NZM1-4 circuit-breaker series up to 1200 A

SK1230+1157_D_D-INT_GB-INT3.qxp

Switching, protection, communication


the new NZM1-4 circuit-breaker series
up to 1200 A

Reliable and safely controlling,


switching and managing
power. In industry, in buildings
and in machine construction.
Innovative protection concepts.
With built-in diagnostics and
communication functions.

Circuit-breaker NZM

Think future. Switch to green.


green

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1230-1157IVZ.fm Page 1 Saturday, May 20, 2006 5:22 PM

Moeller SK1230-1157EN-NA

Page
System overview
Circuit-breakers, disconnect switches
Overview
Circuit-breakers,
Disconnect switches for North America, 3 pole

2
4

Page
Circuit-breakers, disconnect switches
Accessories
Mechanical interlock
Remote operators
Plug-in units
NZM1 terminals
NZM2 terminals
NZM3 terminals
NZM4 terminals
Accessories

59
61
62
64
66
70
74
80
88

Circuit-breakers for North America


Thermomagnetic release, 3 pole
Magnetic 3 pole short-circuit release
Electronic release, 3 pole

6
10
14

Molded case switches for North America


3 pole

20

Insulated terminals

90

Disconnect switches for North America


3 pole

21

Engineering
Auxiliary contacts, trip indicating auxiliary contacts

Tripping characteristics
Tripping characteristics for circuit-breakers
Let-through characteristics for circuit-breakers

91
95

22

Technical data
Circuit-breakers
Disconnect switches
Molded Case Switches
Effective power loss
Terminal capacities
Remote operator, capacitor unit, auxiliary contact
Fitted with auxiliary contacts, timer differences
Undervoltage release, shunt release
Remote operator, capacitor unit
Data Management Interface (DMI Module)
Fieldbus connection
Direction of blow-out, minimum clearances, pipe cable lugs

102
107
108
110
112
114
115
116
117
118
119
121

Engineering
Mechanical interlock
Mechanical interlock for remote operator

122
123

Dimensions
Circuit-breakers, disconnect switches

125

Part number list

173

Alphabetical index

174

Circuit-breakers, disconnect switches


Auxiliary contacts
with screw terminal
Undervoltage releases
with screw terminal
Undervoltage release, off-delayed
Shunt release
with screw terminal
Door coupling rotary handles
Rotary handles with door interlock for UL/CSA
approved NA switches
Rotary handles
Rotary handles with door interlock
Main switch assembly kit

24
26
37
38
50
52
54
55
56

For Immediate Delivery call KMParts.com at (866) 595-9616

Circuit-breakers, disconnect switches


up to 1200 A

Content

SK1157_002-003_a_G.fm Page 2 Friday, May 5, 2006 2:15 PM

System overview
Circuit-breakers, disconnect switches

Circuit-breakers, disconnect switches


up to 1200 A

Moeller SK1230-1157EN-NA

4
5
3

6
7

26

8
2

25

1
22
24
23

10

11
21

20
19

16
17

13
12

18
14

15

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_002-003_a_G.fm Page 3 Monday, July 17, 2006 6:52 PM

Moeller SK1230-1157EN-NA

a 24
Circuit-breakers for North America
1
Rated uninterrupted current up to 1200 A
Switching capacity 25, 35, 42, 85,100 kA
at 480 V
Adjustable releases for overload and
short-circuit
Adjustable time selectivity
Earth-fault protection
Protection of systems, cables, motors,
generators
3 pole version,
UL489/CSA5, IEC 60947
a6
Circuit-breakers without overcurrent 1
protection for North America
Rated uninterrupted current up to 1200 A
Remotely tripped, with undervoltage or
shunt release
3 pole version, UL489/CSA5
a 20

Mounting accessories

Standard auxiliary contact


11
Switching with the main contacts
Used for indication and interlocking tasks

Control circuit terminal


For two terminals at top or bottom

Trip-indicating auxiliary contact


11
General indication of tripping with trip
due to overload or short-circuit as well as
voltage release
Early-make auxiliary contacts
25
For interlocking and load shedding circuits,
as well as for early make of the
undervoltage release in main switch/
Emergency-stop applications
a 24
Voltage releases
Undervoltage release
Non-delayed
OFF-delayed
Shunt release

25

a 26
Spacers

Delay unit for undervoltage releases

10

26

a 50
Door coupling rotary handle
Lockable
With door interlock

13, 15

a 50
Main switch rotary handle for side
panel mounting

12

14

16

19

a 62
Toggle lever interlock device

21

Data Management Interface (DMI


22
Module)
Access to diagnostics and operational data
Recording of current values
Parameterization and control of the circuitbreakers with electronic releases
a 88
EASY-LINK-DS data plug

23

Box terminals
Standard equipment of frame size 1
Fitted within the switch housing

Terminal cover
3
Protection against direct contact where
cable lugs, busbars or tunnel terminals are
used.
NZM1 a 68
NZM2 a 72
NZM3 a 78
NZM4 a 86
Clip plates
NZM1-XC35 for 35 mm top-hat rail
NZM1-XC75 for 75 mm top-hat rail

NZM1 a 66
NZM2 a 70
NZM3 a 76
NZM4 a 82
Plug-in and withdrawable unit

Insulating surround
18
For use with toggle levers, rotary drives
and remote operators protruding from the
enclosure

External warning plate/designation


label

17

NZM1 a 59
IP2X protection against contact with 2
a finger
For box terminals
NZM1 a 68
NZM2 a 72
NZM3 a 78
IP2X protection against contact with 4
a finger
For barrier
NZM1 a 68
NZM2 a 72
NZM3 a 78

a see main Moeller catalogue for


industrial switchgear
PROFIBUS-DP interface

NZM1 a 66
NZM2 a 70
NZM3 a 76
NZM4 a 82

NZM1 a 60
20

a 60
Flange Operator
In preparation

a 92

a 54
Remote operator
For ON and OFF switching and resetting
by means of 2-wire or 3-wire control.

Tunnel terminals for Al and Cu cable


Standard with control circuit terminal

Rear connection

a 50
Rotary handle
Lockable

NZM1 a 68
NZM2 a 72
NZM3 a 76
NZM4 a 86

a 60

a 56
Extension shaft
Can be cut to required length.

NZM1 a 66
NZM2 a 70
NZM3 a 74

a 60

Disconnect switches for


1
North America
Rated uninterrupted current up to 1200 A
Remotely tripped disconnect switches with
undervoltage or shunt release
3 pole version, UL489/CSA5, IEC 60947
a 21

Add-on functions

24

a 88

For Immediate Delivery call KMParts.com at (866) 595-9616

Circuit-breakers, disconnect switches


up to 1200 A

System overview
Circuit-breakers, disconnect switches

SK1157_004-005_a_G.fm Page 4 Monday, July 17, 2006 6:57 PM

Overview
Circuit-breakers, disconnect switches for North America, 3 pole

Overview
Circuit-breakers, disconnect switches for North America, 3 pole
Moeller SK1230-1157EN-NA

Moeller SK1230-1157EN-NA

Circuit-breakers
UL/CSA approved to UL 489, CSA 22.2 No. 5.1 and
to IEC/EN 60947
With main switch characteristics to IEC/EN 60204 and isolating
characteristics to IEC/EN 60947, VDE 0660
Rated uninterrupted current Iu = Rated current In
Adjustable overload releases Ir
Adjustable short-circuit releases Ii
Delayed short-circuit releases Isd

Basic switching capacity1)


NEMA Test Procedure

Thermomagnetic releases
Overload releases
Fixed

Adjustable

Iu
A
NZM1

NZM2

Iu
A
NZM1

NZM2

15 125

15 250

20 125

20 250

Without
Ir
A

1 x In

Iu
A
NZM1

NZM2

1.2 100

1.6 250

Electronic releases
Overload releases
Fixed
Adjustable

Without

Fixed

Adjustable

Iu
A

Iu
A

Ir
A

Iu
A

Iu
A

Iu
A

150
250

100
250

0.5 1 x In

90
220

250
600

250
600

Fixed

Adjustable

Ir
A

Iu
A

Iu
A

Iu
A

Ir
A

Isd
A

Ii
A

Ii
A

0.5 1 x In

220
450

600
1200

800
1200

0.5 1 x In

2 10 x Ir

2 12 x In

2 14 x In

240 V 60 Hz
480 V 60 Hz
600 V 60 Hz
400/415 V
440 V
525 V

sym. rms kA
sym. rms kA
sym. rms kA
kA/cos v
kA/cos v
kA/cos v

NZMB1-...-NA
35
252)

25
0.25
25
0.25
15
0.30

NZMB2-...-NA
35
25
18
25
0.25
25
0.25
15
0.30

Normal switching capacity1)


NEMA Test Procedure
240 V 60 Hz
480 V 60 Hz
600 V 60 Hz
IEC/EN 60947
400/415 V
440 V
525 V
690 V

sym. rms kA
sym. rms kA
sym. rms kA
kA/cos v
kA/cos v
kA/cos v
kA/cos v

NZMN1-...-NA
85
352)

50
0.25
35
0.25
20
0.30
10
0.50

NZMN2-...-NA
85
35
25
50
0.25
35
0.25
25
0.25
20
0.30

NZMN2-...E...-NA
85
35
25
50
0.25
35
0.25
25
0.25
20
0.30

NZMN3-...E...-NA
85
42
35
50
0.25
35
0.25
25
0.25
20
0.30

NZMN4-...E...-NA
85
42
35
50
0.25
35
0.25
25
0.25
20
0.30

NZMH2-...-NA
150
100
50
150
0.20
130
0.20
50
0.25
20
0.30

NZMH2-...E...-NA
150
100
50
150
0.20
130
0.20
50
0.25
20
0.30

NZMH3-...E...-NA
150
100
50
150
0.20
130
0.20
65
0.25
35
0.30

NZMH4-...E...-NA
125
85
50
100
0.20
85
0.20
65
0.25
50
0.30

IEC/EN 60947

High switching capacity1)


NEMA Test Procedure

IEC/EN 60947

Notes

240 V 60 Hz
480 V 60 Hz
600 V 60 Hz
400/415 V
440 V
525 V
690 V

sym. rms kA
sym. rms kA
sym. rms kA
kA/cos v
kA/cos v
kA/cos v
kA/cos v

1) Breakers conform to UL/CSA as well as the IEC regulations


IEC switching performance values are contained on the rating plate. a Technical data
2) for NZM...1-...-NA > 50 A 480Y/277V

Disconnect switches:
UL/CSA approved to UL 489, CSA 22.2 No. 5.1 and to
IEC/EN 60947
With main switch characteristics to IEC/EN 60204 and VDE 0113
isolating characteristics to IEC/EN 60947-3 and VDE 0660.
without overload and short-circuit releases
Rated uninterrupted current Iu = In

Rated short-circuit making capacity Icm


Rated short-time withstand current Icw (1s currentrms)

kA
kA

Short-circuit releases
System protection

Without

The approved switches are suitable for world-wide use. The UL and CSA certificates can be found at www.ul.com and www.csa.com
UL Certificates: file no.:
E 31593 (NZM1-4), E 148671 (N(S)1-4)
CSA certificates: file no.
165628 (NZM1-4)

Molded case switch


UL/CSA approved to UL 489, CSA 22.2 No. 5.1 and
to IEC/EN 60947-2, Annex L
400
550

600
800
1000
1200

N3-...-NA
25
12

N4-...-NA
53
25

With main switch characteristics to IEC/EN 60204 and VDE 0113


Isolating characteristics to IEC/EN 60947
without overcurrent protection
Rated uninterrupted current Iu = In
Values printed in grey available on request
Switching capacity
to UL 489, CSA 22.2 No. 5.1

IEC/EN 60947

For Immediate Delivery call KMParts.com at (866) 595-9616

240 V
480 V
600 V
400/415 V
440 V
525 V
690

63
100
125

160
200
250

NS1-...-NA
85
35

50
35
20
10

NS2-...-NA
150
100
50
150
130
50
20

400
600

800
1000
1200

Motor
protection

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

SK1157_004-005_a_G.fm Page 4 Monday, July 17, 2006 6:57 PM

Overview
Circuit-breakers, disconnect switches for North America, 3 pole

Overview
Circuit-breakers, disconnect switches for North America, 3 pole
Moeller SK1230-1157EN-NA

Moeller SK1230-1157EN-NA

Circuit-breakers
UL/CSA approved to UL 489, CSA 22.2 No. 5.1 and
to IEC/EN 60947
With main switch characteristics to IEC/EN 60204 and isolating
characteristics to IEC/EN 60947, VDE 0660
Rated uninterrupted current Iu = Rated current In
Adjustable overload releases Ir
Adjustable short-circuit releases Ii
Delayed short-circuit releases Isd

Basic switching capacity1)


NEMA Test Procedure

Thermomagnetic releases
Overload releases
Fixed

Adjustable

Iu
A
NZM1

NZM2

Iu
A
NZM1

NZM2

15 125

15 250

20 125

20 250

Without
Ir
A

1 x In

Iu
A
NZM1

NZM2

1.2 100

1.6 250

Electronic releases
Overload releases
Fixed
Adjustable

Without

Fixed

Adjustable

Iu
A

Iu
A

Ir
A

Iu
A

Iu
A

Iu
A

150
250

100
250

0.5 1 x In

90
220

250
600

250
600

Fixed

Adjustable

Ir
A

Iu
A

Iu
A

Iu
A

Ir
A

Isd
A

Ii
A

Ii
A

0.5 1 x In

220
450

600
1200

800
1200

0.5 1 x In

2 10 x Ir

2 12 x In

2 14 x In

240 V 60 Hz
480 V 60 Hz
600 V 60 Hz
400/415 V
440 V
525 V

sym. rms kA
sym. rms kA
sym. rms kA
kA/cos v
kA/cos v
kA/cos v

NZMB1-...-NA
35
252)

25
0.25
25
0.25
15
0.30

NZMB2-...-NA
35
25
18
25
0.25
25
0.25
15
0.30

Normal switching capacity1)


NEMA Test Procedure
240 V 60 Hz
480 V 60 Hz
600 V 60 Hz
IEC/EN 60947
400/415 V
440 V
525 V
690 V

sym. rms kA
sym. rms kA
sym. rms kA
kA/cos v
kA/cos v
kA/cos v
kA/cos v

NZMN1-...-NA
85
352)

50
0.25
35
0.25
20
0.30
10
0.50

NZMN2-...-NA
85
35
25
50
0.25
35
0.25
25
0.25
20
0.30

NZMN2-...E...-NA
85
35
25
50
0.25
35
0.25
25
0.25
20
0.30

NZMN3-...E...-NA
85
42
35
50
0.25
35
0.25
25
0.25
20
0.30

NZMN4-...E...-NA
85
42
35
50
0.25
35
0.25
25
0.25
20
0.30

NZMH2-...-NA
150
100
50
150
0.20
130
0.20
50
0.25
20
0.30

NZMH2-...E...-NA
150
100
50
150
0.20
130
0.20
50
0.25
20
0.30

NZMH3-...E...-NA
150
100
50
150
0.20
130
0.20
65
0.25
35
0.30

NZMH4-...E...-NA
125
85
50
100
0.20
85
0.20
65
0.25
50
0.30

IEC/EN 60947

High switching capacity1)


NEMA Test Procedure

IEC/EN 60947

Notes

240 V 60 Hz
480 V 60 Hz
600 V 60 Hz
400/415 V
440 V
525 V
690 V

sym. rms kA
sym. rms kA
sym. rms kA
kA/cos v
kA/cos v
kA/cos v
kA/cos v

1) Breakers conform to UL/CSA as well as the IEC regulations


IEC switching performance values are contained on the rating plate. a Technical data
2) for NZM...1-...-NA > 50 A 480Y/277V

Disconnect switches:
UL/CSA approved to UL 489, CSA 22.2 No. 5.1 and to
IEC/EN 60947
With main switch characteristics to IEC/EN 60204 and VDE 0113
isolating characteristics to IEC/EN 60947-3 and VDE 0660.
without overload and short-circuit releases
Rated uninterrupted current Iu = In

Rated short-circuit making capacity Icm


Rated short-time withstand current Icw (1s currentrms)

kA
kA

Short-circuit releases
System protection

Without

The approved switches are suitable for world-wide use. The UL and CSA certificates can be found at www.ul.com and www.csa.com
UL Certificates: file no.:
E 31593 (NZM1-4), E 148671 (N(S)1-4)
CSA certificates: file no.
165628 (NZM1-4)

Molded case switch


UL/CSA approved to UL 489, CSA 22.2 No. 5.1 and
to IEC/EN 60947-2, Annex L
400
550

600
800
1000
1200

N3-...-NA
25
12

N4-...-NA
53
25

With main switch characteristics to IEC/EN 60204 and VDE 0113


Isolating characteristics to IEC/EN 60947
without overcurrent protection
Rated uninterrupted current Iu = In
Values printed in grey available on request
Switching capacity
to UL 489, CSA 22.2 No. 5.1

IEC/EN 60947

240 V
480 V
600 V
400/415 V
440 V
525 V
690

63
100
125

160
200
250

NS1-...-NA
85
35

50
35
20
10

NS2-...-NA
150
100
50
150
130
50
20

400
600

For Immediate Delivery call KMParts.com at (866) 595-9616

800
1000
1200

Motor
protection

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

SK1157_006-009_b_G.fm Page 6 Friday, July 14, 2006 9:53 AM

Circuit-breakers for North America


Thermomagnetic releases, 3 pole

Circuit-breakers for North America


Thermomagnetic releases, 3 pole
Moeller SK1230-1157EN-NA

Rated current = rated


uninterrupted current

Setting range
Overload releases

In = Iu
A

Ir
A

Short-circuit
releases
Ii
A

Protection of systems and cables


3-pole
Fixed overload releases
Terminals standard
terminal screw as accessories
15

15

350

20

20

350

25

25

350

30

30

350

35

35

320 400

40

40

320 400

45

45

300 500

50

50

300 500

60

60

380 630

70

70

480 800

80

80

480 800

90

90

600 1000

100

100

600 1000

110

110

750 1250

125

125

750 1250

15

15

350

20

20

350

25

25

350

30

30

350

35

35

320 400

40

40

320 400

45

45

300 500

50

50

300 500

60

60

380 630

70

70

480 800

80

80

480 800

90

90

600 1000

100

100

600 1000

Basic switching capacity


35 kA 240 V
25 kA 480 V1)
18 kA 600 V2)
Part no.
Article no.

Price
see price
list

Normal switching capacity


85 kA 240 V
35 kA 480 V1)
25 kA 600 V2)
Part no.
Price
Article no.
see price
list

NZMB1-AF15-NA
281553
NZMB1-AF20-NA
281554
NZMB1-AF25-NA
281555
NZMB1-AF30-NA
281556
NZMB1-AF35-NA
272204
NZMB1-AF40-NA
272205
NZMB1-AF45-NA
272206
NZMB1-AF50-NA
272207
NZMB1-AF60-NA
272208
NZMB1-AF70-NA
272209
NZMB1-AF80-NA
272250
NZMB1-AF90-NA
272251
NZMB1-AF100-NA
272252
NZMB1-AF110-NA
281557
NZMB1-AF125-NA
281558

NZMN1-AF15-NA
281564
NZMN1-AF20-NA
281565
NZMN1-AF25-NA
281566
NZMN1-AF30-NA
281567
NZMN1-AF35-NA
274220
NZMN1-AF40-NA
274223
NZMN1-AF45-NA
274230
NZMN1-AF50-NA
274231
NZMN1-AF60-NA
274232
NZMN1-AF70-NA
274233
NZMN1-AF80-NA
274234
NZMN1-AF90-NA
274235
NZMN1-AF100-NA
274236
NZMN1-AF110-NA
281568
NZMN1-AF125-NA
281569

NZMB2-AF15-BT-NA
107611
NZMB2-AF20-BT-NA
107612
NZMB2-AF25-BT-NA
107613
NZMB2-AF30-BT-NA
107614
NZMB2-AF35-BT-NA
107615
NZMB2-AF40-BT-NA
107616
NZMB2-AF45-BT-NA
107617
NZMB2-AF50-BT-NA
107618
NZMB2-AF60-BT-NA
107619
NZMB2-AF70-BT-NA
107620
NZMB2-AF80-BT-NA
107621
NZMB2-AF90-BT-NA
107622
NZMB2-AF100-BT-NA
107623

NZMN2-AF15-BT-NA
107631
NZMN2-AF20-BT-NA
107632
NZMN2-AF25-BT-NA
107633
NZMN2-AF30-BT-NA
107634
NZMN2-AF35-BT-NA
107635
NZMN2-AF40-BT-NA
107636
NZMN2-AF45-BT-NA
107637
NZMN2-AF50-BT-NA
107638
NZMN2-AF60-BT-NA
107639
NZMN2-AF70-BT-NA
107640
NZMN2-AF80-BT-NA
107641
NZMN2-AF90-BT-NA
107642
NZMN2-AF100-BT-NA
107643

Moeller SK1230-1157EN-NA
High switching capacity
100 kA 240 V
65 kA 480 V
35 kA 600 V
Part no.
Article no.

Price
see price
list

Std. pack

Notes

1 off

Switches conform to UL/CSA as well as the IEC regulations.


IEC switching performance values are contained on the rating plate.
UL 489, CSA-C22.2-5.1, IEC/EN 60947-2
Fixed overload releases Ir
Adjustable short-circuit release Ii
Approx. 6 10 x In (ex-factory 6 x In)
NZM...-AF35/40-NA: approx. 8 10 x In
Fixed short-circuit releases Ii
350 A at In = 15 30A
1) For

basic switching capacity 25 kA 480 V and


normal switching capacity 35 kA 480 V the following applies:
for NZM...-1-...-NA: 480Y/277 V AC from 60 A.

Line and load Box Lugs installed

Notes

Notes for terminals a 67

For Immediate Delivery call KMParts.com at (866) 595-9616

NZMH2-AF15-BT-NA
107809
NZMH2-AF20-BT-NA
107810
NZMH2-AF25-BT-NA
107811
NZMH2-AF30-BT-NA
107812
NZMH2-AF35-BT-NA
107813
NZMH2-AF40-BT-NA
107814
NZMH2-AF45-BT-NA
107815
NZMH2-AF50-BT-NA
107816
NZMH2-AF60-BT-NA
107817
NZMH2-AF70-BT-NA
107818
NZMH2-AF80-BT-NA
107819
NZMH2-AF90-BT-NA
107820
NZMH2-AF100-BT-NA
107821

1 off

Switches conform to UL/CSA as well as the IEC regulations.


IEC switching performance values are contained on the rating plate.
UL 489, CSA-C22.2-5.1, IEC/EN 60947-2
Fixed overload releases Ir
Adjustable short-circuit release Ii
Approx. 6 10 x In (ex-factory 6 x In)
NZM...-AF35/40-NA: approx. 8 10 x In
Fixed short-circuit releases Ii
350 A at In = 15 30A
2) For basic switching capacity 18 kA 600 V and normal switching capacity 25 kA 600 V the following applies: for

NZM2.

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

SK1157_006-009_b_G.fm Page 6 Friday, July 14, 2006 9:53 AM

Circuit-breakers for North America


Thermomagnetic releases, 3 pole

Circuit-breakers for North America


Thermomagnetic releases, 3 pole
Moeller SK1230-1157EN-NA

Rated current = rated


uninterrupted current

Setting range
Overload releases

In = Iu
A

Ir
A

Short-circuit
releases
Ii
A

Protection of systems and cables


3-pole
Fixed overload releases
Terminals standard
terminal screw as accessories
15

15

350

20

20

350

25

25

350

30

30

350

35

35

320 400

40

40

320 400

45

45

300 500

50

50

300 500

60

60

380 630

70

70

480 800

80

80

480 800

90

90

600 1000

100

100

600 1000

110

110

750 1250

125

125

750 1250

15

15

350

20

20

350

25

25

350

30

30

350

35

35

320 400

40

40

320 400

45

45

300 500

50

50

300 500

60

60

380 630

70

70

480 800

80

80

480 800

90

90

600 1000

100

100

600 1000

Basic switching capacity


35 kA 240 V
25 kA 480 V1)
18 kA 600 V2)
Part no.
Article no.

Price
see price
list

Normal switching capacity


85 kA 240 V
35 kA 480 V1)
25 kA 600 V2)
Part no.
Price
Article no.
see price
list

NZMB1-AF15-NA
281553
NZMB1-AF20-NA
281554
NZMB1-AF25-NA
281555
NZMB1-AF30-NA
281556
NZMB1-AF35-NA
272204
NZMB1-AF40-NA
272205
NZMB1-AF45-NA
272206
NZMB1-AF50-NA
272207
NZMB1-AF60-NA
272208
NZMB1-AF70-NA
272209
NZMB1-AF80-NA
272250
NZMB1-AF90-NA
272251
NZMB1-AF100-NA
272252
NZMB1-AF110-NA
281557
NZMB1-AF125-NA
281558

NZMN1-AF15-NA
281564
NZMN1-AF20-NA
281565
NZMN1-AF25-NA
281566
NZMN1-AF30-NA
281567
NZMN1-AF35-NA
274220
NZMN1-AF40-NA
274223
NZMN1-AF45-NA
274230
NZMN1-AF50-NA
274231
NZMN1-AF60-NA
274232
NZMN1-AF70-NA
274233
NZMN1-AF80-NA
274234
NZMN1-AF90-NA
274235
NZMN1-AF100-NA
274236
NZMN1-AF110-NA
281568
NZMN1-AF125-NA
281569

NZMB2-AF15-BT-NA
107611
NZMB2-AF20-BT-NA
107612
NZMB2-AF25-BT-NA
107613
NZMB2-AF30-BT-NA
107614
NZMB2-AF35-BT-NA
107615
NZMB2-AF40-BT-NA
107616
NZMB2-AF45-BT-NA
107617
NZMB2-AF50-BT-NA
107618
NZMB2-AF60-BT-NA
107619
NZMB2-AF70-BT-NA
107620
NZMB2-AF80-BT-NA
107621
NZMB2-AF90-BT-NA
107622
NZMB2-AF100-BT-NA
107623

NZMN2-AF15-BT-NA
107631
NZMN2-AF20-BT-NA
107632
NZMN2-AF25-BT-NA
107633
NZMN2-AF30-BT-NA
107634
NZMN2-AF35-BT-NA
107635
NZMN2-AF40-BT-NA
107636
NZMN2-AF45-BT-NA
107637
NZMN2-AF50-BT-NA
107638
NZMN2-AF60-BT-NA
107639
NZMN2-AF70-BT-NA
107640
NZMN2-AF80-BT-NA
107641
NZMN2-AF90-BT-NA
107642
NZMN2-AF100-BT-NA
107643

Moeller SK1230-1157EN-NA
High switching capacity
100 kA 240 V
65 kA 480 V
35 kA 600 V
Part no.
Article no.

Price
see price
list

Std. pack

Notes

1 off

Switches conform to UL/CSA as well as the IEC regulations.


IEC switching performance values are contained on the rating plate.
UL 489, CSA-C22.2-5.1, IEC/EN 60947-2
Fixed overload releases Ir
Adjustable short-circuit release Ii
Approx. 6 10 x In (ex-factory 6 x In)
NZM...-AF35/40-NA: approx. 8 10 x In
Fixed short-circuit releases Ii
350 A at In = 15 30A
1) For

basic switching capacity 25 kA 480 V and


normal switching capacity 35 kA 480 V the following applies:
for NZM...-1-...-NA: 480Y/277 V AC from 60 A.

Line and load Box Lugs installed

Notes

NZMH2-AF15-BT-NA
107809
NZMH2-AF20-BT-NA
107810
NZMH2-AF25-BT-NA
107811
NZMH2-AF30-BT-NA
107812
NZMH2-AF35-BT-NA
107813
NZMH2-AF40-BT-NA
107814
NZMH2-AF45-BT-NA
107815
NZMH2-AF50-BT-NA
107816
NZMH2-AF60-BT-NA
107817
NZMH2-AF70-BT-NA
107818
NZMH2-AF80-BT-NA
107819
NZMH2-AF90-BT-NA
107820
NZMH2-AF100-BT-NA
107821

1 off

Switches conform to UL/CSA as well as the IEC regulations.


IEC switching performance values are contained on the rating plate.
UL 489, CSA-C22.2-5.1, IEC/EN 60947-2
Fixed overload releases Ir
Adjustable short-circuit release Ii
Approx. 6 10 x In (ex-factory 6 x In)
NZM...-AF35/40-NA: approx. 8 10 x In
Fixed short-circuit releases Ii
350 A at In = 15 30A
2) For basic switching capacity 18 kA 600 V and normal switching capacity 25 kA 600 V the following applies: for

NZM2.

Notes for terminals a 67

For Immediate Delivery call KMParts.com at (866) 595-9616

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

SK1157_006-009_b_G.fm Page 8 Friday, July 14, 2006 9:53 AM

Circuit-breakers for North America


Thermomagnetic releases, 3 pole

Circuit-breakers for North America


Thermomagnetic releases, 3 pole
Moeller SK1230-1157EN-NA

Rated current = rated


uninterrupted current

Setting range
Overload releases

In = Iu
A

Ir
A

Short-circuit
releases
Ii
A

110

110

750 1250

125

125

750 1250

150

150

960 1600

175

175

1200 2000

200

200

1200 2000

225

225

1500 2500

250

250

1500 2500

20

15 20

350

25

20 25

350

32

25 32

350

40

32 40

320 400

50

40 50

300 500

63

50 63

380 630

80

63 80

480 800

100

80 100

600 1000

125

100 125

750 1250

20

15 20

350

25

20 25

350

32

25 32

350

40

32 40

320 400

50

40 50

300 500

63

50 63

380 630

80

63 80

480 800

100

80 100

600 1000

125

100 125

750 1250

160

125 160

960 1600

200

160 200

1200 2000

250

200 250

1500 2500

Basic switching capacity


35 kA 240 V
25 kA 480 V1)
18 kA 600 V2)
Part no.
Article no.

Moeller SK1230-1157EN-NA

Normal switching capacity


85 kA 240 V
35 kA 480 V1)
25 kA 600 V2)
Part no.
Price
Article no.
see price
list

High switching capacity


100 kA 240 V
65 kA 480 V
35 kA 600 V
Part no.
Article no.

NZMB2-AF110-BT-NA
107624
NZMB2-AF125-BT-NA
107625
NZMB2-AF150-BT-NA
107626
NZMB2-AF175-BT-NA
107627
NZMB2-AF200-BT-NA
107628
NZMB2-AF225-BT-NA
107629
NZMB2-AF250-BT-NA
107630

NZMN2-AF110-BT-NA
107644
NZMN2-AF125-BT-NA
107645
NZMN2-AF150-BT-NA
107646
NZMN2-AF175-BT-NA
107647
NZMN2-AF200-BT-NA
107648
NZMN2-AF225-BT-NA
107649
NZMN2-AF250-BT-NA
107650

NZMH2-AF110-BT-NA
107822
NZMH2-AF125-BT-NA
107823
NZMH2-AF150-BT-NA
107824
NZMH2-AF175-BT-NA
107825
NZMH2-AF200-BT-NA
107826
NZMH2-AF225-BT-NA
107827
NZMH2-AF250-BT-NA
107828

NZMB1-A20-NA
281559
NZMB1-A25-NA
281560
NZMB1-A32-NA
281561
NZMB1-A40-NA
272253
NZMB1-A50-NA
272254
NZMB1-A63-NA
272255
NZMB1-A80-NA
272256
NZMB1-A100-NA
272258
NZMB1-A125-NA
281562

NZMN1-A20-NA
281570
NZMN1-A25-NA
281571
NZMN1-A32-NA
281572
NZMN1-A40-NA
274237
NZMN1-A50-NA
274239
NZMN1-A63-NA
274240
NZMN1-A80-NA
274241
NZMN1-A100-NA
274242
NZMN1-A125-NA
281573

NZMB2-A20-BT-NA
107773
NZMB2-A25-BT-NA
107774
NZMB2-A32-BT-NA
107775
NZMB2-A40-BT-NA
107776
NZMB2-A50-BT-NA
107777
NZMB2-A63-BT-NA
107778
NZMB2-A80-BT-NA
107779
NZMB2-A100-BT-NA
107780
NZMB2-A125-BT-NA
107781
NZMB2-A160-BT-NA
107782
NZMB2-A200-BT-NA
107783
NZMB2-A250-BT-NA
107784

NZMN2-A20-BT-NA
107785
NZMN2-A25-BT-NA
107786
NZMN2-A32-BT-NA
107787
NZMN2-A40-BT-NA
107788
NZMN2-A50-BT-NA
107789
NZMN2-A63-BT-NA
107790
NZMN2-A80-BT-NA
107791
NZMN2-A100-BT-NA
107792
NZMN2-A125-BT-NA
107793
NZMN2-A160-BT-NA
107794
NZMN2-A200-BT-NA
107795
NZMN2-A250-BT-NA
107796

Price
see price
list

Price
see price
list

Std. pack

Notes

1 off

Switches conform to UL/CSA as well as the IEC regulations.


IEC switching performance values are contained on the rating plate.
UL 489, CSA-C22.2-5.1, IEC/EN 60947-2

Protection of systems and cables


3-pole
Fixed overload release
Line and load Box Lugs installed

Fixed overload releases Ir


Adjustable short-circuit release Ii
Approx. 6 10 x In (ex-factory 6 x In)
NZM...-AF35/40-NA: approx. 8 10 x In
Fixed short-circuit releases Ii
350 A at In = 15 30A
2) For basic switching capacity 18 kA 600 V and normal switching capacity 25 kA 600 V the following applies:
for NZM2.

Adjustable overload release


Line and load Box Lugs installed
1 off

Switches conform to UL/CSA as well as the IEC regulations.


IEC switching performance values are contained on the rating plate.
UL 489, CSA-C22.2-5.1, IEC/EN 60947-2
Adjustable overload release Ir
0.8 1 x In (ex-factory 0.8 x In)
Adjustable short-circuit release Ii
6 10 x In (ex-factory 6 x In)
NZM...-A40-NA: 8 10 x In
Fixed short-circuit releases Ii
350 A with In = 20 32 A
1) For

basic switching capacity 25 kA 480 V


and normal switching capacity 35 kA 480 V the following applies:
for NZM...-1-...-NA: 480Y/277 V AC from 60 A.

Adjustable overload releases


Line and load Box Lugs installed

Notes

Notes for terminals a 71

For Immediate Delivery call KMParts.com at (866) 595-9616

NZMH2-A20-BT-NA
107797
NZMH2-A25-BT-NA
107798
NZMH2-A32-BT-NA
107799
NZMH2-A40-BT-NA
107800
NZMH2-A50-BT-NA
107801
NZMH2-A63-BT-NA
107802
NZMH2-A80-BT-NA
107803
NZMH2-A100-BT-NA
107804
NZMH2-A125-BT-NA
107805
NZMH2-A160-BT-NA
107806
NZMH2-A200-BT-NA
107807
NZMH2-A250-BT-NA
107808

1 off

Switches conform to UL/CSA as well as the IEC regulations.


IEC switching performance values are contained on the rating plate.
UL 489, CSA-C22.2-5.1, IEC/EN 60947-2
Adjustable overload release Ir
0.8 1 x In (ex-factory 0.8 x In)
Adjustable short-circuit release Ii
6 10 x In (ex-factory 6 x In)
NZM...-A40-NA: 8 10 x In
Fixed short-circuit releases Ii
350 A with In = 20 32 A
2) For

basic switching capacity 18 kA 600 V and normal switching capacity


25 kA 600 V the following applies: for NZM2.

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

SK1157_006-009_b_G.fm Page 8 Friday, July 14, 2006 9:53 AM

Circuit-breakers for North America


Thermomagnetic releases, 3 pole

Circuit-breakers for North America


Thermomagnetic releases, 3 pole
Moeller SK1230-1157EN-NA

Rated current = rated


uninterrupted current

Setting range
Overload releases

In = Iu
A

Ir
A

Short-circuit
releases
Ii
A

110

110

750 1250

125

125

750 1250

150

150

960 1600

175

175

1200 2000

200

200

1200 2000

225

225

1500 2500

250

250

1500 2500

20

15 20

350

25

20 25

350

32

25 32

350

40

32 40

320 400

50

40 50

300 500

63

50 63

380 630

80

63 80

480 800

100

80 100

600 1000

125

100 125

750 1250

20

15 20

350

25

20 25

350

32

25 32

350

40

32 40

320 400

50

40 50

300 500

63

50 63

380 630

80

63 80

480 800

100

80 100

600 1000

125

100 125

750 1250

160

125 160

960 1600

200

160 200

1200 2000

250

200 250

1500 2500

Basic switching capacity


35 kA 240 V
25 kA 480 V1)
18 kA 600 V2)
Part no.
Article no.

Moeller SK1230-1157EN-NA

Normal switching capacity


85 kA 240 V
35 kA 480 V1)
25 kA 600 V2)
Part no.
Price
Article no.
see price
list

High switching capacity


100 kA 240 V
65 kA 480 V
35 kA 600 V
Part no.
Article no.

NZMB2-AF110-BT-NA
107624
NZMB2-AF125-BT-NA
107625
NZMB2-AF150-BT-NA
107626
NZMB2-AF175-BT-NA
107627
NZMB2-AF200-BT-NA
107628
NZMB2-AF225-BT-NA
107629
NZMB2-AF250-BT-NA
107630

NZMN2-AF110-BT-NA
107644
NZMN2-AF125-BT-NA
107645
NZMN2-AF150-BT-NA
107646
NZMN2-AF175-BT-NA
107647
NZMN2-AF200-BT-NA
107648
NZMN2-AF225-BT-NA
107649
NZMN2-AF250-BT-NA
107650

NZMH2-AF110-BT-NA
107822
NZMH2-AF125-BT-NA
107823
NZMH2-AF150-BT-NA
107824
NZMH2-AF175-BT-NA
107825
NZMH2-AF200-BT-NA
107826
NZMH2-AF225-BT-NA
107827
NZMH2-AF250-BT-NA
107828

NZMB1-A20-NA
281559
NZMB1-A25-NA
281560
NZMB1-A32-NA
281561
NZMB1-A40-NA
272253
NZMB1-A50-NA
272254
NZMB1-A63-NA
272255
NZMB1-A80-NA
272256
NZMB1-A100-NA
272258
NZMB1-A125-NA
281562

NZMN1-A20-NA
281570
NZMN1-A25-NA
281571
NZMN1-A32-NA
281572
NZMN1-A40-NA
274237
NZMN1-A50-NA
274239
NZMN1-A63-NA
274240
NZMN1-A80-NA
274241
NZMN1-A100-NA
274242
NZMN1-A125-NA
281573

NZMB2-A20-BT-NA
107773
NZMB2-A25-BT-NA
107774
NZMB2-A32-BT-NA
107775
NZMB2-A40-BT-NA
107776
NZMB2-A50-BT-NA
107777
NZMB2-A63-BT-NA
107778
NZMB2-A80-BT-NA
107779
NZMB2-A100-BT-NA
107780
NZMB2-A125-BT-NA
107781
NZMB2-A160-BT-NA
107782
NZMB2-A200-BT-NA
107783
NZMB2-A250-BT-NA
107784

NZMN2-A20-BT-NA
107785
NZMN2-A25-BT-NA
107786
NZMN2-A32-BT-NA
107787
NZMN2-A40-BT-NA
107788
NZMN2-A50-BT-NA
107789
NZMN2-A63-BT-NA
107790
NZMN2-A80-BT-NA
107791
NZMN2-A100-BT-NA
107792
NZMN2-A125-BT-NA
107793
NZMN2-A160-BT-NA
107794
NZMN2-A200-BT-NA
107795
NZMN2-A250-BT-NA
107796

Price
see price
list

Price
see price
list

Std. pack

Notes

1 off

Switches conform to UL/CSA as well as the IEC regulations.


IEC switching performance values are contained on the rating plate.
UL 489, CSA-C22.2-5.1, IEC/EN 60947-2

Protection of systems and cables


3-pole
Fixed overload release
Line and load Box Lugs installed

Fixed overload releases Ir


Adjustable short-circuit release Ii
Approx. 6 10 x In (ex-factory 6 x In)
NZM...-AF35/40-NA: approx. 8 10 x In
Fixed short-circuit releases Ii
350 A at In = 15 30A
2) For basic switching capacity 18 kA 600 V and normal switching capacity 25 kA 600 V the following applies:
for NZM2.

Adjustable overload release


Line and load Box Lugs installed
1 off

Switches conform to UL/CSA as well as the IEC regulations.


