Documente Academic
Documente Profesional
Documente Cultură
Review
a r t i c l e
i n f o
Article history:
Received 7 May 2013
Received in revised form
15 September 2013
Accepted 24 September 2013
Keywords:
Series compensated line protection
TCSC
Fault location
Fault classication
a b s t r a c t
In the present-day scenario, per-capita power consumption symbolizes the development of any society.
This has resulted in a multifold increase in power demand. This drives power engineers to generate and
transfer maximum possible power through transmission line, i.e. up to thermal limits, which leads toward
installation of compensating devices. However, this inclusion of compensation introduces changes in system parameters, i.e. in its impedance seen from relay point, voltage and current inversion, introduction of
sub-harmonic frequency components, etc. This requires changes in existing protection concepts. Therefore, there is a need to track all experiences, developments and research in the eld of protection of
series compensated transmission line and look for the gaps in it. This paper gives bibliographical survey
and general backgrounds of research and development in the eld of series compensated lines (xed
capacitor and TCSC) since the application of series compensation. This article also compares and evaluates different techniques with their relative advantages and disadvantages to lead toward optimum
technique for application. More emphasis is given to modern techniques. The literature is divided into
parts to reduce the difculty for new researchers to evaluate different techniques with a set of references
of all concerned contributions.
2013 Elsevier B.V. All rights reserved.
Contents
1.
2.
3.
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Series compensation impact on transmission line protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
94
2.1.
Change in line impedance seen by relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
2.2.
Over voltage protection of series capacitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
2.3.
Voltage and current inversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
2.4.
Series compensator generated transient issues . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
2.5.
Unbalanced line impedance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
2.6.
Parallel lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
2.7.
Faults in capacitor bank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
2.8.
Problems with controlled series compensation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
97
2.8.1.
Capacitive boost mode without MOV conduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
98
2.8.2.
Capacitive boost mode with MOV conduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
2.8.3.
Blocking mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
2.8.4.
TCSC bypass operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
2.8.5.
Circuit breaker bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Series compensated transmission line protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
3.1.
Multiple relay characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
99
3.2.
Compensator modeling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
94
3.3.
3.4.
4.
5.
6.
1. Introduction
To switch from protection of an uncompensated transmission line to a transmission line with series compensation is
considered to be a difcult task for protection engineers, as it
needs to be adapted to the changes introduced by compensation
devices.
With sustainable growth in power demand, the size of the power
system is continuously increasing; it has become the most complex
system ever built. A large amount of money is spent for development of the power system right from generation of power to
transmission and distribution; thus proper protection system is a
must for every power apparatus [1,2].
Continuous increase in power demand leads fast development
in transmission system, and requirement of power transfer up to
the thermal limit of the transmission line. This will lead to installation of series compensation on long Extra-High Voltage (EHV)
transmission lines. The series compensation not only increases
power transferring capacity, but also improves system transient
stability, voltage control, power ow control and will reduce losses.
Two main types of series compensation used are xed capacitor
series compensation and controllable capacitor series compensation, each with their own advantages [3]. Two different line
congurations are used in practice according to position of the
compensating device on the circuit; end-line compensation and
mid-line compensation.
To take full advantage of the series capacitor installation in
a utility network, it is necessary to understand the impact of
series compensation on protection to design appropriate schemes
with necessary changes. As mentioned earlier compensation in a
transmission system is normally introduced for high-power EHV
transmission line, which usually employs distance relay for protection purpose. A distance relay works on real time impedance
calculation of the line with real time measurements aided with
fault type information. In case of series compensated transmission
line, inclusion of compensating device affects the line impedance.
Therefore, the position of fault with respect to the compensator
(fault zone) is required for a distance relay to accomplish its overall decision. Faulted phase selection also increases system stability
and availability by allowing single pole tripping. This will improve
transient stability and reduces switching overvoltage in the system
[4].
