Documente Academic
Documente Profesional
Documente Cultură
ETG - 1.111
GENERAL TECHNICAL SPECIFICATIONS
SEISMIC DESIGN
COLBUN S.A.
ETG - 1.111
ETG - 1.111
GENERAL TECHNICAL SPECIFICATIONS
SEISMIC DESIGN
CONTENT
CLAUSE
SUBJECT
PAGE
Static Method........................................................................................................7
1.6.3.
Dynamic Method.................................................................................................10
..............................................................................................................................17
Category A...........................................................................................................17
2.3.2.
Category B...........................................................................................................20
General................................................................................................................22
2.4.2.
COLBUN S.A.
ETG - 1.111
2.5.1.
General................................................................................................................23
2.5.2.
2.5.3.
2.5.4.
Steam Boilers......................................................................................................26
2.6.2.
2.6.3.
2.6.4.
Floodgates...........................................................................................................30
2.6.5.
Traveling crane...................................................................................................31
2.7.2.
2.7.3.
2.7.4.
Material characteristics......................................................................................33
2.7.5.
2.7.6.
2.7.7.
applicable. ..............................................................................................................................37
2.7.8.
2.7.9.
2.7.10.
..............................................................................................................................54
COLBUN S.A.
ETG - 1.111
General................................................................................................................65
3.9.2.
Analysis procedures...........................................................................................66
3.10.
Retaining walls....................................................................................................66
3.10.1. Generality......................................................................................................................66
3.10.2. Deformable walls. Formulas for Thrust....................................................................68
3.10.3.
Stiff Walls............................................................................................................71
3.10.4.
3.10.5.
3.11.
Underground Works...........................................................................................73
3.12.
Outdoors Pipelines.............................................................................................74
3.13.
Intake towers.......................................................................................................75
3.14.
Chimneys.............................................................................................................77
3.14.1.
General................................................................................................................77
3.14.2.
3.14.3.
3.15.
3.15.1.
3.15.2
Static Method......................................................................................................81
3.15.3
Dynamic Method.................................................................................................82
3.15.4
3.15.5
3.16.
Cooling Towers...................................................................................................83
3.17.
3.18.
Elevated Tanks....................................................................................................87
COLBUN S.A.
ETG - 1.111
3.19.
BRIDGES.............................................................................................................88
3.19.1.
Scope...................................................................................................................88
3.19.2.
Analysis Methods................................................................................................89
3.19.3.
3.19.4.
3.19.5.
3.19.6.
Braces..................................................................................................................92
3.20.
BUILDINGS..........................................................................................................92
3.20.1.
General................................................................................................................92
3.20.2.
Machine House...................................................................................................92
3.20.3.
COLBUN S.A.
ETG - 1.111
ETG - 1.111
GENERAL TECHNICAL SPECIFICATIONS
SEISMIC DESIGN
1.
For the purpose of its seismic design, the works and equipment are classified in the
COLBUN S.A.
ETG - 1.111
COLBUN S.A.
ETG - 1.111
Also belong to category B the constructions which failure would result in intermediary
magnitude losses; buildings destined for housing or workshops, but where usually there
is no agglomeration of people; permanent warehouses to store material and equipment,
with exception for materials or essential spare parts in the event of seismic emergency;
constructions which failure is the exact cause of the failure or lack of operation of works
or equipment classified as category B, but that dont affect those from category A.
Permanent bridges in none essential routes.
Category C.
Equipment which failure doesnt result in malfunction of category A or B equipment that,
additionally, are not indispensable for the continuous operation of the operative or
functional set to which they belong. The seismic design requisite shall only need to
anchor them adequately according to the provisions of clause 2.8 to exclude the
possibility of damage or equipment from categories A or B.
Isolated or provisional constructions, not destined for dwelling and not classified in
categories A or B (such as provisional bridges, material warehouses in construction
sites, etc.) and which failure could cause damages or malfunction to the works or
equipment from categories A or B.
COLBUN S.A.
ETG - 1.111
could be installed in places with different seismic conditions, the analysis will be based
on the horizontal movement parameters of the ground that are listed next:
Seismic Category
a/g
v(cm/s)
d(cm)
0.50
35
25
0.40
30
20
0.30
20
15
b)
Works for which a Special Technical Specification for seismic design has not
been issued.
In these cases, the seismic strains shall be determined as of the linear response
spectrum of Figure 1.
The spectrums of the figure mentioned are valid for works or equipment comprised in
any of the exceptions recently registered and that, moreover belong to the seismic
category A. If consists of works or equipment from categories B or C, the ordinate of
the curves from Figure 1 will be multiplied, respectively by 0.8 and by 0.6. For damping
values not diagramed in the figure, the spectrum ordinate may be obtained by linear
interpolation of the curves.
COLBUN S.A.
ETG - 1.111
In all cases, the seismic category and the damping value employed in the determination
of spectrum ordinates shall count with the approval of the Head Inspector.
1.5. Damping.
For the assessment of the seismic response of linear systems or that reasonably could
be analyzed as if they were, it could be employed in the calculation of damping values
z, expressed as percentage of critical damping, not greater that those provided in Table
1.1 (p.23), without needing greater justification. Values greater than those mentioned
may be admitted, whenever justified by tests or trials in which stress and deformation
levels have been achieved compatible with the application that will be made in the
calculations of the results of such tests or trials. This justification will be especially
demandable when the system (structure or equipment) submitted to study is equipped
with elements specially destined to dissipate energy; the dissipation properties
supposed in the calculation shall have in such case an experimental fundament.
The maximum damping values that could be employed, without needing greater
justification, in the seismic analysis of electric equipment that contain fragile elements,
such as bushings, porcelain insulators, will be those specified in clause 2.7.12.
COLBUN S.A.
ETG - 1.111
1.6.2.Static Method.
In the static method, the effects of seismic actions will assimilate to constant forces
(independent of time) proportional to the weights of the several parts of the system
analyzed and applied in the respective gravity centers. The horizontal components of
these forces will be presumed as acting all in a same direction, in the horizontal
COLBUN S.A.
ETG - 1.111
direction to which is being performed the analysis; the vertical components will be
considered driven all upwards or all downwards, according to the situations that result
most unfavorable for the element submitted to inspection. The analysis shall be
repeated inverting the direction of the horizontal forces to cover the most unfavorable
cases for several elements of the work or its anchorages.
In general will only be necessary to perform the analysis for each one of the horizontal
directions mutually orthogonal or approximately orthogonal, considered separate and
independently. Though, when at the opinion of the Head Inspector the peculiarities of
the system consider necessary, the analysis according to horizontal directions shall also
be performed that, at his criterion are potentially critical.
A.
Basal Level.
The basal level will be defined as the horizontal plan in which is applied the
seismic action.
When the system being studied is directly supported on the ground, the basal
level will be the horizontal plan in which are mutually balanced the horizontal
resultants of the inertia forces and the reactions of the foundation soil. Currently,
the basal level will correspond to the foundation seal; the exceptions to this rule
shall be justified meeting the specific conditions of lateral confinement of the
cementation.
When referenced to equipment supported in buildings, the basal level will be the
floor in which they are anchored.
B.
Seismic Coefficient.
The force of the basal shear design, that is the resulting H of the horizontal
forces of the seismic design applied above the basal level, will be provided by
the formula:
COLBUN S.A.
ETG - 1.111
H = CW
(1)
H p = CW p =
H
Wp
W
(2)
where C is the seismic design coefficient of clause 1.6.2. B and W p is the weight
of the part considered.
When considering very robust equipment or structures but that could accept
rotation movements over its base with amplitudes of certain consideration, it will
COLBUN S.A.
ETG - 1.111
be assumed that the seismic horizontal forces that act over the several parts in
which the system has been split for its analysis are proportional jointly to the
weights and the heights of the parts over the basal level, according to the
following formula:
Hp =
hp W p H
i hi W i
where the sum is extended to all the parts considered and the symbols
employed have the meanings registered next:
H
the subscription p.
wi
COLBUN S.A.
ETG - 1.111
D.
V p = Cv W p
(4)
where W p is the weight of the part considered and C v is the seismic design
coefficient for the vertical actions (adimensional number independent from index
p).
The procedure that shall be followed to determine the seismic coefficient C v is
provided in adequate places of chapter 2 and 3.
1.6.3.Dynamic method.
