Sunteți pe pagina 1din 8

CORRIG DES EXERCICES TIRS DE LEXAMEN PARTIEL A2003

Problme no. 1

a) On divise le rseau en trois zones:


G1
750 MVA
13.8 kV
X

g = 0.2 pu

T1

B1

B2

Ligne 1
345 kV, 200 km
Z = (6.4 + j70)

750 MVA
13.8kV / 345kV Y

Zeq1

Zone 1

B4

M1

500 MVA
15 kV
X

-4 S

1000 MVA
345kV Y / 15kV

Y = j4.2 x 10

= (0.01 + j0.16) pu

T2

B3

eq2

m = 0.2 pu

150 MW
80 Mvar

= (0.01 + j0.16) pu

Zone 3

Zone 2

On choisit Sbase3 = 100 MVA et VbaseLL = 13.8 kV (ct gnrateur)


Zone 1:

Zone 2:

Zone 3:

VbaseLL1 = 13.8 kV
I base1 = 100 ( 3 13.8 )

= 4.184 kA

Z base1 = ( 13.8 )

I base2 = 100 ( 3 345 ) = 0.167 kA

Z base2 = ( 345 )

Z base3 = ( 15 )

100

100

= 1.90

100

= 1190.3

VbaseLL2 = 345 kV
VbaseLL3 = 15 kV
I base3 = 100 ( 3 15 ) = 3.849 kA

Limpdance en pu du gnrateur:
13.8 2 100
X Gpu = 0.2 ---------- --------- = 0.0267 pu
13.8
750
Limpdance en pu du moteur:
15 2 100
X Mpu = 0.2 ------ --------- = 0.04 pu
15
500
Limpdance en pu du transformateur T1:
13.8 2 100
Z eq1pu = ( 0.01 + j0.16 ) ---------- --------- = 0.0013 + j0.0213 pu
13.8
750
Limpdance en pu du transformateur T2:
15 2
100
Z eq2pu = ( 0.01 + j0.16 ) ------ ------------ = 0.001 + j0.016 pu
15
1000
Limpdance srie en pu de la ligne 1:
( 6.4 + j70 )
Z pu = ------------------------------- = 0.0054 + j0.0588 pu
1190.3
Limpdance en pu de la charge ( la barre B4):
2
2
(-----------14 )
(
14 )
- + j ------------150
80
Z ch = ----------------------------------------- = ( 0.581 + j1.089 ) pu
2.25

= 2.25

page

j0.0267 B1

T1

B2

0.0013 + j0.0213

+
Eg
-

Ligne 1

B3

T2

B4

j0.04

0.0054 + j0.0588 0.0010 + j0.0160


0.581 + j1.089

Gnrateur

Em

Charge Moteur

b) Les tensions ligne-neutre de la source 600 V, 60 Hz sont:


=
V
V bn = 346.4 120 V
V cn = 346.4 120 V
an
Car la ligne neutre est connecte, on a trois circuits indpendants pour les trois phases. Les
courants de ligne sont calculs:
V an 346.4 0
I = -------- = ------------------------ = 34.64 0 A
V

346.4

10

10

V bn 346.4 120
= --------------------------------- = 28.867 150 A
I b = --------j12
12 90
V cn
346.4 120
- = ------------------------------ = 23.09 150 A
I c = ---------j15
15 90

Les composantes de squence (composantes symtriques) des courants de ligne Ia, Ib, Ic sont
donnes par:
1
I 0 = --- [ I a + I b + I c ]
3
1
I 0 = --- [ 34.64 0 + 28.867 150 + 23.09 150 ] = 3.452 + j0.963 = 3.584 164.4 A
3
2
1
I 1 = --- [ I a + aI b + a I c ]
3

avec a

= e

j 2 3

1
I 1 = --- [ 34.64 0 + 28.867 270 + 23.09 90 ] = 11.547 j1.926 = 11.706 9.5
3
1
2
I 2 = --- [ I a + a I b + aI c ]
3

avec a

= e

j 2 3

1
I 1 = --- [ 34.64 0 + 28.867 30 + 23.09 30 ] = 26.545 + 0.963 = 26.563 2.0 A
3

page

Problme no. 2

a) Conducteur ACSR Martin 54/19, r = 1.8085 cm, GMR = 1.46 cm, R (50C) = 0.0502 /km
Le rayon moyen gomtrique des faisceaux:
d2 = 3 1.46 502 = 15.3968 cm
La ligne est transpose. La distance moyenne gomtrique des conducteurs:
3 D D 2D = 3 10 10 20 = 12.60 m
GMD =
Linductance srie (squence directe) par km:
0 GM D
7
4
---1260
3
L = ------ ln ---------------------------------------------- 10 = 8.8094 10
H/km
1
GMRfaisceau = 210 ln -15.3968

