SYMBOLS & UNITS


Nominal Voltage
System Supply Frequency
Rated Primary CT Current
Rated Secondary CT Current
Rated Current of the Protection IED
Primary Short Circuit Current
Single conductor length from CT to Relay
Cross Sectional Area of Conductor
Secondary Resistance of the CT
Maximum through fault current
Rated equivalent secondary e.m.f of CT

2.0.0

DESIGN INPUTS

2.1.1

System Parameters

2.1.2

kV
Hz
A
A
A
A
m
mm2

A
V

System Voltage

Vsys

System Supply Frequency

50

Hz

Primary Short Circuit Current

ISC

40

kA

Primary winding voltage

UPN

400

kV

Secondary winding voltage

USN

220

kV

Rated power of the transformer

SN

120

MVA

Impedance of voltage at specifed current as a percentage

uz

12.5

Percentage impedance at negative tap of 0.9

%Zlt

11.25

Selected Tap

IPN

500

Nominal Secondary Current

ISN

CT Secondary Winding Resistance

RCT

10

Rated short circuit current

ISC

40

kA

Rated Short-time Thermal current

Ith

40

kA for 1sec

400 kV

CT Parameters
CT Ratio

CT Lead Details

2.1.3

Maximum operating temperature of Copper wires

20

Single conductor length from CT to Relay

360

Number of runs of conductor

Cross Sectional Area of Conductor

2.5

mm2

Unit AC Lead Resistance

rL

7.41

Relay Make

SIEMENS

Relay Model

7SJ62

Relay Parameters

2 of 22

Rated burden of the protection IED

SR

0.05

VA

Rated current of the protection IED

IR

Resistance of the protection IED

Rr

SR / IR2

Design factor

0.05

1.2

LARSEN & TOUBRO LIMITED


ECC Division - EDRC
PROJECT STANDARDIZATION OF CT SIZING CALCULATION
TITLE

TRANSFORMER DIFFERENTIAL PROTECTION

DOCUMENT NO

DATE

S0000-E-IE-GE-DC-

05.07.08

PREPARED

CHECKED

SANS

AKL

SHEET

LARSEN & TOUBRO LIMITED


ECC Division - EDRC
PROJECT STANDARDIZATION OF CT SIZING CALCULATION
TITLE

TRANSFORMER DIFFERENTIAL PROTECTION

2.0.0

SYSTEM CALCULATIONS

2.1.1

Resistance of the secondary wire

2.1.2

2.1.3

Resistance of the secondary wire and additional load

Calculation of maximum through fault current,

Rlead

Rb'

DOCUMENT NO

DATE

S0000-E-IE-GE-DC-

05.07.08

PREPARED

CHECKED

SANS

AKL

(2*rL*l)/1000

(2*7.41*360)/1000

5.3352

Rlead + Rrelay

5.336 + 0.05

5.3852

Itf-max :

SHEET

Fault MVA / [sqrt(3) x Vsys]

Where,
Fault MVA

Therefore, Maximum through fault current

Trafo. Rating / % Imp. at Lowest tap

120 / 0.1125

1066.667

Itf-max :
:

MVA

1066.667*10^6 / [1.732 x 220*10^3]


