CONTAINER SERIES
POWERMODUL
For Type Series 4000
Table of Contents
Table of Contents
Table of Contents ....................................................................................................................................................... 3
1
General description ............................................................................................................................... 4
1
Container................................................................................................................................................. 5
2
Series Powercontainer .......................................................................................................................... 6
3
Container enclosure .............................................................................................................................. 6
4
Generator power control panel ............................................................................................................. 7
5
Gas system ............................................................................................................................................. 8
6
Ventilation system ................................................................................................................................. 9
7
Cooling system for engine cooling water and mixture cooling ...................................................... 10
8
Heat extraction ..................................................................................................................................... 11
9
Exhaust system .................................................................................................................................... 12
10
Lube oil system .................................................................................................................................... 13
11
Genset ................................................................................................................................................... 14
12
MMC / MIP ............................................................................................................................................. 15
General description
Pos : 3 /Grne Wies e/01- S-Allgemeine Beschr eibung @ 23\mod_1362491382045_433021.doc x @ 595427 @ 1 @ 1
General description
Pos : 4.1 /Grne Wies e/02- SA-C ontai ner- Aggregat-Hauptbaugruppen- 10F @ 23\mod_1362491531243_433021.doc x @ 595455 @ @ 1
Pos : 4.3 /Grne Wies e/02- SA- Aggregat Seri e 4000-10N-A @ 23\mod_1363171414675_433021.doc x @ 596824 @ @ 1
MTU Series 4000 (gas engine with generator mounted onto base frame)
Pos : 4.4 /Grne Wies e/02- SA-MMC (z ur Steuerung, R egelung, Di agnos e)-10N- A @ 23\mod_1363171599341_433021.doc x @ 596853 @ @ 1
Pos : 4.5 /Grne Wies e/02- SA-MIP (MTU Interfac e Panel) zur M otorsteuer ung-10N-A @ 23\mod_1363171765507_433021.doc x @ 596882 @ @ 1
MIP (MTU Interface Panel) for engine control, regulating, and diagnosis
Pos : 4.6 /Grne Wies e/02- WO-Generatorleis tungsfeld- 10N- A @ 23\mod_1363171929381_433021.doc x @ 596941 @ @ 1
Ventilation system
Pos : 4.9 /Grne Wies e/02- SA- Khls ys tem fr Motokhl wass er-10N-A @ 23\mod_1363172267443_433021.doc x @ 597028 @ @ 1
Exhaust system
Pos : 4.12 /Gr ne Wi ese/02- WO- Schmi erls ystem- 10N- A @ 23\mod_1363176773689_433021.doc x @ 597465 @ @ 1
The delivery object of MTU Onsite Energy satisfies the requirement specified in the EC
Machinery Directive and in the German directives and standards.
SH-H-150
NOTICE
When using the unit supplied in a foreign country or special regions, MTU Onsite Energy is
not responsible for adherence to the legal or other regulations / standards at the place of use.
SH-H-151
NOTICE
Pos : 7 /Grne Wies e/04-H I-Ausfhr ung- kann-abweichen- 003 @ 23\mod_1363178579772_433021.doc x @ 597547 @ @ 1
The images may not be identical to the actual design since some available customer options
may be hidden or omitted on purpose. Furthermore, any tailor-made designs are not shown in
these images.
SH-H-150
NOTICE
Container
Pos : 9 /Grne Wies e/01- S-Container @ 23\mod_1363178924966_433021.doc x @ 597551 @ 1 @ 1
Container
Pos : 10 /Gr ne Wi es e/02-T X-Container-abg esc hlos sene- Einheit-10N @ 23\mod_1363179561043_433021.doc x @ 597580 @ @ 1
This container is a complete enclosure and comprises all necessary component necessary for the safe operation of
the generators contained therein. This container unit has been thoroughly tested and is ready to use after
connecting the necessary media at the client's site (fuel gas, power connections, third-party supply auxiliary drives,
heat provided by the customer (if applicable). The tasks performed are limited to the installation of the roof
structures (if applicable), connecting interfaces as described above, as well as those operating fluids available
(cooling water, lubricants, etc.).