IEC switching performance values are contained on the rating plate.
UL 489, CSA-C22.2-5.1, IEC/EN 60947-2
Adjustable overload release Ir
0.8 1 x In (ex-factory 0.8 x In)
Adjustable short-circuit release Ii
6 10 x In (ex-factory 6 x In)
NZM...-A40-NA: 8 10 x In
Fixed short-circuit releases Ii
350 A with In = 20 32 A
1) For

basic switching capacity 25 kA 480 V


and normal switching capacity 35 kA 480 V the following applies:
for NZM...-1-...-NA: 480Y/277 V AC from 60 A.

Adjustable overload releases


Line and load Box Lugs installed

Notes

NZMH2-A20-BT-NA
107797
NZMH2-A25-BT-NA
107798
NZMH2-A32-BT-NA
107799
NZMH2-A40-BT-NA
107800
NZMH2-A50-BT-NA
107801
NZMH2-A63-BT-NA
107802
NZMH2-A80-BT-NA
107803
NZMH2-A100-BT-NA
107804
NZMH2-A125-BT-NA
107805
NZMH2-A160-BT-NA
107806
NZMH2-A200-BT-NA
107807
NZMH2-A250-BT-NA
107808

1 off

Switches conform to UL/CSA as well as the IEC regulations.


IEC switching performance values are contained on the rating plate.
UL 489, CSA-C22.2-5.1, IEC/EN 60947-2
Adjustable overload release Ir
0.8 1 x In (ex-factory 0.8 x In)
Adjustable short-circuit release Ii
6 10 x In (ex-factory 6 x In)
NZM...-A40-NA: 8 10 x In
Fixed short-circuit releases Ii
350 A with In = 20 32 A
2) For

basic switching capacity 18 kA 600 V and normal switching capacity


25 kA 600 V the following applies: for NZM2.

Notes for terminals a 71

For Immediate Delivery call KMParts.com at (866) 595-9616

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

SK1157_010-013_b_G.fm Page 10 Friday, May 12, 2006 3:43 PM

Circuit-breakers for North America


Magnetic 3 pole short-circuit releases

Circuit-breakers for North America


Magnetic 3 pole short-circuit releases
Moeller SK1230-1157EN-NA

Moeller SK1230-1157EN-NA

Basic switching capacity


480 V1)
Rated current = rated
uninterrupted current

Setting range
Short-circuit releases

In = Iu
A

Ii
A

Part no.
Article no.

Price
see price
list

Std. pack

Notes

1 off

Switches conform to UL/CSA as well as the IEC regulations.


40 IEC switching performance values from 40 A are contained on the
rating plate.
UL 489, CSA-C22.2-5.1, IEC/EN 60947-4-1

I
Short-circuit protection
Motor protection in conjunction with contactor and overload relay
With short-circuit release
Without overload release
3 pole
Terminals standard
terminal screw as accessories
1.2
8 14

Notes

12.8 22.4

19.2 33.6

32 56

48 84

12

80 140

18

128 224

26

200 350

33

256 448

40

320 560

50

400 700

63

504 882

80

640 1120

100

800 1250

NZMB1-S1,2-CNA
102906
NZMB1-S2-CNA
102907
NZMB1-S3-CNA
102908
NZMB1-S5-CNA
102909
NZMB1-S8-CNA
103020
NZMB1-S12-CNA
103021
NZMB1-S18-CNA
103022
NZMB1-S26-CNA
103023
NZMB1-S33-CNA
103024
NZMB1-S40-CNA
281263
NZMB1-S50-CNA
281264
NZMB1-S63-CNA
281265
NZMB1-S80-CNA
281266
NZMB1-S100-CNA
281267

Notes for terminals a 67

For Immediate Delivery call KMParts.com at (866) 595-9616

Adjustable short-circuit release Ii


8 14 x In (ex-factory 12 x In)
NZM...1-S1,2 33-CNA: approx. 8 14 x In
NZM...1-S100-CNA: 8 12.5 x In (ex-factory 12 x In)
Without overload release Ir

CNA: The device has components approved to UL, the conditions of


approval must be observed during use.
i.e. the device must be combined with a suitable contactor and
overload relay.
A switching capacity is stated for the complete motor-starter
combination.
The device is approved as a CSA approved single device.
1) 480

Y/277 V AC from 60 A.

11

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

10

SK1157_010-013_b_G.fm Page 10 Friday, May 12, 2006 3:43 PM

Circuit-breakers for North America


Magnetic 3 pole short-circuit releases

Circuit-breakers for North America


Magnetic 3 pole short-circuit releases
Moeller SK1230-1157EN-NA

Moeller SK1230-1157EN-NA

Basic switching capacity


480 V1)
Rated current = rated
uninterrupted current

Setting range
Short-circuit releases

In = Iu
A

Ii
A

Part no.
Article no.

Price
see price
list

Std. pack

Notes

1 off

Switches conform to UL/CSA as well as the IEC regulations.


40 IEC switching performance values from 40 A are contained on the
rating plate.
UL 489, CSA-C22.2-5.1, IEC/EN 60947-4-1

I
Short-circuit protection
Motor protection in conjunction with contactor and overload relay
With short-circuit release
Without overload release
3 pole
Terminals standard
terminal screw as accessories
1.2
8 14

Notes

12.8 22.4

19.2 33.6

32 56

48 84

12

80 140

18

128 224

26

200 350

33

256 448

40

320 560

50

400 700

63

504 882

80

640 1120

100

800 1250

NZMB1-S1,2-CNA
102906
NZMB1-S2-CNA
102907
NZMB1-S3-CNA
102908
NZMB1-S5-CNA
102909
NZMB1-S8-CNA
103020
NZMB1-S12-CNA
103021
NZMB1-S18-CNA
103022
NZMB1-S26-CNA
103023
NZMB1-S33-CNA
103024
NZMB1-S40-CNA
281263
NZMB1-S50-CNA
281264
NZMB1-S63-CNA
281265
NZMB1-S80-CNA
281266
NZMB1-S100-CNA
281267

Adjustable short-circuit release Ii


8 14 x In (ex-factory 12 x In)
NZM...1-S1,2 33-CNA: approx. 8 14 x In
NZM...1-S100-CNA: 8 12.5 x In (ex-factory 12 x In)
Without overload release Ir

CNA: The device has components approved to UL, the conditions of


approval must be observed during use.
i.e. the device must be combined with a suitable contactor and
overload relay.
A switching capacity is stated for the complete motor-starter
combination.
The device is approved as a CSA approved single device.
1) 480

11

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

10

Y/277 V AC from 60 A.

Notes for terminals a 67

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_010-013_b_G.fm Page 12 Wednesday, June 21, 2006 5:24 PM

Circuit-breakers for North America


Magnetic 3 pole short-circuit releases

Circuit-breakers for North America


Magnetic 3 pole short-circuit releases
Moeller SK1230-1157EN-NA

Rated current = rated uninterrupted


current
In = Iu
A

Setting range

Basic switching capacity


480 V
600 V
Part no.
Article no.

Short-circuit releases
Ii
A

Price
see price
list

Moeller SK1230-1157EN-NA

Std. pack

Notes

1 off

Switches conform to UL/CSA as well as the IEC regulations.


40 IEC switching performance values from 40 A are contained on the
rating plate.
UL 489, CSA-C22.2-5.1, IEC/EN 60947-4-1
NZM...2-S250-CNA: IEC/EN 60947-2

I
Short-circuit protection
Motor protection in conjunction with contactor and overload relay
With short-circuit release
Without overload release
3 pole
Line and load Box Lugs installed

Notes

1.6

12.8 22.4

2.4

19.2 33.6

32 56

48 84

12

80 140

18

128 224

26

200 350

33

256 448

40

320 560

50

400 700

63

504 882

80

640 1120

100

800 1400

125

1000 1750

160

1280 2240

200

1600 2500

250

2000 2500

NZMB2-S1,6-BT-CNA
107651
NZMB2-S2,4-BT-CNA
107652
NZMB2-S5-BT-CNA
107653
NZMB2-S8-BT-CNA
107654
NZMB2-S12-BT-CNA
107655
NZMB2-S18-BT-CNA
107656
NZMB2-S26-BT-CNA
107657
NZMB2-S33-BT-CNA
107658
NZMB2-S40-BT-CNA
107659
NZMB2-S50-BT-CNA
107660
NZMB2-S63-BT-CNA
107661
NZMB2-S80-BT-CNA
107662
NZMB2-S100-BT-CNA
107663
NZMB2-S125-BT-CNA
107664
NZMB2-S160-BT-CNA
107665
NZMB2-S200-BT-CNA
107666
NZMB2-S250-BT-CNA
107667

Notes for terminals a 71

For Immediate Delivery call KMParts.com at (866) 595-9616

Adjustable short-circuit release Ii


8 14 x In (ex-factory 12 x In)
NZM...2-S5 33-CNA: approx. 6 10 x In (ex-factory 10 x In)
NZM...2-S250-CNA: 8 10 x In (ex-factory 10 x In)
Without overload release Ir

CNA: The device has components approved to UL, the conditions of


approval must be observed during use.
i.e. the device must be combined with a suitable contactor and overload
relay.
A switching capacity is stated for the complete motor-starter
combination.
The device is approved as a CSA approved single device.

13

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

12

SK1157_010-013_b_G.fm Page 12 Wednesday, June 21, 2006 5:24 PM

Circuit-breakers for North America


Magnetic 3 pole short-circuit releases

Circuit-breakers for North America


Magnetic 3 pole short-circuit releases
Moeller SK1230-1157EN-NA

Rated current = rated uninterrupted


current
In = Iu
A

Setting range

Basic switching capacity


480 V
600 V
Part no.
Article no.

Short-circuit releases
Ii
A

Price
see price
list

Moeller SK1230-1157EN-NA

Std. pack

Notes

1 off

Switches conform to UL/CSA as well as the IEC regulations.


40 IEC switching performance values from 40 A are contained on the
rating plate.
UL 489, CSA-C22.2-5.1, IEC/EN 60947-4-1
NZM...2-S250-CNA: IEC/EN 60947-2

I
Short-circuit protection
Motor protection in conjunction with contactor and overload relay
With short-circuit release
Without overload release
3 pole
Line and load Box Lugs installed

Notes

1.6

12.8 22.4

2.4

19.2 33.6

32 56

48 84

12

80 140

18

128 224

26

200 350

33

256 448

40

320 560

50

400 700

63

504 882

80

640 1120

100

800 1400

125

1000 1750

160

1280 2240

200

1600 2500

250

2000 2500

NZMB2-S1,6-BT-CNA
107651
NZMB2-S2,4-BT-CNA
107652
NZMB2-S5-BT-CNA
107653
NZMB2-S8-BT-CNA
107654
NZMB2-S12-BT-CNA
107655
NZMB2-S18-BT-CNA
107656
NZMB2-S26-BT-CNA
107657
NZMB2-S33-BT-CNA
107658
NZMB2-S40-BT-CNA
107659
NZMB2-S50-BT-CNA
107660
NZMB2-S63-BT-CNA
107661
NZMB2-S80-BT-CNA
107662
NZMB2-S100-BT-CNA
107663
NZMB2-S125-BT-CNA
107664
NZMB2-S160-BT-CNA
107665
NZMB2-S200-BT-CNA
107666
NZMB2-S250-BT-CNA
107667

13

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

12

Adjustable short-circuit release Ii


8 14 x In (ex-factory 12 x In)
NZM...2-S5 33-CNA: approx. 6 10 x In (ex-factory 10 x In)
NZM...2-S250-CNA: 8 10 x In (ex-factory 10 x In)
Without overload release Ir

CNA: The device has components approved to UL, the conditions of


approval must be observed during use.
i.e. the device must be combined with a suitable contactor and overload
relay.
A switching capacity is stated for the complete motor-starter
combination.
The device is approved as a CSA approved single device.

Notes for terminals a 71

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_014-017_b_G.fm Page 14 Friday, July 14, 2006 9:57 AM

Circuit-breakers for North America


Electronic releases, 3 pole

Circuit-breakers for North America


Electronic releases, 3 pole

Circuit-breakers, disconnect switches


up to 1200 A

Moeller SK1230-1157EN-NA

Rated current = rated


uninterrupted current

Setting range
Overload releases

Short-circuit releases

In = Iu
A

Ir
A

Non-delayed
Ii
A

Normal switching capacity


85 kA 240 V
42 kA 480 V
35 kA 600 V
Part no.
Article no.

Price
see price
list

Moeller SK1230-1157EN-NA
High switching capacity
100 kA 240 V
65 kA 480 V
35 kA 600 V
Part no.
Article no.

Price
see price
list

Std. pack

Notes

1 off

Switches conform to UL/CSA as well as the IEC regulations.


IEC switching performance values are contained on the rating plate.
UL 489, CSA-C22.2-5.1, IEC/EN 60947-2

I
Protection of systems and cables
3 pole
Fixed overload releases
Terminal screws standard
terminals as accessories
250

250

500 2750

300

300

600 3300

350

350

700 3850

400

400

800 4400

450

450

900 3600

500

500

1000 4000

550

550

1100 4400

600

600

1200 4800

600

600

1200 7200

700

700

1400 8400

800

800

1600 9600

900

900

1800 10800

1000

1000

2000 12000

1200

1200

2400 14400

3 pole
Adjustable overload releases
Terminal screws standard
terminals as accessories
250

125 250

500 2750

400

200 400

800 4400

600

300 600

1200 4800

800

400 800

1600 9600

1000

500 1000

2000 12000

1200

600 1200

2400 14400

Notes

NZMN3-AEF250-NA
269275
NZMN3-AEF300-NA
269276
NZMN3-AEF350-NA
269277
NZMN3-AEF400-NA
269278
NZMN3-AEF450-NA
269279
NZMN3-AEF500-NA
269280
NZMN3-AEF550-NA
269281
NZMN3-AEF600-NA
269282

NZMH3-AEF250-NA
269283
NZMH3-AEF300-NA
269284
NZMH3-AEF350-NA
269285
NZMH3-AEF400-NA
269286
NZMH3-AEF450-NA
269287
NZMH3-AEF500-NA
269288
NZMH3-AEF550-NA
269289
NZMH3-AEF600-NA
269290

NZMN4-AEF600-NA
271108
NZMN4-AEF700-NA
271109
NZMN4-AEF800-NA
271110
NZMN4-AEF900-NA
271111
NZMN4-AEF1000-NA
271112
NZMN4-AEF1200-NA
271113

NZMH4-AEF600-NA
271114
NZMH4-AEF700-NA
271115
NZMH4-AEF800-NA
271116
NZMH4-AEF900-NA
271117
NZMH4-AEF1000-NA
271118
NZMH4-AEF1200-NA
271119

NZMN3-AE250-NA
269299
NZMN3-AE400-NA
269300
NZMN3-AE600-NA
269301

NZMH3-AE250-NA
269302
NZMH3-AE400-NA
269303
NZMH3-AE600-NA
269304

NZMN4-AE800-NA
271120
NZMN4-AE1000-NA
271121
NZMN4-AE1200-NA
271122

NZMH4-AE800-NA
271123
NZMH4-AE1000-NA
271124
NZMH4-AE1200-NA
271125

Notes for terminals a 71

For Immediate Delivery call KMParts.com at (866) 595-9616

Fixed overload releases Ir


R.m.s. value measurement and thermal memory
Adjustable short-circuit release Ii
With NZM...3-AEF250...400-NA: 2 11 x In (ex-factory 6 x In)
With NZM...3-AEF450...600-NA: 2 8 x In (ex-factory 6 x In)
With NZM...4-AEF...-NA: 2 12x In (ex-factory 6 x In)
1)

1 off

For limiter high switching capacity with NZMH4,


the following applies: 85 kA/480 V

Switches conform to UL/CSA as well as the IEC regulations.


IEC switching performance values are contained on the rating plate.
UL 489, CSA-C22.2-5.1, IEC/EN 60947-2
Adjustable overload release Ir
0.5 1 x In (ex-factory 0.8 x In)
R.m.s. value measurement and thermal memory
Adjustable short-circuit release Ii
With NZM...3-AE250/400-NA: 2 11 x In (ex-factory 6 x In)
With NZM...3-AE600-NA: 2 8 x In (ex-factory 6 x In)
With NZM...4-AE...-NA: 2 12 x In (ex-factory 6 x In)
1)

For limiter high switching capacity with NZMH4,


the following applies: 85 kA/480 V

15

Circuit-breakers, disconnect switches


up to 1200 A

14

SK1157_014-017_b_G.fm Page 14 Friday, July 14, 2006 9:57 AM

Circuit-breakers for North America


Electronic releases, 3 pole

Circuit-breakers for North America


Electronic releases, 3 pole

Circuit-breakers, disconnect switches


up to 1200 A

Moeller SK1230-1157EN-NA

Rated current = rated


uninterrupted current

Setting range
Overload releases

Short-circuit releases

In = Iu
A

Ir
A

Non-delayed
Ii
A

Normal switching capacity


85 kA 240 V
42 kA 480 V
35 kA 600 V
Part no.
Article no.

Price
see price
list

Moeller SK1230-1157EN-NA
High switching capacity
100 kA 240 V
65 kA 480 V
35 kA 600 V
Part no.
Article no.

Price
see price
list

Std. pack

Notes

1 off

Switches conform to UL/CSA as well as the IEC regulations.


IEC switching performance values are contained on the rating plate.
UL 489, CSA-C22.2-5.1, IEC/EN 60947-2

I
Protection of systems and cables
3 pole
Fixed overload releases
Terminal screws standard
terminals as accessories
250

250

500 2750

300

300

600 3300

350

350

700 3850

400

400

800 4400

450

450

900 3600

500

500

1000 4000

550

550

1100 4400

600

600

1200 4800

600

600

1200 7200

700

700

1400 8400

800

800

1600 9600

900

900

1800 10800

1000

1000

2000 12000

1200

1200

2400 14400

3 pole
Adjustable overload releases
Terminal screws standard
terminals as accessories
250

125 250

500 2750

400

200 400

800 4400

600

300 600

1200 4800

800

400 800

1600 9600

1000

500 1000

2000 12000

1200

600 1200

2400 14400

Notes

NZMN3-AEF250-NA
269275
NZMN3-AEF300-NA
269276
NZMN3-AEF350-NA
269277
NZMN3-AEF400-NA
269278
NZMN3-AEF450-NA
269279
NZMN3-AEF500-NA
269280
NZMN3-AEF550-NA
269281
NZMN3-AEF600-NA
269282

NZMH3-AEF250-NA
269283
NZMH3-AEF300-NA
269284
NZMH3-AEF350-NA
269285
NZMH3-AEF400-NA
269286
NZMH3-AEF450-NA
269287
NZMH3-AEF500-NA
269288
NZMH3-AEF550-NA
269289
NZMH3-AEF600-NA
269290

NZMN4-AEF600-NA
271108
NZMN4-AEF700-NA
271109
NZMN4-AEF800-NA
271110
NZMN4-AEF900-NA
271111
NZMN4-AEF1000-NA
271112
NZMN4-AEF1200-NA
271113

NZMH4-AEF600-NA
271114
NZMH4-AEF700-NA
271115
NZMH4-AEF800-NA
271116
NZMH4-AEF900-NA
271117
NZMH4-AEF1000-NA
271118
NZMH4-AEF1200-NA
271119

NZMN3-AE250-NA
269299
NZMN3-AE400-NA
269300
NZMN3-AE600-NA
269301

NZMH3-AE250-NA
269302
NZMH3-AE400-NA
269303
NZMH3-AE600-NA
269304

NZMN4-AE800-NA
271120
NZMN4-AE1000-NA
271121
NZMN4-AE1200-NA
271122

NZMH4-AE800-NA
271123
NZMH4-AE1000-NA
271124
NZMH4-AE1200-NA
271125

Fixed overload releases Ir


R.m.s. value measurement and thermal memory
Adjustable short-circuit release Ii
With NZM...3-AEF250...400-NA: 2 11 x In (ex-factory 6 x In)
With NZM...3-AEF450...600-NA: 2 8 x In (ex-factory 6 x In)
With NZM...4-AEF...-NA: 2 12x In (ex-factory 6 x In)
1)

1 off

For limiter high switching capacity with NZMH4,


the following applies: 85 kA/480 V

Switches conform to UL/CSA as well as the IEC regulations.


IEC switching performance values are contained on the rating plate.
UL 489, CSA-C22.2-5.1, IEC/EN 60947-2
Adjustable overload release Ir
0.5 1 x In (ex-factory 0.8 x In)
R.m.s. value measurement and thermal memory
Adjustable short-circuit release Ii
With NZM...3-AE250/400-NA: 2 11 x In (ex-factory 6 x In)
With NZM...3-AE600-NA: 2 8 x In (ex-factory 6 x In)
With NZM...4-AE...-NA: 2 12 x In (ex-factory 6 x In)
1)

For limiter high switching capacity with NZMH4,


the following applies: 85 kA/480 V

Notes for terminals a 71

For Immediate Delivery call KMParts.com at (866) 595-9616

15

Circuit-breakers, disconnect switches


up to 1200 A

14

SK1157_014-017_b_G.fm Page 16 Friday, July 14, 2006 9:57 AM

Circuit-breakers for North America


Electronic releases, 3 pole

Circuit-breakers for North America


Electronic releases, 3 pole

Circuit-breakers, disconnect switches


up to 1200 A

Moeller SK1230-1157EN-NA

Rated current = rated


uninterrupted current

Setting range
Overload releases

In = Iu
A

Ir
A

Short-circuit releases
Non-delayed
Delayed
Ii
A

Price
see price
list

High switching capacity


65 kA 480 V
35 kA 600 V3)
Part no.
Article no.

150

1800

300 1500

175

175

2100

350 1750

200

200

2400

400 2000

225

225

2700

450 2250

250

250

3000

500 2500

250

250

500 2750

500 2500

300

300

600 3300

600 3000

350

350

700 3850

700 3500

400

400

800 4400

800 4000

450

450

900 3600

675 3150

500

500

1000 4000

750 3500

550

550

1100 4400

825 3850

600

600

1200 4800

900 4200

600

600

1200 7200

1200 6000

700

700

1400 8400

1400 7000

800

800

1600 9600

1600 8000

900

900

1800 10800

1800 9000

1000

1000

2000 12000

2000 10000

1200

1200

2400 14400

2400 12000

NZMN2-VEF150-BT-NA
107593
NZMN2-VEF175-BT-NA
107594
NZMN2-VEF200-BT-NA
107595
NZMN2-VEF225-BT-NA
107596
NZMN2-VEF250-BT-NA
107597

NZMH2-VEF150-BT-NA
107598
NZMH2-VEF175-BT-NA
107599
NZMH2-VEF200-BT-NA
107840
NZMH2-VEF225-BT-NA
107841
NZMH2-VEF250-BT-NA
107842

NZMN3-VEF250-NA
269308
NZMN3-VEF300-NA
269309
NZMN3-VEF350-NA
269310
NZMN3-VEF400-NA
269311
NZMN3-VEF450-NA
269312
NZMN3-VEF500-NA
269313
NZMN3-VEF550-NA
269314
NZMN3-VEF600-NA
269315

NZMH3-VEF250-NA
269316
NZMH3-VEF300-NA
269317
NZMH3-VEF350-NA
269318
NZMH3-VEF400-NA
269319
NZMH3-VEF450-NA
269320
NZMH3-VEF500-NA
269321
NZMH3-VEF550-NA
269322
NZMH3-VEF600-NA
269323

NZMN4-VEF600-NA
271136
NZMN4-VEF700-NA
271137
NZMN4-VEF800-NA
271138
NZMN4-VEF900-NA
271139
NZMN4-VEF1000-NA
271140
NZMN4-VEF1200-NA
271141

NZMH4-VEF600-NA
271142
NZMH4-VEF700-NA
271143
NZMH4-VEF800-NA
271144
NZMH4-VEF900-NA
271145
NZMH4-VEF1000-NA
271146
NZMH4-VEF1200-NA
271147

Terminal screws standard


terminals as accessories

Notes

Price
see price
list

Std. pack

Notes

1 off

Switches conform to UL/CSA as well as the IEC regulations.


IEC switching performance values are contained on the rating plate.
UL 489, CSA-C22.2-5.1, IEC/EN 60947-2

Isd
A

I
Systems, cable, transformer and generator protection
3 pole
Line and load terminals standard
Terminal screws standard
terminals as accessories
150

Normal switching capacity


42 kA 480 V1)
35 kA 600 V2)
Part no.
Article no.

Moeller SK1230-1157EN-NA

Notes for terminals a 71

For Immediate Delivery call KMParts.com at (866) 595-9616

Fixed overload releases Ir


R.m.s. value measurement and 'thermal memory'
Adjustable time delay setting to overcome current peaks tr
2 20 s with 6 x Ir (ex-factory 10 s)
Adjustable delayed short-circuit releases Isd
2 10 x Ir (ex-factory 6 x Ir)
NZM...3-VEF450...600-NA: 1.5 7 x Ir (ex-factory 6 x Ir)
Adjustable delay time tsd
Steps 0, 20, 60, 100, 200, 300, 500, 750, 1000 ms (ex-factory 0 ms)
Adjustable non-delayed short-circuit releases Ii
NZM2 fixed 12 x In
NZM...3-VEF250...400-NA: 2 11 x In (ex-factory 11 x In)
NZM...3-VEF450...600-NA: 2 8 x In (ex-factory 8 x In)
NZM...4-VEF...-NA: 2 12 x In (ex-factory 12 x In)
i2t constant function
NZM2 fixed OFF
NZM3, NZM4 switched (ex-factory OFF)
1)

For normal switching capacity with NZMN2-...-NA,


the following applies: 35 kA/480 V
2) For normal switching capacity with NZMN2-...-NA,
the following applies: 25 kA/600 V
3) For limiter high switching capacity with NZMH4-...-NA,
the following applies: 85 kA/480 V

17

Circuit-breakers, disconnect switches


up to 1200 A

16

SK1157_014-017_b_G.fm Page 16 Friday, July 14, 2006 9:57 AM

Circuit-breakers for North America


Electronic releases, 3 pole

Circuit-breakers for North America


Electronic releases, 3 pole

Circuit-breakers, disconnect switches


up to 1200 A

Moeller SK1230-1157EN-NA

Rated current = rated


uninterrupted current

Setting range
Overload releases

In = Iu
A

Ir
A

Short-circuit releases
Non-delayed
Delayed
Ii
A

Price
see price
list

High switching capacity


65 kA 480 V
35 kA 600 V3)
Part no.
Article no.

150

1800

300 1500

175

175

2100

350 1750

200

200

2400

400 2000

225

225

2700

450 2250

250

250

3000

500 2500

250

250

500 2750

500 2500

300

300

600 3300

600 3000

350

350

700 3850

700 3500

400

400

800 4400

800 4000

450

450

900 3600

675 3150

500

500

1000 4000

750 3500

550

550

1100 4400

825 3850

600

600

1200 4800

900 4200

600

600

1200 7200

1200 6000

700

700

1400 8400

1400 7000

800

800

1600 9600

1600 8000

900

900

1800 10800

1800 9000

1000

1000

2000 12000

2000 10000

1200

1200

2400 14400

2400 12000

NZMN2-VEF150-BT-NA
107593
NZMN2-VEF175-BT-NA
107594
NZMN2-VEF200-BT-NA
107595
NZMN2-VEF225-BT-NA
107596
NZMN2-VEF250-BT-NA
107597

NZMH2-VEF150-BT-NA
107598
NZMH2-VEF175-BT-NA
107599
NZMH2-VEF200-BT-NA
107840
NZMH2-VEF225-BT-NA
107841
NZMH2-VEF250-BT-NA
107842

NZMN3-VEF250-NA
269308
NZMN3-VEF300-NA
269309
NZMN3-VEF350-NA
269310
NZMN3-VEF400-NA
269311
NZMN3-VEF450-NA
269312
NZMN3-VEF500-NA
269313
NZMN3-VEF550-NA
269314
NZMN3-VEF600-NA
269315

NZMH3-VEF250-NA
269316
NZMH3-VEF300-NA
269317
NZMH3-VEF350-NA
269318
NZMH3-VEF400-NA
269319
NZMH3-VEF450-NA
269320
NZMH3-VEF500-NA
269321
NZMH3-VEF550-NA
269322
NZMH3-VEF600-NA
269323

NZMN4-VEF600-NA
271136
NZMN4-VEF700-NA
271137
NZMN4-VEF800-NA
271138
NZMN4-VEF900-NA
271139
NZMN4-VEF1000-NA
271140
NZMN4-VEF1200-NA
271141

NZMH4-VEF600-NA
271142
NZMH4-VEF700-NA
271143
NZMH4-VEF800-NA
271144
NZMH4-VEF900-NA
271145
NZMH4-VEF1000-NA
271146
NZMH4-VEF1200-NA
271147

Terminal screws standard


terminals as accessories

Notes

Price
see price
list

Std. pack

Notes

1 off

Switches conform to UL/CSA as well as the IEC regulations.


IEC switching performance values are contained on the rating plate.
UL 489, CSA-C22.2-5.1, IEC/EN 60947-2

Isd
A

I
Systems, cable, transformer and generator protection
3 pole
Line and load terminals standard
Terminal screws standard
terminals as accessories
150

Normal switching capacity


42 kA 480 V1)
35 kA 600 V2)
Part no.
Article no.

Moeller SK1230-1157EN-NA

Fixed overload releases Ir


R.m.s. value measurement and 'thermal memory'
Adjustable time delay setting to overcome current peaks tr
2 20 s with 6 x Ir (ex-factory 10 s)
Adjustable delayed short-circuit releases Isd
2 10 x Ir (ex-factory 6 x Ir)
NZM...3-VEF450...600-NA: 1.5 7 x Ir (ex-factory 6 x Ir)
Adjustable delay time tsd
Steps 0, 20, 60, 100, 200, 300, 500, 750, 1000 ms (ex-factory 0 ms)
Adjustable non-delayed short-circuit releases Ii
NZM2 fixed 12 x In
NZM...3-VEF250...400-NA: 2 11 x In (ex-factory 11 x In)
NZM...3-VEF450...600-NA: 2 8 x In (ex-factory 8 x In)
NZM...4-VEF...-NA: 2 12 x In (ex-factory 12 x In)
i2t constant function
NZM2 fixed OFF
NZM3, NZM4 switched (ex-factory OFF)
1)

For normal switching capacity with NZMN2-...-NA,


the following applies: 35 kA/480 V
2) For normal switching capacity with NZMN2-...-NA,
the following applies: 25 kA/600 V
3) For limiter high switching capacity with NZMH4-...-NA,
the following applies: 85 kA/480 V

Notes for terminals a 71

For Immediate Delivery call KMParts.com at (866) 595-9616

17

Circuit-breakers, disconnect switches


up to 1200 A

16

SK1157_018-019_b_G.fm Page 18 Friday, July 14, 2006 9:59 AM

Circuit-breakers for North America


Electronic releases, 3 pole

Circuit-breakers for North America


Electronic releases, 3 pole
Moeller SK1230-1157EN-NA

Rated current = rated


uninterrupted current

Setting range
Overload releases

In = Iu
A

Ir
A

Short-circuit releases
Non-delayed
Ii
A

Delayed
Isd
A

19

Moeller SK1230-1157EN-NA

Normal switching capacity


42 kA 480 V1)
35 kA 600 V2)
Part no.
Price
Article no.
see price
list

High switching capacity


65 kA 480 V
35 kA 600 V3)
Part no.
Article no.

NZMN2-VE100-BT-NA
107843
NZMN2-VE160-BT-NA
107844
NZMN2-VE250-BT-NA
107845

NZMH2-VE100-BT-NA
107846
NZMH2-VE160-BT-NA
107847
NZMH2-VE250-BT-NA
107848

NZMN3-VE250-NA
269332
NZMN3-VE400-NA
269333
NZMN3-VE600-NA
269334

NZMH3-VE250-NA
269335
NZMH3-VE400-NA
269336
NZMH3-VE600-NA
269337

NZMN4-VE800-NA
271154
NZMN4-VE1000-NA
271155
NZMN4-VE1200-NA
271156

NZMH4-VE800-NA
271157
NZMH4-VE1000-NA
271158
NZMH4-VE1200-NA
271159

Price
see price
list

Std. pack Notes

Systems, cable, transformer and generator protection


3 pole
Adjustable overload release
Line and load Box Lugs installed
100

50 100

1200

100 1000

160

80 160

1920

160 1600

250

125 250

3000

250 2500

250

125 250

500 2750

250 2500

400

200 400

800 4400

400 4000

600

300 600

1200 4800

450 4200

800

400 800

1600 9600

800 8000

1000

500 1000

2000 12000

1000 10000

1200

630 1200

2400 14400

1260 12000

1 off

Terminal screws standard


terminals as accessories

Switches conform to UL/CSA as well as the IEC regulations.


IEC switching performance values are contained on the rating plate.
UL 489, CSA-C22.2-5.1, IEC/EN 60947-2
Adjustable overload release Ir
0.5 1 x In
R.m.s. value measurement and thermal memory
Adjustable time delay setting to overcome current peaks tr
2 20 s with 6 x Ir (ex-factory 10 s)
Adjustable delayed short-circuit releases Isd
2 10 x Ir (ex-factory 6 x Ir)
NZM...3-VE600-NA: 1.5 7 x Ir (ex-factory 6 x Ir)
Adjustable delay time tsd
Steps: 0, 20, 60, 100, 200, 300, 500, 750, 1000 ms (ex-factory 0 ms)
Adjustable non-delayed short-circuit releases Ii
NZM2 fixed 12 x In
NZM...3-VE250/400-NA: 2 11 x In (ex-factory 11 x In)
NZM...3-VE600-NA: 2 8 x In (ex-factory 8 x In)
NZM...4-VE...-NA: 2 12 x In (ex-factory 12 x In)
i2t constant function
NZM2 fixed OFF
NZM3, NZM4 switched (ex-factory OFF)
1)
2)
3)

Notes

For normal switching capacity with NZMN2-...-NA: 35 kA/480 V


For normal switching capacity with NZMN2-...-NA: 25 kA/600 V
For limiter high switching capacity with NZMH4-...-NA: 85 kA/480 V

Notes for terminals a 71

Rated current = rated uninterrupted current


In = Iu
A

Setting range
Short-circuit releases
Ii
A

Normal switching capacity


480 V
600 V
Part no.
Price
Article no.
see price
list

Std. pack Notes

Short-circuit protection
Motor protection in conjunction with contactor and overload relay
With short-circuit release
Without overload release
3 pole
Line and load Box Lugs installed
90

180 1260

140

280 1960

220

440 3080

NZMN2-SE90-BT-CNA
107849
NZMN2-SE140-BT-CNA
107850
NZMN2-SE220-BT-CNA
107851

Terminal screws standard


terminals as accessories

Notes

220

440 3080

350

700 4900

450

900 6300

NZMN3-SE220-CNA
269341
NZMN3-SE350-CNA
269342
NZMN3-SE450-CNA
284465

Notes for terminals a 71

For Immediate Delivery call KMParts.com at (866) 595-9616

1 off

Switches conform to UL/CSA as well as the IEC regulations.


IEC switching performance values are contained on the rating plate.
UL 489, CSA-C22.2-5.1, IEC/EN 60947-2 and IEC/EN 60947-4
Adjustable short-circuit release Ii
2 14 x In (ex-factory 12 x In)
Without overload release Ir

CNA: The device has components approved to UL, the conditions of approval must be observed during use. i.e. the device must be combined with a suitable
contactor and overload relay. A switching capacity is stated for the complete motor-starter combination.
The device is approved as a CSA approved single device.

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

18

SK1157_018-019_b_G.fm Page 18 Friday, July 14, 2006 9:59 AM

Circuit-breakers for North America


Electronic releases, 3 pole

Circuit-breakers for North America


Electronic releases, 3 pole
Moeller SK1230-1157EN-NA

Rated current = rated


uninterrupted current

Setting range
Overload releases

In = Iu
A

Ir
A

Short-circuit releases
Non-delayed
Ii
A

Delayed
Isd
A

19

Moeller SK1230-1157EN-NA

Normal switching capacity


42 kA 480 V1)
35 kA 600 V2)
Part no.
Price
Article no.
see price
list

High switching capacity


65 kA 480 V
35 kA 600 V3)
Part no.
Article no.

NZMN2-VE100-BT-NA
107843
NZMN2-VE160-BT-NA
107844
NZMN2-VE250-BT-NA
107845

NZMH2-VE100-BT-NA
107846
NZMH2-VE160-BT-NA
107847
NZMH2-VE250-BT-NA
107848

NZMN3-VE250-NA
269332
NZMN3-VE400-NA
269333
NZMN3-VE600-NA
269334

NZMH3-VE250-NA
269335
NZMH3-VE400-NA
269336
NZMH3-VE600-NA
269337

NZMN4-VE800-NA
271154
NZMN4-VE1000-NA
271155
NZMN4-VE1200-NA
271156

NZMH4-VE800-NA
271157
NZMH4-VE1000-NA
271158
NZMH4-VE1200-NA
271159

Price
see price
list

Std. pack Notes

Systems, cable, transformer and generator protection


3 pole
Adjustable overload release
Line and load Box Lugs installed
100

50 100

1200

100 1000

160

80 160

1920

160 1600

250

125 250

3000

250 2500

250

125 250

500 2750

250 2500

400

200 400

800 4400

400 4000

600

300 600

1200 4800

450 4200

800

400 800

1600 9600

800 8000

1000

500 1000

2000 12000

1000 10000

1200

630 1200

2400 14400

1260 12000

1 off

Switches conform to UL/CSA as well as the IEC regulations.


IEC switching performance values are contained on the rating plate.
UL 489, CSA-C22.2-5.1, IEC/EN 60947-2
Adjustable overload release Ir
0.5 1 x In
R.m.s. value measurement and thermal memory
Adjustable time delay setting to overcome current peaks tr
2 20 s with 6 x Ir (ex-factory 10 s)
Adjustable delayed short-circuit releases Isd
2 10 x Ir (ex-factory 6 x Ir)
NZM...3-VE600-NA: 1.5 7 x Ir (ex-factory 6 x Ir)
Adjustable delay time tsd
Steps: 0, 20, 60, 100, 200, 300, 500, 750, 1000 ms (ex-factory 0 ms)
Adjustable non-delayed short-circuit releases Ii
NZM2 fixed 12 x In
NZM...3-VE250/400-NA: 2 11 x In (ex-factory 11 x In)
NZM...3-VE600-NA: 2 8 x In (ex-factory 8 x In)
NZM...4-VE...-NA: 2 12 x In (ex-factory 12 x In)
i2t constant function
NZM2 fixed OFF
NZM3, NZM4 switched (ex-factory OFF)

Terminal screws standard


terminals as accessories

1)
2)
3)

Notes

For normal switching capacity with NZMN2-...-NA: 35 kA/480 V


For normal switching capacity with NZMN2-...-NA: 25 kA/600 V
For limiter high switching capacity with NZMH4-...-NA: 85 kA/480 V

Notes for terminals a 71

Rated current = rated uninterrupted current


In = Iu
A

Setting range
Short-circuit releases
Ii
A

Normal switching capacity


480 V
600 V
Part no.
Price
Article no.
see price
list

Std. pack Notes

Short-circuit protection
Motor protection in conjunction with contactor and overload relay
With short-circuit release
Without overload release
3 pole
Line and load Box Lugs installed
90

180 1260

140

280 1960

220

440 3080

NZMN2-SE90-BT-CNA
107849
NZMN2-SE140-BT-CNA
107850
NZMN2-SE220-BT-CNA
107851

Terminal screws standard


terminals as accessories

Notes

220

440 3080

350

700 4900

450

900 6300

NZMN3-SE220-CNA
269341
NZMN3-SE350-CNA
269342
NZMN3-SE450-CNA
284465

1 off

Switches conform to UL/CSA as well as the IEC regulations.


IEC switching performance values are contained on the rating plate.
UL 489, CSA-C22.2-5.1, IEC/EN 60947-2 and IEC/EN 60947-4
Adjustable short-circuit release Ii
2 14 x In (ex-factory 12 x In)
Without overload release Ir

CNA: The device has components approved to UL, the conditions of approval must be observed during use. i.e. the device must be combined with a suitable
contactor and overload relay. A switching capacity is stated for the complete motor-starter combination.
The device is approved as a CSA approved single device.

