05

11:35

Page 124

Automatic Transfer Switch

ATyS

Communication module

OPTIONS
ATyS 3e, 6e, 6s

Communication module
SAVE COMMAND (RESET)
This command must be completed to save modified
parameters. 0 must be set to address 0600.

> Example: for slave n 5


Slave

Function

Value
high-order

Value
low-order

Values

CRC 16

05

06

06

00

0000

88C6

> NB:
ATyS wont answer. Save command is followed by a
complete reset (software version displayed on LCD).

TEST / CONTROL
> Command
Slave

Function

Add. Pf
high order

Add. Pf
low order

Value Pf
high order

Value Pf
low order

CRC

1 bit /function

05

06

$04

$80

bit 0=1: test


on load
bit 1=1: test
off load
bit 2=1: Control
Pos 1
bit 3=1: Control
Pos 0
bit 4=1: Control
Pos 2

1 = start
CRC
0 = stop

> Reading
Slave

05

124

Function

03

Add. Pf
high order

$01

Add. Pf
low order

$22

Value Pf
high order
1 bit /function
if bit = 0:
no test

Value Pf
low order

CRC

1 bit /function
if bit = 0:
no test

bit 0=1: test


on load
bit 0=1:
bit 1=1: test
started via I/O
off load
bit 1=1:
bit 2=1: Control
started via
Pos 1
interface
bit 3=1: Control
bit 2=1: started
Pos 0
via Comm
bit 4=1: Control
Pos 2

CRC

SOCOMEC - Rf.: 531 848 B

531_848_b-4

10/02/05

11:35

Page 125

Automatic Transfer Switch

ATyS

TROUBLESHOOTING GUIDE
ATyS 3e, 6s, 6e

STATE

ACTION

ATyS 3e, 6s & 6e


Electrical operation is not working

Verify voltage applied on terminals 101 / 102 and 201 / 202


is 220-240 Vac 20 %
Verify selector mode position is on AUTO (Automatic)

Manual operation using handle is not

Verify selector mode position is on Man (Manual)


to allow handle introduction
Verify product is not padlocked
Verify handle rotation direction is correct
Apply enough progressive power on the on the handle to allow movement

A / M selector does not allow AUT position

Verify handle is removed from housing


Verify product is not padlocked
Verify type of key used (ATyS 3e and 6e)

Product is faulty (fault is active)

Disconnect power supply to try to reset the fault


(terminals 101-102, and 201-202)
In case of optional module connection,
verify external fault input Ft1 or Ft2 is not active

Impossible to padlock the product

Verify active mode (manual)


Verify handle is removed from housing
Verify changeover switch position is 0
(excepted in case of 3 positions padlocking option)

ATyS 6s & 6e
Source available led is never active
when available

Press test lamp to verify led is operational


Verify nominal preset values (voltage and frequency)
Verify voltage and frequency thresholds

The changeover switch does not transfer


after loss of main

Verify A / M selector is on AUTO position


Verify emergency source is available (ex: genset is started)
Verify voltage applied on terminals 101 / 102 and 201 / 202
is 220-240Vac 20 %

Test on load and off load


can not be activated from keypad

Verify password to access test (4000)


Verify A / M selector is on AUTO position

The changeover switch


does not re-transfer after main's return

Verify MRT is counted down


Verify A / M selector is on AUTO position
Verify manual retransfer feature is not active
(press validation to allow retransfer)

Retransfer has been realised but


Verfiy CDT is counted down
emergency source in still running (did not stop) Verify start Gen output relay command,
terminals 73-74 (disconnect connector if required)
Optional modules 2I / 2O and
COM not dectected after plug in

Verify optional modules are correctly tightened


Wait for 3 minutes, power off, to reset and allow optional module detection

Electrical operation not according to commands Verify Sce parameter configuration (source 1 or 2).
If Sce = I, command 1 will close switch I.
If Sce = II, command 1 will close switch II
ATyS 3e, 6e
Electrical operation not according
to remote external commands

SOCOMEC - Rf.: 531 848 B

Verify control logic (impulse or contactor mode)


