Documente Academic
Documente Profesional
Documente Cultură
01D1-E-0001
One-line Diagram
PCS
High eciency
(98.5% for DC 1,000 V specifications) (Power conditioner system)
Series expanded to DC 600 V
specications
Substation conguration for easy
construction*
Interconnection with
transmission line of
electric power utility
company
PV panel
PCS
Connection
box,
current
collection
box
PV panel
Main transformer
GIS
VCT
Extra-high-voltage facility
(22 to 154 kV)
High-voltage
facility
(6.6 kV)
System-matched Modules
PCS
Connection
box,
current
collection
box
PV module
PCS
PCS
Power conditioner
Key technology
PCS
PCS
PCS
PCS
Total engineering
Features
Adoption of new IGBT and new circuit system
Fuji Electric commercialized the worlds first three-level module
in which a new RB-IGBT* and an existing IGBT are integrated in
one package.
Application of this new module to a new three-level conversion
circuit enables a large reduction both in power loss and in the
number of parts, resulting in high efficiency and low noise in the
equipment.
: RB-IGBT: Reverse Blocking-Insulated Gate-Bipolar Transistor
World
s highest eciency 98.5%
(DC 1,000 V product)
INV1
99
1000 kVA
LB
INV2
98
Efficiency [%]
97
96
95
94
INV3
93
92
91
90
89
20
40
60
80
100
INV4
Output [%]
New IGBT module
AC voltage
U-V phase (red)
V-W phase (green)
200 V/DIV
AC current
U phase (red)
80
Loss[%]
100
Note: Internal power supply is not included. IEC61683 efficiency tolerance is indicated.
V phase (green)
60
W phase (blue)
25 A/DIV
40
20
0
Existing system
(two-level system)
New system
(new three-level system)
3.6
3.62
3.64
3.66
4.6
4.62
4.64
(Front view)
PCS
PCS
DC main circuit
cable and ground wire
Electric specifications
(DC input)
Electric specifications
(AC output)
System interconnection
Series name
Rated output
Insulation system
DC input voltage range
DC input voltage (MPPT range)
Number of DC input branches
Rated output capacity
Rated output voltage
Rated frequency
Number of output phases
Rated output current
Output power factor
Output current distortion factor (total)
Output current distortion factor (each)
Equipment highest efficiency
Equipment efficiency (Euro efficiency)
Overload capacity
Noise
System protection
Individual operation detection system (passive)
Individual operation detection system (active)
Voltage rise suppression function
FRT
Installation system
Applicable IP
System type
Cable lead-in
Cooling system
Dimensions
PCS single unit (W D H)
Substation (W D H)
Mass
PCS single unit
Substation
Environmental conditions Storage temperature
Operating temperature
Relative humidity
Altitude
Relevant standard
Communication system
Panel structure
PVI1000-3/1000
Remarks
1000 kW
Transformerless system
1000 V
460 V to 950 V
4
24 branches (Option)
1000 kW
270 V10 to 12
50/60 Hz 5
Three-phase, three-wire; isolated neutral system supported.
2138 A
>0.99(at rated output)
Individual operation Q output excluded
(when output is 1/8 of rated output).
<5 % (at rated output)
<3 % (at rated output)
98.5 %
98.2 %
100 % continuous
85 dB
OV, UV, OF, UF
Detection of voltage phase jump
Reactive power variation system
Reactive current compensation,
active current output suppression
Vmin=15 0.625 SRecovery time 3 s Based on the countrys grid code.
Outdoor self-standing type
Measures against salt damage are optional.
IP54
Integrated step-up transformer and switchgear
Substation system
Lower part
Forced-air cooling
360021302830 mm
615024002830 mm
About 7000 kg
About 12500 kg
20 to +50
High-temperature option available for +50 C.
10 to +40
Non-condensing
15 to 95
High-altitude option available for over 2000 m.