10
COLBUN S.A.
ETG - 1.111
minimum demandable in respect to the complexity of the analysis is to perform for the
seismic excitation acting in each of the horizontal directions, considered separate and
independent and that, for each one of them to determine at least by the three first
natural modes. In the systems with irregular distribution of mass or rigidity, whether in
plant or elevation, this minimum demand may be clearly insufficient; in such cases, the
Special Technical Specification will indicate which and how many degrees of freedom
shall be considered in the analysis and the number of natural modes that shall be
determined.
The determination by the calculation of natural frequencies and modal vectors that shall
be employed in the assessment of the response may be performed supposing that the
there is no damping.
To determine the size of each natural mode to the strains (internal forces, bending
moment, etc.), the basal shear force Hj will be calculated contributed by the j order
mode and by the formula:
Hj = Cj M j
(5)
where Cj is the modal seismic design coefficient for j mode, determined as indicated
ahead, and Mj is the mass of the equivalent modal oscillator calculated by the formula.
2
[ i mi ij ]
Mj =
2
i mi ( ij )
(6)
in which Fij is the movement amplitude of mass mi when such oscillates freely in mode j,
the index is to individualize the masses considered in the model and the sum includes
all masses.
11
COLBUN S.A.
ETG - 1.111
Cj =
A (T j )
R
(7)
where A(TJ) is the ordinate of the linear response spectrum assessed for the period and
corresponding damping to the mode and R is a modification coefficient of the response
that complies with the triple purpose of considering the ductility of the structure,
consider the possibility of more than one resistance line and incorporate in the analysis
the experience related to the behavior of structures similar to the one analyzed when
facing real earthquakes.
In electric equipment with fragile components will be employed R = 1; i.e., the seismic
design strains will be those that correspond to the response assessed upon the linear
model.
For buildings, structures and civil works the values of R are specified in Chapter 3.
In general, the damping will be specified as a fraction of critical absorption for each one
of the modes considered in the analysis, without having to introduce them by means of
parameters concentrated in the mathematic model of the system. For the election of
the critical absorption fraction that will be employed in each case the indications of
clause 1.5 and Table 1.1 will be respected. This disposition is not applicable to electric
equipment with fragile components neither to systems that contain elements destined
specially to dissipate energy (mufflers); for such equipment and such systems, the
absorption shall be incorporated to the mathematic model by means of discrete
elements of linear behavior which absorption constant shall be elected according to the
level of strains and deformations. In the event of electric equipment with fragile
elements the conditions of clause 2.7.12 shall be respected related to damping.
The strain S resulting from the superposition of the modal strains Sj will be obtained by
the formula
12
COLBUN S.A.
ETG - 1.111
S=
1
2
| Sj | +
j=1
1
2
r 3
2
j
j=1
(8)
where r indicates the number of modes includes in the analysis.
The resultant seismic strains occasioned by the horizontal movement of the land in the
direction in which the dynamic analysis is being performed will overlap those due to
vertical seismic actions. In general, these last ones may assimilate to the static forces
in the form specified in clause 1.6.2. D. Exception to this rule is made for structures that
are sensible to the vertical vibratory movements, such as great projection, prestressed
beams, bridges with important spans, etc., for which is convenient to make a dynamic
analysis in the vertical direction. The cases in which the dynamic analysis in the vertical
direction results as obligatory will be indicated in the respective Special Technical
Specifications, which will indicate, additionally, the form of combining the resultant
strains of such analysis with those obtained in the seismic analysis for the horizontal
movement.
13
COLBUN S.A.
ETG - 1.111
The calculation report will indicate the or those more unfavorable cases contemplated in
the verification of the demands regarding the resistance, admissible strains,
deformations, displacements, tightness and other functional requirements, as applicable
in each case.
The calculation report shall include the following backgrounds that will serve as
indispensable grounds for the formulation of the mathematic model that will be
employed in the analysis:
b) Edge conditions: for the system as a set and connection between elements that
constitute it.
c) Distribution of masses: of the parts and main components, elements rigidly adhered to
the structure, permanent loads and content, as corresponds in each special case.
d)
COLBUN S.A.
ETG - 1.111
matrix, frequencies and modal vectors, equivalent modal oscillator masses, participation
coefficient of the modes. Seismic strains will also be registered, in each one of the
elements submitted to verification, for each mode and each one of the analysis
directions, together with the strains resulting from modal spectral overlapping (clause
1.6.3.). The demandable verifications will be performed for the load status that includes
seismic action, explicitly stating their results.
If the calculations have been performed by computer, a description of the program
employed shall be provided (or access to the users manual guide) with enough detail to
verify the input data, interpret the results and determine if the calculations comply with
the current Specifications. The list submitted shall clearly identify the program
employed, the structure submitted to analysis, the input data, the final results, the units
used to express the physical magnitudes and the processing date.
Finally, the calculation report shall expressly register and outline that the prescriptions
contained in the current Specification and Special Technical have been complied when
applied.
15
COLBUN S.A.
ETG - 1.111
TABLE 1.1.
TYPICAL DAMPING VALUES
STRESS LEVEL
1. Low: Stress really below
the
proportionality
limit
(below 0.25 times the flow
point)
2. Medium: Stress not
greater to more or less half
the flow.
16
z%
0.5 - 1.0
1 - 2
2 - 3
3 - 5
5 - 7
2 -3
5 -7
7 - 10
10 - 15
5
7 - 10
10 - 15
20
2-5
5-7
7 - 10
COLBUN S.A.
ETG - 1.111
2.
2.1. Scope.
The current chapter complements the provisions of Chapter 1 in respect to the General
Conditions for seismic verification and design of electric equipment, mechanical
equipment and its components, supporting structures, anchorages and structural
connections.
The prescriptions of the current chapter will prevail over those of Chapter 1 and, are
hereinafter subordinate to those provided in the corresponding applicable Special
Technical Specifications.
2.3.1.Category A.
-
17
COLBUN S.A.
ETG - 1.111
Valves (globe, butterfly, others) of main intake, its connections and switching system.
Steam boilers and its auxiliary equipment, such as: grinders, fans and air and gas ducts,
precipitators and coal and ash silos.
Steam-generator turbine set and its auxiliary, control and lubrication equipment.
18
COLBUN S.A.
ETG - 1.111
Power switches.
Power transformers.
Step-up transformers.
Pliers.
Re-connectors.
Lightning rods.
Shunt reactors.
Relays.
19
COLBUN S.A.
ETG - 1.111
Coupling condensers.
Wave Traps
Stationary batteries.
Battery loaders.
Single-phase inverters.
2.3.2.Category B.
-
20
COLBUN S.A.
ETG - 1.111
Hydraulic grids.
2.3.3. Category C.
-
21
COLBUN S.A.
ETG - 1.111
a)
b)
Equipment that, due to the fragility of the materials of some of its components,
present special characteristics in their failure mode, which due to complexity, size or
weight results impracticable or impossible to forward to dynamic tests on vibratory table
as a complete set (examples: sheltered substations insulated in SF 6, power
transformers, refractory material walls inside boilers).
d)
COLBUN S.A.
ETG - 1.111
with the above those eventual actions which occurrence probability with the earthquake
is not despicable, such s short-circuit torque, transient axial thrust in turbines, etc.
23
COLBUN S.A.
ETG - 1.111
H =
1,2 a
W
g
V =
0,6 a
W
g
C =
1,2 a
(9)
C =
0,6 a
(10)
H 0,5 W
(C 0,5)
V 0,25 W
(C 0,25)
(11)
(12)
COLBUN S.A.
ETG - 1.111
value indicated in the Special Technical Specifications. The force H will be distributed as
established in the final part of the clause 1.6.2. C, using formula (3). The force V will be
distributed in the proportion of the weights of the parts in which the system is divided for
its analysis.
Hx =
1,2 a
hx
1+
W
g
h
(13)
Hx W
(14)
where:
h =
hx =
floor height on which the equipment is anchored, referred to the buildings basal level.
The seismic vertical force will be calculated in the form specified in clause 2.5.2., where
a is the maximum horizontal acceleration of the land in which the building is erected.
If the building or structure to which is the equipment rigidly anchored has been analyzed
by the dynamic method, instead of formula (13), the following will be used:
Hx =
1,2 a x
W
g
(15)
25
COLBUN S.A.
