Sunteți pe pagina 1din 10

Rating of Circuit Breaker | Short Circuit Breaking Making Current

Under Electrical Switchgear

The rating of a circuit breaker includes,


1) Rated short circuit breaking current.
2) Rated short circuit making current.
3) Rated operating sequence of circuit breaker.
4) Rated short time current.
Short Circuit Breaking Current of Circuit Breaker
This is the maximum short circuit current which a circuit breaker can withstand before it.
Finally cleared by opening its contacts. When a short circuit flows through a circuit breaker,
there would be thermal and mechanical stresses in the current carrying parts of the breaker. If
the contact area and cross-section of the conducting parts of the circuit breaker are not
sufficiently large, there may be a chance of permanent damage in insulation as well as
conducting parts of the CB.
As per Joules law of heating, the rising temperature is directly proportional to square of
short circuit current, contact resistance and duration of short circuit current. The short circuit
current continuous to flow through circuit breaker until the short circuit is cleared by opening
operation of the circuit breaker. As the thermal stress in the circuit breaker is proportional to the
period of short circuit, the breaking capacity of electrical circuit breaker, depends upon the
operating time.
At 160C aluminum becomes soft and losses its mechanical strength, this temperature
may be taken as limit of temperature rise of breaker contacts during short circuit.
Hence short circuit breaking capacity or short circuit breaking current of circuit
breaker is defined as maximum current can flow through the breaker from time of occurring

Hanif Insan YA/08

short circuit to the time of clearing the short circuit without any permanent damage in the CB.
The value of short circuit breaking current is expressed in RMS.
During short circuit, the CB is not only subjected to thermal stress, it also suffers
seriously from mechanical stresses. So during determining short circuit capacity, the mechanical
strength of the CB is also considered. So for choosing suitable circuit breaker it is obvious to
determine the fault level at that point of the system where CB to be installed.
Once the fault level of any part of electrical transmission is determined it is easy to
choose the correct rated circuit breaker for this part of network.
Rated Short Circuit Making Capacity
The short circuit making capacity of circuit breaker is expressed in peak value not in rms
value like breaking capacity.
Theoretically at the instant of fault occurrence in a system, the fault current can rise to
twice of its symmetrical fault level. At the instant of switching on a circuit breaker in faulty
condition, of system, the short circuit portion of the system connected to the source. The first
cycle of the current during a circuit is closed by circuit breaker, has maximum amplitude. This
is about twice of the amplitude of symmetrical fault current waveform.
The breakers contacts have to withstand this highest value of current during the first
cycle of waveform when breaker is closed under fault. On the basis of this above mentioned
phenomenon, a selected breaker should be rated with short circuit making capacity. As the rated
short circuit making current of circuit breaker is expressed in maximum peak value, it is
always more than rated short circuit breaking current of circuit breaker. Normally value of short
circuit making current is 2.5 times more than short circuit breaking current.
Rated Operating Sequence or Duty Cycle of Circuit Breaker
This is mechanical duty requirement of circuit breaker operating mechanism. The
sequence of rated operating duty of a circuit breaker has been specified as
O t CO - t' - CO

Hanif Insan YA/08

Where O indicates opening operation of CB. CO represents closing operation


immediately followed by an opening operation without any intentional time delay. t' is time
between two operations which is necessary to restore the initial conditions and / or to prevent
undue heating of conducting parts of circuit breaker. t = 0.3 sec for circuit breaker intended for
first auto re closing duty, if not otherwise specified.
Suppose rated duty circle of a circuit breaker is 0 0.3 sec CO 3 min CO. This
means, an opening operation of circuit breaker is followed by a closing operation after a time
interval of 0.3 sec, then the circuit breaker again opens without any intentional time delay. After
this opening operation the CB is again closed after 3 minutes and then instantly trips without
any intentional time delay.
Rated Short Time Current
This is the current limit which a circuit breaker can carry safely for certain specific time
without any damage in it. The circuit breakers do not clear the short circuit current as soon as
any fault occurs in the system. There always some intentional and an intentional time delays
present between the instant of occurrence of fault and instant of clearing the fault by CB. This
delays are because of time of operation of protection relays, time of operation of circuit breaker
and also there may be some intentional time delay imposed in relay for proper coordination of
power system protection. Even a circuit breaker fails to trip, the fault will be cleared by next
higher positioned circuit breaker. In this case the fault clearing time is longer. Hence, after fault,
a circuit breaker has to carry the short circuit for certain time. The summation of all time delays
should not be more than 3 seconds, hence a circuit breaker should be capable of carrying a
maximum faulty current for at least this short period of time. The short circuit current may have
two major affects inside a circuit breaker.
1. Because of the high electric current, there may be high thermal stress in the insulation
and conducting parts of CB.
2. The high short circuit current, produces significant mechanical stresses in different
current carrying parts of the circuit breaker. A circuit breaker is designed to withstand
these stresses. But no circuit breaker has to carry a short circuit current not more than a

