PowerLogicTM Ethernet Gateway EGX300

Setup

63230-319-216A2
3/2010

Topic Selection Page

ENGLISH

Figure 14:

Device Log Export

This option allows you to export device logs in three ways: by E-Mail, FTP,
or HTTP. Each method is described in the following sections.
NOTE: If the E-Mail, FTP, or HTTP servers are not located on the same
Ethernet network segment as the EGX, be sure the EGX Default Gateway is
properly configured. See Ethernet and TCP/IP Settings on page 6

E-mail Export
Action
1. From the Setup page, click Device Log
Export.

Result
Opens the Device Log Export page.

2. Select E-Mail as the mode of transport.

Opens the E-Mail device log export options.

3. Check the Incremental check box.

Selects only new interval data logged since the


last successful data export.

NOTE: If the transport is scheduled for


Hourly or Logging interval, the
incremental check box will be automatically
selected.
NOTE: If the Incremental check box is not
selected, the whole log file is sent via email attachment on each scheduled
interval.

4. Select Hourly, Daily, Weekly, Monthly, or Selects how often the data logs are sent.
Logging interval.

2010 Schneider Electric. All Rights Reserved.

19

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216A2
3/2010

Action

Result

ENGLISH

5. Depending on which options you selected Selects when the data logs are sent.
in the previous step, select the time of day,
day of the week, and/or the day of the
month.
6. In the From Address text box, type the e- Enters from whom the e-mail was sent.
mail address of the person administering
the device.
NOTE: A From e-mail address is required
because most SMTP servers require it.
7. In the To Addresses text boxes, type the Enters the e-mail addresses of the recipients
e-mail addresses (5 maximum) that will be
receiving the data logs (one address per
text box).
8. In the Server IP Address text boxes, enter Enters the address of the server delivering the
the address of the outgoing mail server
e-mail data logs.
(0.0.0.0 to 255.255.255.255).
NOTE: Contact your network administrator
if you do not know the address of the
Simple Mail Transfer Protocol (SMTP)
server.
9. In the Server TCP Port text box, enter the Enters the outgoing mail server delivery port.
outgoing mail server delivery port.
Default: 25
10. If the SMTP server requires login
information, enable the SMTP server
requires login check box.

Allows you to enter SMTP server login


information.

NOTE: The EGX supports Plain, Login,


CRAM-MD5, and Digest-MD5 access
authentication.
11. If you have checked the SMTP server
Records your SMTP server login information.
requires login check box, enter your
username and password in the text boxes.
12. Click Test E-mail to send a test e-mail
using the parameters you set, or click
Apply.

Sends a test e-mail, and/or applies the log


export e-mail settings.

NOTE: Clicking Test E-mail applies the


log export e-mail settings and sends a test
e-mail, and clicking Apply only applies the
settings.

Figure 15:

20

Device Log Export Page - E-mail

2010 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216A2
3/2010

FTP Export
Result
Opens the Device Log Export page.

2. Select FTP as the mode of transport.

Opens the FTP device log export options.

3. Enable the Incremental check box.

Selects only new data logged since the last


good send interval to be sent.

NOTE: If the transport is scheduled for


Hourlyor Logging interval, the
incremental check box will be automatically
selected.

ENGLISH

Action
1. From the Setup page, click Device Log
Export.

NOTE: If the Incremental check box is not


selected, the whole log file is sent via FTP
on each scheduled interval.
4. Select Hourly, Daily, Weekly, Monthly, or Selects how often the data logs are
Logging interval.
transported.
5. Depending on which options you selected Selects when the data logs are transported.
in the previous step, select the time of day,
day of the week, and/or the day of the
month.
6. In the Server IP Address text boxes, enter Enters the address of the server transporting
the address of the outgoing FTP server
the data logs.
(0.0.0.0 to 255.255.255.255).
NOTE: Contact your network administrator
if you do not know the address of the File
Transfer Protocol (FTP) server.
7. In the Server TCP Port text box, enter the Enters the outgoing delivery port.
FTP server port.
Default: 21
8. In the Directory text box, enter the
directory.