2799.27

LARSEN & TOUBRO LIMITED


ECC Division - EDRC
PROJECT
TITLE

STANDARDIZATION OF CT SIZING CALCULATION


TRANSFORMER OVERCURRENT PROTECTION

DOCUMENT NO

DATE

S0000-E-IE-GE-DC-

05.07.08

PREPARED

SHEET

CHECKED

SANS

AKL

CT SIZING CALCULATION
OVERCURRENT PROTECTION

LARSEN & TOUBRO LIMITED


ECC Division - EDRC
PROJECT
TITLE

STANDARDIZATION OF CT SIZING CALCULATION


TRANSFORMER OVERCURRENT PROTECTION

DOCUMENT NO

DATE

S0000-E-IE-GE-DC-

05.07.08

PREPARED

SHEET

SANS

CHECKED
AKL

INDEX
0.0.0

PURPOSE AND SCOPE

1.0.0

SYMBOLS & UNITS

2.0.0

REFERENCE STANDARDS

3.0.0

ASSUMPTIONS

4.0.0

DESIGN INPUTS

5.0.0

CALCULATION

6.0.0

RESULT

LARSEN & TOUBRO LIMITED


ECC Division - EDRC
PROJECT
TITLE

0.0.0

STANDARDIZATION OF CT SIZING CALCULATION


TRANSFORMER OVERCURRENT PROTECTION

DOCUMENT NO

DATE

S0000-E-IE-GE-DC-

05.07.08

PREPARED

SHEET

SANS

CHECKED
AKL

PURPOSE AND SCOPE


The purpose of this document is to select proper CT Sizing Calculation for Overcurrent Protection

1.0.0

2.0.0

SYMBOLS & UNITS


Vk

Minimum required knee point Voltage

Ipn

CT Primary current

Isn

Nominal Secondary current

SR

Burden of protection IED

VA

IR

Rated current of the protection IED

Rlead

Resistance of Secondary wire and additional load

Rrelay

Relay burden

Single conductor length from CT to relay

A
Ith

Area of cross section of conductor

mm2

Rated Short-time Thermal current

Idyn

Rated dynamic current

REFERENCE STANDARDS
IEC 60044-1
IEC 60044-6

3.0.0

ASSUMPTIONS
NA

LARSEN & TOUBRO LIMITED


ECC Division - EDRC
PROJECT
TITLE

4.0.0

STANDARDIZATION OF CT SIZING CALCULATION


TRANSFORMER OVERCURRENT PROTECTION

DOCUMENT NO
S0000-E-IE-GE-DC-

05.07.08

PREPARED

SHEET

AKL

DESIGN INPUTS

5.0.0

KNEE POINT VOLTAGE CALCULATION (As per IEC 44-6)

5.1.1

Rated symmetrical short circuit current factor

5.1.3

CHECKED

SANS

Rated Resistive Burden

5.1.2

DATE

Dimensioning Parameter

The Excitation limiting secondary voltage

Rated Knee point e.m.f.,

KSSC

Eal

ISC / IPN

40*1000 / 500

80.00

2*KS

2*1.2

2.40

K*KSSC*(RCT+Rb)*ISN

2.4*80*(10+5)*1

2880.00

Eknee :

VA

Eal/1.2

2880/1.2

2400.00

LARSEN & TOUBRO LIMITED


ECC Division - EDRC
PROJECT
TITLE

STANDARDIZATION OF CT SIZING CALCULATION


TRANSFORMER OVERCURRENT PROTECTION

DOCUMENT NO

DATE

S0000-E-IE-GE-DC-

05.07.08

PREPARED

SHEET

CHECKED

SANS

AKL

6.0.0

RESULT

6.1.1

Relay make

ABB

6.1.2

Relay type

RET670

6.1.3

Selected tap

500

6.1.4

Nominal Secondary Current

6.1.5

Cross Sectional Area of Conductor

#REF!