Hanif Insan YA/08

short period depending upon the coordination of protection. So it is sufficient to make CB


capable of withstanding affects of short circuit current for a specified short period. The
rated short time current of a circuit breaker is at least equal to rated short circuit
breaking current of the circuit breaker.
Rated Voltage of Circuit Breaker
Rated voltage of circuit breaker depends upon its insulation system. For below 400 KV
system, the circuit breaker is designed to withstand 10% above the normal system voltage. For
above or equal 400 KV system the insulation of circuit breaker should be capable of
withstanding 5% above the normal system voltage. That means, rated voltage of circuit breaker
corresponds to the highest system voltage. This is because during no load or small load
condition the voltage level of power system is allowed rise up to highest voltage rating of the
system.
A circuit breaker is also subject to two other high voltage condition.
1) Sudden disconnection of huge load for any other cause, the voltage imposed on the CB
and also between the contacts when the CB is open, may be very high compared to higher
system voltage. This voltage may be of power frequency but does not stay for very long
period as this high voltage situation must be cleared by protective switchgear.
But a circuit breaker may have to withstand this power frequency over voltage, during its
normal life span.
The Circuit Breaker must be rated for power frequency withstand voltage for a specific
time only. Generally the time is 60 seconds. Making power frequency withstand capacity,
more than 60 second is not economical and not practically desired as all the abnormal
situations of electrical power system are definitely cleared within much smaller period
than 60 seconds.
2) Like other apparatuses connected to power system, a circuit breaker may have also to
face lighting impulse and switching impulses during its life span.

Hanif Insan YA/08

The insulation system of CB and contact gap of an open CB have to withstand these
impulse voltage waveform amplitude of this disturbance is very very high but extremely
transient in nature. So a circuit breaker is designed to withstand this impulse peaky
voltage for microsecond range only

Power
Nominal
Voltage

System

Highest System

Frequency

Impulse

Voltage

Withstand

Voltage Level

Voltage
11 KV

12 KV

33 KV

36 KV

70 KV

170 KV

132 KV

145 KV

275 KV

650 KV

220 KV

245 KV

460 KV

1050 KV

400 KV

420 KV

Hanif Insan YA/08

Rating CB | Arus Kerja-Nominal Hubung Singkat


Menurut Peralatan Switching Kelistrikan

Rating CB meliputi
1) Rating Arus Kerja Hubung Singkat
2) Rating Arus Nominal Hubung Singkat
3) Rating Urutan Operasi CB
4) Rating Waktu Arus Hubung Singkat
Arus Kerja Hubung Singkat pada Circuit Breaker
Merupakan arus hubung singkat maksimal yang dapat ditahan oleh sebuah circuit
breaker sebelum memutus rangkaian dengan membuka kontaknya. Saat arus hubung singkat
mengalir melalui sebuah CB, akan timbul tekanan termal dan mekanis pada komponen yang
menghantarkan arus. Apabila luas dan penampang kontak tidak cukup besar, akan ada
kemungkinan kerusakan permanen pada isolator, juga konduktor-konduktor Circuit Breaker.
Berdasarkan Hukum Pemanasan Joule, kenaikan temperatur sebanding dengan kuadrat
dari arus hubung singkat, resistansi kontak dan durasi hubung singkat. Arus Hubung Singkat
secara terus menerus mengalir melalui CB hingga hubung singkat dihentikan dengan terbukanya
pengoperasian dari CB. Karena tekanan termal sebanding dengan durasi hubung singkat, maka
kapasitas pemutusan rangkaian oleh CB bergantung pada waktu pengoperasian.

