GRD Journals- Global Research and Development Journal for Engineering | Volume 1 | Issue 6 | May 2016

ISSN: 2455-5703

Wavelet Feature Based Fault Detection and


Classification Technique for Transmission line
Protection
Manish Kurre
PG Student
Department of Electrical and Electronics Engineering
Disha Institute of Management and Technology, Raipur, CG,
India

Shailesh. M. Deshmukh
Assistant Professor & Head of Department
Department of Electrical and Electronics Engineering
Disha Institute of Management and Technology, Raipur, CG,
India

Abstract
In the present scenario, the efficiency of a power system depends on how a fault is accurately detected and classified, so that
quick restoration and maintenance of power is accomplished. Fault detection, fault classification, needs to be performed using a
fast and responsive algorithm at different levels of a power system. Effect of factors such as fault impedance, fault inception
angle (FIA), and fault distance, which cause disturbances in power line can be analyzed by Wavelet based multi resolution
analysis (MRA). This paper proposed, a fault detection and classification technique using MRA based on wavelet transform. The
present paper also deals with the exploration of advantages and problems related with the proposed fault detection and
classification technique. The method of fault detection and classification proposed in this work is based on the three-phase
current and voltage waveforms measured during the occurrence of fault in the power transmission-line. The technique proposed
in this paper, is verified using MATLAB/Simulink software and the obtained results shows that the wavelet based MRA is a
good tool for detection and classification of faults. However it is also shown that the most critical problem related to this
technique is the selection of appropriate threshold values for all the three phases. It has been also shown that this technique
requires expert hands and knowledge of the system for the selection of proper threshold value.
Keywords- Transmission line, fault detection and classification, wavelet feature, multi-resolution analysis

I. INTRODUCTION
The two most important tasks involved in transmission-line relaying are fault detection and classification [19]. These two tasks
must be accomplished in fast and precise manner as much as possible to protect the system from the harmful faults. The
higher accuracy is also important to restore the system efficiently. Interruption of power flow in a power line is mainly due to
the occurrence of faults at various levels. Meanwhile, the reliability and economical aspects of power transfer is highly
affected by the occurrence of the faults which in turn affects the profit from the system. However the performance of the system
can be enhanced by accurate and fast fault detection. Wavelet Transform (WT) [18] conducts both time and frequency domain
analysis of current signals and transients in voltage waveforms and hence provides a tool for detection and classification of faults.
It is usually observed that, the overhead lines are affected by transients, due to the travelling wave phenomenon after the
inception of fault. With the analysis of the faults due to induced transients one can gather handy information which covers a
wide range of aspects like location and detection of fault. Ideally, the identification of mother wavelet signifies the preciseness
of wavelet analysis. The choice of the appropriate mother wavelet depends on the nature of the signal and on the type of
information to be extracted from the signal. In this paper Wavelet multi resolution analysis is used as the solution for
information extraction from transient signals caused by faults. Wavelet family, dB4 (Daubechies) is used as the mother wavelet.
By applying wavelet MRA technique [6], extraction of third level detailed coefficient from the current signal after summation is
performed. The existence of a fault is identified based on the detail coefficients summation magnitude, a generalized algorithm
has been implemented for the transmission line faults classification.

II. DISCRETE WAVELET TRANSFORM


Filter bank theory [1] is the foundation for the development of the discrete wavelet transform (DWT). At level (k), the wavelet
transform coefficients of a signal are determined by using a high pass and a low pass filters. The obtained coefficients of low
pass filter from the earlier stage are then down sampled by a factor two to reduce the dimension. The high pass filter is obtained
from the mother wavelet function and further measures the details coefficients for the input signal. Similarly, the low pass filter
delivers a smoothed version of the input signal and is derived from a scaling function, which is associated to the mother wavelet
function [2] & [3]. For a function s(t), its continuous wavelet transform (WT) can be calculated from the following equation:

All rights reserved by www.grdjournals.com

123

Wavelet Feature Based Fault Detection and Classification Technique for Transmission line Protection
(GRDJE/ Volume 1 / Issue 6 / 021)

1
t-
wr ,m (t )
s (t )
dt

m
m

(1)

1
C (m, )
s(t ) Wr',m (t )dt

m0

(2)

Fundamentally, in the wavelet decomposition, the wavelet function generates a detail version of the decomposed signal
and the scaling function generates the approximated version of the signal that is decomposed. Consequently, Wavelet transform
performs a Conversion of scale versus time signal to amplitude versus time signal.
In the same context, the MRA utilizes the scaling functions along with the wavelet functions as building blocks for
decomposition and construction of signal at different levels of resolution. Wavelet is a waveform of limited duration has an
average value of zero. In general the implementation of discrete wavelet transform is done by using multi resolution analysis. The
transmission line faults in power system are usually classified as Symmetrical faults and Unsymmetrical fault whereas the
three-phase fault is termed as a symmetrical type of fault. A three level wavelet decomposition tree for multi-resolution analysis
used in this paper is shown in figure (1).

