Selection &
application guidelines
APPLICATION GUIDELINES
CONTENTS
FEATURES ................................................................................................................................4
SCROLL COMPRESSION PRINCIPLE ...................................................................................................5
The scroll compression process .................................................................................................................................. 5
DIMENSIONS ..........................................................................................................................10
MLZ/MLM015-019-021-026 .......................................................................................................................................10
MLZ/MLM030-038-045-048 .......................................................................................................................................11
MLZ/MLM058-066-076 ................................................................................................................................................12
Oil sight glass ..................................................................................................................................................................13
Schrader ............................................................................................................................................................................13
Suction and discharge connections .......................................................................................................................13
FRCC.PC.016.A1.22
APPLICATION GUIDELINES
CONTENTS
INSTALLATION ........................................................................................................................33
System cleanliness.........................................................................................................................................................33
Compressor handling and storage ..........................................................................................................................33
Compressor mounting.................................................................................................................................................33
Compressor holding charge ......................................................................................................................................33
Tube brazing procedure ..............................................................................................................................................33
Brazing material .............................................................................................................................................................33
Vacuum evacuation and moisture removal .........................................................................................................34
Liquid line filter driers ..................................................................................................................................................35
Refrigerant charging.....................................................................................................................................................35
Insulation resistance and dielectric strength ......................................................................................................35
FRCC.PC.016.A1.22
APPLICATION GUIDELINES
FEATURES
With its unique scroll design and manufacturing
process flexibility, the new Danfoss MLZ/MLM refrigeration compressor offers a highly efficient solution for demanding refrigeration applications.
This new family of refrigeration compressors includes 11 sizes of medium temperature scroll com-
FRCC.PC.016.A1.22
APPLICATION GUIDELINES
SUCTION
COMPRESSION
DISCHARGE
Danfoss scroll compressors are manufactured using the most advanced machining, assembly, and
process control techniques. In design of both the
compressor and the factory, very high standards
FRCC.PC.016.A1.22
of reliability and process control were first priority. The result is a highly efficient product with the
highest reliability obtainable, and a low sound
level.
APPLICATION GUIDELINES
Nomenclature
Type
Size
M LZ 021
Motor
Features
T4L
P9
Application
M: medium temperature refrigeration
Other features
LP gauge Gas equalisaOil
Oil sight Oil equalisation
port
drain
tion port
glass
Schrader
None
9 Threaded None
None
Nominal capacity
In thousand Btu/h at 60 Hz,
ARI, MBP conditions
Motor protection
L: internal motor protection
Model variation
T: design optimised for refrigeration
Label
Serial number
S
Manufacturing location
Production week
Production year
FRCC.PC.016.A1.22
03 09
K 12345
Incremental number
TECHNICAL SPECIFICATIONS
R134a
R134a
R22
60 Hz
R404A**
R22
50 Hz
R404A**
APPLICATION GUIDELINES
Model
Ton
MLZ015
MLZ019
MLZ021
MLZ026
MLZ030
MLZ038
MLZ045
MLZ048
MLZ058
MLZ066
MLZ076
MLZ015
MLZ019
MLZ021
MLZ026
MLZ030
MLZ038
MLZ045
MLZ048
MLZ058
MLZ066
MLZ076
MLZ/MLM015
MLZ/MLM019
MLZ/MLM021
MLZ/MLM026
MLZ/MLM030
MLZ/MLM038
MLZ/MLM045
MLZ/MLM048
MLZ/MLM058