Notes for terminals a 71

For Immediate Delivery call KMParts.com at (866) 595-9616

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

18

SK1157_020-021_b_G.fm Page 20 Thursday, June 22, 2006 10:25 AM

Circuit-breakers, disconnect switches


up to 1200 A

20

Molded case switches for North America


3 pole
Moeller SK1230-1157EN-NA

Rated current
= rated
uninterrupted
current

Switching capacity

Response
range of the
short-circuit
releases

In = Iu
A

At 480 V
kA

Ii
A

At 600 V
kA

3 switch positions I, + , 0 ;
can be tripped remotely with
shunt/under voltage release
Part no.
Price
Article no.
see price
list

Std. pack

Notes

NS1-63-NA
102681
NS1-100-NA
102682
NS1-125-NA
102683

1 off

Switches feature a fixed short-circuit


release (self-protection) and comply to
UL 489/CSA 22.2 No 5.1 regulations.
Furthermore the switches are tested to
IEC/EN 60947-2 as circuit-breakers
without overcurrent protection (CBI-X)
with main switch characteristics to
IEC/EN 60204 and isolating
characteristics to IEC 60947.

NS2-160-BT-NA
107578
NS2-200-BT-NA
107579
NS2-250-BT-NA
107610

1 off

Switches feature a fixed short-circuit


release (self-protection) and comply to
UL 489/CSA 22.2 No 5.1 regulations.
Furthermore the switches are tested to
IEC/EN 60947-2 as circuit-breakers
without overcurrent protection (CBI-X)
with main switch characteristics to
IEC/EN 60204 and isolating
characteristics to IEC 60947.

Molded case switches


These switches are recommended especially as incoming circuit-breakers for
the North American market.
3 pole
Terminals standard
terminal screw as accessories
63

35

1250

100

35

1250

125

35

1250

160

100

50

2500

200

100

50

2500

250

100

50

2500

400

100

50

4800

600

100

50

4800

800

100

50

14400

1000

100

50

14400

1200

100

50

14400

Line and load Box Lugs installed

Terminal screws standard


terminals as accessories
NS3-400-NA
102687
NS3-600-NA
102688

NS4-800-NA
102689
NS4-1000-NA
102690
NS4-1200-NA
102691

NS3 and NS4 currently under


development. Contact your Moeller
representative.

Notes
Notes for terminals a 67
NS2, NS3 and NS4 can be combined with remote operator NZM...-XR...
Voltage releases U/A and trip-indicating auxiliary contacts can be used.

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_020-021_b_G.fm Page 21 Thursday, June 22, 2006 10:28 AM

21

Moeller SK1230-1157EN-NA
3 switch positions I, + , 0 ;
can be tripped remotely with
shunt/under voltage release
Rated current = rated
uninterrupted current

In = Iu
A

Short-circuit
protection,
max. gG/gL fuse1)

Short-circuit
protection max. fuse
OTS characteristic

Short-circuit rating with


OTS fuse
At 480 V:

At 600 V:

kA

kA

63

125

150

10

100

125

150

10

125

125

150

10

250

225

10

10

400

630

2)

14

14

550

630

2)

14

14

600

1600

2)

25

25

800

1600

2)

25

25

1000

1600

2)

25

25

1200

1600

2)

25

25

Part no.
Article no.

Price
see price
list

Std.
pack

Switch-disconnector
3 pole
Terminals standard
terminal screws as accessories
1 off

Line and load Box Lugs installed


160

1 off

Terminal screws standard


terminals as accessories

Notes

N3-400-NA
271169
N3-550-NA
293635

N4-600-NA
292386
N4-800-NA
271171
N4-1000-NA
271172
N4-1200-NA
271173

Main switch characteristics including positive drive to IEC/EN 60204 and VDE 0113.
Isolating characteristics to IEC/EN 60947-3 and VDE 0660.
Protection against accidental contact according to IEC.
Undervoltage and shunt releases and HIA trip-indicating auxiliary contacts can be used in addition to N disconnect switches.
N3... and N4... can also be combined with the NZM...-XR... remote operator.
Switches conform to UL 489/CSA 22.2 No. 5.1 as well as to the IEC regulations.
Notes for terminals a 67
1) for
2) for

use when using a switch-disconnector to EN 60947-3.


use when using a switch-disconnector to N3...-NA and N4...-NA without protective device to UL 1087, CSA 22.2 No 5.2.

For Immediate Delivery call KMParts.com at (866) 595-9616

1 off

Circuit-breakers, disconnect switches


up to 1200 A

Disconnect switches for North America


3 pole

SK1157_022-023_g_G.fm Page 22 Thursday, May 4, 2006 10:15 AM

Circuit-breakers, disconnect switches


up to 1200 A

22

Engineering
Auxiliary contacts, trip indicating auxiliary contacts
Moeller SK1230-1157EN-NA
Contact sequence of the auxiliary contacts
Standard auxiliary contact (HIN)
I

+
L1L2L3

0lI

Switch-on

0mI

Switch-off

+mI

Trip

HIN

Q
q

Contact closed
Contact open

Q
q

Contact closed
Contact open

Q
q

Contact closed
Contact open

Q
q

Contact closed
Contact open

+
L1L2L3
HIN

L1L2L3
HIN

Early-make auxiliary contact (HIV)


NZM 1, 2, 3

+
L1L2L3
HIV

HIV

HIV

L1L2L3

+mI

Trip

0lI

Switch-on

0mI

Switch-off

+mI

Trip

HIV

L1L2L3

Switch-off

HIV

L1L2L3

0mI
I

L1L2L3

NZM 4

Switch-on

+
L1L2L3

0lI

HIV

Trip-indicating auxiliary contact (HIA)


+

L1L2L3

0lI

Switch-on

0mI

Switch-off

+mI

Trip

HIA

L1L2L3
HIA

+
L1L2L3
HIA

Maximum component fitting


HIN
HIA
HIV
Notes

1 N/O or 1 N/C
1 N/O or 1 N/C
2 N/O

NZM1

NZM2

NZM3

NZM4

1
1
1

2
1
1

3
1
1

3
2
1

If early-make contacts are required in combination with shunt or undervoltage releases,


please select the combination type in the Release section.

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_022-023_g_G.fm Page 23 Thursday, May 4, 2006 10:15 AM

Notes

Circuit-breakers, disconnect switches


up to 1200 A

Moeller SK1230-1157EN-NA

23

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_024-025_b_G.fm Page 24 Saturday, May 20, 2006 5:25 PM

Circuit-breakers, disconnect switches


Auxiliary contacts, with screw terminal

Circuit-breakers, disconnect switches


Auxiliary contacts, with screw terminal
Moeller SK1230-1157EN-NA

For use with

Auxiliary contacts: f = safety


Contact
function, by positive opening to
sequence
IEC/EN 60947-5-1
N/O = Normally N/C = Normally
open
closed

Part no.
Article no.
when ordered
separately

NZM1, 2, 3, 4
N1, 2, 3, 4

1 N/O

M22-K10
216376

Price
see price
list

Moeller SK1230-1157EN-NA
Notes

Auxiliary contacts
Standard auxiliary contact
Switching with the main contacts
Used for indicating and interlocking tasks

1.X3

1.X4

1 N/C f

1.X1

M22-K01
216378

The following can be clipped into the switches:


NZM1 a standard auxiliary contact
NZM2 up to two M22-K... standard auxiliary contacts
NZM3 as well as NZM4 - up to 3 standard auxiliary
contacts M22-(C)K...
Any combinations of the auxiliary contact types is possible.
Marking on switch: HIN

1.X2

Early-make auxiliary contact


For interlock and load-shedding circuits
With clamp terminal
on the left-hand
switch side.

NZM1
N1

2 N/O

3.13 3.23

NZM1-XHIV
259426

3.14 3.24

With clamp terminal


on the right-hand
switch side.

2 N/O

With 3 m connection
cable instead of
screw termination.

2 N/O

3.13 3.23

Not in conjunction with undervoltage release NZM...XU(C)... or shunt release NZM...-XA(C)...


Early-make with on and off switching (manual operation):
approx. 20 ms

NZM1-XHIVR
292195

3.14 3.24

3.13 3.23

NZM1-XHIVL
259432

3.14 3.24

NZM2, 3
N2, 3

2 N/O

3.13 3.23

NZM4
N4

2 N/O

3.13 3.23

NZM2/3-XHIV
259430

3.14 3.24

NZM4-XHIV
266172

Not in conjunction with undervoltage release NZM...XU(C)..., shunt release NZM...-XA(C)... or remote operator
NZM...-XR...
Early-make with switch on (manual operation): approx.
90 ms

M22-K10
216376

The following can be clipped into the switches:


NZM1 - one trip-indicating auxiliary switch
NZM2 - one M22-(C)K... trip-indicating auxiliary switch
NZM3 - one M22-(C)K... trip-indicating auxiliary switch
NZM4 - up to two M22-(C)K... trip-indicating auxiliary
switches
Any combinations of the auxiliary contact types ispossible.
Marking on switch: HIA

3.14 3.24

Trip-indicating auxiliary contact (HIA)


General trip indication '+', when tripped by voltage release, overload release or short-circuit release
NZM1, 2, 3, 4
1 N/O
N1, 2, 3, 4

4.X3

4.X4

1 N/C f

4.X1

M22-K01
216378

4.X2

For Immediate Delivery call KMParts.com at (866) 595-9616

25

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

24

SK1157_024-025_b_G.fm Page 24 Saturday, May 20, 2006 5:25 PM

Circuit-breakers, disconnect switches


Auxiliary contacts, with screw terminal

Circuit-breakers, disconnect switches


Auxiliary contacts, with screw terminal
Moeller SK1230-1157EN-NA

For use with

Auxiliary contacts: f = safety


Contact
function, by positive opening to
sequence
IEC/EN 60947-5-1
N/O = Normally N/C = Normally
open
closed

Part no.
Article no.
when ordered
separately

NZM1, 2, 3, 4
N1, 2, 3, 4

1 N/O

M22-K10
216376

Price
see price
list

Moeller SK1230-1157EN-NA
Notes

Auxiliary contacts
Standard auxiliary contact
Switching with the main contacts
Used for indicating and interlocking tasks

1.X3

1.X4

1 N/C f

1.X1

M22-K01
216378

The following can be clipped into the switches:


NZM1 a standard auxiliary contact
NZM2 up to two M22-K... standard auxiliary contacts
NZM3 as well as NZM4 - up to 3 standard auxiliary
contacts M22-(C)K...
Any combinations of the auxiliary contact types is possible.
Marking on switch: HIN

1.X2

Early-make auxiliary contact


For interlock and load-shedding circuits
With clamp terminal
on the left-hand
switch side.

NZM1
N1

2 N/O

3.13 3.23

NZM1-XHIV
259426

3.14 3.24

With clamp terminal


on the right-hand
switch side.

2 N/O

With 3 m connection
cable instead of
screw termination.

2 N/O

3.13 3.23

Not in conjunction with undervoltage release NZM...XU(C)... or shunt release NZM...-XA(C)...


Early-make with on and off switching (manual operation):
approx. 20 ms

NZM1-XHIVR
292195

3.14 3.24

3.13 3.23

NZM1-XHIVL
259432

3.14 3.24

NZM2, 3
N2, 3

2 N/O

3.13 3.23

NZM4
N4

2 N/O

3.13 3.23

NZM2/3-XHIV
259430

3.14 3.24

NZM4-XHIV
266172

Not in conjunction with undervoltage release NZM...XU(C)..., shunt release NZM...-XA(C)... or remote operator
NZM...-XR...
Early-make with switch on (manual operation): approx.
90 ms

M22-K10
216376

The following can be clipped into the switches:


NZM1 - one trip-indicating auxiliary switch
NZM2 - one M22-(C)K... trip-indicating auxiliary switch
NZM3 - one M22-(C)K... trip-indicating auxiliary switch
NZM4 - up to two M22-(C)K... trip-indicating auxiliary
switches
Any combinations of the auxiliary contact types ispossible.
Marking on switch: HIA

3.14 3.24

Trip-indicating auxiliary contact (HIA)


General trip indication '+', when tripped by voltage release, overload release or short-circuit release
NZM1, 2, 3, 4
1 N/O
N1, 2, 3, 4

4.X3

4.X4

1 N/C f

4.X1

M22-K01
216378

4.X2

For Immediate Delivery call KMParts.com at (866) 595-9616

25

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

24

SK1157_026-029_b_G.fm Page 26 Wednesday, July 26, 2006 3:19 PM

Circuit-breakers, disconnect switches


Undervoltage release

Circuit-breakers, disconnect switches


Undervoltage release
Moeller SK1230-1157EN-NA

For use with

Rated control voltage

Moeller SK1230-1157EN-NA

Part no.
Article no.
when ordered separately

Std. pack

Notes

NZM1-XU24AC
259434
NZM1-XU110-130AC
259440
NZM1-XU208-240AC
259442
NZM1-XU380-440AC
259444
NZM1-XU480-525AC
259446
NZM1-XU600AC
259448
NZM1-XU12DC
259450
NZM1-XU24DC
259452
NZM1-XU110-130DC
259458
NZM1-XU220-250DC
259460

1 off

When the undervoltage release is de-energized, accidental


contact with the main contacts of the switch during attempts to
switch on, is safely prevented .

Us
V
Undervoltage releases
Without auxiliary contact
Non-delayed disconnection of NZM circuit-breakers or N disconnect switches
when the control voltage sinks below 35 70% US.
For use with Emergency-Stop devices in conjunction with Emergency-Stop button.
With clamp terminal on the
NZM1, N1
D1
left-hand switch side.
U<
D2

24 V 50/60 Hz
110 V 130 V 50/60 Hz
208 V 240 V 50/60 Hz
380 V 440 V 50/60 Hz
480 V 525 V 50/60 Hz
600 V 50/60 Hz
12 V DC
24 V DC
110 V 130 V DC
220 V 250 V DC

For Immediate Delivery call KMParts.com at (866) 595-9616

Undervoltage release cannot be installed simultaneously with


NZM...-XHIV... early-make auxiliary contact or NZM...-XA...
shunt release.

27

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

26

SK1157_026-029_b_G.fm Page 26 Wednesday, July 26, 2006 3:19 PM

Circuit-breakers, disconnect switches


Undervoltage release

Circuit-breakers, disconnect switches


Undervoltage release
Moeller SK1230-1157EN-NA

For use with

Rated control voltage

Moeller SK1230-1157EN-NA

Part no.
Article no.
when ordered separately

Std. pack

Notes

NZM1-XU24AC
259434
NZM1-XU110-130AC
259440
NZM1-XU208-240AC
259442
NZM1-XU380-440AC
259444
NZM1-XU480-525AC
259446
NZM1-XU600AC
259448
NZM1-XU12DC
259450
NZM1-XU24DC
259452
NZM1-XU110-130DC
259458
NZM1-XU220-250DC
259460

1 off

When the undervoltage release is de-energized, accidental


contact with the main contacts of the switch during attempts to
switch on, is safely prevented .

Us
V
Undervoltage releases
Without auxiliary contact
Non-delayed disconnection of NZM circuit-breakers or N disconnect switches
when the control voltage sinks below 35 70% US.
For use with Emergency-Stop devices in conjunction with Emergency-Stop button.
With clamp terminal on the
NZM1, N1
D1
left-hand switch side.
U<
D2

24 V 50/60 Hz
110 V 130 V 50/60 Hz
208 V 240 V 50/60 Hz
380 V 440 V 50/60 Hz
480 V 525 V 50/60 Hz
600 V 50/60 Hz
12 V DC
24 V DC
110 V 130 V DC
220 V 250 V DC

Undervoltage release cannot be installed simultaneously with


NZM...-XHIV... early-make auxiliary contact or NZM...-XA...
shunt release.

For Immediate Delivery call KMParts.com at (866) 595-9616

27

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

26

SK1157_026-029_b_G.fm Page 28 Wednesday, July 26, 2006 3:27 PM

Circuit-breakers, disconnect switches


Undervoltage release

Circuit-breakers, disconnect switches


Undervoltage release
Moeller SK1230-1157EN-NA

For use with

Rated control voltage

Moeller SK1230-1157EN-NA

Part no.
Article no.
when ordered separately

Std. pack

Notes

NZM2/3-XU24AC
259491
NZM2/3-XU110-130AC
259497
NZM2/3-XU208-240AC
259499
NZM2/3-XU380-440AC
259501
NZM2/3-XU480-525AC
259503
NZM2/3-XU600AC
259505
NZM2/3-XU12DC
259507
NZM2/3-XU24DC
259509
NZM2/3-XU110-130DC
259515
NZM2/3-XU220-250DC
259517

1 off

When the undervoltage release is de-energized, accidental


contact with the main contacts of the switch during attempts to
switch on, is safely prevented .

NZM4-XU24AC
266189
NZM4-XU110-130AC
266192
NZM4-XU208-240AC
266193
NZM4-XU380-440AC
266194
NZM4-XU480-525AC
266195
NZM4-XU600AC
266196
NZM4-XU12DC
266203
NZM4-XU24DC
266204
NZM4-XU110-130DC
266207
NZM4-XU220-250DC
266208

1 off

Us
V
Undervoltage releases
Without auxiliary contact
Non-delayed disconnection of NZM circuit-breakers or N disconnect switches
when the control voltage sinks below 35 70% US.
For use with Emergency-Stop devices in conjunction with Emergency-Stop button.

NZM2, N2
D1
NZM3, N3
U<

24 V 50/60 Hz
110 V 130 V 50/60 Hz

D2

208 V 240 V 50/60 Hz


380 V 440 V 50/60 Hz
480 V 525 V 50/60 Hz
600 V 50/60 Hz
12 V DC
24 V DC
110 V 130 V DC
220 V 250 V DC
D1

NZM4, N4

24 V 50/60 Hz

U<
D2

110 V 130 V 50/60 Hz


208 V 240 V 50/60 Hz
380 V 440 V 50/60 Hz
480 V 525 V 50/60 Hz
600 V 50/60 Hz
12 V DC
24 V DC
110 V 130 V DC
220 V 250 V DC

For Immediate Delivery call KMParts.com at (866) 595-9616

Undervoltage release cannot be installed simultaneously with


NZM...-XHIV... early-make auxiliary contact or NZM...-XA...
shunt release.

29

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

28

SK1157_026-029_b_G.fm Page 28 Wednesday, July 26, 2006 3:27 PM

Circuit-breakers, disconnect switches


Undervoltage release

Circuit-breakers, disconnect switches


Undervoltage release
Moeller SK1230-1157EN-NA

For use with

Rated control voltage

Moeller SK1230-1157EN-NA

Part no.
Article no.
when ordered separately

Std. pack

Notes

NZM2/3-XU24AC
259491
NZM2/3-XU110-130AC
259497
NZM2/3-XU208-240AC
259499
NZM2/3-XU380-440AC
259501
NZM2/3-XU480-525AC
259503
NZM2/3-XU600AC
259505
NZM2/3-XU12DC
259507
NZM2/3-XU24DC
259509
NZM2/3-XU110-130DC
259515
NZM2/3-XU220-250DC
259517

1 off

When the undervoltage release is de-energized, accidental


contact with the main contacts of the switch during attempts to
switch on, is safely prevented .

NZM4-XU24AC
266189
NZM4-XU110-130AC
266192
NZM4-XU208-240AC
266193
NZM4-XU380-440AC
266194
NZM4-XU480-525AC
266195
NZM4-XU600AC
266196
NZM4-XU12DC
266203
NZM4-XU24DC
266204
NZM4-XU110-130DC
266207
NZM4-XU220-250DC
266208

1 off

Us
V
Undervoltage releases
Without auxiliary contact
Non-delayed disconnection of NZM circuit-breakers or N disconnect switches
when the control voltage sinks below 35 70% US.
For use with Emergency-Stop devices in conjunction with Emergency-Stop button.

NZM2, N2
D1
NZM3, N3
U<

24 V 50/60 Hz
110 V 130 V 50/60 Hz

D2

208 V 240 V 50/60 Hz


380 V 440 V 50/60 Hz
480 V 525 V 50/60 Hz
600 V 50/60 Hz
12 V DC
24 V DC
110 V 130 V DC
220 V 250 V DC
D1

NZM4, N4

24 V 50/60 Hz

U<
D2

110 V 130 V 50/60 Hz


208 V 240 V 50/60 Hz
380 V 440 V 50/60 Hz
480 V 525 V 50/60 Hz
600 V 50/60 Hz
12 V DC
24 V DC
110 V 130 V DC
220 V 250 V DC

Undervoltage release cannot be installed simultaneously with


NZM...-XHIV... early-make auxiliary contact or NZM...-XA...
shunt release.

For Immediate Delivery call KMParts.com at (866) 595-9616

29

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

28

SK1157_030-033_b_G.fm Page 30 Wednesday, July 26, 2006 3:32 PM

Circuit-breakers, disconnect switches


Undervoltage release

Circuit-breakers, disconnect switches


Undervoltage release
Moeller SK1230-1157EN-NA

For use with

Rated control voltage

Moeller SK1230-1157EN-NA

Part no.
Article no.
when ordered separately

Std. pack

Notes

NZM1-XUHIV24AC
259531
NZM1-XUHIV110-130AC
259537
NZM1-XUHIV208-240AC
259539
NZM1-XUHIV380-440AC
259541
NZM1-XUHIV480-525AC
259543
NZM1-XUHIV12DC
259545
NZM1-XUHIV24DC
259547
NZM1-XUHIV110-130DC
259553
NZM1-XUHIV220-250DC
259555

1 off

When the undervoltage release is de-energized, accidental


contact with the main contacts of the switch during attempts to
switch on is safely prevented.
Early-make of the auxiliary contacts with on and off switching
(manual operation): approx. 20 ms.
Undervoltage releases cannot be installed simultaneously with
NZM...-XHIV... early-make auxiliary contact or NZM...-XA...
shunt release.

NZM1-XUHIVL24AC
259557
NZM1-XUHIVL110-130AC
259563
NZM1-XUHIVL208-240AC
259565
NZM1-XUHIVL380-440AC
259567
NZM1-XUHIVL480-525AC
259569
NZM1-XUHIVL12DC
259571
NZM1-XUHIVL24DC
259573
NZM1-XUHIVL110-130DC
259579
NZM1-XUHIVL220-250DC
259581

1 off

When the undervoltage release is de-energized, accidental


contact with the main contacts of the switch during attempts to
switch on is safely prevented.
Early-make of the auxiliary contacts with on and off switching
(manual operation): approx. 20 ms.
Undervoltage releases cannot be installed simultaneously with
NZM...-XHIV... early-make auxiliary contact or NZM...-XA...
shunt release.

Us
V
Undervoltage releases
With two early-make auxiliary contacts
For interlocking and load-shedding circuits,
as well as for early-make of the undervoltage release in main-switch applications.
With clamp terminal on the
NZM1, N1
D1 3.13
left-hand switch side.

24 V 50/60 Hz
110 V 130 V 50/60 Hz

D2

208 V 240 V 50/60 Hz

3.14

380 V 440 V 50/60 Hz


480 V 525 V 50/60 Hz
12 V DC
24 V DC
110 V 130 V DC
220 V 250 V DC

D1

3.13

With 3 m connection cable


instead of screw termination.

NZM1, N1

24 V 50/60 Hz
110 V 130 V 50/60 Hz

D2

3.14

208 V 240 V 50/60 Hz


380 V 440 V 50/60 Hz
480 V 525 V 50/60 Hz
12 V DC
24 V DC
110 V 130 V DC
220 V 250 V DC

For Immediate Delivery call KMParts.com at (866) 595-9616

31

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

30

SK1157_030-033_b_G.fm Page 30 Wednesday, July 26, 2006 3:32 PM

Circuit-breakers, disconnect switches


Undervoltage release

Circuit-breakers, disconnect switches


Undervoltage release
Moeller SK1230-1157EN-NA

For use with

Rated control voltage

Moeller SK1230-1157EN-NA

Part no.
Article no.
when ordered separately

Std. pack

Notes

NZM1-XUHIV24AC
259531
NZM1-XUHIV110-130AC
259537
NZM1-XUHIV208-240AC
259539
NZM1-XUHIV380-440AC
259541
NZM1-XUHIV480-525AC
259543
NZM1-XUHIV12DC
259545
NZM1-XUHIV24DC
259547
NZM1-XUHIV110-130DC
259553
NZM1-XUHIV220-250DC
259555

1 off

When the undervoltage release is de-energized, accidental


contact with the main contacts of the switch during attempts to
switch on is safely prevented.
Early-make of the auxiliary contacts with on and off switching
(manual operation): approx. 20 ms.
Undervoltage releases cannot be installed simultaneously with
NZM...-XHIV... early-make auxiliary contact or NZM...-XA...
shunt release.

NZM1-XUHIVL24AC
259557
NZM1-XUHIVL110-130AC
259563
NZM1-XUHIVL208-240AC
259565
NZM1-XUHIVL380-440AC
259567
NZM1-XUHIVL480-525AC
259569
NZM1-XUHIVL12DC
259571
NZM1-XUHIVL24DC
259573
NZM1-XUHIVL110-130DC
259579
NZM1-XUHIVL220-250DC
259581

1 off

When the undervoltage release is de-energized, accidental


contact with the main contacts of the switch during attempts to
switch on is safely prevented.
Early-make of the auxiliary contacts with on and off switching
(manual operation): approx. 20 ms.
Undervoltage releases cannot be installed simultaneously with
NZM...-XHIV... early-make auxiliary contact or NZM...-XA...
shunt release.

Us
V
Undervoltage releases
With two early-make auxiliary contacts
For interlocking and load-shedding circuits,
as well as for early-make of the undervoltage release in main-switch applications.
With clamp terminal on the
NZM1, N1
D1 3.13
left-hand switch side.

24 V 50/60 Hz
110 V 130 V 50/60 Hz

D2

208 V 240 V 50/60 Hz

3.14

380 V 440 V 50/60 Hz


480 V 525 V 50/60 Hz
12 V DC
24 V DC
110 V 130 V DC
220 V 250 V DC

D1

3.13

With 3 m connection cable


instead of screw termination.

NZM1, N1

24 V 50/60 Hz
110 V 130 V 50/60 Hz

D2

3.14

208 V 240 V 50/60 Hz


380 V 440 V 50/60 Hz
480 V 525 V 50/60 Hz
12 V DC
24 V DC
110 V 130 V DC
220 V 250 V DC

For Immediate Delivery call KMParts.com at (866) 595-9616

31

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

30

SK1157_030-033_b_G.fm Page 32 Wednesday, July 26, 2006 3:35 PM

Circuit-breakers, disconnect switches


Undervoltage release

Circuit-breakers, disconnect switches


Undervoltage release
Moeller SK1230-1157EN-NA

For use with

Rated control voltage

Moeller SK1230-1157EN-NA

Part no.
Article no.
when ordered separately

Std. pack

Notes

NZM2/3-XUHIV24AC
259583
NZM2/3-XUHIV110-130AC
259589
NZM2/3-XUHIV208-240AC
259591
NZM2/3-XUHIV380-440AC
259594
NZM2/3-XUHIV480-525AC
259598
NZM2/3-XUHIV12DC
259600
NZM2/3-XUHIV24DC
259602
NZM2/3-XUHIV110-130DC
259608
NZM2/3-XUHIV220-250DC
259610

1 off

When the undervoltage release is de-energized, accidental


contact with the main contacts of the switch during attempts to
switch on is safely prevented.
Early-make of the auxiliary contacts with on and off switching
(manual operation): approx. 20 ms.
Cannot be used in conjunction with NZM...-XR... remote
operator.
Undervoltage releases cannot be installed simultaneously with
NZM...-XHIV... early-make auxiliary contact or NZM...-XA...
shunt release.

NZM4-XUHIV24AC
266217
NZM4-XUHIV110-130AC
266220
NZM4-XUHIV208-240AC
266221
NZM4-XUHIV380-440AC
266222
NZM4-XUHIV480-525AC
266223
NZM4-XUHIV12DC
266231
NZM4-XUHIV24DC
266232
NZM4-XUHIV110-130DC
266235
NZM4-XUHIV220-250DC
266236

1 off

When the undervoltage release is de-energized, accidental


contact with the main contacts of the switch during attempts to
switch on is safely prevented.
Early-make of the auxiliary contacts with switch on (manual
operation): approx. 90 ms.
Cannot be used in conjunction with NZM...-XR... remote
operator.
Undervoltage releases cannot be installed simultaneously with
NZM...-XHIV... early-make auxiliary contact or NZM...-XA...
shunt release.

Us
V
Undervoltage releases
With two early-make auxiliary contacts
For interlocking and load-shedding circuits,
as well as for early-make of the undervoltage release in main-switch applications.
NZM2, N2
D1 3.13
NZM3, N3

24 V 50/60 Hz
110 V 130 V 50/60 Hz

D2

208 V 240 V 50/60 Hz

3.14

380 V 440 V 50/60 Hz


480 V 525 V 50/60 Hz
12 V DC
24 V DC
110 V 130 V DC
220 V 250 V DC

D1

3.13

NZM4, N4

24 V 50/60 Hz
110 V 130 V 50/60 Hz

D2

3.14

208 V 240 V 50/60 Hz


380 V 440 V 50/60 Hz
480 V 525 V 50/60 Hz
12 V DC
24 V DC
110 V 130 V DC
220 V 250 V DC

For Immediate Delivery call KMParts.com at (866) 595-9616

33

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

32

SK1157_030-033_b_G.fm Page 32 Wednesday, July 26, 2006 3:35 PM

Circuit-breakers, disconnect switches


Undervoltage release

Circuit-breakers, disconnect switches


Undervoltage release
Moeller SK1230-1157EN-NA

For use with

Rated control voltage

Moeller SK1230-1157EN-NA

Part no.
Article no.
when ordered separately

Std. pack

Notes

NZM2/3-XUHIV24AC
259583
NZM2/3-XUHIV110-130AC
259589
NZM2/3-XUHIV208-240AC
259591
NZM2/3-XUHIV380-440AC
259594
NZM2/3-XUHIV480-525AC
259598
NZM2/3-XUHIV12DC
259600
NZM2/3-XUHIV24DC
259602
NZM2/3-XUHIV110-130DC
259608
NZM2/3-XUHIV220-250DC
259610

1 off

When the undervoltage release is de-energized, accidental


contact with the main contacts of the switch during attempts to
switch on is safely prevented.
Early-make of the auxiliary contacts with on and off switching
(manual operation): approx. 20 ms.
Cannot be used in conjunction with NZM...-XR... remote
operator.
Undervoltage releases cannot be installed simultaneously with
NZM...-XHIV... early-make auxiliary contact or NZM...-XA...
shunt release.

NZM4-XUHIV24AC
266217
NZM4-XUHIV110-130AC
266220
NZM4-XUHIV208-240AC
266221
NZM4-XUHIV380-440AC
266222
NZM4-XUHIV480-525AC
266223
NZM4-XUHIV12DC
266231
NZM4-XUHIV24DC
266232
NZM4-XUHIV110-130DC
266235
NZM4-XUHIV220-250DC
266236

1 off

When the undervoltage release is de-energized, accidental


contact with the main contacts of the switch during attempts to
switch on is safely prevented.
Early-make of the auxiliary contacts with switch on (manual
operation): approx. 90 ms.
Cannot be used in conjunction with NZM...-XR... remote
operator.
Undervoltage releases cannot be installed simultaneously with
NZM...-XHIV... early-make auxiliary contact or NZM...-XA...
shunt release.

Us
V
Undervoltage releases
With two early-make auxiliary contacts
For interlocking and load-shedding circuits,
as well as for early-make of the undervoltage release in main-switch applications.
NZM2, N2
D1 3.13
NZM3, N3

24 V 50/60 Hz
110 V 130 V 50/60 Hz

D2

208 V 240 V 50/60 Hz

3.14

380 V 440 V 50/60 Hz


480 V 525 V 50/60 Hz
12 V DC
24 V DC
110 V 130 V DC
220 V 250 V DC

D1

3.13

NZM4, N4

24 V 50/60 Hz
110 V 130 V 50/60 Hz

D2

3.14

208 V 240 V 50/60 Hz


380 V 440 V 50/60 Hz
480 V 525 V 50/60 Hz
12 V DC
24 V DC
110 V 130 V DC
220 V 250 V DC

For Immediate Delivery call KMParts.com at (866) 595-9616

33

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

32

SK1157_034-037_b_G.fm Page 34 Wednesday, July 26, 2006 4:45 PM

Circuit-breakers, disconnect switches


up to 1200 A

34

Circuit-breakers, disconnect switches


Undervoltage release
Moeller SK1230-1157EN-NA
For use with

Rated control voltage


Us
V

Undervoltage releases
With two separate early-make auxiliary contacts
With 3 m connection cable instead of screw termination.
NZM1, N1
D1

3.13 3.23

D2

3.14

24 V 50/60 Hz
110 V 130 V 50/60 Hz

3.24

208 V 240 V 50/60 Hz


380 V 440 V 50/60 Hz
480 V 525 V 50/60 Hz
12 V DC
24 V DC
Contacts 3.23 and 3.24 with separate 3 m connection cables.
NZM2, N2
D1
3.13 3.23
NZM3, N3

24 V 50/60 Hz
110 V 130 V 50/60 Hz

D2

3.14

3.24

208 V 240 V 50/60 Hz


380 V 440 V 50/60 Hz
480 V 525 V 50/60 Hz
12 V DC
24 V DC
Notes

Part no.
Article no.
when ordered separately

Price
see price
list

Std. pack

NZM1-XUHIV20L24AC
259612
NZM1-XUHIV20L110-130AC
259620
NZM1-XUHIV20L208-240AC
259622
NZM1-XUHIV20L380-440AC
259624
NZM1-XUHIV20L480-525AC
259626
NZM1-XUHIV20L12DC
259628
NZM1-XUHIV20L24DC
259630

1 off

NZM2/3-XUHIV2024AC
259640
NZM2/3-XUHIV20110-130AC
259648
NZM2/3-XUHIV20208-240AC
259651
NZM2/3-XUHIV20380-440AC
259653
NZM2/3-XUHIV20480-525AC
259655
NZM2/3-XUHIV2012DC
259657
NZM2/3-XUHIV2024DC
259659

1 off

When the undervoltage release is de-energized, accidental contact with the main contacts of the switch during attempts to switch on is safely
prevented.
Early-make of the auxiliary contacts with on and off switching (manual operation): approx. 20 ms.
Cannot be used in conjunction with NZM...-XR... remote operator.
Undervoltage releases cannot be installed simultaneously with NZM...-XHIV... early-make auxiliary contact or NZM...-XA... shunt release.

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_034-037_b_G.fm Page 35 Wednesday, July 26, 2006 4:47 PM

35

Moeller SK1230-1157EN-NA
For use with

Rated control voltage

Part no.
Article no.
when ordered separately

Price
see price
list

Std. pack

Us
V
Undervoltage releases
With two separate early-make auxiliary contacts
Coil connection wired to clamp terminal,
auxiliary switch connections wired with 3 m loose connection cables
NZM1, N1
24 V 50/60 Hz
D1

3.13 3.23

D2

3.14

110 V 130 V 50/60 Hz


3.24

208 V 240 V 50/60 Hz


24 V DC
Coil connection with 3 m loose connection cables,
auxiliary switch connections wired to clamp terminal
NZM1, N1
D1

3.13 3.23

D2

3.14

24 V 50/60 Hz
110 V 130 V 50/60 Hz

3.24

208 V 240 V 50/60 Hz


24 V DC
Coil connection with 3 m loose connection cables,
auxiliary switch connections wired to clamp terminal
NZM2, N2
D1
3.13 3.23
NZM3, N3

24 V 50/60 Hz
110 V 130 V 50/60 Hz

D2

3.14

3.24

208 V 240 V 50/60 Hz


24 V DC

Notes

NZM1-XUHIV20KL24AC
284388
NZM1-XUHIV20KL110-130AC
284389
NZM1-XUHIV20KL208-240AC
284400
NZM1-XUHIV20KL24DC
284387

1 off

NZM1-XUHIV20LK24AC
284402
NZM1-XUHIV20LK110-130AC
284403
NZM1-XUHIV20LK208-240AC
284404
NZM1-XUHIV20LK24DC
284401

1 off

NZM2/3-XUHIV20LK24AC
285291
NZM2/3-XUHIV20LK110-130AC
284407
NZM2/3-XUHIV20LK208-240AC
284408
NZM2/3-XUHIV20LK24DC
284405

1 off

When the undervoltage release is de-energized, accidental contact with the main contacts of the switch during attempts to turn on the switch
is safely prevented.
Early-make of the auxiliary contacts with on and off switching (manual operation): approx. 20 ms.
Cannot be used in conjunction with NZM...-XR... remote operator.
Undervoltage releases cannot be installed simultaneously with NZM...-XHIV... early-make auxiliary contact or NZM...-XA... shunt release.

For Immediate Delivery call KMParts.com at (866) 595-9616

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


Undervoltage release

SK1157_034-037_b_G.fm Page 36 Wednesday, July 26, 2006 4:47 PM

Circuit-breakers, disconnect switches


up to 1200 A

36

Circuit-breakers, disconnect switches


Undervoltage release
Moeller SK1230-1157EN-NA
For use with

Rated control voltage

Part no.
Article no.
when ordered separately

Price
see price
list

Std. pack

Us
V
Undervoltage releases
With two separate early-make auxiliary contacts
Contacts 3.23 and 3.24 with separate 3 m connection cables.
NZM4, N4
D1

3.13 3.23

D2

3.14

24 V 50/60 Hz
110 V 130 V 50/60 Hz

3.24

208 V 240 V 50/60 Hz


380 V 440 V 50/60 Hz
24 V DC

Notes

NZM4-XUHIV2024AC
266244
NZM4-XUHIV20110-130AC
266247
NZM4-XUHIV20208-240AC
266248
NZM4-XUHIV20380-440AC
266249
NZM4-XUHIV2024DC
266258

1 off

When the undervoltage release is de-energized, accidental contact with the main contacts of the switch during attempts to switch on is safely
prevented.
Early-make of the auxiliary contacts with switch on (manual operation): approx. 90 ms.
Cannot be used in conjunction with NZM...-XR... remote operator.
Undervoltage releases cannot be installed simultaneously with NZM...-XHIV... early-make auxiliary contact or NZM...-XA... shunt release.

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_034-037_b_G.fm Page 37 Thursday, May 4, 2006 6:06 PM

Moeller SK1230-1157EN-NA
For use with

Part no.
Article no.
when ordered
separately

Price
see price
list

Std. pack

Notes

UVU-NZM
260154

1 off

Adjustable delay time 70 ms 4 s.


With additional capacitor up to 16 s.
A special tripping device is required.
Cannot be installed simultaneously with
NZM...-XHIV... or NZM...-XA... shunt release.
Delay unit for separate installation
(Fixing: top-hat rail or screws).
For other operating voltages use control
transformer.

NZM1-XUVL
271607
NZM2/3-XUV
259527
NZM4-XUV
266588

1 off

UVU-NZM delay unit is additionally required.


Cannot be installed simultaneously with
separate NZM...-XHIV early-make auxiliary
contact or NZM...-XA... shunt release.

NZM1-XUVHIVL
271608
NZM2/3-XUVHIV
259684
NZM4-XUVHIV
266596

1 off

Cannot be used in conjunction with NZM...-XR...


remote operator.
UVU-NZM delay unit is additionally required.
Cannot be installed simultaneously with
separate NZM...-XHIV early-make auxiliary
contact or NZM...-XA... shunt release.
NZM1, 2, 3: Early-make of the auxiliary contacts
with on and off switching (manual operation):
approx. 20 ms.
NZM4: Early-make of the auxiliary contacts with
switch on (manual operation): approx. 90 ms.

NZM1-XUVHIV20L
271609
NZM2/3-XUVHIV20
259688
NZM4-XUVHIV20
266604

1 off

Cannot be used in conjunction with NZM...-XR...


remote operator.
UVU-NZM delay unit is additionally required.
Cannot be installed simultaneously with
separate NZM...-XHIV early-make auxiliary
contact or NZM...-XA... shunt release.
NZM1, 2, 3: Early-make of the auxiliary contacts
with on and off switching (manual operation):
approx. 20 ms.
NZM4: Early-make of the auxiliary contacts with
switch on (manual operation): approx. 90 ms.