2
La ractance srie (squence directe) par km:
4
= 0.3321 /km
X = L = 120 8.8094 10
1
1
Chaque faisceau contient 3 conducteurs dont la rsistance 50C est 0.0502 /km. La
rsistance srie R de la ligne est donc:
GMR

faisceau

GMR

cond

/km
b) Conducteur ACSR Martin 54/19, r = 1.8085 cm, GMR = 1.46 cm
Le rayon moyen gomtrique des faisceaux (pour le calcul des capacits):
R

0.0502
= ---------------- = 0.0167
3

d 2 = 3 1.8085 502 = 16.5356 cm


La distance moyenne gomtrique des conducteurs:
3 D D 2D = 3 10 10 20 = 12.60 m
GMD =
La capacit shunt (squence directe) par km:
12
2
8
2 8.854 10
0
F/km
C = ------------------------------------------- 1000 = ------------------------------------------- 1000 = 1.2838 10
1
GMD
1260

ln -------------------------------ln ------------------ GMRfai sceau


16.5356
Ladmittance shunt (squence directe) par km:
8
6
S/km.
Y = C = 120 1.2838 10
= 4.8398 10
1
1
c) Avec V = (500/1.732) kV = 288.68 kV, la charge lectrique (par m) sur un faisceau est:
C V
( 1.2838 108 ) ( 288.68 103 )
6
1 1
C/m
q = ------------- = --------------------------------------------------------------------- = 3.706 10
GMR

faisceau

1000

1000

Le faisceau contient 3 conducteurs. La charge sur un conducteur sera

6
q
-- = 1.2354 10
3

C/m.

page

q/3
d = 0.5 m

d = 0.5 m

q/3

q/3
d = 0.5 m

Le champ lectrique la surface dun conducteur est la somme vectorielle des champs lectriques
crs par les trois conducteurs du faisceau:
( q 3)
r
E rmax = -------------- 1 + 3 --20 r
d
6
1.8085
1.2354 10
- 1 + 3 ---------------- = 13048
E rmax = ---------------------------------------------------------12
50
2 ( 8.854 10 )1.8085

V/cm

kV/cm
On peut remarquer que la contribution des deux autres conducteurs est ngligeable cause de la
grande distance entre les conducteurs (d = 50 cm) par rapport au rayon du conducteur (r =
1.8085 cm)
E rmax = 13.048

page

Problme no. 3

a) Modle de ligne moyenne (circuit quivalent en pi nominal):


IS

IR

VS

Paramtres de transmission (ABCD):

+
Y/2

Y/2

A = D = 1 + YZ
------2-

VR

B=Z

C = Y 1 + YZ
------4 -

Z = z l = ( 0.088 + j0.465 ) 250 = 22 + j116.25 = 118.31 79.3


On a:
Y = y l = ( j3.524 106 ) 250 = j0.881 103 S
et
Les paramtres de transmission (ABCD) sont:

3
( j0.881 10 ) ( 22 + j116.25 )
------1
A = D = 1 + YZ
=
+
---------------------------------------------------------------------- = 0.9488 + j0.0097 = 0.9488 0.6
2
2

B = Z = 22 + j116.25 = 118.31 79.3

j0.881 10 3 ) ( 22 + j116.25 )- = 4.269 106 + j8.584 10 4 S


= j0.881 103 1 + (---------------------------------------------------------------------C = Y 1 + YZ
------

4
4

Remarque: On peut ngliger la partie relle de C:


a) La tension la charge:
Le courant la charge:
La tension la source:

C j8.584 104

--------- = 115.47 0 kV
V R = 200
3
3
200 3
I R = 200
--------------V R - = --------------115.47- = 0.577 0 kA

V S = AV R + BI R = ( 0.9488 0.6 ) ( 115.47 0 ) + ( 118.31 79.3 ) ( 0.577 0 )


V S = 140 29.2 V
ou 242.5 kV ligne-ligne

Le courant la source:

I S = CV R + DI R = ( j8.584 104 ) ( 115.47 0 ) + ( 0.9488 0.6 ) ( 0.577 0 )


I S = 0.558 10.8 kA
VS
140 - = 147.55 kV (ou 255.57 kV ligne-ligne)
b) Tension vide de la ligne:
V RNL = --------=
--------------A
0.9488

La ligne est ouverte (sans charge). La tension VR monte 255.57 kV.


IS

On connecte au bout de la charge une


ractance shunt pour ramener la tension
VR 230 kV.