MLZ/MLM066
MLZ/MLM076
MLZ015
MLZ019
MLZ021
MLZ026
MLZ030
MLZ038
MLZ045
MLZ048
MLZ058
MLZ066
MLZ076
MLZ015
MLZ019
MLZ021
MLZ026
MLZ030
MLZ038
MLZ045
MLZ048
MLZ058
MLZ066
MLZ076
MLZ/MLM015
MLZ/MLM019
MLZ/MLM021
MLZ/MLM026
MLZ/MLM030
MLZ/MLM038
MLZ/MLM045
MLZ/MLM048
MLZ/MLM058
MLZ/MLM066
MLZ/MLM076
2
2
3
3
4
5
6
7
7
9
10
2
2
3
3
4
5
6
7
7
9
10
2
2
3
3
4
5
6
7
7
9
10
2
2
3
3
4
5
6
7
7
9
10
2
2
3
3
4
5
6
7
7
9
10
2
2
3
3
4
5
6
7
7
9
10
Power
input*
kW
Efficiency *
COP
EER
W/W
Btu/h/W
Swept
volume
in3/rev
Displacement
cfh
4 600
4 900
6 100
7 400
8 800
10 600
11 600
13 400
15 900
17 700
15 800
16 800
21 000
25 200
30 100
36 200
39 400
45 700
54 100
60 300
2.34
2.49
3.08
3.63
4.33
5.00
5.50
6.76
7.54
8.64
1.98
1.98
2.00
2.03
2.03
2.12
2.10
1.98
2.10
2.04
6.75
6.75
6.82
6.94
6.94
7.24
7.17
6.75
7.17
6.98
2.66
2.82
3.49
4.20
4.94
6.02
6.56
7.69
9.08
9.91
267
284
351
423
497
606
660
774
914
998
36
36
36
53
53
53
53
90
90
90
68
68
68
82
82
82
82
97
99.6
99.6
2 900
3 100
3 800
4 600
5 400
6 700
7 100
8 400
9 800
10 900
9 900
10 500
13 000
15 700
18 400
22 800
24 200
28 800
33 500
37 300
1.40
1.45
1.77
2.11
2.56
2.95
3.18
3.95
4.49
5.11
2.07
2.13
2.15
2.18
2.10
2.26
2.23
2.14
2.18
2.14
7.07
7.26
7.34
7.45
7.18
7.72
7.59
7.30
7.45
7.30
2.66
2.82
3.49
4.20
4.94
6.02
6.56
7.69
9.08
9.91
267
284
351
423
497
606
660
774
914
998
36
36
36
53
53
53
53
90
90
90
68
68
68
82
82
82
82
97
99.6
99.6
4 600
4 900
6 200
7 200
8 500
10 700
11 600
13 200
15 800
18 100
15 600
16 700
21 300
24 700
29 100
36 400
39 500
45 100
53 900
61 800
2.03
2.23
2.62
3.20
3.79
4.50
4.92
5.78
6.43
7.43
2.26
2.19
2.38
2.27
2.25
2.37
2.36
2.29
2.46
2.44
7.71
7.48
8.13
7.74
7.67
8.09
8.04
7.81
8.39
8.32
2.66
2.82
3.49
4.20
4.94
6.02
6.56
7.69
9.08
9.91
267
284
351
423
497
606
660
774
914
998
36
36
36
53
53
53
53
90
90
90
68
68
68
82
82
82
82
97
99.6
99.6
5 700
6 100
7 600
8 900
10 700
12 900
14 100
16 300
19 200
21 700
19 500
20 800
25 800
30 300
36 500
44 100
48 200
55 600
65 500
73 900
2.81
2.98
3.75
4.25
5.13
6.16
6.71
8.01
9.14
10.43
2.03
2.05
2.02
2.09
2.09
2.10
2.11
2.03
2.10
2.08
6.93
6.99
6.88
7.13
7.12
7.17
7.19
6.94
7.17
7.09
2.66
2.82
3.49
4.20
4.94
6.02
6.56
7.69
9.08
9.91
323
343
424
510
600
731
797
934
1104
1205
36
36
36
53
53
53
53
90
90
90
68
68
68
82
82
82
82
97
99.6
99.6
3 600
3 800
4 700
5 700
6 700
8 100
8 600
10 300
11 800
13 300
12 300
13 100
16 100
19 500
22 900
27 600
29 300
35 200
40 400
45 500
1.68
1.74
2.10
2.57
3.05
3.64
3.88
4.69
5.34
6.16
2.14
2.21
2.25
2.22
2.20
2.22
2.22
2.20
2.22
2.16
7.31
7.54
7.69
7.59
7.50
7.59
7.56
7.51
7.57
7.38
2.66
2.82
3.49
4.20
4.94
6.02
6.56
7.69
9.08
9.91
323
343
424
510
600
731
797
934
1104
1205
36
36
36
53
53
53
53
90
90
90
68
68
68
82
82
82
82
97
99.6
99.6
5 700
6 100
7 800
9 000
10 600
12 900
14 100
16 400
19 200
22 400
19 500
21 000
26 600
30 800
36 200
44 100
48 300
55 900
65 600
76 300
2.68
2.59
3.27
3.80
4.48
5.34
5.88
7.04
7.92
9.27
2.13
2.37
2.38
2.37
2.37
2.42
2.41
2.33
2.42
2.41
7.28
8.08
8.12
8.10
8.10
8.26
8.21
7.95
8.28
8.23
2.66
2.82
3.49
4.20
4.94
6.02
6.56
7.69
9.08
9.91
323
343
424
510
600
731
797
934
1104
1205
36
36
36
53
53
53
53
90
90
90
68
68
68
82
82
82
82
97
99.6
99.6
* at ARI conditions: SST = 20F, SDT = 120F, RGT = 65F, SC = 0F. Presented data are for motor voltage code 4, 400V/3ph/50Hz & 460V/3ph/60Hz
** R507 performance data are nearly identical to R404A performance data
FRCC.PC.016.A1.22
APPLICATION GUIDELINES
TECHNICAL SPECIFICATIONS
50 Hz
Models
SST = 20 , SDT = 105 F SST = 25 F, SDT = 105 F SST = 32 F, SDT = 105 F SST = 25 F, SDT = 110 F SST = 20 F, SDT = 120 F
RGT = 65 F, SC = 0 F
RGT = 65 F, SC = 0 F
RGT = 65 F, SC = 0 F
RGT = 65 F, SC = 0 F
RGT = 65 F, SC = 0 F
Cold room
Ice machine
Air drier
Milk tank
ARI MT conditions
Capacity
(Btu/h)
EER
(Btu/h/W)
Capacity
(Btu/h)
EER
(Btu/h/W)
Capacity
(Btu/h)
EER
(Btu/h/W)
Capacity
(Btu/h)
EER
(Btu/hr/W)
Capacity
(Btu/h)
EER
(Btu/h/W)
R404A *
MLZ015
MLZ019
18 400
9.49
20 300
10.52
23 300
12.12
19 400
9.42
15 800
6.75
MLZ021
19 500
9.51
21 600
10.51
24 700
12.07
20 600
9.42
16 800
6.75
MLZ026
24 400
9.60
27 000
10.63
30 900
12.21
25 800
9.53
21 000
6.82
MLZ030
29 400
9.74
32 500
10.78
37 300
12.37
31 000
9.67
25 200
6.94
MLZ038
35 100
9.71
38 800
10.71
44 400
12.25
37 000
9.61
30 100
6.94
MLZ045
42 200
10.17
46 700
11.23
53 400
12.86
44 500
10.08
36 200
7.24
MLZ048
46 000
10.09
50 800
11.16
58 200
12.82
48 400
10.00
39 400
7.17
MLZ058
54 800
9.76
60 900
10.86
70 200
12.47
57 700
9.69
45 700
6.75
MLZ066
62 800
9.92
69 300
10.90
79 300
12.35
66 200
9.84
54 100
7.17
MLZ076
72 400
9.94
79 900
10.89
91 500
12.35
75 600
9.74
60 300
6.98
MLZ019
10 900
9.22
12 300
10.32
14 500
12.05
12 000
9.46
9 900
7.07
MLZ021
11 600
9.46
13 100
10.59
15 400
12.35
12 700
9.71
10 500
7.26
MLZ026
14 400
9.61
16 200
10.76
19 100
12.55
15 700
9.85
13 000
7.34
MLZ030
17 300
9.74
19 500
10.91
22 900
12.74
18 900
9.99
15 700
7.45
MLZ038
20 400
9.40
23 000
10.52
27 000
12.25
22 300
9.62
18 400
7.18
MLZ045
25 300
10.19
28 600
11.44
33 700
13.38
27 600
10.44
22 800
7.72
MLZ048
26 800
10.01
30 300
11.20
35 600
13.05
29 300
10.24
24 200
7.59
MLZ058
32 000
9.56
36 000
10.63
42 100
12.27
34 800
9.73
28 800
7.30
MLZ066
37 100
9.75
