March 7, 2014
Note: Before using this information and the product that it supports, read the information in Notices and Trademarks on
page B-1.
Contents
Preface
1 IBM PureData System for Analytics N200X Models
Model N2002-002 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Model N2002-005 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Model N2002-010 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Model N2002-020 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Model N2002-040 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
iii
iv
Tables
Table 2-1:
Table 2-2:
Table 2-3:
Table 2-4:
Table 2-5:
Table 3-1:
Table 3-2:
Table 3-3:
Table 3-4:
Table 3-5:
Table 4-1:
Table 4-2:
Table 4-3:
Table 4-4:
Table 4-5:
Table 5-1:
Table 5-2:
Table 5-3:
Table 5-4:
Table 5-5:
Table 6-1:
Table 6-2:
Table 6-3:
Table 6-4:
Table 6-5:
Table A-1:
vi
Figures
Figure 1-1:
Figure 1-2:
Figure 1-3:
Figure 1-4:
Figure 1-5:
Figure 2-1:
Figure 3-1:
Figure 4-1:
Figure 5-1:
Figure 6-1:
vii
viii
Preface
The IBM PureData System for Analytics Model N200X is a high-performance, integrated
data warehouse appliance that provides unparalleled performance, extensive scaling, high
reliability, and ease of use. The system uses a unique architecture that combines current
trends in processor, network, and software technologies to deliver a very high-performance
system for large enterprise customers.
Maintaining a location.
Hardware specifications.
Chapter 1, IBM PureData System for Analytics N200X Models Lists the different
system models and describes the location of the major components within the system.
ix
Abbreviations
This guide uses the following abbreviations throughout:
Abbreviation
Description
ampere
ACID
GB
Gigabyte
HTTP
Hz
Hertz
in.
Inch
kg
Kilogram
KVA
Kilo Volt-Amps
KVM
Keyboard-Video-Mouse
lb
Pound
meter
Mb
Megabit
MB
Megabyte
ms
Milliseconds
MSFI
Abbreviation
Description
MSPU
NIC
NPS system
PCI
PCIe
PCI Express
PCIx
PCI eXtended
PDU
RAID
RPC
SAS
SATA
SCSI
SFI
SNMP
SPA
SPU
TB
Terabyte
VAC
xi
The name and version of the manual that you are using
xii
CHAPTER 1
IBM PureData System for Analytics N200X Models
This chapter contains the following information:
A description of each system, including the number of racks, S-Blades, and SPAs in
the system
An illustration of each system showing the placement of components within each rack.
Model N2002-002
The Model N2002-002 is a single-rack system containing 2 S-Blades housed in 1 SPA.
Note: The racks are bolted together into a single unit and cannot be separated.
Figure 1-1 shows a Model N2002-002 system.
Note: The switches are only visible from the rear of the rack.
1-1
Site Preparation and Specifications: IBM PureData System for Analytics Model N200x
Model N2002-005
The Model N2002-005 is a single-rack system containing 4 S-Blades housed in 1 SPA.
Note: The racks are bolted together into a single unit and cannot be separated.
Figure 1-2 shows a Model N2002-005 system.
Note: The switches are only visible from the rear of the rack.
1-2
D27700-2
Rev.7.0
Model N2002-010
Model N2002-010
The Model N2002-010 is a single-rack system containing 7 S-Blades housed in 1 SPA.
Note: The racks are bolted together into a single unit and cannot be separated.
Figure 1-3 shows a Model N2002-010 system.
Note: The switches are only visible from the rear of the rack.
D27700-2
Rev.7.0
1-3
Site Preparation and Specifications: IBM PureData System for Analytics Model N200x
Model N2002-020
The Model N2002-020 is a two-rack system containing 14 S-Blades housed in 2 SPAs.
Note: The racks are bolted together into a single unit and cannot be separated.
Figure 1-4 shows a Model N2002-020 system.
Note: The switches are only visible from the rear of the rack.
1-4
D27700-2
Rev.7.0
Model N2002-040
Model N2002-040
The Model N2002-040 is a four-rack system containing 28 S-Blades housed in 4 SPAs.
Note: The racks are bolted together into a single unit and cannot be separated.
Figure 1-5 shows a Model N2002-040 system.
Note: The switches are only visible from the rear of the rack.
