Sunteți pe pagina 1din 6

NPTEL Chemical Mass Transfer Operation 1

MODULE 6
HUMIDIFICATION AND AIR CONDITIONING
LECTURE NO. 8
Example Problem 6.2: It is planned to cool water from 43.30C to 29.40C in a
packed countercurrent water-cooling tower using entering air at 29.40C with a
wet bulb temperature of 23.90C. The water flow is 9764.9 kg/h.m2 and the air flow
is 6835.4 kg/h.m2. The overall mass transfer coefficient is KY/a=2500 kg/m3h
(Y/). Calculate (a) minimum air rate that can be used and (b) tower height
needed if air flow of 6835.4 kg/h.m2 is used.
Given: Height of transfer unit, HtoG=Gs/KY/a. Tie lines are vertical.
Enthalpies of saturated air-water vapor (Base temperature: 00C)
Temperature H/(kJ/kg

H */ (kJ/kg

Temperature

H/(kJ/kg

H */ (kJ/kg

(0C)

dry air)

(0C)

dry air)

dry air)

15.6

43.68

37.8

122.4

148.2

26.7

84.0

40.6

139.4

172.1

154.8

197.2

dry air)

29.4

71.7

97.2

43.3

32.2

88.4

112.1

46.1

224.5

35.0

105.4

128.9

60.0

461.5

Solution 6.2:

Y1/ =0.0165 kg/kg dry air [From Psychrometric chart]


H1/ =71.7 kJ/kg
H 2/ =154.8 kJ/kg
From Graph, at Gs, min, H 2/ =197 kJ/kg at 43.30C

Joint initiative of IITs and IISc Funded by MHRD

Page 1 of 6

NPTEL Chemical Mass Transfer Operation 1

(a) Gs, min=4546.4 kg/h.m2.

240

Equilibrium line
Operating line

220
200
180
160

'

'

P(TL2,H2)

140
120
100
80
'

60

Approach

Tas

25

Q (TL1,H1)
30

TL1

Range

35

40

50

TL2

TG, TL

TL

H/

H */

1/[ H */ -H/]

29.4

71.7

97.2

0.039216

32.2

88.4

112.1

0.042194

35

105.4

128.9

0.042553

37.8

122.4

148.2

0.03876

40.6

139.4

172.1

0.030581

43.3

154.8

197.2

0.023585

Joint initiative of IITs and IISc Funded by MHRD

45

Page 2 of 6

NPTEL Chemical Mass Transfer Operation 1

0.05

0.04

0.03

1
( H */ H / )
0.02

0.01

0.00
30

31

32

33

34

35

36

37

38

39

40

41

42

43

TL ( C)

NtoG=Area under the curve= (154.8-71.7)0.036148=3.004


HtoG=2.734 m
(b)Tower height= 2.7343.004 m=8.213 m (Ans.)

Joint initiative of IITs and IISc Funded by MHRD

Page 3 of 6

NPTEL Chemical Mass Transfer Operation 1

Example Problem 6.3: A cooling tower of 50 m2 cross-sectional area is required


to cool the warm water from 420C to 290C at a rate of 425250 kg/h. The ambient
air at 320C has a wet-bulb temperature of 220C and air rate (moist) is 6000
kg/h.m2. The overall mass transfer coefficient, KY/ a =740.375 kg/m3h (Y/) where

a is specific interfacial area of air-water contact. Determine (a) the minimum air
rate and (b) overall gas-phase enthalpy transfer units. (c) Keeping other
conditions unchanged, if the wet-bulb temperature is changed to 25.50C, what
will the cold water temperature?
Given: Antoine Equation: ln PAV (bar ) 11.96481

3984.923
, temperature in K.
(T 39.724)

Total pressure is 1 atm.

Solution 6.3:

240

Equilibrium line
Operating line

220
200
180
160

'

'

P(TL2,H2)

140
120
100
80
'

60

Q (TL1,H1)

Approach

Tas

25

30

TL1

Joint initiative of IITs and IISc Funded by MHRD

Range

35

40

TL2

45

50

TG, TL

Page 4 of 6

NPTEL Chemical Mass Transfer Operation 1

TG1=32C, Tw1=22C, From psychrometric chart, Y1/ 0.013 kg / kg dry air

H1/ 65.44 kJ / kg
(a) Draw tangent to equilibrium curve from point Q.
Slope of the operating line for minimum air rate:
S

LcwL
9.37
Gsmin

L=425250/50 kg/h.m2=8505 kg/h.m2


cwL=4.187 kJ/kgC
Gsmin=3800.47 kg/h.m2
Gs=6000/(1+0.013) kg/h.m2 =5923 kg/h.m2
Slope of the operating line for actual air rate:
S

LcwL 8505 4.187

6.006
Gs
5923

Draw operating line with slope 6.006 through point Q. TL2=42C. Locate point P.
(Get H 2/ from graph).
or,

LcwL (TL 2 TL1 ) Gs( H 2/ H1/ )


8505 4.187(42 29) 5923( H 2/ 65.5)
H 2/ 143.6 kJ / kg
H toG

NtoG

Gs
5923

m8m
/
KY a 740.375
H 1/

H 2/

dH /
2.82
( H */ H / )

Height of the cooling tower=82.82 m=22.56 m


(b) Overall gas-phase enthalpy transfer unit (NtoG)=2.82
(c) TL1 is unknown. Height of the cooling tower is same, i.e., 22.56 m. Slope of
the operating line is as before, i.e., 6.006. TL1 should be greater than 29C.
Assume TL1 as 32C.
Joint initiative of IITs and IISc Funded by MHRD

Page 5 of 6

NPTEL Chemical Mass Transfer Operation 1

Get height of the cooling tower.


If height is 22.56 m, 32C is the answer. Otherwise guess another TL1.
Or,
TG1=32C, Tw1=25.5C, From psychrometric chart, Y1/ 0.017 kg / kg dry air

H1/ 75.682 KJ / kg
LcwL (TL 2 TL1 ) Gs( H 2/ H1/ )

8505 4.187(42 TL1 )

6000
(143.6 65.5)
(1 0.017)

TL1=30.8C

Joint initiative of IITs and IISc Funded by MHRD