41 800
10.86
48 900
12.57
40 400
9.94
33 500
7.45
MLZ076
41 400
9.56
46 600
10.65
54 600
12.32
45 100
9.74
37 300
7.30
MLZ/MLM019
17 300
10.11
19 200
11.20
22 200
12.77
18 600
10.24
15 600
7.71
MLZ/MLM021
18 400
9.91
20 400
10.99
23 500
12.54
19 800
10.06
16 700
7.48
MLZ/MLM026
23 400
10.90
25 900
12.03
29 800
13.70
25 100
10.94
21 300
8.13
MLZ/MLM030
27 500
10.25
30 500
11.49
35 100
13.13
29 600
10.49
24 700
7.74
MLZ/MLM038
32 100
10.15
35 700
11.34
41 200
12.96
34 600
10.36
29 100
7.67
MLZ/MLM045
40 000
10.70
44 200
11.70
50 900
13.38
42 900
10.68
36 400
8.09
MLZ/MLM048
43 200
10.59
48 100
11.67
55 600
13.39
46 800
10.68
39 500
8.04
MLZ/MLM058
50 200
10.54
56 300
11.81
65 700
13.66
54 600
10.77
45 100
7.81
MLZ/MLM066
58 800
10.93
65 700
12.13
76 000
13.85
63 900
11.14
53 900
8.39
MLZ/MLM076
68 000
11.11
75 500
12.23
87 100
13.95
73 400
11.19
61 800
8.32
R134a
MLZ015
R22
MLZ/MLM015
FRCC.PC.016.A1.22
TECHNICAL SPECIFICATIONS
APPLICATION GUIDELINES
60 Hz
Models
SST = 20 , SDT = 105 F SST = 25 F, SDT = 105 F SST = 32 F, SDT = 105 F SST = 25 F, SDT = 110 F SST = 20 F, SDT = 120 F
RGT = 65 F, SC = 0 F
RGT = 65 F, SC = 0 F
RGT = 65 F, SC = 0 F
RGT = 65 F, SC = 0 F
RGT = 65 F, SC = 0 F
Cold room
Ice machine
Air drier
Milk tank
ARI MT conditions
Capacity
(Btu/h)
EER
(Btu/h/W)
Capacity
(Btu/h)
EER
(Btu/h/W)
Capacity
(Btu/h)
EER
(Btu/h/W)
Capacity
(Btu/h)
EER
(Btu/hr/W)
Capacity
(Btu/h)
EER
(Btu/h/W)
MLZ019
22 600
9.68
24 900
10.71
28 500
12.29
23 800
9.60
19 500
6.93
MLZ021
24 100
9.72
26 600
10.76
30 400
12.33
25 400
9.68
20 800
6.99
MLZ026
29 900
9.58
33 000
10.58
37 800
12.12
31 600
9.51
25 800
6.88
MLZ030
35 200
9.89
38 900
10.88
44 400
12.41
37 100
9.81
30 300
7.13
MLZ038
42 200
9.84
46 500
10.82
53 100
12.33
44 500
9.74
36 500
7.12
MLZ045
51 100
10.01
56 400
11.05
64 500
12.62
53 900
9.92
44 100
7.17
MLZ048
56 000
9.96
61 800
10.96
70 600
12.51
59 000
9.87
48 200
7.19
MLZ058
66 600
9.83
73 900
10.80
84 900
12.26
69 900
9.70
55 600
6.94
MLZ066
75 900
9.71
83 800
10.61
95 900
11.96
80 000
9.63
65 500
7.17
MLZ076
86 600
9.76
95 600
10.68
109 400
12.05
91 000
9.65
73 900
7.09
R404A *
MLZ015
R134a
MLZ015
MLZ019
13 600
9.45
15 400
10.59
18 100
12.32
14 900
9.73
12 300
7.31
MLZ021
14 500
9.74
16 400
10.91
19 300
12.71
15 900
10.03
13 100
7.54
MLZ026
17 800
9.96
20 200
11.14
23 800
12.94
19 600
10.23
16 100
7.69
MLZ030
21 500
9.81
24 300
11.01
28 700
12.84
23 600
10.12
19 500
7.59
MLZ038
25 200
9.75
28 500
10.94
33 700
12.73
27 700
10.04
22 900
7.50
MLZ045
31 000
10.10
35 000
11.32
41 200
13.20
33 800
10.33
27 600
7.59
MLZ048
32 800
10.02
37 000
11.20
43 500
12.99
35 800
10.23
29 300
7.56
MLZ058
39 100
9.84
43 900
10.90
51 400
12.49
42 500
9.98
35 200
7.51
MLZ066
44 900
9.89
50 400
10.94
59 000
12.53
48 900
10.02
40 400
7.57
MLZ076
50 400
9.68
56 600
10.72
66 200
12.29
54 900
9.82
45 500
7.38
R22
MLZ/MLM015
MLZ/MLM019
21 300
9.31
23 700
10.37
27 400
11.93
23 100
9.57
19 500
7.28
MLZ/MLM021
23 100
10.33
25 500
11.63
29 400
13.35
24 800
10.72
21 000
8.08
MLZ/MLM026
28 900
10.75
31 700
11.76
36 200
13.25
31 000
10.75
26 600
8.12
MLZ/MLM030
33 600
10.44
37 500
11.54
43 300
13.13
36 400
10.62
30 800
8.10
MLZ/MLM038
39 900
10.52
44 300
11.52
51 000
13.06
43 000
10.59
36 200
8.10
MLZ/MLM045
48 700
10.85
54 200
11.96
62 500
13.61
52 700
10.96
44 100
8.26
MLZ/MLM048
53 300
10.79
59 200
11.92
68 300
13.60
57 500
10.92
48 300
8.21
MLZ/MLM058
62 100
10.46
69 100
11.58
80 000
13.29
67 000
10.63
55 900
7.95
MLZ/MLM066
71 500
10.59
79 500
11.68
91 700
13.34
77 400
10.78
65 600
8.28
MLZ/MLM076
83 600
10.70
92 500
11.83
106 200
13.46
89 900
10.87
76 300
8.23
FRCC.PC.016.A1.22
APPLICATION GUIDELINES
DIMENSIONS
MLZ/MLM015-019-021-026
9.40
7.50
4 x 0.75
5.06
4.32
9.40
7.50
4.38
34
31
45
73
6.45
Discharge
port1/2
ODF
2.90
Oil sight glass
15.48
14.19
Schrader valve
and cap
9.09
7.67
2.15
3.09
All dimensions in Inch
0.74
0.43
Terminal box
Mounting grommet
0.06
1.16
1.61
5/16 - 18 UNC
self tapping
0.43
1.61
Recommended torque for mounting bolts:
100 lbf.in (10 lbf.in)
10
FRCC.PC.016.A1.22
APPLICATION GUIDELINES
DIMENSIONS
MLZ/MLM030-038-045-048
9.41
7.48
4 x 0.75
5.26
4.66
9.41
7.49
1) 4.76
2) 4.80
34
31
45
73
7.187-7.265
Discharge port
1) 1/2 ODF
2) 3/4 ODF
3.70
17.16
Oil sight glass
15.85
10.27
Schrader valve
and cap
7.9
1) MLZ/MLM 030-038-045
2) MLZ/MLM 048
3.36
2.22
0.74
0.43
Terminal box
Mounting grommet
0.06
1.16
1.61
5/16 - 18 UNC
self tapping
0.43
1.61
Recommended torque for mounting bolts:
100 lbf.in (10 lbf.in)
FRCC.PC.016.A1.22
11
APPLICATION GUIDELINES
DIMENSIONS
MLZ/MLM058-066-076
9.13
7.491 - 7.509
4 x 0.75 - 0.78
5.24
4.93
9.13
7.491-7.509
4.84
34
31
73
45
7.211 - 7.288
Discharge
port 7/8 ODF
Suction port 11/8 ODF
3.63 - 3.70
1) 19.29
2) 19.66
1) 20.34
2) 20.72
13.79
11.28
Schrader valve
and cap
0.28
1) MLZ/M058
2) MLZ/M066-076
1.91
0.27
0.74
Terminal box
Mounting grommet
0.06
1.16
1.61
5/16 - 18 UNC
self tapping
0.43
1.61
Recommended torque for mounting bolts:
100 lbf.in (10 lbf.in)
12
FRCC.PC.016.A1.22
APPLICATION GUIDELINES
DIMENSIONS
Schrader
MLZ / MLM scroll compressors are factory delivered with brazed connections only. Dedicated
rotolock adaptors and adaptor sets are available
as accessory.
