Documente Academic
Documente Profesional
Documente Cultură
384~388, 2012
http://dx.doi.org/10.5370/JEET.2012.7.3.384
1. Introduction
Ampacity is a term given by Del Mar in 1951 to the
current carrying capacity of a cable [1]. Calculation of the
current-carrying capability, or ampacity of power cables
has been extensively discussed in the literature and is the
subject of several international and national standards.
Ampacity calculation techniques are as old as the cables
themselves. Anders has summarized the history of
ampacity calculations in his book [2]. There are analytical
and numerical approaches to calculate cable ampacity. The
two major international standard associations, the IEEE
and the IEC, have adopted the analytical methods as the
basis for their standards [3-5]. The calculation procedures
in both standards are, in principle, the same and are based
on the model that is proposed by Neher and McGrath paper
[6]. The major difference between them is the use of units
and because of this, the same equations look completely
different. The numerical approaches are mainly based on
finite differences, finite volume or finite elements
techniques. The finite volume technique is better suited for
cable ampacity because of physical condition of this
problem, Anders [7], Nahman [8].
Thermal field problem of underground cable for
different cable route has been studied by many researchers,
Gela [9], Koopmans [10], Al-Ohaly [11], Vaucheret [12].
Ampacity in an underground cable system is determined
by the capacity of the installation to extract heat from the
cable and dissipate it in the surrounding soil and
atmosphere. The maximum operating temperature of a
cable is a function of the damage that the insulation can
suffer as a consequence of high operating temperatures.
The insulation withstands different temperatures as
2. Modeling
In the development of a mathematical model we will use
cable shown in Fig. 1. This is a 145 kV, paperpolypropylene-paper cable with 2000 mm2 copper
segmental conductor and aluminum corrugated sheath. The
outer covering is a PE jacket. The cables are laid in a flat
formation without transposition, in the soil, with ambient
temperature equal to 25o C. The sheaths are cross bounded
with unknown minor section length. The centers of the
cables are below the ground and phases are 0.5 m apart (in
three phase configuration). This laying condition is called
the standard conciliation of this cable. The cable
parameters are provided in Table 1 [14].
385
85 C
System frequency
60 Hz
T1
0.579 oKm/W
T3
0.056 oKm/W
T4
1.276 oKm/W
Current in conductor
1365 A
ys
0.132
yp
0.005
2.8
tan
0.001
0.150
Wc
23.40 W/m
Wd
6.53 W/m
WI
26.92 W/m
Wt
33.45 W/m
Di
Fig. 1
External diameter of
conductor
dc
Fig. 1
Calculated Data
2000 mm
1.02
S
20 [1+ ( - 20)]
20
(1)
where
20 = resistivity of the conductor at 20oC
S = cross-sectional area of conductor
20 = temperature coefficient of resistance at 20oC
= maximum operating temperature
In the second stage, the DC value is modified to take
into account the skin and proximity effects. The resistance
of a conductor when carrying an alternating current is
higher than that of the conductor when carrying a direct
current. The principle reasons for the increase are: skin
effect, proximity effect, hysteresis and eddy current losses
in nearby ferromagnetic materials, and induced losses in
short-circuited non-ferromagnetic materials nearby. The
degree of complexity of the calculations that can
economically be justified varies considerably. Except in
very high voltage cables consisting of large segmental
conductors, it is common to consider only skin effect,
proximity effect, and in some cases, an approximation of
the effect of metallic sheath and/or conduit. The relevant
expression is:
R = R (1+ ys + y p )
(2)
where
ys = skin effect fator
yp = proximity effect fator
When paper and solid dielectric insulations are subjected
to alternating voltage, they act as large capacitors and
charging currents flow in them. The work required to effect
the realignment of electrons each time the voltage direction
changes (i.e., 50 or 60 times a second) produces heat and
results in a loss of real power that is called dielectric loss,
which should be distinguished from reactive loss. For a
unit length of a cable, the magnitude of the required
charging current is a function of the dielectric constant of
386
2
0
(3)
D
18ln i
dc
U
U0 =
3
-9
(4)
(6)
Heat Generation = WI
Case 1:
12 m of route is considered, the length of route is
divided to 3 equal segments and different thermal
resistivity is assigned to the soil (Fig. 2).
