Documente Academic
Documente Profesional
Documente Cultură
T A I S E I C O R P O R A T I O N , Y o k oh a m a , 2 4 5 - 0 0 5 1 , J a p a n
ABSTRACT
This paper verifies analytically the fire resistance of the World Trade Centers steel frames and also examines precautions
to be taken in designing skyscrapers.
In the analysis, the temperature increase of steel members for the columns (perimeter and core columns) and the floor
trusses of the World Trade Center, when subjected to heating by hydrocarbon fire and standard fire, was calculated in
case the steel members were adequately fire-protected and in case they were not fire-protected (or in case the fire
protection was blown off). The fire resistance of these steel members was also verified by thermal deformation analysis.
The analysis revealed that, compared with the columns (core columns) of heavy sections, the floor trusses composed of
light-gauge steel members, even if fire-protected or not, experienced a temperature increase at a more rapid pace, that
the increase in steel temperature posed restraint on thermal deformation, thereby causing the steel members to buckle
and leading eventually to the failure of the floor trusses at a relatively low temperature, and that a larger restraint acted
on the end connections.
Based on the findings, this paper advances the following three suggestions:
(i) Elaborate care should be exercised in using light-gauge steel members for skyscrapers.
(ii) When hinged connections are to be used, the existence of any fractures at joints should be checked for especially at
elevated temperatures and after cooling.
(iii) For designing skyscrapers, fire engineering is essential in addition to traditional structural calculations.
Further, the use of steels with superior heat resistance is recommended to improve fire resistance of steel frames. This
does not mean that the fire protection can be deleted, but that given the same or similar protection, the length of time
that the steel can tolerate fire is extended. Or, if the fire protection system is destroyed, the unprotected steel will have
a longer survival time.
This paper will describe the characteristic of the steel and fire resistance of columns made by the steel compared to the
conventional steel. In addition, some of the important major structures in which it has bee used in Japan, will be
presented.
1. Foreword
The collapse of the World Trade Center Towers (hereafter referred
to as WTC, Photo 1 : at the time of construction) was caused by
damage to the structures due to aircraft impact and ensuing fire
exposure that led to loss of the structures load-bearing capacity.
The WTC, like other high-rise buildings, was required to have threehour fire resistance for its columns and two-hour resistance for its
floor system members. Its steel frames were protected from fire
with insulating materials (hereafter referred to as fire protection)
to meet the requirements.
The lengths of time between the aircraft impact and total collapse
were fifty-six minutes for WTC1 and one hour forty-three minutes
for WTC2. Indeed, there is little point in discussing the precise
details of the collapse time, since damage to the structures due to
both aircraft impact and the burning of the aviation fuel were
extraordinary
eventsradical
departures
from
the
conditions
expected by fire laws and regulations. But, to clarify the cause for
the collapse can be considered extremely useful for designing highrise buildings in the future.
From this point of view, this paper examines the fire resistance of WTCs steel frames by referring to the
report [1] made public by the Federal Emergency Management Agency (hereafter referred to as FEMA
Report).
2. Fire Exposure
The Boeing 767-200ER aircraft that impacted the WTC carried about 10,000 gallons (about 38,000 liters) of
jet fuel. The FEMA report assumes: of the total jet fuel carried, 1,000 to 3,000 gallons were exhausted as
fire balls, 3,000 gallons flowed onto other floors and the remaining 4,000 gallons were burnt within the
impact floors.
The calorific value of the jet fuel was 1 to 1.5 GW. If one-third or a half of that energy was released to the
structure, gas temperatures reached 900 to
1,100C around the ceilings and 400 to 800C
at the rest of indoor spaces according to the
analysis of the FEMA Report. The jet fuel
remaining on the floors burned within about
five
minutes,
with
the
blaze
engulfing
For buildings other than typical buildings, the gas temperature for a petrol spill fire is also specified in the
United States (ASTM E1529 [5], hereafter referred to as hydrocarbon pool fire). Fig. 1 shows the
comparison of gas temperature between standard fire and hydrocarbon pool fire. In the case of a
hydrocarbon pool fire, the temperature at first rises more rapidly to a high of about 1,100C in the first five
minutes (than for the case of a standard fire) and, afterwards, the temperature remains constant according
to the U.S. specifications.