c d e f
Compressor models
3/4"
Rotolock
1-1/4"
3/4"
MLZ/MLM 015-019-021-026
Code Number
Rotolock adaptor
(c adaptor only)
Code Number
120Z0366
120Z0126
Discharge
1/2"
1"
1/2"
Suction
7/8"
1-1/4"
7/8"
MLZ/MLM 030-038-045
120Z0365
120Z0367
120Z0127
Discharge
1/2"
1"
1/2"
Suction
7/8"
1-1/4"
7/8"
MLZ/MLM 048
120Z0365
120Z0367
120Z0128
Discharge
3/4"
1-1/4"
3/4"
Suction
1-1/8"
1-3/4"
1-1/8"
MLZ/MLM 058-066-076
120Z0366
120Z0364
120Z0129
Discharge
7/8"
FRCC.PC.016.A1.22
1-1/4"
7/8"
120Z0367
13
APPLICATION GUIDELINES
Motor voltage
Nominal voltage
200-220 V / 3 ph / 50 Hz
380-400 V / 3 ph / 50 Hz
220-240 V / 1 ph / 50Hz
Voltage range
180 - 242 V
340 - 460 V
198 - 264 V
208-230 V / 1 ph / 60 Hz
208-230 V / 3 ph / 60 Hz
460 V / 3 ph / 60 Hz
187 - 253 V
187 - 253 V
414 - 506 V
50 Hz
Nominal voltage
60 Hz
Voltage range
Wiring connections
the two outside tabs of the cover engage the terminal box.
push
push
push
IP rating
The compressor terminal box IP rating according to CEI 529 is IP22 for all models.
First numeral, level of protection against contact and foreign objects
2 protection against object size over 1/2 inch (fingers of similar)
Second numeral, level of protection against water
2 protection against dripping water when tilted up to 15
14
FRCC.PC.016.A1.22
APPLICATION GUIDELINES
Compressor model
MLZ/MLM015T4
MLZ/MLM019T4
MLZ/MLM021T4
MLZ/MLM026T4
MLZ/MLM030T4
MLZ/MLM038T4
MLZ/MLM045T4
MLZ/MLM048T4
MLZ/MLM058T4
MLZ/MLM066T4
MLZ/MLM076T4
MLZ019T2
MLZ021T2
MLZ026T2
MLZ030T2
MLZ038T2
MLZ045T2
MLZ048T2
MLZ058T2
MLZ066T2
MLZ076T2
Compressor model
MLZ/MLM 015T5
MLZ/MLM 019T5
MLZ/MLM 021T5
MLZ/MLM 026T5
MLZ/MLM 030T5
MLZ/MLM 038T5
MLZ019T1
MLZ021T1
MLZ026T1
MLZ030T1
MLZ038T1
LRA
A
MCC
A
Max Oper.A
A
45
45
45
60
70
82
87
95
110
140
95
95
95
120
123
170
190
190
235
235
9.5
9.5
11
13
15
15
16
20
24
25
17.5
17.5
22.0
26.0
26.0
30.0
37.0
40.0
46.0
50.0
6.7
6.8
8.3
9.8
11.7
14.1
15.3
18.1
20.3
23.9
13.3
13.6
16.6
19.7
23.5
28.2
30.6
36.1
40.7
47.6
Winding resistance ()
T1-T3
T1-T2
T2-T3
3.4
3.4
3.4
2.6
2.3
1.9
1.7
1.4
1.3
1.1
0.87
0.87
0.87
0.67
0.60
0.48
0.43
0.37
0.32
0.32
LRA
A
MCC
A
Max. Oper. A
A
97
97
97
127
130
97
97
115
150
160
23.0
25.0
27.0
32.0
42.0
25.0
24.5
31.5
38.0
45.0
18.3
19.5
24.2
28.9
33.9
19.9
21.4
26.8
31.9
37.2
4.7
4.7
4.7
2.6
2.3
1.9
1.7
1.4
1.3
1.1
1.18
1.18
1.18
0.67
0.60
0.46
0.44
0.37
0.32
0.32
4.7
4.7
4.7
2.6
2.4
1.8
1.7
1.4
1.3
1.1
1.18
1.18
1.18
0.68
0.61
0.48
0.43
0.37
0.33
0.33
Winding resistance ()
run
start
0.69
0.69
0.69
0.42
0.39
0.67
0.67
0.55
0.34
0.28
1.51
1.51
1.51
1.31
1.02
1.57
1.57
1.47
0.90
1.76
The MCC is the current at which the internal motor protection trips under maximum load and low
voltage conditions.
This MCC value is the maximum at which the compressor can be operated in transient conditions
and out of the application envelope. Above this
value the overload will switch off to protect the
motor.
The Max Oper. A is the current when the compressor operates at maximum load conditions and
10% below nominal voltage.
FRCC.PC.016.A1.22
15
APPLICATION GUIDELINES
Winding resistance
Winding resistance is the resistance between indicated terminal pins at 77F (resistance value
7%).