D27700-2
Rev.7.0
1-5
Site Preparation and Specifications: IBM PureData System for Analytics Model N200x
1-6
D27700-2
Rev.7.0
CHAPTER 2
Model N2002-002 Specifications
This chapter explains the following requirements for the Model N2002-002 system:
Space requirements
Environmental requirements
EU
NA
Circuits
Voltage
Circuit Breaker Rating
Connector
Maximum Power
Power/Area
30 - 32A
IEC 309 32A P+N+G
Hubbell 332C6 or similar
3,200 W
3,200 W
420 W/ft2
(4,522 W/m2)
420 W/ft2
(4,522 W/m2)
2-1
Site Preparation and Specifications: IBM PureData System for Analytics Model N200x
Space requirements
Each rack in the system has a footprint of 25.5 in. (64.8 cm) by 43 in. (109.2 cm). An
additional 36 in. (91.5 cm) of clear space is required in front of each rack and 30 in. (76.2
cm) behind the rack. This is to allow unrestricted airflow and access to the system.
IBM recommends an extended service clearance of 60 in. (152 cm) in front of the rack to
allow unrestricted access for service.
Note: The Model N2002-002 system is housed in a rack that is wider than a standard 24
in. (61 cm) data center floor tile. Plan accordingly.
A full height system rack is 87.5 in. (222 cm) tall including its shipping pallet. Without the
pallet, the rack stands 79.5 in. (202 cm) tall including casters. Allow for this when planning the movement of the system from the unloading point to its permanent location.
Figure 2-1 shows the space requirements for each rack.
25.5 in
(64.8 cm)
30 in
(76 cm)
40 in
(101.6 cm)
36 in
91.5 cm)
60 in
(152 cm)
between rows
recommended
2-2
Including Clearance
25.5 in. by 130 in.
(64.8 cm x 330.2 cm)
D27700-2
Rev.7.0
Environmental Requirements
Environmental Requirements
The Model N2002-002 system is designed to operate within the following temperature,
humidity, and altitude ranges:
Table 2-3: Model N2002-002 Operating Environment
Operating
Non-operating
Temperature
10C to 35C
(50F to 95F)
-15C to 45C
(5F to 113F)
Altitude
0 to 3,048 m
(0 to 10,000 ft)
0 to 9,144 m
(0 to 30,000 ft)
Humidity
Cooling
10,850 BTU/hr
Air Changes
D27700-2
Rev.7.0
Value
Maximum Weight
Maximum Weight/Area
2-3
Site Preparation and Specifications: IBM PureData System for Analytics Model N200x
Number
Description
Processors
two
Memory
Power supplies
two
Fans
four
Ethernet ports
(1 Gigabit)
four ports
(one available)
Ethernet ports
(10 Gigabit)
six ports
(two available)
IMM port
two
FibreChannel ports
two
(two available)
seven
PCI slots
six
(three available)
Six - PCI-Express x8
(one full length, one half length,
one low profile are available)
six
(five available)
Serial port
one
DVD-ROM/CD-RW
one
8X / 24X max
Form Factor
2U (3.5)
rack-mountable
Management
2-4
IMM2
D27700-2
Rev.7.0
CHAPTER 3
Model N2002-005 Specifications
This chapter explains the following requirements for the Model N2002-005 system:
Space requirements
Environmental requirements
EU
NA
Circuits
30 to 32A
30A
4,200 W
4,200 W
552 W/ft2
(5,935 W/m2)
552 W/ft2
(5,935 W/m2)
Voltage
Circuit Breaker Rating
Connector
Maximum Power
Power/Area
3-1
Site Preparation and Specifications: IBM PureData System for Analytics Model N200x
Space requirements
Each rack in the system has a footprint of 25.5 in. (64.8 cm) by 43 in. (109.2 cm). An
additional 36 in. (91.5 cm) of clear space is required in front of each rack and 30 in. (76.2
cm) behind the rack. This is to allow unrestricted airflow and access to the system.
IBM recommends an extended service clearance of 60 in. (152 cm) in front of the rack to
allow unrestricted access for service.
Note: The Model N2002-005 system is housed in a rack that is wider than a standard 24
in. (61 cm) data center floor tile. Plan accordingly.
