Contents
Low voltage
automatic
transfer switch
High voltage
automatic
transfer switch
F-4
F-41
Type
Standard
Model
WN
Economy
WS (New model)
WP
Rated voltage
AC600V
AC600V
AC600V
AC600V
Rated current
6300 ~ 3200A
600 ~ 3200A
63~400A
63~400A
2,3,4
2,3,4
2,3,4
2,3,4
Pole
Connection type
Transfer sequence
AB
AB
AB
A Neutral(off) B
A Neutral(off) B
A Off(pause) B
A Off(pause) B
(Pause : 3~30s)
Features
and
application
Details
F-2
F-8
F-6
F-11
F-10
TR
HV/600V
TR
HV/7.2kV
Ultra-small
HS
CTTS
VTS
AC250V
AC600V
7.2kV
100/200A
63 ~ 3200A
400, 600A
2-poles exclusive
2,3,4
Front typ
AB
AB
AB
A Neutral(off) B
A overlapping B
(Synchronizing)
Uninterruptible transfer available
In a scheduled outage by Power company
Single phase load transfer under 15kW
Ultra-small type and built-in UPS available
Built-in portable generator available
Hospital, broadcasting station, traffic signal
controller, etc.
F-5
F-12
F-42
F-3
Low voltage
Automatic Transfer
Switch
TR
24kV/600V
Contents
1. Ratings and Specifications
F 5~13
F-4
F 14
F 15
4. Caution
F 16
5. Options
F 17
F 18
7. Circuit diagram
F 19~23
F 24~39
Ratings and
Specifications
Application
and Selection
Caution
Circuit Diagram
Automatic Transfer
Switch (ATS)
Outside Drawing
Ultra-Small ATS
Ultra-Small ATS
HS type ...
2P
, 100A , 200A
Features
Power saving type
Instantaneous excitation with small operation current
(1.6A for AC 220V operation)
Safe design
Dust-free structure by mold structure applied to breaking
section ensures semi-permanent contact part.
Ultra-small size
Ultra-small size, which can be built in the portable
generator or UPS.
Low cost
Optimal for single phase load (non-inductive) under 200A.
Applied standard
JEM1465 / UL1008
Type
Rated current
Rated voltage
Pole
Connection type
Performance
Short-time withstand current (1s)kA
Short circuit peak current
Switching capacity
Endurance
Electrical
Mechanical
Switching frequency
Transfer sequence
Operating time Opening
Closing
Operating voltage and current
External dimension and weight
Weight
Caution
A
V
P
21HS
100
22HS
200
AC240
2
Front
kA
Times
Times
Times/hr
ms
ms
10
25
Closing 10Ie, breaking 8Ie, Cos=0.35
50, 000
250, 000
150(No. 4)
AB
30
60
AC220V, 1.6A
AC220V, 4.85A
165
176
127
151
100
121
kg
1.1
2.2
1) Transfer time is 0.3s or less, but operating instruction of 0.5s or more can ensure stable operation.
2) Simultaneous operating instruction for both A side and B side can lead to coil burnout.
3) Provide sufficient contact capacity well over operating current for the operation relay
Circuit diagram
Drawing
See F-21
See F-35
F-5
Automatic Transfer
Switch (ATS)
Two-coil type
Two-coil type simple operation
Ratings and
Specifications
Application
and Selection
Caution
Circuit Diagram
Outside Drawing
Standard ATS
610WS
800/1000
AC 600
3, 4
Double Throw
616WS
1250/1600
AC 600
3, 4
Double Throw
15
kA
Class
Times
Times
Time/h
22
37.5
AC3
10, 000
50, 000
150(No. 4)
35
55
AC3
10, 000
50, 000
150(No. 4)
ms
ms
ms
ms
100
30
135
30
25
50
AC3
10, 000
50, 000
150(No. 4)
A B, A Neutral(off) B
115
30
145
30
3P
4P
8
10
8
10
4
5
2
1
A
A
A
A
A
H
W
Front type
dimension
(mm)
Back type
dimension
(mm)
Weight
66WS
600/630
AC 600
3, 4
Double Throw
A
V
P
T
Front type
Back type
Other details
Circuit diagram
Time chart
Drawing
Caution
H
W
D
kg
kg
3P
7
7
3.5
4P
8
8
4
2
1
311
372
D
220
372
194
43
33
See F-19
See F-18
See F-30, 34
See F-16
(1) Switching capacity : AC3 class : Closing 10Ie, breaking 8Ie, Cos=0.35
DC1 class : Closing 1.1Ie, breaking 1.1Ie, L/R=1ms
AC2 class : Closing 4Ie, breaking 4Ie, Cos=0.65
(2) Trip : Opening of a circuit to a neutral position off from power A or power B.
F-6
311
442
131
220
442
194
51
42
575
453
131
380
453
304
56
40
See F-19
See F-18
See F-31, 34
See F-16
575
536
218
380
536
304
66
51
115
30
150
30
3P
10
10
5
4P
13
13
6.5
2
1
615
528
218
380
528
304
62
47
615
636
218
380
636
304
74
59
See F-19
See F-18
See F-32, 34
See F -16
Standard ATS
50
60
AC3
5, 000
10, 000
30(No. 5)
80
AC3
5, 000
10, 000
30(No. 5)
180
30
220
30
140
35
190
35
3P
13
13
6.5
Features
630WS
2500/3200
AC 600
3, 4
Double Throw
4P
16
16
13
3P
16
16
8
4
2
Reliable insulation
The current breaking part is completely sealed in a mold
structure to exclude the risk of electric shock by human
body contact, or electric faults due to accumulated dusts
or foreign matters on conducting parts during long-term
use.