IR

+
VS
-

Y/2

Y/2

VR

jXL

page

La tension V

R dsire:

V R = 132.79 0

On a:

V S = 140 s
On a la relation suivante:

V R = 230 3 = 132.79 kV
V R 132.79 0
132.79

et
I R = -------=
-------------------------=

j
--------------jX L
X L -
jX L
132.79- = 140
V S = AV R + BI R = A ( 132.79 ) + B j --------------s
X
L

132.79- = 140
( 0.9488 + j0.0097 )( 132.79) + ( 22 + j116.25 ) j --------------s
X
L

On dduit:

2921.4- = 140
15437- j --------------( 125.99 + j1.29 ) + -------------s
X
X

Ou bien:

15437- + j 1.29 2921.4


125.99 + -------------
--------------
X L - = 140 s
XL

15437- 2 + 1.29 2921.4


125.99 + ------------- 2 = 140
--------------

XL
XL
15437- 2 + 1.29 2921.4
125.99 + ------------- 2 = ( 140 )2
--------------
XL
XL
3.725 103 X 2L + 3.882 106 X L + 2.4684 108 = 0
Solution:

L = 1102

c) Considrons le cas o V

S = 1.0 pu, VR = 0.95 pu, max = 35 et fp =1.0.

La puissance transportable par la ligne est donne par la relation suivante:

A VR 2
VS VR
P R = -------------------------Z - cos ( Z ) -------------------------Z - cos ( Z A )

230 0.95- cos ( 79.3 35 ) 0.9488


( 230 0.95 )2- cos ( 79.3 0.6 )
---------------------------------------------------------------------------------------------P R = 230
118.31
118.31
P R = 304 75 = 229 MW

page

Problme no. 4
a)

La nature des barres du rseau:


Barre B1 (barre de rfrence)

V 1 = 1.0 pu

Barre B2 (barre de charge)

P 2 = 0 pu

Q 2 = 0 pu

calculer: V2 et

Barre B3 (barre de gnration)

V 3 = 1.05 pu

P 3 = 4.0 pu

calculer:

Barre B4 (barre de charge)

P 4 = 0 pu

Q 4 = 0 pu

calculer: V4 et

Barre B5 (barre de charge)

P 5 = 4.0 pu

Q 5 = 1.0 pu

calculer: V5 et

Barre B6 (barre de charge)

P 6 = 3.0 pu

Q 6 = 1.0 pu

calculer: V6 et

b) Rseau quivalent:

B1

B2

calculer: P 1 et Q1

= 0

B5

0.0054+j0.0588

0.002+j0.032
j0.5

j0.5

et Q 3

0.0054+j0.0588
j0.5

B6

j0.5

j0.5

0.0054+j0.0588

B4

j0.5

0.0013+j0.0214
B3

Y11 Y 12
Y 12 Y 22

La matrice Ybus:

0
0
0
0

0 Y 25 0

Y33 Y 34 0 0
0 Y 34 Y 44 Y 45 0
Y 25 0 Y 45 Y 55 Y 56
0 0 0 Y 56 Y 66
0

Les lments non-nuls sont donns:


1
Y 11 = ----------------------------------0.002 + j0.032

1
Y 12 = Y 21 = ----------------------------------0.002 + j0.032

1
1
Y 22 = ----------------------------------- + ----------------------------------------- + j0.5
0.002 + j0.032 0.0054 + j0.0588

1
Y 25 = Y 52 = ----------------------------------------0.0054 + j0.0588

1
Y 33 = ----------------------------------------0.0013 + j0.0214

1
Y 34 = Y 43 = ----------------------------------------0.0013 + j0.0214

page

1
1
Y 44 = ----------------------------------------- + ----------------------------------------- + j0.5
0.0013 + j0.0214 0.0054 + j0.0588

1
Y 45 = Y 54 = ----------------------------------------0.0054 + j0.0588

1
1
1
Y 55 = ----------------------------------------- + ----------------------------------------- + ----------------------------------------- + j0.5 + j0.5 + j0.5
0.0054 + j0.0588 0.0054 + j0.0588 0.0054 + j0.0588
1
Y 56 = Y 65 = ----------------------------------------0.0054 + j0.0588
1
Y 66 = ----------------------------------------- + j0.5
0.0054 + j0.0588

c) Commentaires sur les rsultats de calcul de logiciel PowerWorld:


- Les tensions aux barres sont dans les limites acceptables (0.95, 1.05) except les barres B5 et
B6 o les tensions sont de 0.89 pu et 0.79 pu respectivement.
- Les transformateurs fonctionnent dans les limites permises.
- Les lignes fonctionnent dans les limites permises.
La ligne no. 1 est sous utilise (elle transport 37.5% de sa capacit)
La ligne no. 2 est sous utilise (elle transport 36.7% de sa capacit)
La ligne no. 3 est sous utilise (elle transport 47.7% de sa capacit)
Les pertes dans les quipements:
Transformateur T1 : 2.46 MW
Transformateur T2 : 2.36 MW
Ligne 1 : 7.17 MW
Ligne 2 : 8.17 MW
Ligne 3 : 10.81 MW
Les problmes et solutions
1) La tension la barre B5 (0.89 pu) est infrieure la valeur acceptable 0.95. On peut connecter
cette barre un banc de condensateurs afin daugmenter la tension.
2) La tension la barre B6 (0.79 pu) est infrieure la valeur acceptable 0.95. On peut connecter
cette barre un banc de condensateurs afin daugmenter la tension.

page

S-ar putea să vă placă și