FOULING RESISTANCES FOR TYPICAL PROCESS APPLICATIONS
Adapted fiom Standards of Tubular Exchanger Manufacturers Association
‘The values given in this table are typical of the situations described, but allowances must be made for
‘substantial variations from one case to the next. The resistances are referenced tothe surface area in contact with tt
{lind snd are to be used in connection with equations of the form of (1.19) end (1.20)
“The waits on the resistances are f° °F / Bi
Lo Water
Temperature of Heating Medium Up to MOF 24°F. - 40°F
Temperature of Water 25°F or lew Over 125°
Types of Water Water Velocity
FtiSec
3itand | Over di.
less
[Sea Water 0.003 ‘0002
Brackish Water 0.003 0.002
\Cooling Tower and Artificial Spray Pond:
‘Treated Makeup 0.001 0.001 0.002 0.002
Untreated 0.003 0.003 0.005 0.004
city or Well Water (Such as
Great Lakes) 0.001 0.001 0.002 0.002,
|creat Lakes 0.001 0.001 0.002 0.002
lRiver Water:
Minions 0.002 0.001 0.003, 0.002
Mississippi 0.003 0.002 | 0.004 0.003
Deleware, Schuylkill 0.003 0.002 0.004 0.003
East River and New York 0.003 0.002 0.00% 0.003
[Bay
‘Chicago Sanitary Canal 0.003 0.006 oon 0.008
[Muddy or Silty 0.003 0.003 0.005 0.005
[rtrd (Over 15 grains/gal) 0.003 0.003 | 000s 0.00,
[Enaine Jacket 0.001 0.001 0.001 0.001
Distilled 0.0005 0.0005 | 0.0005 0.0005
[Treated Boiler Feedwater 0.001 0.0005 | 0.001 0.001
[Boiler Blowdown 0.02 0.002 | 0002 9.002