Therefore, the fault type classication and fault zone identication are very important aspects for protection of series
compensated transmission line. Research efforts toward fault
analysis have been evaluated in Section 3. With the help of
this information, contributions toward fault location are analyzed in Section 4. Moreover, Section 2 investigates briey,
the effect of series compensation on transmission line protection.
100
100
101
101
101
102
102
103
103
103
105
106
107
95
(a)
(b)
Fig. 1. Change in impedance as seen from relay.
96
400
Left side of Compensator
300
Voltage (kV)
200
100
0
-100
-200
-300
-400
3,500
0.2
0.25
0.3
Time (Sec)
Fig. 4. Circuit condition and waveforms for a case of voltage inversion.
1
=f
2 LC
XC
XL
97
Table 1
Summary of series compensation effects on distance relay.
Effect of series compensation
Consequences
Relay overreach
Relay underreach
Voltage inversion
Current inversion
Relay overreach
of total line impedance. That means, increases in zero and negative sequence components of the currents and needs change in
protection algorithms, especially for earth sensing relays.
2.6. Parallel lines
Problems with protection of the series compensated lines
amplify with a parallel line conguration. The series compensator
gets rid of a portion of the self-reactance of the transmission line.
However, its effect is negligible on the mutual impedance of the
parallel lines. Moreover, the outage of any line and grounding on
either end changes the impedance equation. Therefore, all these
conditions should also be considered during the protection design
of parallel series compensated transmission line protection.
2.7. Faults in capacitor bank
The series compensators are normally installed as a capacitor
bank on a platform. An internal over-voltage protection is always
necessary for this capacitor bank. The compensator necessitates
shorting the whole capacitor platform in case of any over-voltage
(for example, group over-voltage because of fuse blowing). For
a single-phase fault, capacitor bank protection system needs to
bypass other two phase capacitor platforms also. A delay in bypass
of other two platforms provides a window of opportunity for a high
speed sensitive ground and direction detection schemes to operate. This is due to the fact that this capacitor unbalance appears as
internal fault of the protected system [12].
Table 1 gives a summary of the problems faced by a distance
protection scheme, when subjected to protect a transmission line
with series compensation.
BI-DIRECTIONAL
THYRISTORS
jXL
ITCR
ILINE
-jXC
IC
+ VC -
Ld
Electronically Controlled Series Compensation (CSC) provides
better control over power ow of a transmission line than xed
series compensation. The CSC increases transient stability of the
system as well. However, it introduces additional harmonics,
rapid changes associated to its control actions in primary system
parameters such as line impedances and load currents. Being the
INDUCTOR
LS
MOV
AIR GAP
CIRCUIT BREAKER
TCR
98
fault current. If the short circuit current were large enough, MOV
would be in reduces resistance mode, and will produce equivalent
impedance of TCSC in bypassed mode (inductive). Therefore, TCSCs
capacitive reactance would decrease and gradually change into
inductive reactance. This affects adversely to the transmission line
protection settings [15,16]. If the fault current is not large enough,
TCSCs control system will not send its commands to bypass the
thyristor, in this case TCSCs impedance characteristic becomes
complicated. Moreover, with a fault where transient voltage and
currents waveforms are not symmetrical, the TCSC ring becomes
confusing. In this condition, TCSCs harmonics become very complicated [17]. Ghassemi and Johns [18] investigated the effect on
distance protection measurement due to the residual compensation when an earth fault occurs on a series compensated line. The
directional integrity of the normal impedance relay will be compromised with TCSC installation as investigated in [14].
To understand the TCSC operation during a fault period, let we
understand the normal operating conditions of TCSC. The TCSC normally operates with anyone out of following operating modes [3]:
will persist through TCSC continuously. Due to existence of compensation, the relay can overreach considerably, and also can lose
its directional integrity.