2000 m or less
IEC62109-1
RS-485/MOD BUS/TCP
1000 kW
4.16 to 34.5 kV
50/60 Hz
Three-phase, three-wire
200 A
12.5 kA
1000 kVA
Three-phase
50/60 Hz
Oil-immersed self-cooling
Remarks
Base (1)
1000
150
800
Concrete foundation
Step-up transformer
LBS panel
(Top view)
1000
800
1200
2400
Operation screen
2130
Example of appearance
2830
Specifications
1200
2550
3600
6150
(Unit: mm)
Electric specifications
(DC input)
Electric specifications
(AC output)
Series name
Rated output
Insulation system
DC input voltage range
DC input voltage (MPPT range)
Number of DC input branches
Rated output capacity
Rated output voltage
Rated frequency
Number of output phases
Rated output current
Output power factor
Dimensions
Mass
Environmental
conditions
Installation system
Applicable IP
System type
Cable lead-in
Cooling system
PCS single unit (W D H)
Substation (W D H)
PCS single unit
Substation
Storage temperature
Operating temperature
Relative humidity
Altitude
Relevant standard
Communication system
PVI7503/750
Remarks
750kW
Transformerless system
750 V
320 V to 750 V
4
16 branches (Option)
750 kW
200 V10 to 12
50/60 Hz 5
Three-phase, three-wire; isolated neutral system supported.
2165 A
>0.99(at rated output)
Individual operation Q output excluded
(when output is 1/8 of rated output).
<5 % (at rated output)
<3 % (at rated output)
97.8 %
97.4 %
100 % continuous
85 dB
OV, UV, OF, UF
Detection of voltage phase jump
Reactive power variation system
Reactive current compensation,
active current output suppression
JEAC97012010
Based on the countrys grid code
(conforms to supplementary version of 2011)
Outdoor self-standing type
Measures against salt damage are optional.
IP54
Substation system
Integrated step-up transformer and switchgear.
Lower part
Forced-air cooling
360021302830 mm
615024002830 mm
About 7000 kg
About12500 kg
20 to +50
10 to +40
High-temperature option available for +50 C.
15 to 95
Non-condensing
2000 m or less
JIS, JEM, JEC
RS485/MOD BUS/TCP
Rated output
Power supply voltage
Power supply frequency
Number of power supply phases
Rated current
Breaking capacity
Capacity
Number of phases
Frequency
Cooling system
Connection system
Others
750 kW
6.6 kV
50/60 Hz
Three-phase, three-wire
200 A
12.5 kA
750 kVA
Three-phase
50/60 Hz
Oil-immersed self-cooling
Remarks
PCS optional
New
Series !
Series name
Rated output
Insulation system
Electric specifications DC input voltage range
(DC input)
DC input voltage (MPPT range)
Number of DC input branches
Electric specifications Rated output capacity
(AC output)
Rated output voltage
Rated frequency
Number of output phases
Rated output current
Output power factor
Output current distortion factor (total)
Output current distortion factor (each)
Equipment highest efficiency
Equipment efficiency (Euro efficiency)
Overload capacity
Noise
System
System protection
Individual operation detection system (passive)
interconnection
Individual operation detection system (active)
Voltage rise suppression function
FRT
Installation system
Panel structure
Applicable IP
System type
Cable lead-in
Cooling system
Dimensions
PCS single unit (W D H)
Substation (W D H)
Mass
PCS single unit
Substation
Environmental
Storage temperature
conditions
Operating temperature
Relative humidity
Altitude
Relevant standard
Communication system
PVI7503/500
500kW
Transformerless system
750V
320V to 700V
5
500kW
200V10 to +12
50/60Hz
Three-phase, three-wire; isolated neutral system supported.
1444A
>0.99 (at rated output)