Hp / A = 35.7
Hp / A = 173.4
Hp / A = 144.6
-1.09 (27.7mm)
The sizes of the columns (core and perimeter) are only those assumed because the FEMA Report gives no
specified dimensions for them at and around the impact floors. Hp/A is the indicator of a members thermal
capacity (the rate of a members temperature increase), with Hp = circumferential length and A = sectional
area. The larger the Hp/A, the higher the rate of steel-frame temperature increase.
Figs. 2 and 3 clearly reveal the following:
(i) The increase of the steel-frame temperature corresponds to thermal capacity (Hp/A), regardless of fire
protection. In the case of the floor truss rod and the perimeter column with smaller thermal capacity
(Hp/A is larger), the temperatures rise more rapidly, reaching as high as 900C in five minutes
especially when the y are not fire-protected.
(ii) By comparison, in the case of the core column that has extremely large thermal capacity, the speed at
which the temperature rises is moderate even when it is not fire-protected (or when fire protection is
blown off). The temperature increases to about 600C in approximately 20 minutes.
(iii) In the case of a hydrocarbon pool fire, the temperature of steel frames (fire-protected or unprotected)
increases faster than in the case of standard fire, especially in the first five minutes. A hydrocarbon pool
fire causes the gas temperature to rise rapidly and that is why, when steel frames are not fire-protected,
the difference between a hydrocarbon pool fire and a standard fire is more pronounced in terms of the
rate of the steel-frame temperature increase.
heating (the heat test). The condition of failure immediately after a loaded heat test made on a column is
shown in Photo 6. The proof stress of steel frames decreases with the increase of temperature, leading to
the loss of the frames load-bearing capacity.
For the ASTM E-119 fire test in the United States [4], the heat test is prevalent for columns, and the critical
temperatures for steel members are specified at:
Column:
Beam:
As for fire testing in Japan [3], the heat test traditionally has been applied with the critical temperatures
specified as follows:
Column:
Beam:
But, today, the loaded heat test is also in practice. The load applied is specified as a load equivalent to the
long-term critical stress (2/3 of the yield point).
Fig. 6 shows the integration of the critical temperatures in the two countries with Fig. 4 (high-temperature
strength of steel materials). The difference between the two countries is about twice in the critical
temperature, eventually leading to a wide difference in the thickness of fire protection required.
This study obtained analytically the fire resistance of the columns (core and perimeter) of the WTC at and
around the impact floors. The sizes of the columns adopted were identical to those used for the analysis of
steel-frame temperatures in Section 3. The steel grade was A36 and the ratio of axial force was set at 0.5,
although no reference is made to the columns ratio of axial force in the FEMA Report. However, since the
stress applied on the diagonal members of the floor trusses was estimated, on calculation, at about 50% of
the yield point, the ratio was assumed to be the same.
Fig. 7 shows the results of the analysis. The columns underwent thermal expansion as the temperature
increased (vertical elongation: V), buckled due to the lowering of steel strength and the loss of their loadbearing capacity (horizontal deflection at the middle of the columns: H). The calcula ted buckling
temperatures were 515C for a core column and 520C for a perimeter column.
A comparison between the above analysis results and the critical temperature shown in Fig. 6 reveals:
(i) The buckling temperature of the columns virtually corresponds to steels high-temperature strength and
the columns ratio of axial force.
(ii) The U.S. critical temperature, 538C, is considered almost equivalent to the ratio of axial force of 0.5.
The failure temperature of beams is related to the presence of the floor. It is higher than that of the
columns, because the temperature of the steel frames in contact with the floor increases at a slower rate
and also because the floor itself shares the applied load. The critical temperature of 593C for beams, as
specified in the United States, is considered to put a restriction on the load applied.
Attention should also be paid to the fact that the high-temperature strength of steel materials shown in Figs.
