GENERAL
1.1
1.2
SEC shall be responsible for obtaining all necessary approvals, licenses and
permissions, which are related to design, manufacturing & supply within
SECs scope of supply,. These shall be obtained at appropriate time to
ensure that the construction and commissioning programme can be realised.
2.0
3.0
DUST CONTROL
Dust emission to the air from the the equipment supplied , shall be
controlled by providing suitable dust control systems.
4.0
NOISE CONTROL
4.1
SPEC.NO.
TCE.4857A-C510-01
TITLE
4.2
4.3
OF
Where the requirements stated above are not met within the basic design of
the plant they shall be achieved by the supply under the Contract of suitable
means of noise control, which shall conform to the following requirements:
(a)
(b)
(c)
If above means are not adequate and enclosures are used for noise
abatement, close fitting and easily removable enclosures shall be
provided.
d)
In case the noise level exceeds the limits for the equipment supplied
by SEC , same shall have to be corrected by SEC
5.0
SPEC.NO.
TCE.4857A-C510-01
TITLE
6.0
OF
7.0
8.0
9.0
For ESP the dust concentration at the ESP outlet shall always be below 75
mg/Nm3 with all field in service and 100 mg/Nm 3 with N-1 fields in service
where N is the total number of fields.
10.0
Additional provision shall be made to insert and work with the probe of
pollution control authorities at the following places
a) ID discharge duct
b) Every limb of the flue gas ducts before ESP
11.0
For measuring the dust concentration at the outlet of ESP, sampling pipes
with dummy flanges shall be provided.