A full height system rack is 87.5 in. (222 cm) tall including its shipping pallet. Without the
pallet, the rack stands 79.5 in. (202 cm) tall including casters. Allow for this when planning the movement of the system from the unloading point to its permanent location.
Figure 3-1 shows the space requirements for each rack.
25.5 in
(64.8 cm)
30 in
(76 cm)
40 in
(101.6 cm)
36 in
91.5 cm)
60 in
(152 cm)
between rows
recommended
3-2
Including Clearance
25.5 in. by 130 in.
(64.8 cm x 330.2 cm)
D27700-2
Rev.7.0
Environmental Requirements
Environmental Requirements
The Model N2002-005 system is designed to operate within the following temperature,
humidity, and altitude ranges:
Table 3-3: Model N2002-005 Operating Environment
Operating
Non-operating
Temperature
10C to 35C
(50F to 95F)
-15C to 45C
(5F to 113F)
Altitude
0 to 3,048 m
(0 to 10,000 ft)
0 to 9,144 m
(0 to 30,000 ft)
Humidity
Cooling
15,500 BTU/hr
Air Changes
D27700-2
Rev.7.0
Value
Maximum Weight
Maximum Weight/Area
3-3
Site Preparation and Specifications: IBM PureData System for Analytics Model N200x
Number
Description
Processors
two
Memory
Power supplies
two
Fans
four
Ethernet ports
(1 Gigabit)
four ports
(one available)
Ethernet ports
(10 Gigabit)
six ports
(two available)
IMM port
two
FibreChannel ports
two
(two available)
seven
PCI slots
six
(three available)
Six - PCI-Express x8
(one full length, one half length,
one low profile are available)
six
(five available)
Serial port
one
DVD-ROM/CD-RW
one
8X / 24X max
Form Factor
2U (3.5)
rack-mountable
Management
3-4
IMM2
D27700-2
Rev.7.0
CHAPTER 4
Model N2002-010 Specifications
This chapter explains the following requirements for the Model N2002-010 system:
Space requirements
Environmental requirements
EU
3-Phase Delta
NA
NA
Circuits
Voltage
Circuit Breaker
Rating
Connector
Maximum Power
Power/Area
200-240/380-415 VAC,
50 Hz/60 Hz
16 to 32A
20 to 32A
200-208 VAC,
50 Hz/60 Hz
Single Phase
EU
NA
200-240 VAC,
50 Hz/60 Hz
30A
60 to 63A
60A
7,500 W
985 W/ft2
(10,600 W/m2)
4-1
Site Preparation and Specifications: IBM PureData System for Analytics Model N200x
Space requirements
Each rack in the system has a footprint of 25.5 in. (64.8 cm) by 43 in. (109.2 cm). An
additional 36 in. (91.5 cm) of clear space is required in front of each rack and 30 in. (76.2
cm) behind the rack. This is to allow unrestricted airflow and access to the system.
IBM recommends an extended service clearance of 60 in. (152 cm) in front of the rack to
allow unrestricted access for service.
Note: The Model N2002-010 system is housed in a rack that is wider than a standard 24
in. (61 cm) data center floor tile. Plan accordingly.
A full height system rack is 87.5 in. (222 cm) tall including its shipping pallet. Without the
pallet, the rack stands 79.5 in. (202 cm) tall including casters. Allow for this when planning the movement of the system from the unloading point to its permanent location.
Figure 4-1 shows the space requirements for each rack.
25.5 in
(64.8 cm)
30 in
(76 cm)
40 in
(101.6 cm)
36 in
91.5 cm)
60 in
(152 cm)
between rows
recommended
4-2
Including Clearance
25.5 in. by 130 in.