Safe conducting performance
Safe conducting performance is maintained by constant
contact pressure for each phase. Short-circuit overcurrent
strength is high because it is protected by latch
mechanism.
High class design
This product has a one-phase structure insulated and
separated by phase, so that three- or four-phase
conducting parts can be assembled conforming to the
capacity and number of phases according to the users
convenience.
4P
18
18
9
4
2
218
380
603
316
380
736
316
580
823
388
580
1010
388
115
135
150
190
See F-19
See F-18
See F-32, 34
See F-16
One-coil type
This is a compact type in which both normal side and
standby side can be closed.
Safe opening characteristic
Semi-permanent lifetime is ensured by employing a
unique structure arc chute, with short arc breaking time
and low wear of contact. The trip operation by breaking
spring always realizes stable breaking characteristic,
regardless of operating voltage.
Neutral point type
Power source is transferred after the stability and safety
of circuit are checked, and the neutral position off
(
status) is available via the trip structure.
That is, A off A / B off B as well as A off
B / B off A, and instantaneous transfer are all
available.
See F-19
See F-18
See F-33, 34
See F-16
F-7
Automatic Transfer
Switch (ATS)
620WS
2000
AC 600
3, 4
Double Throw
Ratings and
Specifications
Application
and Selection
Caution
Circuit Diagram
Outside Drawing
Standard ATS
Front type
Back type
A
V
P
T
61WN
63/100
AC 600
2, 3, 4
Double Throw
5
kA
Class
Times
Times
Time/h
10
12.5
AC3
50, 000
250, 000
150 (No. 4)
ms
ms
ms
ms
55
20
80
20
A
A
A
A
A
H
W
D
H
W
D
kg
kg
2P
4
4
2
191
204
112
176
204
148
4.5
4.5
3P
4
4
2
1.4
0.7
4P
5
5
2.5
191
234
112
176
234
148
6
6
191
264
112
176
264
148
8
8
Other details
Circuit diagram
Time chart
Drawing
Caution
(1) Switching capacity : AC3 class : Closing 10Ie, breaking 8Ie, Cos=0.35
DC1 class : Closing 1.1Ie, breaking 1.1Ie, L/R=1ms
AC2 class : Closing 4Ie, breaking 4Ie, Cos=0.65
(2) Trip : Opening of a circuit to a neutral position off from power A or power B.
F-8
62WN
125/160/200
AC 600
2, 3, 4
Double Throw
64WN
250/400
AC 600
2, 3, 4
Double Throw
12
15
25
30
AC3
AC3
50, 000
50, 000
250, 000
250, 000
150 (No. 4)
150 (No. 4)
A B, A Neutral(off) B
55
60
20
25
80
90
20
25
2P
5
5
2.5
252
234
112
176
234
158
6
6
3P
5
5
2.5
1.4
0.7
4P
7.2
7.2
3.6
252
279
112
176
279
158
8
8
252
324
112
176
324
158
10
10
See F-19
See F-18
See F-26, 27, 29
See F-16
2P
6.4
6.4
3.2
278
280
132
224
280
216
11
11
3P
6.4
6.4
3.2
2
1
4P
9
9
4.5
278
340
132
224
340
216
14
14
278
400
132
224
400
216
18
18
66WN
600/630
AC 600
3, 4
Double Throw
610WN
800, 1000
AC 600
3, 4
Double Throw
22
37.5
AC3
10, 000
50, 000
150 (No. 4)
25
50
AC3
10, 000
50, 000
150 (No. 4)
100
30
135
30
115
30
145
30
3P
7
7
3.5
4P
8
8
4
2
3P
8
8
4
1
545
465
220
410
405
210
43
33
4P
10
10
5
2
1
545
530
220
390
470
210
51
42
609
510
220
410
450
250
56
40
See F-19
See F-18
See F-28, 29
See F-16
609
590
220
390
530
250
66
51
Standard ATS
620WN
2000
AC 600
3, 4
Double Throw
35
55
AC3
10, 000
50, 000
150 (No. 4)
50
60
AC3
5, 000
10, 000
30(No. 5)
A B, A Neutral(off) B
180
30
220
30
115
30
150
30
3P
10
10
5
2
4P
13
13
6.5
3P
13
13
6.5
80
AC3
5, 000
10, 000
30(No. 5)
140
35
190
35
3P
16
16
8
4
2
1
645
570
220
410
510
250
62
47
4P
16
16
8
630WN
2500/3200
AC 600
3, 4
Double Throw
645
670
220
390
610
250
74
59
See F-19
See F-18
See F-28, 29
See F-16
4P
18
18
9
4
2
One-coil type
This is a compact type in which both normal side and
standby side can be closed (Model utility registration No.
34781).
Neutral point type
When there is an UPS, power source is transferred after
the stability and safety of circuit are checked in case of
power failure or power restoration, instead of emergency
transfer, and the neutral position (off status) is available
via the trip structure.