Verify external command are not inhibited (terminals 313 and 317)

125

531_848_b-4

10/02/05

11:35

Page 126

Automatic Transfer Switch

ATyS

SPARE PARTS
ATyS 3e, 6s, 6e

1. Power supply and


control module
4. Kit
connections

3. Changeover
switch
2. Motorized
module

5. Handle support /
handle

Indice
1

Product
Power supply and control module

Motorized module

Changeover switch

4
5

Connector kit (1 of each)


Handle support / handle

Key (2 keys)

C. 126

ATYS 102 A NB

ATYS 110 A NB

6. Key

References
ATyS 6s
ATyS 6e
ATyS 3e
125 A
160 A
250 A
400 A
630 A
800 A
1000 A
1 250 A
1 600 A
125 A 3P
160 A 3P
250 A 3P
400 A 3P
630 A 3P
800 A 3P
1000 A 3P
1 250 A 3P
1 600 A 3P
125-630 A
800-1 600 A

1539 2001
1559 2001
1569 2001
1509 5012
1509 5016
1509 5025
1509 5040
1509 5060
1509 5080
1509 5100
1509 5120
1509 5160
1509 3012
1509 3016
1509 3025
1509 3040
1509 3063
1509 3080
1509 3100
1509 3120
1509 3060
1509 0002
1599 6001
1599 6011
1599 9502

125 A 4P
160 A 4P
250 A 4P
400 A 4P
630 A 4P
800 A 4P
1000 A 4P
1 250 A 4P
1 600 A 4P

1509 4012
1509 4016
1509 4025
1509 4040
1509 4063
1509 4080
1509 4100
1509 4120
1509 4060

SOCOMEC - Rf.: 531 848 B

531_848_b-4

10/02/05

11:35

Page 127

Automatic Transfer Switch

ATyS

ANNEXES
ATyS 3e, 6e, 6s

Networks analysis
TYPES OF NETWORKS
> Three phases network with neutral - 4NBL
Source 2
1

Source 1

Source 2

ATYS 174 A GB

ATYS 173 A GB

Source 1
1

> Two phases network (with midpoint) - 2NBL

Load

> Phase-Phase network without neutral - 2BL

Load

> Single phase network with neutral


(phase-neutral) - 1BL
Source 1

Source 2

ATYS 176 A GB

Source 2

ATYS 175 A GB

Source 1

Load

> Three phases network without neutral - 3NBL

Load

> Three phases network with neutral on source


Single phase network with neutral on source
Source 1

Source 1
1

- 41 NBL

Source 2
1

Source 2
1

ATYS 178 A GB

ATYS 177 A GB

Load

N
Load

Only single phase loads.

> Three phases metering on network

ATYS 179 A GB

Source 1

- single phase metering on network


Source 2

- 42 NBL

Only consider single phase sensing (phse 1-3) on


source 2 . Allows single phase sensing on three phases
emergency source.
Only possible on ATyS 6e. Single phase
sensing standard on source 2 on ATyS 6s.

Load

SOCOMEC - Rf.: 531 848 B

C. 127

531_848_b-4

10/02/05

11:35

Page 128

Automatic Transfer Switch

ATyS

ANNEXES
ATyS 6e, 6s

Programming and connection on ATyS 6s


ATyS integrates all identified networks in his programm.
It is necessary to verify this parameter before use.

ATyS 6s - THREE PHASES SENSING ON SOURCE 1


SINGLE PHASE SENSING ON SOURCE 2

Prog. ATyS

3 phases
4 wires
4NBL

1 phase
3 wires
2NBL

1 phase
2 wires
2 BL

1 phase
1 wire
1BL

3 phases
3 wires
3NBL

3 phases
41NBL

Source 1
(active
connectors)

2
3

Source 2
(active
connectors)

2
3

Sensing
Source 1 U12, U23, U31, U12, U23,
parameters
U1, U2, U3
U31
available
Source 2 U31
U31