2.8.2. Capacitive boost mode with MOV conduction
For a high-current fault case, the MOV conducts to decrease the
voltage across the SC (Fig. 8(b)). However, the MOV is fast enough to
conduct and reset within a half-cycle. In this case, neither the MOV
nor the circuit breaker would be short out the capacitor continuously. This short-duration condition usually repeated several times
during the fault period. During this condition, the TCSC impedance
would be the parallel combination of the capacitor and the MOV in
a lower resistance mode. The relay would overreach but differently
from the previous case without MOV operation.
2.8.3. Blocking mode
During fault transient time, phase angle of the voltage across
capacitor changes swiftly, which changes the ring angle of the
TCSC rapidly in some cases. To avoid overcurrent situation for this
case, the thyristors are blocked by ring mechanism. In this condition, the TCSC acts like a xed series capacitor only (Fig. 8(c)). The
relay would overreach as in case of xed SC with MOV. However,
this overreach is less than the case, when the TCSC is in capacitive
boost mode.
2.8.4. TCSC bypass operation
For a very heavy fault current condition, the MOV operation is
not enough to decrease the capacitor voltage. This leads toward
total thyristor conduction (bypass mode Fig. 8(d)). In this case, the
distance relay would underreach due to the presence of the reactor
in circuit.
2.8.5. Circuit breaker bypass
If the fault is not cleared within a pre-specied time period, the
TCSC transits to circuit breaker bypass mode (Fig. 8 (e)). Since the
CT
99
SC
G1 PT
RELAY
(a)
CT
SC
PT
G1
RELAY
(b)
series reactor in the circuit breaker circuit is very small, the relay
experiences the normal situation. This condition is used only for
back-up protection.
Table 2 summarized these operating conditions and its effect on
distance protection.
3. Series compensated transmission line protection
Addition of series compensation force changes into design of
the transmission line protection system. These changes are according to alteration in system parameters as per size, location and
over voltage protection of the compensator as discussed earlier.
Besides the detection of faulty condition, fault type classication is
an essential protective relaying aspect for transmission line protection. In a series compensated transmission line, the end line
fault currents may be of the order of the load currents. Moreover,
identical impedance conditions exist on either side of the series
compensation (Fig. 1). This necessitates information about location
of fault with respect to the compensator (fault zone). Therefore, the
nal impedance calculations of the distance relay always use fault
type and zone information. Reviews for fault analysis (fault zone
and type identication) methods with fault location methods have
been presented throughout this section.
In recent times, considerable development efforts have been
registered for development of protective relaying schemes for
series compensated transmission lines. The available approaches
can broadly be classied in following categories:
(1) Application of multiple/dynamic impedance characteristics
according to the presence of the series compensator in the fault
circuit [19], or to use memory polarization to eliminate voltage
alteration across compensation [20,21].
(2) Development of a mathematical model of the compensation
device to estimate the impedance level during a course of fault.
The voltage across the compensator can be estimated to correct
the measured voltage [2224].
(3) Protection of the series compensated line with a digital protection system that employs an advanced digital signal processing
tool and/or articial intelligence technique. Normally, these
schemes operate into two stages:
(i) Signal pre-processing and feature extraction
In this stage, features of the measured electrical quantities are
extracted and enhanced for further analysis. Signal processing
tools like Fourier Transform (FT), Discrete Fourier Transform
(DFT), Fast Fourier Transform (FFT), Wavelet Transform (WT),
100
MOV
Fig. 11. Compensator modeling [24].
101
Fourier lter based series compensated transmission line protection scheme for simultaneously removal of the sub synchronous
frequency components to develop a clear fundamental frequency
component in a quick time. With series compensation, this process
can take a long time to extract features due to long time decaying
sub-harmonic resonance.
The DFT is one of the most preferred tools for protection industry. The computational cost of the recursive DFT lter is lower.