Hanif Insan YA/08

Pada temperatur 160o C, alumunium melunak dan kehilangan kekuatan mekanisnya,


temperatur ini dinyatakan sebagai batas kenaikan temperatur pada kontak CB selama hubung
singkat.
Oleh karena itu, kapasitas pemutusan hubung singkat atau arus kerja hubung
singkat/arus kerja didefinisikan sebagai arus maksimum yang dapat melalui CB dari waktu
terjadinya gangguan hingga waktu pemutusan gangguan hubung singkat tanpa adanya kerusakan
permanen pada CB.
Nilai arus pemutusan hubung singkat dinyatakan dalam RMS. Selama hubung singkat,
CBtidak hanya mengalami tekanan termal, namun juga tekanan mekanis. Jadi, dalam
menentukan kapasitas pemutusan hubung singkat, kekuatan mekanis CB juga dipertimbangkan.
Maka, untuk memilih CB yang tepat, diharuskan menentukan tingkat gangguan pada system
yang akan dipasang CB.
Saat tingkat gangguan dari segala komponen transmisi listrik ditentukan, akan menjadi
mudah untuk memilih CB dengan rating yang tepat untuk jaringan.
Kapasitas Nominal Terhitung Hubung Singkat
Kapasitas nominal CB dinyatakan dalam nilai puncak, tidak seperti kapasitas pemutusan
yang dinyatak dalam rms. Secara teori, pada kejadian gangguan yang seketika di dalam system,
arus gangguan dapat naik hingga dua kali tingkat gangguan simetrisnya. Saat switching yang
seketika pada CB yang mengalami gangguan, bagian hubung singkat pada system terhubung ke
sumber. Siklus pertama arus selama rangkaian tertutup oleh CB, memiliki amplitudo yang
maksimal/paling besar. Yang kira-kira besarnya dua kali lipat dari amplitudo gelombang arus
gangguan simetris.
Kontak-kontak CB harus menahan nilai tertinggi arus selama siklus pertama gelombang
saat pemutus tertutup dalam keadaan gangguan.
Berdasarkan fenomena di atas, sebuah CB yang dipilih harus dihitung dengan kapasitas
pembentukan hubung singkatnya.

Hanif Insan YA/08

Sebagaimana arus nominal hubung singkat terhitung CB dinyatakan dalam nilai puncak
maksimum, nilai tersebut selalu melebihi rating arus pemutusan hubung singkat CB. Normalnya,
besar arus nominal adalah 2,5 kali dari arus pemutusan.
Urutan Kerja Terhitung atau Siklus Kerja CB
Merupakan persyaratan kerja mekanis dari mekanisme pengoperasian CB. Urutan kerja
CB dispesifikasikan dalam
O t CO t CO
Dimana O mengindikasikan operasi pembukaan CB.
CO merepresentasikan operasi penutupan yang segera diikuti dengan operasi pembukaan
tanpa adanya penundaan waktu yang disengaja.
t merupakan waktu diantara dua pengoperasian yang dibutuhkan untuk memulihkan
kondisi awal dan/atau menghindari pemanasan yang tidak semestinya komponen-komponen
konduksi CB. t=0,3 sekon pada CB yang dimaksudkan untuk penutupan otomatis yang pertama
kali, atau sebaliknya.
perkiraan siklus kerja terhitung pada CB adalah
O 0,3 sekon CO 3min CO
Hal ini berarti operasi pembukaan pada CB diikuti dengan operasi penutupan setelah
interval waktu 0,3 sekon, kemudian CB tebuka kembali tanpa waktu jeda. Setelah operasi
terbukanya CB tersebut, CB tertutup kembali setelah 3 menit dan kemudian memutus tanpa jeda
waktu.
Waktu Terhitung Arus Hubung Singkat
Merupakan batas arus yang dapat ditahan CB pada jangka waktu tertentu tanpa
mengalalmi kerusakan.
Circuit Breaker tidak secara langsung menghentikan gangguan yang ada pada system,
namun selalu ada jeda waktu antara mulai terjadinya gangguan dan waktu penghentian