That is, A off A / B off B as well as A off B / B
off A is available. As in the existing products,
instantaneous transfer is also available according to
operating instruction.
Transfer time can be arbitrarily specified via external
sequence in the WN type with neutral (Off) position to
definitely prevent the contact between the power source
and residual voltage at the load side.
Power-saving type
Power consumption is very low due to instantaneous
excitation, short-circuit current strength is high due to the
protection of contact pressure by latch mechanism, and a
unique structure arc chute facilitates short arc breaking
time and low contact wear, realizing semi-permanent
lifetime.
Diversified products
Diversified products including 600V and 63-3200A
products in series with dust-proof structure by mold are
provided. DC load switching is also available.
580
675
335
580
810
335
580
825
370
580
1000
370
115
135
150
190
See F-19
See F-18
See F-28, 29
See F-16
Features
Breaking characteristic
Trip operation by breaking spring always realizes stable
breaking characteristic regardless of operation voltage.
See F-19
See F-18
See F-28, 29
See F-16
F-9
Automatic Transfer
Switch (ATS)
616WN
1250/1600
AC 600
3, 4
Double Throw
Ratings and
Specifications
Application
and Selection
Caution
Circuit Diagram
Outside Drawing
Type
Rated current
Rated voltage
Pole
Throw
Connection type Front
Back
Performance
Short-time withstand current (1s)kA
Short circuit peak current
Switching capacity
Endurance
Electrical
Mechanica
Switching frequency
Transfer sequence
Operating time opening
closing
Closing delay (off)
Operating voltage and current
DC110V - 125V
AC100 - 120V
AC220 - 240V
External dimension and weight
Front type
dimension
(mm)
Back type
dimension
(mm)
Weight
Other details
Circuit diagram
Time chart
Drawing
Caution
61W
63/100
AC 600
2, 3, 4
Double Throw
62W
125/160/200
AC 600
2, 3, 4
Double Throw
64W
250/400
AC 600
2, 3, 4
Double Throw
5
kA
Class
Times
Times
Time/h
10
12.5
AC3
50, 000
250, 000
150 (No. 4)
5
30
AC3
50, 000
250, 000
150 (No. 4)
ms
ms
sec
4P
7.5
7.5
3.8
2P
7.5
7.5
3.8
12
25
AC3
50, 000
250, 000
150 (No. 4)
AB
60
200
3P
7.5
7.5
3.8
4P
11
11
5.5
191
264
112
176
264
148
8
252
234
112
176
234
158
6
252
279
112
176
279
158
8
252
324
112
176
324
158
10
A
V
P
T
A
A
A
2P
5.4
5.4
2.7
60
200
3P
5.4
5.4
2.7
H
W
D
H
W
D
kg
191
204
112
176
204
148
4.5
191
234
112
176
234
148
6
(1) Switching capacity : AC3 class : Closing 10Ie, breaking 8Ie, Cos=0.35
DC1 class : Closing 1.1Ie, breaking 1.1Ie, L/R=1ms
F-10
See F-21
See F-18
See F-26, 27, 29
See F-16
2P
10
10
5
60
250
3P
10
10
5
4P
12.8
12.8
6.4
278
280
132
224
280
216
11
278
340
132
224
340
216
14
278
400
132
224
400
216
18
WP type
Pause function added
A PauseB
2P
5.4
5.4
2.7
191
214
112
176
214
148
4.5
62WP
125/160/200
AC 600
2, 3, 4
Double Throw
10
12.5
AC3
50, 000
250, 000
150 (No. 4)
A B, A
60
200
0, 3~30(timer)
3P
4P
5.4
7.5
5.4
7.5
2.7
3.8
191
244
112
176
244
148
6
191
274
112
176
274
148
8
12
25
30
AC3
AC3
50, 000
50, 000
250, 000
250, 000
150 (No. 4)
150( (No. 4)
Off(pause) B, A Off(pause) B
60
60
200
200
0, 3~30(timer)
0, 3~30(timer)
2P
3P
4P
2P
3P
7.5
7.5
11
10
10
7.5
7.5
11
10
10
3.8
3.8
5.5
5
5
252
244
112
176
244
158
6
252
289
112
176
289
158
8
Features
64WP
250/400
AC 600
2, 3, 4
Double Throw
252
334
112
176
334
158
10
278
290
132
224
290
216
11
278
350
132
224
350
216
14
Safe design
Dust-proof structure at the current breaking part
provides safe operation.
For both AC/DC
Control circuit can use both AC and DC power
sources.
Single coil instantaneous excitation type
- One coil, instantaneous excitation type that saves
power consumption.
- AC 110V/240V can be available for the operating
coil.