The container enclosure provides the necessary protection from the environment. The containment enclosure
ensures that the noise created by the gas generators are kept to a predefined residual volume.
Access and maintenance doors are provided. Furthermore, certain structural elements are installed that make it
possible to move components in and out of the container.
In order to protect the environment, the floor plates of the container are designed as an oil sump and equipped with
detection devices (holding capacity 110 % of the fluids inside the container). This is compliant with the WHG
(German Federal Water Act).
Depending on the series or their application, the technical data of the containers may change.
Pos : 11 /Gr ne Wi es e/05-FO- 0050-001 @ 43\mod_1377864378483_0.doc x @ 779526 @ @ 1
Series Powercontainer
Pos : 13 /Gr ne Wi es e/01-S- Baurei he Powercontainer @ 23\mod_1363183641927_433021.doc x @ 598628 @ 1 @ 1
Series Powercontainer
Container enclosure
A modified version of the ISO 40ft High Cube Container is the basis for this structure that will be used for special
applications.
The container is stackable and easy to transport (CSC certified).
Basically, the container is divided into two rooms.
The machine room contains the generator, the control system, and the auxiliary drives. The radiator room is a
separate area.
The generator is placed on the support rails that are anchored into the floor. All other components that are
necessary for the operation of the generator, e.g., gas, lubrication oil, or cooling system as well as the control units
and the generator's power control panel are located here.
The second partitioned area of the container houses the necessary heat exchangers for cooling the engine and
mixture. Installation of the plate heat exchanger and optimizing the use of the generated heat.
The connections provided by the customer include gas, power supply, and auxiliary drives and are located along
the side wall.
Connections for utilizing the heat (optional) of the engine cooling water are located on the container's roof.
Pos : 17 /OX-Seitenumbruc h @ 0\mod_1218433559331_0.doc x @ 441052 @ @ 1
Pos : 19 /Gr ne Wi es e/02-SA-Gener atorleistungs fel d-montier t-in-Seitenwand- 10N @ 23\mod_1363184794920_433021.doc x @ 598744 @ @ 1
The generator's power control panel is completely wired and mounted onto the side wall of the container.
Pos : 20.1 /Gr ne Wi ese/02-SA-Bestehend-aus-Hauptkomponenten- 10F @ 23\mod_1363184942826_433021.doc x @ 598773 @ @ 1
Pos : 20.3 /Gr ne Wi ese/02- WO- Kundenansc hlusss ys tem- 10N- A @ 23\mod_1363185147167_433021.doc x @ 598831 @ @ 1
Pos : 20.4 /Gr ne Wi ese/02- WO- Vers orgung-Hilfs antriebe- 10N- A @ 23\mod_1363185213806_433021.doc x @ 598860 @ @ 1
Pos : 20.5 /Gr ne Wi ese/02-SA-Kl emmen-Sc hnitts tell en- Kundenkommuni kation-10N-A @ 23\mod_1363185277742_433021.doc x @ 598889 @ @ 1
The generator power control panel is the interface to the customer's network.
This sub-assembly will also be used when disconnecting the system from the main power supply.
All necessary external feed-in lines for the most important axillary drives which are necessary for the safe
operation are supplied via a separate feed-in point.
Accessibility/operation of the above-mentioned components from the outside.
Place of installation is along the side wall of the container.