Winding resistance is generally low and it requires
adapted tools for precise measurement. Use a digital ohm-meter, a 4 wires method and measure
under stabilised ambient temperature. Winding
resistance varies strongly with winding temperature ; If the compressor is stabilised at a different
value than 77F, the measured resistance must be
corrected with following formula:
Electrical connections
PSC wiring
Rtamb = R77F
a + tamb
a + t77F
Thermostat
IOL
If the starting torque of the PSC wiring is not sufficient due to pressures not fully equalized during
the off-cycle or some voltage drop during starting, the PTCSCR wiring might be an option. PTCSRC wiring provides more motor torque than PSC
wiring but less than CSR wiring. The PTC is wired in
parallel to the run capacitor.
When starting the compressor, the PTC, which is at
low resistance, provides additional starting current
to the motors start winding. The current passing
through the PTC causes it to heat up and, at a certain temperature, change to a very high resistance.
At this time the motor is up to nominal speed and
the run capacitor determines the current through
the start winding. The PTC remains at high temperature and thus at high resistance as long as
power is connected to the compressor. When the
compressor is switched off, the PTC cools down to
its initial low resistance and becomes available to
support the next compressor start.
It is important to provide sufficient time between
Model
MLZ/MLM015
MLZ/MLM019
MLZ/MLM021
MLZ/MLM026
MLZ/MLM030
MLZ/MLM038
Run capacitor
Voltage code 1
208-230 V/1~/60 Hz
305C12*
305C9* / 305C11*
305C9* / 305C11*
305C12*
305C9* / 305C11*
305C9* / 305C11*
Thermostat
IOL
Run capacitor
PTC
Voltage code 5
220-240 V/1~/50 Hz
305C9* / 305C11*
305C9* / 305C11*
305C9* / 305C11*
305C9* / 305C11*
305C9* / 305C11*
305C9* / 305C11*
Note: MLZ compressors with PTCSCR are not approved by UL. It is the customers responsibility to get final approval for the system
when required.
16
FRCC.PC.016.A1.22
APPLICATION GUIDELINES
CSR wiring
L
Start Relay
C
5
Thermostat
2
Run capacitor
MLZ/MLM015-019-021-026
220-240 V /1/50 Hz
Motor voltage code 5
208-230 V / 1 / 60 Hz
Motor voltage code 1
Start capacitor
15 k -1 w
Relay
Reference
3ARR3J3AL4
RVA9CKL
MLZ/MLM030
50
370
161-193
250
3ARR3J24AP4
RVA3EKL
MLZ/MLM038-045-048
55
440
88-108
330
3ARR3J25AS4
RVA4GKL
MLZ/MLM019-021
45
370
145-175
250
3AAR3*3M*
MLZ/MLM026
60
370
88-108
330
3ARR3*3L*
MLZ/MLM030-033
60
370
161-193
250
3ARR3*3L*
MLZ/MLM038
55
440
88-108
250
3ARR3*25S*
Three phase
CONTROL CIRCUIT
L1
L3
L2
Q1
F1
F1
KM
KA
KM
KA
KS
KA
PM
A1
T1
T2
A3
KS
Control device.................................................. TH
Optional short cycle timer (3 min) .........180 s
Control relay .................................................... KA
Liquid Line Solenoid valve .........................LLSV
Compressor contactor .................................. KM
Phase monitor ................................................ PM
Safety lock out relay........................................KS
Pump-down control low pressure switch ..LP
High pressure safety switch........................ HPs
Fused disconnect ............................................Q1
Fuses ...................................................................F1
Compressor motor ...........................................M
Discharge gas thermostat ......................... DGT
FRCC.PC.016.A1.22
180 s
HPs
T3
A2
TH
LP
KS
M
DGT
KM
KA
LLSV
KS
17
APPLICATION GUIDELINES
MLZ/MLM015-038 scroll compressors are designed to operate for a maximum of 150 hours in
reverse, but as a reverse rotation situation can go
unnoticed for longer periods, phase monitors are
recommended.
Voltage imbalance
For three-phase applications the voltage measured at the compressor terminals for each phase
18
FRCC.PC.016.A1.22
APPLICATION GUIDELINES
Conformity to directives
Products
114
MLZ/MLM 030-048
114
MLZ/MLM 058-076
375
FRCC.PC.016.A1.22
19
APPLICATION GUIDELINES
OPERATING CONDITIONS
The scroll compressor application range is influenced by several parameters which need to be
monitored for a safe and reliable operation.
These parameters and the main recommendations for good practice and safety devices are explained hereunder.
General information
R22
R22 is an HCFC refrigerant and is still a wide use today. It has a low ODP (Ozone Depletion Potential)
and therefore it will be phased out in the future.
Check local legislation.
R134a
R404A
R507
R507 is an HFC refrigerant with properties comparable to R404A. R507 has no ozone depletion
potential (ODP = 0). As with R404A, R507 is particularly suitable for low evaporating temperature
PVE
The compressor technology applied in MLZ compressors in combination with PVE lubricant provides the best possible result in terms of reliability
and compressor lifetime.
The PVE lubricant is compatible with R22 which
makes the MLZ compressors a very versatile multirefrigerant solution.
Alkylbenzene oil
MLM series compressors are charged with Alkylbenzene oil and herewith offer an economically
interesting alternative to the MLZ series in regions
where R22 is still the predominant refrigerant.
Note however that MLM compressors can not be
used with HFC refrigerants.
20
FRCC.PC.016.A1.22
APPLICATION GUIDELINES
OPERATING CONDITIONS
Motor supply
Compressor ambient
temperature
In case of enclosed fitting and high ambient temperature its recommend to check the temperature
of power wires and conformity to their insulation
specification.
In case of safe tripping by the internal compressor overload protection the compressor must cool
down to about 140F before the overload will reset. A high ambient temperature can strongly delay this cool-down process.
Application envelope
R134a and R22. The operating limits serve to define the envelope within which reliable operations
of the compressor are guaranteed:
Maximum discharge gas temperature: 275F
A suction superheat below 10F is not recommended due to the risk of liquid flood back
Minimum and maximum evaporating and condensing temperatures as per the operating envelopes.