(64.8 cm x 330.2 cm)
D27700-2
Rev.7.0
Environmental Requirements
Environmental Requirements
The Model N2002-010 system is designed to operate within the following temperature,
humidity, and altitude ranges:
Table 4-3: Model N2002-010 Operating Environment
Operating
Non-operating
Temperature
10C to 35C
(50F to 95F)
-15C to 45C
(5F to 113F)
Altitude
0 to 3,048 m
(0 to 10,000 ft)
0 to 9,144 m
(0 to 30,000 ft)
Humidity
Cooling
27,000 BTU/hr
Air Changes
D27700-2
Rev.7.0
Value
2,000 lb
(907.2 kg)
262.7 lb/ft2
(1,282.6 kg/m2)
4-3
Site Preparation and Specifications: IBM PureData System for Analytics Model N200x
Number
Description
Processors
four
Memory
Power supplies
two
Fans
three
NIC - 1Gb
six ports
(four available)
NIC - 10Gb
eight ports
(two available)
two ports
(two available)
IMM port
one
seven
PCI slots
eight
(three available)
Eight - PCI-Express x8
(three full height/half length, five low profile/half length)
six
Serial port
one
DVD-ROM/CD-RW
one
8X / 24X max
Form Factor
2U (3.5)
rack-mountable
Management
4-4
IMM
D27700-2
Rev.7.0
CHAPTER 5
Model N2002-020 Specifications
This chapter explains the following requirements for the Model N2002-020 system:
Space requirements
Environmental requirements
EU
3-Phase Delta
NA
NA
Circuits
Voltage
Circuit Breaker
Rating
Connector
Maximum Power
Power/Area
200-240/380-415 VAC,
50 Hz/60 Hz
16 to 32A
20 to 32A
200-208 VAC,
50 Hz/60 Hz
Single Phase
EU
NA
200-240 VAC,
50 Hz/60 Hz
30A
60 to 63A
60A
15,000 W
985 W/ft2
(10,600 W/m2)
5-1
Site Preparation and Specifications: IBM PureData System for Analytics Model N200x
Space requirements
The Model N2002-020 consists of two racks. The racks are bolted together into a group of
racks called a pod. In this system there is a single pod of two racks.
Each rack in the system has a footprint of 25.5 in. (64.8 cm) by 43 in. (109.2 cm). An
additional 36 in. (91.5 cm) of clear space is required in front of each rack and 30 in. (76.2
cm) behind the rack. This is to allow unrestricted airflow and access to the system.
IBM recommends an extended service clearance of 60 in. (152 cm) in front of the rack to
allow unrestricted access for service.
Note: Each rack in the Model N2002-020 system is wider than a standard 24 in. (61 cm)
data center floor tile. Plan accordingly.
A full height system rack is 87.5 in. (222 cm) tall including its shipping pallet. Without the
pallet, the rack stands 79.5 in. (202 cm) tall including casters. Allow for this when planning the movement of the system from the unloading point to its permanent location.
Figure 5-1 shows the space requirements for the pod.
51.0 in
(129.6 cm)
30 in
(76 cm)
40 in
(101.6 cm)
36 in
91.5 cm)
60 in
(152 cm)
between rows
recommended
5-2
Physical
Including Clearance
51 in. by 43 in.
(128.6 cm x 109.2 cm)
D27700-2
Rev.7.0
Environmental Requirements
Environmental Requirements
The Model N2002-020 system is designed to operate within the following temperature,
humidity, and altitude ranges:
Table 5-3: Model N2002-020 Operating Environment
Operating
Non-operating
Temperature
10C to 35C
(50F to 95F)
-15C to 45C
(5F to 113F)
Altitude
0 to 3,048 m
(0 to 10,000 ft)
0 to 9,144 m
(0 to 30,000 ft)
Humidity
Cooling
54,000 BTU/hr
Air Changes
D27700-2
Rev.7.0
2-Rack Pod
4,000 lb (1814.4 kg)
262.7 lb/ft2 (1,282.6 kg/m2)
5-3
Site Preparation and Specifications: IBM PureData System for Analytics Model N200x
Number
Description
Processors
four
Memory
Power supplies
two
Fans
three
NIC - 1Gb
six ports
(four available)
NIC - 10Gb
eight ports
(two available)
two ports
(two available)
IMM port
one
seven
PCI slots
eight
(three available)
Eight - PCI-Express x8
(three full height/half length, five low profile/half length)
six
Serial port
one
DVD-ROM/CD-RW
one
8X / 24X max
Form Factor
2U (3.5)
rack-mountable
Management
5-4
IMM
D27700-2
Rev.7.0
CHAPTER 6
Model N2002-040 Specifications
This chapter explains the following requirements for the Model N2002-040 system:
Space requirements
Environmental requirements
EU
3-Phase Delta
NA
NA
Circuits
Voltage
Circuit Breaker
Rating
Connector
Maximum Power
Power/Area
200-240/380-415 VAC,
50 Hz/60 Hz
16 to 32A
20 to 32A
200-208 VAC,
50 Hz/60 Hz
Single Phase
EU
NA
200-240 VAC,
50 Hz/60 Hz
30A
60 to 63A
60A
30,000 W
985 W/ft2
(10,600 W/m2)
6-1
Site Preparation and Specifications: IBM PureData System for Analytics Model N200x
Space requirements
The Model N2002-040 consists of four racks. The racks are bolted together into a group of
racks called a pod. In this system there is a single pod of four racks.