Moreover, a very good harmonic immunity can be achieved by
DFT ltration, which improves the fault information. However,
during approximation of a discontinuous function (fault induces
current/voltage); the function is dened in the whole interval
of interest by a global basis set. Therefore, Gibbs phenomenon
will restrict the nal resolution. With exploration of recent signal
processing tools like Gabor Transform (GT) and Wavelet Transforms (WT); the implementation of DFT has reduced drastically,
as they can provide more meaningful information for protective
requirements.
Current (kA)
2
1
0
-1
-2
Time (Sec)
Current (kA)
2
1
0
-1
-2
Time (Sec)
102
103
The application of fuzzy logic for series compensated line protection is limited due to large variation in system parameters. The
formation of fuzzy rules under such variation makes it difcult and
slow in nature. However, other classier with a help of a fuzzy
system can make the system more accurate and easy.
A basic scheme with signal processing tool aiding articial intelligence tool is shown in Fig. 14.
4. Fault location and fault distance calculation
Introduction of series compensation makes fault location estimation difcult due to change in system parameters as discussed in
previous section. Moreover, the fault location algorithm normally
developed under an assumption of a properly transposed system.
The unbalance or non-symmetry in line parameters and measurements get amplied with inclusion of series compensation and
introduces error in fault distance calculations. Furthermore, most
of the fault locator algorithm utilizes a lumped parameter model
for system parameter calculations. The series compensation also
amplies line charging due to shunt capacitance, which is neglected
during uncompensated relaying and affects the fault distance calculation. Fault location techniques in the literature can broadly be
classied as per measurement for analysis as:
single-end measurement algorithms (Fig. 15),
two-ends measurement algorithms (Fig. 16), and
multi-ends measurement algorithms.
The single end algorithm poses an advantage as derives the
nal fault distance estimation on relaying end measurements only.
Two end and multi end algorithms need measurements from each
end of line. Moreover, data transmission requires a communication channel. These data can be used either in synchronized or
unsynchronized mode of calculations. In a way, the single end measurement algorithms are the easiest and yield fewer computational
bourdon, however, lacks in accuracy. The two and multi end algorithms gain an advantage that measurements from either side of
fault eliminate the effect of fault impedance and compensation
voltage drop on distance calculations.
Fault location techniques with series compensated transmission
line in the literature can also be categorized on their working as:
104
Phasor based approach is the most fundamental for a transmission line [32,61]. This method can have different variations
as per system parameter measurement location as described earlier. However, during a fault period, the voltage and current signal
are not purely sinusoidal; therefore, the phasor based approach
carries error-prone information and nal fault location accuracy
gets affected. This problem amplies with introduction of nonlinear series compensating devices. Time-domain algorithms have
been developed with single-circuit networks to overcome this
problem [7,31,32,36]. A high-frequency transient traveling waves
based fault locator estimates the fault distance by reection of the
high frequencies in transients. This method provided better fault
location accuracy with series compensated devices also. However,
accurate and faithful measurement of data is prime requirement
for this method. Use of modern analysis and classication tool can
also be reported by researchers.
In an initial approach for fault location estimation, Girgis at el.
[62] applied Carsons developed method for fault impedance calculations with additional estimation of the compensator equivalent
impedance. The SCMOV combination voltage has been predicted
with curve tting application of the Kalman lter. The SCMOV
combined impedance has been predicted with method suggested
by Goldsworthy [22], in a fault location approach by Ghassemi
et al. [63]. These schemes show encouraging results for series
compensated transmission line fault location according to their
time; however, wide authentication has not been provided by the
authors.
A single ended fault location algorithm using phasor coordinates
has been proposed in [61]. The method calculates two different
synchronized voltages from either side of the line with help of a
distributed time model. An approach to estimate voltage across
compensation devices to help estimating fault location has been
developed by Al-Dabbagh et al. [32]. However, in these methods
[32,61], the procedure ignores shunt and mutual capacitance of the
line that restricts accuracy of nal distance calculations. In [64] a
high speed numerical method is proposed on the directional comparison principle. The method uses a communication channel and
measurement from either side of the line, to sum up fault location.