(Refer to the manual)
4P
12.8
12.8
6.4
278
410
132
224
410
216
18
See F-20
See F-18
See F-24, 25, 29
See F-16
F-11
Automatic Transfer
Switch (ATS)
61WP
63/100
AC 600
2, 3, 4
Double Throw
Ratings and
Specifications
Application
and Selection
Caution
Circuit Diagram
Outside Drawing
A
V
P
T
Front
Back
Performance
Short-time withstand current (1s)kA
Short circuit peak current
Switching capacity
Endurance
Electrical
Mechanical
Switching frequency
Transfer sequence
Condition for uninterruptible transfer
closing
Oper Power A
trip
ating
closing
time Power B
trip
Operating voltage and current
Closing
DC110V - 125V
AC110V - 120V
AC220 - 240V
Trip
AC220 - 240V
DC110V - 125V
External dimension and weight
Front type
dimension
(mm)
D
Back type
dimension
(mm)
Weight
D
Front type
Back type
5
kA
Class
Times
Times
Time/h
61CT
63/100
AC 600
2, 3, 4
Double Throw
10
12.5
AC3
50, 000
250, 000
150 (No. 4)
62CT
125/160/200
AC 600
2, 3, 4
Double Throw
66CT
600/630
AC 600
2, 3, 4
Double Throw
610CT
800, 1000
AC 600
2, 3, 4
Double Throw
12
15
22
25
30
37.5
AC3
AC3
AC3
50, 000
50, 000
10, 000
250, 000
250, 000
50, 000
150 (No. 4)
150 (No. 4)
150( (No. 4)
A B, A Neutral(off) B, A (overlapping) B
25
50
AC3
10, 000
50, 000
150( (No. 4)
55
20
80
20
2P 3P 4P
4
4
5
4
4
5
2
2
2.5
1.4
0.7
55
20
80
20
2P 3P 4P
5
5
7
5
5
7
2.5 2.5 3.6
1.4
0.7
H
W
112
H
W
268 268
211 241
112 112
268
271
112
283
241
112
283
286
112
283
331
132
307 307
293 353
132 132
307
413
220
545
465
220
545
530
220
609
510
220
609
590
kg
kg
6.5
6.5
10
10
8
8
10
10
12
12
14
14
21
21
53
43
61
52
66
50
76
61
ms
ms
ms
ms
A
A
A
A
A
8
8
Other details
Circuit diagram
Drawing
Caution
(1) Switching capacity : AC3 class: Closing 10Ie, breaking 8Ie, Cos=0.35
DC1 class: Closing 1.1Ie, breaking 1.1Ie, L/R=1ms
AC2 class: Closing 4Ie, breaking 4Ie, Cos=0.65
(2) Trip : Opening of a circuit to a neutral position off from power A or power B.
F-12
64CT
250/400
AC 600
2, 3, 4
Double Throw
See F-22
See F-36~38
See F-16
2P
6.4
6.4
3.2
60
25
90
25
3P 4P
6.4
9
6.4
9
3.2 4.5
2
1
17
17
100
30
135
30
3P
7
7
3.5
115
30
145
30
4P
8
8
4
3P
8
8
4
2
1
4P
10
10
5
2
1
See F-22
See F-37, 39
See F-16
After simultaneous supply of normal power (A) and emergency generation power (B), this closed transition
transfer switch (CTTS) detects the differences for voltage and frequency, verifies the synchronizing condition,
and performs uninterruptible transfer automatically within 0.1s (100ms) in the direction of control.
620CT
2000
AC 600, DC125
2, 3, 4
Double Throw
630CT
2500/3200
AC 600, DC125
2, 3, 4
Double Throw
Phase difference: Electric angle 10, Frequency difference: 0.2Hz, Voltage: Difference with common voltage5%,
Instantaneous linking time: 0.05s, Voltage: Difference from common voltage5%, Instantaneous linking time: 0.05s
3P
10
10
5
180
30
220
30
4P
13
13
6.5
3P
13
13
6.5
2
1
645
570
220
72
57
140
35
190
35
4P
16
16
8
3P
16
16
8
4
2
4p
18
18
9
Transfer operations
N
4
2
600
683
329
600
818
329
600
833
364
600
1018
364
130
150
165
205
See F-22
See F-38, 39
See F-16
645
670
220
84
69
Major plants
Uninterruptible transfer to emergency generator power is
available in case of a voltage drop or power failure of
normal power source, for example by lightning, or a longterm power failure. Transfer to normal power source is
also available in an uninterruptible way.
* Uninterruptible transfers
Scheduled outage from Power company side
GeneratorPower company transfer when Power company
power supply is restored
When temporary failure is expected due to weather
conditions, etc.
When generators or equipment are to be tested.
35
50
55
60
80
AC3
AC3
AC3
10, 000
5, 000
5, 000
50, 000
10, 000
10, 000
150 (No. 4)
30(No. 5)
30(No. 5)
A B, A Neutral(off) B, A (overlapping) B
115
30
150
30
Major Uses
F-13
Automatic Transfer
Switch (ATS)
616CT
1250/1600
AC 600, DC125
2, 3, 4
Double Throw
Ratings and
Specifications
Application
and Selection
Caution
Circuit Diagram
Outside Drawing
JEM 1038
KSC 4504
UL 1008
KSC 0703
Control instruction
Closing and trip transfer operation is completed in 0.3s, but
operating instruction of 0.5s or more can ensure stable operation.
Interlock
Install the interlock (electrical) at the operation circuit so that there
can be no simultaneous instruction for power A and power B. For
WN type, set the sequence so that there can be no closing and trip
instructions in the same direction.
Operational transformer capacity
Use the capacity greater than the value calculated with the
following equation for the transformer capacity for operation circuit.
Operating voltage x Operating current x 0.5 = ( )VA
Ex) Operating voltage : AC 220V, operating current : 4A
22040.5 = 440VA
Use the transformer of 440VA or higher.