(5)
(7)
3. Simulation
The calculation of the ampacity of a cable (with conduit
or without conduit) routed through soil with different
thermal resistivity is very complex. Due to different
thermal resistivity of soil around the cable, 3D
387
system in conduit.
Comparison of ampacity of single phase cable (without
conduit) in homogenous and non-homogenous soil are
shown in Fig. 8, for non-homogenous soil with conduit and
without conduit the variation of ampacity shows similar
trace shape.
4. Simulation Results
Simulations are done for different condition (with
conduit and without conduit) for three phase cable system
(three single phase cable in flat configuration) and single
phase cable.
Comparison of ampacity of three phase cable (with
conduit) in homogenous and non-homogenous soil are
shown in Fig. 5.
Comparison of ampacity of single phase cable (with
conduit) in homogenous and non-homogenous soil are
shown in Fig. 6, for non-homogenous soil with conduit and
without conduit the variation of ampacity shows similar
trace shape.
Comparison of ampacity of three phase cable (without
conduit) in homogenous and non-homogenous soil are
shown in Fig. 7. In non homogenous soil for with conduit
and without conduit the variation of ampacity shows
different trace shapes (Fig. 7). For three phase cable with
conduit (three phases are in a pipe shape conduit) in the
point of view of heat dissipating the conduit acts like single
phase cable and the variation of ampacity shows a trace
shape like single phase cable. But for without conduit each
phase dissipates the heat and thermal field for this system
in the surrounding soil is not the same as three phase
388
5. Conclusion
In the present paper a 3D simulation is introduced for
computation of power cable ampacity in different
conditions of route soil.
From results of the present paper simulations (Figs. 5 to
8) can judge that calculation of cable ampacity for
homogenous soil and non-homogenous soil are not the
same and there is a difference of more than 10%.
Therefore computation of cable ampacity for homogenous
soil and then using the cable in a route with nonhomogenous soil can over load the cable.
[11]
[12]
[13]
[14]
References
L. DeLeon, Calculation of underground cable
ampacity, CYME International T&D, pp 1-6, 2005.
[2] G. L. Anders, Rating of Electric Power CablesAmpacity Calculations for Transmission, Distribution
and Industrial application, McGraw-Hill, 1998.
[3] IEEE Standard, Power Cable Ampacity Tables, IEEE
Std. 835-1994.
[4] IEC Standard 60287, Calculation of the Continues
Current Rating of Cables (100% load factor), 1st
edition 1969, 2nd edition 1982, 3rd edition 1994-1995.
[5] IEC Standard 60287, part 2-1, Calculation of Thermal
Resistances, 1994.
[6] J. H. Neher and M. H. McGrath, The calculation of
the temperature rise and load capability of cable
systems, AIEE Trans. Power App. Syst., vol. 76, pp
752772, 1957.
[7] G. L. Anders and H. S. Radhakrishna, Power cable
thermal analysis with considerationof heat and
moisture transfer in the soil, IEEE Trans. On Power
Delivery, vol. 3, pp 1280-1288, 1988.
[8] J. Nahman and M. Tanaskovic, Determination of the
current carrying capacity of cables using the finite
element method, Electric Power Systems Reasearch,
Elsevier, vol. 61, pp 109-117, 2002.
[9] G. Gela, and J. J. Dai, Calculation of thermal fields
of underground cables using the boundary element
method, IEEE Transaction on Power Delivery, vol. 3,
pp 1341-1347, 1988.
[10] G. Koopmans, G. M. L. M. Van de Wiel, L. J. M. Van
Loon and C. L. Palland, Soil physical route survey
[1]