Pos : 22 /Gr ne Wi es e/05-FO- 0050-003 @ 43\mod_1377864735088_0.doc x @ 779615 @ @ 1
SH-H-150
NOTICE
Gas system
Pos : 25 /Gr ne Wi es e/01-S- Gass ystem @ 23\mod_1363253009628_433021.doc x @ 599042 @ 1 @ 1
Gas system
Pos : 26 /Gr ne Wi es e/02-SA-Gass ystem- Komplett betriebsfertige Gasreg elstrec ke- 10N @ 23\mod_1363253128702_433021.doc x @ 599071 @ @ 1
Gas filter
Pos : 27.3 /Gr ne Wi ese/02- WO-Z wei Mag netventil- 10N- A @ 23\mod_1363254035960_433021.doc x @ 599158 @ @ 1
Pos : 27.5 /Gr ne Wi ese/02- WO- Ventildic htheits kontroll e-10N-A @ 23\mod_1363254357702_433021.doc x @ 599216 @ @ 1
Pos : 27.6 /Gr ne Wi ese/02- WO- Edelstahls chl auchl eitung-10N-A @ 23\mod_1363254575352_433021.doc x @ 599245 @ @ 1
Pos : 27.7 /Gr ne Wi ese/02- WO- Abs perreinric htung-10N-A @ 23\mod_1363254654881_433021.doc x @ 599274 @ @ 1
Shut-off devices
Pos : 27.8 /Gr ne Wi ese/02- WO- Sicherheits absperr ventil-10N-A @ 23\mod_1363254997088_433021.doc x @ 599303 @ @ 1
A safety shutoff valve is included for the installation into the gas line outside of the container.
Pos : 28 /Gr ne Wi es e/02-T X-Gass ystem-Sic herheits ventil-Sc hnittstelle-Kunde-10N @ 23\mod_1363255363331_433021.doc x @ 599360 @ @ 1
A welded DIN-compliant flange in the container wall is used to provide an interface to the customer.
Pos : 29 /Gr ne Wi es e/05-FO- 0050-004 @ 43\mod_1377864903336_0.doc x @ 779645 @ @ 1
Pos : 30 /Gr ne Wi es e/04-HI- Siehe- Bedienungs anl eitung-Hers tell erdokumente-006 @ 23\mod_1363330661425_433021.doc x @ 599679 @ @ 1
NOTICE
SH-H-150
Compliance with the currently valid specifications for fluids and lubricants is mandatory!
SH-H-023
INFORMATION
Ventilation system
Pos : 33 /Gr ne Wi es e/01-S- Lftungss ystem @ 23\mod_1363331865998_433021.doc x @ 599712 @ 1 @ 1
Ventilation system
A ventilation system is integrated into the container and ensures the following features.
Pos : 34.2 /Gr ne Wi ese/02-SA-Sic herstell en der Mi ndestl uftmenge-10N-A @ 49\mod_1405590630278_433021.doc x @ 831730 @ @ 1
It ensures the proper amount of compressed air is supplied to the machine base (cp. safety concept).
Pos : 34.3 /Gr ne Wi ese/02-SA-Fr der ung der Verbr ennungsl uft des M otors-10N-A @ 23\mod_1363333564916_433021.doc x @ 599799 @ @ 1
Transporting the cooling air for the generator and other components installed in the system.
One or several fans are used to carry the necessary amount the air.
The operating mode of the fans as well as their activation may be indifferent, depending on the series of the
container.
Pos : 36 /Gr ne Wi es e/03-T K-Lftungss ystem-Powerc ontai ner-CHP-Container-10N @ 23\mod_1363338543211_433021.doc x @ 599915 @ @ 1
Powercontainer
CHP Container
Sound dampeners
Pos : 37.4 /Gr ne Wi ese/02-SA- Wetters chutz- Klei ntiergitter-10N-A @ 23\mod_1363342983453_433021.doc x @ 600002 @ @ 1
Pos : 38 /Gr ne Wi es e/03-T K-Lftungss ystem-Zul uft- Abl uft- 10N @ 23\mod_1363343362113_433021.doc x @ 600088 @ @ 1
Outlet
Inlet
SH-H-150
NOTICE
Pos : 43 /Gr ne Wi es e/02-SA-Khls ystem-Abfuhr- anfall ender- Abwr me-Gas motor-10N @ 23\mod_1363350276004_433021.doc x @ 600245 @ @ 1
For removal, the waste heat of the gas engine complete cooling systems are mounted.