160
140
Transient conditions
120
RGT: 65F
100
80
60
40
-30
-20
-10
10
20
30
40
50
60
FRCC.PC.016.A1.22
21
APPLICATION GUIDELINES
OPERATING CONDITIONS
MLZ - R134a
170
160
150
140
130
SH: 20F
120
110
100
90
80
70
60
0
10
20
30
40
50
60
70
130
120
SH: 20F
110
100
RGT: 77F
90
80
70
60
50
-30
-20
-10
10
20
22
FRCC.PC.016.A1.22
30
40
50
60
APPLICATION GUIDELINES
OPERATING CONDITIONS
MLZ / MLM
160
150
R22 - SH 20F
HP1
140
Example 1
130
HP2
120
Example 2
110
100
90
80
LP1
LP2
70
60
50
-30
-20
-10
10
20
30
40
50
60
Thermostat
Discharge line
Insulation
Bracket
FRCC.PC.016.A1.22
23
APPLICATION GUIDELINES
OPERATING CONDITIONS
R22
R404A
R134a
PSI
102 - 405
104 - 395
71.2 - 321
PSI
10.3 - 92.8
15.1 -104
9.3 - 58
PSI
432
431
342
PSI
7.4
11.6
6.5
13.6
19.0
12.3
High pressure
MLZ/MLM 015-048 scroll compressors are equipped with an internal pressure relief valve (IPRV),
for protection against blocked condenser and fan
failure conditions (IPRV setting 464 PSI 58 differential pressure HP / LP). Still, a high pressure (HP)
safety switch is recommended.
The high-pressure switch can be set to lower values depending on the application and ambient
conditions. The HP switch must either be placed in
a lockout circuit or consist of a manual reset device
to prevent cycling around the high-pressure limit.
If a discharge valve is used, the HP switch must be
connected to the service valve gauge port, which
must not be isolated.
Low pressure
the LP safety switch must either be a manual lockout device or an automatic switch wired into an
electrical lockout circuit. The LP switch tolerance
must not allow for vacuum operations of the compressor. LP switch settings for pump-down cycles
with automatic reset are also listed in the table
above.
The system must be designed in a way that provides a minimum compressor running time of 2
minutes so as to provide for sufficient motor cooling after start-up along with proper oil return.
24
FRCC.PC.016.A1.22
APPLICATION GUIDELINES
General
Piping should be designed with adequate threedimensional flexibility (figure 2). It should not be
in contact with the surrounding structure, unless
a proper tubing mount has been installed. This
protection proves necessary to avoid excess vibration, which can ultimately result in connection
or tube failure due to fatigue or wear from abrasion. Aside from tubing and connection damage,
excess vibration may be transmitted to the surrounding structure and generate an unacceptable sound level within that structure as well (for
more information on sound and vibration, see the
section on: Sound and vibration management
page 31).
fig.1
g. 2
To condenser
Upper loop
0.5 % slope,
13 ft/s or more
U-trap
Condenser
max. 13 ft
HP
U-trap, as short as possible
U-trap
LP
26 to 40 ft/s
3D exibility
max. 13 ft
0.5 % slope,
13 ft/s or more
Evaporator
FRCC.PC.016.A1.22
25
APPLICATION GUIDELINES
Use the tables below to quickly evaluate the required compressor protection in relation with the
system charge and the application. More detailed
information can be found in the paragraphs hereafter. Please contact Danfoss for any deviation
from these guidelines.
Model
MLZ015-026
MLZ030-048
MLZ058-076
8
12
16
Depending on test results, crankcase heaters, Liquid Line Solenoid Valve, pump down or suction accumulator must be applied see below.
BELOW charge limit
Packaged units
System with remote heat exchanger
REC Recommended
REC
REQ Required
REQ
REQ
REQ
REQ
Note: for special conditions such as low ambient temperature, low load operation or brazed plate heat exchangers please refer to corresponding sections
O-cycle migration
26
The presence of liquid in the crankcase can be easily detected by checking the sump level through
the oil sight glass. Foam in the oil sump indicates
a flooded start.
A noisy start, oil loss from the sump and sump cool
down are indications for migration. Depending on
the amount of migration graduate measures shall
be taken:
Crankcase heater
Liquid line solenoid valve
Pump down cycle
FRCC.PC.016.A1.22
MLZ/MLM scroll compressors can tolerate occasional flooded starts as long as the system has
been evaluated.
APPLICATION GUIDELINES
Provide separate electrical supply for the heaters so that they remain energized even when the
machine is out of service (eg. Seasonal shutdown).
Belt-type crankcase heater accessories are available from Danfoss (see page 39).
The heater must be energized whenever the compressor is off.
FRCC.PC.016.A1.22
Optimum
location area
charge transfer or excessive migration to the compressor during off-cycles. The quantity of refrigerant remaining in the low-pressure side of the
system can be further reduced by using a pumpdown cycle in association with the LLSV.
Models MLZ/MLM015-048 incorporate an internal low leak check valve that is appropriate for
pump-down operations. This valve prevents the
back flow of refrigerant from the high pressure
to the low pressure side through the compressor
so pump down conditions can be achieved and
maintained.
Models MLZ/MLM058-076 are not equipped with
this low leak check valve. Under certain conditions, the internal valve may not completely seal,
and due to the refrigerant back flow the compressor might restart during pump-down applications.
Repeated short cycling can result in a compressor
breakdown. It is recommended to install an external magnetic check valve (such as Danfoss Part No.
120Z5046) close to the compressors discharge
connector so the discharge volume is minimized.
A magnetic check valve is recommended for this
as it offers the best solution regarding minimal required and maximal pressure drop over the wide
application envelope of the MLZ/MLM compressors. If a Danfoss NRV check valve is applied it has
to be carefully selected for the specific operation
conditions of the individual system.
27
APPLICATION GUIDELINES
Tests for pump down cycle approval:
As the pump-down switch setting is inside the
application envelope, tests should be carried out
to check unexpected cut-out during transient
conditions (ie. defrost cold starting). When unwanted cut-outs occur, the low pressure pumpdown switch can be delayed. In this case a low
pressure safety switch without any delay timer
is mandatory.
While the thermostat is off, the number of pressure switch resets should be limited to avoid
short cycling of the compressor. Use dedicated
wiring and an additional relay which allows for
one shot pump-down.
A continuous liquid flood back will cause oil dilution and, in extreme situations lead to lack of
lubrication and high rate of oil leaving the compressor.
temperature be less than 65F above the saturated discharge temperature, this indicates liquid
flood back.
During operations, liquid flood back may be detected by measuring either the oil sump temperature or the discharge gas temperature. If at any
time during operations, the oil sump temperature
drops to within 20F or less above the saturated
suction temperature, or should the discharge gas
Suction accumulator: a suction accumulator offers protection against refrigerant flood back at
start-up, during operations or defrosting by trapping the liquid refrigerant upstream from the
compressor. The suction accumulator also protects against off-cycle migration by providing additional internal free volume to the low side of the
system.
28
The pump-down allows to store all the refrigerant in the high pressure side circuit. On unitary or
close-coupled systems, where the system refrigerant charge is expected to be both correct and
definable the entire system charge may be stored
in the condenser during pump-down if all components have been properly sized.