mm2

6.1.6

Knee Point Voltage

2400.00

LARSEN & TOUBRO LIMITED


ECC Division - EDRC
PROJECT
TITLE

STANDARDIZATION OF CT SIZING CALCULATION


TRANSFORMER OVERCURRENT PROTECTION

DOCUMENT NO

DATE

S0000-E-IE-GE-DC-

05.07.08

PREPARED

SHEET

SANS

CT SIZING CALCULATION
OVERCURRENT PROTECTION

CHECKED
AKL

LARSEN & TOUBRO LIMITED


ECC Division - EDRC
PROJECT
TITLE

STANDARDIZATION OF CT SIZING CALCULATION


TRANSFORMER OVERCURRENT PROTECTION

DOCUMENT NO

DATE

S0000-E-IE-GE-DC-

05.07.08

PREPARED

SHEET

SANS

CHECKED
AKL

INDEX
0.0.0

PURPOSE AND SCOPE

1.0.0

SYMBOLS & UNITS

2.0.0

REFERENCE STANDARDS

3.0.0

ASSUMPTIONS

4.0.0

DESIGN INPUTS

5.0.0

CALCULATION

6.0.0

RESULT

LARSEN & TOUBRO LIMITED


ECC Division - EDRC
PROJECT
TITLE

0.0.0

STANDARDIZATION OF CT SIZING CALCULATION


TRANSFORMER OVERCURRENT PROTECTION

DOCUMENT NO

DATE

S0000-E-IE-GE-DC-

05.07.08

PREPARED

SHEET

SANS

CHECKED
AKL

PURPOSE AND SCOPE


The purpose of this document is to select proper CT Sizing Calculation for Overcurrent Protection

1.0.0

2.0.0

SYMBOLS & UNITS


Vk

Minimum required knee point Voltage

Ipn

CT Primary current

Isn

Nominal Secondary current

SR

Burden of protection IED

VA

IR

Rated current of the protection IED

Rlead

Resistance of Secondary wire and additional load

Rrelay

Relay burden

Single conductor length from CT to relay

Area of cross section of conductor

mm2

REFERENCE STANDARDS
IEC 60044-1
IEC 60044-6

3.0.0

ASSUMPTIONS
NA

LARSEN & TOUBRO LIMITED


ECC Division - EDRC
PROJECT
TITLE

4.0.0

STANDARDIZATION OF CT SIZING CALCULATION


TRANSFORMER OVERCURRENT PROTECTION

DOCUMENT NO

DATE

S0000-E-IE-GE-DC-

05.07.08

PREPARED

SHEET

CHECKED

SANS

AKL

DESIGN INPUTS
KALF'

Required minimum effective accuracy limiting factor =

20

PBN

Selected VA burden for CT core

VA

LARSEN & TOUBRO LIMITED


ECC Division - EDRC
PROJECT
TITLE

STANDARDIZATION OF CT SIZING CALCULATION


TRANSFORMER OVERCURRENT PROTECTION

DOCUMENT NO

DATE

S0000-E-IE-GE-DC-

05.07.08

PREPARED

SHEET

CHECKED

SANS

AKL

5.0.0

KNEE POINT VOLTAGE CALCULATION

5.1.1

Maximum short-circuit current

Ihighsetpoint :

5.1.2

Rated accuracy limiting factor

KALF :

((RBC+RCT)/(RBN+RCT))*KALF'

Connected VA to CT core with 20% Design margin,

PBC

1.2*External Burden

1.2*5.3852

6.47

PBC/ISN2

6.47/1

6.47

PBN/ISN2

5/1

Connected Burden Resistance

Nominal Burden Resistance

Therefore,

RBC

RBN

KALF :
:

2799.27

VA

((6.47+10)/(5+10))*20
21.96

LARSEN & TOUBRO LIMITED


ECC Division - EDRC
PROJECT
TITLE

5.1.3

5.1.4

STANDARDIZATION OF CT SIZING CALCULATION


TRANSFORMER OVERCURRENT PROTECTION

Required symmetrical short-circuit current factor,

Effective symmetrical short-circuit current factor,

Since, KSSC KALF


5.1.5

Minimum required knee point voltage,

DOCUMENT NO

DATE

S0000-E-IE-GE-DC-

05.07.08

PREPARED

SHEET

CHECKED

SANS
K'SSC :

AKL
Max [IHighestpoint/Ipn , 20]

MAX[2799.28/500 , 20]

20

K'SSC :

KSSC*(RCT+Rb) / (RCT+R'b)

21.96*(10+5) / (10+5.3852)