Fig. 1: Three level wavelet decomposition used for MRA.

III. SIMULATION STUDY OF DIFFERENT FAULT CASES AND RESULTS


A three-phase transmission line of rating 400 kv and line length of 300 km has been considered for the simulation studies of
various fault cases; their detection and classification. Figure (2) represents the circuit diagram of simulated system in MATLB
Simulink 2013(a). The complete system parameters used for the development of Simulink model are given in appendix A.

Fig. 2: Schematic circuit diagram of simulated system

All rights reserved by www.grdjournals.com

124

Wavelet Feature Based Fault Detection and Classification Technique for Transmission line Protection
(GRDJE/ Volume 1 / Issue 6 / 021)

Three phase fault current obtained at source end for different abnormal conditions are utilized for the fault identification
in simulated transmission line. Sampling time taken for the analysis is 10 ms which relates to sampling frequency of 1 KHz, and
the total no of wavelet level consider is three, third level output corresponds to frequency band of 125 250 Hz. The detail
coefficient of third level wavelet decomposition for the currents in phases A, B and C respectively over different fault inception
angle and locations has been extracted. The extracted detail coefficients have been summed individually denoted as Sa, Sb, Sc
respectively for phase A, B and C. These respective sums are again summed and compared with predefined threshold value for
the detection of the fault in the transmission line. The flow diagram of the fault occurrence detection technique used in this paper
is shown in Figure (3). Where the value of threshold T is selected as T = 4.
Three Phase
Current Signals

Wavelet
Decomposition

Extract High
Frequency Detail
Coefficients

If
(Sa+Sb+Sc)<=0
And Sa<T

No
No Fault

Yes
Fault Classifier

Fig. 3: Fault occurrence detection technique used in this paper.

The waveforms of the phase currents obtained for different fault cases are shown from figure (4) to figure (9).
10
Ia
Ib
Ic

-2

-4

-6

50

100

150

200

250

300

Fig. 4: Ia, Ib, and Ic for LG fault at D== 100 km, FIA = 0, Rf = 0.001
5
Ia
Ib
Ic

-1

-2

-3

-4

50

100

150

200

250

300

Fig. 5: Ia, Ib, and Ic for LG fault at D== 100 km, FIA = 0, Rf = 1

All rights reserved by www.grdjournals.com

125

Wavelet Feature Based Fault Detection and Classification Technique for Transmission line Protection
(GRDJE/ Volume 1 / Issue 6 / 021)

6
Ia
Ib
Ic
4

-2

-4

-6

50

100

150

200

250

300

Fig. 6: Ia, Ib, and Ic for LL fault at D== 200 km, FIA =60, Rf = 0.001
6
Ia
Ib
Ic
4

-2

-4

-6

50

100

150

200

250

300

Fig. 7: Ia, Ib, and Ic for LLG fault at D== 200 km, FIA =60, Rf = 0.001
20
Ia
Ib
Ic
15

10

-5

-10

-15

50

100

150

200

250

300

Fig. 8: Ia, Ib, and Ic for LLL fault at D== 100 km, FIA =0, Rf = 0.001

All rights reserved by www.grdjournals.com

126

Wavelet Feature Based Fault Detection and Classification Technique for Transmission line Protection
(GRDJE/ Volume 1 / Issue 6 / 021)
15
Ia
Ib
Ic
10