A Phasor Measurement Unit (PMU) based two-ended fault location estimation algorithm has been demonstrated by Chi-Shan et al.
[65]. The algorithm is unaffected by position and type of the compensator. Another PMU based fault location estimation on series
compensated line has been developed in [66]. The scheme claims
application for uncompensated transmission line also. However,
application of GPS for synchronization and requirement of a dedicated communication channel makes it complex and expensive for
105
Table 3
Comparison of few fault location estimation algorithms for series compensated transmission lines.
Article
Type of algorithm
reported
Data requirement
Number of
considered test
cases
One-end algorithm
Phasor approach
1 cycle
12
One-end algorithm
Deterministic
Differential Approach
(DDA)
1 cycle
12
Line currents
One-end algorithm
ANN approach
1 cycle or more
12
One-end algorithm
1 cycle or more
Few
One-end algorithm
1 cycle
Few
One-end algorithm
1.25 cycles
1944
Type of Fault
FIA
Three phase current
measurements
Three phase local pre-fault
current values
There phase voltages
Two-end algorithm
1 cycle
08
Two-end algorithm
1 cycle
500
One-end algorithm
600
NA
Al-Dabbagh [32]
Two-end algorithm
90
Two-end algorithm
One cycle
108
NA
One-end algorithm
60
NA
Two-end algorithm
One cycle
66
NA
Two-end algorithm
One cycle
200
Two-end algorithm
One cycle
Few
One-end algorithm
One cycle
6280
in the method to accommodate the effect of the series compensation has been provided by same authors [76].
The method presented by Cheong et al. [77] presented two-stage
methodology for fault location estimation with help of wavelet
transform and self-organizing map neural networks. The method
requires ve cycle post fault data to estimate fault location. Five
cycle post fault data is a rare possibility in todays digital protection
environment. The method proposed in [78] also applies wavelet
106
these issues is still due from industries; however, few practical solutions are available in implementation manuals of the relays and are
based on eld experiences.
In normal approach with impedance relay for series compensated transmission line, numerical relays are equipped with
adaptive impedance characteristic. Each phase and ground zone
element can be set to the quadrilateral or mho characteristic, with
exibility of adopting appropriate characteristic shapes that suit
availability of the compensator in the circuit. The exemplary implementation and performance of the numerical relay can be seen in
[79].
With addition of series compensation, the accuracy and reliability of distance relay are in question. Therefore, phasor comparison
based approaches were common in initial series compensated
transmission line protection schemes. However, phasor based twoended relaying approaches found operational difculties during
implementation [9]. Recent advancements in signal conditioning
improve phasor base unit protection scheme. Moreover, the segregated phase-comparators remove mixing of signals and can be able
to provide fault type information as well [80].
With introduction of series compensation in a 400 kV transmission system of the Central Western Network in Venezuela [81], the
existing protection scheme has been replaced with newly designed
numerical protection relay. The newly applied numerical relays
are capable to operate in series compensated environment. The
reach of rst zone, second zone and third zone of these relays are
reduced considerably to overcome the problem of overreaching in
its study [81]. However, relay settings remain unaltered for the lines
that have feasibility to have line side voltage measurements. As
mentioned earlier, use of the bus-side voltage measurement signicantly improves reliability of the distance protection scheme.
However, application of bus-side voltage for protection application is more feasible and practical option for end-line compensation
(Fig. 9). Basic possible practical approach for Series Compensated
Transmission line Cameroon-Southern Interconnected System has
been shown in [82]. The suggested scheme in this work uses nonunit protection type distance relay with modications to negate
effects of series compensation.
The current only schemes are normally simpler and easy compared to those schemes utilizing potential measurement also.
As the series compensation largely affects potential drop across
faulted circuit, application of the current only scheme provides an
advantage over other schemes [83].