ETG - 1.111
with the same limitation of the formula (14). Here ax is the maximum horizontal
acceleration of the anchorage floor, obtained to determine the linear response of the
building in the direction to which the equipment shall be analyzed.
The equipment elastically assembled on upper levels of the building will be subject to
the provisions of the Special Technical Specifications.
COLBUN S.A.
ETG - 1.111
27
COLBUN S.A.
ETG - 1.111
The weight W, besides its own weight, will include those of the content, lining and
insulations.
Verification in the displacements will be made in case of earthquakes, to corroborate the
nonexistence of shock or interference danger with other elements. For such purpose
the assumption of maximum seismic deformation (horizontal or vertical) shall be
admitted as twice of the one calculated for the static method loads.
The minimum distance between the pipeline and the deformed duct, including lining and
any other element will be 100 mm, for the most unfavorable combinations of directions
and seismic strain direction and cold or hot pipeline cases.
It will be considered that hydraulic type buffers may be employed for pipelines of great
flexibility, which when conveniently displaced, may enable free thermal dilatation of
pipelines, although under a seismic, constitute fix points.
The interaction of the pipelines with structures or with fix equipment shall be considered,
inasmuch as for little flexible pipelines, connected to massive or rigid components, the
structures or the different structural elements, may be broken or damaged as
consequence of differential displacements due to rotation movements of the
foundations during earthquakes or by differential settlement and displacement
associated with foundation soil compaction due to vibration effect caused by
earthquakes. Rigid pipeline systems shall be avoided which could put up resistance to
the lateral displacement of a structure to which are anchored or connected.
COLBUN S.A.
ETG - 1.111
In the calculation of hydrodynamic pressures caused by the earthquake the cover of the
deposit will be considered as being rigid and part of the content, duly justified by
calculation, a solidarity moving with it. If a justification acceptable to the Head Inspector
is not provided, it shall be construed as the liquid mass adhered to the walls of the
deposit corresponding to the total content. This same hypothesis shall be made when
there is no free surface for liquid inside the deposit.
If there is liquid spillage possibility due to seismic movement, is shall be corroborated
that the outflow above the free rest level is enough to avoid such occurrence. In
covered tanks, the support structures that sustain it shall be verified and if connections
to the walls are watertight and capable of resisting the hydrodynamic pressure that is
produced when the overflow is insufficient.
B.
2.6.4.Floodgates.
In the seismic design of floodgates and its supports and anchorage, in addition to the
forces due to proper weight and hydrostatic pressure, the following seismic forces are
considered:
-
H =
1,2 a
W
g
(H 0,5 W)
(16)
29
COLBUN S.A.
ETG - 1.111
V =
0,6 a
W
g
(V 0,25 W)
(17)
P =
1,25 ha
z
sen
2h
g
(18)
gravity acceleration.
2.6.5.Traveling crane.
The seismic analysis of the traveling crane will be made employing the static method.
The seismic coefficient of horizontal and vertical design will be:
Ch =
C =
1,2 a
g
0,6 a
g
C h 0,4
C v 0,2
(19)
(20)
where a is the maximum horizontal acceleration specified in clause 1.3. The weight W to
30
COLBUN S.A.
ETG - 1.111
which is applied such coefficients include the crane weight plus the car and other
equipment, but doesnt include the loads freely suspended.
The seismic forces over the traveling crane are not combined with other horizontal
forces eventually occurring, such as brakes and the dynamic forces associated to the
normal equipment operation.
Adjustable bumpers shall be made available with the purpose of stopping from falling in
case of derailment or earthquake. These bumpers will be supported on the crane track.
Bumpers will also be arranged to limit the crane movement in the vertical direction and
avoid it from leaping from the rails.
a)
maximum displacement is such that, according to clause 1.3 and according to the
seismic category, correspond to applying to standardized equipment susceptible to
being installed in places with several seismic conditions, not necessarily known
beforehand.
b)
In the vertical direction: a uniform and constant acceleration field with intensity
31
COLBUN S.A.
ETG - 1.111
32
COLBUN S.A.
ETG - 1.111
2.7.4.Material characteristics.
The documents that endorse the guaranteed characteristics of the materials (trial
protocols issued by the respective manufacturers) shall be delivered. These include the
following:
-
Absorption level that corroborate the damping, if such is foreseen in the design. The
protocols shall demonstrate that the absorption is not less than the minimum value
guaranteed in the range of temperatures between -10 oC and +55oC.
In order to determine the admissible strain for the traction due to flexion in the insulators,
values of characteristic resistance that dont exceed 110 daN/cm 2 may be employed,
33
COLBUN S.A.
ETG - 1.111
without needing greater justification of the Contractor. Without limitation, before the
execution of seismic tests, all insulators supplied by Colbn S.A. will be subject to routine
tests consisting in submitting each insulator, assembled in the flanges foreseen in the
equipment design, to a flexion moment equivalent to 70% of the guaranteed flexion
moment, in each one of the orthogonal directions considered separately and in both
directions.
If the Contractor uses values of characteristic resistance greater than 110 daNcm 2, the
shall be justified with rupture tests to flexion on a sample formed by not less than 5
insulators extracted randomly from the fabrication lot supplied by Colbn S.A., in order to
determine the value of the characteristic resistance Rc defined as:
Rc = R - 2 sr
(21)
where R and sr are, respectively, the mean values and the Standard deviation of the
rupture stress, obtained as of the results of the trials by the formulas:
n
R =
Ri
Sr =
Ri - R
(22)
n -1
where Ri (i= 1, 2, ....., n) are the rupture stress values observed in trials and n 5 is the
number of insulators tested.
The determination of the insulators characteristic resistance will consider the final
disposition of parts assembled with the purpose of considering all stress concentrations
that such assemblage could produce.
In all cases the quality Standard and trial standards employed shall be notified.
For insulators, the characteristic resistance shall be indicated in the conclusion of the
flexion moment in the critical section of insulator rupture.
34
COLBUN S.A.
ETG - 1.111
b)
c)
H =
1,2 a
W
g
(H 0,5 W)
(23)
V =
0,6 a
W
g
(V 0,25 W)
(24)
35
COLBUN S.A.
ETG - 1.111
they are mechanically coupled. In order to make the verification, the most unfavorable
hypothesis shall be considered in respect to the direction in which the seismic forces act
over each one of the parts, equipment or structures mechanically coupled.
H =
1,2 AW
g
V =
0,6 AW
g
(25)
where A is the maximum ordinate of the subdue response spectrum that should be
applied according to clause 2.7.2.
The absorption value employed in the determination of A shall count with the approval
of the Head Inspector.
When applying this variant of the static method, force H shall be distributed among the
parts according to equation (3) of clause 1.6.2. C. The force V will be distributed in the
proportion of the weights of the parts.
36
COLBUN S.A.
ETG - 1.111
2.7.7. Seismic qualification methods for equipment to which the static analysis is not
applicable.
When the conditions to apply clauses 2.7.5 and 2.7.6 are not achievable, the seismic
verification and qualification of the electric substations will have the following steps:
A.
Analytical verification.
Among the terms set forth by the Contract for the delivery of plans and technical
information for the approval of the Head Inspector, the Contractor will submit for
approval of Colbn S.A. the calculation report with a dynamic analysis of the design.
The calculation report will comply with the requisites of clause 1.7 of this Specification.
This calculation has as purpose to opportunely verify, before tests, that the critical points
of the design have been settled by the manufacturer. This calculation may be performed
upon modal analysis or other which the Contractor considers more precise.
In the event when the modal analysis is chosen, the Contractor will follow the provisions
set forth in clause 2.7.12., of this Specification.
B.
Seismic qualification.
The seismic qualification will be made by a combination of trials and calculations and
will have the following stages:
1.
Execution
of
routine
tests specified
in the
corresponding
Special Technical
Specifications of the equipment to be tested. These tests will include the verification of
the characteristic resistance value of insulators, as correspondent according to clause
2.7.4 of this Specification.
2.
3.
Repetition of the routine tests indicated in 1, except for the verification tests of the
insulators characteristic resistance.
37
COLBUN S.A.
ETG - 1.111
4.
38
COLBUN S.A.
ETG - 1.111
each of the elements that the Head Inspector indicates. For the execution of these
tests, the equipment, in loading conditions, will be fixed over a rigid base by means
forecasted in its design.