Undervoltage releases, off-delayed


Combination of separate delay unit and special tripping device.
Not UL/CSA approved
Delay unit
Voltage dips of less than the setting between 0.06 16 s
do not cause disconnection of the NZM circuit-breaker or
N switch-disconnector.
NZM1, 2, 3, 4
N1, 2, 3, 4
50/60 Hz
220 V 240 V
380 V 440 V
480 V 550 V
DC/AC
24 V

Special tripping device


For combination with separate delay unit
Without auxiliary contacts
NZM1 with 3 m separate connection cables instead of
screw terminal, NZM2, 3 , 4 with screw terminal
NZM1
N1
NZM2, N2
NZM3, N3
NZM4
N4

D1

U
D2

With 2 early-make auxiliary contacts


NZM1 with 3 m separate connection cables instead of
screw terminal, NZM2, 3 , 4 with screw terminal
D1

3.13

D2

3.14

NZM1
N1
NZM2, N2
NZM3, N3
NZM4
N4

With 2 separately operating early-make auxiliary contacts


NZM1 with 3 m separate connection cables instead of screw
terminal, NZM2, 3, 4 with screw terminal, contact 3.23 and 3.24
with 3 m separate connection cables.
D1

3.13 3.23

D2

3.14

3.24

NZM1
N1
NZM2, N2
NZM3, N3
NZM4
N4

For Immediate Delivery call KMParts.com at (866) 595-9616

37

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


Undervoltage release, off-delayed

SK1157_038-041_b_G.fm Page 38 Thursday, June 8, 2006 9:32 AM

Circuit-breakers, disconnect switches


Shunt releases with screw terminal for NZM1

Circuit-breakers, disconnect switches


Shunt releases with screw terminal
Moeller SK1230-1157EN-NA

For use with

Rated control voltage

Moeller SK1230-1157EN-NA

Part no.
Article no.
when ordered separately

Std. pack

Notes

NZM1-XA12AC/DC
259706
NZM1-XA24AC/DC
259708
NZM1-XA110-130AC/DC
259724
NZM1-XA208-250AC/DC
259726
NZM1-XA380-440AC/DC
259728
NZM1-XA480-525AC/DC
259730

1 off

When the undervoltage release is de-energized, accidental contact


with the main contacts of the switch during attempts to switch on,
is safely prevented.

NZM1-XAL12AC/DC
259734
NZM1-XAL24AC/DC
259736
NZM1-XAL110-130AC/DC
259742
NZM1-XAL208-250AC/DC
259744
NZM1-XAL380-440AC/DC
259746
NZM1-XAL480-525AC/DC
259748

1 off

Us
V
Shunt releases
Without auxiliary contact
Switches are tripped by a voltage pulse or by the application of uninterrupted voltage.
With clamp terminal on the NZM1, N1
C1
left-hand switch side.

12 V AC/DC
24 V AC/DC

C2

110 V 130 V AC/DC


208 V 250 V AC/DC
380 V 440 V AC/DC
480 V 525 V AC/DC
C1

C2

With 3 m connection cable


instead of screw
termination.

NZM1, N1

12 V AC/DC
24 V AC/DC
110 V 130 V AC/DC
208 V 250 V AC/DC
380 V 440 V AC/DC
480 V 525 V AC/DC

For Immediate Delivery call KMParts.com at (866) 595-9616

Shunt release cannot be installed simultaneously with


NZM...-XHIV... early-make auxiliary contact or NZM...-XU...
undervoltage release.

When the undervoltage release is de-energized, accidental contact


with the main contacts of the switch during attempts to switch on,
is safely prevented.
Shunt release cannot be installed simultaneously with
NZM...-XHIV... early-make auxiliary contact or NZM...-XU...
undervoltage release.

39

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

38

SK1157_038-041_b_G.fm Page 38 Thursday, June 8, 2006 9:32 AM

Circuit-breakers, disconnect switches


Shunt releases with screw terminal for NZM1

Circuit-breakers, disconnect switches


Shunt releases with screw terminal
Moeller SK1230-1157EN-NA

For use with

Rated control voltage

Moeller SK1230-1157EN-NA

Part no.
Article no.
when ordered separately

Std. pack

Notes

NZM1-XA12AC/DC
259706
NZM1-XA24AC/DC
259708
NZM1-XA110-130AC/DC
259724
NZM1-XA208-250AC/DC
259726
NZM1-XA380-440AC/DC
259728
NZM1-XA480-525AC/DC
259730

1 off

When the undervoltage release is de-energized, accidental contact


with the main contacts of the switch during attempts to switch on,
is safely prevented.

NZM1-XAL12AC/DC
259734
NZM1-XAL24AC/DC
259736
NZM1-XAL110-130AC/DC
259742
NZM1-XAL208-250AC/DC
259744
NZM1-XAL380-440AC/DC
259746
NZM1-XAL480-525AC/DC
259748

1 off

Us
V
Shunt releases
Without auxiliary contact
Switches are tripped by a voltage pulse or by the application of uninterrupted voltage.
With clamp terminal on the NZM1, N1
C1
left-hand switch side.

12 V AC/DC
24 V AC/DC

C2

110 V 130 V AC/DC


208 V 250 V AC/DC
380 V 440 V AC/DC
480 V 525 V AC/DC
C1

C2

With 3 m connection cable


instead of screw
termination.

NZM1, N1

12 V AC/DC
24 V AC/DC
110 V 130 V AC/DC
208 V 250 V AC/DC
380 V 440 V AC/DC
480 V 525 V AC/DC

Shunt release cannot be installed simultaneously with


NZM...-XHIV... early-make auxiliary contact or NZM...-XU...
undervoltage release.

When the undervoltage release is de-energized, accidental contact


with the main contacts of the switch during attempts to switch on,
is safely prevented.
Shunt release cannot be installed simultaneously with
NZM...-XHIV... early-make auxiliary contact or NZM...-XU...
undervoltage release.

For Immediate Delivery call KMParts.com at (866) 595-9616

39

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

38

SK1157_038-041_b_G.fm Page 40 Wednesday, July 26, 2006 4:58 PM

Circuit-breakers, disconnect switches


Shunt releases with screw terminal for NZM2, 3 and 4

Circuit-breakers, disconnect switches


Shunt releases with screw terminal
Moeller SK1230-1157EN-NA

For use with

Rated control voltage

Moeller SK1230-1157EN-NA

Part no.
Article no.
when ordered separately

Std. pack

Notes

NZM2/3-XA12AC/DC
259752
NZM2/3-XA24AC/DC
259754
NZM2/3-XA110-130AC/DC
259760
NZM2/3-XA208-250AC/DC
259763
NZM2/3-XA380-440AC/DC
259766
NZM2/3-XA480-525AC/DC
259768

1 off

When the undervoltage release is de-energized, accidental contact


with the main contacts of the switch during attempts to switch on,
is safely prevented.

NZM4-XA12AC/DC
266446
NZM4-XA24AC/DC
266447
NZM4-XA110-130AC/DC
266450
NZM4-XA208-250AC/DC
266451
NZM4-XA380-440AC/DC
266452
NZM4-XA480-525AC/DC
266453

1 off

Us
V
Shunt releases
Without auxiliary contact
Switches are tripped by a voltage pulse or by the application of uninterrupted voltage.

NZM2, N2
C1
NZM3, N3

12 V AC/DC
24 V AC/DC

C2

110 V 130 V AC/DC


208 V 250 V AC/DC
380 V 440 V AC/DC
480 V 525 V AC/DC
C1

C2

NZM4, N4

12 V AC/DC
24 V AC/DC
110 V 130 V AC/DC
208 V 250 V AC/DC
380 V 440 V AC/DC
480 V 525 V AC/DC

For Immediate Delivery call KMParts.com at (866) 595-9616

Shunt release cannot be installed simultaneously with


NZM...-XHIV... early-make auxiliary contact or NZM...-XU...
undervoltage release.

When the undervoltage release is de-energized, accidental contact


with the main contacts of the switch during attempts to switch on,
is safely prevented.
Shunt release cannot be installed simultaneously with
NZM...-XHIV... early-make auxiliary contact or NZM...-XU...
undervoltage release.

41

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

40

SK1157_038-041_b_G.fm Page 40 Wednesday, July 26, 2006 4:58 PM

Circuit-breakers, disconnect switches


Shunt releases with screw terminal for NZM2, 3 and 4

Circuit-breakers, disconnect switches


Shunt releases with screw terminal
Moeller SK1230-1157EN-NA

For use with

Rated control voltage

Moeller SK1230-1157EN-NA

Part no.
Article no.
when ordered separately

Std. pack

Notes

NZM2/3-XA12AC/DC
259752
NZM2/3-XA24AC/DC
259754
NZM2/3-XA110-130AC/DC
259760
NZM2/3-XA208-250AC/DC
259763
NZM2/3-XA380-440AC/DC
259766
NZM2/3-XA480-525AC/DC
259768

1 off

When the undervoltage release is de-energized, accidental contact


with the main contacts of the switch during attempts to switch on,
is safely prevented.

NZM4-XA12AC/DC
266446
NZM4-XA24AC/DC
266447
NZM4-XA110-130AC/DC
266450
NZM4-XA208-250AC/DC
266451
NZM4-XA380-440AC/DC
266452
NZM4-XA480-525AC/DC
266453

1 off

Us
V
Shunt releases
Without auxiliary contact
Switches are tripped by a voltage pulse or by the application of uninterrupted voltage.

NZM2, N2
C1
NZM3, N3

12 V AC/DC
24 V AC/DC

C2

110 V 130 V AC/DC


208 V 250 V AC/DC
380 V 440 V AC/DC
480 V 525 V AC/DC
C1

C2

NZM4, N4

12 V AC/DC
24 V AC/DC
110 V 130 V AC/DC
208 V 250 V AC/DC
380 V 440 V AC/DC
480 V 525 V AC/DC

Shunt release cannot be installed simultaneously with


NZM...-XHIV... early-make auxiliary contact or NZM...-XU...
undervoltage release.

When the undervoltage release is de-energized, accidental contact


with the main contacts of the switch during attempts to switch on,
is safely prevented.
Shunt release cannot be installed simultaneously with
NZM...-XHIV... early-make auxiliary contact or NZM...-XU...
undervoltage release.

For Immediate Delivery call KMParts.com at (866) 595-9616

41

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

40

SK1157_042-043_b_G.fm Page 42 Friday, May 12, 2006 3:58 PM

Circuit-breakers, disconnect switches


Shunt releases with screw terminal

Circuit-breakers, disconnect switches


Shunt releases with screw terminal
Moeller SK1230-1157EN-NA

For use with

Rated control voltage

Part no.
Article no.
when ordered separately

Price
see price list

Moeller SK1230-1157EN-NA

Std. pack

Std. pack

Notes

1 off

1 off

Cannot be installed simultaneously with NZM...-XHIV... earlymake auxiliary contact or NZM...-XU... undervoltage release.

Us
V
Shunt releases
Without auxiliary contacts
For mesh-network circuit-breakers
For intermittent operation
Maximum on time = 1 s
Operating range 10 110 % Us
not UL/CSA approved
C1

NZM3, N3

230 V AC

NZM3-XA-230AC-MNS
274097

C2

Intermittent operation guaranteed by series connection of an


M22-(C)K10 make contact.
The maximum operating time of the shunt release for mesh
network circuit-breaker is 1 s.

L1 (L+)
C1

NZM4, N4

230 V AC

NZM4-XA-230AC-MNS
274138

1 off

1 off

C2

Q
HIN
-Q1

-S11
0

1.13

M22-...K10

1.14
C1
C2

NZM...-XA...-MNS

N (L-, L2)
a
-S11
Q
-Q1

For Immediate Delivery call KMParts.com at (866) 595-9616

43

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

42

Reverse-power relay contact


Remote off
Standard auxiliary contact
Shunt release

SK1157_042-043_b_G.fm Page 42 Friday, May 12, 2006 3:58 PM

Circuit-breakers, disconnect switches


Shunt releases with screw terminal

Circuit-breakers, disconnect switches


Shunt releases with screw terminal
Moeller SK1230-1157EN-NA

For use with

Rated control voltage

Part no.
Article no.
when ordered separately

Price
see price list

Moeller SK1230-1157EN-NA

Std. pack

Std. pack

Notes

1 off

1 off

Cannot be installed simultaneously with NZM...-XHIV... earlymake auxiliary contact or NZM...-XU... undervoltage release.

Us
V
Shunt releases
Without auxiliary contacts
For mesh-network circuit-breakers
For intermittent operation
Maximum on time = 1 s
Operating range 10 110 % Us
not UL/CSA approved
C1

NZM3, N3

230 V AC

NZM3-XA-230AC-MNS
274097

C2

Intermittent operation guaranteed by series connection of an


M22-(C)K10 make contact.
The maximum operating time of the shunt release for mesh
network circuit-breaker is 1 s.

L1 (L+)
C1

NZM4, N4

230 V AC

NZM4-XA-230AC-MNS
274138

1 off

1 off

C2

Q
HIN
-Q1

-S11
0

1.13

M22-...K10

1.14
C1
C2

NZM...-XA...-MNS

N (L-, L2)
a
-S11
Q
-Q1

43

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

42

Reverse-power relay contact


Remote off
Standard auxiliary contact
Shunt release

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_044-049_b_G.fm Page 44 Thursday, June 8, 2006 9:34 AM

Circuit-breakers, disconnect switches


Shunt releases with screw terminal

Circuit-breakers, disconnect switches


Shunt releases with screw terminal
Moeller SK1230-1157EN-NA

For use with

Rated control voltage

Moeller SK1230-1157EN-NA

Part no.
Article no.
when ordered separately

Std. pack

Notes

NZM1-XAHIV12AC/DC
259772
NZM1-XAHIV24AC/DC
259774
NZM1-XAHIV110-130AC/DC
259780
NZM1-XAHIV208-250AC/DC
259782
NZM1-XAHIV380-440AC/DC
259784
NZM1-XAHIV480-525AC/DC
259786

1 off

When the shunt release is energized, accidental contact with


the main contacts of the switch during attempts to switch on
is safely prevented.
Early-make of the auxiliary contact with on and off switching
(manual operation): approx. 20 ms.
Shunt release cannot be installed simultaneously with
NZM...-XHIV.. early-make auxiliary contact or NZM...-XU...
undervoltage release.

NZM1-XAHIVL12AC/DC
259790
NZM1-XAHIVL24AC/DC
259792
NZM1-XAHIVL110-130AC/DC
259798
NZM1-XAHIVL208-250AC/DC
259800
NZM1-XAHIVL380-440AC/DC
259802
NZM1-XAHIVL480-525AC/DC
259804

1 off

Us
V
Shunt releases
With early-make auxiliary contact
C1

3.13

C2

3.14

With clamp terminal on the


left-hand switch side.

NZM1, N1

12 V AC/DC
24 V AC/DC
110 V 130 V AC/DC
208 V 250 V AC/DC
380 V 440 V AC/DC
480 V 525 V AC/DC

C1

3.13

C2

3.14

With 3 m connection cable


instead of screw termination.

NZM1, N1

12 V AC/DC
24 V AC/DC
110 V 130 V AC/DC
208 V 250 V AC/DC
380 V 440 V AC/DC
480 V 525 V AC/DC

For Immediate Delivery call KMParts.com at (866) 595-9616

45

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

44

SK1157_044-049_b_G.fm Page 44 Thursday, June 8, 2006 9:34 AM

Circuit-breakers, disconnect switches


Shunt releases with screw terminal

Circuit-breakers, disconnect switches


Shunt releases with screw terminal
Moeller SK1230-1157EN-NA

For use with

Rated control voltage

Moeller SK1230-1157EN-NA

Part no.
Article no.
when ordered separately

Std. pack

Notes

NZM1-XAHIV12AC/DC
259772
NZM1-XAHIV24AC/DC
259774
NZM1-XAHIV110-130AC/DC
259780
NZM1-XAHIV208-250AC/DC
259782
NZM1-XAHIV380-440AC/DC
259784
NZM1-XAHIV480-525AC/DC
259786

1 off

When the shunt release is energized, accidental contact with


the main contacts of the switch during attempts to switch on
is safely prevented.
Early-make of the auxiliary contact with on and off switching
(manual operation): approx. 20 ms.
Shunt release cannot be installed simultaneously with
NZM...-XHIV.. early-make auxiliary contact or NZM...-XU...
undervoltage release.

NZM1-XAHIVL12AC/DC
259790
NZM1-XAHIVL24AC/DC
259792
NZM1-XAHIVL110-130AC/DC
259798
NZM1-XAHIVL208-250AC/DC
259800
NZM1-XAHIVL380-440AC/DC
259802
NZM1-XAHIVL480-525AC/DC
259804

1 off

Us
V
Shunt releases
With early-make auxiliary contact
C1

3.13

C2

3.14

With clamp terminal on the


left-hand switch side.

NZM1, N1

12 V AC/DC
24 V AC/DC
110 V 130 V AC/DC
208 V 250 V AC/DC
380 V 440 V AC/DC
480 V 525 V AC/DC

C1

3.13

C2

3.14

With 3 m connection cable


instead of screw termination.

NZM1, N1

12 V AC/DC
24 V AC/DC
110 V 130 V AC/DC
208 V 250 V AC/DC
380 V 440 V AC/DC
480 V 525 V AC/DC

For Immediate Delivery call KMParts.com at (866) 595-9616

45

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

44

SK1157_044-049_b_G.fm Page 46 Thursday, June 8, 2006 9:35 AM

Circuit-breakers, disconnect switches


Shunt releases with screw terminal

Circuit-breakers, disconnect switches


Shunt releases with screw terminal
Moeller SK1230-1157EN-NA

For use with

Rated control voltage

Moeller SK1230-1157EN-NA

Part no.
Article no.
when ordered separately

Std. pack

Notes

NZM2/3-XAHIV12AC/DC
259808
NZM2/3-XAHIV24AC/DC
259810
NZM2/3-XAHIV110-130AC/DC
259816
NZM2/3-XAHIV208-250AC/DC
259818
NZM2/3-XAHIV380-440AC/DC
259820
NZM2/3-XAHIV480-525AC/DC
259822

1 off

When the shunt release is energized, accidental contact with


the main contacts of the switch during attempts to switch on
is safely prevented.
Early-make of the auxiliary contact with on and off switching
(manual operation): approx. 20 ms.
Cannot be used in conjunction with NZM...-XR... remote
operator.
Shunt release cannot be installed simultaneously with
NZM...-XHIV.. early-make auxiliary contact or NZM...-XU...
undervoltage release.

NZM4-XAHIV12AC/DC
266470
NZM4-XAHIV24AC/DC
266471
NZM4-XAHIV110-130AC/DC
266474
NZM4-XAHIV208-250AC/DC
266475
NZM4-XAHIV380-440AC/DC
266476
NZM4-XAHIV480-525AC/DC
266477

1 off

When the shunt release is energized, accidental contact with


the main contacts of the switch during attempts to switch on
is safely prevented.
Early-make of the auxiliary contact with switch on (manual
operation): approx. 90 ms.
Cannot be used in conjunction with NZM...-XR... remote
operator.
Shunt release cannot be installed simultaneously with
NZM...-XHIV.. early-make auxiliary contact or NZM...-XU...
undervoltage release.

Us
V
Shunt releases
With early-make auxiliary contact
C1

3.13

C2

3.14

NZM2, N2
NZM3, N3

12 V AC/DC
24 V AC/DC
110 V 130 V AC/DC
208 V 250 V AC/DC
380 V 440 V AC/DC
480 V 525 V AC/DC

C1

3.13

C2

3.14

NZM4, N4

12 V AC/DC
24 V AC/DC
110 V 130 V AC/DC
208 V 250 V AC/DC
380 V 440 V AC/DC
480 V 525 V AC/DC

For Immediate Delivery call KMParts.com at (866) 595-9616

47

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

46

SK1157_044-049_b_G.fm Page 46 Thursday, June 8, 2006 9:35 AM

Circuit-breakers, disconnect switches


Shunt releases with screw terminal

Circuit-breakers, disconnect switches


Shunt releases with screw terminal
Moeller SK1230-1157EN-NA

For use with

Rated control voltage

Moeller SK1230-1157EN-NA

Part no.
Article no.
when ordered separately

Std. pack

Notes

NZM2/3-XAHIV12AC/DC
259808
NZM2/3-XAHIV24AC/DC
259810
NZM2/3-XAHIV110-130AC/DC
259816
NZM2/3-XAHIV208-250AC/DC
259818
NZM2/3-XAHIV380-440AC/DC
259820
NZM2/3-XAHIV480-525AC/DC
259822

1 off

When the shunt release is energized, accidental contact with


the main contacts of the switch during attempts to switch on
is safely prevented.
Early-make of the auxiliary contact with on and off switching
(manual operation): approx. 20 ms.
Cannot be used in conjunction with NZM...-XR... remote
operator.
Shunt release cannot be installed simultaneously with
NZM...-XHIV.. early-make auxiliary contact or NZM...-XU...
undervoltage release.

NZM4-XAHIV12AC/DC
266470
NZM4-XAHIV24AC/DC
266471
NZM4-XAHIV110-130AC/DC
266474
NZM4-XAHIV208-250AC/DC
266475
NZM4-XAHIV380-440AC/DC
266476
NZM4-XAHIV480-525AC/DC
266477

1 off

When the shunt release is energized, accidental contact with


the main contacts of the switch during attempts to switch on
is safely prevented.
Early-make of the auxiliary contact with switch on (manual
operation): approx. 90 ms.
Cannot be used in conjunction with NZM...-XR... remote
operator.
Shunt release cannot be installed simultaneously with
NZM...-XHIV.. early-make auxiliary contact or NZM...-XU...
undervoltage release.

Us
V
Shunt releases
With early-make auxiliary contact
C1

3.13

C2

3.14

NZM2, N2
NZM3, N3

12 V AC/DC
24 V AC/DC
110 V 130 V AC/DC
208 V 250 V AC/DC
380 V 440 V AC/DC
480 V 525 V AC/DC

C1

3.13

C2

3.14

NZM4, N4

12 V AC/DC
24 V AC/DC
110 V 130 V AC/DC
208 V 250 V AC/DC
380 V 440 V AC/DC
480 V 525 V AC/DC

For Immediate Delivery call KMParts.com at (866) 595-9616

47

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

46

SK1157_044-049_b_G.fm Page 48 Friday, May 12, 2006 3:59 PM

Circuit-breakers, disconnect switches


Shunt releases with screw terminal

Circuit-breakers, disconnect switches


Shunt releases with screw terminal
Moeller SK1230-1157EN-NA

For use with

Rated control voltage


Us
V

Moeller SK1230-1157EN-NA

Part no.
Article no.
when ordered separately

Std. pack

Notes

NZM3-XAHIV-230AC-MNS
274141

1 off

Cannot be installed simultaneously with NZM...-XHIV... earlymake auxiliary contact or NZM...-XU... undervoltage release.
Cannot be used in conjunction with NZM...-XR... remote
operator.

Shunt releases
With early-make auxiliary contact
For mesh-network circuit-breakers
For intermittent operation
Maximum on time = 1 s
Operating range 10 110 % Us
not UL/CSA approved
C1

3.13

C2

3.14

C1

3.13

C2

3.14

NZM3, N3

NZM4, N4

230 V AC

230 V AC

NZM4-XAHIV-230AC-MNS
274143

For Immediate Delivery call KMParts.com at (866) 595-9616

1 off

Intermittent operation guaranteed by series connection of a


N/O contact M22-(C)K10 (standard auxiliary contact).
The maximum operating time of the shunt release for mesh
network circuit-breaker is 1 s.
NZM3: Early-make of the auxiliary contact with on and off
switching (manual operation): approx. 20 ms.
NZM4: Early-make of the auxiliary contact with switch on
(manual operation): approx. 90 ms.

49

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

48

SK1157_044-049_b_G.fm Page 48 Friday, May 12, 2006 3:59 PM

Circuit-breakers, disconnect switches


Shunt releases with screw terminal

Circuit-breakers, disconnect switches


Shunt releases with screw terminal
Moeller SK1230-1157EN-NA

For use with

Rated control voltage


Us
V

Moeller SK1230-1157EN-NA

Part no.
Article no.
when ordered separately

Std. pack

Notes

NZM3-XAHIV-230AC-MNS
274141

1 off

Cannot be installed simultaneously with NZM...-XHIV... earlymake auxiliary contact or NZM...-XU... undervoltage release.
Cannot be used in conjunction with NZM...-XR... remote
operator.

Shunt releases
With early-make auxiliary contact
For mesh-network circuit-breakers
For intermittent operation
Maximum on time = 1 s
Operating range 10 110 % Us
not UL/CSA approved
C1

3.13

C2

3.14

C1

3.13

C2

3.14

NZM3, N3

NZM4, N4

230 V AC

230 V AC

NZM4-XAHIV-230AC-MNS
274143

1 off

Intermittent operation guaranteed by series connection of a


N/O contact M22-(C)K10 (standard auxiliary contact).
The maximum operating time of the shunt release for mesh
network circuit-breaker is 1 s.
NZM3: Early-make of the auxiliary contact with on and off
switching (manual operation): approx. 20 ms.
NZM4: Early-make of the auxiliary contact with switch on
(manual operation): approx. 90 ms.

For Immediate Delivery call KMParts.com at (866) 595-9616

49

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

48

SK1157_050-053_b_G.fm Page 50 Thursday, June 8, 2006 9:37 AM

Circuit-breakers, disconnect switches


Door coupling rotary handles

Circuit-breakers, disconnect switches


Door coupling rotary handles
Moeller SK1230-1157EN-NA

For use with

Part no.
Article no.
when ordered
separately

Price
see price
list

Std. pack

Notes

Moeller SK1230-1157EN-NA
For a max. shaft length of 60 mm
Part no.
Price
Article no.
see price
when ordered
list
separately

Std. pack

Notes

Extremely narrow fittings


Part no.
Price
Article no.
see price
when ordered
list
separately

Std. pack

Notes

CSA only
Door coupling rotary handle
Complete including rotary drive and coupling parts
An additional extension shaft is necessary with the NZM...-XT(V)D(V)(R)(-60) types.
Degree of protection IP66/UL/CSA Type 4X
Standard, black/grey
Lockable in 0 position on
NZM1, N1
handle. With door
interlock
NZM2, N2
NZM3, N3
NZM4, N4
Lockable on handle and
switch. Can be locked in
0 position, with adequate
modification also in
I position. With door
interlock Lockable in
0 position on circuitbreaker.

Red-yellow for Emergency-Stop


Lockable on handle and
switch. Lockable in
0 position on handle. With
door interlock Lockable in
0 position on circuitbreaker.

NZM1, N1
NZM2, N2
NZM3, N3
NZM4, N4

NZM1, N1
NZM2, N2
NZM3, N3
NZM4, N4

NZM1-XTVD
260166
NZM2-XTVD
260168
NZM3-XTVD
260170
NZM4-XTVD
266614
NZM1-XTVDV
260172
NZM2-XTVDV
260174
NZM3-XTVDV
260176
NZM4-XTVDV
266616

Door interlock
Not defeated in the locked
OFF and ON positions
Can be modified such that it
can be defeated from the
outside using a screwdriver,
when it is in the unlocked
ON position.
Door can be opened in OFF
NZM...-XTVD(V)
External warning plate/
designation label can be
clipped on

NZM1-XTVDV-60
271508
NZM2-XTVDV-60
271509
NZM3-XTVDV-60
271510
NZM4-XTVDV-60
271511

NZM1-XTVDVR-60
271512
NZM2-XTVDVR-60
271513
NZM3-XTVDVR-60
271514
NZM4-XTVDVR-60
271515

NZM1-XTVDVR
260178
NZM2-XTVDVR
260180
NZM3-XTVDVR
260182
NZM4-XTVDVR
266618

1 off

Door interlock
Not defeatable in the
locked OFF position.
Can be modified such that it
can be defeated from the
outside using a screwdriver,
when it is in the unlocked
ON position.
Door can be opened in OFF
NZM...-XTVDVR
External warning plate/
designation label can be
clipped on

1 off

Can be cut to required length

Extension shaft

Notes

Max. mounting depth:


400 mm

NZM1, N1
NZM2, N2
NZM3, N3
NZM4, N4

NZM1/2-XV4
261232
NZM3/4-XV4
261234

Max. mounting depth:


600 mm

NZM1, N1
NZM2, N2
NZM3, N3
NZM4, N4

NZM1/2-XV6
260191
NZM3/4-XV6
260193

Circuit-breaker can also be installed in a lying position 90 left/right, with the handle still in the same position.

For Immediate Delivery call KMParts.com at (866) 595-9616

1 off

Door interlock
For maximum shaft length 60
mm
Without shaft support
Cannot be combined with
NZM...-XDZ additional handle
External warning plate/
designation label can be
clipped on

NZM1-XTVDV-0
279396
NZM2-XTVDV-0
279397
NZM3-XTVDV-0
279398
NZM4-XTVDV-0
279399

Door interlock
Not defeatable in the locked
OFF position.
Can be modified such that it
can be defeated from the
outside using a screwdriver,
when it is in the unlocked ON
position.
Door can be opened in OFF
NZM...-XTVDVR-60
For maximum shaft length 60
mm
Without shaft support
Cannot be combined with
NZM...-XDZ additional handle
External warning plate/
designation label can be
clipped on

NZM1-XTVDVR-0
279400
NZM2-XTVDVR-0
279401
NZM3-XTVDVR-0
279402
NZM4-XTVDVR-0
279403

Door interlock
Not defeated in the locked OFF
and ON positions
Can be modified such that it can
be defeated from the outside
using a screwdriver, when it is in
the unlocked ON position.
Door can be opened in OFF
NZM...-XTVDV-0
For extremely narrow fittings
With special short extension
shaft
Cannot be combined with
NZM...-XDZ additional handle
External warning plate/
designation label can be clipped
on

1 off

Door interlock
Not defeatable in the locked OFF
position.
Can be modified such that it can
be defeated from the outside
using a screwdriver, when it is in
the unlocked ON position.
Door can be opened in OFF
NZM...-XTVDVR-0
For extremely narrow fittings
With special short extension
shaft
Cannot be combined with
NZM...-XDZ additional handle
External warning plate/
designation label can be clipped
on

51

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

50

SK1157_050-053_b_G.fm Page 50 Thursday, June 8, 2006 9:37 AM

Circuit-breakers, disconnect switches


Door coupling rotary handles

Circuit-breakers, disconnect switches


Door coupling rotary handles
Moeller SK1230-1157EN-NA

For use with

Part no.
Article no.
when ordered
separately

Price
see price
list

Std. pack

Notes

Moeller SK1230-1157EN-NA
For a max. shaft length of 60 mm
Part no.
Price
Article no.
see price
when ordered
list
separately

Std. pack

Notes

Extremely narrow fittings


Part no.
Price
Article no.
see price
when ordered
list
separately

Std. pack

Notes

CSA only
Door coupling rotary handle
Complete including rotary drive and coupling parts
An additional extension shaft is necessary with the NZM...-XT(V)D(V)(R)(-60) types.
Degree of protection IP66/UL/CSA Type 4X
Standard, black/grey
Lockable in 0 position on
NZM1, N1
handle. With door
interlock
NZM2, N2
NZM3, N3
NZM4, N4
Lockable on handle and
switch. Can be locked in
0 position, with adequate
modification also in
I position. With door
interlock Lockable in
0 position on circuitbreaker.

Red-yellow for Emergency-Stop


Lockable on handle and
switch. Lockable in
0 position on handle. With
door interlock Lockable in
0 position on circuitbreaker.

NZM1, N1
NZM2, N2
NZM3, N3
NZM4, N4

NZM1, N1
NZM2, N2
NZM3, N3
NZM4, N4

NZM1-XTVD
260166
NZM2-XTVD
260168
NZM3-XTVD
260170
NZM4-XTVD
266614
NZM1-XTVDV
260172
NZM2-XTVDV
260174
NZM3-XTVDV
260176
NZM4-XTVDV
266616

Door interlock
Not defeated in the locked
OFF and ON positions
Can be modified such that it
can be defeated from the
outside using a screwdriver,
when it is in the unlocked
ON position.
Door can be opened in OFF
NZM...-XTVD(V)
External warning plate/
designation label can be
clipped on

NZM1-XTVDV-60
271508
NZM2-XTVDV-60
271509
NZM3-XTVDV-60
271510
NZM4-XTVDV-60
271511

NZM1-XTVDVR-60
271512
NZM2-XTVDVR-60
271513
NZM3-XTVDVR-60
271514
NZM4-XTVDVR-60
271515

NZM1-XTVDVR
260178
NZM2-XTVDVR
260180
NZM3-XTVDVR
260182
NZM4-XTVDVR
266618

1 off

Door interlock
Not defeatable in the
locked OFF position.
Can be modified such that it
can be defeated from the
outside using a screwdriver,
when it is in the unlocked
ON position.
Door can be opened in OFF
NZM...-XTVDVR
External warning plate/
designation label can be
clipped on

1 off

Can be cut to required length

1 off

Door interlock
For maximum shaft length 60
mm
Without shaft support
Cannot be combined with
NZM...-XDZ additional handle
External warning plate/
designation label can be
clipped on

NZM1-XTVDV-0
279396
NZM2-XTVDV-0
279397
NZM3-XTVDV-0
279398
NZM4-XTVDV-0
279399

Door interlock
Not defeatable in the locked
OFF position.
Can be modified such that it
can be defeated from the
outside using a screwdriver,
when it is in the unlocked ON
position.
Door can be opened in OFF
NZM...-XTVDVR-60
For maximum shaft length 60
mm
Without shaft support
Cannot be combined with
NZM...-XDZ additional handle
External warning plate/
designation label can be
clipped on

NZM1-XTVDVR-0
279400
NZM2-XTVDVR-0
279401
NZM3-XTVDVR-0
279402
NZM4-XTVDVR-0
279403

Door interlock
Not defeated in the locked OFF
and ON positions
Can be modified such that it can
be defeated from the outside
using a screwdriver, when it is in
the unlocked ON position.
Door can be opened in OFF
NZM...-XTVDV-0
For extremely narrow fittings
With special short extension
shaft
Cannot be combined with
NZM...-XDZ additional handle
External warning plate/
designation label can be clipped
on

1 off

Door interlock
Not defeatable in the locked OFF
position.
Can be modified such that it can
be defeated from the outside
using a screwdriver, when it is in
the unlocked ON position.
Door can be opened in OFF
NZM...-XTVDVR-0
For extremely narrow fittings
With special short extension
shaft
Cannot be combined with
NZM...-XDZ additional handle
External warning plate/
designation label can be clipped
on

Extension shaft

Notes

Max. mounting depth:


400 mm

NZM1, N1
NZM2, N2
NZM3, N3
NZM4, N4

NZM1/2-XV4
261232
NZM3/4-XV4
261234

Max. mounting depth:


600 mm

NZM1, N1
NZM2, N2
NZM3, N3
NZM4, N4

NZM1/2-XV6
260191
NZM3/4-XV6
260193

Circuit-breaker can also be installed in a lying position 90 left/right, with the handle still in the same position.

For Immediate Delivery call KMParts.com at (866) 595-9616

51

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

50

SK1157_050-053_b_G.fm Page 52 Thursday, June 8, 2006 9:39 AM

Circuit-breakers, disconnect switches


Rotary handles with door interlock for UL/CSA approved NA switches

Circuit-breakers, disconnect switches


Rotary handles with door interlock for UL/CSA approved NA switches
Moeller SK1230-1157EN-NA

For use with

Standard
Part no.
Article no.
when ordered
separately

Price
see price
list

Moeller SK1230-1157EN-NA
For a max. shaft length of 60 mm
Part no.
Price
Article no.
see price
when ordered
list
separately

Notes

Extremely narrow fittings


Part no.
Price
Article no.
see price
when ordered
list
separately

Std. pack

Notes

Std. pack Notes

NZM1-XTVDV-NA
100683
NZM2-XTVDV-NA
100684
NZM3-XTVDV-NA
100685
NZM4-XTVDV-NA
100686

1 off

Door interlock
Not defeated in the locked
OFF position
Door opening possible with
active rotation beyond the
0 position.
Cannot be combined with
mechanical interlock
External warning plate/
designation label can be
clipped on

NZM1-XTVDV-60-NA
100667
NZM2-XTVDV-60-NA
100668
NZM3-XTVDV-60-NA
100669
NZM4-XTVDV-60-NA
100670

Door interlock
Not defeated in the locked OFF
position
Door opening possible with active
rotation beyond the 0 position.
Cannot be combined with
mechanical interlock
External warning plate/
designation label can be clipped
on
NZM...-XTVDV-60-NA
For a maximum shaft length of
60 mm
Without shaft support
Cannot be combined with
NZM...-XDZ additional handle
External warning plate/
designation label can be clipped
on

NZM1-XTVDV-0-NA
100675
NZM2-XTVDV-0-NA
100676
NZM3-XTVDV-0-NA
100677
NZM4-XTVDV-0-NA
100678

1 off

Door interlock
Not defeated in the locked OFF
position
Door opening possible with active
rotation beyond the 0 position.
Cannot be combined with
mechanical interlock
External warning plate/
designation label can be clipped
on
NZM...-XTVDV-0-NA
For extremely narrow fittings
With special short extension shaft
Cannot be combined with
NZM...-XDZ additional handle
External warning plate/
designation label can be clipped
on

NZM1-XTVDVR-NA
271449
NZM2-XTVDVR-NA
271450
NZM3-XTVDVR-NA
271451
NZM4-XTVDVR-NA
271452

1 off

Door interlock
Not defeated in the locked
OFF position
Door opening possible with
active rotation beyond the
0 position.
Cannot be combinedwith
mechanical interlock
External warning plate/
designation label can be
clipped on

NZM1-XTVDVR-60-NA
100671
NZM2-XTVDVR-60-NA
100672
NZM3-XTVDVR-60-NA
100673
NZM4-XTVDVR-60-NA
100674

Door interlock
Not defeated in the locked OFF
position
Door opening possible with active
rotation beyond the 0 position.
Cannot be combined with
mechanical interlock
External warning plate/
designation label can be clipped
on
NZM...-XTVDVR-60-NA
For a maximum shaft length of
60 mm
Without shaft support
Cannot be combined with
NZM...-XDZ additional handle
External warning plate/
designation label can be clipped
on

NZM1-XTVDVR-0-NA
100679
NZM2-XTVDVR-0-NA
100680
NZM3-XTVDVR-0-NA
100681
NZM4-XTVDVR-0-NA
100682

1 off

Door interlock
Not defeated in the locked OFF
position
Door opening possible with active
rotation beyond the 0 position.
Cannot be combined with
mechanical interlock
External warning plate/
designation label can be clipped
on
NZM...-XTVDVR-0-NA
For extremely narrow fittings
With special short extension shaft
Cannot be combined with
NZM...-XDZ additional handle
External warning plate/
designation label can be clipped
on

NZM1,
N1
NZM2,
N2
NZM3,
N3
NZM4, N4

NZM1/2-XV4
261232

1 off

Can be cut to required length

NZM1,
N1
NZM2,
PN2, N2
NZM3,
N3
NZM4, N4

NZM1/2-XV6
260191

Door coupling rotary handle


Complete including rotary drive and coupling parts
Extension shaft additionally required.
Degree of protection IP66/UL/CSA Type 4X
Standard, black/grey
Lockable on handle and
switch. Can be locked in
0 position, with adequate
modification also in
I position. With door
interlock Lockable in
0 position on breaker.

NZM1, N1
NZM2, N2
NZM3, N3
NZM4, N4

Red-yellow for Emergency-Stop


Lockable on handle and
switch. Lockable in
0 position on handle. With
door interlock Lockable in
0 position on breaker.

NZM1, N1
NZM2, N2
NZM3, N3
NZM4, N4

Extension shaft
Max. mounting depth:
400 mm

Max. mounting depth:


600 mm

Notes

NZM3/4-XV4
261234

NZM3/4-XV6
260193

Circuit-breaker can also be installed in a lying position 90 left/right, with the handle still in the same position.

