TDXM Modular Series

TDX300S Transient Discriminating Panel Protection


Features
Transient
Discriminating (TD)
Technology provides
increased service life
Modular design
allows individual
modes to be eld
replaceable, built-in
disconnect and fusing
eliminates need for
external fusing
Built-in features
include TD
Technology, thermal
protection, short
circuit current
cartridge fusing and
a surge counter
Status indication ag
per mode, voltage
presence LEDs,
audible alarm and
voltage-free contacts
providing remote
status monitoring

The TDX300 Series of Transient Voltage Surge


Suppressors is designed for critical protection
applications. The 300kA 8/20s of surge protection
exceeds the IEEEC62.41.2 Scenario II single shot
surge rating requirements for exposed service
entrance locations Exposure 3.
The NEMA-4 weather-tight housing allows the TDX to
be installed on indoor or outdoor service panels. The
precongured connecting leads simplify installation.
The unique narrow construction allows the SPD to
t between adjacent panel boards and connect via a
90-degree elbow.
Listed as a Type 1 SPD to
UL1449 3rd Edition, the
260 mm
TDX300 Series can be
(10.40)
installed within a Type
1 or 2 location in accordance
with the NEC2008.

83 mm
(3.25)

257 mm (10.32)
Model
Nominal Voltage, Un
Distribution System
Max Cont. Operating Voltage, Uc
Stand-off Voltage
Frequency
Short Circuit Current Rating, Isc
Technology
Max Discharge Current Imax
Impulse Current, Iimp
Nominal Discharge Current
Protection Modes
Voltage Protection Level
(8/20s)
Status

300kA 8/20s per


phase maximum
surge rating provides
protection suitable
for service entrance,
main-distribution
panels and highly
exposed applications

Mounting
Temperature
Humidity
Approvals
Surge Rated to Meet

CE, Listed to
UL 1449 Edition 3

Available Options

Dimensions H x D x W: mm (in)
Weight: kg (lbs)
Enclosure
Connection

Replacement Module

TDX300S120/208
TDX300S120/240
TDX300S277/480
120/208 V
120/240 V
277/480 V
3Ph 4W+G
1Ph 3W+G
3Ph 4W+G
170/295 V AC
170/340 V AC
310/536 V AC
240/415 V
240/480 V
480/831 V
50/60 Hz
200 kAIC
Over-current Replaceable Cartridge Fusing
TD Technology with thermal disconnect
300 kA 8/20 s per phase
22.5 kA 10/350 s per mode
120 kA 8/20 s
All modes protected via L-N, L-G, & N-G
L-N
L-N
800 V @ 3 kA
1.2 kV @ 3 kA
Audible Alarm
LED status indication per phase, mechanical ag per mode, all modes monitored
Remote contacts, change-over, 400 V~ / 3 A, max 1.5 mm (#14 AWG) terminals
260 x 83 x 257 (10.40 x 3.25 x 10.32)
5.9 (13.00)
Aluminum, IP 65 (NEMA-4)
Line: 762 mm of 5.26 mm (30 of # 10 AWG) ying leads
Neutral/Ground: 900 mm of 5.26 mm (36 of # 10 AWG) ying leads
3/4 straight nipple
-40C to 80C (-40F to 176F)
0 % to 95 %
C-Tick, CE, IEC 61643-1, UL 1449 Ed. 3 Listed Type 1
ANSI/IEEE C62.41-1991 Cat A, Cat B, Cat C
ANSI/IEEE C62.41.2 Scenario II, Exposure 3, 100 kA 8/20 s, 10 kA 10/350 s
IEC 61643-1 Class I, Class II
UL 1449 Ed. 3 In 20 kA mode
Replacement Fuse Cartridge (Order TDXFUSE)
Replacement Surge Module (Order TDS150M150 or TDS150M277),
please refer to installation instructions
TDS150M150
TDS150M277

WARNING
ERICO products shall be installed and used only as indicated in ERICOs product instruction sheets and training materials. Instruction
sheets are available at www.erico.com and from your ERICO customer service representative. Improper installation, misuse,
misapplication or other failure to completely follow ERICOs instructions and warnings may cause product malfunction, property
damage, serious bodily injury and death.
Copyright 2011 ERICO International Corporation. All rights reserved.