Current based unit protection scheme were reported in [84] for
a series compensated transmission line in Dai-kurobe, Japan and
ve-end series compensated transmission line in Moscow [85]. For
the lone series compensated transmission line in Japan [84], primary protection has been provided by a phase-comparison scheme,
whereas, the FM based current differential protection has been utilized for nal tripping. The FM based current differential protection
is the same as used before integration of the series compensation.
With an implementation experiences [85], it has been shown
that the current based line differential protection provides a better solution for protection of long series compensated, high-voltage
transmission lines with more than two ends. The proposed charging
current compensation method is independent of voltage measurements, proved to work very well for such long overhead
line congurations. Combination of multi-terminal line differential
protection with a distance protection scheme provides a better protection solution for multi-end lines. However, impedance schemes
with line-side potential are found more advantageous than the current only scheme in recent studies [86].
Application of memory polarization for the relay is another preferred solution for series compensated transmission line protection
[80]. However, the under voltage control used for normal memory
polarization in uncompensated line faces a problem due to voltage reversal in series compensated environment. Therefore, the
memory control is normally applied in series compensated line for
retaining the voltage value until the impedance fault criterion is
reset, and positive sequence voltage exceeds a specic rated value
[83]. However, the sequence network outcome must be analyzed
with due consideration for the operating conditions of the SCMOV
network [5].
Few of high-speed numerical distance relays REL-531 (ABB)
[87], SEL-421 (SEL) [88], SIPROTEC (Siemense) [89], D90+ (GE) [90],
IEDREL-670-ANSI [80] (ABB) are available in the market, which are
designed with series compensating capacitors in transmission lines
in mind. All these relays are designed with hybrid distance protection schemes with adaptive distance characteristics. Therefore,
these relays can provide effective protection to uncompensated,
series compensated and adjacent line that can have exposure to
series compensation. A special directional functional is necessary
for all these relay to cope with capacitive reactance of the compensator.
Field implementations of these specially designed protective
numerical relays [8790] for series compensated transmission lines
involve some additional considerations compared to the protection functions of the normal uncompensated transmission lines.
Few of these additional important considerations necessary as suggested by the instructional manuals of these relays [8790] can be
summarized as:
The sub-synchronous oscillations in the system due to the series
capacitor should be considered during impedance settings; as it
affects nal impedance measurement.
The relay parameter settings should consider an effect of the
series capacitor bank on fault clearance time.
A correct capacitor bank equivalent impedance calculation for
the actual fault current is important for all range of the protected
zone. Iterative calculations are necessary for many critical points
along the line.
For directional integrity the many relays use memory voltage
polarization when applied to series compensated transmission
lines. A multi-input comparator is commonly used to deal with
current inversion issues in series compensated lines.
A comprehensive study report should be prepared for each series
compensated transmission line to improve the required settings.
With all of these drawbacks of the distance protection schemes,
application of traveling wave based protection schemes are also
considered as interesting options by protection industries [5].
Traveling-wave differential equation based relaying algorithm for
series compensated transmission line has been developed in [72].
The developed methodology modies the traveling wave equations
to include effects of series compensation.
6. Conclusion
An overview of work in the eld of series compensated transmission line protection is presented in this paper. This work presents a
bibliographical survey of relevant background, effect of series compensation on transmission line protection and protection efforts for
series compensated line. An effort is made to present all the techniques and algorithms presented till the date. Each technique is
evaluated separately to identify the optimum techniques for application. The article leads the researchers toward use of modern-day
processing and classication techniques to improve performance
of the protective relays.
Based on the literature available the following gaps are identied in the protection of series compensated transmission lines:
References
[1] C.R. Masson, The Art and Science of Protective Relaying, John Wiley & Sons, Inc.,
1956.
[2] L.M. Wedepohl, Polarised mho distance relay New approach to the analysis of
practical characteristics, Proceedings of the Institution of Electrical Engineers
112 (1965) 525535.