Each one of the elements which frequency and absorption should be determined, will
be separated from its balance position, applying in the gravity center a force that will be
gradually increased until reaches a value not lower than one third of the element and
free oscillations will be registered that are produced when the force application is
abruptly interrupted.
When the Head Inspector considers necessary, he may indicate for free oscillation
exploratory test to be performed separate and independently, in more than one force
application direction. It will be preferentially selected the directions that correspond to
the more vulnerable axis of the equipment. If the majority of vulnerable axes are not
known, two orthogonal horizontal directions may be arbitrarily selected. In all cases, the
test directions shall count with the approval of the Head Inspector.
The absorption rate will be determined according to the graphic of Figure 2, employing
that register zone in which the declination of the oscillations appears with clarity and
precision. When the equipment contains two or more elements susceptible of vibrating
with similar frequencies, it is possible that its vibrations interfere producing flapping. In
such cases, the absorption will determine the procedure as indicated in the upper left
part of Figure 2.
The frequency of the tested element will be determined based on the three first
oscillation cycles registered.
B.
Static test.
At the height of the gravity center of the trialed element and in the horizontal direction
considered of interest, a force will be applied that will grow gradually under the almoststatic conditions, until reaches a maximum value. This value will be equivalent to the
product of the element mass by the acceleration of its gravity center, determined this
39
COLBUN S.A.
ETG - 1.111
last one upon calculation as of the response spectrum set forth in the Special Technical
Specifications, considering the element as a linear system with a freedom degree with
the frequency and the absorption obtained in the explanatory tests of free oscillation
referred in the previous letter A.
If the Special Technical Specifications have not been issued or if such specifications
dont establish response spectrum applicable to the equipment being studied, those
contained in Figure 1 of the current Specification will be applied.
Once obtained its maximum value, the force applied will be gradually reduced to zero
and repeated the operation until completed three loading and unloading cycles.
This test pursues the following purposes:
a)
b)
Determine strains and deformations in critical points under almost static conditions.
c)
Detect if permanent displacements are produced at the end of the load and unload
cycles.
d)
e)
In case of equipment equipped with dampers, corroborate that undesirable impacts are
not produced in such devices, before submitting the equipment to more severe dynamic
tests.
In order to comply with the objectives a) and b) deformation detectors will be installed at
least in the points of the most requested parts according to the response of the element
object of the trial and will determine the calibration curves for loading and unloading
(force applied versus deformation, or, force applied versus elastic tension).
To comply with the objectives c) and d), the transversal displacements will be measured
40
COLBUN S.A.
ETG - 1.111
in points of interest (for example, the gravity center or the highest point of the
equipment or trialed element; equipment terminals coupling points). The displacements
measured will be put into a graphic in terms of the force applied, for both loading as well
as unloading stages. This test phase will comply, additionally, with the purpose of
detecting deviations in respect with the linear elastic behavior.
The static test will be performed for the same horizontal directions of the exploratory
tests of free oscillation.
The Head Inspector may indicate that the static test shall be made making loading and
unloading cycles with inversion of the applied force direction, specially when intended to
determine the hysteretic behavior of the sealing, structural unions or energy dissipating
devices (buffers), as well as when there is the assumption that the mechanical behavior
depends in the direction of the force applied.
In the execution of the static tests the same requisites of equipment reinforcement and
fixation set forth in the free oscillation tests will be observed.
C.
Frequency scanning.
The frequency scanning test pursues the following objectives:
a)
Determine the equipment resonant frequencies as a set (modal frequencies) within the
range that interests for the determination of seismic response (0.5 - 30 Hz).
b)
Determine the absorption of each of the modes which frequency doesnt exceed 30 Hz.
This determination will be obligatory when the equipment is provided with elements
destined specifically to dissipate energy (buffers) or when intended to employ in the
calculations absorption values greater than the admitted in clause 2.7.12.
c)
Provide information for the performance of constant frequency tests (point D).
d)
41
COLBUN S.A.
ETG - 1.111
e)
Provide information that, considered jointly with the one obtained in the exploratory tests
of free oscillation and in the static tests, serves as background for the elaboration of the
mathematic model of the equipment.
The equipment, settled over a vibratory table according to the provisions set forth in
sub-clause G-04, will be submitted to oscillatory movement of its base at constant
amplitude and variable frequency. The frequency will vary in the stage between 0.5 and
30 Hz, with a variation speed that doesnt exceed one octave per minute, and will be
maintained constant in each stage during sufficient time period to establish the
maximum response, to this frequency, during at least 5 complete cycles of oscillation.
The test will be repeated for different amplitudes of the table, until obtained the
maximum response register in the different equipment elements, with readings not lower
than 10 times the minimum sensibility of the measured, for excitation frequencies
between 0.5 and 30 Hz, but without overcoming any of the elements 60% of the seismic
response that corresponds to it according to the specified response scope. The
compliance of this last limitation implies in the prior justification by the maximum
excitation level acceptable in the test, in frequency range.
The results will be represented in amplitude curves of the response for each element in
terms of excitation frequency, for different constant excitation amplitudes (resonance
curves). The resonance frequency and the absorption rates will be estimated as of
these curves. The curves will serve, additionally, to detect none linear dynamic effect.
D.
1.
A seismic test will be performed in a vibratory table with amplitude excitation essentially
constant and frequency equivalent to the fundamental frequency detected in the
scanning test. The oscillation amplitude of the vibratory table will be adjusted in such
42
COLBUN S.A.
ETG - 1.111
way that the "maximum sinusoidal acceleration" a1 of the gravity center of the element
results equivalent to the value provided by the formula:
a1 = K A ( T 1 )
(26)
where:
K
eventually have not been considered to specify the response spectrum of the
design (effects of foundation soil, soil-structure interaction, etc.). This factor will
be indicated in the Special Technical Specifications. When not specified, it will be
considered K=1.
A(T1)
In the test of sub-clause 1, the duration of the excitation shall be such that the response
is maintained during an interval not lower than 20 seconds or greater than 30 seconds.
2. For each one of the upper resonant frequencies determined in the scanning test, a
sinusoidal flapping test will be made consistent in the application of a set of five flapping
formed by five oscillation cycles each, separated among them by sufficiently large
pauses for the interference between the effects of successive flapping are despicable
(see figure 3).
3. The greater acceleration of the vibrating table during each flapping will be equivalent to 60%
43
COLBUN S.A.
ETG - 1.111
of the design acceleration, in the equipment base, established in the E.T.P. If such
specifications have not been issued or if the design acceleration has not been
established, the greater acceleration of the vibratory table during the flapping tests will
be equivalent to 0.3 g.
4. The Head Inspector may require the execution of additional flapping tests for frequencies
different from those determined in the scanning tests. The purpose of such additional
tests will be that the set of responses obtained in the vibratory table covers the design
scope in the entire range of frequencies of interest (0.5 - 30 Hz). The additional tests will
be performed according to the provisions of sub-clauses 3 and 4 above.
5. If the test referred in sub-clause 2.7.8.D.1, the "maximum sinusoidal acceleration" of the
gravity center exceeds the value a1 required by the equation (26), the correction of the
maximum value of tensions will be accepted, for the effects of comparing them with the
admissible voltages, multiplying them by the ration between a1 and the referred
"maximum sinusoidal acceleration"
6. Unless the Contractor has agreed with Colbn S.A. an alternative verification method for the
operation conditions that shall have the equipment such as power breakers (see clause
2.7.7.B), these equipment shall be submitted to an operation cycle unloaded, during the
frequency test execution part of sub-clause 2.7.8.D.1.
7. In case the excitation of an element to a corresponding response is not possible by the
procedure set forth in this clause or when the element is not accessible to measure its
response, a separate test shall be performed on such element, fixed on a rigid base by
elements identical to those that will be assembled in the equipment. The excitation
employed in such test and in the details of the test procedures shall be approved by the
Head Inspector.
E.
44
COLBUN S.A.
ETG - 1.111
1.
Horizontal acceleration response in the gravity center of each one of the elements
subject to verification.
2.
Elastic strain in at least two points of the most demanded part by response of each
element. If the columns are constituted by two or more insulators, the Inspector will
determine the need to install additional sensors. Special care will be taken with the
installation of deformation detectors to avoid incorrect registers; especially deformation
detectors shall be installed in insulators directly on porcelain and not over vitrified part.
