Documente Academic
Documente Profesional
Documente Cultură
General
Specications
GS 33L01A10-40E
GENERAL
This document provides the overall system specications of the CENTUM VP Systems with Vnet/IP.
SYSTEM CONFIGURATION
Vnet/IP domain
SNTP
Server
Open
Display
Style
Console
HIS
Enclosed
Display
Style
Console
HIS
HIS
Human
Interface
Station
ProSafe-RS
Safety
Instrumented
System
PC for
engineering
(ENG)
SENG
L3SW
Layer 3 switch
Other
Vnet/IP
domains
L3SW
Layer 3 switch
Bus 1
Vnet/IP
Bus 2
SCS
SIOS
System
Integration
OPC Station
Other
PCS
GSGW
Generic
Subsystem
Gateway
APCS
Advanced
Process
Control
Station
V net router
FCS
(for FIO)
ESB bus
Other system
Local node
Other
V net
domains
ER bus
(Subsystem)
Remote node
F01E.ai
GS 33L01A10-40E
Copyright Feb. 2008 (YK)
9th Edition Jun. 2, 2010 (YK)
<<Contents>> <<Index>>
SYSTEM COMPONENTS
Human Interface Station (HIS)
An HIS serves as a human machine interface for
plant operators. Software packages are installed in a
general-purpose personal computer (an IBM PC/AT
compatible computer, hereinafter referred to as a
general-purpose PC). The HIS PC can be assembled
in the console box.
For connections to the Vnet/IP, a VI702 Control Bus
Interface Card is required.
For more information on HIS hardware requirements,
see the following General Specications:
Enclosed Display Style Console Assembly
(GS 33M50B40-40E)
Open Display Style Console Assembly
(GS 33M50B50-40E)
Standard Operation and Monitoring Function
(GS 33M05D10-40E)
Vnet/IP Interface Card (GS 33L50C10-40E)
GS 33L01A10-40E
May 1, 2009-00
<<Contents>> <<Index>>
Vnet/IP
Layer 3 Switch
Layer 2 Switch
This is the COTS (Commercial off-the-shelf) switch
equipment. At least two switches are mandatory for one
Vnet/IP system. The transmission speed for Vnet/IP
has to be 1 Gbps.
V net Router
This is the equipment to connect a Vnet/IP system
and a V net system. This router enables the HIS of
both Vnet/IP and V net to operate the FCS of the other
systems.
The following product is available.
AVR10D: Duplexed V net Router (for redundant use
of communications and power supply
modules)
For information on the hardware specications, see
Duplexed V net Router (GS 33L50D30-40E).
SNTP Server
The time of all the components connected to the
Vnet/IP network is synchronized. By connecting the
COTS SNTP server on the Vnet/IP network, the time
of Vnet/IP components can be synchronized with UTC
(Coordinated Universal Time).
Peripherals Device
Please use compatible models of the peripheral
devices, such as printers, which support the designated
Operation Systems. Consult with a Yokogawa
sales department for more information about those
compatible devices with HIS.
GS 33L01A10-40E
Jun. 1, 2010-00
<<Contents>> <<Index>>
SYSTEM SPECIFICATIONS
Number of Tag
Up to 100,000 per system (when using LHS4000, up to
1,000,000 per system)
Minimum System
A minimum system consists of one HIS with
engineering function and one FCS.
Maximum System
64 components/domain
16 domain/system
256 stations/system
Components:
Human Interface Station (HIS)
Field Control Station (FCS)
Advanced Process Control Station (APCS)
Generic Subsystem Gateway (GSGW)
System Integration OPC Station (SIOS)
Safety Instrumented Systems (ProSafe-RS)
OPC Interface Package (Exaopc) OPC server
Field Communications Server for Plant Resource
Manager (PRM)
V net Router (AVR10D)
On the bus 2, up to 124 general-use Ethernet devices
(including intelligent network devices) other than listed
above can be additionally connected.
Expanded System
The former systems than V net such as HF bus or RL
bus can be connected on a Vnet/IP system through a
bus converter on a V net.
Vnet/IP domains and V net domains can be managed
in the same project, or can be connected with a
Multiple Project Connection Package.
For more information, see Multiple Project Connection
Package (GS 33M05K20-40E).