U31

U1

U12, U23,
U31

U1, U2, U3

U31

U1

U31

U1

Source 1 U12, U23,


U31

U12, U23,
U31

U31

U1

U12, U23,
U31

U1, U2, U3

Source 2 U31

U31

U31

U1

U31

U1

Controls

Source 1 U12 = U23 = U31 = 240 V U31 = 240 V U1 = 240 V


Example
Un = 240 V
U31 = 240 V
Source 2 240 V

128

240 V

240 V

240 V

U12 = U23 = U1 = U2 =
U31 = 240 V U3 = 240 V
240 V

240 V

SOCOMEC - Rf.: 531 848 B

531_848_b-4

10/02/05

11:35

Page 129

Automatic Transfer Switch ATyS

ANNEXES

Programming and connections ATyS 6e


ATyS 6e - THREE PHASES SENSING ON SOURCES 1 ET 2

Prog. ATyS

3 phases
4 wires
4NBL

Source 1
(active
connectors)

1 phase
3 wires
2NBL
1

1 phase
2 wires
2 BL
1

1 phase
1 wire
1BL

3 phases
3 wires
3NBL

3 phases
41NBL

42NBL

2
3

Source 2
(active
connectors)

N
3

2
3

N
3

N
3

Sensing
Source 1
Source 1
parameters U12, U23, U31, U12, U23,
available U1, U2, U3, f1 U31, f1

Source 1
U31, f1

Source 1
U1, f1

Source 1
U12, U23,
U31, f1

Source 2
Source 2
U12, U23, U31, U12, U23,
U1, U2, U3, f2 U31, f2

Source 2
U31, f2

Source 2
U1, f2

Source 2
Source 2
U31, f2, U12, U1, f2
U23

Source 2
U31, f2

Source 1
Source 1
U12, U23, U31, U12, U23,
f1
U31, f1

Source 1
U31, f1

Source 1
U1, f1

Source 1
U12, U23,
U31, f1

Source 1
U12, U23, U31,
f1

Source 2
Source 2
U12, U23, U31, U12, U23,
f2
U31, f2

Source 2
U31, f2

Source 2
U1, f2

Source 2
Source 2
U31, f2, U12, U1, f2
U23

Source 2
U31, f2

Source 1
Source 1
Source 1
Source 1
U12 = U23 = U31 = 240 V U31 = 240 V U1 = 240 V
U31 = 240 V f1 = 50 Hz
f1 = 50 Hz
f1 = 50 Hz
f1 = 50 Hz

Source 1
U12 = U23 =
U31 = 240 V
f1 = 50 Hz

Source 1
U1 = U2 =
U3 = 240 V
f1 = 50 Hz

Source 1
U12 = U23 =
U31 = 240 V
f1 = 50 Hz

Source 2
Source 2
Source 2
Source 2
U12 = U23 = U31 = 240 V U31 = 240 V U1 = 240 V
U31 = 240 V f2= 50 Hz
f2 = 50 Hz
f2 = 50 Hz
f2 = 50 Hz

Source 2
Source 2
U12 = U23 = U1 = 240 V
U31 = 240 V f2 = 50 Hz
f2 = 50 Hz

Source 2
U31 = 240 V
f2 = 50 Hz

Controls

Example
Un = 240

SOCOMEC - Rf.: 531 848 B

Source 1
U1, U2, U3,
f1

Source 1
U1, U2, U3,
f1

Source 1
U12, U23, U31,
U1, U2, U3, f1

129

531_848_b-4

10/02/05

11:35

Page 132

SOCOMEC - Ref.: 531 848 B - 02 / 05

HEAD OFFICE

SALES MANAGEMENT DIVISION

SOCOMEC GROUP SWITCHGEAR AND UPS


S.A. capital 10 923 800 - R.C. Strasbourg 548500 149 B
1, rue de Westhouse - B.P. 10 - 67235 Benfeld Cedex
Tl. + 33 03 88 57 41 41
Fax + 33 03 88 57 78 78

SOCOMEC
95, rue Pierre Grange
94132 Fontenay-sous-Bois Cedex
Tl. + 33 01 45 14 63 90
Fax + 33 01 45 14 63 38

www.socomec.com