For Immediate Delivery call KMParts.com at (866) 595-9616

53

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

52

SK1157_050-053_b_G.fm Page 52 Thursday, June 8, 2006 9:39 AM

Circuit-breakers, disconnect switches


Rotary handles with door interlock for UL/CSA approved NA switches

Circuit-breakers, disconnect switches


Rotary handles with door interlock for UL/CSA approved NA switches
Moeller SK1230-1157EN-NA

For use with

Standard
Part no.
Article no.
when ordered
separately

Price
see price
list

Moeller SK1230-1157EN-NA
For a max. shaft length of 60 mm
Part no.
Price
Article no.
see price
when ordered
list
separately

Notes

Extremely narrow fittings


Part no.
Price
Article no.
see price
when ordered
list
separately

Std. pack

Notes

Std. pack Notes

NZM1-XTVDV-NA
100683
NZM2-XTVDV-NA
100684
NZM3-XTVDV-NA
100685
NZM4-XTVDV-NA
100686

1 off

Door interlock
Not defeated in the locked
OFF position
Door opening possible with
active rotation beyond the
0 position.
Cannot be combined with
mechanical interlock
External warning plate/
designation label can be
clipped on

NZM1-XTVDV-60-NA
100667
NZM2-XTVDV-60-NA
100668
NZM3-XTVDV-60-NA
100669
NZM4-XTVDV-60-NA
100670

Door interlock
Not defeated in the locked OFF
position
Door opening possible with active
rotation beyond the 0 position.
Cannot be combined with
mechanical interlock
External warning plate/
designation label can be clipped
on
NZM...-XTVDV-60-NA
For a maximum shaft length of
60 mm
Without shaft support
Cannot be combined with
NZM...-XDZ additional handle
External warning plate/
designation label can be clipped
on

NZM1-XTVDV-0-NA
100675
NZM2-XTVDV-0-NA
100676
NZM3-XTVDV-0-NA
100677
NZM4-XTVDV-0-NA
100678

1 off

Door interlock
Not defeated in the locked OFF
position
Door opening possible with active
rotation beyond the 0 position.
Cannot be combined with
mechanical interlock
External warning plate/
designation label can be clipped
on
NZM...-XTVDV-0-NA
For extremely narrow fittings
With special short extension shaft
Cannot be combined with
NZM...-XDZ additional handle
External warning plate/
designation label can be clipped
on

NZM1-XTVDVR-NA
271449
NZM2-XTVDVR-NA
271450
NZM3-XTVDVR-NA
271451
NZM4-XTVDVR-NA
271452

1 off

Door interlock
Not defeated in the locked
OFF position
Door opening possible with
active rotation beyond the
0 position.
Cannot be combinedwith
mechanical interlock
External warning plate/
designation label can be
clipped on

NZM1-XTVDVR-60-NA
100671
NZM2-XTVDVR-60-NA
100672
NZM3-XTVDVR-60-NA
100673
NZM4-XTVDVR-60-NA
100674

Door interlock
Not defeated in the locked OFF
position
Door opening possible with active
rotation beyond the 0 position.
Cannot be combined with
mechanical interlock
External warning plate/
designation label can be clipped
on
NZM...-XTVDVR-60-NA
For a maximum shaft length of
60 mm
Without shaft support
Cannot be combined with
NZM...-XDZ additional handle
External warning plate/
designation label can be clipped
on

NZM1-XTVDVR-0-NA
100679
NZM2-XTVDVR-0-NA
100680
NZM3-XTVDVR-0-NA
100681
NZM4-XTVDVR-0-NA
100682

1 off

Door interlock
Not defeated in the locked OFF
position
Door opening possible with active
rotation beyond the 0 position.
Cannot be combined with
mechanical interlock
External warning plate/
designation label can be clipped
on
NZM...-XTVDVR-0-NA
For extremely narrow fittings
With special short extension shaft
Cannot be combined with
NZM...-XDZ additional handle
External warning plate/
designation label can be clipped
on

NZM1,
N1
NZM2,
N2
NZM3,
N3
NZM4, N4

NZM1/2-XV4
261232

1 off

Can be cut to required length

NZM1,
N1
NZM2,
PN2, N2
NZM3,
N3
NZM4, N4

NZM1/2-XV6
260191

Door coupling rotary handle


Complete including rotary drive and coupling parts
Extension shaft additionally required.
Degree of protection IP66/UL/CSA Type 4X
Standard, black/grey
Lockable on handle and
switch. Can be locked in
0 position, with adequate
modification also in
I position. With door
interlock Lockable in
0 position on breaker.

NZM1, N1
NZM2, N2
NZM3, N3
NZM4, N4

Red-yellow for Emergency-Stop


Lockable on handle and
switch. Lockable in
0 position on handle. With
door interlock Lockable in
0 position on breaker.

NZM1, N1
NZM2, N2
NZM3, N3
NZM4, N4

Extension shaft
Max. mounting depth:
400 mm

Max. mounting depth:


600 mm

Notes

NZM3/4-XV4
261234

NZM3/4-XV6
260193

Circuit-breaker can also be installed in a lying position 90 left/right, with the handle still in the same position.

For Immediate Delivery call KMParts.com at (866) 595-9616

53

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

52

SK1157_054-058_b_G.fm Page 54 Thursday, June 8, 2006 9:41 AM

Circuit-breakers, disconnect switches


up to 1200 A

54

Circuit-breakers, disconnect switches


Rotary handles
Moeller SK1230-1157EN-NA
For use with

Part no.
Article no.
when ordered
separately

NZM1, N1

NZM1-XDV
260125

NZM2, N2

NZM2-XDV
260127

NZM3, N3

NZM3-XDV
260129
NZM4-XDV
266608

Price
see price
list

Std. pack

Notes

CSA only
Rotary handles
Complete with rotary drive
Standard, black/grey
Lockable on the 0 position
on the switch using up to
3 padlocks.

NZM4, N4

Lockable on the 0 position


on the handle using up to
3 padlocks.

Red-yellow for Emergency-Stop


Lockable on the 0 position
on the switch using up to
3 padlocks.

NZM1, N1

NZM1-XDVG
285247

NZM2, N2

NZM2-XDVG
285248

NZM1, N1

NZM1-XDVR
260135

NZM2, N2

NZM2-XDVR
260137

NZM3, N3

NZM3-XDVR
260140
NZM4-XDVR
266610

NZM4, N4

Lockable on the 0 position


on the handle using up to 3
padlocks.

Notes

NZM1, N1

NZM1-XDVGR
285249

NZM2, N2

NZM2-XDVGR
285280

NZM1, 2, 3: Can also be combined


with insulating surround.
MODAN handle position detection by
wire release can be retrofitted.

Can also be combined with insulating


surround.

1 off

NZM1, 2, 3: Can also be combined


with insulating surround.
MODAN handle position detection by
wire release can be retrofitted.

Can also be combined with insulating


surround.

Circuit-breaker can also be installed in a lying position 90 left/right, with the handle still in the same position.

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_054-058_b_G.fm Page 55 Thursday, June 8, 2006 9:42 AM

Notes

Circuit-breakers, disconnect switches


up to 1200 A

Moeller SK1230-1157EN-NA

55

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_054-058_b_G.fm Page 56 Friday, May 12, 2006 4:04 PM

Circuit-breakers, disconnect switches


up to 1200 A

56

Circuit-breakers, disconnect switches


Main switch assembly kit
Moeller SK1230-1157EN-NA
For use with

Part no.
Article no.
when ordered
separately

Price
see price
list

Std. pack

CSA only
Main switch assembly kit
Equipment supplied:
Rotary door-coupling handle
NZM...-XV4 extension shaft
External warning plate/designation label in German/English
Black and yellow flash
For enhanced protection against direct contact on the incomer side, IP2X protection against contact with a finger can be
ordered a 68
Other external warning plates/designation labels can be clipped on.
With black door coupling rotary handle
Lockable in 0 position on handle. With
NZM1
door interlock
N1
NZM2
N2
NZM3
N3
NZM4
N4

NZM1-XHB
266626
NZM2-XHB
266627
NZM3-XHB
266628
NZM4-XHB
271779

1 off

With red door coupling rotary handle for using switch as Emergency-Stop device according to IEC/EN 602041
Lockable in 0 position on handle.
Lockable door, locking facility on
circuit-breaker in 0 position.

NZM1
N1
NZM2
N2
NZM3
N3
NZM4
N4

NZM1-XHBR
266632
NZM2-XHBR
266633
NZM3-XHBR
266634
NZM4-XHBR
271842

Main switch assembly kit for side panel mounting


Actuation of the switch on the control panel side wall
Switch mounting on mounting plate
Equipment supplied:
Door coupling rotary handle
NZM...-XV4 extension shaft
External warning plate/designation label in German/English
Black and yellow flash
For enhanced protection against direct contact on the incomer side, IP2X protection against contact with a finger can be
ordered a 68
Other external warning plates/designation labels can be clipped on.
Standard, black/grey
Can be locked in 0 position, with
For operation on
NZM1
adequate modification also in I
the left
N1
position.
NZM2
N2
NZM3
N3
NZM4
N4

Red-yellow for Emergency-Stop


Lockable in 0 position on handle.

NZM1-XS-L
266641
NZM2-XS-L
266642
NZM3-XS-L
266643
NZM4-XS-L
289806

For operation on
the right

NZM1
N1
NZM2
PN2, N2
NZM3
N3
NZM4
N4

NZM1-XS-R
266644
NZM2-XS-R
266645
NZM3-XS-R
266646
NZM4-XS-R
289807

For operation on
the left

NZM1
N1
NZM2
N2
NZM3
N3
NZM4
N4

NZM1-XSR-L
266653
NZM2-XSR-L
266654
NZM3-XSR-L
266655
NZM4-XSR-L
289808

For operation on
the right

NZM1
N1
NZM2
N2
NZM3
N3
NZM4
N4

NZM1-XSR-R
266656
NZM2-XSR-R
266657
NZM3-XSR-R
266658
NZM4-XSR-R
289809

For Immediate Delivery call KMParts.com at (866) 595-9616

1 off

SK1157_054-058_b_G.fm Page 57 Friday, May 12, 2006 4:04 PM

57

Moeller SK1230-1157EN-NA
For use with

Part no.
Article no. when
ordered separately

Price
see price
list

Std. pack

Main switch assembly kit for side wall installation


Actuation of the switch on the control panel door.
Mounting the breaker on the control panel side wall
Equipment supplied:
Door coupling rotary handle
NZM...-XV4 extension shaft
External warning plate/designation label in German/English
Black and yellow flash
For enhanced protection against direct contact on the incomer side, IP2X protection against contact with a finger can be
ordered a 68
Other external warning plates/designation labels can be clipped on.
Standard, black/grey
Lockable on handle and switch. Can be
For operation
NZM1, N1
locked in 0 position, with adequate
on the left
modification also in I position. Tamperproof
NZM2, N2
with door interlock in closed OFF and ON
position.
NZM3, N3
NZM4, N4
For operation
on the right

NZM1, N1
NZM2, N2
NZM3, N3
NZM4, N4

Red-yellow for Emergency-Stop


Lockable on handle and switch. Lockable in
0 position on handle. Tamperproof with
door interlock in closed OFF position.

For operation
on the left

NZM1, N1
NZM2, N2
NZM3, N3
NZM4, N4

For operation
on the right

NZM1, N1
NZM2, N2
NZM3, N3
NZM4, N4

NZM1-XSF-L
289810
NZM2-XSF-L
289811
NZM3-XSF-L
289812
NZM4-XSF-L
289813

1 off

NZM1-XSF-R
289814
NZM2-XSF-R
289815
NZM3-XSF-R
289816
NZM4-XSF-R
289817
NZM1-XSRF-L
289818
NZM2-XSRF-L
289819
NZM3-XSRF-L
289820
NZM4-XSRF-L
289821
NZM1-XSRF-R
289822
NZM2-XSRF-R
289823
NZM3-XSRF-R
289824
NZM4-XSRF-R
289825

For Immediate Delivery call KMParts.com at (866) 595-9616

1 off

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


Main switch assembly kit

SK1157_054-058_b_G.fm Page 58 Friday, May 12, 2006 4:04 PM

Circuit-breakers, disconnect switches


up to 1200 A

58

Circuit-breakers, disconnect switches


Main switch assembly kit
Moeller SK1230-1157EN-NA
For use with

Part no.
Article no. when
ordered
separately

Price
see price
list

Std. pack

CSA only
Main switch assembly kit for side panel mounting with mounting bracket
For direct mounting of circuit-breaker and handle in the side wall of the control cabinet
Equipment supplied:
Door coupling rotary handle
Mounting bracket
Special short extension shaft
External warning plate/designation label in German/English
Black and yellow flash
For enhanced protection against direct contact on the incomer side, IP2X protection against contact with a finger can be
ordered a 68
Other external warning plates/designation labels can be clipped on.
Standard, black/grey
Can be locked in 0 position, with adequate modification also For operation
NZM1
in I position. Narrowest minimum clearance between
on the left
N1
enclosure side plates of control panel and circuit-breaker is For operation
NZM2
defined by mounting bracket. Extensions cannot be used.
on the left
N2
For operation
NZM1
on the right
N1
For operation
NZM2
on the right
N2
Red-yellow for Emergency-Stop
Lockable in 0 position on handle. Narrowest minimum
clearance between enclosure side plates of control panel and
circuit-breaker is defined by mounting bracket. Extensions
cannot be used.

For operation
on the left
For operation
on the left
For operation
on the right
For operation
on the right

NZM1
N1
NZM2
N2
NZM1
N1
NZM2
N2

NZM1-XSM-L
266663
NZM2-XSM-L
266664
NZM1-XSM-R
266665
NZM2-XSM-R
266666

1 off

NZM1-XSRM-L
266671
NZM2-XSRM-L
266672
NZM1-XSRM-R
266673
NZM2-XSRM-R
266674

1 off

NZM1/2-XZB
266676

1 off

Add-on plate
For fitting to the mounting bracket when using N conductor or PE conductor terminals K25, K50, K95 or K150.

NZM1,
N1
NZM2,
N2

Additional terminal arrangement for side wall operator with mounting bracket
NZM1-XS(R)M-..., NZM2-XS(R)M-...
Additional terminals K25, K50, K95, K150
Actuation:
3-pole
For operation on the right

MII

For operation on the left

MI

Mounting areas
Variation options
Maximum number of additional
terminals

MI

K25
K50
K95
K150

MI
V1
2x

V2

2x

MII

V3

1x

V4

1x

MII
V1

1x

V2

1x

Example: In mounting area MI, variation option 1 allows the K25 additional terminal to be mounted twice.

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_059-061_b_G.fm Page 59 Thursday, May 4, 2006 6:19 PM

Moeller SK1230-1157EN-NA
For use with

Part no.
Article no.
when ordered
separately

NZM1, N1
NZM2, N2
NZM3, N3
NZM4, N4

ZFS61/62-NZM7
272525
ZFS61-NZM7
051089
ZFS62-NZM7
065957
ZFS63-NZM7
065958
ZFS60-NZM7
065896

Price
see price
list

Std. pack

Notes

10 off

A bilingual external warning plate/


designation label in German/English is
already included in the main switch assembly
kit.

External warning/marking plate


Main switch open in 0 position
German/English
German
English
French
Blank (for engraving or printing)
Further languages

ZFS*-NZM7
999978

External warning plates are available in the


following languages:
64 Bulgarian
73 Romanian
65 Danish
74 Russian
66 Finnish
75 Swedish
67 Dutch
76 Serbo-Croatian
68 Italian
77 Spanish
69 Greek
78 Czech
70 Norwegian
79 Turkish
71 Polish
80 Hungarian
72 Portugese
81 Afrikaans
To obtain the reference for ordering, insert
the language code number into the type
reference required
Ordering example
External warning plate in Finnish:
ZFS66-NZM7

Lightning symbol
For main switches
small

large

U X
V Y
W Z

L1 T1 N PEN
L2 T2
L3 T3 PE

NZM1, N1
NZM2, N2

BPF-NZM7
217294

10 off

U X
V Y
W Z

L1 T1 N PEN
L2 T2
L3 T3 PE

NZM3, N3
NZM4, N4

BPF-NZM10
231363

10 off

Included as standard in main switch


assembly kit

For Immediate Delivery call KMParts.com at (866) 595-9616

59

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


Accessories

SK1157_059-061_b_G.fm Page 60 Thursday, May 4, 2006 6:19 PM

Circuit-breakers, disconnect switches


up to 1200 A

60

Circuit-breakers, disconnect switches


Accessories
Moeller SK1230-1157EN-NA
For use with

Part no.
Article no.
when ordered
separately

Price
see price
list

Std. pack

Notes

NZM1/2-XDZ
266621

1 off

Push-fits on to the extension shaft


100 mm free extension shaft required.

NZM3/4-XDZ
266622

1 off

NZM1-XBR
260195

1 off

For oblong cut-out on doors and enclosures with


material thicknesses of 1.5 5 mm.
External warning plate/designation label can be
clipped on
NZM4-XBR cannot be combined with rotary handle
with rotary drive.

NZM1-XKAV
260199
NZM2/3-XKAV
260201

1 off

Cannot be combined with insulating surround.

NZM1, N1
NZM2, N2

NZM1/2-XAB
260203

1 set

NZM3
N3
NZM4
N4

NZM3-XAB
260211

1 set

NZM1-XC35
260213

1 off

For top-hat rail 35 mm

NZM2-XC75
260215

1 off

For top-hat rail 75 mm


Not suitable for circuit-breakers with remote
operator.

Add-on handle
Enables switching when the control panel door is open
NZM1, N1
NZM2, N2
NZM3, N3
NZM4, N4
Insulating surrounds
For toggle lever, rotary handle with rotary drive and remote
operator.
NZM1
N1
NZM2
N2
NZM3
N3
NZM4
N4

NZM2-XBR
260197
NZM3-XBR
284645
NZM4-XBR
284646

Toggle lever locking device


Off position lockable using up to 3 padlocks
(hasp thickness 4 8 mm)
NZM1
N1
NZM2, N2
NZM3, N3

1 off

Spacers
Enables fast and low-priced adjustment of differing frame sizes
with/without rotary handle to the same front depth
Grid depth 17.5 mm, M4 thread
Type contains 4 off spacer
Maximum component capacity:
NZM1: 4 units per fixing screw,
NZM2: 2 units per fixing screw
2 (NZM1) or 4 (NZM2) fixing screws contained per
circuit-breaker
Grid depth 17.5 mm, M5 thread
One set contains 4 spacers
NZM3, NZM4: 1 off per fixing screw
4 fixing screws per switch included

Clip plate
Enables snap-fit of the circuit-breaker to a DIN rail
NZM1
N1

NZM2
N2

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_059-061_b_G.fm Page 61 Thursday, May 4, 2006 6:19 PM

Moeller SK1230-1157EN-NA
For use with

Part no.
Article no.
when ordered
separately

Price
see price
list

Std. pack

Notes

1 off

Rotary handles on switches or door


coupling rotary handles are additionally
required.
Cannot be combined with paralleling
mechanisms, side wall operators and
remote operator as well as NZM4-XBR
insulating surrounds.
Cannot be combined with rotary
handles and door coupling rotary handles
for -UL/CSA approved NA switches.
In order to establish a mechanical interlock
at least 2 interlock modules are required.
Possible combinations and interlock
variants a engineering
Order Bowden cables separately

NZM-XBZ225
281585
NZM-XBZ600
281586
NZM-XBZ1000
281587

1 off

NZM2-XMVR1)
104543
NZM2/3-XMVR1)
104544
NZM3-XMVR1)
104545
NZM3/4-XMVR1)
104546
NZM4-XMVR1)
104547

1 off

Type contains parts for both switches.


Remote operator also required.
Maximum switching distance a
engineering
Cannot be combined with rotary handles,
door coupling rotary handles and earlymake auxiliary contacts.

NZM2-XMVRL1)
104548
NZM2/3-XMVRL1)
104549
NZM3-XMVRL1)
104550
NZM3/4-XMVRL1)
104551
NZM4-XMVRL1)
104552

1 off

Type contains parts for both switches.


Remote operator also required.
Maximum switching distance a
engineering
Cannot be combined with rotary
handles, door coupling rotary handles and
early-make auxiliary contacts.

Mechanical interlocking of (door coupling) rotary handles


NZM1
N1

NZM1-XMV
281581

NZM2
N2

NZM2-XMV
281582

NZM3
N3
NZM4
N4

NZM3-XMV
281583
NZM4-XMV
281584

Bowden cables
For mechanical interlocking of (door coupling) rotary handles
NZM1, N1
NZM2, N2
NZM3, N3
NZM4, N4

Mechanical interlock for remote operator


For 2 switches of the same or next frame size with each other.
Mounting beside one another.
NZM2(-4), N2(-4)
+NZM2(-4), N2(-4)
NZM2(-4), N2(-4)
+NZM3(-4), N3(-4)
NZM3(-4), N3(-4)
+NZM3(-4), N3(-4)
NZM3(-4), N3(-4)
+NZM4(-4), N4(-4)
NZM4(-4), N4(-4)
+NZM4(-4), N4(-4)

For 2 switches of the same or next frame size with each other. Extra
long Bowden cables for mounting in neighbouring control panel fields.
NZM2(-4), N2(-4)
+NZM2(-4), N2(-4)
NZM2(-4), N2(-4)
+NZM3(-4), N3(-4)
NZM3(-4), N3(-4)
+NZM3(-4), N3(-4)
NZM3(-4), N3(-4)
+NZM4(-4), N4(-4)
NZM4(-4), N4(-4)
+NZM4(-4), N4(-4)

Notes

1) on

request

For Immediate Delivery call KMParts.com at (866) 595-9616

61

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


Mechanical interlock

SK1157_062-063_b_G.fm Page 62 Thursday, June 8, 2006 3:55 PM

Circuit-breakers, disconnect switches


Remote operators

Circuit-breakers, disconnect switches


Remote operators
Moeller SK1230-1157EN-NA

For use with

Rated control voltage

Part no.
Article no.
when ordered separately

Price
see price
list

Std. pack

Moeller SK1230-1157EN-NA
Notes

Us
V
Remote operator
For remote switching of circuit-breakers and disconnect switches.
ON and OFF switching and resetting by means of 2-wire or 3-wire control.
Can be synchronized.
Local switching by hand possible
Lockable in the 0 position of the remote operator with up to 3 padlocks (hasp thickness: 4 8 mm)
NZM2
110 130 V 50/60 Hz
N2
208 240 V 50/60 Hz
380 440 V 50/60 Hz
24 30 V DC
110 130 V DC
220 250 V DC
NZM3
N3

110 130 V 50/60 Hz


208 240 V 50/60 Hz
380 440 V 50/60 Hz
24 30 V DC
110 130 V DC
220 250 V DC

NZM4
N4

48 60 V 50/60 Hz
110 130 V 50/60 Hz
208 240 V 50/60 Hz
380 440 V 50/60 Hz
24 30 V DC
48 60 V DC
110 130 V DC
220 250 V DC

Clamp terminal springloaded clamp


Control circuit terminal springloaded terminals
NZM...-XR...

NZM2-XR110-130AC
259830
NZM2-XR208-240AC
259832
NZM2-XR380-440AC1)
259834
NZM2-XR24-30DC
259836
NZM2-XR110-130DC
259840
NZM2-XR220-250DC
259842

1 off
A standard auxiliary contact (HIN) for the switch position detection is supplied.
3-wire control
L1
(L1+)

70

Terminal 70/71:
Please note during engineering:
Full current flows through the contact during make and break!
RMQ series contact elements can be used for the
NZM2(3,4)-XR... remote operators.

H1
71 72
75

74

N
(L1, L2)

NZM3-XR110-130AC
259848
NZM3-XR208-240AC
259850
NZM3-XR380-440AC1)
259852
NZM3-XR24-30DC
259854
NZM3-XR110-130DC
259858
NZM3-XR220-250DC
259860

2-wire control
L1
(L1+)

Terminal 75:
Ready for activation signal after the cover is closed and
not locked.
AC-15: 400 V; 2 A
DC-13: 220 V; 0.2 A

0 I

H1
70

71 72
75
74

N
(L1, L2)

3-wire control with automatic reset to the OFF position after the switch has tripped

NZM4-XR48-60AC
266683
NZM4-XR110-130AC
266684
NZM4-XR208-240AC
266685
NZM4-XR380-440AC1)
266686
NZM4-XR24-30DC
266691
NZM4-XR48-60DC
266692
NZM4-XR110-130DC
266693
NZM4-XR220-250DC
266694

L1
(L1+)

H1

HIA

70

71 72
75
74

N
(L1, L2)

Switching cycle:
NZM2-XR
60 ms
OFF

ON

ON

t>3s

60 ms
OFF

OFF

ON

NZM3-XR
80 ms

NZM-XRC
266696

1 off

OFF

ON

ON

t>3s

80 ms
OFF

OFF

ON

NZM4-XR
100 ms
OFF

ON

ON

t>3s
OFF

100 ms
OFF

ON

The time interval between OFF and ON is 3 seconds.


On commands received during the time interval are ignored within the first 3 seconds after switch off.

Notes

1) Not

UL/CSA approved.

For Immediate Delivery call KMParts.com at (866) 595-9616

63

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

62

SK1157_062-063_b_G.fm Page 62 Thursday, June 8, 2006 3:55 PM

Circuit-breakers, disconnect switches


Remote operators

Circuit-breakers, disconnect switches


Remote operators
Moeller SK1230-1157EN-NA

For use with

Rated control voltage

Part no.
Article no.
when ordered separately

Price
see price
list

Std. pack

Moeller SK1230-1157EN-NA
Notes

Us
V
Remote operator
For remote switching of circuit-breakers and disconnect switches.
ON and OFF switching and resetting by means of 2-wire or 3-wire control.
Can be synchronized.
Local switching by hand possible
Lockable in the 0 position of the remote operator with up to 3 padlocks (hasp thickness: 4 8 mm)
NZM2
110 130 V 50/60 Hz
N2
208 240 V 50/60 Hz
380 440 V 50/60 Hz
24 30 V DC
110 130 V DC
220 250 V DC
NZM3
N3

110 130 V 50/60 Hz


208 240 V 50/60 Hz
380 440 V 50/60 Hz
24 30 V DC
110 130 V DC
220 250 V DC

NZM4
N4

48 60 V 50/60 Hz
110 130 V 50/60 Hz
208 240 V 50/60 Hz
380 440 V 50/60 Hz
24 30 V DC
48 60 V DC
110 130 V DC
220 250 V DC

Clamp terminal springloaded clamp


Control circuit terminal springloaded terminals
NZM...-XR...

NZM2-XR110-130AC
259830
NZM2-XR208-240AC
259832
NZM2-XR380-440AC1)
259834
NZM2-XR24-30DC
259836
NZM2-XR110-130DC
259840
NZM2-XR220-250DC
259842

1 off
A standard auxiliary contact (HIN) for the switch position detection is supplied.
3-wire control
L1
(L1+)

70

Terminal 70/71:
Please note during engineering:
Full current flows through the contact during make and break!
RMQ series contact elements can be used for the
NZM2(3,4)-XR... remote operators.

H1
71 72
75

74

N
(L1, L2)

NZM3-XR110-130AC
259848
NZM3-XR208-240AC
259850
NZM3-XR380-440AC1)
259852
NZM3-XR24-30DC
259854
NZM3-XR110-130DC
259858
NZM3-XR220-250DC
259860

2-wire control
L1
(L1+)

Terminal 75:
Ready for activation signal after the cover is closed and
not locked.
AC-15: 400 V; 2 A
DC-13: 220 V; 0.2 A

0 I

H1
70

71 72
75
74

N
(L1, L2)

3-wire control with automatic reset to the OFF position after the switch has tripped

NZM4-XR48-60AC
266683
NZM4-XR110-130AC
266684
NZM4-XR208-240AC
266685
NZM4-XR380-440AC1)
266686
NZM4-XR24-30DC
266691
NZM4-XR48-60DC
266692
NZM4-XR110-130DC
266693
NZM4-XR220-250DC
266694

L1
(L1+)

H1

HIA

70

71 72
75
74

N
(L1, L2)

Switching cycle:
NZM2-XR
60 ms
OFF

ON

ON

t>3s

60 ms
OFF

OFF

ON

NZM3-XR
80 ms

NZM-XRC
266696

1 off

OFF

ON

ON

t>3s

80 ms
OFF

OFF

ON

NZM4-XR
100 ms
OFF

ON

ON

t>3s
OFF

100 ms
OFF

ON

The time interval between OFF and ON is 3 seconds.


On commands received during the time interval are ignored within the first 3 seconds after switch off.

Notes

1) Not

63

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

62

UL/CSA approved.

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_064-065_b_G.fm Page 64 Thursday, May 4, 2006 6:22 PM

Circuit-breakers, disconnect switches


up to 1200 A

64

Circuit-breakers, disconnect switches


Plug-in units
Moeller SK1230-1157EN-NA
For use with

Number of poles

Part no.
Article no.
when ordered
with basic unit

Price
see price
list

Part no.
Article no.
when ordered
separately

Price
see price
list

Std. pack

Notes

1 off

Inmax. at:
20 C: 250 A
40 C: 230 A (NZM...2-...)
250 A (NZM...2-E...)
Mounting position:
vertical, 90 right, 90 left
Order control circuit plug
unit separately!

Plug-in units
For circuit-breakers NZM and disconnect switches N
not UL/CSA approved
Plug-in adapter elements
Complete
Only in combination with circuit-breaker
NZM2
3 pole
N2

+NZM2-XSV
266697

Sockets
e.g. for reserved slots
Retrofit of circuit-breaker with plug-in module.
NZM2
3 pole
N2

Removable module
Fits socket base
Only in combination with circuit-breaker
NZM2
3 pole
N2

Control circuit plug unit


NZM2
N2
NZM2
N2

for auxiliary contact,


shunt/undervoltage
for remote operator

NZM2-XSVS
266699

+NZM2-XSVE
266701

1 off

1 off

NZM2-XSVHI
266705
NZM2-XSVR
266706

1 off

1 off

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_064-065_b_G.fm Page 65 Thursday, May 4, 2006 6:22 PM

Moeller SK1230-1157EN-NA
For use with Number Part no.
of poles Article no. when
ordered with
basic unit

Price
see price
list

Part no.
Article no. when
ordered
separately

Price
see price
list

Std. pack

Notes

1 off

Inmax. at:
20 C: 605 A (NZM3), 1600 A
(NZM4)
40 C: 550 A (NZM3), 1500 A
(NZM4)
Mounting position:
NZM3: vertical, 90 left
NZM4: vertical, 3 positions
Connected, test, disconnected
The 3 positions are indicated
mechanically.

Withdrawable unit with control circuit


plug unit
For circuit-breakers NZM and
disconnect switches N
not UL/CSA approved
Withdrawable unit with auxiliary plug-in
adapter
Complete
Only in combination with circuit-breaker
NZM3
3 pole
N3
NZM4
3 pole
N4

+NZM3-XAV
266707
+NZM4-XAV
266709

Socket base
e.g. for reserved slots
Retrofit of circuit-breaker with withdrawable
carrier.
NZM3
3 pole
N3
NZM4
3 pole
N4

NZM3-XAVS
266711
NZM4-XAVS
266713

1 off

Additionally, auxiliary contacts are


use for remote signalling. An
optional M22-(C)K01 N/C contact or
M22-(C)K10 N/O contact per
position.
Also see the RMQ-Titan control
circuit device range.
All connections of auxiliary
switches (HIA, HIN, HIV) and
undervoltage and shunt releases to
the control circuit plug units are
already present.
Cannot be combined with
NZM4/NZM14 (NZM4-XSAS14-...)
or N(ZM)4/N(ZM)12 adapter kits.

Withdrawable carrier
Not UL/CSA approved.
NZM3
N3
NZM4
N4

3 pole
3 pole

+NZM3-XAVE
266715
+NZM4-XAVE
266717

1 off

For Immediate Delivery call KMParts.com at (866) 595-9616

65

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


Plug-in units

SK1157_066-069_b_G.fm Page 66 Thursday, May 4, 2006 9:35 AM

Circuit-breakers, disconnect switches


NZM1 terminals
Moeller SK1230-1157EN-NA

Max. cable connection

For use with

Terminal capacities
Type of conductor

Terminal capacities

AWG/kcmil

mm2

Moeller SK1230-1157EN-NA
Terminal capacities
Cu strip
(number of segments x
width x segment thickness)
mm

Copper busbar
width x
thickness
mm

Part no.
Article no.
when ordered
separately

Price
see price
list

Std. pack

Notes

NZM1-XKC
260015

1 off

Standard connection with all switches NZM1, and N(S)1.


Conversion kit for circuit-breaker with screw connection.
Type contains parts for a 3 pole switch side.
Fitted within the switch housing

NZM1-XKS
260019

1 off

Type contains parts for a terminal located at top or bottom for


3 pole circuit-breakers.
Fitted outside the switch housing
Mounting of the cover NZM1-XKSA obligatory (supplied).

NZM1-XKA
266730

1 off

Type contains parts for a terminal located at top or bottom for


3 pole circuit-breakers.
A standard with control circuit terminal for 1 x 0.75 2.5 mm2
(18 14 AWG) or 2 x 0.75 1.5 mm2 (18 14 AWG) copper
conductors.
Fitted outside the switch housing
Use with flexible and highly flexible conductors ferrules. Maximum
specified cross-section can only be connected when stranded and
without ferrules.
Mounting of the cover NZM1-XKSA obligatory (supplied).

NZM1-XKR
266734

1 off

Type contains parts for a terminal located at top or bottom for


3 pole circuit-breakers.

Box terminal
Standard equipment
Three pole

Cu cable

1 x 10 701)
2 x 6 25

1 x 8 2/0

NZM1,
N(S)1

Three pole

Copper cable lugs

1 x 10 70
2 x 6 25
1 x 10 35
2 x 10 35

1 x 8 2/0

1 x 6 3/0

10

NZM1,
N(S)1

2 x 9 x 0.8

12

Screw connection

o 6.5

Aluminium
cable lugs

16

min. 12 x 5

Tunnel terminal

NZM1,
N(S)1

Three pole

Copper cablesS
Al cable s S

1 x 16 95

NZM1,
N(S)1

Three pole

Copper cable lugs

1 x 2.5 25
2 x 2.5 25
1 x 10 35
2 x 10 35

Connection on rear
not UL/CSA approved

Notes

1) Up

to 240 mmB can be connected depending on the cable manufacturer.

For Immediate Delivery call KMParts.com at (866) 595-9616

min. 12 x 5
max. 16 x 5

67

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


NZM1 terminals

Circuit-breakers, disconnect switches


up to 1200 A

66

SK1157_066-069_b_G.fm Page 66 Thursday, May 4, 2006 9:35 AM

Circuit-breakers, disconnect switches


NZM1 terminals
Moeller SK1230-1157EN-NA

Max. cable connection

For use with

Terminal capacities
Type of conductor

Terminal capacities

AWG/kcmil

mm2

Moeller SK1230-1157EN-NA
Terminal capacities
Cu strip
(number of segments x
width x segment thickness)
mm

Copper busbar
width x
thickness
mm

Part no.
Article no.
when ordered
separately

Price
see price
list

Std. pack

Notes

NZM1-XKC
260015

1 off

Standard connection with all switches NZM1, and N(S)1.


Conversion kit for circuit-breaker with screw connection.
Type contains parts for a 3 pole switch side.
Fitted within the switch housing

NZM1-XKS
260019

1 off

Type contains parts for a terminal located at top or bottom for


3 pole circuit-breakers.
Fitted outside the switch housing
Mounting of the cover NZM1-XKSA obligatory (supplied).

NZM1-XKA
266730

1 off

Type contains parts for a terminal located at top or bottom for


3 pole circuit-breakers.
A standard with control circuit terminal for 1 x 0.75 2.5 mm2
(18 14 AWG) or 2 x 0.75 1.5 mm2 (18 14 AWG) copper
conductors.
Fitted outside the switch housing
Use with flexible and highly flexible conductors ferrules. Maximum
specified cross-section can only be connected when stranded and
without ferrules.
Mounting of the cover NZM1-XKSA obligatory (supplied).

NZM1-XKR
266734

1 off

Type contains parts for a terminal located at top or bottom for


3 pole circuit-breakers.

Box terminal
Standard equipment
Three pole

Cu cable

1 x 10 701)
2 x 6 25

1 x 8 2/0

NZM1,
N(S)1

Three pole

Copper cable lugs

1 x 10 70
2 x 6 25
1 x 10 35
2 x 10 35

1 x 8 2/0

1 x 6 3/0

10

NZM1,
N(S)1

2 x 9 x 0.8

12

Screw connection

o 6.5

Aluminium
cable lugs

16

min. 12 x 5

Tunnel terminal

NZM1,
N(S)1

Three pole

Copper cablesS
Al cable s S

1 x 16 95

NZM1,
N(S)1

Three pole

Copper cable lugs

1 x 2.5 25
2 x 2.5 25
1 x 10 35
2 x 10 35

Connection on rear
not UL/CSA approved

Notes

1) Up

min. 12 x 5
max. 16 x 5

to 240 mmB can be connected depending on the cable manufacturer.

For Immediate Delivery call KMParts.com at (866) 595-9616

67

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


NZM1 terminals

Circuit-breakers, disconnect switches


up to 1200 A

66

SK1157_066-069_b_G.fm Page 68 Friday, May 5, 2006 4:49 PM

Circuit-breakers, disconnect switches


NZM1 terminals

Circuit-breakers, disconnect switches


NZM1 terminals
Moeller SK1230-1157EN-NA

Max. cable connection

For use with

Terminal capacities
Type of conductor

Terminal capacities

AWG/kcmil

mm2

Moeller SK1230-1157EN-NA
Terminal capacities
Cu strip
(number of segments x
width x segment thickness)
mm

Copper busbar
width x
thickness
mm

Part no.
Article no.
when ordered
separately

Price
see price
list

Std. pack

Notes

NZM1-XSTS
260150

1 off

NZM-XSTK
266739

1 off

Type contains parts for two terminal locations located at top or bottom
for 3 pole circuit-breakers.
Included as standard with tunnel terminal
Degree of protection IP1X
NZM-XSTK cannot be combined with NZM1-XIPK IP2X protection
against contact with a finger.
Height or thickness of the control terminals:
NZM-XSTK = 2 mm
NZM-XSTS = 2 mm

Control circuit terminal

NZM1,
N(S)1

Three- and fourpole

Screw connection

1 x 0.75 2.5
2 x 0.75 1.5

Box terminal

1 x 18 14
2 x 18 16

Cover

NZM1,
N(S)1

3 pole

NZM1-XKSA
260021

1 off

Type contains parts for a terminal located at top or bottom


for 3 pole circuit-breakers.
Protection against direct contact where cable lugs, busbars or tunnel
terminals are used
Contained in kit with tunnel terminals or screw connection terminals.
Degree of protection IP1X on the connection side when using insulated
conductor material.

NZM1, N1

3 pole

NZM1-XKSFA
100780

1 off

Type contains parts for a terminal located at top or bottom


for 3 pole circuit-breakers.
Enhancement of the protection against direct contact (simplified
protection against contact with a finger).
Cannot be combined with NZM-XSTK control circuit terminal.

NZM1,
N1
NZM1,
N1

3 pole

NZM1-XIPK
266744

1 off

Type contains parts for a terminal located at top or bottom


for 3 pole circuit-breakers.
Enhancement of the protection against direct contact to IP2X.
Protection when reaching into the cable connection area with the
connection of cables in the box terminal.
Cannot be combined with NZM-XSTK control circuit terminal.

NZM1, NS1

3 pole

NZM1-XIPA
266748

1 off

Type contains parts for a terminal located at top or bottom


for 3 pole circuit-breakers.
Enhancement of the protection against direct contact to IP2X.

Connection cover, knockout


For box terminals

NZM1,
N1
IP2X protection against contact with a finger
For box terminals

For cover NZM1-XKSA or NZM1...(C)NA, N(S)1...NA

For Immediate Delivery call KMParts.com at (866) 595-9616

69

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

68

SK1157_066-069_b_G.fm Page 68 Friday, May 5, 2006 4:49 PM

Circuit-breakers, disconnect switches


NZM1 terminals

Circuit-breakers, disconnect switches


NZM1 terminals
Moeller SK1230-1157EN-NA

Max. cable connection

For use with

Terminal capacities
Type of conductor

Terminal capacities

AWG/kcmil

mm2

Moeller SK1230-1157EN-NA
Terminal capacities
Cu strip
(number of segments x
width x segment thickness)
mm

Copper busbar
width x
thickness
mm

Part no.
Article no.
when ordered
separately

Price
see price
list

Std. pack

Notes

NZM1-XSTS
260150

1 off

NZM-XSTK
266739

1 off

Type contains parts for two terminal locations located at top or bottom
for 3 pole circuit-breakers.
Included as standard with tunnel terminal
Degree of protection IP1X
NZM-XSTK cannot be combined with NZM1-XIPK IP2X protection
against contact with a finger.
Height or thickness of the control terminals:
NZM-XSTK = 2 mm
NZM-XSTS = 2 mm

Control circuit terminal

NZM1,
N(S)1

Three- and fourpole

Screw connection

Box terminal

1 x 0.75 2.5
2 x 0.75 1.5

1 x 18 14
2 x 18 16

Cover

NZM1,
N(S)1

3 pole

NZM1-XKSA
260021

1 off

Type contains parts for a terminal located at top or bottom


for 3 pole circuit-breakers.
Protection against direct contact where cable lugs, busbars or tunnel
terminals are used
Contained in kit with tunnel terminals or screw connection terminals.
Degree of protection IP1X on the connection side when using insulated
conductor material.