FRCC.PC.016.A1.22
A suction accumulator must be carefully dimensioned, taking into account the refrigerant charge
as well as the gas velocity in the suction line. Depending on the operating conditions it may happen that the recommended connections of the
accumulator are one size smaller than the suction
line.
APPLICATION GUIDELINES
FRCC.PC.016.A1.22
29
APPLICATION GUIDELINES
the motor receives enough cooling under conditions of lowest refrigerant mass flow.
Brazed plate
heat exchangers
A brazed plate heat exchanger needs very little internal volume to satisfy the heat transfer requirements. Consequently, the heat exchanger offers
very little internal volume for the compressor to
draw vapour from the suction side. The compressor can then quickly enter into a vacuum condition. It is therefore important that the expansion
device be sized correctly and that a sufficient pressure differential across the expansion device be
available to ensure adequate refrigerant feed into
the evaporator. This aspect is of special concern
when operating the unit under low ambient and
load conditions. For further information on these
conditions, please refer to the previous sections.
Corrosion: Materials in the system shall be compliant with water and protected against corrosion.
30
FRCC.PC.016.A1.22
When using a brazed plate condenser heat exchanger, a sufficient free volume for the discharge
gas to accumulate is required in order to avoid excess pressure build-up. At least 3 ft of discharge
line is necessary to generate this volume. To help
reduce the discharge gas volume immediately
after start-up, the supply of cooling water to the
heat exchanger may be opened before the compressor starts, to remove superheat and condense
the incoming discharge gas more quickly.
APPLICATION GUIDELINES
50 Hz
Model
60 Hz
MLZ/MLM 019
65
57
68
60
MLZ/MLM 021
65
57
68
60
MLZ/MLM026
67
59
70
62
MLZ/MLM 030
70
62
73
65
MLZ/MLM 038
71
63
74
66
MLZ/MLM 045
71
63
74
66
MLZ/MLM 048
72
64
75
67
MLZ/MLM 058
74
66
77
69
MLZ/MLM 066
74
66
77
69
MLZ/MLM 076
74
66
77
69
MLZ/MLM 015
MLZ/MLM have a unique discharge valve design that minimizes stopping noise. This results in very low
shutdown sound.
Sound generation in a
refrigeration system
Typical sound and vibration in refrigeration systems encountered by design and service engineers may be broken down into the following
three source categories.
Sound radiation: This generally takes an airborne
path.
FRCC.PC.016.A1.22
31
APPLICATION GUIDELINES
Mechanical vibrations
Vibration isolation constitutes the primary method for controlling structural vibration. MLZ/MLM
scroll compressors are designed to produce minimal vibration during operations. The use of rubber isolators on the compressor base plate or on
the frame of a manifolded unit is very effective
in reducing vibration being transmitted from the
compressor(s) to the unit. Rubber grommets are
supplied with all MLZ/MLM compressors. Once
the supplied rubber grommets have been properly mounted, vibration transmitted from the
compressor base plate to the unit are held to a
strict minimum. In addition, it is extremely important that the frame supporting the mounted
compressor be of sufficient mass and stiffness to
help dampen any residual vibration potentially
transmitted to the frame. The tubing should be
designed so as to both reduce the transmission of
vibrations to other structures and withstand vibration without incurring any damage. Tubing should
also be designed for three-dimensional flexibility.
For more information on piping design, please see
the section entitled "Essential piping design considerations" p. 25.
Gas pulsation
The MLZ/MLM scroll compressors have been designed and tested to ensure that gas pulsation has
been minimized for the most commonly encountered refrigeration pressure ratio. On installations
where the pressure ratio lies beyond the typical
range, testing should be conducted under all ex-
32
FRCC.PC.016.A1.22
APPLICATION GUIDELINES
System cleanliness
INSTALLATION
Each MLZ/MLM compressor is shipped with printed Instructions for installation. These Instructions
can also be downloaded from our web site
tion in the vertical position, with a maximum inclination of 15 from vertical. Store the compressor
between -31F and 131F, not exposed to rain or
corrosive atmosphere.
Compressor mounting
Compressor holding
charge
Each compressor is shipped with a nominal dry nitrogen holding charge between 6 and 10PSI, and
is sealed with elastomer plugs. The plugs should
be removed with care to avoid oil loss when the
holding charge is released. Remove the suction
plug first and the discharge plug afterwards. The
plugs shall be removed only just before connecting the compressor to the installation in order to
avoid moisture entering the compressor. When
the plugs are removed, it is essential to keep the
compressor in an upright position to avoid oil
spillage.
that are a potential cause of failure. Recommended brazing procedures and material, are described
on following page.
Brazing material
FRCC.PC.016.A1.22
33
APPLICATION GUIDELINES
INSTALLATION
Compressor connection
34
FRCC.PC.016.A1.22
Heat shield
APPLICATION GUIDELINES
INSTALLATION
A properly sized & type of drier is required. Important selection criteria include the driers water
content capacity, the system refrigeration capacity, and the system refrigerant charge. The drier
must be able to reach and maintain a moisture
level of 50 ppm end point dryness (EPD). Danfoss
recommends DCL (solid core) driers for the MLM
compressor (R22 with Alkylbenzene) and DML
(100% molecular sieve) driers for MLZ compressors (R404A, R507, R134a, R22) with PVE oil.
Insulation resistance must be higher than 1 megohm when measured with a 500 volt direct current
megohm tester.
In testing insulation resistance, Danfoss recommends that the system be first operated briefly to
distribute refrigerant throughout the system. Following this brief operation, retest the compressor
for insulation resistance or current leakage.
Refrigerant charging
FRCC.PC.016.A1.22
Be sure to follow all government regulations regarding refrigerant reclamation and storage.
35
APPLICATION GUIDELINES
Packaging
Compressors are packed individually in a cardboard box. They can be ordered in any quantity.
Minimum ordering quantity = 1. As far as possible,
Danfoss will ship the boxes on full pallets of 6 or 9
compressors according below table.
Single pack
Industrial pack
Packaging details
US pallets
Optimized for overseas container loading
Danfoss pallets
Optimized for overseas container loading & European storage racks
120U.
121U.