Pos : 44.1 /Gr ne Wi ese/02-SA-Das Khls ystem-z wei-getrennte- Kreis e-10F @ 23\mod_1363350589228_433021.doc x @ 600274 @ @ 1
Pos : 44.3 /Gr ne Wi ese/02-SA-Motor khl wass er kreis- 10N- A @ 23\mod_1363351298393_433021.doc x @ 600303 @ @ 1
Pos : 45 /Gr ne Wi es e/02-T X-Khls ys tem-F rderung-der-Khl medi en- 10N @ 23\mod_1363854702342_433021.doc x @ 600595 @ @ 1
The cooling system must be filled with a mixture of water and antifreeze/corrosion protection agent in accordance
with the fluids and lubricants specifications of MTU Onsite Energy.
An electrical pump is used to deliver the cooling media. Mechanically or electrically operated mixing valves are
used to control the necessary temperatures in the cooling system.
Radiators with electric fans are integrated into the container and ensure the heat exchange to the surroundings.
The design of the radiators (sandwich/split core etc.) can vary.
Pos : 46 /Gr ne Wi es e/05-FO- 0050-006 @ 43\mod_1377865091240_0.doc x @ 779705 @ @ 1
SH-H-150
NOTICE
10
Heat extraction
Pos : 49 /Gr ne Wi es e/01-S- Wrmeaus kopplung @ 23\mod_1363855588736_433021.doc x @ 600653 @ 1 @ 1
Heat extraction
Pos : 50 /Gr ne Wi es e/02-T X-Wr meaus kopplung-des HT-Kr eises-10N @ 23\mod_1363855681389_433021.doc x @ 600682 @ @ 1
The heat extraction (optional) of the HT circuits is realized by using plate heat exchangers and can be used by the
customer for subsequent applications (heat circuit, process heat, etc.). These plate heat exchangers are the
hydraulic separation of the systems.
Pos : 51 /Gr ne Wi es e/04-HI- Siehe- Bedienungs anl eitung-005 @ 23\mod_1363343627308_433021.doc x @ 600142 @ @ 1
SH-H-150
NOTICE
11
Exhaust system
Pos : 53 /Gr ne Wi es e/01-S- Abg ass ys tem @ 23\mod_1363856175429_433021.doc x @ 600711 @ 1 @ 1
Exhaust system
Expansion joints
Pos : 55.4 /Gr ne Wi ese/02- WO- Abgassc hall dmpfer-10N-A @ 23\mod_1363856843170_433021.doc x @ 600827 @ @ 1
Pos : 55.5 /Gr ne Wi ese/02- WO-Oxi dati ons katal ys ator-10N-A @ 23\mod_1363856907418_433021.doc x @ 600856 @ @ 1
Pos : 55.6 /Gr ne Wi ese/02- WO- Abgas wr metaus cher-10N-A @ 23\mod_1363857001260_433021.doc x @ 600885 @ @ 1
In the following features are provided with the installed exhaust gas system:
Pos : 56.2 /Gr ne Wi ese/02-SA-Abgas s ystem-Reduzier ung-des Abgasger us ches-10N-A @ 23\mod_1363857281348_433021.doc x @ 600971 @ @ 1
Pos : 56.3 /Gr ne Wi ese/02-SA-Abgas s ystem-Ei nhaltung-der Emissionen- 10N- A @ 23\mod_1363857461904_433021.doc x @ 601000 @ @ 1
Compliance with the necessary emission rules (when utilizing the option of oxidation catalytic
converter)
Pos : 56.4 /Gr ne Wi ese/02-SA-Abgas s ystem-Abfhr ung-Verbr ennungs abg ase- 10N-A @ 23\mod_1363857668550_433021.doc x @ 601029 @ @ 1
Pos : 57 /Gr ne Wi es e/02-T X-Abgass ys tem-M ontag eort- des- Abg ass ys tems- 10N @ 23\mod_1363858697916_433021.doc x @ 601086 @ @ 1
The design or installation location of the exhaust gas system may vary depending on the requirements, scope, etc.
of the system.