NZM1, N1

3 pole

NZM1-XKSFA
100780

1 off

Type contains parts for a terminal located at top or bottom


for 3 pole circuit-breakers.
Enhancement of the protection against direct contact (simplified
protection against contact with a finger).
Cannot be combined with NZM-XSTK control circuit terminal.

NZM1,
N1
NZM1,
N1

3 pole

NZM1-XIPK
266744

1 off

Type contains parts for a terminal located at top or bottom


for 3 pole circuit-breakers.
Enhancement of the protection against direct contact to IP2X.
Protection when reaching into the cable connection area with the
connection of cables in the box terminal.
Cannot be combined with NZM-XSTK control circuit terminal.

NZM1, NS1

3 pole

NZM1-XIPA
266748

1 off

Type contains parts for a terminal located at top or bottom


for 3 pole circuit-breakers.
Enhancement of the protection against direct contact to IP2X.

Connection cover, knockout


For box terminals

NZM1,
N1
IP2X protection against contact with a finger
For box terminals

For cover NZM1-XKSA or NZM1...(C)NA, N(S)1...NA

For Immediate Delivery call KMParts.com at (866) 595-9616

69

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

68

SK1157_070-073_b_G.fm Page 70 Thursday, May 4, 2006 6:25 PM

Circuit-breakers, disconnect switches


NZM2 terminals
Moeller SK1230-1157EN-NA

Max. cable connection


area

For use with

Terminal capacities
Type of conductor Terminal
capacities

AWG/kcmil

mm2

Terminal capacities
Cu strip (number of
segments x width x
segment thickness)
mm

Moeller SK1230-1157EN-NA
Part no.
Copper busbar Article no.
when ordered with
width x
basic unit
thickness
mm

Price
see price
list

Part no.
Article no.
when ordered
separately

Price
see price
list

Std.

Notes

1 off

Type suffix and type contain parts for a circuit-breaker side at top
or bottom for 3 pole circuit-breakers.
Conversion kit for circuit-breaker with screw connection.
Fitted within the switch housing
O = for fitting at the top
U = for fitting at the bottom
Ue f 525 V AC:
Use cover NZM2-XKSA.

NZM2-XKS
260030

1 off

Type contains parts for a terminal located at top or bottom for


3 pole circuit-breakers.
Standard connection with all NZM2 and N2 circuit-breakers.
Conversion kit for circuit-breaker with box terminal.
Use special cable lug narrow version, a 101
Fitted within the switch housing
If a busbar is used its insulation (400 mm) e.g. by heat-shrink and
a shroud NZM2-XKSA are necessary.
Ue f 525 V AC:
On all other connection types a shroud NZM2-XKSA should be
used.

NZM2-XKA
271457

1 off

Type contains parts for a terminal located at top or bottom for


3 pole circuit-breakers.
A standard with control circuit terminal for 1 x 0.75 2.5 mm2
(18 14 AWG) or 2 x 0.75 1.5 mm2 (18 16 AWG) copper
conductors.
Fitted outside the switch housing
Use with flexible and highly flexible conductors ferrules.
Maximum specified cross-section can only be connected when
stranded and without ferrules.
Mounting of the cover NZM2-XKSA obligatory (supplied).

NZM2-XKR
266765

1 off

Type suffix and type contain parts for a circuit-breaker side at top
or bottom for 3 pole circuit-breakers.
O = for fitting at the top
U = for fitting at the bottom

Box terminal
Three
pole

15

NZM2,
N(S)2

Copper
conductors
Cu cable

1 x 4 185
2 x 4 70

1 x 11 350

+NZM2-160-XKCO
262218
+NZM2-160-XKCU
262223
+NZM2-250-XKCO
262242
+NZM2-250-XKCU
262243

f 2 x 9 x 0.8

18

NZM2-160-XKC
262240

NZM2-250-XKC
262244

Screw connection
NZM2,
N(S)2
o 8.5

Three
pole

Copper cable lugs


Aluminium
cable lugs.

1 x 4 185
2 x 4 70
1 x 10 50
2 x 10 50

1 x 11 3/0

1 x 6 350

f 2 x 16 x 0.8

f 16 x 5

24

Tunnel terminal
Three
pole

Copper cablesS
Copper cablesS

1 x 16 1851)

not UL/CSA approved


When using cable lugs without NZM3-XKSA cover, they must be insulated.

NZM2,
Three
N2
pole

Copper cable lugs

1 x 4 185
2 x 4 70
1 x 10 50
2 x 10 50

NZM2,
N(S)2

Connection on rear

Aluminium
cable lugs.

Notes

1) Up

to 240 mmB can be connected depending on the cable manufacturer.

For Immediate Delivery call KMParts.com at (866) 595-9616

min. 2 x 16 x 0.8
max. 6 x 24 x 0.5

Min. 16 x 5
Max. 20 x 5

+NZM2-XKRO
266763
+NZM2-XKRU
266764

71

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


NZM2 terminals

Circuit-breakers, disconnect switches


up to 1200 A

70

SK1157_070-073_b_G.fm Page 70 Thursday, May 4, 2006 6:25 PM

Circuit-breakers, disconnect switches


NZM2 terminals
Moeller SK1230-1157EN-NA

Max. cable connection


area

For use with

Terminal capacities
Type of conductor Terminal
capacities

AWG/kcmil

mm2

Terminal capacities
Cu strip (number of
segments x width x
segment thickness)
mm

Moeller SK1230-1157EN-NA
Part no.
Copper busbar Article no.
when ordered with
width x
basic unit
thickness
mm

Price
see price
list

Part no.
Article no.
when ordered
separately

Price
see price
list

Std.

Notes

1 off

Type suffix and type contain parts for a circuit-breaker side at top
or bottom for 3 pole circuit-breakers.
Conversion kit for circuit-breaker with screw connection.
Fitted within the switch housing
O = for fitting at the top
U = for fitting at the bottom
Ue f 525 V AC:
Use cover NZM2-XKSA.

NZM2-XKS
260030

1 off

Type contains parts for a terminal located at top or bottom for


3 pole circuit-breakers.
Standard connection with all NZM2 and N2 circuit-breakers.
Conversion kit for circuit-breaker with box terminal.
Use special cable lug narrow version, a 101
Fitted within the switch housing
If a busbar is used its insulation (400 mm) e.g. by heat-shrink and
a shroud NZM2-XKSA are necessary.
Ue f 525 V AC:
On all other connection types a shroud NZM2-XKSA should be
used.

NZM2-XKA
271457

1 off

Type contains parts for a terminal located at top or bottom for


3 pole circuit-breakers.
A standard with control circuit terminal for 1 x 0.75 2.5 mm2
(18 14 AWG) or 2 x 0.75 1.5 mm2 (18 16 AWG) copper
conductors.
Fitted outside the switch housing
Use with flexible and highly flexible conductors ferrules.
Maximum specified cross-section can only be connected when
stranded and without ferrules.
Mounting of the cover NZM2-XKSA obligatory (supplied).

NZM2-XKR
266765

1 off

Type suffix and type contain parts for a circuit-breaker side at top
or bottom for 3 pole circuit-breakers.
O = for fitting at the top
U = for fitting at the bottom

Box terminal
Three
pole

15

NZM2,
N(S)2

Copper
conductors
Cu cable

1 x 4 185
2 x 4 70

1 x 11 350

+NZM2-160-XKCO
262218
+NZM2-160-XKCU
262223
+NZM2-250-XKCO
262242
+NZM2-250-XKCU
262243

f 2 x 9 x 0.8

18

NZM2-160-XKC
262240

NZM2-250-XKC
262244

Screw connection
NZM2,
N(S)2
o 8.5

Three
pole

Copper cable lugs


Aluminium
cable lugs.

1 x 4 185
2 x 4 70
1 x 10 50
2 x 10 50

1 x 11 3/0

1 x 6 350

f 2 x 16 x 0.8

f 16 x 5

24

Tunnel terminal
Three
pole

Copper cablesS
Copper cablesS

1 x 16 1851)

not UL/CSA approved


When using cable lugs without NZM3-XKSA cover, they must be insulated.

NZM2,
Three
N2
pole

Copper cable lugs

1 x 4 185
2 x 4 70
1 x 10 50
2 x 10 50

NZM2,
N(S)2

Connection on rear

Aluminium
cable lugs.

min. 2 x 16 x 0.8
max. 6 x 24 x 0.5

Min. 16 x 5
Max. 20 x 5

+NZM2-XKRO
266763
+NZM2-XKRU
266764

Notes

1) Up

to 240 mmB can be connected depending on the cable manufacturer.

For Immediate Delivery call KMParts.com at (866) 595-9616

71

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


NZM2 terminals

Circuit-breakers, disconnect switches


up to 1200 A

70

SK1157_070-073_b_G.fm Page 72 Thursday, May 4, 2006 6:26 PM

Circuit-breakers, disconnect switches


NZM2 terminals

Circuit-breakers, disconnect switches


NZM2 terminals
Moeller SK1230-1157EN-NA

Max. cable
connection area

For use with

Terminal capacities
Type of conductor

Terminal
capacities

AWG/kcmil

mm2

73

Moeller SK1230-1157EN-NA
Terminal capacities
Cu strip (number of
segments x width x
segment thickness)
mm

Copper busbar
width x
thickness
mm

Part no.
Article no.
when ordered with
basic unit

Price
see price
list

Part no.
Article no.
when ordered
separately

Price
see price
list

Std. pack Notes

Control circuit terminal

NZM2, N(S)2

Three
pole

Screw connection

1 x 0.75 2.5
2 x 0.75 1.5

1 x 18 14
2 x 18 16

NZM2-XSTS
260156

1 off

Type contains parts for two terminal


locations located at top or bottom for
3 pole circuit-breakers.
Included as standard with tunnel terminal
Degree of protection IP1X
NZM-XSTK cannot be combined with
NZM2-XIPK IP2X protection against
contact with a finger.
Height or thickness of the control circuit
terminals:
NZM-XSTK = 2 mm
NZM-XSTS = 2 mm

NZM2,
N(S)2

Three
pole

Box terminal

1 x 0.75 2.5
2 x 0.75 1.5

1 x 18 14
2 x 18 16

NZM-XSTK
266739

1 off

NZM2, NS2

3 pole

NZM2-XKSA
260038

1 off

Type contains parts for a terminal located


at top or bottom for 3 pole circuit-breakers.
Protection against direct contact where
cable lugs, busbars or tunnel terminals are
used
Degree of protection IP1X on the
connection side when using insulated
conductor material.

Connection cover, knockout

NZM2, N(S)2

3 pole

NZM2-XKSFA
104640

1 off

Type contains parts for a terminal located


at top or bottom for 3 pole circuit-breakers.
Enhancement of the protection against
direct contact (simplified protection against
contact with a finger).

NZM2, N(S)2

3 pole

NZM2-XIPK
266773

1 off

Type contains parts for a terminal located


at top or bottom for 3 pole circuit-breakers.
Enhancement of the protection against
direct contact to IP2X.
Protection when reaching into the cable
connection area with the connection of
cables in the box terminal.
With 2 conductors minimum cross-section
25 mm2 or AWG4.
Cannot be combined with NZM-XSTK
control circuit terminal.

NZM2, N(S)2

3-pole

NZM2-XIPA
266777

1 off

Type contains parts for a terminal located


at top or bottom for 3 pole circuit-breakers.
Enhancement of the protection against
direct contact to IP2X.
When mounting NZM2-..-(C)NA or
NZM...-NA the following applies:
With 2 conductors minimum cross-section
25 mm2 or AWG4.

Three
pole

KS95-NZM7
059775
KS120-NZM7
059776
KS150-NZM7
059777
NZM2-XKS185
260032

3 off

Type contains a cable lug for 3 pole


switches.
Special cable lug, narrow style

Cover

IP2X protection against


For box terminals

For covers NZM2-XKSA or NZM2 or NZM2...(C)NA and N(S)2...NA

Copper cable lug


not UL/CSA approved
When using cable lugs without NZM2-XKSA cover, they must be insulated.

95 mm2

120 mm2

150 mm2

185 mm2

NZM2,
N2

For Immediate Delivery call KMParts.com at (866) 595-9616

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

72

SK1157_070-073_b_G.fm Page 72 Thursday, May 4, 2006 6:26 PM

Circuit-breakers, disconnect switches


NZM2 terminals

Circuit-breakers, disconnect switches


NZM2 terminals
Moeller SK1230-1157EN-NA

Max. cable
connection area

For use with

Terminal capacities
Type of conductor

Terminal
capacities

AWG/kcmil

mm2

73

Moeller SK1230-1157EN-NA
Terminal capacities
Cu strip (number of
segments x width x
segment thickness)
mm

Copper busbar
width x
thickness
mm

Part no.
Article no.
when ordered with
basic unit

Price
see price
list

Part no.
Article no.
when ordered
separately

Price
see price
list

Std. pack Notes

Control circuit terminal

NZM2, N(S)2

Three
pole

Screw connection

1 x 0.75 2.5
2 x 0.75 1.5

1 x 18 14
2 x 18 16

NZM2-XSTS
260156

1 off

Type contains parts for two terminal


locations located at top or bottom for
3 pole circuit-breakers.
Included as standard with tunnel terminal
Degree of protection IP1X
NZM-XSTK cannot be combined with
NZM2-XIPK IP2X protection against
contact with a finger.
Height or thickness of the control circuit
terminals:
NZM-XSTK = 2 mm
NZM-XSTS = 2 mm

NZM2,
N(S)2

Three
pole

Box terminal

1 x 0.75 2.5
2 x 0.75 1.5

1 x 18 14
2 x 18 16

NZM-XSTK
266739

1 off

NZM2, NS2

3 pole

NZM2-XKSA
260038

1 off

Type contains parts for a terminal located


at top or bottom for 3 pole circuit-breakers.
Protection against direct contact where
cable lugs, busbars or tunnel terminals are
used
Degree of protection IP1X on the
connection side when using insulated
conductor material.

Connection cover, knockout

NZM2, N(S)2

3 pole

NZM2-XKSFA
104640

1 off

Type contains parts for a terminal located


at top or bottom for 3 pole circuit-breakers.
Enhancement of the protection against
direct contact (simplified protection against
contact with a finger).

NZM2, N(S)2

3 pole

NZM2-XIPK
266773

1 off

Type contains parts for a terminal located


at top or bottom for 3 pole circuit-breakers.
Enhancement of the protection against
direct contact to IP2X.
Protection when reaching into the cable
connection area with the connection of
cables in the box terminal.
With 2 conductors minimum cross-section
25 mm2 or AWG4.
Cannot be combined with NZM-XSTK
control circuit terminal.

NZM2, N(S)2

3-pole

NZM2-XIPA
266777

1 off

Type contains parts for a terminal located


at top or bottom for 3 pole circuit-breakers.
Enhancement of the protection against
direct contact to IP2X.
When mounting NZM2-..-(C)NA or
NZM...-NA the following applies:
With 2 conductors minimum cross-section
25 mm2 or AWG4.

Three
pole

KS95-NZM7
059775
KS120-NZM7
059776
KS150-NZM7
059777
NZM2-XKS185
260032

3 off

Type contains a cable lug for 3 pole


switches.
Special cable lug, narrow style

Cover

IP2X protection against


For box terminals

For covers NZM2-XKSA or NZM2 or NZM2...(C)NA and N(S)2...NA

Copper cable lug


not UL/CSA approved
When using cable lugs without NZM2-XKSA cover, they must be insulated.

95 mm2

120 mm2

150 mm2

185 mm2

NZM2,
N2

For Immediate Delivery call KMParts.com at (866) 595-9616

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

72

SK1157_074-079_b_G.fm Page 74 Thursday, June 8, 2006 9:49 AM

Circuit-breakers, disconnect switches


NZM3 terminals
Moeller SK1230-1157EN-NA

Max. cable connection

Rated
current1)

For use with

Terminal capacities
Type of conductor Terminal
capacities

In
A

AWG/kcmil

mm2

Moeller SK1230-1157EN-NA
Terminal capacities
Cu strip (number of
segments x width x
segment thickness)

Copper busbar
width x
thickness

mm

mm

Part no.
Article no.
when ordered
with basic unit

Price
see price
list

Part no.
Article no.
when ordered
separately

Price
see price
list

Std. pack

Notes

NZM3-XKC
260042

1 off

Type suffix and type contain parts for a


circuit-breaker side at top or bottom for
3 pole circuit-breakers.
Conversion kit for circuit-breaker with
screw connection.
Fitted within the switch housing
O = for fitting at the top
U = for fitting at the bottom
Ue f 525 V AC:
Use NZM3-XKSA cover.
Use with flexible and highly flexible
conductors ferrules, note the max.
terminal capacity when using ferrules.

Box terminal
Max. 500
400 UL/CSA

NZM3,
N(S)3

Three
pole

Copper
conductors
Cu cable

1 x 35 240
2 x 16 120

1 x 2 500

Max. 630

25

min. 6 x 16 x 0.8
max. 20 x 24 x 0.5
max. 11 x 21 x 1

+NZM3-XKCO
262246

10 x 24 x 1.0
+ 5 x 24 x 1.0 or
(2 x) 8 x 24 x 1.0

+NZM3-XKCU
262245

Screw connection
15

Max. 630

NZM3,
N(S)3

Three
pole

Max. 400
o 10.5

Copper cable lugs

1 x 4 350

10 x 32 x 1.0
+ 5 x 32 x 1.0

30 x 10
+ 30 x 5

NZM3-XKS
260039

1 off

Aluminium
cable lugs

1 x 16 240
2 x 16 240
1 x 10 120
2 x 10 120

Type contains parts for a terminal located


at top or bottom for 3 pole circuitbreakers.
Standard connection with all NZM3, and
N3 circuit-breakers.
Conversion kit for circuit-breaker with
box terminal.
Use special cable lugs narrow version,
a 73
Fitted within the switch housing
When a busbar is used insulation is
required (400 mm) e.g. using heat shrink
and a shroud NZM3-XKSA.
Ue f 525 V AC:
A shroud NZM3-XKSA must be used with
all other connection types.

Copper cable lugs

2 x 300

2 x 500

(2 x) 10 x 50 x 1.0

(2 x) 10 x 50

NZM3-XKV70
100514

1 off

Type contains parts for a terminal located


at top or bottom for 3 pole circuitbreakers.
Central holes, e.g. for up to 2 cable lugs
per phase.
Can be fitted to circuit-breaker with
screw termination
Phase isolator supplied.
Distance between pole centres with
NZM3-XKV70: 70 mm
Drilled hole available for control cable.
Terminals NZM3-XK300 and
NZM3-XK22X21 can be mounted.

32

Connection width extension


Max. 630

NZM3,
N(S)3

Three
pole

Aluminium
cable lugs

Notes

1) The

following applies for the rated current: The values have been determined conform to IEC 60947 (switchgear standard) and
generally relate to the max. defined cross-sections and are intended for the purpose of orientation.
The engineering standards which apply in each case must be observed.

For Immediate Delivery call KMParts.com at (866) 595-9616

75

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


NZM3 terminals

16

Circuit-breakers, disconnect switches


up to 1200 A

74

SK1157_074-079_b_G.fm Page 74 Thursday, June 8, 2006 9:49 AM

Circuit-breakers, disconnect switches


NZM3 terminals
Moeller SK1230-1157EN-NA

Max. cable connection

Rated
current1)

For use with

Terminal capacities
Type of conductor Terminal
capacities

In
A

AWG/kcmil

mm2

Moeller SK1230-1157EN-NA
Terminal capacities
Cu strip (number of
segments x width x
segment thickness)

Copper busbar
width x
thickness

mm

mm

Part no.
Article no.
when ordered
with basic unit

Price
see price
list

Part no.
Article no.
when ordered
separately

Price
see price
list

Std. pack

Notes

NZM3-XKC
260042

1 off

Type suffix and type contain parts for a


circuit-breaker side at top or bottom for
3 pole circuit-breakers.
Conversion kit for circuit-breaker with
screw connection.
Fitted within the switch housing
O = for fitting at the top
U = for fitting at the bottom
Ue f 525 V AC:
Use NZM3-XKSA cover.
Use with flexible and highly flexible
conductors ferrules, note the max.
terminal capacity when using ferrules.

Box terminal
Max. 500
400 UL/CSA

NZM3,
N(S)3

Three
pole

Copper
conductors
Cu cable

1 x 35 240
2 x 16 120

1 x 2 500

Max. 630

25

min. 6 x 16 x 0.8
max. 20 x 24 x 0.5
max. 11 x 21 x 1

+NZM3-XKCO
262246

10 x 24 x 1.0
+ 5 x 24 x 1.0 or
(2 x) 8 x 24 x 1.0

+NZM3-XKCU
262245

Screw connection
15

Max. 630

NZM3,
N(S)3

Three
pole

Max. 400
o 10.5

Copper cable lugs

1 x 4 350

10 x 32 x 1.0
+ 5 x 32 x 1.0

30 x 10
+ 30 x 5

NZM3-XKS
260039

1 off

Aluminium
cable lugs

1 x 16 240
2 x 16 240
1 x 10 120
2 x 10 120

Type contains parts for a terminal located


at top or bottom for 3 pole circuitbreakers.
Standard connection with all NZM3, and
N3 circuit-breakers.
Conversion kit for circuit-breaker with
box terminal.
Use special cable lugs narrow version,
a 73
Fitted within the switch housing
When a busbar is used insulation is
required (400 mm) e.g. using heat shrink
and a shroud NZM3-XKSA.
Ue f 525 V AC:
A shroud NZM3-XKSA must be used with
all other connection types.

Copper cable lugs

2 x 300

2 x 500

(2 x) 10 x 50 x 1.0

(2 x) 10 x 50

NZM3-XKV70
100514

1 off

Type contains parts for a terminal located


at top or bottom for 3 pole circuitbreakers.
Central holes, e.g. for up to 2 cable lugs
per phase.
Can be fitted to circuit-breaker with
screw termination
Phase isolator supplied.
Distance between pole centres with
NZM3-XKV70: 70 mm
Drilled hole available for control cable.
Terminals NZM3-XK300 and
NZM3-XK22X21 can be mounted.

32

Connection width extension


Max. 630

NZM3,
N(S)3

Three
pole

Aluminium
cable lugs

Notes

1) The

following applies for the rated current: The values have been determined conform to IEC 60947 (switchgear standard) and
generally relate to the max. defined cross-sections and are intended for the purpose of orientation.
The engineering standards which apply in each case must be observed.

For Immediate Delivery call KMParts.com at (866) 595-9616

75

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


NZM3 terminals

16

Circuit-breakers, disconnect switches


up to 1200 A

74

SK1157_074-079_b_G.fm Page 76 Thursday, June 8, 2006 9:49 AM

Circuit-breakers, disconnect switches


NZM3 terminals

Circuit-breakers, disconnect switches


NZM3 terminals
Moeller SK1230-1157EN-NA

Max. cable connection

Rated
current1)

For use with

Terminal capacities
Type of conductor Terminal
capacities

In
A

AWG/kcmil

mm2

77

Moeller SK1230-1157EN-NA
Terminal capacities
Cu strip (number of
segments x width x
segment thickness)

Copper busbar
width x
mm

Part no.
Article no.
when ordered
with basic unit

Price
see price
list

Part no.
Article no.
when ordered
separately

Price
see price
list

Std. pack Notes

mm

Terminals for connection width extension


not UL/CSA approved
Max. 500

NZM3, N3

3-pole

Cu cable

1 x 120 300

NZM3-XK300
100782

1 off

Type contains parts for a terminal located


at top or bottom for 3 pole circuit-breakers.
Only in conjunction with connection width
extension NZM3-XKV70.
Use with flexible and highly flexible
conductors ferrules.
Standard with control circuit terminal for
1 x 0.75 2.5 mm2 or 2 x 0.75 1.5 mm2
copper conductors.

1 off

Type contains parts for a terminal located


at top or bottom for 3 pole circuit-breakers.
A standard with control circuit terminal for
1 x 0.75 2.5 mm2 (18 14 AWG) or
2 x 0.75 1.5 mm2 (18 16 AWG) copper
conductors.
Fitted outside the switch housing
Use with flexible and highly flexible
conductors ferrules. Maximum specified
cross-section can only be connected when
stranded and without ferrules.
Mounting of the cover NZM3-XKSA
obligatory (supplied).

NZM3-XKR
266792

1 off

Type suffix and type contain parts for a


circuit-breaker side at top or bottom for
3 pole circuit-breakers.
O = for fitting at the top
U = for fitting at the bottom

NZM-XSTK
266739

1 off

NZM3/4-XSTS
266797

1 off

Type contains parts for two terminal


locations located at top or bottom for 3
pole circuit-breakers.
Included as standard with tunnel terminal
Degree of protection IP1X
NZM-XSTK cannot be combined with
NZM1-XIPK IP2X protection against
contact with a finger.
Height or thickness of the control terminals:
NZM-XSTK = 2 mm
NZM-XSTS = 2 mm

NZM3,
N3
Max. 630

NZM3, N3

3-pole

Max. 350

NZM3,
N(S)3

Three
pole

22 x 21 x 1.0

NZM3-XK22X21
100784

Tunnel terminal

Copper cablesS
Al cable s S

1 x 16 1852)

1 x 6 350

NZM3-XKA1
271459

1 x 50 240
2 x 50 240

1 x 0 500
2 x 0 500

NZM3-XKA2
271461

Max. 630

Connection on rear
not UL/CSA approved

Max. 630

NZM3,
N3

Three
pole

Copper
conductors
Cu cable

1 x 16 240
2 x 16 240

Al conductors
Al cable

1 x 10 120
2 x 10 120

Box terminal

1 x 0.75 2.5
2 x 0.75 1.5

+NZM3-XKRO
266790
+NZM3-XKRU
266791

Max. 500

min.6 x 16 x 0.8
max. 10 x 32 x 1.0

Min. 20 x 5
Max. 30 10

Control circuit terminal

Notes

NZM3,
N(S)3

NZM3,
N(S)3

Three
pole

1 x 18 14
2 x 18 16

Screw connection

1) The following applies for the rated current: The values have been determined conform to IEC 60947 (switchgear standard) and generally relate

to the max. defined cross-sections and are intended for the purpose of orientation.
The engineering standards which apply in each case must be observed.
2) Up to 240 mmB can be connected depending on the cable manufacturer.

For Immediate Delivery call KMParts.com at (866) 595-9616

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

76

SK1157_074-079_b_G.fm Page 76 Thursday, June 8, 2006 9:49 AM

Circuit-breakers, disconnect switches


NZM3 terminals

Circuit-breakers, disconnect switches


NZM3 terminals
Moeller SK1230-1157EN-NA

Max. cable connection

Rated
current1)

For use with

Terminal capacities
Type of conductor Terminal
capacities

In
A

AWG/kcmil

mm2

77

Moeller SK1230-1157EN-NA
Terminal capacities
Cu strip (number of
segments x width x
segment thickness)

Copper busbar
width x
mm

Part no.
Article no.
when ordered
with basic unit

Price
see price
list

Part no.
Article no.
when ordered
separately

Price
see price
list

Std. pack Notes

mm

Terminals for connection width extension


not UL/CSA approved
Max. 500

NZM3, N3

3-pole

Cu cable

1 x 120 300

NZM3-XK300
100782

1 off

Type contains parts for a terminal located


at top or bottom for 3 pole circuit-breakers.
Only in conjunction with connection width
extension NZM3-XKV70.
Use with flexible and highly flexible
conductors ferrules.
Standard with control circuit terminal for
1 x 0.75 2.5 mm2 or 2 x 0.75 1.5 mm2
copper conductors.

1 off

Type contains parts for a terminal located


at top or bottom for 3 pole circuit-breakers.
A standard with control circuit terminal for
1 x 0.75 2.5 mm2 (18 14 AWG) or
2 x 0.75 1.5 mm2 (18 16 AWG) copper
conductors.
Fitted outside the switch housing
Use with flexible and highly flexible
conductors ferrules. Maximum specified
cross-section can only be connected when
stranded and without ferrules.
Mounting of the cover NZM3-XKSA
obligatory (supplied).

NZM3-XKR
266792

1 off

Type suffix and type contain parts for a


circuit-breaker side at top or bottom for
3 pole circuit-breakers.
O = for fitting at the top
U = for fitting at the bottom

NZM-XSTK
266739

1 off

NZM3/4-XSTS
266797

1 off

Type contains parts for two terminal


locations located at top or bottom for 3
pole circuit-breakers.
Included as standard with tunnel terminal
Degree of protection IP1X
NZM-XSTK cannot be combined with
NZM1-XIPK IP2X protection against
contact with a finger.
Height or thickness of the control terminals:
NZM-XSTK = 2 mm
NZM-XSTS = 2 mm

NZM3,
N3
Max. 630

NZM3, N3

3-pole

Max. 350

NZM3,
N(S)3

Three
pole

22 x 21 x 1.0

NZM3-XK22X21
100784

Tunnel terminal

Copper cablesS
Al cable s S

1 x 16 1852)

1 x 6 350

NZM3-XKA1
271459

1 x 50 240
2 x 50 240

1 x 0 500
2 x 0 500

NZM3-XKA2
271461

Max. 630

Connection on rear
not UL/CSA approved

Max. 630

NZM3,
N3

Three
pole

Copper
conductors
Cu cable

1 x 16 240
2 x 16 240

Al conductors
Al cable

1 x 10 120
2 x 10 120

Box terminal

1 x 0.75 2.5
2 x 0.75 1.5

+NZM3-XKRO
266790
+NZM3-XKRU
266791

Max. 500

min.6 x 16 x 0.8
max. 10 x 32 x 1.0

Min. 20 x 5
Max. 30 10

Control circuit terminal

Notes

NZM3,
N(S)3

NZM3,
N(S)3

Three
pole

1 x 18 14
2 x 18 16

Screw connection

1) The following applies for the rated current: The values have been determined conform to IEC 60947 (switchgear standard) and generally relate

to the max. defined cross-sections and are intended for the purpose of orientation.
The engineering standards which apply in each case must be observed.
2) Up to 240 mmB can be connected depending on the cable manufacturer.

For Immediate Delivery call KMParts.com at (866) 595-9616

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

76

SK1157_074-079_b_G.fm Page 78 Thursday, June 8, 2006 9:49 AM

Circuit-breakers, disconnect switches


NZM3 terminals

Circuit-breakers, disconnect switches


NZM3 terminals
Moeller SK1230-1157EN-NA

Max. cable
connection
area

For use with

Terminal capacities
Type of
Terminal
conductor capacities
mm2

AWG/kcmil

Terminal capacities
Cu strip (number of
segments x width x
segment thickness)
mm

Copper busbar
width x
thickness
mm

Moeller SK1230-1157EN-NA
Part no.
Article no.
when ordered with
basic unit

Price
see price
list

Part no.
Article no.
when ordered
separately

Price
see price
list

Std. pack

Notes

Cover

NZM3,
N(S)3

3 pole

NZM3-XKSA
260045

1 off

Type contains parts for a terminal located at top or bottom for


3 pole circuit-breakers.
Insulation/protection against direct contact where cable lugs, busbars or
tunnel terminals are used.
Included in set with tunnel terminals
Degree of protection IP1X on the connection side when using insulated
conductor material.

NZM3,
N(S)3

3 pole

NZM3-XKP
100512

1 off

Type contains parts for a terminal located at top or bottom for


3 pole circuit-breakers.
Included with the connection width extension.
Cannot be combined with the NZM3-XKA tunnel terminal,
NZM3-XKR connection on rear.
Insulation protection where cable lugs, busbars or flat conductor.

NZM3,
N(S)3

3 pole

NZM3-XKSFA
104642

1 off

Type contains parts for a terminal located at top or bottom for


3 pole circuit-breakers.
Enhancement of the protection against direct contact to (simplified
protection against contact with a finger).

NZM3,
N3

3 pole

NZM3-XIPK
266804

1 off

Type contains parts for a terminal located at top or bottom for


3 pole circuit-breakers.
Enhancement of the protection against direct contact to IP2X.
Protection when reaching into the cable connection area with the
connection of cables in the box terminal.
With 2 conductors minimum cross-section 70 mm2 00 or AW00.
Cannot be combined with NZM-XSTK control circuit terminal.

3 pole

NZM3-XIPA
266808

1 off

Type contains parts for a terminal located at top or bottom for


3 pole circuit-breakers.
Enhancement of the protection against direct contact to IP2X.
When mounting NZM3-..-(C)NA or N3...-NA the following applies:
With 2 conductors minimum cross-section 70 mm2 00 or AW00.

NZM3-XKS240
260041
NZM3-XKS185
260040

3 off

Type contains a cable lug for 3 pole switches.


Special cable lug, narrow style

Phase isolator

Connection cover, knockout

IP2X protection against contact with a finger


For box terminals

For cover NZM3-XKSA or NZM3...(C)NA and N(S)3...NA


NZM3,
N(S)3

Copper cable lug


not UL/CSA approved
When using cable lugs without NZM3-XKSA cover, they must be insulated.
185 mm2
NZM3,
Three
N3
pole
NZM4,
240 mm2
N4

For Immediate Delivery call KMParts.com at (866) 595-9616

3 off

79

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

78

SK1157_074-079_b_G.fm Page 78 Thursday, June 8, 2006 9:49 AM

Circuit-breakers, disconnect switches


NZM3 terminals

Circuit-breakers, disconnect switches


NZM3 terminals
Moeller SK1230-1157EN-NA

Max. cable
connection
area

For use with

Terminal capacities
Type of
Terminal
conductor capacities
mm2

AWG/kcmil

Terminal capacities
Cu strip (number of
segments x width x
segment thickness)
mm

Copper busbar
width x
thickness
mm

Moeller SK1230-1157EN-NA
Part no.
Article no.
when ordered with
basic unit

Price
see price
list

Part no.
Article no.
when ordered
separately

Price
see price
list

Std. pack

Notes

Cover

NZM3,
N(S)3

3 pole

NZM3-XKSA
260045

1 off

Type contains parts for a terminal located at top or bottom for


3 pole circuit-breakers.
Insulation/protection against direct contact where cable lugs, busbars or
tunnel terminals are used.
Included in set with tunnel terminals
Degree of protection IP1X on the connection side when using insulated
conductor material.

NZM3,
N(S)3

3 pole

NZM3-XKP
100512

1 off

Type contains parts for a terminal located at top or bottom for


3 pole circuit-breakers.
Included with the connection width extension.
Cannot be combined with the NZM3-XKA tunnel terminal,
NZM3-XKR connection on rear.
Insulation protection where cable lugs, busbars or flat conductor.

NZM3,
N(S)3

3 pole

NZM3-XKSFA
104642

1 off

Type contains parts for a terminal located at top or bottom for


3 pole circuit-breakers.
Enhancement of the protection against direct contact to (simplified
protection against contact with a finger).

NZM3,
N3

3 pole

NZM3-XIPK
266804

1 off

Type contains parts for a terminal located at top or bottom for


3 pole circuit-breakers.
Enhancement of the protection against direct contact to IP2X.
Protection when reaching into the cable connection area with the
connection of cables in the box terminal.
With 2 conductors minimum cross-section 70 mm2 00 or AW00.
Cannot be combined with NZM-XSTK control circuit terminal.

3 pole

NZM3-XIPA
266808

1 off

Type contains parts for a terminal located at top or bottom for


3 pole circuit-breakers.
Enhancement of the protection against direct contact to IP2X.
When mounting NZM3-..-(C)NA or N3...-NA the following applies:
With 2 conductors minimum cross-section 70 mm2 00 or AW00.

NZM3-XKS240
260041
NZM3-XKS185
260040

3 off

Type contains a cable lug for 3 pole switches.


Special cable lug, narrow style

Phase isolator

Connection cover, knockout

IP2X protection against contact with a finger


For box terminals

For cover NZM3-XKSA or NZM3...(C)NA and N(S)3...NA


NZM3,
N(S)3

Copper cable lug


not UL/CSA approved
When using cable lugs without NZM3-XKSA cover, they must be insulated.
185 mm2
NZM3,
Three
N3
pole
NZM4,
240 mm2
N4

3 off

For Immediate Delivery call KMParts.com at (866) 595-9616

79

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

78

SK1157_080-087_b_G.fm Page 80 Thursday, May 4, 2006 9:44 AM

Circuit-breakers, disconnect switches


NZM4 terminals
Moeller SK1230-1157EN-NA

Max. cable connection area

Rated
current 1)

For use with

Terminal capacities
Type of conductor

In
A

Not UL/CSA approved

Moeller SK1230-1157EN-NA
Terminal capacities

Terminal
capacities

AWG/kcmil

mm2

81

Cu strip
Copper busbar
(number of segments x
width x thickness
width x segment thickness)
mm

mm

Part no.
Article no.
when ordered
separately

Price
see price
list

Std. pack

Notes

off

Double hole fitting for M10 screws with 25 mm clearance.


Use special cable lug narrow version.
Ue f 525 V or cross-section > 185 mm2:
Use of shroud NZM4-XKSA required.

1 off

Type contains parts for a terminal located at top or bottom for


3 pole circuit-breakers.
For M10 screws. Can be enlarged for M12 screws.
Use special cable lug narrow version.
Can be fitted to circuit-breaker with screw termination
Insulation through NZM4-XKSA cover or NZM4-XKP phase
separator necessary

Screw connection
Standard equipment
Double
hole

Max. 1250
Max.
o10.5

NZM4
N4
N(S)4

Three
pole

Cu cable lugs

1 x 120 185
4 x 50 185

1 x 250 350
4 x 0 350

2 x (10 x 40 x 1.0)

(2 x) 50 x 10

2 x (10 x 40 x 1.0)
2 x (10 x 50 x 1.0)

(2 x) 40 x 10
(2 x) 50 x 10

o10.5

25
50

Module plate
Single
hole

Max. 1250

NZM4,
N(S)4

3 pole

Copper cable lugs

1 x 120 300
2 x 95 300

1 x 250 600
2 x 000 600

NZM4-XKM1
266814

Double
hole

Max. 1400

NZM4,
N(S)4

3 pole

Copper cable lugs

2 x 95 185
4 x 35 185
4 x 50

2 x 000 350
4 x 2 350
4x0

NZM4-XKM2
266820

Double
hole

Max. 1250

NZM4,
N(S)4

3 pole

Copper cable lugs

2 x 95 300

2 x 000 600

NZM4-XKM2S-1250
284471

Max. 1600

NZM4,
N(S)4

3 pole

Copper cable lugs


Copper cable lugs

Max. 1600

NZM4, N(S)4

3 pole

Cu cable lugs

Type contains parts for a terminal located at top or bottom for


3 pole circuit-breakers.
Insulation through cover NZM4-XKSA or phase isolator NZM4XKP necessary.

NZM4-XKM2S-1600
284473

Connection width extension

Notes

4 x 300
6 x 95 240

1) The

4 x 600
6 x 000 500

following applies for the rated current: The values have been determined conform to IEC/EN 60947 (switchgear standard) and generally relate
to the max. defined cross-sections and are intended for the purpose of orientation.
The engineering standards which apply in each case must be observed.

For Immediate Delivery call KMParts.com at (866) 595-9616

NZM4-XKV95
281591
NZM4-XKV110
281593

1 off

Type contains parts for a terminal located at top or bottom for


3 pole circuit-breakers.
Five way holes, e.g. for up to 9 cable lugs per phase.
Can be fitted to circuit-breaker with screw termination
Phase isolator supplied.
Distance between pole centres with NZM4-XKV95: 95 mm
Installation conditions for current transformer up to 130 mm
width with 80 mm busbar width.
Distance between pole centres with NZM4-XKV110: 107.5 mm
Installation conditions for current transformer up to 135 mm
width with 80 mm busbar width.
Distance between pole centres with NZM4-XKV120: 122 mm
Installation conditions for current transformer up to 164 mm
width with 80 mm busbar width.
4 mm drilled holes for control circuit terminal available.

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


NZM4 terminals

20

Circuit-breakers, disconnect switches


up to 1200 A

80

SK1157_080-087_b_G.fm Page 80 Thursday, May 4, 2006 9:44 AM

Circuit-breakers, disconnect switches


NZM4 terminals
Moeller SK1230-1157EN-NA

Max. cable connection area

Rated
current 1)

For use with

Terminal capacities
Type of conductor

In
A

Not UL/CSA approved

Moeller SK1230-1157EN-NA
Terminal capacities

Terminal
capacities

AWG/kcmil

mm2

81

Cu strip
Copper busbar
(number of segments x
width x thickness
width x segment thickness)
mm

mm

Part no.
Article no.
when ordered
separately

Price
see price
list

Std. pack

Notes

off

Double hole fitting for M10 screws with 25 mm clearance.


