Sunteți pe pagina 1din 21

Substation Automation Products

Transformer protection RET670


Restricted earth fault protection

1MRG019260

Chapter 04

Contents

ABB Group
September 10, 2015 | Slide 2

Application

Operating characteristics

Logical Diagram

In and output signals

Settings

Monitored data

Application restricted earth fault protection

Faults resulting in large fault currents may


cause severe damages to windings and the
core

Could also result in high gas pressure


damaging the tank

The restricted earth fault protection is fast


and sensitive and can detect faults in the
winding:

ABB Group
September 10, 2015 | Slide 3

Chapter 04

in impedance earthed systems

close to the star point in solid earthed systems

The restricted earth fault protection is often


used as main protection for all winding faults
involving earth

Restricted earth fault protection


Application

Low impedance type

Can be used to protect directly or low impedance


earthed windings

Zero sequence differential protection

An additional directional comparison feature is


included

No need for magnitude or phase angle correction

Internally summation if multi breaker arrangement

Fundamental frequency components

OLTC does not influence the function

Insensitive to inrush and overexcitation

Only danger is eventual CT saturation

ABB Group
September 10, 2015 | Slide 4

Chapter 04

2nd harmonic restraint included

Chapter 04

Restricted earth fault protection


Application

1.

1B

3A

Transformer
A.

Solidly earthed winding with or without OLTC

B.

Earthed though Z-0 earthing transformer

2.

Autotransformer with or without OLTC

3.

Reactor
A.

ABB Group
September 10, 2015 | Slide 5

1A

Solidly earthed

Restricted earth fault protection


Application

Single circuit breaker or

Multiple circuit breaker applications

ABB Group
September 10, 2015 | Slide 6

summation inside the function

Number of instances

Customized: 0 - 3

Pre-configured (A10, A30, B30, A40, B40, A25):

Included: A10: 1; x30/y40: 2; A25: 0

Optional: y40: 1

Chapter 04

Chapter 04

Operating characteristics
Restricted earth fault protection

Calculated or measured residual


current on terminal side, 3I0 (Ires)

The differential current, Idiff, is the


vector sum:

125

3I0_Wx is the summation of


CT1 and CT2 for winding x

3I0_W2 is used in
autotransformer applications

Stabilizing current, Ibias

ABB Group
September 10, 2015 | Slide 7

where

The highest current among all


current inputs

Chapter 04

Operating characteristics
Restricted earth fault protection

Two fixed slopes defines as:

1st: 70% ; 2nd: 100%

End of slope 1: 125% of IBase

Setting: Minimum operation, Idmin

125

ABB Group
September 10, 2015 | Slide 8

In percent of IBase: 4.0 - 100.0

IBase

Rated current of the winding or CT


rating

For autotransformers the highest


winding rated current i.e. low
voltage side

Operating characteristics
Restricted earth fault protection, Ibias

The bias current stabilizes the protection

Higher currents harder conditions higher probability that


Idiff > Idmin due to: CT saturation

Ibias is defined as the maximum current of:


curr(a) = MAX [I3PW1CT1] / CTFactorPri1
curr(b) = MAX [I3PW1CT2] / CTFactorPri2
curr(c) = MAX [I3PW2CT1] / CTFactorSec1
curr(d) = MAX [I3PW2CT2] / CTFactorSec2
curr(x) = MAX [I3PW1CT1 + I3PW1CT2]
curr(y) = MAX [I3PW2CT1 + I3PW2CT2]
curr(z) = IN
where the CTFactor = Irated_CT / Irated_W
default setting: 1.0 (1.0-10.0)

ABB Group
September 10, 2015 | Slide 9

Chapter 04

Operating characteristics
Restricted earth fault protection, Ibias

Example:

CT1
1000 A

The CTFactor :

gives a possibility to adjust the sensitivity

does not influence curr(x-z)

Single breaker application

CT2
1000 A

Chapter 04

Normally the CT ratio matches the winding and the


CTFactor = 1.0

Multiple breaker application

Could be necessary to modify CTFactor

500 A

curr(a) = MAX [I3PW1CT1] / CTFactorPri1

IBase = Irated_W and

Irated_CT > or >> Irated_W

curr(a and/or b) might stabilize to much due to transfer


currents (fault or load currents)