Control circuit
ATS is designed to switch off the operating current using the
internal switch after operation. Switching off the operating current
using the auxiliary switch in the main body leads to erroneous
operation.
Selection of control relay
Use the voltage relay 27 and 84 and timer with a conducting
current at the contact higher than the operating current of ATS. It
is safe to select a relay that can break the operating current,
considering chattering, etc. of control relay.
* When the operating power is unstable, please use the voltage
buildup relay.
F-14
Current
Pole
Type
HS
Connection type
4
Front
Back
100A
AC250V
200A
63, 100A
AC600V
DC125V
250, 400A
63, 100A
AC600V
DC125V
250, 400A
63, 100A
250, 400A
600, 630A
10
800, 1000A
16
1250, 1600A
20
2000A
AC600V
30
2500, 3200A
600, 630A
10
800, 1000A
AC600V
16
1250, 1600A
DC125V
20
2000A
30
2500, 3200A
63, 100A
AC600V
250, 400A
AC600V
DC125V
WP
Ultra-small
WN
WS
1250, 1600A
20
2000A
AC600V
30
2500, 3200A
Rated voltage
(600V)
Rated current
(100A)
W-Type
Pole
600, 630A
10
800, 1000A
16
6
CT
F
Standard
Standard
DC125V
Economy
Automatic Transfer
Switch (ATS)
Description
CTTS
F-15
Application
and Selection
Ratings and
Specifications
Caution
Circuit Diagram
Outside Drawing
Lower
Operating power
When there is a dropper circuit for the DC operating
power, be sure to connect the operating power of ATS
to the input of the dropper circuit.
F-16
Options
Condenser Trip Device
Automatic Transfer
Switch (ATS)
F-17
Application
and Selection
Ratings and
Specifications
Caution
Circuit Diagram
Outside Drawing
Closing instruction
at power A side
Closing instruction
at power B side
Trip instruction
at power A side
Power A side
Power B side
Main
circuit
Operating
circuit
WP Type
Power B side
Operating
instruction
Main circuit
Power A side
Operation
completed
Power B side
Operating
instruction
Power B side
Operation
completed
Main circuit
Power A side
Operating
instruction
Operation
completed
Operating
instruction
Power A side
Power B side
Power A side
Power B side
Operating
circuit
Operating
circuit
Closing coil
Closing coil
Auxiliary
switch
Auxiliary
switch
W type
Power B side
Main circuit
Power A side
Power B side
Operating
circuit
Closing
Auxiliary
switch
F-18
Operating
instruction
Power A side
Operation
completed
Operating
instruction
Power B side
Operation
completed
Power B side
Operation
completed
Circuit Diagram
WN, WS Type
Internal Circuit
Power A side
Automatic Transfer
Switch (ATS)
Power B side
Operating Circuit
In normal transfer (instantaneous transfer)
Manual
In condenser trip
F-19
Application
and Selection
Ratings and
Specifications
Caution
Circuit Diagram
Outside Drawing
Internal
Circuit
Power A side
Load
side
Operation terminal
A1 - A2: Power A side closing terminal
B1 - B2: Power B side closing terminal
T1 - T2: Timer connection terminal
Power B side
Operating
Circuit 1
Operating
Circuit 2
B Aransfer/Pause at the
neutral position
A B, B A two-way transfer/
Pause at the neutral position
TM: Timer
R: Limit resistor
27, 84: Relay Voltage relay
Load
side
Power A side
Power A side
TM: Timer
R: Limit resistor
27, 84: Relay Voltage relay
Power A side operating power
Load
side
Power B side
Power B side
Caution
For temporary pause at the neutral position, connect the
timer and limit resistor to terminals T1 and T2.
Limit resistor
Type
Operating voltage
Timer
61WP~62WP
64WP
AC110-120V AC220-240V AC110-120V AC220-240V
Select a timer that can break the operating current.