4 and 6 is the average. Fig. 8 shows the results of examining the high- temperature strength of steel
materials, made by the Japan Iron and Steel Federation (JISF) [7]. The high-temperature strength varies
widely, as shown in the figure. In addition, there are cases where columns and beams are restrained by
peripheral frames due to thermal expansion, resulting in failure at lower temperatures than expected, as
discussed later. It is considered that, with such indefinite factors in mind, the critical temperature of 350C
adopted in Japan secures a higher level of safety.
Fig. 9 shows the schematic diagram of the WTCs floor structure. The floor is of a structure designed to
support lightweight concrete (10 cm thick) on steel decking by trusses arranged at a spacing of 6 ft. 8 in.
(about 2 m). Their maximum length is 60 ft. (18.3 m). The trusses are lightweight, using angles for the
upper and lower chords and round bars for the diagonal members. Their ends are linked to the perimeter
columns and the core girders by two high-strength bolts (A325 bolt, 5/8 in. dia.) followed by welding after
erection. Fig. 10 shows the details of the truss end (FEMA Report).
Fig. 11 analyzes the failure process of the floor truss by raising the steel-frame temperature.
The FEMA Report gives no reference to the dimensions of the upper and lower chords. For this analysis,
two angles, each measuring L-3.5 x 3/8 in. (88.9 x 9.525 mm), were overlapped to match the normaltemperature stress level
(about 50% of yield point) of the trusss diagonal member (1.09 in.). Though the floor trusses are the
composite structure with the concrete slabs, the concrete slabs were not considered in the analysis. The
loads were design loads (dead load and service load).
When the hinged end was adopted for one end of the truss and the roller end for the other end of the truss,
the increase of the steel-frame temperature caused the truss deformation to concentrate on the roller end
side and the vertical members of the utmost end to buckle at 340C. Deflection at the time of buckling was
7.50 cm in the middle of the truss, and horizontal deflection on the roll end side was 6.61 cm.
When each end of the truss was hinged, constraints on the thermal expansion of the truss resulted in the
trusss large deflection. Constraints concentrated on the upper chord, and the resultant buckling of the
chord caused the failure of the truss at 264C. The central deflection at the time of the failure was 27.9 cm.
Fig. 12 shows the truss ends horizontal restraint load. The restraint load was pulled inward at normal
temperature. Due to the thermal expansion of the truss, it then turned around but was eased by
deformation of the upper chord. Maximum restraint load occurring outwards was about 30 tons. According
to the FEMA Report, the shear strength of the high-strength bolts at each end (A325 bolt, 5/8 in. in inside
dia. x 2) is as follows (the strength decreases by half at 550C):
Room temperature: Ru = 232 kips (105.2 tons)
550C (1,022F):
Since the trusses were connected to the perimeter columns and the core girders, it is assumed that
approximately the central values of those given in the above two cases must have been applied for actual
behavior. Besides, as the floor slabs serve to retard the thermal expansion of the trusses and to constrain
the buckling of the upper chords, it can also be assumed that the actual failure temperatures must have
been higher than those in the above analyses.
But, when such a large-span truss is heated and undergoes thermal expansion, it deforms (deflects) due to
constraints on its ends and its individual structural members are subjected to large compression stresses. In
addition, a large shearing force acts on the end connections. From these, it is quite likely that the failure
temperature of the truss is far lower than the critical temperature for beams (593C: 1,100F) in the fire test.
Grade
2
N/mm (ksi)
Yield strength
Tensile strength
N/mm (ksi)
Yield ratio
Elongation
Charpy
N/mm (ksi)
energy J
at 0 C
at 600 C
at 0 C
at 0 C
at 0 C
at 0 C
min / max
min
min / max
max
min
min
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
FR Steel
Grade 325
325/445
217 min
490 / 610
80
21
27
AST M A992
345/450 (50/65)
450 min
85
18
1)
Note 1) : charpy absorption energy is a supplementary requirement for use at the option of the purchaser
Application of FR Steel
Whether FR Steel is used with or without protection is determined by building application and design
concept.