[3] N.G. Hingorani, L. Gyugyi, Understanding FACTS, First Indian ed., IEEE Press,
2001.
[4] P. Dash, A. Pradhan, G. Panda, Apparent impedance calculations for distanceprotected transmission lines employing series-connected FACTS devices,
Electric Power Components and Systems 29 (2001) 577595.
[5] B. Kasztenny, Distance protection of series compensated lines problems and
solutions, in: Proceedings of the 28th Annual Western Protective Relay Conference, Spokane, WA, 2001.
[6] M. Mandour, A. El-Alaily, Swivelling characteristic for the protection of series
compensated lines, Electric Power Systems Research 18 (1990) 3135.
[7] D. Novosel, A. Phadke, M.M. Saha, S. Lindahl, Problems and solutions for
microprocessor protection of series compensated lines, in: Sixth International
Conference on Developments in Power System Protection, 1997, pp. 1823.
[8] C.T. Summers, Distance Protection Aspects of Transmission Lines Equipped
with Series Compensation Capacitors, Electrical Engineering, Faculty of the
Virginia Polytechnic Institute and State University, Blacksburg, VA, 1999.
[9] G. Alexander, J. Andrichak, S. Rowe, S. Wilkinson, Series compensated line protection: a practical evaluation, in: Western Protective Relay Conference, 1988,
pp. 2527.
[10] P.K. Dash, A.K. Pradhan, G. Panda, A.C. Liew, Digital protection of power transmission lines in the presence of series connected FACTS devices IEEE Power
Engineering Society Winter Meeting, 2000 January, pp. 19671972.
[11] R. Grnbaum, K. Wikstrm, G. Strmberg, On series compensation impact
on line protection and TRV, in: North American Power Symposium (NAPS),
Vsters, Sweden, 2009 October, pp. 15.
[12] G.E. Alexander, J. Mooney, W. Tyska, Advanced Application Guidelines for
Ground Fault Protection, Schweitzer Engineering Laboratories, Inc., 2001.
[13] E.V. Larsen, K. Clark, S.A. Miske Jr., J. Urbanek, Characteristics and rating considerations of thyristor controlled series compensation, IEEE Transactions on
Power Delivery 9 (1994) 9921000.
107
108
[66] A. Abdelaziz, S. Mekhamer, M. Ezzat, Fault location of uncompensated/seriescompensated lines using two-end synchronized measurements, Electric Power
Components and Systems 41 (2013) 693715.
[67] C. Apostolopoulos, G. Korres, Accurate fault location algorithm for doublecircuit series compensated lines using a limited number of two-end
synchronized measurements, International Journal of Electrical Power &
Energy Systems 42 (2012) 495507.
[68] M.G. Ahsaee, J. Sadeh, A novel fault-location algorithm for long transmission
lines compensated by series FACTS Devices, IEEE Transactions on Power Delivery 26 (2011) 22992308.
[69] A. Hosny, M. Sauddin, ANN-based protection system for controllable seriescompensated transmission lines, in: IEEE Power Systems Conference and
Exposition, 2009. PSCE09. IEEE/PES, 2009, pp. 16.
[70] A. Yusuff, C. Fei, A. Jimoh, J. Munda, Fault location in a series compensated
transmission line based on wavelet packet decomposition and support vector
regression, Electric Power Systems Research 81 (2011) 12581265.
[71] D. Spoor, J.G. Zhu, Improved single-ended traveling-wave fault-location algorithm based on experience with conventional substation transducers, IEEE
Transactions on Power Delivery 21 (2006) 17141720.
[72] F. Wang, Study on traveling-wave differential protection for series compensated line, Journal of International Council on Electrical Engineering 1 (2011)
359366.
[73] G. Lerosey, J. De Rosny, A. Tourin, A. Derode, G. Montaldo, M. Fink, Time reversal
of electromagnetic waves, Physical Review Letters 92 (2004) 193904.