3.
4.
5.
6.
Change of status (closed-open) of such elements with relays, contactors, breakers and
disconnecting switches.
F.
G.
Laboratory characteristics.
45
COLBUN S.A.
ETG - 1.111
The vibratory table shall have enough dimensions and mass in order to achieve an
oscillation predominantly sinusoidal, with the equipment assembled over it under test
conditions. This condition will be construed as complied when the amplitude of the sum
of harmonics in the displacement wave for a mass doesnt exceed 15% of the
fundamental amplitude.
2.
The frequency of the table shall be adjustable between 0.5 and 30 Hz, with a precision
better than 1% of the adjusted frequency value, with the purpose of achieving enough
excitation stability on the resonance points.
3.
The installation shall count with the measurement equipment necessary to achieve a
simultaneous registration of the measures indicated in letter E, of this clause.
Likewise, the Laboratory will count with the necessary computer facilities to calculate,
reliably, the effective values (rms) of the accelerations as of the instantaneous
acceleration registers.
4.
The safety of the trialed equipment will be performed according to the means foreseen
in the design for the equipment assemblage under service conditions. In the event when
the safety devices are not the same used in the assemblage of the equipment in
service, the Contractor will justify before the performance of the tests indicated,
additionally, which measurements will be performed to assess the influence of such
difference; in this case; the execution of tests will not be performed without the
authorization of the Head Inspector.
5.
The laboratory shall count with the calibration certificates, in force on the date of the
tests performance, for all instruments and sensors used in the corresponding
measurements. The certificates shall have been granted by a specialized institution,
independent from the Contractor or equipment supplier.
46
COLBUN S.A.
ETG - 1.111
Over price for the execution of alternative tests (for example, multi-frequency excitation,
seismic movement simulated with energy scope provided, etc.).
b)
Detailed description of the procedure to determine the excitation level in which the
seismic qualification shall be performed.
c)
d)
e)
Laboratory background that will perform the tests, with indication of similar tests recently
performed.
Colbn S.A. will indicate with the Contract adjudication, if accepts the alternative tests.
The definitive test program will be agreed with the awarded bidder.
COLBUN S.A.
ETG - 1.111
D.
The minimum tests of horizontal resistance will be performed according as indicated
next:
a)
The equipment, in energized conditions, will be fixed over a rigid base, by means
foreseen in its design. Instruments will be installed to register the acceleration in the
gravity center and deformation detectors (strain gauges) to register strain variations in
the most demanded points.
b)
1,3 W a1
g
where
a1 is provided by the equation (26) and W is the equipment weight over basal level.
c)
The average quadratic value (rms) of the first acceleration semi-waves shall be
equivalent or greater than
a1
2
d)
The equipment submitted to test shall not present, after it, any deformation, damage or
leakage and shall be fully capable of resisting any of the receipt tests specified.
Additionally, safety factors of elastic strain shall be assessed according to clause 2.9.;
for this effect, the qualification strains that are compared with the admissible will be
those obtained multiplying the average quadratic values by 2 of the first strain semiwaves.
COLBUN S.A.
ETG - 1.111
and control devices will be submitted to tests on vibratory table according to the
following pattern:
The elements indicated shall be assembled on panels, cabinets or corresponding cells.
Relays, instruments and control devices, and corresponding cells shall be assembled
with the means foreseen in the design.
The equipment will be submitted to an oscillatory movement at its base with a constant
acceleration and variable frequency between 0.5 and 30 Hz.
Unless otherwise
COLBUN S.A.
ETG - 1.111
performed, adopting for the response modification factor the value R=1.
The mathematic model of the equipment analyzed shall include a sufficient number of
elements for all important components of the equipment to be represented and to be
capable of reproducing vibrating modes with frequencies lower than 30 Hz.
Special care shall be taken when modeling the coupling conditions between the subsystems or complex equipment parts, as well as the assignment of absorption values for
the different natural modes. Due to the importance that the absorption has for the
assessment of the response, it is convenient that the estimated values to be on the safe
side. Therefore, unless the measurement results otherwise justifies, the absorption
associated with the joints or connections may not be greater than the values provided
next as percentage of the critical absorption:
-
Welded joints
4%
7%
Fragile components
0.5%
50
COLBUN S.A.
ETG - 1.111
Internal pressure in elements that contain gas or air; in case of power switches the
internal pressure will correspond to the maximum work pressure when performed the
interruption of nominal short-circuit current.
Sudden pull of equipment terminals: will suppose the direction that provides the most
unfavorable combination with a value of:
100 daN for equipment with nominal voltage equivalent or lower than 245 kV.
175 daN for equipment with nominal voltage greater than 245 kV.
Other service strains (for example, those originated by the operation of oil pressure
mechanisms of power breakers, compression forces originated by fixation devices of
power transformers).
The coupling has enough clearance to admit dislocations equal to or greater than the
51
COLBUN S.A.
ETG - 1.111
sum of relative dislocations of each one of the components in respect to the ground. If
the components are not assembled over a common foundation, such circumstance shall
be considered.
2)
3)
COLBUN S.A.
ETG - 1.111
structure dont occur due to equipment failure or form the own connection and
anchorage elements. Special care shall be taken in case of equipment that has to act
jointly with the structural elements due to their rigidity of the building destined to resist
horizontal forces.
The admissible strains under seismic conditions in the materials of the anchorage
devices are specified in clause 2.9.
2.9. Admissible Strain.
In general, the seismic verification of mechanical and electric equipment, as well as
seismic design of its supporting structures, fixation and anchorage elements, will be
made following the criterion of admissible strains without loss to the verifications for
admissible dislocations and other criterions applicable to special equipment.
For those load combinations which includes seismic action, the admissible strains in the
ductile materials of members and structural connections may be even 33% greater the
strains admitted by the standard agreed for none eventual load status, but without
exceeding 80% of the flow point.
For fragile materials (porcelains) the admissible tension to traction due to flexion, under
seismic conditions, will not exceed 55 daN/cm 2, unless, according to the provisions of
clause 2.7.4, the Contractor justifies with trials a characteristic value Rc greater than 110
daN/cm2. In this last case, the admissible strain will not exceed de 1/2 Rc.
3.
3.1. Scope.
This chapter contains general dispositions that contemplate the provisions set forth in
Chapter 1 in respect to the analysis and seismic design of civil works. In general,
seismic actions are specified here with more details that shall be considered in the
structural calculation of these works.
53
COLBUN S.A.
ETG - 1.111
The prescriptions of the current chapter will prevail over Chapter 1 and, therefore, will
be subservient to those provided in the Special Technical Specifications when
applicable.
The combination of actions that characterizes the different load status to which the
structure should be designed or verified, including those combinations in which seismic
actions are interposed, as well as also safety coefficients, admissible strain, load
resistance increasing or reduction coefficients, will be those prescribed in the Special
Technical Specifications applicable to the materials and work types or structures
covered in each special case. The Special Technical Specifications will indicate which
standards, specifications or design guides are applicable and establish the exceptions
or additional demands that eventually are necessary adopted.
54
COLBUN S.A.
ETG - 1.111
Table 3.1.
Civil Works Classification by Seismic Categories
WORK
1.
2.
3.
C AT E G O R Y
A
A
B
C
A
B
C
A
A
A
B
A
A
4.
A
A
Transmission Systems.
- Transmission line towers
- Substation command houses
A
A
55
COLBUN S.A.
ETG - 1.111
It will be adopted as the start point the linear response spectrum of accelerations A(T,z)
that the Special Technical Specifications assigns for the work site and corresponding
seismic category.
I such specifications have not been issued or if these dont mention the linear response
spectrum applicable to the work site, the start point to elaborate the design spectrum will
be the linear response spectrum of figure 1, with due consideration to the seismic
category of the work to which they apply.
A value for the damping ratio z shall be adopted according to Table 1.1 and the pertinent
clauses of these General Technical Specifications.
The ordinates a (T) of the design spectrum will be provided by the following
expressions:
(T) =
( T1 ) =
A (T, )
,
R
T > T1
A ( T1 , )
R
(T) = (1 -
(27)
T
T
)a +
* ( T1 ) ,
T1
T1
0 T T1
Where :
a
T1
56
COLBUN S.A.
ETG - 1.111
57
COLBUN S.A.
ETG - 1.111
Table 3.2.