Each rack in the system has a footprint of 25.5 in. (64.8 cm) by 43 in. (109.2 cm). An
additional 36 in. (91.5 cm) of clear space is required in front of each rack and 30 in. (76.2
cm) behind the rack. This is to allow unrestricted airflow and access to the system.
IBM recommends an extended service clearance of 60 in. (152 cm) in front of the rack to
allow unrestricted access for service.
Note: Each rack in the Model N2002-040 system is wider than a standard 24 in. (61 cm)
data center floor tile. Plan accordingly.
A full height system rack is 87.5 in. (222 cm) tall including its shipping pallet. Without the
pallet, the rack stands 79.5 in. (202 cm) tall including casters. Allow for this when planning the movement of the system from the unloading point to its permanent location.
Figure 6-1 shows the space requirements for the Pod.
102.0 in
(259.2 cm)
30 in
(76 cm)
40 in
(101.6 cm)
36 in
91.5 cm)
60 in
(152 cm)
between rows
recommended
6-2
Physical
Including Clearance
D27700-2
Rev.7.0
Environmental Requirements
Environmental Requirements
The Model N2002-040 system is designed to operate within the following temperature,
humidity, and altitude ranges:
Table 6-3: Model N2002-040 Operating Environment
Operating
Non-operating
Temperature
10C to 35C
(50F to 95F)
-15C to 45C
(5F to 113F)
Altitude
0 to 3,048 m
(0 to 10,000 ft)
0 to 9,144 m
(0 to 30,000 ft)
Humidity
Cooling
108,000 BTU/hr
Air Changes
D27700-2
Rev.7.0
4-Rack Pod
8,000 lb (3628.8 kg)
262.7 lb/ft2 (1,282.6 kg/m2)
6-3
Site Preparation and Specifications: IBM PureData System for Analytics Model N200x
Number
Description
Processors
four
Memory
Power supplies
two
Fans
three
NIC - 1Gb
six ports
(four available)
NIC - 10Gb
eight ports
(two available)
two ports
(two available)
IMM port
one
seven
PCI slots
eight
(three available)
Eight - PCI-Express x8
(three full height/half length, five low profile/half length)
six
Serial port
one
DVD-ROM/CD-RW
one
8X / 24X max
Form Factor
2U (3.5)
rack-mountable
Management
6-4
IMM
D27700-2
Rev.7.0
APPENDIX
Model Comparison
Table A-1 provides a comparison between the available models of the IBM PureData System for Analytics Model N200X.
Table A-1: Model Comparison
User Data
System
Host
Processors
S-Blades
Racks
High
Availability
no compression
4x compression
Model N2002-002
8 TB
32 TB
Yes
Model N2002-005
24 TB
96 TB
Yes
Model N2002-010
48 TB
192 TB
Yes
Model N2002-020
96 TB
384 TB
14
Yes
Model N2002-040
192 TB
768 TB
28
Yes
A-1
Site Preparation and Specifications: IBM PureData System for Analytics Model N200x
A-2
D27700-2
Rev.7.0
APPENDIX
This section describes some important notices, trademarks, and compliance information.
Notices
This information was developed for products and services offered in the U.S.A.
IBM may not offer the products, services, or features discussed in this document in other
countries. Consult your local IBM representative for information on the products and services currently available in your area. Any reference to an IBM product, program, or service
is not intended to state or imply that only that IBM product, program, or service may be
used. Any functionally equivalent product, program, or service that does not infringe any
IBM intellectual property right may be used instead. However, it is the user's responsibility
to evaluate and verify the operation of any non-IBM product, program, or service.