Hanif Insan YA/08

gangguan. Jeda tersebut dikarenakan waktu operasi dari relay proteksi, waktu operasi CB dan
jeda waktu pada relay dalam pengkoordinasian dengan proteksi system tenaga listrik. Saat
sebuah CB gagal trip, gangguan akan dihentikan oleh CB dengan posisi/rating yang lebih tinggi.
Dalam hal ini, waktu penghentian gangguan akan lebih lama. Oleh karena itu, setelah terjadinya
gangguan, CB harus menahan hubung singkat selama jangka waktu tertentu. Penjumlahan
seluruh jeda waktu (seharusnya) tidak lebih dari 3 sekon, karenanya sebuah CB harus mampu
menahan arus maksimum gangguan , minimal selama jeda waktu tersebut.
Arus hubung singkat sangat berpengaruh pada CB dalm dua hal:
1. Karena besarnya arus, akan timbul tekanan termal dalam komponen-komponen insulasi
dan penghantar CB.
2. Besarnya arus hubung singkat menghasilkan tekanan mekanis yang signifikan pada
komponen penghantar arus yang berbeda pada CB
Circuit Breaker didesain untuk menahan tekanan-tekanan tersebut. Namun,tidak ada CB yang
dapat menahan arus hubung singkat tidak lebih dari periode singkat jeda, bergantung pada
koordinasi proteksinya. Maka dari itu, CB cukup didesain untuk mampu menahan pengaruh arus
hubung singkat pada jangka waktu singkat yang spesifik.
Periode singkat arus yang terhitung pada CB setidaknya samam dengan rating arus kerja pada
CB.
Rating Tegangan CB
Rating tegangan CB bergantung pada system insulasinya. Untuk system dibawah 400 kV,
CB didesain untuk menahan tegangan 10% diatas tegangan normal system. Untuk system diatas
atau sama dengan 400 kV, insulasi CB setidaknya mampu menahan tegangan 5% di atas
tegangan normalnya. Artinya, rating tegangan CB berkorespondensi dengan tegangan tertinggi
system. Dikarenakan, pada saat kondisi tanpa beban atau beban rendah, tegangan system
memungkinkan untuk naik pada tingkat tertingginya.
Circuit Breaker juga terdampak pada dua kondisi tegangan tinggi.
1. Pemutusan beban besar yang tiba-tiba karena sebab-sebab yang lain, tegangan yang
terbebani pada CB dan di antara kontak-kontak CB yang terbuka, bisa sangat tinggi bila
Hanif Insan YA/08

disbanding dengan tegangan tinggi system. Tegangan ini dapat menjadi penguat
frekuensi, namun tidak dapat bertahan dalam jangka waktu yang lama karena kondisi
tegangan tinggi tersebut harus dihentikan dengan peralatan proteksi.
Namun, CB harus menahan kekuatan frekuensi terhadap tegangan, selama rentang waktu
pengoperasiannya (usia).
Circuit breaker sebaiknya terhitung untuk kekuatan frekuensi yang menahan tegangan
untuk jangka waktu tertentu saja, yang biasanya selama 60 sekon. Mengatur kapasitas
penahanan kekuatan frekuensi lebih dari 60 sekon tidaklah ekonomis dan secara praktek
tidak diinginkan karena segala situasi gangguan pada system tenaga listrik sebenarnya
dihentikan dalam waktu kurang dari 60 sekon.
2. Seperti halnya peralatan yang lain yang terhubung pada system tenaga listrik, sebuah
Circuit Breaker juga mengalami impulse pembakaran dan impulse karena switching
selama usia pengoperasiannya. System insulasi CB dan celah kontak CB yang terbuka
harus menahan impuls tersebut. Amplitudo tegangan dari gangguan tersebut sangatlah
tinggi, namun secara ekstrim mengalami peralihan alami. Maka, sebuah CB didesain untuk
menahan impuls tegangan puncak tersebut dalam satuan mikrosekon saja.

Tegangan

Nominal Tegangan Sistem

Kuat

Frekuensi

Menahan

Tingkat

Sistem

Tertinggi

11 KV

12 KV

33 KV

36 KV

70 KV

170 KV

132 KV

145 KV

275 KV

650 KV

220 KV

245 KV

460 KV

1050 KV

400 KV

420 KV

Tegangan

Hanif Insan YA/08

Tegangan

Impuls

S-ar putea să vă placă și