Example: CTFactor = 1000/500 = 2.0

curr(b) = MAX [I3PW1CT2] / CTFactorPri2


curr(x) = MAX [I3PW1CT1 + I3PW1CT2]

ABB Group
September 10, 2015 | Slide 10

Chapter 04

Operating characteristics
Directional criterion
IN , 3I0, IDiff

The restricted earth fault protection may be


very sensitive

ABB Group
September 10, 2015 | Slide 11

No room for any false unbalance currents

External faults may cause

CT saturation false residual currents


false tripping

The stabilizing characteristics helps to


stabilize to some extent

Objective:

Positively distinguish between internal and


external earth faults

Enhancing the security for heavy external


faults

Operating characteristics
Directional criterion

Same direction in the neutral for both external and internal faults

External fault

ABB Group
September 10, 2015 | Slide 12

Current in the neutral serves as directional reference

The currents are 180o out of phase (IED reference direction: towards the object)

Chapter 04

Operating characteristics
Directional criterion

Internal fault

The residual currents are approximately in phase

Not measuring the same primary current, IN and 3I0

Setting:

ABB Group
September 10, 2015 | Slide 13

Relay operate angle (ROA) 60 90o

Chapter 04

Chapter 04

Operating characteristics
Directional criterion

The directional check is executed if:

within the operate area of the REFcharacteristic

3I0 (terminal side) is at least 3% of IBase

The trip is issued if:

If the check is not executed (small currents)


then:

ABB Group
September 10, 2015 | Slide 14

both 3I0 an IN are within the operating region

the check is not a condition for trip

Chapter 04

Operating characteristics
Second harmonic blocking

Current [pu]

Shunt reactor switching


150 Mvar 220 kV 50 Hz

IN 3I0

Cycles

ABB Group
September 10, 2015 | Slide 15

Prevent unwanted operation on reactor energizing due to

terminal side CT saturation cased by

high DC component

The calculation adaptive (input: 3I0, IN, IBias and timing)

No setting: 2nd harmonic ratio: fixed to 60%

Chapter 04

Simplified logical diagram


Restricted earth fault protection
3I0

3I0 < 3% of IBase


3I0 > 3% of Ibase

IN
Directional
check

IN > 50% of Idmin


ABB Group
September 10, 2015 | Slide 16

&

TRIP

&

START

In- and output signals


Restricted earth fault protection

Analog input signals


(SMAI group signal output)

Binary input signal

ABB Group
September 10, 2015 | Slide 17

Neutral point current


Residual current - W1 - CT1
- W1 - CT2
- W2 - CT1
- W2 - CT2
Block input

Chapter 04

In- and output signals


Restricted earth fault protection

Trip
Start
Directionality: High Internal fault
Second harmonic blocking
Residual current W1+W2 (3I0)
Neutral current (IN)
Bias current
Differential current
Angle from zero sequence feature
Second harmonic ratio

ABB Group
September 10, 2015 | Slide 18

Chapter 04

Binary output signals

Analog output signals


HMI and Disturbance
recorder

Chapter 04

Restricted earth fault protection settings


Overview

Operation On/Off
Base values
Pick up level
Factors influencing bias

ABB Group
September 10, 2015 | Slide 19

Chapter 04

Monitored data
Restricted earth fault protection

ABB Group
September 10, 2015 | Slide 20

Tests/Functions status/Differential
Protection/LowImpREF(PDIF,87N)

TRIP

START

DIROK Internal fault

BLK2H Block due to 2nd harmonic

IRES Magnitude of residual current


(3I0, A)

IN Magnitude of neutral current (A)

IBIAS Magnitude of bias current (A)

IDIFF Magnitude of differential current


(A)

ANGLE Direction angle from zero


sequence feature (deg)

I2RATIO Second harmonic ratio

Chapter 04

ABB
SA-TGroup
Training
September 10, 2015 | Slide 21

S-ar putea să vă placă și