GS 33L01A10-40E
Jun. 1, 2010-00
<<Contents>> <<Index>>
The Vnet/IP is a real-time process control network used to connect system components. The Vnet/IP supports
two types of communications: control-bus communications and open communications. The Vnet/IP is always dualredundant. Usually, control bus communications are carried out via bus 1. Open communications are carried out via
bus 2. If a control communications error occurs on bus 1, control bus communications will be carried out via bus 2.
The Vnet/IP uses general-purpose communications devices for network connection.
HIS ENG
APCS GSGW
Exaopc
1000BASE-T
Max. 100 m
Up to seven levels of
layer 2 switch
Bus 1
V net router
V net
domain
Bus 2
Layer 2 switch
Layer 2 switch
Vnet/IP domain
BCV-H
HF-bus
domain
Wide-area connection
enabled by dedicated-line
connection
Layer 3
switch
Vnet/IP
domain
Vnet/IP
domain
Layer 3
switch
FFCS-L
F03E.ai
GS 33L01A10-40E
Jul. 1, 2008-00
<<Contents>> <<Index>>
Communications Specications
Control communications
Communication Method: Read/write communication,
message communication, and intercontroller communication
Inter-Controller Communication Period: 100 msec
Open communications
Open communications are executed via bus 2.
Commercially available Ethernet communications
devices can be connected.
The total bandwidth that can be used for open
communications on bus 2 is up to 300 Mbps.
Transmission Path Specications
Network Topology: Star Topology
Transmission Path Redundancy: Available (control
bus communications only)
Transmission Cable: Unshielded twisted pair (UTP) at
enhanced category 5 or better.
Connection
Between
component and
a layer 2 switch
Between layer 2
switches
Between a layer 2
switch and a layer
3 switch
*1:
Cable
Standard
100BASE-TX
(IEEE802.3u)
1000BASE-T
(IEEE802.3ab)
1000BASE-T
(IEEE802.3ab)
1000BASE-LX
(IEEE802.3z)
1000BASE-T
(IEEE802.3ab)
1000BASE-LX
(IEEE802.3z)
Speed
100 Mbps
(*1)
1 Gbps
Maximum
Distance
100 m
1 Gbps
100 m
1 Gbps
5 km
1 Gbps
100 m
1 Gbps
5 km
GS 33L01A10-40E
Jul. 1, 2008-00
<<Contents>> <<Index>>
Maximum Number of
Local Nodes
3
Total Number of
Local and Remote Nodes
3
14
If local nodes are connected to an AFV10S or AFV10D FCU, ESB Bus Coupler Modules (EC401) have to be installed in
slots 7 and 8.
ER Bus
Application
An ER bus is a remote I/O communications bus to connect an FCU or local node unit to the I/O expansion nodes
remotely. The nodes connected on the ER bus are named remote node.
Communication Specications
Connectable Devices: Remote node units (ANR10S, ANR10D)
Number of ER buses: Max. 4 per FCU
Number of Connectable Devices: The number of remote node units that can be connected to an ER bus varies
according to the model and database selected.
Database
Control Function for Standard Field Control Unit
Control Function for Standard Field Control Unit plus Application Capacity
Expansion Package (LFS1530)
*1:
Maximum Number of
Remote Nodes
3
Total Number of
Local and Remote Nodes
3
14 (*1)
14
<<Contents>> <<Index>>
Transmission Path Specications
Network Topology: Bus topology
Transmission Path Redundancy: Available
Transmission Speed: 10 Mbps
Transmission Cable: Coaxial cable (YCB141, YCB311). Use YCB147 ER-bus Adapter and YCB149 ER Bus
Converter Unit for connecting YCB141 and YCB311 cables.
One grounding unit (YCB117) per segment (*1) should be used when connecting YCB311 cable.
Transmission Distance:
YCB141: Max.185 m
When mixing YCB141 and YCB311:
Length of YCB141 + (185/500) x Length of YCB311 185
Number of Bus Adapter Units: Max. 4 per segment (*1)
General-purpose Ethernet Repeater:
The total transmission distance is limited by the number of repeaters.