Adjusted time of timer
3sec ~ 30sec
200W
200W
200
50
F-20
Rated power
Resistance
200W
50
200W
200
Circuit diagram
W type
Internal Circuit
Power A side
Load
side
Xa1-Xa2
:
Xb1-Xb2 Control switch
CC: Closing coil
Si: Silicon rectifier
Automatic Transfer
Switch (ATS)
Operation terminal
A1 - A2: Power A side closing terminal
B1 - B2: Power B side closing terminal
AUX: Auxiliary switch
Power B side
Operating
Circuit 1
In normal transfer
(instantaneous transfer)
Operating
Circuit 2
Automatic
Manual
HS type
Control
Circuit diagram
Load
side
Power A side
Power B side
F-21
Ratings and
Specifications
Application
and Selection
Caution
Circuit Diagram
Outside Drawing
Power
failure
Failure
verification timer
Generator
operation
B Line level
Voltage buildup
Generator
operation
Restoration
verification timer
CTTS
generator side On
CTTS
normal side Off
Supply with
generator power
Overlap
CTTS
Transfer
generator side
Off
operation
Overlapping time: about 50-100ms
Same phase
check
Supply with
normal power
A Line level
Voltage buildup
Operating
Circuit
Normal power
Generator power
External
control
Alarm
signal
Big
failure
Load
transfer
signal
Speed
H/L
Contro
l signal
Voltage
H/L
Control
signal
Control
part
Operation
Indication/Alarm
Operating panel
CTTS
control partl
Normal
operating coil
Operating relay
UNIT Control unit
F-22
Generator
operating coil
Internal Circuit
Automatic Transfer
Switch (ATS)
A1, A2
AT1, AT2
ATS1, ATS2
BTS1, BTS2
AUX1, 2
AX, BX
B1, B2
BT1, BT2
C
COM
CTTS
E1, E2, E3
NO
NC
N1, N2, N3
S1A, S1B, S1C
S2A, S2B
S3A, S3B, S3C
TC
T1, T2, T3
: Closed : Open
Utility side
Switch position
COM - NC
Aux. 1
COM - NO
Standby side
Aux. 2
Utility closed
COM - NO
Neutral
Utility open
Neutral
Standby closed
F-23
Application
and Selection
Ratings and
Specifications
Caution
Circuit Diagram
Outside Drawing
A
214
244
274
B
113
143
173
62WP
Front Connection
A
244
289
334
B
143
188
233
64WP
Front Connection
A
290
350
410
B
174
234
294
F-24
Auxiliary switch
Transfer indicator
Outside Drawing
WP Type
61WP
Back connection
Automatic Transfer
Switch (ATS)
A
214
244
274
B
113
143
173
62WP
Back Connection
A
244
289
334
B
143
188
233
64WP
Back Connection
A
290
350
410
B
174
234
294
Auxiliary switch
Transfer indicator
F-25
Ratings and
Specifications
Application
and Selection
Caution
Circuit Diagram
Outside Drawing
A
204
234
264
B
103
133
163
62WN, 62W
Front Connection
A
234
279
324
B
133
178
223
64WN, 64W
Front Connection
A
280
340
400
B
164
224
284
F-26
Auxiliary switch
Transfer indicator
Outside Drawing
WN, W Type
61WN, 61W
Back Connection
Automatic Transfer
Switch (ATS)
A
204
234
264
B
103
133
163
62WN, 62W
Back Connection
A
234
279
324
B
133
178
223
64WN, 64W
Back Connection
A
280
340
400
B
164
224
284
Auxiliary switch
Transfer indicator
F-27
Ratings and
Specifications
Application
and Selection
Caution
Circuit Diagram
Outside Drawing
200V
600V
S1
45mm
90mm
S2
430mm
450mm
66WN - 616WN
Front Connection
Type 66WN 68WN 610WN 612WN 616WN
3P 465
510
570
4P 530
590
670
3P 435
480
540
B
4P 500
560
640
C
545
608.5
645
G
10
12
15
I
95.7
101.6
112.4
J
65
80
100
L
73
91
111
M
15
15
15
N
68
79.5
109
Q
44
78
65
R
65
74
76
S
55
55
57
A
200V
600V
S1
45mm
90mm
S2
430mm
450mm
620/630WN
Back Connection
Type
3P
4P
3P
B
4P
E
F
G
H
I
J
L
A
620WN
675
810
635
770
119
132.5
15
15
121
135
90
630WN
825
1000
785
970
114
130
20
20
146
185
125
200V
600V
S1
S2
50mm 560mm
100mm 600mm
* Earth terminal is mounted at the right side of operating circuit terminal support.
F-28
Auxiliary switch
Transfer indicator
W, WN-Type
WP-Type
64W, WN
164
224
284
200
M8
Type 606-61WP
62WP
2P
113
143
B 3P
143
188
4P
173
233
D
152
152
R
M5
Automatic Transfer
Switch (ATS)
64WP
174
234
294
200
M8
Back Connection
W, WN-Type
WP-Type
64W, WN
164
224
284
200
135
195
255
180
9
M8
Type 606-61WP
62WP
2P
113
143
B 3P
143
188
4P
173
233
D
152
152
2P
85
110
P 3P
115
155
4P
145
200
Q
140
T
7.5
R
M5
64WP
174
234
294
200
135
195
255
180
9
M8
66-616WN
Front Connection
Type
3P
B
4P
I
Y
66-620WN
630WN(3P)
630WN(4P)
66WN
435
500
360
M12
Back Connection
4-M12 Bolt mounting hole
Type 66WN
3P 365
B
4P 440
I
360
3P 335
J
4P 400
K
330
L
20
Z
-
F-29
Ratings and
Specifications
Application
and Selection
Caution
Circuit Diagram
Outside Drawing
3P
371.2
360.7
254
4P
441.2
430.7
324
200V
600V
S1
45mm
90mm
S2
226mm
226mm
66S
Back Connection
A
B
C
3P
371.2
360.7
254
4P
441.2
430.7
324
200V
600V
S1
45mm
90mm
S2
226mm
226mm
F-30
Auxiliary switch