<5% (at rated output)
<3% (at rated output)
97.7%
97.3%
100% continuous
75dB or less
OV, UV, OF, UF
Detection of voltage phase jump
Reactive power variation system
Reactive current compensation, active current output suppression
Vmin=15%0.625s Recovery time 3 s
Outdoor self-standing type
Lower part
Forced-air cooling
24009001950 mm
2000kg
20 to +50
10 to +40
5 to 90
1000m or less
JIS, JEM, JEC
RS485
Remarks
Optional
Demarcation point
Non-condensing
500 kW
6.6 kV
50/60 Hz
Three-phase, three-wire
200 A
12.5 kA
500 kVA
Three-phase
50/60 Hz
Oil-immersed self-cooling
DT
-MC
-MC
V
Wh
MCCB
SD
MCCB
Rectifier panel
MCCB Storage
battery
Rectifier panel
MCCB MCCB
2CT
A
MCCB
MCCB
MCCB
High-voltage panel
U>
Z >
Spare
High-voltage panel
PAS
(with VT, LA and SOG)
V
Wh
Spare
DC panel
MCCB
Aerial wire
Spare
Storage
battery
Remarks
ZCT
U>
DT
2CT
U>
From temporary
generator
F-MPC60B
LA3
NGR
51G
2CT
LBS
PF
MCCB
MCCB
Others(meteorological
equipment, display)
No.1 Substation
No.1 PCS
MCCB
CT1, 2
MC11
MC21
MC31
L12
L22
L32
L42
C1 L11
C2 L21
C3 L31
C4 L41
DCCT11,12
PWU1
DCCT21,22
PWU2
DCCT31,32
PWU3
DCCT41,42
PWU4
F11,12
F21,22
F31,32
F41,42
DCCT10
DCCT30
MCB11
MCB31
Solar cell
Solar cell
Solar cell
4 blocks
10
MC41
Solar cell
27
59
64
67S
95LH
66 kV transmission line
Demarcation point
Monitoring and control panel (outdoor)
3BCT
ES (manual)
F-MPC
LA3
DS
89R(Electrically operated)
ES (manual)
Outdoor meter panel
(Supplied by electric power
utility company)
VD
W/TD
Var/TD
VCB(52R) C-GIS
ES (manual)
CLR
EVT
VCT
VCT
F-MPC
F-MPC
3BCT
Bus duct
Tr-1
Main transformer
Three-phase outdoor oil-immersed self-cooling
EVT
LA3
V/TD
5CT
CLR
F-MPC
Incoming panel
64G
To each PCS panel
F-MPC
52S
VCB
Feeder panel
U>
From temporary
generator
DT
-MC
-MC
V
Wh
SD
MCCB
Rectifier panel
MCCB Storage
battery
Rectifier panel
MCCB MCCB
2CT
A
MCCB
MCCB
High-voltage panel
U>
Z >
Spare
High-voltage panel
MCCB
DC panel
MCCB
Wh
MCCB
MCCB
Others(meteorological
equipment, display)
No.2
No.1 Substation
No.3
No.4
PAS
(with VT, LA and SOG)
No.5 Substation
No.6
No.7
No.8
MCCB
No.5 PCS
MC21
MC31
MC41
L12
L22
L32
L42
C1 L11
C2 L21
C3 L31
C4 L41
DCCT11,12
PWU1
DCCT21,22
PWU2
DCCT31,32
PWU3
DCCT41,42
PWU4
F11,12
F21,22
F31,32
F41,42
DCCT10
DCCT30
MCB11
MCB31
Solar cell
Solar cell
Same as
on the left
Same as
on the left
Same as
on the left
MC11
27
59
64
67S
95LH
Same as
on the left
Solar cell
Same as
on the left
Same as
on the left
CT1,2
MC21
MC31
MC41
L12
L22
L32
L42
C1 L11
C2 L21
C3 L31
C4 L41
DCCT11,12
PWU1
DCCT21,22
PWU2
DCCT30
MCB11
MCB31
Solar cell
Solar cell
4 blocks
11
DCCT31,32
PWU3
DCCT10
Solar cell
No.10
No.9 PCS
MCCB
CT1,2
MC11
No.9 Substation
MCCB
CT1, 2
4 blocks
10
Aerial wire
PAS
(with VT, LA and SOG)
Solar cell
F-MPC60B
ZCT
Aerial wire
Spare
ZCT
PAS
(with VT, LA and SOG)
VCB
(52F3)
LA3
Aerial wire
Spare
Storage
battery
F-MPC
LA3
ZCT
U>
DT
2CT
MCCB
F-MPC60B
LA3
NGR
51G
2CT
2CT
2CT
LBS
PF
VCB
54F2
Same as
on the left
Same as
on the left
Same as
on the left
DCCT41,42
PWU4
27
59
64
67S
95LH
Solar cell
Same as
on the left
Same as
on the left
Same as
on the left
MC11
MC21
MC31
MC41
L12
L22
L32
L42
C1 L11
C2 L21
C3
L31
C4
L41
DCCT11,12
PWU1
DCCT21,22
PWU2
DCCT31,32
PWU3
DCCT41,42
PWU4
F11,12
F21,22
F31,32
F41,42
DCCT10
DCCT30
MCB11
MCB31
Solar cell
Solar cell
Solar cell
Same as
on the left
Solar cell
27
59
64
67S
95LH
Same as
on the left
4 blocks
12
VCT
PAS
Incoming panel
VD
Installation of
electric pole
DS
89R
(remote manual operation)
Incoming panel
2VT
VCB52R
RPS
Wh
64G
2CT
