Documente Academic
Documente Profesional
Documente Cultură
October, 2010
solid objects, and too much detail can make
the simulation process more cumbersome
than it needs to be. This is certainly true in
data centers, where small gaps between
equipment are fair game for the CFD solver,
but may not be particularly relevant to the
large-scale flow patterns in the room. Facility analysts must always consider whether or
not the air flow in a narrow gap is an important feature of the flow in the room as a
Introduction
WP104
Case 1
Problem Definition
A 5000 sq.ft. L-shaped data center is in operation at a major medical facility in the
Northeast. It has a raised floor and ceiling
return. Three downflow CRACs with turning vanes are positioned on the perimeter and
an upflow CRAC is positioned in the center
of the room. Ductwork is used to pipe the
supply air from the upflow CRAC to several
locations around the room.
Racks with heat loads ranging from 10 Watts
to 8 kW comprise a total heat load of 226
kW with a heat density of about 45 kW/sq.ft.
Four power density units (PDUs) each add an
average of 1 kW of heat to the room. The
supply plenum contains a number of pipes
and blockages. The rooms adjacent to the
data center are at a constant temperature of
72F, and the wall resistance is 2 ft2-F/(Btu/
Hr).
In the original model, the racks and 1inch
gaps between them - were properly sized, as
shown in Figure 2 (top). Gaps created in this
fashion are assumed to be important details
when the automated mesh generator goes to
work. However, their importance in the
global data center flow is questionable. To
find out how important the gaps are, a second
model is built in which the racks have the
same location but are given a slightly increased width to eliminate the gaps. The
To illustrate this point, two models of medium-sized data centers are considered using
CoolSim software. The original models of
the data centers are both accurate in the CAD
sense. All of the equipment is carefully represented, but as a result, there are gaps between adjacent equipment or there is excessive geometric detail. The models are then
improved for CFD by simplifying the geometry. The simulations are run and a thorough comparison is done to contrast the
original and modified geometries. In both
2010 Applied Math Modeling Inc.
WP104
2.801M
4.53
3.74
81
82
Results
WP104
Case 2
Problem Definition
Figure 4: A simplified structure on the CRAC return does not have all of the features
of the original, but does include the essential shielding and open areas
2010 Applied Math Modeling Inc.
WP104
Summary
These examples demonstrate that for the purpose of CFD modeling, simplified geometry
has advantages over complex, CADComplex
Simple
style geometries. In addition to saving
1.590 M
1.168M
Number of Cells
on the number of computational cells
2.32
1.87
Solution Time (Hours)
and solution time, the effort involved
in the setup is reduced as well. With
98
96
Max Room Temperature (F)
automatic grid generation and solution
91
90
Max Rack Inlet Temperature (F)
procedures in place for software de2,530
2,515
Max Perf Tile Flowrate (CFM)
signed for data center modeling, time
839
818
Min Perf Tile Flowrate (CFM)
savings during the setup can be significant. For the complex CRAC top,
Table 2: A comparison of the size, solution time,
for example, the original structure was
and a few results for the data center modeled with a
built using 33 baffle objects. By concomplex CRAC top and a simple CRAC top
trast, the simple model needed only 9
By changing only the structure on top of one
baffles. Even if the final goal is to have a
of the CRACs in the room, about 400,000
CFD model with a large amount of geometric
cells are saved and the CPU time is reduced
detail, these results show that simplified
by just under 30 minutes - or 19%. The
models are an excellent first pass solution
maximum rack inlet temperature differs by
and indeed, are usually just as good as mod1F and the maximum temperature in the
els with increased detail.
room by 2F. The maximum and minimum
flowrates through the perforated tiles are
within 2.5%.
WP104