21

Vk

(IHighsetpoint/1.3*IPN)*(RCT+R'b)*ISN

(2799.28/1.3*500)*(10+5.39)*1

66.26

6.0.0

RESULT

6.1.1

Relay make

SIEMENS

6.1.2

Relay type

7SJ62

6.1.3

Selected tap

500

LARSEN & TOUBRO LIMITED


ECC Division - EDRC
PROJECT
TITLE

STANDARDIZATION OF CT SIZING CALCULATION


TRANSFORMER OVERCURRENT PROTECTION

DOCUMENT NO

DATE

S0000-E-IE-GE-DC-

05.07.08

PREPARED

SHEET

CHECKED

SANS

AKL

6.1.4

Nominal Secondary Current

6.1.5

Cross Sectional Area of Conductor

#REF!

mm2

6.1.6

Knee Point Voltage

66.26

LARSEN & TOUBRO LIMITED


ECC Division - EDRC
PROJECT

STANDARDIZATION OF CT SIZING
CALCULATION

DOCUMENT NO
S0000-E-IE-GE-DC-

05.07.08

TITLE

TRANSFORMER OVERCURRENT
PROTECTION

PREPARED

SHEET

SANS

DATE
CHECKED
AKL

CT SIZING CALCULATION
OVERCURRENT PROTECTION

LARSEN & TOUBRO LIMITED


ECC Division - EDRC
PROJECT

STANDARDIZATION OF CT SIZING
CALCULATION

DOCUMENT NO
S0000-E-IE-GE-DC-

05.07.08

TITLE

TRANSFORMER OVERCURRENT
PROTECTION

PREPARED

SHEET

SANS

DATE
CHECKED
AKL

INDEX
0.0.0

PURPOSE AND SCOPE

1.0.0

SYMBOLS & UNITS

2.0.0

REFERENCE STANDARDS

3.0.0

ASSUMPTIONS

4.0.0

DESIGN INPUTS

5.0.0

CALCULATION

6.0.0

RESULT

LARSEN & TOUBRO LIMITED


ECC Division - EDRC
PROJECT

STANDARDIZATION OF CT SIZING
CALCULATION

DOCUMENT NO
S0000-E-IE-GE-DC-

05.07.08

TITLE

TRANSFORMER OVERCURRENT
PROTECTION

PREPARED

SHEET

0.0.0

SANS

DATE
CHECKED
AKL

PURPOSE AND SCOPE


The purpose of this document is to select proper CT Sizing Calculation for Overcurrent Protection

1.0.0

2.0.0

SYMBOLS & UNITS


Vk

Minimum required knee point Voltage

Ipn

CT Primary current

Isn

Nominal Secondary current

SR

Burden of protection IED

VA

IR

Rated current of the protection IED

Rlead

Resistance of Secondary wire and additional load

Rrelay

Relay burden

Single conductor length from CT to relay

Area of cross section of conductor

mm2

REFERENCE STANDARDS
IEC 60044-1
IEC 60044-6

3.0.0

ASSUMPTIONS
NA

LARSEN & TOUBRO LIMITED


ECC Division - EDRC
PROJECT

STANDARDIZATION OF CT SIZING
CALCULATION

DOCUMENT NO
S0000-E-IE-GE-DC-

05.07.08

TITLE

TRANSFORMER OVERCURRENT
PROTECTION

PREPARED

SHEET

4.0.0

KNEE POINT VOLTAGE CALCULATION

4.1.1

Minimum required knee point voltage,

CHECKED

SANS

Vk

DATE

AKL

0.5*Itf*(RCT +R'b)*ISN/IPN

5.0.0

RESULT

5.1.1

Relay make

AREVA

5.1.2

Relay type

MICOMP141

5.1.3

Selected tap

5.1.4

Nominal Secondary Current

5.1.5

Cross Sectional Area of Conductor

mm2

5.1.6

Knee Point Voltage

A
1