COEFFICIENT R OF RESPONSE MODIFICATION FOR STRUCTURES OTHER THAN
BUILDINGS.
STRUCTURE TYPE
1.
2.
3.0
3.
3.5
3.5
4.
4.5
5.
6.
Chutes and elevated boxes that are not classified as inverted pendulum,
over ductile rigid frames or structure counterbraced with diagonals.
5.0
7.
Silos and chimneys which walls reach the foundation in a continuous form
5.0
8.
Bridge strain:
58
COLBUN S.A.
ETG - 1.111
- In the form of wall, for seismic forces acting parallel along the wall
3.0
- In the form of wall, for seismic forces acting perpendicularly along the wall
3.5
3.5
9.
5.0
3.5
4.0
COLBUN S.A.
ETG - 1.111
example, spillway walls, floodgate nipple, etc.) the design coefficients C and Cv will be
employed as specified in the equations (28) and (29) of clause 3.8.
When the preliminary analysis indicates the possibility of important dynamic
amplifications, due to the natural period estimated falling within the range of great
spectral ordinates, it one of the following methods shall be elected:
-
Static method with a horizontal seismic coefficient depending on the period value
estimated, distributing in the basal section according to the vertical in the form indicated
ahead.
60
COLBUN S.A.
ETG - 1.111
The soil liquefaction is manifested in the soils that are below the water table level.
Are susceptible to liquefaction the limpid granular soils or with none plastic thins or low
plasticity (Plasticity rate lower or equivalent to 5%).
The liquefaction potential of the soils that dont have gravels will be investigated based
on the results obtained from the Standard Projection Essays defined in the standard
ASTM - D 1586, using the criterions set forth in the "Simplified Procedure for the
assessment of the soil liquefaction" proposed by H.B. Seed and I.M. Idriss, duly
61
COLBUN S.A.
ETG - 1.111
updated, or other procedure that counts with the approval of the Head Inspector.
1 a
C =
4 g
1
4
si
0,30
(28)
a
a
, si < 0,30
g
g
C = 0,6
where a is the maximum horizontal acceleration on the land surface set forth by the
Special Technical Specifications for the site and seismic category of the work.
For the vertical seismic coefficient of the design Cv will be adopted
Cv =
1
C
2
(29)
The pressure increments over the water surface above and the decrement in the waters
below, due to the horizontal seismic action will be calculated by graphics and Tables that
gather the results obtained by Zangar. In the special case when the water surface
above is a plan, instead of the graphics the approximate expression below may be
employed:
62
COLBUN S.A.
ETG - 1.111
P =
y
Ch
y
*
2 - +
2
h
h
y
y
2 -
h
h
* f( )
(30)
with
f( ) = 0,735 - 1,25
- 1,75
180
180
(31)
y=
depth of the point where p is assessed, measured since the free rest surface.
h=
g=
q=
Q(y) = 0,726 py
2
M(y) = 0,299 py
(32)
It will not be considered increase in the sub-pressure for seismic purposes. Neither will
be considered the inertia forces that act over the accumulated sediments at the dam
wall bases; it shall only suppose that the effect of the hydro-dynamic pressures existing
up to the wall base, as if the sediments didnt exist.
The structures and equipment installed over the wall top, as well as its anchorages and
safety shall be designed at least for a coefficient equal to the double of coefficient C
employed in the seismic design of the wall, without loss to the provisions of clause 3.6.
63
COLBUN S.A.
ETG - 1.111
Conduct geologic studies to establish the eventual existence of local failures, its nature
and seismic activity.
Geotechnical studies to assess foundation ground stability at the work site, under
seismic conditions and, in special, to determine its liquefaction potential.
Geotechnical studies which purpose is to assess the seismic stability of the natural
slopes surrounding the reservoir and the possibility that such produces slippages or
64
COLBUN S.A.
ETG - 1.111
avalanches, including underwater slides that imply in spillage risks over the dam body.
-
Ground and laboratory investigations to define the dynamic characteristics and material
resistance (wave propagation speed, transversal elasticity module, absorption, etc.).
3.9.2.Analysis Procedures.
The seismic design of the earth and rockfill walls will be made over the limiting base of
permanent deformations and displacements caused by the design seism at values that
are defined as admissible.
For dams with heights greater than 60 m the calculation of permanent displacements
will be accepted according to the simplified method of Makidsi and Seed, or other
similar ones that count with the approval of the Head Inspector, whenever the dam wall
material is not subject to fast and important increases of pore pressure, under dynamic
load action and that dont produce great deformations due to the accumulated effect of
load cycles. When the height of the wall exceeds 60 m., or any of the conditions
recently numbered are not complied, other analysis methods shall be applied that are
not covered by the current Specification.
The Special Technical Specifications may qualify the wall designed as "critical work", yet
by the great magnitude of eventual damages or the risk for Human Township sited
downstream. The walls classified as such shall be submitted to special analysis
procedures, established in the respective Technical Specification Particular.
COLBUN S.A.
ETG - 1.111
load actions may move, whether due to translation or rotation, in an amount sufficient to
generate an active pressure status in the filling it sustains.
The thrust over deformable walls, both under seismic conditions and none seismic, are
calculated supposing that the filling is presented in a limit balance status.
Conventional retaining walls belong to a class of deformable walls, founded over
grounds and that have free cap. The retaining walls with free cap, founded on rock, will
be designed as they were deformable, but will be verified as rigid, considering the
strains in this last condition as of eventual nature.
Rigid (none-deformable) walls are earth filling structures that cant move or rotate, even
when laterally loaded (e.g.: underground walls propped by floor slabs, buried box walls).
The thrust over rigid walls, in both seismic and none seismic conditions are calculated
under the hypothesis that the soil retained by it is in elastic balance, i.e., are far from the
limit balance status.
The basic hypothesis of Mononobe method will be accepted, according to which the
pressure that the filling exercises over the retaining wall, under seismic conditions, may
be calculated according to the usual theories of earth thrust applicable, under static
conditions, to the wall type and for the border conditions that rule in the case submitted
to exam, with the purpose of aggregating to the gravity field a field of fictitious, uniform
and constant forces of components khg, in the horizontal direction perpendicular to the
wall cap and kvg, in the vertical direction, where kh and kv are two seismic coefficients,
horizontal and vertical, respectively, and g is the intensity of the gravity field. The
problem is therefore submitted to the usual methods, changing the intensity of the
gravity field for.
g = g
k h2 +
1 - kv
(33)
and rotating the internal wall outer face and the free filling surface in an angle q
provided by
66
COLBUN S.A.
ETG - 1.111
kh
1 - kv
= arc tg
(34)
According to which the applicable theory is the Coulomb or Rankine, the calculation
method of thrust under seismic conditions will be denominated Mononobe - Coulomb or
Mononobe - Rankine.
The assessment of the thrust in general (internal outer face wall not flat, irregular
surface filling, overload of the filling surface, water table, etc.), will be performed by well
known graphic methods. In the simpler cases of homogeneous filling, without water
table, straight internal outer face and flat free surface without overloads, the formulas
provided in the continuation and in sub-clause 3.10.2 and 3.10.3 may be applied. Its
convenient to warn that such formulas are only valid if, in addition to the conditions
recently listed, the following is complied:
-
The soil with immediate contact with the internal outer face is formed by filling placed
after the construction of such wall.
The balance may be studied by longitude wall unit (walls sufficiently large).
Es =
1
H2
2
1 - kv
(35)
Ks
where:
Es
67
COLBUN S.A.
ETG - 1.111
Ks
Kv
Counterfort walls in cantilever, for which the Mononobe Ranking method will be
applied.
A.
K aS
cos2 ( - - )
=
cos cos2 ( + ) * cos( + + ) (1 +
2
n)
(36)
where:
n =
sen ( + ) * sen ( - - i)
cos ( + + i) * cos (i - )
(37)
COLBUN S.A.
ETG - 1.111
d = friction angle between the concrete and filling (normal conditions may be suppose d=/ 2)
i = filling inclination.
kh
1- kv
= arctg
The active thrust coefficient under seismic conditions KaS is provided by:
(see fig. 4b).
K aS =
cos i
2
[ cos (i - ) - m ] + [sen (i + ) - sen (i - )]
cos - [ cos (i + ) + m ]
(38)
where:
m = cos2 (i + ) - cos2
(39)
Ka =
cos2 i - cos2
cos2 i - cos2
69
(40)
COLBUN S.A.