Code number
Shipped accessories
Pack type
Industrial pack
Single pack
Industrial pack
Single pack
16
9*
12
6*
Not included
Not included
Not included
Included
Not included
Included
Included
Included
Included
Included
Included
Included
Not included
Included
Not included
Included
Included
Included
Included
Included
36
FRCC.PC.016.A1.22
APPLICATION GUIDELINES
US pallet
MLM models
Danfoss palett
MLZ models
US pallet
Compressors
Model
Connections Features
variation
Single pack
Industrial pack
code 4
code 5
MLZ015
120U8058
120U8036
120U8002
120U8024
120U8057
120U8035
120U8001
120U8023
MLZ019
120U8060
120U8038
120U8004
120U8026
120U8059
120U8037
120U8003
120U8025
MLZ021
120U8062
120U8040
120U8006
120U8028
120U8061
120U8039
120U8005
120U8027
MLZ026
120U8064
120U8042
120U8008
120U8030
120U8063
120U8041
120U8007
120U8029
MLZ030
120U8066
120U8044
120U8010
120U8032
120U8065
120U8043
120U8009
120U8031
MLZ038
120U8068
120U8046
120U8012
120U8034
120U8067
120U8045
120U8011
120U8033
MLZ045
120U8048
120U8014
120U8047
120U8013
MLZ048
120U8050
120U8016
120U8049
120U8015
MLZ058
120U8052
120U8018
120U8051
120U8017
MLZ066
120U8054
120U8020
120U8053
120U8019
MLZ076
120U8056
120U8022
120U8055
120U8021
MLZ015
121U8058
121U8036
121U8002
121U8024
121U8057
121U8035
121U8001
121U8023
MLZ019
121U8060
121U8038
121U8004
121U8026
121U8059
121U8037
121U8003
121U8025
MLZ021
121U8062
121U8040
121U8006
121U8028
121U8061
121U8039
121U8005
121U8027
MLZ026
121U8064
121U8042
121U8008
121U8030
121U8063
121U8041
121U8007
121U8029
MLZ030
121U8066
121U8044
121U8010
121U8032
121U8065
121U8043
121U8009
121U8031
MLZ038
121U8068
121U8046
121U8012
121U8034
121U8067
121U8045
121U8011
121U8033
MLZ045
121U8048
121U8014
121U8047
121U8013
MLZ048
121U8050
121U8016
121U8049
121U8015
MLZ058
121U8052
121U8018
121U8051
121U8017
MLZ066
121U8054
121U8020
121U8053
121U8019
MLZ076
121U8056
121U8022
121U8055
121U8021
MLM015
120U8106
120U8072
120U8094
120U8105
120U8071
120U8093
MLM019
120U8108
120U8074
120U8096
120U8107
120U8073
120U8095
MLM021
120U8110
120U8076
120U8098
120U8109
120U8075
120U8097
MLM026
120U8112
120U8078
120U8100
120U8111
120U8077
120U8099
MLM030
120U8114
120U8080
120U8102
120U8113
120U8079
120U8101
MLM038
120U8116
120U8082
120U8104
120U8115
120U8081
120U8103
MLM045
120U8118
120U8084
120U8117
120U8083
MLM048
120U8120
120U8086
120U8119
120U8085
MLM058
120U8122
120U8088
120U8121
120U8087
MLM066
120U8124
120U8090
120U8123
120U8089
MLM076
120U8126
120U8092
120U8125
120U8091
FRCC.PC.016.A1.22
code 1
code 2
code 4
code 5
code 1
code 2
37
APPLICATION GUIDELINES
Type
Code n
Description
Application
Packaging
Pack
size
70 F
120Z0051 PSC wiring Run Capacitor 70 F, motor voltage code 5 - 220-240V / 1 / 50Hz
MLZ015-019-021-026
Multipack
10
50 F
8173233 PSC wiring Run Capacitor 50 F, motor voltage code 5 - 220-240V / 1 / 50Hz
MLZ030
Multipack
10
55 F
8173234 PSC wiring Run Capacitor 55 F, motor voltage code 5 - 220-240V / 1 / 50Hz
MLZ038-045-048
Multipack
10
Application
Packaging
Pack
size
145-175 F 120Z0399 CSR wiring Start Capacitor 145-175 F, motor voltage code 5 - 220-240V / 1 / 50Hz MLZ015-019-021-026
Multipack
10
161-193 F 120Z0040 CSR wiring Start Capacitor 161-193 F, motor voltage code 5 - 220-240V / 1 / 50Hz MLZ030
Multipack
10
88-108 F
Multipack
10
Type
Code n
Description
8173001 CSR wiring Start Capacitor 88-108 F, motor voltage code 5 - 220-240V / 1 / 50Hz
MLZ038-045-048
RVA9CKL
120Z0393 CSR wiring Starting Relay, motor voltage code 5 - 220-240V / 1 / 50Hz
MLZ015-019-021-026
Multipack
10
RVA3EKL
120Z0394 CSR wiring Starting Relay, motor voltage code 5 - 220-240V / 1 / 50Hz
MLZ030
Multipack
10
MLZ038-045-048
Multipack
10
Packaging
Pack
size
RVA4GKL 120Z0395 CSR wiring Starting Relay, motor voltage code 5 - 220-240V / 1 / 50Hz
Type
Code n
Description
Application
MLZ 015-019-021-026
Multipack
MLZ 030-038-045
Multipack
MLZ 048
Multipack
MLZ 058-066-076
Multipack
Application
Packaging
Pack
size
Multipack
10
Multipack
10
Multipack
10
10
Multipack
10
Multipack
10
Rotolock adaptor
Type
38
Code n
Description
FRCC.PC.016.A1.22
APPLICATION GUIDELINES
Crankcase heater
Type
Code No
Application
Packaging
Pack
Size
MLZ/MLM 015-019-021-026-030-038-045048-058-066-076
MLZ/MLM 015-019-021-026-030-038-045048-058-066-076
MLZ/MLM 015-019-021-026-030-038-045048-058-066-076
Multipack
Multipack
Multipack
MLZ/MLM 030-038-045-048-058-066-076
Multipack
MLZ/MLM 030-038-045-048-058-066-076
Multipack
Description
Type
Code No
Description
Application
Packaging
Pack
Size
7750009
All models
Multipack
10
7973008
All models
Industry pack
50
Packaging
Pack
Size
Single pack
Packaging
Pack
Size
Lubricant
Type
320HV
Code No
Description
Application
MLZ
Mounting hardware
Type
Code No
Description
Application
All models
Single pack
All models
Single pack
All models
Single pack
All models
Single pack
FRCC.PC.016.A1.22
39
Controls for
Commercial Refrigeration
Controls for
Industrial Refrigeration
Industrial Automation
Household Compressors
Commercial Compressors
Sub-Assemblies
Thermostats
Brazed plate
heat exchanger
We are offering a single source for one of the widest ranges of innovative refrigeration
and air conditioning components and systems in the world. And, we back technical
solutions with business solution to help your company reduce costs,
streamline processes and achieve your business goals.
Danfoss A/S www.danfoss.com