-5

-10

-15

-20

50

100

150

200

250

300

Fig. 9: Ia, Ib, and Ic for LLL fault at D== 100 km, FIA =60, Rf = 0.001

Let Sa, Sb, Sc be the summation of 3rdlevel detail coefficients for current signals for a, b, c phases respectively. Table-1
to Table-4, below show the values of Sa, Sb, Sc for different types of faults. From these tables it is observed that the magnitudes
of Sa, Sb, Sc increases whenever any fault occurs in a transmission line. Based on the sampling rate the signal is divided into
four decomposition levels. Among different levels only 3rd level is consider for analysis because the frequency corresponding to
this level is covering 2nd and 3rd harmonics which are dominant in the fault conditions.
Table 1: L-G fault with different fault distances the values of Sa, Sb, Sc with FIA = 0
Fault Location
10 km
30 km
100 km 150 km 200 km
Sa
-22.6535 -10.3160 -3.4470 -2.3011 -1.7086
Sb
-1.0245
-1.0593 -1.0770 -1.0764 -1.0761
Sc
0.4680
0.4333
0.4155
0.4160
0.4165
Table 2: L-L fault with different fault distances the values of Sa, Sb, Sc with FIA = 0
Fault Location
10 km
30 km
100 km 150 km 200 km
Sa

-9.7777

-5.7237

-2.4045

-1.7240

-1.3583

Sb

9.4579

5.4039

2.0847

1.4043

1.0385

Sc
0.3198
0.3198
0.3197
0.3197
0.3197
Table 3: L-L-G fault with different fault distances the values of Sa, Sb, Sc with FIA = 0
Fault Location
10 km
30 km
100 km 150 km 200 km
Sa

-24.6637

-12.3979

-4.7238

-3.3270

-2.5969

Sb

-5.4240

-1.2719

-0.2338

-0.2008

-0.1995

Sc
0.4859
0.5200
0.5572
0.5785
0.5995
Table 4: L-L-L fault with different fault distances the values of Sa, Sb, Sc with FIA = 0
Fault Location
10 km
30 km
100 km 150 km 200 km
Sa

-33.5438

-19.2419

-7.7057

-5.3731

-4.1062

Sb

-14.3145

-8.1274

-3.2171

-2.2452

-1.7089

Sc

47.8584

27.3694

10.9228

7.6183

5.8150

Now the fault classification technique developed in this paper based on the sum of detail coefficients is shown in figure (10).

All rights reserved by www.grdjournals.com

127

Wavelet Feature Based Fault Detection and Classification Technique for Transmission line Protection
(GRDJE/ Volume 1 / Issue 6 / 021)

Fault Detector

Acquire Sa, Sb and Sc from Fault Detector

Is 0< (Sa+Sb+Sc)< T1

YES

Line
FAULT

NO

Is (Sa+Sb+Sc)> T2

Ground
FAULT

Fig. 10: Proposed Fault Classification Technique.

For the proper classification of the faults the selection of threshold values are critical and very much depends on the
system. Here in this paper, the threshold values selected are T1 = 2 and T2 = 5. Finally the complete fault detection and
classification system developed is tested against various faults on the system and the results of this testing is tabulated in Table5.
S. No.
1
2
3
4
5
6
7
8
9
10
11

Table 5: Different fault detection and classification results of proposed technique


Fault Type
Correct detection Classification Result
Phase A to Ground Fault
Yes
Ground Fault
Phase B to Ground Fault
Yes
Ground Fault
Phase C to Ground Fault
Yes
Ground Fault
Phase AB to Ground Fault
Yes
Ground Fault
Phase AC to Ground Fault
Yes
Ground Fault
Phase BC to Ground Fault
Yes
Ground Fault
Phase ABC to Ground Fault
Yes
Ground Fault
Phase A to Phase B Line Fault
Yes
Line Fault
Phase A to Phase C Line Fault
Yes
Line Fault
Phase B to Phase C Line Fault
Yes
Line Fault
Phase A to Phase B to Phase C Line Fault
Yes
Line Fault

From Table-5, it is clearly observable that the proposed wavelet transform based MRA technique is reliable and robust
in accurately detection and classification of different faults occurred in the transmission line. The only limitation of this proposed
technique is the selection of the proper threshold values for comparison of wavelet coefficients during the decision making for
both the detection and classification of faults.

IV. CONCLUSIONS
In this paper, we have proposed a robust and reliable technique for the protection of the 400 kv transmission line. The proposed
technique accurately detects the fault occurrence and also provides the classification of faults in two categories. Furthermore, the
obtained results also confirmed the higher protection efficiency of the proposed technique. The only limitation of this technique
is the selection of proper threshold.