ETG - 1.111
ES =
1
H 2 ( 1 - k v ) K os
2
(41)
where
K os = f K o
(42)
f =
K as
Ka
(43)
An amplification coefficient that will be considered at the ration between the thrust
coefficients under seismic conditions and static conditions, calculated according to the
formulas from Mononobe - Coulomb or Mononobe Rankine method, according to
which corresponds the best wall conditions.
70
COLBUN S.A.
ETG - 1.111
surface.
3.10.5. Seismic Coefficient Kh y Kv .
Except when the election of other values satisfactorily justifies at the decision of the
Head Inspector, the seismic coefficients Kh and Kv will be.
kh =
1 a
2 g
kv =
1
Kh
2
(44)
(45)
where the maximum ground acceleration of the work site indicated in the Special
Technical Specifications for the corresponding seismic category.
In case of deformable walls, instead of applying equation 44, the value Kh may be
achieved from the ratio:
a 0,087 v 2
kh =
g
a
1
4
(46)
where a and v are, respectively, the acceleration and maximum speed of the ground
according to the Special Technical Specifications and the seismic category of the work
corresponds to apply, and is the permanent horizontal displacement of the wall cap,
due to the earthquake considered admissible. The value of shall count with the
approval from the Head Inspector. The horizontal and vertical components of the inertia
forces corresponding to the wall mass will be calculated employing the same
coefficients Kh and Kv used in the ground thrust calculation. The vertical component will
be supposed as distributed uniformly in the entire wall volume. The same is valid for the
horizontal component, in case of rigid walls. In the other hand when considering
deformable walls the distribution of equation 3 (clause 1.6.2 C) will be used.
71
COLBUN S.A.
ETG - 1.111
Propagation speed of the several types of elastic waves in the ambience that surrounds
the work, or enough background to enable to determine them (elasticity modules,
density, rock quality rates, etc.)
In the calculation will be considered the attenuation of the acceleration amplitudes and
ambience particles speed with the depth, the incidence angle that is more unfavorable
according to the wave type covered, the coherence of the movement and the effects
related with the heterogeneity of the ambience (passage of one type of soil to another,
for example).
The following basic formulas will be employed to calculate the deformations, angular
distortions and corresponding curvatures to the body waves to the work depth:
Compression and dilatation wave:
V
,
a
2
(47)
Shear waves:
72
COLBUN S.A.
ETG - 1.111
V
V
a
, =
, = 2
(48)
maximum curvature.
C =
1
a
*
2
g
Cv =
1
* C
2
(49)
COLBUN S.A.
ETG - 1.111
form that such specifications prescribe. For the response modification coefficient will be
used R=4.
m(z) = mo (z)
(50)
74
COLBUN S.A.
ETG - 1.111
b)
(51)
vertical coordinate
m0
me (z)
It is supposed that the mass mi (z) y me (z) moves jointly with the structure.
When the tower is a revolution body, the masses mi (z) and me (z) may be evaluated
using the results established for the tanks and cylindrical towers, using as cylinder
radium ri (z), if considering mi (z), and re (z) if requires to assess me (z). Here ri (z), re (z)
are, respectively, the inside and outside radius of the tower in the vertical coordinate
section z. If the tower section is rectangular, mi (z) it may be assessed using the
expressions for rectangular tanks; whereas me (z) will be assessed as if the tower was a
cylinder with diameter equal to the diagonal of a square with side equivalent to the
smaller or greater of the sides of the external rectangular section of the tower, according
to the direction of the seismic action whether longitudinal or transversal.
It will be aggregated, additionally, one mass M1, elastically connected to the inside walls
of the tower to represent the fundamental mode of the undulating superficial movement
of the liquid inside. For the calculation of the mass M1 and the form which it shall be
connected to the rest of the system will follow the same criterions employed in the
Housner model for rigid wall tanks.
The vertical seismic actions will be similar to a vertical acceleration field, uniform and
constant with intensity a/2, where a is the maximum horizontal acceleration on the
surface of the land established in the Special Technical Specifications.
For the assessment of the design scope corresponding to the horizontal actions will be
75
COLBUN S.A.
ETG - 1.111
3.14. Chimneys.
3.14.1. General.
In the election of the analysis directions shall be considered the localization of the
orifices and other singularities (duct input, manholes and cleaning wells, etc.). When
referred to chimneys which shaft doesnt reach directly the foundation, shall be
considered, additionally, the privileged directions that the supporting structure may have
Analogical considerations are valid for chimneys that are not self-supporting (anchored,
laterally supported into a structure) or chimneys with more than one fume duct. In
special cases, it will result as necessary to perform the analysis according to more than
two horizontal directions; such eventuality will be signaled in the Special Technical
Specifications.
The vertical seismic actions will be similar to a vertical acceleration field, the uniform
intensity and constant equal to half of the maximum horizontal acceleration on the
ground surface, driven to upward or downward according to which of the directions
results as more adverse.
The shaft of the chimney will be molded with a beam that deforms exclusively by flexion,
without effects P - D. Namely, the additional flexion moments produced by vertical
forces as consequence of lateral displacements due to seism will be despised.
In the analysis will be included the mass of the shaft, ducts, lining, armoring, isolation,
support console and other accessories adhered to the chimney. In the event when the
steel chimneys are lined with shotcrete (gunite), the rigidity of the additional flexion shall
be considered contributed by the lining. The Special Technical Specifications will signal
if necessary to consider the interaction of the soil-structure.
Preferentially, the spectral modal analysis method described in clause 1.6.3 will be
employed, including the superposition procedure of modal responses that are specified
76
COLBUN S.A.
ETG - 1.111
there. The modal analysis will be obligatory in case of chimneys that lay over a
supporting structure.
The method will be applicable to analysis of chimneys with height not greater than 60 m
which shaft reaches directly the foundation. Only estimative preliminary calculations will
be applied to greater height chimneys.
s T s2 + T 2
=
2
T s2 + T
(52)
where:
z =
zs =
absorption of the structure over fix base ( = 0,03, for reinforced concrete chimneys; =
77
COLBUN S.A.
ETG - 1.111
TF =
sway period of the structure as it was a rigid body over the elastic foundation.
Ts =
period of the first mode for the structure with its fix base.
The modification coefficient of linear response will be applied according to the provisions of
clause 3.4. In general, the value R = 4.5 will be used except for reinforced concrete chimneys
on site which reaches in a continuous form the foundation; in this last case the value R = 5 may
be adopted.
H =
A (T, ) W
gR
(53)
where:
A(T,z ) =
acceleration of gravity.
78
COLBUN S.A.
ETG - 1.111
T =
1,57 h2
3 Do - Dh
(54)
Where T is expressed in seconds and the other symbols have the following meaning:
h =
Height, m.
D0 =
Dh =
E =
Once obtained the basal shear force, its distribution according to the height and calculation of
flexion and bending moments will be performed as provided in the Chilean standard NCH 433
of. 72 in its clause 6.2.1 for flexible structures.
79
COLBUN S.A.
ETG - 1.111
The horizontal direction of analysis will be chosen meeting the requirements of orifices and
other singularities (lateral discharge orifice; position of columns, when applicable; distribution of
the silos in the plant, when considering a battery of silos, etc.). In some cases it may result as
necessary to perform the analysis in more then two horizontal directions; such eventuality will
be indicated in the Special Technical Specifications.
H = C W + W ef
(55)
where:
W = structure weight and of elements jointly adhered to it.
Wef = efficient weight of ensilaged material, defined as indicated next:
-
In 80% of the ensilaged material, when such material lies directly on the
ground.
C =
80
COLBUN S.A.
ETG - 1.111
In item (b) of clause 4.2.1 of the Standard ANSI/ACI 313-77, when enumerating the
overloads reference is made among them those from wind and earthquakes, specifying
that they will be designed considering the greater among them. Its convenient to
aggregate that even if the wind conducts to greater strains than the earthquake, the
structural elements (e.g.: columns) shall be detailed to obtain the required rigidity under
seismic conditions.
COLBUN S.A.
ETG - 1.111
construed that under seismic conditions, the vertical force acting in the bottom by the
ensilaged material is equivalent to 80% of the material weight. To such forces will be
aggregated the thermal strains that shall be considered according to the ensilaged
material nature.