Transfer indicator
Outside Drawing
S Type
610W
Front Connection
3P
166
333
452.7
6
12
4P
249
416
535.7
8
16
Automatic Transfer
Switch (ATS)
A
B
C
D
E
610S
Back Connection
A
B
C
D
3P
333
452.7
166
18
4P
416
535.7
243
24
Auxiliary switch
Transfer indicator
F-31
Ratings and
Specifications
Application
and Selection
Caution
Circuit Diagram
Outside Drawing
3P
216
408
527.7
18
4P
324
516
635.7
24
616/620WS
Back Connection
3P
108
216
88.5
85.8
304
408
527.7
307.4
75
12
20
40
40
36
14
616WS
4P
108
324
88.5
85.8
304
516
635.7
307.4
75
12
20
40
40
48
14
620WS
3P
4P
133
133
266
399
100
100
97.8
97.8
316
316
483
616
602.7
735.7
294.4
294.4
100
100
15
15
28.8
28.8
44.4
44.4
44.4
44.4
36
48
14.5
14.5
F-32
Classifi
cation
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
Auxiliary switch
Transfer indicator
4P
1010
970
485
6
72
Automatic Transfer
Switch (ATS)
A
B
C
D
E
Auxiliary switch
Transfer indicator
F-33
Ratings and
Specifications
Application
and Selection
Caution
Circuit Diagram
Outside Drawing
Classification
A
B
C
D
E
F
G
H
I
F-34
3P
4P
3P
4P
3P
4P
-
Front
200
200
254
324
200
3
9
600A
Back
200
200
254
324
200
209
279
14
180
3
9
1000A
Front
Back
349.4
349.4
349.4
349.4
333
333
416
416
349.4
349.4
264.5
347.5
28.5
380
4
4
14
14
600A
Front
Back
349.4
349.4
349.4
349.4
408
408
516
516
349.4
349.4
339.5
447.5
28.5
390
4
4
14
14
2000A
Front
Back
349.4
349.4
483
616
349.4
414.5
547.5
28.5
390
4
14
3000A
Back
548
548
785
970
545.2
730
40
6
14
Automatic Transfer
Switch (ATS)
Parts Name
A Operating circuit terminal
B Operating circuit terminal
A power source side main circuit terminal
Loading side main circuit terminal
B power source side main circuit terminal
Manual operating lever
F
Bus dimension
22HS
Parts Name
A Operating circuit terminal
B Operating circuit terminal
A power source side main circuit terminal
Loading side main circuit terminal
B power source side main circuit terminal
Manual operating lever
Bus dimension
F-35
Ratings and
Specifications
Application
and Selection
Caution
Circuit Diagram
Outside Drawing
A
210.8
240.8
270.8
B
199.8
229.8
259.8
62CT
Front Connection
The arc space dimension (S1) is
30mm for a main circuit voltage
of 220V, and 60mm for 600V.
2P
3P
4P
A
240.8
285.8
330.8
B
229.8
274.8
319.8
F-36
Transfer indicator
Auxiliary switch
64CT
Front Connection
The arc space dimension (S1) is
30mm for a main circuit voltage
of 220V, and 60mm for 600V.
A
292.5
352.5
412.5
2P
3P
4P
B
278.5
338.5
398.5
Automatic Transfer
Switch (ATS)
F
Manual operation hole
Power A side main circuit terminal
Transfer indicator
Auxiliary switch
66-616CT
Front Connection
Arc space dimension
dimensions
200V
600V
Type
3P
4P
3P
B
4P
C
G
I
J
L
M
N
Q
R
S
A
A
25mm
90mm
B
430mm
450mm
Auxiliary switch
Transfer indicator
F-37
Application
and Selection
Ratings and
Specifications
Caution
Circuit Diagram
Outside Drawing
S2
560
600
Type
2000A
3P
683
4P 818
3P
645
B
4P 780
E
128.5
F
132.5
G
15
H
15
I
123
J
135
L
90
3000A
833
1018
795
980
126
130
20
20
148
185
125
200V
600V
Type
2P
A 3P
4P
B
C
R
F-38
100A
199.8
229.8
259.8
200A
229.5
274.8
319.8
152
76
M5
400A
278.5
338.5
398.5
200
100
M8
Auxiliary switch
Transfer indicator
F
Type
2P
3P
I
600A
435
500
360
800A
1000A 1200A
480
560
360
1600A
540
640
360
620-630CT
Back Connection
Mounting hole
Type 2000A
2P 645
3P 780
I
568
3P 420
J
4P 555
K
460
L
28
Z
B
Mounting hole
3000A
795
980
568
545
730
460
40
490
F-39
High-Voltage Vacuum
T r a n s f e r S w i t c h( V T S)
TR
24/7.2kV
Contents
1. Ratings and Specifications
F 42
F 44
3. Circuit Diagram
F 46
4. Outside Drawing
F 48
Ratings and
Specifications
Circuit Diagram
Outside Drawing
Features
Built-in electrical/mechanical interlock.
Interlock at the transfer part prevents erroneous
operation. Design is easy without having to consider
external electrical/mechanical interlock.
Long lifetime
The vacuum interrupter employed at the switching part
has 20 years or more vacuum lifetime, with very little
contact wear.
Easy maintenance
This VTS is draw-out type for which maintenance is easy,
and has open type mold insulation barrier for easy
cleaning. Transfer operation is instantaneous excitation
type, and electric power is consumed only at the transfer
operation.
Multiple stage installation available
Panel width can be reduced in comparison to fixed type
products. This product also allows other multiple-stage
high voltage devices to be installed. It is light-weight for
easy handling.