APPENDIX -A
Line data of 400-kV, 300 km length.
Line Length = 300 km
R1 0.249168 /km
All rights reserved by www.grdjournals.com

128

Wavelet Feature Based Fault Detection and Classification Technique for Transmission line Protection
(GRDJE/ Volume 1 / Issue 6 / 021)

L1 0.00156277 H /km

C1 19.469E-9 F/km
R0 0.60241 /km

L0 0.004830 H /km
C0 12.06678E-9 F/km
Source impedance
Sending End
Z S1 17.177 j 45.5285

Z S 0 2.5904 j14.7328
Receiving End
Z S1 15.31 j 45.9245
Z S 0 0.7229 j15.1288

REFERENCES
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]
[11]
[12]
[13]
[14]
[15]
[16]
[17]
[18]
[19]

M. Jayabharata Reddy, and D.K. Mohanta, A wavelet-fuzzy combined approach for classification and location of transmission line faults ,International
journal of Electrical Power and Energy system, Volume 29, Issue 9, pp 669-678, November 2007.
Omar AS, Combined fuzzy-logic wavelet-based fault classification technique for power system relaying, IEEE Trans. On Power Delivery, Vol.19, No.
2, pp.582-589, July 2004.
Biswarup Das and J.Vittal Reddy, Fuzzy-Logic-Based Fault classification , IEEE Trans. On power Delivery, Vol.20, No.2, pp 609-616, April, 2005.
M. M. Tawfik and M. M. Morcos, ANN-Based Techniques for Estimating Fault Location on Transmission Lines using Prony Method, IEEE Trans.
On Power Delivery, Vol. 16, No. 2, pp. 219-224, April 2001.
Gopalakrishnan, M. Kezunovic, S. M. Mckenna, D. M. Hamai,Fault Location using the Distributed Parameter Transmission Line Model, IEEE Trans. On
Power Delivery, Vol. 15, pp. 1169-1174, October, 2000.
D. Chanda, N. K. Kishore, A. K. Sinha, A Wavelet Multi resolution Analysis for Location of Faults on Transmission Lines, Electrical Power & Energy
Systems, Vol. 25, pp.59-69, October, 2003.
H. Osman and O. P. Malik, Protection of Parallel Transmission Lines using Wavelet Transform, IEEE Transactions On Power Delivery, Vol. 19, No. 1,
pp. 49-55, October, 2004.
Ferrero A, Sangiovanni S, Zappitelli E, A fuzzy-set approach to fault type identification in digital relaying, IEEE Trans. On Power Delivery, Vol.
10, No.1, pp. 169-175, July, 2003.
M. Jaya Bharata Reddy, D. K. Mohanta and B. M. Karan, Power System Disturbance Recognition using Wavelet and S-Transform Techniques,
International Journal of Emerging Electric Power Systems, Vol. 1, Issue. 2, pp. 1-16, October, 2004.
Wavelet Toolbox Users Guide by the Math Works, http//:www.mathworks.com, 2006.
Z. Y. He, X. Q. Chen and G. M. Luo, Wavelet entropy measure definition and its application for transmission line fault detection and identification
(part I: Definition and methodology), in Proc. IEEE Int. Conf. Power System Technology, Oct. 2006, pp. 16.
Zhengyou He, Ling Fu, Sheng Lin, and Zhiqian Bo, Fault Detection and Classification in EHV Transmission Line Based on Wavelet Singular
Entropy, IEEE Transactions on Power Delivery, Vol.25, No.4, October 2010.
O. A. S. Youssef, Combined fuzzy-logic wavelet-based fault classification technique for power system relaying, IEEE Trans. Power Del., vol. 19, no. 2,
pp. 582589, Apr. 2004.
V. C. Klema and A. J. Laub, The singular value decomposition: Its computation and some applications, IEEE Trans. Autom. Control, vol. AC- 25, no.
2, pp. 164176, Apr. 1980.
J. Cadzow, SVD representation of unitarily invariant matrices, IEEE Trans. Acoust., Speech Signal Process., vol. 32, no. 3, pp. 512516, Jun. 1984.
C. E. Shannon, A mathematical theory of communication, Bell Syst. Tech. J., vol. 27, pp. 379423, 623656, Jul., Oct. 1948.
S. G. Mallat, A theory for multi-resolution signal decomposition: The wavelet representation, IEEE Trans. Pattern Anal. Mach. Intell., vol. 11, no. 7, pp.
674693, Jul. 1989.
Fernando H. Magnago and Ali Abur, Fault Location Using Wavelets IEEE Transactions on Power Delivery, Vol. 13, No. 4, October 1998.
K. M. Silva, B. A. Souza, and N. S. D. Brito, Fault detection and classification in transmission lines based on wavelet transform and ANN, IEEE
Trans. Power Del., vol. 21, no. 4, pp. 2058--2063, Oct. 2006.