Allows you to enter directory information for the


remote server.

9. Enter your username and password in the


text boxes.

Records your server login information.

10. Enable the Passive check box.

Sets FTP file transfer mode to passive.

11. Click Test to test the FTP parameters you


set, or click Apply.

Sends a test file to the FTP server and


directory, and/or applies the FTP settings.

NOTE: Clicking Test applies the log export


FTP settings and transfers a test file, and
clicking Apply only applies the settings.

Figure 16:

Device Log Export Page - FTP

NOTE: If the transport is scheduled for Hourly or Logging interval, the incremental check box
will automatically be selected.

2010 Schneider Electric. All Rights Reserved.

21

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216A2
3/2010

HTTP Export

ENGLISH

Action

Result

1. From the Setup page, click Device Log


Export.

Opens the Device Log Export page.

2. Select HTTP as the mode of transport.

Opens the HTTP device log export options.

3. Enable the Incremental check box.

Selects only new data logged since the last


good send interval to be sent.

NOTE: If the transport is scheduled for


Hourly or Logging interval, the
incremental check box will be automatically
selected.
NOTE: If the Incremental check box is not
selected, the whole log file is sent via
HTTP on each scheduled interval.

4. Select Hourly, Daily, Weekly, Monthly, or Selects how often the data logs are
Logging interval.
transported.
5. Depending on which options you selected Selects when the data logs are transported.
in the previous step, select the time of day,
day of the week, and/or day of the month.
6. In the Server IP Address text boxes, enter Enters the address of the server transporting
the address of the HTTP server (0.0.0.0 to the data logs.
255.255.255.255).
NOTE: Contact your network administrator
if you do not know the address of the
Hyper Text Transfer Protocol (HTTP)
server.
7. In the Server TCP Port text box, enter the Enters the outgoing delivery port.
HTTP server port.
Default: 80
8. In the Path text box, enter the path to the Enters the server script path.
server script the web server will execute as
a result of the EGX posting data to it.
9. In the Field Name box, enter the name
Allows the EGX to push files to an existing
under which the web server will expect the WWW server script.
file name.
NOTE: If there is no such requirement, use
the default value datafile1.
10. In the Host Name box, enter the domain
name of the host.

Identifies a specific host on the WWW server if


it is hosting multiple domains on a single IP
address. (Blank by default)

11. Enter your user name and password in the Records your server login information.
text boxes.
12. Click Test to test the HTTP parameters
you set, or click Apply.

Sends a test file to the HTTP server and


directory, and/or applies the HTTP settings.

NOTE: Clicking Test applies the log export


HTTP settings and transfers a test file.
Clicking Apply only applies the settings.

22

2010 Schneider Electric. All Rights Reserved.

PowerLogicTM Ethernet Gateway EGX300


Setup

63230-319-216A2
3/2010

Device Log Export Page - HTTP

ENGLISH

Figure 17:

Date and Time

The Date and Time page allows you to set the date and time for the EGX.
Action

Result

1. From the Setup menu, click Date and


Time.

Opens the Date and Time page.

2. Configure the year, month, day, hour,


minutes, and seconds.

Sets up the date and time.

3. Select the Time Zone Offset.

Sets the clock to the selected time zone.

4. To set the clock to automatically adjust to Allows you to set the clock to adjust to Daylight
Daylight Savings Time, enable the Enable Savings Time automatically.
Automatic Daylight Savings Time
Adjustment check box.
5. Enter the number, day, month, and hour to Sets the beginning and end of the Daylight
begin and end Daylight Savings Time.
Savings Time adjustment.
6. Click Apply.

Figure 18:

Network Time Synchronization

Saves the Date and Time settings.

Date and Time Page

Enabling network time synchronization allows the time and date of the EGX
system clock to be set by a Network Time Protocol (NTP) server.
NOTE: If the NTP server is not located on the same Ethernet network segment
as the EGX, be sure the EGX Default Gateway is properly configured.

2010 Schneider Electric. All Rights Reserved.