L 4 - 0.5 n
L: total transmission distance (km)
n: the number of the general-purpose Ethernet repeater (Max. 4 repeaters)
*1:
If repeaters are used on ER bus, each part of the ER bus segregated by a repeater is referred to as a segment.
AFV10D (Node1)
EB401
ER bus
ANR10D (Node2)
EB501
EB401
AFV10D
(Node1)
Repeater
Repeater
Optical Fiber
Cable
Optical Fiber
Cable
Repeater
ANR10D (Node3)
Repeater
EB501
Repeater
Optical Fiber
Cable
Repeater
ANR10D (Node4)
EB501
ANR10D (Node2)
Repeater
Optical Fiber
Cable
Repeater
ER bus
Repeater
EB501
Repeater
Repeater
Repeater
Optical Fiber
Cable
Repeater
Repeater
EB501
ANR10D (Node3)
Repeater
Optical Fiber
Cable
Repeater
EB501
ANR10D (Node4)
F04.ai
<<Contents>> <<Index>>
SOFTWARE
Operation and Monitoring Software
LHS1100 Standard Operation and Monitoring
Function
LHS1120 Console HIS Support Package for
Enclosed Display Style
LHS1130 Console HIS Support Package for Open
Display Style
LHS1150 Server for Remote Operation and
Monitoring Function
LHS2411 Exaopc OPC Interface Package (for HIS)
LHS2412 CENTUM Data Access Library
LHS4000 Million Tag Handling Package
LHS4100 Congured Information Reference
Package
LHS4150 Recorder Output Package
LHS4190 Line Printer Support Package
LHS4200 Consolidated Historical Message Viewer
(Meeting FDA)
LHS4410 Control Drawing Status Display Package
LHS4420 Logic Chart Status Display Package
LHS4450 Multiple Project Connection Package
LHS4600 Multiple-monitor Package
LHS4700 Advanced Alarm Filter Package
LHS6510 Long-term Data Archive Package
LHS6530 Report Package
LHS6600 CS Batch 3000 Process Management
Package
LHS6710 FCS Data Setting/Acquisition Package
(PICOT)
For more information on the above functions, see the
respective GSs.
The following operating systems can be used on HIS
which supports operation, monitoring, and engineering.
Windows Vista Business Edition
Windows XP Professional Edition
Windows Server 2003 Standard Edition
Windows Server 2008 Standard Edition
As for Windows OS and Service Pack, see Standard
Operation and Monitoring Function (GS 33M05D1040E) and Standard Builder Function (GS 33M10D1040E).
If it is necessary to run other third-party software on
the HIS, consult with a Yokogawa sales department to
conrm that it is supported.
Engineering Software
LHS5100
LHS5110
LHS5150
LHS5160
LHS5161
GS 33L01A10-40E
Jun. 2, 2010-00
10
<<Contents>> <<Index>>
Documents
LHS5495 Electronic Document
For more information, see Electronic Instruction
Manual (GS 33M01W10-40E).
INSTALLATION AND
ENVIRONMENTAL CONDITIONS
11
<<Contents>> <<Index>>
The CENTUM VP Entry Class is available for small-scale systems. Up to 8,000 tag names can be used in a CENTUM
VP Entry Class system.
Product
Standard Operation and Monitoring Function
Server for Remote Operation and Monitoring Function
Control Drawing Status Display Package
Logic Chart Status Display Package
CS Batch 3000 Process Management Package
LHM6600
LHM6710
Remarks
Number of operation and monitoring tags : up to 8000
Engineering Software
Entry Class Model
LHM5100
LHM5150
LHM5490
Product
Standard Builder Function
Test Function
Self-documentation Package
Remarks
Restrictions
For CENTUM VP Entry Class, the following restrictions apply.
Only one domain per system
The HIS in a CENTUM VP Entry Class project cannot access the FCSs in other projects of CENTUM VP, CENTUM
VP Entry Class, CENTUM CS 3000 and CENTUM CS 3000 Entry Class.
The HIS in a CENTUM VP Entry Class project can access the FCSs in the Micro-XL system ,but not other former
CENTUM systems.
12
<<Contents>> <<Index>>
REGULATORY COMPLIANCE
*3:
*4:
*5:
*6:
*7:
*8:
*9:
TRADEMARKS
GS 33L01A10-40E
Jun. 1, 2010-00