Additionally the other loads and strains that shall be considered, the columns that
sustains the bottom of the silos or chutes shall be capable of supporting the vertical
loads received by the bottom, including the total of the ensilaged material weight when
the load condition considered includes the seismic actions.
3.16. Cooling Towers.
The design of cooling towers in reinforced concrete in hyperboloid revolution form will
be made according to the recommendations of the Committee 334 of ACI-ASCE: "ACI
334. 2R-77 (Rev.1982). Reinforced Concrete Cooling Tower Shells - Practice and
Commentary".
Such as indicated therein, a modal spectral analysis may be employed supposing that
the seismic action of a sole horizontal component of arbitrary direction. The linear
response spectrum employed in the analysis will be indicated in the Special Technical
Specifications. Absorption of 5% of the critical will be supposed in all modes. The
superposition of modal responses will be made according to the provisions of the
current General Technical Specifications (clause 1.6.3. equation. 8).
In the preliminary design will be adopted a modification coefficient of the response R =
2.0. In the final design may be adopted values greater than R whenever such procedure
is justified, upon none linear analysis, in the form recommended in Section 4.5 of the
Committee Comments ACI-ASCE.
COLBUN S.A.
ETG - 1.111
atmosphere, will be made following the provisions of Appendix E of the standard "API
Standard 650-Welded Steel Tanks for Oil Storage", 7th Edition, November 1980
(ANSI/API 650-1980, Rev. 1, February 1984), with modifications at the clauses that are
indicated:
I
E.3.3.2
0,45
C 2 = 0,4
T
2
3
(56)
where T is the fundamental period of the undulation movement of the liquid container in
the deposit, expressed in seconds.
II
the work site, the formula for M contained in clause E.3.1 of the standard
API-650 will be employed as next.
M = CW 2 X 2 + C W r H t + W 1 X 1
(57)
C =
A (T , )
gR
(58)
83
COLBUN S.A.
ETG - 1.111
C =
A (T , )
gR
(59)
in which
A (T,z ) = ordinate of acceleration spectrum for the period T
of fundamental oscillation mode of liquid and the absorption z
= 0.005.
A (T',z') = ordinate of acceleration spectrum for the period
T' of the fundamental mode of the system formed by the
structure and the water adhered and an absorption z' = 0,02.
R
Clarification.
E.4.1. Y E.4.2.:
W L = 7,9 t b
F by G H
(60)
COLBUN S.A.
ETG - 1.111
Overflow.
E.8.1.: In order to reduce the risk of spillage and prevent damages
in the roof and the cylindrical wall surface, an overflow will be designed, r,
between the free surface of liquid and the structure of the cover not less
than.
(61)
Additional Dispositions.
In order to forestall the lack of cylindrical mantle of tanks not anchored
due to instability in compression, it will be corroborated that the following
condition is complied:
n
E t2 Wt d
t
*
*
2*
D H W 1 2H t b
0,1
> 5. I
a
g
(62)
where
n = 0,1 + 0,4
H
D
(63)
85
COLBUN S.A.
ETG - 1.111
z = 5%
z = 3%
z = 2%
The vertical seismic actions will be similar to a uniform and constant acceleration field
av, equal to an intensity of half the maximum horizontal acceleration of the ground. If
considered as acting simultaneously with the seismic horizontal strains, in the direction
86
COLBUN S.A.
ETG - 1.111
that results most critical for the structural element submitted to analysis. In special, the
effect of the vertical seismic actions, represented here, over the pressure exercised by
the liquid against the walls and the bottom of the deposit, is equivalent to multiply the
hydrostatic pressures (in repose) by the factor: 1 av /g.
3.19. BRIDGES.
3.19.1. Scope.
The specifications of the current section are applicable to the seismic design of bridges
of convectional structuring which largest stretch has a free span not exceeding 80 m. It
will be construed as conventional structuring bridges those which superstructure is
made based on beams or caisson piles, straight, of concrete (reinforced, prestressed or
post-stressed) of steel, either continuous or simply supported, with collaboration of
platform slab or without it.
They are not applicable to bridges that have other structural configuration (suspension,
anchored, in steel, etc.).
The buried bridges (culverts) will not need analysis or seismic design, except when
corresponding to the dynamic increment due to earth pressure during an earthquake
against the walls (clauses 3.10). Such increment will not be applied if the total height of
the culvert is lower than two times the filling thickness over the rivet.
The current Specification doesnt include the analysis and design of the foundations.
3.19.2. Analysis Methods.
a)
87
COLBUN S.A.
ETG - 1.111
To model the structure (platform, beams, pillars, support guides or bolts) as one system
with freedom degree, the configuration of static deformation will be adopted to the form
of fundamental mode, for each analysis direction, that results from applying parallel
horizontal forces at the analysis direction and proportional to the weights of the different
parts of the work. Special care will be taken in representing the actual support
conditions of the platform; in special will be included in the deformity model the
neoprene support plates (elastometers).
The fundamental period will be determined by the Rayleigh method, i.e., as of the
equation that results from equalizing the maximum kinetic energy with the maximum
potential energy of the structure oscillating according to the approximate modal form
obtained as indicated in the previous paragraph. With this result and the value
attributed to the absorption the spectral ordinate A(T,z) will be obtained, using for such
the linear response spectrum indicated in the Special Technical Specifications. In these
cases z = 0.05 will be used, unless otherwise determined by the specifications recently
mentioned.
The simplified dynamic method may be employed in the design of structures relatively
rigid (T< 0,5 s ) and absorption relatively high (z= 0.05 or greater) that comply,
additionally, with the restriction of clause 3.19.1.
The bridges with one single stretch and the bridges formed by several independent
stretches, simply supported over stumps which height doesnt exceed 20 m are settled
within the application field of the simplified dynamic method. For such effect, the height,
of the stumps will be measured as of the corresponding undermine line to the annual
average outpouring line up to beams support.
The analysis will be made, separate and independently according to the parallel and
perpendicular directions of the longitudinal axis of the platform. It will be undertaken that
the displacements for each analysis direction are produced precisely in such direction.
Consequently, the method shall not be applied to bridges with major angles (greater
than 15).
88
COLBUN S.A.
ETG - 1.111
The method will not be applied in continuous beams bridges in which the rate between
the adjacent stretch spans is not settled between 0.8 and 1.25.
Such method will neither be applied when the stump have heights, or lateral rigidity,
very disparate.
Finally, the simplified dynamic method will not be applied when the platform is formed by
beams that have ball-socket joints between consecutive supports.
b)
89
COLBUN S.A.
ETG - 1.111
3.20. BUILDINGS.
3.20.1. General.
The seismic design of workshop or dwelling buildings and other similar structures will
comply with the provisions of standard Nch 433. of 72, in everything that contradicts the
current General Technical Specifications.
While the National Institute of Standardization doesnt issue the new standard for
seismic design currently in study, the criterions to conciliate the provisions of standard
Nch 433 Of. 72 with the provisions set forth in the current Specifications will be
established case by case in the respective Special Technical Specifications.
3.20.2. Machine House.
Whenever the static method is employed the seismic coefficient for horizontal forces will
be determined by the ratio:
90
COLBUN S.A.
ETG - 1.111
C =
(T)
g
where a(T) is provided by the equation 27 of clause 3.4 and T corresponds to the
natural functional period in the analysis of the direction.
For the calculation of a(T) will be employed the value indicated in the Special Technical
Specifications. The value of z will be selected following the indications of Table 1.1. The
angle periods T1 and T2 may be selected equal to those indicated in picture 1 for the
absorption that shall be applied.
3.20.3. Boiler supporting structures.
An analysis may be performed only with the purpose of pre-dimensioning the structure.
The definitive analysis will be made according to the dynamic method, following the
provisions of clause 2.6.1.
91
COLBUN S.A.
ETG - 1.111
EQUATION OF HYPERBOLE
FIG.1
NATURAL PERIOD
T (Sec)
92
v=50 cm/s
COLBUN S.A.
ETG - 1.111
93
94
CYCLES EACH
COLBUN S.A.
ETG - 1.111
95
MONONOBE OKABE THEORY, COULOMB CONDITIONS
COLBUN S.A.
ETG - 1.111
96
MONONOBE OKABE THEORY, RANKINE CONDITIONS
COLBUN S.A.
ETG - 1.111