[74] H. Mahmoudimanesh, G. Lugrin, R. Razzaghi, R. Romero, C. Alberto, M. Paolone,
F. Rachidi-Haeri, A new method to locate faults in power networks based on
electromagnetic time reversal, in: Signal Processing Advances in IEEE 13th
International Workshop on Wireless Communications (SPAWC), 2012.
[75] R. Razzaghi, G. Lugrin, H. Manesh, C. Romero, M. Paolone, F. Rachidi, An efcient
method based on the electromagnetic time reversal to locate faults in power
networks, IEEE Transaction on Power Delivery 28 (2013) 16631673.
[76] R. Razzaghi, G. Lugrin, M. Paolone, F. Rachidi, On the use of electromagnetic
time reversal to locate faults in series-compensated transmission lines, in:
Proceedings of the 2013 IEEE Grenoble PowerTech, IEEE Power Engineering
Society and Grenoble Institute of Technology, France, 2013, pp. 15.
[77] W.J. Cheong, R.K. Aggarwal, A novel fault location technique based on current signals only for thyristor controlled series compensated transmission lines
using wavelet analysis and self organising map neural networks, in: Developments in Power System Protection, 2004. Eighth IEE International Conference
on, Vol. 221, 2004, pp. 224227.
[78] C.Y. Evrenosoglu, A. Abur, Fault location for teed circuits with mutually coupled
lines and series capacitors, in: Power Tech Conference Proceedings, 2003 IEEE
Bologna, IEEE, Vol. 3, 2003, p. 6.
[79] C.M. Leoaneka, Dynamic Performance of numerical Distance Protection Relays
in Heavily Series Compesated Networks, School of Electrical, Electronic and
Computer Engineering, University of KwaZulu-Natal, Durban, South Africa,
2010.
[80] Technical Reference Manual Line Distance Protection IED REL 670 ANSI, ABB
Ltd., 2007, March.
[81] R.A. Castro, H.A. Pineda, Protection system considerations for 400 kV series
compensated transmission lines of the Central Western Network in Venezuela,
in: Transmission & Distribution Conference and Exposition: Latin America,
2006. TDC06. IEEE/PES, IEEE, 2006, pp. 15.
[82] D.N. Nkwetta, V. Van Thong, R. Belmans, Protection of transmission lines using
series compensation capacitors in Cameroon-Southern Interconnected System,
in: Proceedings of 3rd IEEE Benelux Young Researchers Symposium in Electrical
Power Engineering, 2006, p. 5.
[83] G. Alexander, S. Rowe, J. Andrchak, S. Wikinson, W. Tyska, Series Compensated
Line Protection Evaluation & Solutions. GE Power Management, GER3736,
1998.
[84] F. Kumura, T. Yamada, M. Kuwabara, H. Kameda, T. Matsushima, Experiences
of Series Compenssated EHV Line Portection and Fault Location in Japan, 2005.
[85] I.B.Z. Gajic, F. Rios, Experience with Multiterminal Line Differential Protection
Installed on Series Compensated, 400 kV Line with Five-Ends, Moscow, 2009.
[86] T. Areva, Network Protection and Automation Guide, Flash Espace, Cayfosa,
2002, pp. 9295.
[87] ABB Instruction Manual High speed line distance protection terminal REL531, 2003.
[88] SEL-421 Relay: Instruction Manual for Protection and Automation System,
2011.
[89] Siemens PTD EA Applications for SIPROTEC Protection Relays Application
Example for 400 kV Overhead Transmission Line Protection, 2005.
[90] Instruction Manual for GE-D90Plus Line Distance Protection System, 2012.
[91] J. Sadeh, N. Hadjsaid, A.M. Ranjbar, R. Feuillet, Accurate fault location algorithm
for series compensated transmission lines, IEEE Transactions on Power Delivery
15 (2000) 10271033.