Final Report :: A - Earthquake
Codes
IITK-GSDMA Project on Building
Codes
IITK-GSDMA-EQ21V2.0
Example
1/Page 4
y
(1)
(2)
(3)
(4)
(4)
( 5)
(A)
3 @ 5000
(B)
(C)
(D)
4 @ 5000
PLAN
3200
3200
3200
4200
ELEVATION
Figure 1.1 Building configuration
IITK-GSDMA-EQ21V2.0
Example
1/Page 5
= 0.09(13.8) / 20
= 0.28 sec
The building is located on Type II (medium soil).
Solution:
Design Parameters:
For seismic zone V, the zone factor Z is 0.36
(Table 2 of IS: 1893). Being an office building,
the importance factor, I, is 1.0 (Table 6 of IS:
1893). Building is required to be provided with
moment resisting frames detailed as per IS:
13920-1993. Hence, the response reduction
factor, R, is 5.
ZI S a
=
2Rh g
0.36 1.0
=
2.5
25
= 0.09
=
= 0.09 15,600
= 1,440 kN
W1=W2 =W3
=300(12+0.54)
= 4,200 kN
Roof:
W4
= 30010
= 3,000 kN
(clause7.3.1, Table 8 of IS: 1893 Part 1)
= 34,200 + 3,000
= 15,600 kN
Fundamental Period:
Lateral load resistance is provided by moment
resisting frames infilled with brick masonry
panels. Hence, approximate fundamental natural
period:
(Clause 7.6.2. of IS: 1893 Part 1)
EL in X-Direction:
g =
Floors:
Sa
= 0.09h / d
= 0.09(13.8) / 15
= 0.32 sec
S
a
2.5;
g
Ah
=
= 0.09
Table 1.1 Lateral Load Distribution with Height by the Static Method
Storey
Level
h (m)
i i
i 2i
Wh
W h2 (1000)
W (kN )
i i
W h2
4
3
2
1
3,000
4,200
4,200
4,200
13.8
10.6
7.4
4.2
571.3
471.9
230.0
74.1
1,347.3
0.424
0.350
0.171
0.055
1,000
th
Lateral Force at i
Level for EL in
direction (kN)
X
611
504
246
79
1,440
Y
611
504
246
79
1,440
Figure 1.2 -- Design seismic force on the building for (a) X-direction, and (b) Y-direction
Examples on IS 1893(Part 1)
IITK-GSDMA-EQ21V2.0
Example
11/Page 8