Documente Academic
Documente Profesional
Documente Cultură
the
that
the
the
%Overload=
LD=
Steam
Gas
Combine cycle
Diesel
Total
Amount of
Generating Unit
5
1
3
31
303
f
f system
Dispatch Power
(MW)
Where LD=Total load shedding (%),
69,9
OL=Overload (pu), f=Expected frequency
18
(Hz), fsystem=Nominal frequency (Hz), and
51,1
d=load reduction factor.
156,4
295,3
OL
f
d 1
f system
( 1+OL )
1d 1
LoadsRemainGenerator Capacity
RemainGenerator Capacity
Load (MW)
33.1
9.8
18.1
25.7
15.9
75.9
22.8
34.4
57.7
293.4
d=
Percentageload change
Percentagefrequency change
m 0=
60 P step
d
{ t=0=
dt
2H
2 Hs dfs
=Pdiff
fo dt
Where HS=System inertia (s), fo=nominal
frequency (50 Hz), dfs/dt=Rate of change of
frequency (Hz/s), and Pdiff=Total power
difference (pu)
The calculation takes the value of inertia of
system with formulation [2]:
b.
Collect data which is related from
DigSILENT.
c. Perform processing data for load shedding
scheme
and
the
H 1 MVA 1+ H 2 MVA 2+ +
HnMVAn
Hsystem=
establishment of the island.
MVA 1+ MVA 2++d.MVAn
Simulate load shedding scheme and the
establishment
of
the
island
along
with
troubleshooting
when
The amount of disturbance in the system is
problems
occur
in
proportional to the rate of change of frequency.
the simulation.
Total load shedding to stabilize the system must e. Conduct an analysis of the proposed scheme
consider the amount of disturbance. Therefore, defense
and
the total load shedding should consider to the
defense existing defence schemes in East
rate of change of frequency.
Kalimantan
power system.
C. Islanding Based On Generator Coherency
Islanding is an advance defence scheme
when the load shedding unable to return the
system frequency into normal. This scheme will
form several islands that isolated one with one
another. An island consists of generating units
and load that operate locally. Coherency of the
generator is determined by looking at changes
in the swing phase angle between the rotor
generator units when there is a power
imbalance. Group coherent generator is a
generator that has a phase change swing rotor
f
(Hz)
49.3
49.1
48.9
48.7
48.5
49.3
49.1
48.9
48.7
48.5
1
2
3
4
5
Total
Total Load
Shedding
Percentage (%)
15
17
20
23
25
100
1
2
3
4
5
Total
15
17
20
23
25
100
Stage
Total Load
Shedding The proposed defense scheme based on
(MW)
UFR with frequency setting is implemented
6.6
into the system. Disturbance causes the system
7.5
frequency drops to 48.8 Hz and 49.5 Hz in
8.8
steady state point. 47 MW loads has been shed.
10.1
44.1
7.1
9.4
10.8
11.8
47.1
V. CONCLUSION
Proposed defense scheme on East
Kalimantan power system is designed to be
able to overcome large disturbance therefore
setting UFR is not only frequency but also rate
of change of frequency. UFR by setting
frequency can shed the load up to 39.1%
overload.
UFR by rate of change of frequency setting
faster stabilizing the system than just using the
REFERENCES