RPS
F-MPC60B
Wh
ZPD
PF:20A
LBS
VCB
52F2
VCB
52F1
2CT
2CT
F-MPC60B
2CT
MCCB
2CT
Wh
MCCB
Wh
MCCB
Power load
Spare
6.6 kV cubicle
No.1 Substation
MCCB
F-MPC60B
ZCT
ZCT
MCCB
MCB11
Spare
Remote monitoring
No.2 Substation
No.2 Substation
MCB11
CT1,2
CT1,2
Measuring instrument
MC11
MC21
L12
C1
L11
L22
C2
DCCT11,12
PWU1
MC31
MC41
L32
C3
L21
DCCT21,22
PWU2
L31
L42
C4
DCCT31,32
PWU3
DCCT41,42
27
59
64
F31,32
67S
MCB11
MCB31
95LH
Solar cell
Solar cell
4 blocks
13
PWU1
F11,12
Solar cell
Solar cell
L11
MC31
L22
C2
DCCT11,12
PWU4
DCCT30
MC21
L12
C1
L41
DCCT10
MC11
MC41
L32
C3
L21
DCCT21,22
PWU2
L31
L42
C4
DCCT31,32
PWU3
L41
DCCT41,42
PWU4
DCCT10
F11,12
F31,32
MCB11
MCB31
Solar cell
27
DCCT30
Solar cell
Solar cell
59
64
67S
95LH
Solar cell
4 blocks
14
VCT
PAS
Installation of
electric pole
Incoming panel
VD
Incoming panel
2VT
VCB(52R)
RPS
Wh
RPS
64G
To each PCS panel
2CT
Wh
FMPC60B
ZPD
PF:20A
LBS
VCB(52F2)
VCB(52F1)
2CT
2CT
FMPC60B
ZCT
FMPC60B
ZCT
Wh
LBS
2CT
Wh
LBS
MCCB
MCCB
Power load
Spare
6.6 kV cubicle
MCCB
MCCB
Spare
Remote monitoring
No.1PCS
(500kW)
MCB
MC21
L12
L11
L21
DCCT
Solar
cell
Solar
cell
MCB5
MCB4
Solar
cell
PWU2
MCB3
Solar
cell
DCCT
PWU1
MCB2
Solar
cell
L22
L21
DCCT
MCB1
Solar
cell
MCB5
Solar
cell
L11
PWU2
MCB4
Solar
cell
MC21
L12
DCCT
MCB3
Solar
cell
MCB2
Solar
cell
L22
PWU1
MC11
L21
DCCT
MCB1
Solar
cell
MCB5
Solar
cell
L11
PWU2
MCB4
Solar
cell
MC21
L12
DCCT
MCB3
Solar
cell
MCB2
Solar
cell
L22
PWU1
CT
MC11
L21
DCCT
MCB1
Solar
cell
MCB5
MCB4
Solar
cell
L11
PWU2
MCB3
MCB2
MCB1
Solar
cell
L12
DCCT
PWU1
MC21
No.2PCS
(500kW)
MCB
CT
MC11
L22
No.1PCS
(500kW)
MCB
CT
MC11
C
No.2PCS
(500kW)
MCB
CT
Measuring instrument
15
Solar
cell
Solar
cell
16
Features
The SCADA system has the highest quality and cost performance in the industry.
The system has many features such as a web function, multilingual function,
high speed, extensibility, and reliability.
The system can be applied to a large-scale power generation system with several to more than 400,000 I/O points.
High speed
Extensibility
Reliability
A system with minimal data loss is
achieved with a PC-based
conguration.
Communication functions and server
functions can be provided in
completely redundant configurations to
build a system that is safe, secure and
trouble-free, even in the event of any
malfunctions in a PC or in the network.
PV facility
Thermometer
PV facility
RS panel
Client display
RS panel
RS panel
RS-485
(Selling power)
(Purchasing power)
Sunshine
recorder
Remote monitoring
server
22 to154kV
Extra-high-voltage
incoming panel
Sunshine
recorder
Modbus, etc.
Thermometer
System
interconnection
facility
RS panel
Internet(WAN/VPN)
17
Remote monitoring
from existing personal
computers is possible.
Radio equipment
Remote monitoring control personal computer
18
About Microgrids
Fuji Electric also develops renewable energy solutions such as photovoltaic power generation and
wind power generation for isolated islands. These microgrid congurations can achieve balanced
operation with diesel power generation using a system with an advanced high-performance power
PCS and a lithium ion capacitor mounted stabilizer. We participate in many verication tests aiming
to reduce CO2 emissions and power generation costs.
MEMO
Interconnection point
total output
Large output
variation
Compensation
output
Output
PCS
Storage battery
PCS
On-island diesel
power generation system
Control unit
Output
PCS
19
20
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan
Phone : (03)5435-7111