VTS
2 breakers
Product price
Medium pric
Low price
High price
Low price
High price
High price
Low price
High price
Medium pric
Low price
Medium pric
High price
Installation
price
Maintenance
cost
Total
F-42
High-Voltage Vacuum
Transfer Switch (VTS)
VITZROTECH vacuum transfer switch provides excellent insulating performance by using vacuum
interrupter and BMC barrier, and is equipped with electrical and mechanical interlock and
overcurrent lock to prevent accidents by breaking failure in case of short circuit and overcurrent
conduction.
Applied Facilities
Type
Rated current
Rated voltage
Pole
Performance
Short-time withstand current (1s)kA
Rated making current
Lock current
Endurance Rated current switching
No-load switching
Transfer sequence
Main circuit-earth
Power
frequency Between main circuits (two-phase)
withstand etween main circuits (one-phase)
voltage Control circuit-earth
Impulse Main circuit-earth
withstand Between main circuits (two-phase)
voltage Between main circuits (one-phase)
Operation type
Operating power Closing
Trip)
Control
External dimension and weight
Weight
Fixed
Draw-out
Dimension(mm)
Fixed
Draw-out
A
kV
P
VTS-6N6
VTS-6N6E
600
7.2
3
12.5
kA
A
Times
Times
31.5
2500
10, 000
10, 000
A off(trip) B
22
22
35
2
60
60
70
Magnetic operation (Instantaneous energized type)
DC 100/110V, 30A or less
DC 100/110V, 5A or less
DC 100/110V, 0.3A or less
kV
kV
kV
kV
kV
kV
kV
kg
kg
H
W
D
Reference standard
VTS-6N4
VTS-6N4E
400
High-Voltage Vacuum
Transfer Switch (VTS)
120
140
Fixed
585
530
700
130
150
Draw-out
545
592
870
Fixed
585
530
700
JIS C4605
Draw-out
545
592
870
F-43
Ratings and
Specifications
Circuit Diagram
Outside Drawing
Switch
Breaker
Contactor Switch
35kV
35kV
22kV
16kV
22kV
22kV
22kV
16kV
22kV
22kV
22kV
16kV
70kV
70kV
60kV
N/A
60kV
60kV
60kV
45kV
60kV
60kV
60kV
45k
(Lock in case of
exceeding the breaking
current of switch)
(Max. 4.4A)
Withstand voltage
performance
F-44
(Max. 4.4A)
High-Voltage Vacuum
Transfer Switch (VTS)
For high-voltage power transfer (two-line supply, normal-standby/normal-generator), the designer is highly responsible for
selecting methods and devices because there is no unified regulation on the circuit and devices.
Fig. 1 is a representative power transfer single line diagram. By examining this circuit considering theHigh-voltage receiving
facility guide, a risk can be recognized if a switch equipped with disconnecting capacity is not applied to normal (A) normal
(B) transfer or normal generator transfer.
High-Voltage Vacuum
Transfer Switch (VTS)
Disconnection available
if a switch is used at the
section point
F
Disconnection available if a switch
is used at the section point
Disconnection available if a
switch is used at the section
point
Normal
DS: Disconnecting switch
G
52: Breaker
42D: VTS
F-45
Ratings and
Specifications
Circuit Diagram
Outside Drawing
10s
10s
10s
10s
10s
10s
Outage check
DE automatic start
7min
Restoration check
10s
Re-interruption within
3 minutes after
closing of 52R
10s
start
In case of re-interruption exceeding 3 minutes after closing of 52R: the same
operation as in usual normal side outage (See Fig. 3).
Normal
Spare
[Condition]
With normal power-priority circuit
Only after 3 or more minutesfeeding from standby line can the normal power be restored.
The same condition is applied to the transfer to standby line.
(52R)
(OFF)
42D(B)
(OFF)
42D(A)
(ON)
(52R)
(ON)
F-46
(52R)
(OFF)
42D(B)
(OFF)
42D(A)
(ON)
(52R)
(ON)
High-Voltage Vacuum
Transfer Switch (VTS)
* 1: CR S/A
* 2: ZNR S/A
Normal
Dry-type
transformer
*2
Motor
KMSA-3.6
KMSA-7.2
Rated voltage
kV
3.3
6.6
kV
3.6
7.2
kV
9~10
18~20
Discharge voltage
kV
13
26
kA
40
40
Hz
60
60
Weight
kg
0.41
0.6
F-47
High-Voltage Vacuum
Transfer Switch (VTS)
Ratings and
Specifications
Circuit Diagram
Outside Drawing
Name.
CC: Closing Coil
TC: Trip Coil
AUX: Auxiliary switch
CR: Closing control Relay
XR: Interlock Relay
Ma: Check Switch
IL: Interlock contact (Draw-out type)
OCL: Overcurrent lock contact
F-48
Auxiliary switch
Trip circuit
Auxiliary switch
* When a transformer for operation is used at the operating power, connect the indicator lamp at AC side.
power A side
power B side
High-Voltage Vacuum
Transfer Switch (VTS)
Outside Drawing
Fixed Type (N)
Input terminal
High-Voltage Vacuum
Transfer Switch (VTS)
Rating
Individual barrier
Combined barrier
A
275
295
B
145
125
Difference
Epoxy barrier
BMC barrie
Operating position
Testing and disconnecting position
Support insulator
Interlock Guide
Main circuit
disconnecting switch
Main circuit terminal
Stop Bar
Earth contact
Load side
Mounting hole
7(Earthing)
F-49