Utilization of the exhaust gases (optional) can be achieved with the help of a waste-gas heat exchanger. In this
case, it will be installed outside of the container.
Pos : 58 /Gr ne Wi es e/05-FO- 0050-007 @ 43\mod_1377865153848_0.doc x @ 779735 @ @ 1
SH-H-150
NOTICE
12
10
Completely installed lubricating oil system for the necessary supply of lubricants for the installed engines.
Pos : 63.1 /Gr ne Wi ese/02-SA-Bestehend-aus-Komponenten- 10F @ 23\mod_1363253767216_433021.doc x @ 599100 @ @ 1
Oil pump (mounted to the base frame of the generator) for pre-lubrication/emptying the oil sump
Pos : 63.3 /Gr ne Wi ese/02-SA-Sc hmi erls ys tem-M agnetventil e-Abs perrung-10N-A @ 23\mod_1363860768210_433021.doc x @ 601231 @ @ 1
Pos : 63.4 /Gr ne Wi ese/02-SA-Sc hmi erls ys tem-N achflltank-10N-A @ 23\mod_1363860881784_433021.doc x @ 601260 @ @ 1
Pos : 63.5 /Gr ne Wi ese/02-SA-Sc hmi erls ys tem- Steuerung-ls ystem-MMC-10N-A @ 23\mod_1363860980327_433021.doc x @ 601289 @ @ 1
Pos : 63.6 /Gr ne Wi ese/02- WO- Schmi erls ystem- Vol umen-10N-A @ 23\mod_1363861083487_433021.doc x @ 601318 @ @ 1
Pos : 63.7 /Gr ne Wi ese/02-SA-Sc hmi erls ys tem- Schl auchanschl uss- 10N- A @ 23\mod_1363861232715_433021.doc x @ 601347 @ @ 1
Pos : 64 /Gr ne Wi es e/04-HI- Standz eiten-Reic hweite-l vol umen- 007 @ 23\mod_1363861707358_433021.doc x @ 601429 @ @ 1
Service life/range of the oil volume depending on the engine variant/operating mode.
SH-H-150
NOTICE
SH-H-150
NOTICE
13
Genset
Pos : 67 /Gr ne Wi es e/01-S- Aggregat @ 23\mod_1363861927305_433021.doc x @ 601433 @ 1 @ 1
11
Genset
In the internal combustion engine the energy contained in the fuel is converted into mechanical work and heat. The
generator which converts the mechanical work into electrical energy is connected to the engine by means of a
flexible coupling. The generator is mounted on two slide rails, so that it can be moved when the coupling element
needs to be replaced. The engine and the generator are connected to the base frame via flexible, vibrationdampening elements.
Pos : 69 /Gr ne Wi es e/05-FO- 0050-008 @ 43\mod_1377865211801_0.doc x @ 779765 @ @ 1
Pos : 70 /Gr ne Wi es e/04-HI- Siehe-F unktions beschr eibung-Aggregat-008 @ 23\ mod_1363862256466_433021.doc x @ 601545 @ @ 1
NOTICE
SH-H-150
SH-H-150
NOTICE
14
MMC / MIP
Pos : 73 /Gr ne Wi es e/01-S-MMC / MIP @ 23\mod_1363862630546_433021.doc x @ 601578 @ 1 @ 1
12
MMC / MIP
All regulators, controllers and monitoring systems, as well as communication to and from outside, are implemented
by means of the hardware and software from inside the control cabinet.
The cabinet is installed inside the machine room. Operation of the control system takes place outside of the
container.
Pos : 75 /Gr ne Wi es e/05-FO- 0050-009 @ 43\mod_1377865267972_0.doc x @ 779795 @ @ 1
For precise and detailed information concerning the control and regulation of the
module / genset, see the MMC operating manual / function description.
SH-H-150
NOTICE
15