IBM may have patents or pending patent applications covering subject matter described in
this document. The furnishing of this document does not grant you any license to these
patents. You can send license inquiries, in writing, to: This information was developed for
products and services offered in the U.S.A.
IBM Director of Licensing
IBM Corporation
North Castle Drive
Armonk, NY 10504-1785 U.S.A.
For license inquiries regarding double-byte (DBCS) information, contact the IBM Intellectual Property Department in your country or send inquiries, in writing, to:
IBM World Trade Asia Corporation
Licensing 2-31 Roppongi 3-chome, Minato-ku
Tokyo 106-0032, Japan
The following paragraph does not apply to the United Kingdom or any other country where
such provisions are inconsistent with local law: INTERNATIONAL BUSINESS MACHINES
CORPORATION PROVIDES THIS PUBLICATION "AS IS" WITHOUT WARRANTY OF ANY
KIND, EITHER EXPRESS OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, THE
B-1
Site Preparation and Specifications: IBM PureData System for Analytics Model N200x
B-2
D27700-2
Rev.7.0
Trademarks
COPYRIGHT LICENSE:
This information contains sample application programs in source language, which illustrate
programming techniques on various operating platforms. You may copy, modify, and distribute these sample programs in any form without payment to IBM, for the purposes of
developing, using, marketing or distributing application programs conforming to the application programming interface for the operating platform for which the sample programs are
written. These examples have not been thoroughly tested under all conditions. IBM, therefore, cannot guarantee or imply reliability, serviceability, or function of these programs.
Each copy or any portion of these sample programs or any derivative work, must include a
copyright notice as follows:
your company name) (year). Portions of this code are derived from IBM Corp. Sample
Programs.
Copyright IBM Corp. _enter the year or years_.
If you are viewing this information softcopy, the photographs and color illustrations may not
appear.
Trademarks
IBM, the IBM logo, ibm.com and Netezza are trademarks or registered trademarks of International Business Machines Corporation in the United States, other countries, or both. If
these and other IBM trademarked terms are marked on their first occurrence in this information with a trademark symbol ( or ), these symbols indicate U.S. registered or
common law trademarks owned by IBM at the time this information was published. Such
trademarks may also be registered or common law trademarks in other countries. A current
list of IBM trademarks is available on the Web at Copyright and trademark information at
ibm.com/legal/copytrade.shtml.
Adobe is a registered trademark of Adobe Systems Incorporated in the United States, and/
or other countries.
Linux is a registered trademark of Linus Torvalds in the United States, other countries, or
both.
Microsoft, Windows, Windows NT, and the Windows logo are trademarks of Microsoft Corporation in the United States, other countries, or both.
NEC is a registered trademark of NEC Corporation.
UNIX is a registered trademark of The Open Group in the United States and other
countries.
Java and all Java-based trademarks are trademarks of Sun Microsystems, Inc. in the United
States, other countries, or both.
Red Hat is a trademark or registered trademark of Red Hat, Inc. in the United States and/or
other countries.
D-CC, D-C++, Diab+, FastJ, pSOS+, SingleStep, Tornado, VxWorks, Wind River, and the
Wind River logo are trademarks, registered trademarks, or service marks of Wind River Systems, Inc. Tornado patent pending.
APC and the APC logo are trademarks or registered trademarks of American Power Conversion Corporation.
Other company, product or service names may be trademarks or service marks of others.
D27700-2
Rev.7.0
B-3
Site Preparation and Specifications: IBM PureData System for Analytics Model N200x
B-4
D27700-2
Rev.7.0
D27700-2
Rev.7.0
B-5
Site Preparation and Specifications: IBM PureData System for Analytics Model N200x
This is a Class A product based on the standard of the Voluntary Control Council for Interference (VCCI). If this equipment is used in a domestic environment, radio interference
may occur, in which case the user may be required to take corrective actions.
Japan Electronics and Information Technology Industries Association (JEITA) Statement
This is electromagnetic wave compatibility equipment for business (Type A). Sellers and
users need to pay attention to it. This is for any areas other than home.
Russia Electromagnetic Interference (EMI) Class A Statement
B-6
D27700-2
Rev.7.0
D27700-2
Rev.7.0
B-7
Site Preparation and Specifications: IBM PureData System for Analytics Model N200x
B-8
D27700-2
Rev.7.0