Fig. 14 shows numbers of buildings using FR Steel provided by Nippon Steel since 1989. Car parks, atriums,
sport facilities, art galleries and a station building have been the major applications without protection.
External steel-frame buildings also are a major application.
Station
buildings(8
Sport faclities
External steel
frames
Car park
Photos. 7 and 8 show the application of FR Steel to a
multi-story car park.
Others
Art galleries
Car parks
Atriums
design intention was adopted as the material for this large truss structure.
Station building
East Japan Railway Company constructed a commercial building spanning the tracks of Oimachi Station in
Tokyo (Photos. 10 and 11). In the case of constructing a large-scale building spanning a railway, it is
necessary to provide protection for steel frames in the vicinity of the tracks. However, because of the
exfoliation of maintenance, steel-frame construction without protection was required for this building.
Office building (external steel-frame building)
This 31-story building in Kobe houses offices and research laboratories (Photo 12). A suspended megastructure, in which six stories are structured as one unit, was adopted for the construction of the building.
It features a structural design in which the mega-structure is presented as the buildings structural design
element. In the building construction, FR Steel was adopted to give the impression of slenderness of the
structural members through the application of lighter protection to columns and beams.
In addition, it is important to verify the fire resistance of steel frames by means of fire-safety design.
Fire tests address such structural members as columns and beams, as stated in section 4, and they do not
reflect the behavior of steel frames as a whole during a fire. Steel frames expand thermally due to heating
by fire and the structural members are exposed to large additional stress by constraints. Especially
lightweight structural members not only undergo rapid temperature increases within a short time, but also
lose their load-bearing capacity even at a relatively low temperature due to buckling and the like. Besides,
load concentrates in connections, so hinged end and similar connections can fracture during the course of
heating or cooling.
6. Summary
5. Summary
In Japan, the number of such failure analyses have been increasing since around 1990, where fire-safety
designs are used to verify the fire resistance of steel frames, targeting buildings adopting FR steel and
concrete-filled steel tube columns. Henceforth, imperative is the active adoption of fire-safety designs
particularly for high-rise buildings and publicly important buildings. The adoption of fire-safety design for
high-rise steel buildings ensures greater safety in fire. FR Steel, used successfully in Japan for a decade, is
an option to be considered.
ACKNOWLEDGMENT
The photos of the WTC at the time of construction, shown in this paper, were provided by Mikio Kasajima,
former president of Daiken Sekkei Co. His cooperation is highly appreciated.
REFERENCES
[1] World Trade Center; Building Performance Study, (2002), Federal Emergency Management Agency, New York, U.S.A.
[2] ISO834 (1975), Fire-Resistance Tests, Elements of Building Construction, International Organization for
Standardization
[3] JIS A1304 (1975), Method for Fire Resistant Tests for Structural Part of Buildings, Japan Standards Association,
Tokyo, Japan
[4] ASTM E119 (1983), Standard Methods for Fire Tests of Building Construction and Materials, American Society of
Testing and Materials, Philadelphia, U.S.A.
[5] ASTM E1529, Standards Test Methods for Determining Effects of Large Hydrocarbon Pool Fires on Structural Members
and Assemblies, American Society of Testing and Materials,
[6] ASTM A36, Standard Specification for Carbon Structural Steel, American Society of Testing and Materials, Philadelphia,
U.S.A.
[7] Zakoh, R., et al, (2000), High-temperature Strength of Steel Products for Building Structures, Summary of Technical
Papers of Annual Meeting, Architectural Institute of Japan
[8] Sakumoto, Y., Yamaguchi, T., Ohashi, M., and Saito H. (1992), High-Temperature Properties of Fire-Resistant Steel
for Buildings, ASCE Journal of Structural Engineering, 118(2), pp.392-407
[9] ASTM A992 (2001), Standard Specification for Structural Shapes, American Society of Testing and Materials,
Philadelphia, U.S.A.
[10] JIS G3136 (2001), Rolled Steels for Building Structure, Japan Standards Association, Tokyo, Japan