Use special cable lug narrow version.
Ue f 525 V or cross-section > 185 mm2:
Use of shroud NZM4-XKSA required.

1 off

Type contains parts for a terminal located at top or bottom for


3 pole circuit-breakers.
For M10 screws. Can be enlarged for M12 screws.
Use special cable lug narrow version.
Can be fitted to circuit-breaker with screw termination
Insulation through NZM4-XKSA cover or NZM4-XKP phase
separator necessary

Screw connection
Standard equipment
Double
hole

Max. 1250
Max.
o10.5

NZM4
N4
N(S)4

Three
pole

Cu cable lugs

1 x 120 185
4 x 50 185

1 x 250 350
4 x 0 350

2 x (10 x 40 x 1.0)

(2 x) 50 x 10

2 x (10 x 40 x 1.0)
2 x (10 x 50 x 1.0)

(2 x) 40 x 10
(2 x) 50 x 10

o10.5

25
50

Module plate
Single
hole

Max. 1250

NZM4,
N(S)4

3 pole

Copper cable lugs

1 x 120 300
2 x 95 300

1 x 250 600
2 x 000 600

NZM4-XKM1
266814

Double
hole

Max. 1400

NZM4,
N(S)4

3 pole

Copper cable lugs

2 x 95 185
4 x 35 185
4 x 50

2 x 000 350
4 x 2 350
4x0

NZM4-XKM2
266820

Double
hole

Max. 1250

NZM4,
N(S)4

3 pole

Copper cable lugs

2 x 95 300

2 x 000 600

NZM4-XKM2S-1250
284471

Max. 1600

NZM4,
N(S)4

3 pole

Copper cable lugs


Copper cable lugs

Max. 1600

NZM4, N(S)4

3 pole

Cu cable lugs

Type contains parts for a terminal located at top or bottom for


3 pole circuit-breakers.
Insulation through cover NZM4-XKSA or phase isolator NZM4XKP necessary.

NZM4-XKM2S-1600
284473

Connection width extension

Notes

4 x 300
6 x 95 240

4 x 600
6 x 000 500

NZM4-XKV95
281591
NZM4-XKV110
281593

1 off

Type contains parts for a terminal located at top or bottom for


3 pole circuit-breakers.
Five way holes, e.g. for up to 9 cable lugs per phase.
Can be fitted to circuit-breaker with screw termination
Phase isolator supplied.
Distance between pole centres with NZM4-XKV95: 95 mm
Installation conditions for current transformer up to 130 mm
width with 80 mm busbar width.
Distance between pole centres with NZM4-XKV110: 107.5 mm
Installation conditions for current transformer up to 135 mm
width with 80 mm busbar width.
Distance between pole centres with NZM4-XKV120: 122 mm
Installation conditions for current transformer up to 164 mm
width with 80 mm busbar width.
4 mm drilled holes for control circuit terminal available.

1) The

following applies for the rated current: The values have been determined conform to IEC/EN 60947 (switchgear standard) and generally relate
to the max. defined cross-sections and are intended for the purpose of orientation.
The engineering standards which apply in each case must be observed.

For Immediate Delivery call KMParts.com at (866) 595-9616

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


NZM4 terminals

20

Circuit-breakers, disconnect switches


up to 1200 A

80

SK1157_080-087_b_G.fm Page 82 Friday, May 12, 2006 4:34 PM

Circuit-breakers, disconnect switches


NZM4 terminals

Circuit-breakers, disconnect switches


NZM4 terminals
Moeller SK1230-1157EN-NA

Max. cable connection area

Rated
current 1)

For use with

Terminal capacities
Type of conductor

In
A

Moeller SK1230-1157EN-NA
Terminal capacities

Terminal
capacities

AWG/kcmil

mm2

83

Cu strip
(number of segments x
width x segment thickness)

Copper busbar
width x thickness

mm

mm

Part no.
Article no.
when ordered
separately

Price
see price
list

Std. pack

Notes

NZM4-XKA

1 off

Type contains parts for a terminal located at top or


bottom for 3 pole circuit-breakers.
A standard with control circuit terminal for
1 x 0.75 2.5 mm2 (18 14 AWG) or 2 x 0.75 1.5 mm2
(18 16 AWG) copper conductors.
Can be fitted to circuit-breaker with screw termination
Use with flexible and highly flexible conductors ferrules.
Mounting of the cover NZM4 -XKSA obligatory (supplied).

NZM4-XKR
266842

1 off

Type contains parts for a terminal located at top or


bottom for 3 pole circuit-breakers.
Can also be retrofitted:
NZM4...-XKM... module plate or NZM4-...-XKV...
connection width extension

Tunnel terminal

Max. 1400

NZM4, N(S)4

3 pole

Copper cablesS
Al cable s S

1 x 50 240
4 x 50 240
1 x 50 240
4 x 50 240

Max. 1250

NZM4,
N4

Three
pole

Copper cable lugs

1 x 120 185
2 x 95 185
4 x 35 185
1 x 185
2 x 70 185
4 x 50 185

1 x 0 500
4 x 0 500

Connection on rear
not UL/CSA approved

Aluminium
cable lugs

Notes

1) See

page 80

For Immediate Delivery call KMParts.com at (866) 595-9616

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

82

SK1157_080-087_b_G.fm Page 82 Friday, May 12, 2006 4:34 PM

Circuit-breakers, disconnect switches


NZM4 terminals

Circuit-breakers, disconnect switches


NZM4 terminals
Moeller SK1230-1157EN-NA

Max. cable connection area

Rated
current 1)

For use with

Terminal capacities
Type of conductor

In
A

Moeller SK1230-1157EN-NA
Terminal capacities

Terminal
capacities

AWG/kcmil

mm2

83

Cu strip
(number of segments x
width x segment thickness)

Copper busbar
width x thickness

mm

mm

Part no.
Article no.
when ordered
separately

Price
see price
list

Std. pack

Notes

NZM4-XKA

1 off

Type contains parts for a terminal located at top or


bottom for 3 pole circuit-breakers.
A standard with control circuit terminal for
1 x 0.75 2.5 mm2 (18 14 AWG) or 2 x 0.75 1.5 mm2
(18 16 AWG) copper conductors.
Can be fitted to circuit-breaker with screw termination
Use with flexible and highly flexible conductors ferrules.
Mounting of the cover NZM4 -XKSA obligatory (supplied).

NZM4-XKR
266842

1 off

Type contains parts for a terminal located at top or


bottom for 3 pole circuit-breakers.
Can also be retrofitted:
NZM4...-XKM... module plate or NZM4-...-XKV...
connection width extension

Tunnel terminal

Max. 1400

NZM4, N(S)4

3 pole

Copper cablesS
Al cable s S

1 x 50 240
4 x 50 240
1 x 50 240
4 x 50 240

Max. 1250

NZM4,
N4

Three
pole

Copper cable lugs

1 x 120 185
2 x 95 185
4 x 35 185
1 x 185
2 x 70 185
4 x 50 185

1 x 0 500
4 x 0 500

Connection on rear
not UL/CSA approved

Aluminium
cable lugs

Notes

1) See

page 80

For Immediate Delivery call KMParts.com at (866) 595-9616

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

82

SK1157_080-087_b_G.fm Page 84 Thursday, May 4, 2006 9:44 AM

Circuit-breakers, disconnect switches


NZM4 terminals

Circuit-breakers, disconnect switches


NZM4 terminals
Moeller SK1230-1157EN-NA

Max. cable connection area

Rated
current 1)

For use with

Terminal capacities
Type of conductor

Moeller SK1230-1157EN-NA
Terminal capacities

Terminal
capacities

AWG/kcmil

Cu strip
(number of segments x
width x segment thickness)

Copper busbar
width x thickness

mm

mm

Part no.
Article no.
when ordered
separately

Price
see price
list

Std. pack

Notes

Kit for conversion of N(ZM)12 to N(ZM)4.


Using the connection lugs of the exchange kit all 3-pole
NZM12 or N12 can be adapted to the connection
dimensions of the NZM4 or N4, which have been
manufactured since 1983.
Non-exchangable are 4-pole base units as well as devices
with withdrawable units and remote operators.

Not UL/CSA approved

In
A

Adapter set N(ZM)4/N(ZM)12

Max. 1000

N4

3 pole

N4-XAS12-1000
285609

1 off

Max. 1250

N4

3 pole

N4-XAS12-1250
285610

1 off

Max. 1600

N4

3 pole

N4-XAS12-1600
285611

1 off

Max. 1000

NZM4

3 pole

NZM4-XAS12-1000
285612

1 off

Scope of the exchange kits N(ZM)4-XAS12...:


3 connection extensions on outlet side
3 connection extensions on trip block side
2 mounting brackets
4 fixing screws
4 phase isolators
6 fixing screws, nuts and washers
Paper drilling template in the assembly instructions (AWA)
The exchange kits have identical dimensions to the types
N(ZM)12..., which correspond to the types manufactured
from 02/97 onwards.

NZM4-XAS12-1250
285613

1 off

Special feature:
The N(ZM)12-800 manufactured before 02/97 features
10 mm connection lugs instead of the 8 mm connections
lugs currently used. With these types the customer must
determine the year of manufacture of the device by
measuring the thickness of the connection lugs and order
the exchange kit N(ZM)4-XAS12-1250.

NZM4-XAS12-1600
285614

1 off

Max. 1250

Notes

mm2

Max. 1600

NZM4

NZM4

3 pole

3 pole

1) The

following applies for the rated current: The values have been determined conform to IEC/EN 60947 (switchgear standard) and generally relate to
the max. defined cross-sections and are intended for the purpose of orientation.
The engineering standards which apply in each case must be observed.

For Immediate Delivery call KMParts.com at (866) 595-9616

Example:
N(ZM)12-800...(1000) > N(ZM)4-XAS12-1000
N(ZM)12-800 before 02/97 > N(ZM)4-XAS12-1250
N(ZM)12-1250 > N(ZM)4-XAS12-1250
N(ZM)12-1600 > N(ZM)4-XAS12-1600
Expansion for devices manufactured before 1983!
The exchange kit for switch-disconnector can be used
completely here. The adapters will only fit on top on the
circuit-breaker with the longer ZM version! The devices
are about 65 mm longer at the bottom and the lower
connection is about 26 mm lower. Accordingly, the
adapters are too short for the bottom and the height does
not correspond either.

85

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

84

SK1157_080-087_b_G.fm Page 84 Thursday, May 4, 2006 9:44 AM

Circuit-breakers, disconnect switches


NZM4 terminals

Circuit-breakers, disconnect switches


NZM4 terminals
Moeller SK1230-1157EN-NA

Max. cable connection area

Rated
current 1)

For use with

Terminal capacities
Type of conductor

Moeller SK1230-1157EN-NA
Terminal capacities

Terminal
capacities

AWG/kcmil

Cu strip
(number of segments x
width x segment thickness)

Copper busbar
width x thickness

mm

mm

Part no.
Article no.
when ordered
separately

Price
see price
list

Std. pack

Notes

Kit for conversion of N(ZM)12 to N(ZM)4.


Using the connection lugs of the exchange kit all 3-pole
NZM12 or N12 can be adapted to the connection
dimensions of the NZM4 or N4, which have been
manufactured since 1983.
Non-exchangable are 4-pole base units as well as devices
with withdrawable units and remote operators.

Not UL/CSA approved

In
A

Adapter set N(ZM)4/N(ZM)12

Max. 1000

N4

3 pole

N4-XAS12-1000
285609

1 off

Max. 1250

N4

3 pole

N4-XAS12-1250
285610

1 off

Max. 1600

N4

3 pole

N4-XAS12-1600
285611

1 off

Max. 1000

NZM4

3 pole

NZM4-XAS12-1000
285612

1 off

Scope of the exchange kits N(ZM)4-XAS12...:


3 connection extensions on outlet side
3 connection extensions on trip block side
2 mounting brackets
4 fixing screws
4 phase isolators
6 fixing screws, nuts and washers
Paper drilling template in the assembly instructions (AWA)
The exchange kits have identical dimensions to the types
N(ZM)12..., which correspond to the types manufactured
from 02/97 onwards.

NZM4-XAS12-1250
285613

1 off

Special feature:
The N(ZM)12-800 manufactured before 02/97 features
10 mm connection lugs instead of the 8 mm connections
lugs currently used. With these types the customer must
determine the year of manufacture of the device by
measuring the thickness of the connection lugs and order
the exchange kit N(ZM)4-XAS12-1250.

NZM4-XAS12-1600
285614

1 off

Max. 1250

Notes

mm2

Max. 1600

NZM4

NZM4

3 pole

3 pole

Example:
N(ZM)12-800...(1000) > N(ZM)4-XAS12-1000
N(ZM)12-800 before 02/97 > N(ZM)4-XAS12-1250
N(ZM)12-1250 > N(ZM)4-XAS12-1250
N(ZM)12-1600 > N(ZM)4-XAS12-1600
Expansion for devices manufactured before 1983!
The exchange kit for switch-disconnector can be used
completely here. The adapters will only fit on top on the
circuit-breaker with the longer ZM version! The devices
are about 65 mm longer at the bottom and the lower
connection is about 26 mm lower. Accordingly, the
adapters are too short for the bottom and the height does
not correspond either.

1) The

following applies for the rated current: The values have been determined conform to IEC/EN 60947 (switchgear standard) and generally relate to
the max. defined cross-sections and are intended for the purpose of orientation.
The engineering standards which apply in each case must be observed.

For Immediate Delivery call KMParts.com at (866) 595-9616

85

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

84

SK1157_080-087_b_G.fm Page 86 Thursday, May 4, 2006 9:44 AM

Circuit-breakers, disconnect switches


NZM4 terminals

Circuit-breakers, disconnect switches


NZM4 terminals
Moeller SK1230-1157EN-NA

Max. cable

For use with

Terminal capacities
Type of conductor

Terminal
capacities

AWG/kcmil

mm2
Control circuit terminal

Moeller SK1230-1157EN-NA
Terminal capacities
Cu strip
(number of segments x
width x segment thickness)
mm

Copper busbar
width x thickness

Part no.
Article no.
when ordered
separately

Price
see price
list

Std. pack

Notes

NZM3/4-XSTS
266797

1 off

Type contains parts for two terminal locations located at


top or bottom for 3 pole circuit-breakers.
Included as standard with tunnel terminal
Degree of protection IP1X
NZM-XSTK cannot be combined with NZM3-XIPK or NZM4XIPK IP2X protection against contact with a finger.
Height or thickness of the control circuit terminals:
NZM-XSTK = 2 mm
NZM-XSTS = 2 mm

mm

NZM3,
N(S)3
NZM4,
N(S)4

Three- and
four-pole

NZM4,
N(S)4

3 pole

NZM4-XKSA
266846

1 off

Type contains parts for a terminal located at top or bottom


for 3 pole circuit-breakers.
Protection against direct contact where cable lugs, busbars,
flat conductor terminals or tunnel terminals are used.
Contained in kit with module plates, flat conductor
terminals and tunnel terminals.
Degree of protection IP4X at front, side and rear, on the
connection side when using insulated conductor material to
IP1X.

NZM4,
N4

3 pole

NZM4-XKSFA
292193

1 off

Type contains parts for a terminal located at top or bottom


for 3 pole circuit-breakers.
Enhancement of the protection against direct contact to
(simplified protection against contact with a finger).

NZM4
N(S)4

3 pole

NZM4-XKP
281595

1 off

Type contains parts for a terminal located at top or bottom


for 3 pole circuit-breakers.
Included with the connection width extension.
Cannot be combined with the tunnel terminal
NZM4-XKA, connection NZM4-XKR on rear.
Insulation protection where cable lugs, busbars, module
plates or flat cable terminals are used.

NZM3,
N3
NZM4,
N4

3 pole

NZM3-XKS185
260040
NZM3-XKS240
260041

3 off

Type contains a cable lug for 3 pole switches.


Special cable lug, narrow style

Screw connection

1 x 0.75 2.5
2 x 0.75 1.5

1 x 18 14
2 x 18 16

Cover

Terminal cover

Phase isolators

Cable lug
not UL/CSA approved
185 mm2
240 mm2

For Immediate Delivery call KMParts.com at (866) 595-9616

87

3 off

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

86

SK1157_080-087_b_G.fm Page 86 Thursday, May 4, 2006 9:44 AM

Circuit-breakers, disconnect switches


NZM4 terminals

Circuit-breakers, disconnect switches


NZM4 terminals
Moeller SK1230-1157EN-NA

Max. cable

For use with

Terminal capacities
Type of conductor

Terminal
capacities

AWG/kcmil

mm2
Control circuit terminal

Moeller SK1230-1157EN-NA
Terminal capacities
Cu strip
(number of segments x
width x segment thickness)
mm

Copper busbar
width x thickness

Part no.
Article no.
when ordered
separately

Price
see price
list

Std. pack

Notes

NZM3/4-XSTS
266797

1 off

Type contains parts for two terminal locations located at


top or bottom for 3 pole circuit-breakers.
Included as standard with tunnel terminal
Degree of protection IP1X
NZM-XSTK cannot be combined with NZM3-XIPK or NZM4XIPK IP2X protection against contact with a finger.
Height or thickness of the control circuit terminals:
NZM-XSTK = 2 mm
NZM-XSTS = 2 mm

mm

NZM3,
N(S)3
NZM4,
N(S)4

Three- and
four-pole

NZM4,
N(S)4

3 pole

NZM4-XKSA
266846

1 off

Type contains parts for a terminal located at top or bottom


for 3 pole circuit-breakers.
Protection against direct contact where cable lugs, busbars,
flat conductor terminals or tunnel terminals are used.
Contained in kit with module plates, flat conductor
terminals and tunnel terminals.
Degree of protection IP4X at front, side and rear, on the
connection side when using insulated conductor material to
IP1X.

NZM4,
N4

3 pole

NZM4-XKSFA
292193

1 off

Type contains parts for a terminal located at top or bottom


for 3 pole circuit-breakers.
Enhancement of the protection against direct contact to
(simplified protection against contact with a finger).

NZM4
N(S)4

3 pole

NZM4-XKP
281595

1 off

Type contains parts for a terminal located at top or bottom


for 3 pole circuit-breakers.
Included with the connection width extension.
Cannot be combined with the tunnel terminal
NZM4-XKA, connection NZM4-XKR on rear.
Insulation protection where cable lugs, busbars, module
plates or flat cable terminals are used.

NZM3,
N3
NZM4,
N4

3 pole

NZM3-XKS185
260040
NZM3-XKS240
260041

3 off

Type contains a cable lug for 3 pole switches.


Special cable lug, narrow style

Screw connection

1 x 0.75 2.5
2 x 0.75 1.5

1 x 18 14
2 x 18 16

Cover

Terminal cover

Phase isolators

Cable lug
not UL/CSA approved
185 mm2
240 mm2

87

3 off

For Immediate Delivery call KMParts.com at (866) 595-9616

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

86

SK1157_088-089_b_G.fm Page 88 Friday, May 5, 2006 4:54 PM

Circuit-breakers, disconnect switches


up to 1200 A

88

Circuit-breakers, disconnect switches


Accessories
Moeller SK1230-1157EN-NA
Description

Diagnostic and configurator software for NZM and DMI (at the machine)
PC software for direct connection to all new NZM circuitbreakers with electronic releases (IEC and UL/CSA
devices) or for direct connection to the DMI module,
including the connection cable.
Protection parameters: Online display and characteristic
representation, export option to Moeller CurveSelect
characteristics program.
Warning and trip messages: Read of the diagnostics
memory even in a no-voltage state.
Load currents: Display and trend representation.
Recording and export feature to MS-Excel for load
currents and diagnostic messages.
Configuration of the DMI: motor starter, remote
operator, assignment of the DMI inputs and outputs and
displays.
Data Management Interface (DMI Module)
Query of diagnostics and operational data, display of
currents, motor starter function, parameterization and
control of the circuit-breaker with electronic release.
Comprehensive remote diagnostic options and remote
operation via fieldbus in combination with fieldbus
connection.
Inclusive NZM-XDMI-CAB connection cable between
NZM and DMI (length: 2 m).
DEL

ESC

Part no.
Article no.

NZM-XPC-KIT
265631

Price

Std. pack

Notes

1 off

Only suitable for use in conjunction


with circuit-breakers having
electronic releases.
Free-of-charge download of the
manual AWB1230-1459 and a
demo software at
www.moeller.net.

NZM-XDMI612
electronic

ALT

OK

Expansion unit, networking

Fieldbus interface: to PROFIBUS-DPV1 slave.


Can be operated with class 1 and class 2 masters.
Addresses available: 1 to 126
Fieldbus connection to CANopen
Addresses available: 1 to 127
Fieldbus connection to DeviceNet
Addresses available: 0 to 63

NZM-XDMI-DPV1
EASY204-DP.

EASY221-CO
1 off
233540

Switched-mode power supply unit


Rated input voltage: 50/60 HZ: 115/230 V AC
Rated output voltage (residual ripple): 24 V DC (g 3 %)
Rated output current: 1.25 A

EASY400-POW

Telescopic adapter
for DMI module
For equalization of the mounting depth when rear mounted in CI-K.. enclosures
and cabinets.
With 35 mm top-hat rail IEC/EN 60715, adjustable from
75 115 mm. Screw-on and snap fitting.

1 off

226161

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_088-089_b_G.fm Page 89 Friday, May 5, 2006 4:55 PM

89

Moeller SK1230-1157EN-NA
Description

Part no.
Article no.

Price
see price
list

Std. pack

Notes

FDT-NAVIGATOR
281623

1 off

The connection of the field devices can be


implemented via the PROFIBUS-DPV1 master
or via gateways (e.g.: USB/PROFIBUS, Ethernet/
PROFIBUS).
Communication interfacing for the PC and a
communication DTM (driver) is necessary for
this purpose. Please inquire.

NZM-XPC-DTM
281624

1 off

For connection of the circuit-breaker to the


PROFIBUS-DP fieldbus, the accessory device
NZM-XDMI-612 and the fieldbus interface
NZM-XDMI-DPV1 are required.

FDT frame software for operating field devices


PC software for integration of software modules (DTM's)
according to the FDT standard V1.2 (e.g. NZM-XPC-DTM).
Operation of a temporary or stationary service station for
engineering, remote diagnostics, remote operation and remote
parameter definition of networked switchgear and field
devices.
Engineering of the network topology of networked field
devices.
Overview representation of the topology with online status
information.
Access to the device specific DTM's for configuration,
operation, parameterization and diagnostics of the devices.
Storage of all engineering information in a central database.
Download and upload from/to the devices.
DTM software module to FTD standard
PC software module (Device Type Manager) to FDT/DTM standard
V1.2 for integration in the FDT navigator or other FDT capable
framework software packages (primary control system, PLC
engineering systems).
Remote diagnostics, remote monitoring, remote parameter
definition and remote operation of the new NZM2,3,4 circuitbreakers with electronic trip release via Profibus-DPV1.
Display of the circuit-breaker state (on/off/tripped), the phase
currents, parameter data, status data and diagnostics data.
Definition of the trip parameters.
Display and setting of the DMI motor starter functions and
assignment of the DMI inputs and outputs.
Control of the motor starter functions.

For Immediate Delivery call KMParts.com at (866) 595-9616

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


Accessories

SK1157_090-090_b_G.fm Page 90 Friday, May 12, 2006 5:55 PM

Circuit-breakers, disconnect switches


up to 1200 A

90

Circuit-breakers, disconnect switches


Insulated terminals
Moeller SK1230-1157EN-NA
Rated
uninterrupted
current
Iu
A

Terminal capacities

Part no.
Article no.
when ordered
separately

Price
see price
list

Std. pack

mm2

Additional insulated terminals


For looping through the neutral and protective conductor
1 pole
32
Flexible, 1 x (1.5 6)
63

Flexible, 1 x (6 16), stranded, 1 x (16 25 )

100

Flexible, 1 x (10 35), stranded, 1 x (16 50)

160

Stranded, 1 x (16 95)

250

Stranded, 1 x (35 150), 2 x (16 70)

400

Stranded, 1 x (50 240), 2 x (25 120)

630

Stranded, 1 x (240 300), 2 x (50 240)

K10/1
093827
K25/1
096200
K50/1
098573

10 off

K95/1N/BR
012336
K150/1/BR
014709
K240/1/BR
017082
K2X240/1/BR
019455

1 off

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_091-094_G_G.fm Page 91 Tuesday, April 25, 2006 11:31 AM

Tripping characteristics
Tripping characteristics for circuit-breakers

91

System and line protection with NZM1

System and line protection with NZM2


2.5 h 8000
6000
4000

NZM1 - A(F)...

Tripping time [s]

2000

NZM2 - A(F)...

2000

1000
800
(10 min) 600
400

1000
800
(10 min) 600
400

200
100
80
(1 min) 60
40

Tolerance tr [s]

200
100
80
(1 min) 60
40
20
10
8
6
4

Tolerance tr [s]

Tripping time [s]

2.5 h 8000
6000
4000

20
10
8
6
4
2

2
Setting range

1
0.8
0.6
0.4
Ii = 6

0.2

10x In

0.02

0.02

0.01
0.008
0.006
0.004

0.01
0.008
0.006
0.004

0.002

0.002
2

5 6 7 8 910

15

Ii = 6

0.2
0.1
0.08
0.06
0.04

Setting range

1
0.8
0.6
0.4

0.1
0.08
0.06
0.04

0.001

Circuit-breakers, disconnect switches


up to 1200 A

Moeller SK1230-1157EN-NA

20

30

40 50 60 70 80 100

0.001

5 6 7 8 910

10x In

15

x Ir

For Immediate Delivery call KMParts.com at (866) 595-9616

20

30

40 50 60 70 80 100
x Ir

SK1157_091-094_G_G.fm Page 92 Tuesday, April 25, 2006 11:31 AM

Tripping characteristics
Tripping characteristics for circuit-breakers
Moeller SK1230-1157EN-NA

Tripping time [s]

2.5 h 8000
6000
4000

System and line protection with NZM3

NZM2 - VE(F)...
Characteristics for Ir = 1,0 x In

2000

1000
800
(10 min) 600
400

2.5 h 8000
6000
4000

Tripping time [s]

Systems, cable, selectivity and generator protection with NZM2

1000
800
(10 min) 600
400

200

200
100
80
(1 min) 60
40

10
8
6
4

tr [s]
20
17
14
10
8
6
4

20

20
10
8
6
4
2

tsd [ms]
1000
750
500

1
0.8
0.6
0.4

1
0.8
0.6
0.4

300
200

0.2

0.2

100
60

0.1
0.08
0.06
0.04

0.1
0.08
0.06
0.04

20
Isd = 2

5 6 7 8 9 10 x Ir

0.02

0.01
0.008
0.006
0.004

0.002

0.002
2

5 6 7 8 910

15

Ii =

2 2.5 3 3.5 4

5 6 7 8

Ii =

5 6 7 8 9 11 x In

5 6 7 8 910

x In

20

30

40 50 60 70 80 100

0.001

15

x Ir

Systems, cable, selectivity and generator protection with NZM3


2.5 h 8000
6000
4000

NZM3 - VE(F)...
Characteristics for Ir = 1,0 x In

2000

1000
800
(10 min) 600
400
200
100
80
(1 min) 60
40

10
8
6
4

tr [s]
20
17
14
10
8
6
4

20

1
0.8
0.6
0.4
0.2

Isd = 1.5

2.5 3 3.5 4

0.1
0.08
0.06
0.04

5 6 7

tsd [ms]
1000
750
500
300
200
x Ir
100
60

0
5 6 7 8 9 10 x Ir

Isd =

0.01
0.008
0.006
0.004

Ii =

2 2.5 3 3.5 4

5 6 7 8

Ii =

5 6 7 8 9 11x In

5 6 7 8 910

0.002
0.001

without I2t = constant function


630 A

20

0.02

x In

15

630 A
250 A, 400 A

0.02

Ii = 12 x In

0.01
0.008
0.006
0.004

0.001

NZM3 - AE(F)...
Characteristics for Ir = 1,0 x In

2000

100
80
(1 min) 60
40

Tripping time [s]

Circuit-breakers, disconnect switches


up to 1200 A

92

250 A, 400 A

630 A
250 A, 400 A

20

30

40 50 60 70 80 100
x Ir

For Immediate Delivery call KMParts.com at (866) 595-9616

20

30

40 50 60 70 80 100
x Ir

SK1157_091-094_G_G.fm Page 93 Tuesday, April 25, 2006 11:31 AM

93

Moeller SK1230-1157EN-NA

Tripping time [s]

2.5 h 8000
6000
4000

System and line protection with NZM4

NZM3 - VE(F)...
Characteristics for Ir = 1,0 x In

2000

1000
800
(10 min) 600
400

2.5 h 8000
6000
4000

Tripping time [s]

Systems, cable, selectivity and generator protection with NZM3

2000

1000
800
(10 min) 600
400

200

200

100
80
(1 min) 60
40

100
80
(1 min) 60
40

10
8
6
4

tr [s]
20
17
14
10
8
6
4

20

1
0.8
0.6
0.4
s]

t sd

0.1
0.08
0.06
0.04

20
10
8
6
4
2

00

20

0.2

[m

Isd = 1.5

2 2.5 3 3.54

5 6 7

Isd =

5 6 7 8 910 x Ir

1
0.8
0.6
0.4

I2t = constant

10

....

....

0.2

x Ir

630 A
250 A, 400 A

0.02

0.01
0.008
0.006
0.004

Ii =

2 2.5 3 3.5 4

5 6 7 8

0.01
0.008
0.006
0.004

0.002

Ii =

5 6 7 8 9 11 x In 250 A, 400 A

5 6 7 8 910

630 A

x In

15

20

30

Ii =

0.1
0.08
0.06
0.04

0.02

0.001

NZM4 - AE(F)...
Characteristics for Ir = 1,0 x In

5 6 7 8 10 12x In

5 6 7 8 910

0.002
40 50 60 70 80 100

0.001

x Ir

Systems, cable, selectivity and generator protection with NZM4

Tripping time [s]

2.5 h 8000
6000
4000

NZM4 - VE(F)...
Characteristics for Ir = 1,0 x In

2000

1000
800
(10 min) 600
400
200
100
80
(1 min) 60
40

10
8
6
4

tr [s]
20
17
14
10
8
6
4

20

tsd [ms]
1000
750
500
without I2t = constant function
300
200
100
60
20
0

1
0.8
0.6
0.4
0.2
0.1
0.08
0.06
0.04
0.02

Isd = 2

5 6 7 8 9 10

5 6 7 8

5 6 7 8 910

Ii =

0.01
0.008
0.006
0.004

x Ir

10 12 x In

0.002
0.001

15

20

30

40 50 60 70 80 100
x Ir

For Immediate Delivery call KMParts.com at (866) 595-9616

15

20

30

40 50 60 70 80 100
x Ir

Circuit-breakers, disconnect switches


up to 1200 A

Tripping characteristics
Tripping characteristics for circuit-breakers

SK1157_091-094_G_G.fm Page 94 Tuesday, April 25, 2006 11:31 AM

Tripping characteristics
Tripping characteristics for circuit-breakers
Moeller SK1230-1157EN-NA
Systems, cable, selectivity and generator protection with NZM4
2.5 h 8000
6000
4000

Tripping time [s]

Circuit-breakers, disconnect switches


up to 1200 A

94

NZM4 - VE(F)...
Characteristics for Ir = 1,0 x In

2000

1000
800
(10 min) 600
400
200

(1 min)

100
80
60
40

10
8
6
4

tr [s]
20
17
14
10
8
6
4

20

1
0.8
0.6
0.4

I2t = constant

00

...1

....

...
0..

0.2

s] =

[m
d

0.1
0.08
0.06
0.04

ts

0.02

Isd = 2

5 6 7 8 9 10

5 6 7 8

5 6 7 8 910

Ii =

0.01
0.008
0.006
0.004

x Ir

10 12 x In

0.002
0.001

15

20

30

40 50 60 70 80 100
x Ir

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_095-101_G_G.fm Page 95 Friday, May 5, 2006 5:05 PM

Tripping characteristics
Let-through characteristics circuit-breakers

95

Circuit-breakers, disconnect switches


up to 1200 A

Moeller SK1230-1157EN-NA
Let-through current xD
200

D
[kA]

NZMB1(-4)-A(M,S,AF)15...160(-(C)NA)

200
NZMN1(-4)-A(M,S,AF)15...160(-(C)NA)

100

80

80

60

60

40

40

2x

Ic

Ic

100

2x

D
[kA]

20

20

415 V
525 V

10

415 V

10

525 V
690 V

1
1

5 6

8 10

15 20

30 40 50 60 80 100

150

5 6

8 10

15 20

Icc rms [kA]

For Immediate Delivery call KMParts.com at (866) 595-9616

30 40 50 60 80 100

150

Icc rms [kA]

SK1157_095-101_G_G.fm Page 96 Wednesday, June 7, 2006 7:40 PM

Tripping characteristics
Let-through characteristics for circuit-breakers
Moeller SK1230-1157EN-NA
Let-through current xD
200

D
[kA]

NZMB2-A(S,AF)15...250(-(C)NA)

200

100

80

80

60

60

40

40

100

NZMN2-A(S,VE,ME,AF,VEF,SE)1,6...250(-(C)NA)

2x

2x

Ic

Ic

D
[kA]

20

20

415 V
525 V

415 V

690 V

10

10

525 V

8
6

1
1

5 6

8 10

15 20

30 40 50 60 80 100

150

5 6

8 10

15 20

Icc rms [kA]

200

NZMH2(-4)-A(S,VE,ME,AF,VEF,SE)1,6...250(-(C)NA)

100
80
60

40

Ic

D
[kA]

2x

Circuit-breakers, disconnect switches


up to 1200 A

96

415 V

20
525 V
690 V

10
8
6
4
3

5 6

8 10

15 20

30 40 50 60 80 100

150

Icc rms [kA]

For Immediate Delivery call KMParts.com at (866) 595-9616

30 40 50 60 80 100

150

Icc rms [kA]

SK1157_095-101_G_G.fm Page 97 Thursday, June 8, 2006 3:42 PM

Tripping characteristics
Let-through characteristics for circuit-breakers

97

Circuit-breakers, disconnect switches


up to 1200 A

Moeller SK1230-1157EN-NA
Let-through current xD
200

D
[kA]

NZMN3-AE(VE,AEF,VEF,SE)220...600(-(C)NA)

200
NZMH3(-4)-AE(VE,AEF,VEF,SE)220...600(-(C)NA)

100

100

80

80

60

60

40

40

Ic

690 V

2x

Ic

690 V
2x

D
[kA]

20

20
525 V

525 V
415 V

415 V
10

10

1
1

5 6

8 10

15 20

30 40 50 60 80 100

150

1
1

5 6

8 10

15 20

Icc rms [kA]

For Immediate Delivery call KMParts.com at (866) 595-9616

30 40 50 60 80 100

150

Icc rms [kA]

SK1157_095-101_G_G.fm Page 98 Thursday, June 8, 2006 3:37 PM

Circuit-breakers, disconnect switches


up to 1200 A

98

Tripping characteristics
Let-through characteristics for circuit-breakers
Moeller SK1230-1157EN-NA
Let-through energy J
Zy
[A2 s]

107

Zy
[A2 s]

NZMB1-A(S,AF)1,2...125(-(C)NA)

107

NZMN1-A(S,AF,)15...125(-(C)NA)

106

106

6
415 V

415 V

525 V

525 V

690 V
2

105
8

105
8

104

104
1

5 6

8 10

15 20

30 40 50 60 80 100

150

5 6

8 10

15 20

Icc rms [kA]

For Immediate Delivery call KMParts.com at (866) 595-9616

30 40 50 60 80 100

150

Icc rms [kA]

SK1157_095-101_G_G.fm Page 99 Wednesday, June 7, 2006 7:40 PM

Tripping characteristics
Let-through characteristics for circuit-breakers

99

Circuit-breakers, disconnect switches


up to 1200 A

Moeller SK1230-1157EN-NA
Let-through energy J
Zy
[A2 s]

107

Zy
[A2 s]

NZMB2-A(S,AF)1,6...250(-(C)NA)

107

NZMN2-A(S,VE,ME,AF,VEF,SE)15...250(-(C)NA)

106

106

415 V

415 V
2

525 V
2

525 V

105
8

105
8

104

5 6

8 10

15 20

30 40 50 60 80 100

150

690 V

104
1

5 6

8 10

15 20

Icc rms [kA]

Zy
[A2 s]

107

NZMH2(-4)-A(M,S,VE,ME)20...250

8
6
4

106
8
6
4
415 V
525 V
2
690 V
105
8
6
4

104
1

5 6

8 10

15 20

30 40 50 60 80 100

150

Icc rms [kA]

a 1st half-wave

For Immediate Delivery call KMParts.com at (866) 595-9616

30 40 50 60 80 100

150

Icc rms [kA]

SK1157_095-101_G_G.fm Page 100 Wednesday, June 7, 2006 7:40 PM

Circuit-breakers, disconnect switches


up to 1200 A

100

Tripping characteristics
Let-through characteristics for circuit-breakers
Moeller SK1230-1157EN-NA

Let-through energy J
Zy
[A2 s]

107

Zy
[A2 s]

NZMN3-AE(VE,AEF,VEF,SE)220...600(-(C)NA)

107
6

NZMH3(-4)-AE(VE,AEF,VEF,SE)220...600(-(C)NA)

2
690 V

106

690 V

106

525 V

6
525 V

415 V

4
415 V

105
8

105
8

104

5 6

8 10

15 20

30 40 50 60 80 100

150

104
1

5 6

8 10

15 20

Icc rms [kA]

For Immediate Delivery call KMParts.com at (866) 595-9616

30 40 50 60 80 100

150

Icc rms [kA]

SK1157_095-101_G_G.fm Page 101 Friday, May 5, 2006 5:05 PM

Notes

Circuit-breakers, disconnect switches


up to 1200 A

Moeller SK1230-1157EN-NA

101

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_102-105_e_G-g.fm Page 102 Thursday, June 8, 2006 9:56 AM

Technical data
Circuit-breakers

Technical data
Circuit-breakers
Moeller SK1230-1157EN-NA
Rated uninterrupted current: 125 A
NZMB1
NZMN1

Rated uninterrupted current: 250 A


NZMB2
NZMN2
NZMH2

IEC/EN 60947: UL 489, CSA 22.2 No. 5.1


Finger and back of hand proof to VDE 0106 Part 100

IEC/EN 60947: UL 489, CSA 22.2 No. 5.1


Finger and back of hand proof to VDE 0106 Part 100

Damp heat, constant, according to IEC 60068-2-78


Damp heat, cyclical to IEC 60068-2-30

Damp heat, constant, according to IEC 60068-2-78


Damp heat, cyclical to IEC 60068-2-30

C
C

-25/+70
-25/+70
20 (half-sinusoidal shock 20 ms)

-25/+70
-25/+70
20 (half-sinusoidal shock 20 ms)

V AC
V AC

500
300

500
300

General
Standards
Protection against direct contact
Climatic proofing
Ambient temperature
Storage
Operation
Mechanical shock resistance (IEC/EN 60068-2-27)
Safe isolation to VDE 0106 Part 101 and Part 101/A1
between auxiliary contacts and main contacts
between the auxiliary contacts
Mounting position

Moeller SK1230-1157EN-NA
Rated uninterrupted current: 600 A
NZMN3
NZMH3

Vertical and 90 in all directions


With plug-in adapter NZM2: vertical, 90
right/left

90
90

90
With withdrawable unit
NZM3: vertical, 90 left
NZM4: vertical

90
90
90

Direction of incoming supply


Degree of protection
Device
Enclosures
Terminals

90
90

As required

As required

In the operating controls area: IP20


(basic degree of protection)
With insulating surround: IP40,
with door coupling rotary handle: IP66
Tunnel terminal: IP10
Phase isolator and strip terminal: IP00

In the operating controls area: IP20


(basic degree of protection)
With insulating surround: IP40,
with door coupling rotary handle: IP66
Tunnel terminal: IP10
Phase isolator and strip terminal: IP00

For Immediate Delivery call KMParts.com at (866) 595-9616

with remote operator:


NZM2, NZM3, NZM4: vertical and 90 in all
directions

Rated uninterrupted current: 1200 A


NZMN4
NZMH4

103

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

102

SK1157_102-105_e_G-g.fm Page 102 Thursday, June 8, 2006 9:56 AM

Technical data
Circuit-breakers

Technical data
Circuit-breakers
Moeller SK1230-1157EN-NA
Rated uninterrupted current: 125 A
NZMB1
NZMN1

Rated uninterrupted current: 250 A


NZMB2
NZMN2
NZMH2

IEC/EN 60947: UL 489, CSA 22.2 No. 5.1


Finger and back of hand proof to VDE 0106 Part 100

IEC/EN 60947: UL 489, CSA 22.2 No. 5.1


Finger and back of hand proof to VDE 0106 Part 100

Damp heat, constant, according to IEC 60068-2-78


Damp heat, cyclical to IEC 60068-2-30

Damp heat, constant, according to IEC 60068-2-78


Damp heat, cyclical to IEC 60068-2-30

C
C

-25/+70
-25/+70
20 (half-sinusoidal shock 20 ms)

-25/+70
-25/+70
20 (half-sinusoidal shock 20 ms)

V AC
V AC

500
300

500
300

General
Standards
Protection against direct contact
Climatic proofing
Ambient temperature
Storage
Operation
Mechanical shock resistance (IEC/EN 60068-2-27)
Safe isolation to VDE 0106 Part 101 and Part 101/A1
between auxiliary contacts and main contacts
between the auxiliary contacts
Mounting position

Moeller SK1230-1157EN-NA
Rated uninterrupted current: 600 A
NZMN3
NZMH3

Rated uninterrupted current: 1200 A


NZMN4
NZMH4

Vertical and 90 in all directions


With plug-in adapter NZM2: vertical, 90
right/left

90
90

90
With withdrawable unit
NZM3: vertical, 90 left
NZM4: vertical

90
90
90

Direction of incoming supply


Degree of protection
Device
Enclosures
Terminals

90
90

As required

As required

In the operating controls area: IP20


(basic degree of protection)
With insulating surround: IP40,
with door coupling rotary handle: IP66
Tunnel terminal: IP10
Phase isolator and strip terminal: IP00

In the operating controls area: IP20


(basic degree of protection)
With insulating surround: IP40,
with door coupling rotary handle: IP66
Tunnel terminal: IP10
Phase isolator and strip terminal: IP00

with remote operator:


NZM2, NZM3, NZM4: vertical and 90 in all
directions

For Immediate Delivery call KMParts.com at (866) 595-9616

103

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

102

SK1157_102-105_e_G-g.fm Page 104 Thursday, June 8, 2006 3:35 PM

Technical data
Circuit-breakers

Technical data
Circuit-breakers
Moeller SK1230-1157EN-NA

Circuit-breakers
Rated impulse withstand voltage Uimp
Main contacts
Auxiliary contacts
Rated operational voltage
Overvoltage category/pollution degree
Rated insulation voltage
For use in IT electrical power networks

Moeller SK1230-1157EN-NA

Rated uninterrupted current: 160 A


NZMB1
NZMN1

Rated uninterrupted current: 250 A


NZMB2
NZMN2

NZMH2

Rated uninterrupted current: 600 A


NZMN3
NZMH3

Rated uninterrupted current: 1200 A


NZMN4
NZMH4

6000
6000
690
III/3
690
690

8000
6000
690
III/3
1000
525

8000
6000
690
III/3
1000
690

8000
6000
690
III/3
1000
690

8000
6000
690
III/3
1000
690

8000
6000
690
III/3
1000
690

8000
6000
690
III/3
1000
525

8000
6000
690
III/3
1000
525

Ui

V
V

6000
6000
690
III/3
690
525

Icm
Icm
Icm
Icm
Icm

kA
kA
kA
kA
kA

63
53
53
30

187
105
74
40
17

63
53
53
30

187
105
74
53
40

330
330
286
105
40

187
105
74
53
40

330
330
286
143
74

105
105
74
53
40

275
220
187
143
105

30
25
25
15

30
25
25
7.5

85
50
35
20
10
85
50
35
10
7.5
A

30
25
25
15

30
25
25
15

85
50
35
25
20
85
50
35
25
5
A

150
150
130
50
20
150
150
130
38
5
A

85
50
35
25
20
85
50
35
13
5
A

150
150
130
65
35
150
150
130
33
9
A

50
50
35
25
20
37
37
26
19
15
B

125
100
85
65
50
63
50
43
49
37
B

1.9
1.9

1.9
1.9

3.3
3.3

3.3
3.3

19.2
19.2

160
160
160
160
20000

160
160
160
160
20000

250
250
250
250
20000

250
250
250
250
20000

250
250
250
250
20000

600
600
600
600
15000

600
600
600
600
15000

1200
1200
12003)
12003)
10000

1200
1200
12003)
12003)
10000

120

120

120

120

120

60

60

60

60

10000
7500
7500
5000
13

10000
7500
7500
5000
13

10000
7500
6500
5000
19

10000
7500
6500
5000
19

10000
7500
6500
5000
19

5000
3000
2000
2000
40

5000
3000
2000
2000
40

3000
2000
2000
1000
97

3000
2000
2000
1000
97

0.7

< 10

0.7

< 10

0
0
< 10

0
0
< 10

0
0
< 10

0
< 10

0
< 10

0
< 25 F 415 V; < 35
> 415 V

0
< 25 F 415 V; < 35
> 415 V

35
252)

85
352)

35
25
18

85
35
25

1504)
1004)
504)

85
42
35

1504)
1004)
504)

85
42
35

1256)
85
50

Ue

V
V
V AC

105

Switching capacity
Rated short-circuit making capacity
240 V 50/60 Hz
400/415 V 50/60 Hz
440 V 50/60 Hz
525 V 50/60 Hz
690 V 50/60 Hz

Rated short-circuit breaking capacity Icn


Icu to IEC/EN 60947 operating sequence 240 V 50/60 Hz
Icu
kA
O-t-CO
kA
400/415 V 50/60 Hz
Icu
kA
440 V 50/60 Hz
Icu
kA
525 V 50/60 Hz
Icu
kA
690 V 50/60 Hz
Icu
Ics
kA
Icu to IEC/EN 60947 operating sequence 240 V 50/60 Hz
O-t-CO-t-CO
kA
400/415 V 50/60 Hz
Ics
kA
440 V 50/60 Hz
Ics
kA
525 V 50/60 Hz
Ics
kA
690 V 50/60 Hz
Ics
Utilization category to IEC/EN 60947-2
Rated short-time withstand current
t = 0.3 s
Icw
kA
kA
t=1s
Icw
Rated making and breaking capacity
Rated operational current
AC-1
400/415 V 50/60 Hz
Ie
A
A
690 V 50/60 Hz
Ie
A
AC-3
400/415 V 50/60 Hz
Ie
690 V 50/60 Hz
Ie
A
Lifespan, mechanical
Operations
(of which max. 50 % trip by shunt/undervoltage release)
Maximum operating frequency
Ops/h
Lifespan, electrical to IEC/EN 60947-4-1 section B
AC-1
400/415 V 50/60 Hz
Operations
690 V 50/60 Hz
Operations
AC-3
400/415 V 50/60 Hz
Operations
690 V 50/60 Hz
Operations
W
Current heat loss per pole at I u
Overload releases
Temperature compensation for NZM2 to IEC/EN 60947, residual error in the range -25 C/+70 C (reference
temperature 40 C)
Thermomagnetic
%/K
Electronic
Total opening delay at short-circuit
ms
Technical data, divergent from the products for the IEC market
Switching capacity NA switches (UL489, CSA 22.2 No. 5.1)
240 V 60 Hz
480V 60Hz
600 V 60 Hz
Notes

kA
kA
kA

1) For

switching capacity of NA switches with NZM...1-...NA the following applies: 480Y/277 V from 60 A
rated operational current AC-3 at NZM4 the following applies: 400 V: max. 650 kW; 600 V: max. 600 kW
3) For switching capacity of NA switches with NZMH2 and NZMH3 the following applies: current limiting switch to UL489
4) For switching capacity of NA switches with NZMH4 at 240 V 60 Hz the following applies: please enquire
2) For

For Immediate Delivery call KMParts.com at (866) 595-9616

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

104

SK1157_102-105_e_G-g.fm Page 104 Thursday, June 8, 2006 3:35 PM

Technical data
Circuit-breakers

Technical data
Circuit-breakers
Moeller SK1230-1157EN-NA

Circuit-breakers
Rated impulse withstand voltage Uimp
Main contacts
Auxiliary contacts
Rated operational voltage
Overvoltage category/pollution degree
Rated insulation voltage
For use in IT electrical power networks

Moeller SK1230-1157EN-NA

Rated uninterrupted current: 160 A


NZMB1
NZMN1

Rated uninterrupted current: 250 A


NZMB2
NZMN2

NZMH2

Rated uninterrupted current: 600 A


NZMN3
NZMH3

Rated uninterrupted current: 1200 A


NZMN4
NZMH4

6000
6000
690
III/3
690
690

8000
6000
690
III/3
1000
525

8000
6000
690
III/3
1000
690

8000
6000
690
III/3
1000
690

8000
6000
690
III/3
1000
690

8000
6000
690
III/3
1000
690

8000
6000
690
III/3
1000
525

8000
6000
690
III/3
1000
525

Ui

V
V

6000
6000
690
III/3
690
525

Icm
Icm
Icm
Icm
Icm

kA
kA
kA
kA
kA

63
53
53
30

187
105
74
40
17

63
53
53
30

187
105
74
53
40

330
330
286
105
40

187
105
74
53
40

330
330
286
143
74

105
105
74
53
40

275
220
187
143
105

30
25
25
15

30
25
25
7.5

85
50
35
20
10
85
50
35
10
7.5
A

30
25
25
15

30
25
25
15

85
50
35
25
20
85
50
35
25
5
A

150
150
130
50
20
150
150
130
38
5
A

85
50
35
25
20
85
50
35
13
5
A

150
150
130
65
35
150
150
130
33
9
A

50
50
35
25
20
37
37
26
19
15
B

125
100
85
65
50
63
50
43
49
37
B

1.9
1.9

1.9
1.9

3.3
3.3

3.3
3.3

19.2
19.2

160
160
160
160
20000

160
160
160
160
20000

250
250
250
250
20000

250
250
250
250
20000

250
250
250
250
20000

600
600
600
600
15000

600
600
600
600
15000

1200
1200
12003)
12003)
10000

1200
1200
12003)
12003)
10000

120

120

120

120

120

60

60

60

60

10000
7500
7500
5000
13

10000
7500
7500
5000
13

10000
7500
6500
5000
19

10000
7500
6500
5000
19

10000
7500
6500
5000
19

5000
3000
2000
2000
40

5000
3000
2000
2000
40

3000
2000
2000
1000
97

3000
2000
2000
1000
97

0.7

< 10

0.7

< 10

0
0
< 10

0
0
< 10

0
0
< 10

0
< 10

0
< 10

0
< 25 F 415 V; < 35
> 415 V

0
< 25 F 415 V; < 35
> 415 V

35
252)

85
352)

35
25
18

85
35
25

1504)
1004)
504)

85
42
35

1504)
1004)
504)

85
42
35

1256)
85
50

Ue

V
V
V AC

105

Switching capacity
Rated short-circuit making capacity
240 V 50/60 Hz
400/415 V 50/60 Hz
440 V 50/60 Hz
525 V 50/60 Hz
690 V 50/60 Hz

Rated short-circuit breaking capacity Icn


Icu to IEC/EN 60947 operating sequence 240 V 50/60 Hz
Icu
kA
O-t-CO
kA
400/415 V 50/60 Hz
Icu
kA
440 V 50/60 Hz
Icu
kA
525 V 50/60 Hz
Icu
kA
690 V 50/60 Hz
Icu
Ics
kA
Icu to IEC/EN 60947 operating sequence 240 V 50/60 Hz
O-t-CO-t-CO
kA
400/415 V 50/60 Hz
Ics
kA
440 V 50/60 Hz
Ics
kA
525 V 50/60 Hz
Ics
kA
690 V 50/60 Hz
Ics
Utilization category to IEC/EN 60947-2
Rated short-time withstand current
t = 0.3 s
Icw
kA
kA
t=1s
Icw
Rated making and breaking capacity
Rated operational current
AC-1
400/415 V 50/60 Hz
Ie
A
A
690 V 50/60 Hz
Ie
A
AC-3
400/415 V 50/60 Hz
Ie
690 V 50/60 Hz
Ie
A
Lifespan, mechanical
Operations
(of which max. 50 % trip by shunt/undervoltage release)
Maximum operating frequency
Ops/h
Lifespan, electrical to IEC/EN 60947-4-1 section B
AC-1
400/415 V 50/60 Hz
Operations
690 V 50/60 Hz
Operations
AC-3
400/415 V 50/60 Hz
Operations
690 V 50/60 Hz
Operations
W
Current heat loss per pole at I u
Overload releases
Temperature compensation for NZM2 to IEC/EN 60947, residual error in the range -25 C/+70 C (reference
temperature 40 C)
Thermomagnetic
%/K
Electronic
Total opening delay at short-circuit
ms
Technical data, divergent from the products for the IEC market
Switching capacity NA switches (UL489, CSA 22.2 No. 5.1)
240 V 60 Hz
480V 60Hz
600 V 60 Hz
Notes

kA
kA
kA

1) For

switching capacity of NA switches with NZM...1-...NA the following applies: 480Y/277 V from 60 A
rated operational current AC-3 at NZM4 the following applies: 400 V: max. 650 kW; 600 V: max. 600 kW
3) For switching capacity of NA switches with NZMH2 and NZMH3 the following applies: current limiting switch to UL489
4) For switching capacity of NA switches with NZMH4 at 240 V 60 Hz the following applies: please enquire
2) For

For Immediate Delivery call KMParts.com at (866) 595-9616

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

104

SK1157_106_n_G-m.fm Page 106 Thursday, June 8, 2006 9:59 AM

Circuit-breakers, disconnect switches


up to 1200 A

106

Technical data
Circuit-breakers
Moeller SK1230-1157EN-NA

Current limiting specifications: NZMH2... and NZMH3...

Circuit-breakers
Type
max.
frame size
NZMH2A...
AF...

[A]
250 A

Voltage
At 60 Hz
[V]
240
480
600

Threshold current
Maximum
sym. rms
Peak
[kA]
[kA]
16.25
12.80
16.25
13.20
16.25
12.98

I2dt
[kA2s]
0.36
0.50
0.60

Intermediate current
Maximum
sym. rms
Peak
[kA]
[kA]
100
20.23
65
23.63
30
19.40

I2dt
[kA2s]
0.40
0.85
0.67

High interrupting capacity


Maximum
sym. rms
Peak
[kA]
[kA]
150
20.00
100
26.55
50
24.40

I2dt
[kA2s]
0.38
0.78
0.84

NZMH2VE...
VEF...

250 A

240
480
600

16.25
16.25
16.25

11.40
14.23
14.33

0.31
0.48
0.48

100
65
30

18.23
23.63
19.60

0.27
0.58
0.60

150
100
50

20.40
26.43
24.63

0.32
0.62
0.79

NZMH3

600 A

240
480
600

39
39
30

41.20
29.50
29.50

3.30
1.60
2.24

100
65
42

31.00
36.40
33.80

1.01
2.34
2.04

150
100
50

36.80
43.10
39.15

1.34
1.92
2.42

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_107_n_G-g.fm Page 107 Thursday, June 8, 2006 10:00 AM

Technical data
Disconnect switches, derating

N3
550 A max.

N4
1200 A max.

Ue

V
V
V AC

8000
6000
690

8000
6000
690

Iu
Iu

A
A

630
550

1600
1200

Ue

V AC

III/3
1000

III/3
1000

Icm

kA

25

53

Icw
Icw

kA
kA

12
12

25
25

A gG/gL

550

2 x 600

400/415 V
690 V

kA
kA
A gG/gL

100
80
630

100
80
2 x 600

400/415 V
690 V

kA
kA

100
100

100
80

A
A
Ops/h

550
550
15000
60

1200
1200
10000
60

5000
3000
3000
2000
40

3000
2000
2000
1000
97

Disconnect switches
Rated impulse withstand voltage Uimp
Main contacts
Auxiliary contacts
Rated operational voltage
Rated uninterrupted current max.
IEC/EN 61131-3
Technical data, divergent from
the products for the IEC market
UL489, CSA 22.2 No. 5.1
Overvoltage category/pollution degree
Rated insulation voltage
Switching capacity
Rated short-circuit making capacity
Rated short-time withstand current
t = 0.3 s
t=1s
Rated conditional short-circuit current
with back-up fuse

With downstream fuse

Rated making and breaking capacity


Rated operational current,
AC-22/23A

415 V
690 V

Lifespan, mechanical
Maximum operating frequency
Lifespan, electrical to IEC/EN 60947-4-1 section B
AC-1
400/415 V
690 V
AC-3
400/415 V
690 V
Current heat loss per pole at I u1)
1) The

Notes

3) 690

Notes

Operations
Operations
Operations
Operations

current heat loss per pole ratings refer to the maximum current rating of the frame size.
V: max. 160 kW

NZM1,
NS1
125 A

Permissible loading at different ambient


temperatures (derating)
open
20C
%
30C
%
40C
%
50C
%
60C
%
65C
%
70C
%

Ie
Ie
Operations

Circuit-breakers, disconnect switches


up to 1200 A

Moeller SK1230-1157EN-NA

100
100
100
100
86
83
79

NZM2, NS2
250 A
without
with XSV
TM

100
100
100
100
90
85
80

100
100
100
94
88
84
81

100
97
92
87
81
78
75

NZM3, N3, NS3 600 A


without

with XAV

NZM4, N4, NS4


1200 A
without
with XAV

100
100
100
100
90
85
80

96
92
87
83
78
75
73

100
100
100
100
87
85
82

XSV = plug-in unit


XAV = withdrawable unit
TM = thermomagnetic
E = electronic

For Immediate Delivery call KMParts.com at (866) 595-9616

107

100
98
93
89
85
83
80

SK1157_108-109_e_G-m.fm Page 108 Monday, April 24, 2006 10:42 AM

Circuit-breakers, disconnect switches


up to 1200 A

108

Technical data
Molded Case Switches
Moeller SK1230-1157EN-NA

Molded Case Switch


Rated impulse withstand voltage
Main contacts
Auxiliary contacts
Rated operational voltage
Rated uninterrupted current max.
IEC/EN 60947-2 Annex L
UL489/CSA 22.2 No. 5.1
Overvoltage category/pollution degree
Rated insulation voltage

NS1-...-NA
max. 125A

NS2-...-NA
max. 250A

6000
6000
690

8000
6000
690

125
125
III/3
690

250
250
III/3
1000

85
35

150
100
50

187
105
74
53
17
85
50
35
20
10
85
50
35
10
7.5
20000
120
10000
7500
7500
5000
13
< 10

330
330
286
105
53
150
150
130
50
20
150
150
130
37.5
5
20000
120
10000
7500
6500
5000
19
< 10

Uimp

Ue
Iu
Iu
Ui

Switching capacity to UL 489, CSA 22.2 No. 5.1


240 V
480 V
600 V
Switching capacity, divergent from the products for the NA market
Rated short-circuit making capacity
240 V
400/415 V
440 V
525 V
690 V
Rated short-circuit breaking capacity
Icu to IEC/EN 60947
240 V
Icc = Icu to IEC/EN 60947-2 Annex L
test cycle O-t-CO
400/415 V
440 V
525 V
690 V
Ics to IEC/EN 60947
240 V
test cycle O-t-CO-t-CO
400/415 V
440 V
525 V
690 V
Lifespan, mechanical
Maximum operating frequency
Lifespan, electrical
AC-1
400/415 V
690 V
AC-3
400/415 V
690 V
Current heat loss per pole at Iu1)
Total opening delay on short-circuit
Notes

1)

Icm
Icm
Icm
Icm
Icm
Icu
Icu
Icu
Icu
Icu
Ics
Ics
Ics
Ics
Ics
Operations
Operations
Operations
Operations
Operations

Details relate to the maximum nominal current of the frame size

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_108-109_e_G-m.fm Page 109 Monday, April 24, 2006 10:42 AM

Notes

Circuit-breakers, disconnect switches


up to 1200 A

Moeller SK1230-1157EN-NA

109

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_110-111_e_G-m.fm Page 110 Thursday, June 8, 2006 10:01 AM

Technical data
Effective power loss

Technical data
Effective power loss
Moeller SK1230-1157EN-NA

NZM up to 250A with thermomagnetic release (3 pole)


Fixed mounted
NZM1A...-NA
AF...-NA
P
R
P
In [A]
[W]
[Ohm]
[W]
1.2
1.6
2
2.4
3
5
8
12
15
18
20
25
26
30
32
33
35
40
45
50
60
63
70
80
90
100
110
125
150
160
175
200
225
250

9.8
8.8

9.1

11

13.5

14

15.5

24

38

50

Note:

The values stated in the table apply for fixed mounted 3 pole devices which are loaded uniformly.
The entire resistive load is for the measured three-pole or four-pole value.
The total heat dissipation is the measured value for In at 50/60 Hz for a 3-pole switch.
The heat dissipation can be calculated using the fromula: P = 3 x R x I

8180
4680

3030

2220

1760

1190

850

730

570

460

5.5

9.8
8.8

8.2

8.2
11
10.7
13.5
12.9

12.5
15.5
17.7
24
20.7
38

NZM up to 1200 A with electronic release (3 pole)


Fixed mounted Additional
Fixed mounted
Plug-in units
NZM2NZM3N3-

R
[Ohm]

S...-CNA
P
[W]

R
[Ohm]

NS1...-NA
P
[W]

8180

8180
4680

3030

2220
2220
1760
1760
1190

850
850
730
730
570
570

1.2

0.5

1.1
0.4
1
0.5

1.3

3.2

2.7

4.2

6.7

10.8

16.9

413000

66000

66000
9180
9180
1670

1670

1050

1050

562

562

562

562

562

6.7

16.9

26.3

R
[Ohm]

R
[Ohm]

R
[Ohm]

Additional
Withdrawable
units
R
[Ohm]

275

100

100

90

70

Note:

The values stated in the table apply for 3 pole devices which are loaded uniformly.
The total resistive load is the measured value for a 3 pole switch
(independent of In and the type of release).
The total resistive load for a switch in fixed or withdrawable design results from:
the resistive value for fixed mounting + resistive value for plug-in or withdrawable design.
The heat dissipation can be calculated using the fromula: P = 3 x R x I

R
[Ohm]

Fixed mounted
NZM4N4R
[Ohm]

R
[Ohm]

Additional
Withdrawable
units
R
[Ohm]

37

37

10

For Immediate Delivery call KMParts.com at (866) 595-9616

Moeller SK1230-1157EN-NA

R
[Ohm]

Fixed mounted
NZM2A...-NA
P
R
[W]
[Ohm]

AF...-NA
P
[W]

562

562

562

5.1
8

10

13

18

20

22

28

29

40

48

57

5.1
6

11
13
15
18
19

17
22
23
28
22
29
35

37
48
46
57

4250
4250

3140

2800

2270

1700

1070

855

589

427

332

310

R
[Ohm]

S...-CNA
P
[W]

4250

4250
3140

3140

2800
2800
2270
2270
1700

1070
1070
855
855
589
589
427

332
332
310
310

6.2

8.4

0.2
0.5
0.4

0.5

0.9

1.5

2.5

10

15

25

40

59.4

R
[Ohm]

NS2...-NA
P
[W]

R
[Ohm]

750000

450000

4600
4600
1200

1200

780

780

317

317

317

317

317

317

317

317

317

25

40

59.4

317

317

317

111

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

110

SK1157_110-111_e_G-m.fm Page 110 Thursday, June 8, 2006 10:01 AM

Technical data
Effective power loss

Technical data
Effective power loss
Moeller SK1230-1157EN-NA

NZM up to 250A with thermomagnetic release (3 pole)


Fixed mounted
NZM1A...-NA
AF...-NA
P
R
P
In [A]
[W]
[Ohm]
[W]
1.2
1.6
2
2.4
3
5
8
12
15
18
20
25
26
30
32
33
35
40
45
50
60
63
70
80
90
100
110
125
150
160
175
200
225
250

9.8
8.8

9.1

11

13.5

14

15.5

24

38

50

Note:

The values stated in the table apply for fixed mounted 3 pole devices which are loaded uniformly.
The entire resistive load is for the measured three-pole or four-pole value.
The total heat dissipation is the measured value for In at 50/60 Hz for a 3-pole switch.
The heat dissipation can be calculated using the fromula: P = 3 x R x I

8180
4680

3030

2220

1760

1190

850

730

570

460

5.5

9.8
8.8

8.2

8.2
11
10.7
13.5
12.9

12.5
15.5
17.7
24
20.7
38

NZM up to 1200 A with electronic release (3 pole)


Fixed mounted Additional
Fixed mounted
Plug-in units
NZM2NZM3N3-

R
[Ohm]

S...-CNA
P
[W]

R
[Ohm]

NS1...-NA
P
[W]

8180

8180
4680

3030

2220
2220
1760
1760
1190

850
850
730
730
570
570

1.2

0.5

1.1
0.4
1
0.5

1.3

3.2

2.7

4.2

6.7

10.8

16.9

413000

66000

66000
9180
9180
1670

1670

1050

1050

562

562

562

562

562

6.7

16.9

26.3

R
[Ohm]

R
[Ohm]

R
[Ohm]

Additional
Withdrawable
units
R
[Ohm]

275

100

100

90

70

Note:

The values stated in the table apply for 3 pole devices which are loaded uniformly.
The total resistive load is the measured value for a 3 pole switch
(independent of In and the type of release).
The total resistive load for a switch in fixed or withdrawable design results from:
the resistive value for fixed mounting + resistive value for plug-in or withdrawable design.
The heat dissipation can be calculated using the fromula: P = 3 x R x I

R
[Ohm]

Fixed mounted
NZM4N4R
[Ohm]

R
[Ohm]

Additional
Withdrawable
units
R
[Ohm]

37

37

10

Moeller SK1230-1157EN-NA

R
[Ohm]

Fixed mounted
NZM2A...-NA
P
R
[W]
[Ohm]

AF...-NA
P
[W]

562

562

562

5.1
8

10

13

18

20

22

28

29

40

48

57

5.1
6

11
13
15
18
19

17
22
23
28
22
29
35

37
48
46
57

4250
4250

3140

2800

2270

1700

1070

855

589

427

332

310

R
[Ohm]

S...-CNA
P
[W]

4250

4250
3140

3140

2800
2800
2270
2270
1700

1070
1070
855
855
589
589
427

332
332
310
310

6.2

8.4

0.2
0.5
0.4

0.5

0.9

1.5

2.5

10

15

25

40

59.4

R
[Ohm]

NS2...-NA
P
[W]

R
[Ohm]

750000

450000

4600
4600
1200

1200

780

780

317

317

317

317

317

317

317

317

317

25

40

59.4

317

317

317

For Immediate Delivery call KMParts.com at (866) 595-9616

111

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

110

SK1157_112-113_e_G-g.fm Page 112 Thursday, June 8, 2006 3:29 PM

Technical data
Terminal capacities

Technical data
Terminal capacities
Moeller SK1230-1157EN-NA

Cu conductors, Cu cable
Box terminal

Tunnel terminal

In1)
A

NZM2, NS2
250 A

In1)
A

NZM3, N3, NS3


600 A

In1)
A

NZM4, N4, NS4


1200 A

In1)
A

Box terminal
Screw connection
Tunnel terminal
Connection on
rear

Screw terminal
Box terminal
Tunnel terminal
Connection on
rear

Screw terminal
Box terminal
Tunnel terminal
Connection on rear

Screw terminal
Tunnel terminal
Connection on rear
Strip terminal

125

2 x 16

500

250

1 x (4 16)
2 x (4 16)
1 x (25 185)
2 x (25 70)
1 x (16 185)
1 x (25 185)

250

mm2
mm2
mm2

1 x (10 16)
2 x (6 16)
1 x (25 70)3)
2 x 25
1 x 16
1 x (25 95)

mm2

1 x (35 240)
2 x (25 120)

1 x (25 185)
1 x (50 240)
2 x (50 240)

mm2

1 x (10 16)
2 x (6 16)
1 x (25 70)3)
2 x 25

125

1 x (4 16)
2 x (4 16)
1 x (25 185)
2 x (25 70)

250

Solid

mm2

Stranded

mm2

Solid
Stranded

Single hole
Double hole
fitting
4-hole

Bolt terminal and rear-side connection


Direct on the Solid
switch
Stranded
Module plate Single hole
Module plate Double hole

mm2
min.
max.
min.
max.

Connection width extension


Al conductors, Al cable
Tunnel terminal

Solid
Stranded

mm2
mm2
mm2

1 x 16
1 x (25 95)

125

mm2
mm2

Module plate

1 x (10 16)
2 x (10 16)
1 x (25 35)
2 x (25 35)

125

1 x (10 16)
2 x (10 16)
1 x (25 50)
2 x (25 50)

250

2 x 9 x 0.8
9 x 9 x 0.8

125

2 x 9 x 0.8
10 x 16 x 0.8

250

mm
mm
mm2

mm
mm

2 x 16 x 0.8
10 x 16 x 0.8

250

mm2

min.
max.

mm2
mm2

M6
12 x 5
16 x 5

125

M8
16 x 5
20 x 5

250

min.
max.

mm2
mm2
mm2
mm2
mm2

mm2
min.
max.

Single hole

min.
max.

Connection width extension


Copper busbar (width x thickness)
Bolt terminal and rear-side connection
Screw connection
Direct on the switch

Module plate Single hole


Module plate Double hole
Connection width extension
Notes

min.
max.

Bolt terminal and rear-side connection


Flat copper strip, with holes
Flat copper strip, with holes

mm2
mm2
mm2
mm2

Cu strip (number of segments x width x segment thickness)


Box terminal
min.
mm2
max.
mm2
Flat conductor terminal

250

250

Bolt terminal and rear-side connection


Direct on the Solid
switch
Stranded
Module plate Single hole
Single hole
Module plate Double hole
Connection width extension

mm2
mm2
mm2
mm2
mm2

125

1 x 16
1 x (25 185)

Single hole
Double hole
fitting
4-hole

min.
max.

Moeller SK1230-1157EN-NA

NZM1, NS1
125 A
Terminal capacities
Standard equipment
Accessories

113

NZM...1...NA,
NS1...NA

NZM...2...NA,
NS2...NA

NZM...3...NA,
N3...NA, NS3...NA

NZM...4...NA,
N4...NA, NS4...NA

Box terminal
Screw connection
Tunnel terminal
Connection on rear

Screw terminal
Box terminal
Tunnel terminal
Connection on rear

Screw terminal
Box terminal
Tunnel terminal
Connection on rear

Screw terminal
Tunnel terminal
Connection on rear
Strip terminal

AWG

1 x (12 6)

1 x (12 6)

AWG/kcmil

1 x (4 2/0)

1 x (4 350)

1 x (2 500)

350
600

AWG
AWG/kcmil
AWG/kcmil

1x6
1 x (4 3/0)

1x6
1 x (4 350)

4 x (50 240)

1200

AWG/kcmil

1x6
1 x (4 350)
1 x (0 500)
2 x (0 500)

1 x 16
2 x 16
1 x (25 240)
2 x (25 240)

2 x 300

600

AWG

1 x (12 6)

1 x (120 185)
4 x (50 185)
1 x (120 300)
2 x (95 300)
2 x (95 185)
4 x (35 185)
4 x 300
6 x (95 240)

1200

AWG/kcmil

1 x (12 6)
2 x (9 6)
1 x (4 2/0)

1 x (4 3/0)

1 x (4 350)

1000

1200

kcmil
AWG/kcmil
AWG/kcmil
AWG/kcmil
AWG/kcmil

2 x 500

1 x (250 350)
4 x (0 350)
1 x (250 600)
2 x (3/0 600)
2 x (3/0 350)
4 x (2 350)
4 x 600
6 x (3/0 500)

1 x 16
1 x (25 185)2)
1 x (50 240)
2 x (50 240)

350
600

AWG
AWG/kcmil
AWG/kcmil

4 x (50 240)

1200

AWG/kcmil

1 x 16
2 x (10 16)
1 x (25 120)
2 x (25 120)

400

AWG

AWG/kcmil

1 x (185 240)
2 x (70 185)
4 x 50
2 x 240
6 x (70 240)

on request
on request

on request

kcmil
AWG/kcmil
AWG
AWG/kcmil

6 x 16 x 0.8
10 x 24 x 1.0
+ 5 x 24 x 1.0
(2 x) 8 x 24 x 1.0

600

mm
mm

2 x 9 x 0.8
9 x 9 x 0.8

2 x 9 x 0.8
10 x 16 x 0.8

6 x 16 x 0.8
(2 x) 10 x 32 x 1.0
(2 x) 10 x 50 x 1.0

1100

mm
mm
mm

6 x 16 x 0.8
10 x 24 x 1.0
+ 5 x 24 x 1.0
(2 x) 8 x 24 x 1.0

6 x 16 x 0.8
10 x 32 x 1.0 + 5
x 32 x 1.0
(2 x) 10 x 50 x 1.0

600

(2 x) 10 x 50 x 1.0
(2 x) 10 x 50 x 1.0

1200

mm
mm

2 x 16 x 0.8
10 x 16 x 0.8

(2 x) 10 x 50 x 1.0
(2 x) 10 x 50 x 1.0

(2 x) 10 x 80 x 1.0

1200

mm

6 x 16 x 0.8
10 x 32 x 1.0 + 5
x 32 x 1.0
(2 x) 10 x 50 x 1.0

M10
20 x 5
30 x 10
+30 x 5

2 x (10 x 50)

600

M10
25 x 5
2 x (50 x 10)

1200

mm
mm

M6
12 x 5
16 x 5

M8
16 x 5
20 x 5

M10
25 x 5
2 x (50 x 10)

600

25 x 5
2 x (50 x 10)
2 x (50 x 10)
60 x 10
2 x (80 x 10)

1200

mm
mm
mm
mm
mm

M10
20 x 5
30 x 10
+30 x 5

2 x (10 x 50)

1) The

600

rated currents In have been determined conform to IEC/EN 60947 (switchgear standard) and generally relate to the max. defined cross-sections and
are intended for the purpose of orientation. The engineering standards which apply in each case must be observed.
2) depending on the cable manufacturer up to 240 mm can be connected.
3) depending on the cable manufacturer up to 95 mmB can be connected.

For Immediate Delivery call KMParts.com at (866) 595-9616

1200

1200

1200
1200

4 x (0 500)

6 x 16 x 0.8
(2 x) 10 x 32 x 1.0
(2 x) 10 x 50 x 1.0

(2 x) 10 x 80 x 1.0

25 x 5
2 x (50 x 10)
2 x (50 x 10)
60 x 10
2 x (80 x 10)

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

112

SK1157_112-113_e_G-g.fm Page 112 Thursday, June 8, 2006 3:29 PM

Technical data
Terminal capacities

Technical data
Terminal capacities
Moeller SK1230-1157EN-NA

Cu conductors, Cu cable
Box terminal

Tunnel terminal

In1)
A

NZM2, NS2
250 A

In1)
A

NZM3, N3, NS3


600 A

In1)
A

NZM4, N4, NS4


1200 A

In1)
A

Box terminal
Screw connection
Tunnel terminal
Connection on
rear

Screw terminal
Box terminal
Tunnel terminal
Connection on
rear

Screw terminal
Box terminal
Tunnel terminal
Connection on rear

Screw terminal
Tunnel terminal
Connection on rear
Strip terminal

125

2 x 16

500

250

1 x (4 16)
2 x (4 16)
1 x (25 185)
2 x (25 70)
1 x (16 185)
1 x (25 185)

250

mm2
mm2
mm2

1 x (10 16)
2 x (6 16)
1 x (25 70)3)
2 x 25
1 x 16
1 x (25 95)

mm2

1 x (35 240)
2 x (25 120)

1 x (25 185)
1 x (50 240)
2 x (50 240)

mm2

1 x (10 16)
2 x (6 16)
1 x (25 70)3)
2 x 25

125

1 x (4 16)
2 x (4 16)
1 x (25 185)
2 x (25 70)

250

Solid

mm2

Stranded

mm2

Solid
Stranded

Single hole
Double hole
fitting
4-hole

Bolt terminal and rear-side connection


Direct on the Solid
switch
Stranded
Module plate Single hole
Module plate Double hole

mm2
min.
max.
min.
max.

Connection width extension


Al conductors, Al cable
Tunnel terminal

Solid
Stranded

mm2
mm2
mm2

1 x 16
1 x (25 95)

125

mm2
mm2

Module plate

1 x (10 16)
2 x (10 16)
1 x (25 35)
2 x (25 35)

125

1 x (10 16)
2 x (10 16)
1 x (25 50)
2 x (25 50)

250

2 x 9 x 0.8
9 x 9 x 0.8

125

2 x 9 x 0.8
10 x 16 x 0.8

250

mm
mm
mm2

mm
mm

2 x 16 x 0.8
10 x 16 x 0.8

250

mm2

min.
max.

mm2
mm2

M6
12 x 5
16 x 5

125

M8
16 x 5
20 x 5

250

min.
max.

mm2
mm2
mm2
mm2
mm2

mm2
min.
max.

Single hole

min.
max.

Connection width extension


Copper busbar (width x thickness)
Bolt terminal and rear-side connection
Screw connection
Direct on the switch

Module plate Single hole


Module plate Double hole
Connection width extension
Notes

min.
max.

Bolt terminal and rear-side connection


Flat copper strip, with holes
Flat copper strip, with holes

mm2
mm2
mm2
mm2

Cu strip (number of segments x width x segment thickness)


Box terminal
min.
mm2
max.
mm2
Flat conductor terminal

250

250

Bolt terminal and rear-side connection


Direct on the Solid
switch
Stranded
Module plate Single hole
Single hole
Module plate Double hole
Connection width extension

mm2
mm2
mm2
mm2
mm2

125

1 x 16
1 x (25 185)

Single hole
Double hole
fitting
4-hole

min.
max.

Moeller SK1230-1157EN-NA

NZM1, NS1
125 A
Terminal capacities
Standard equipment
Accessories

113

NZM...1...NA,
NS1...NA

NZM...2...NA,
NS2...NA

NZM...3...NA,
N3...NA, NS3...NA

NZM...4...NA,
N4...NA, NS4...NA

Box terminal
Screw connection
Tunnel terminal
Connection on rear

Screw terminal
Box terminal
Tunnel terminal
Connection on rear

Screw terminal
Box terminal
Tunnel terminal
Connection on rear

Screw terminal
Tunnel terminal
Connection on rear
Strip terminal

AWG

1 x (12 6)

1 x (12 6)

AWG/kcmil

1 x (4 2/0)

1 x (4 350)

1 x (2 500)

350
600

AWG
AWG/kcmil
AWG/kcmil

1x6
1 x (4 3/0)

1x6
1 x (4 350)

4 x (50 240)

1200

AWG/kcmil

1x6
1 x (4 350)
1 x (0 500)
2 x (0 500)

1 x 16
2 x 16
1 x (25 240)
2 x (25 240)

2 x 300

600

AWG

1 x (12 6)

1 x (120 185)
4 x (50 185)
1 x (120 300)
2 x (95 300)
2 x (95 185)
4 x (35 185)
4 x 300
6 x (95 240)

1200

AWG/kcmil

1 x (12 6)
2 x (9 6)
1 x (4 2/0)

1 x (4 3/0)

1 x (4 350)

1000

1200

kcmil
AWG/kcmil
AWG/kcmil
AWG/kcmil
AWG/kcmil

2 x 500

1 x (250 350)
4 x (0 350)
1 x (250 600)
2 x (3/0 600)
2 x (3/0 350)
4 x (2 350)
4 x 600
6 x (3/0 500)

1 x 16
1 x (25 185)2)
1 x (50 240)
2 x (50 240)

350
600

AWG
AWG/kcmil
AWG/kcmil

4 x (50 240)

1200

AWG/kcmil

1 x 16
2 x (10 16)
1 x (25 120)
2 x (25 120)

400

AWG

AWG/kcmil

1 x (185 240)
2 x (70 185)
4 x 50
2 x 240
6 x (70 240)

on request
on request

on request

kcmil
AWG/kcmil
AWG
AWG/kcmil

6 x 16 x 0.8
10 x 24 x 1.0
+ 5 x 24 x 1.0
(2 x) 8 x 24 x 1.0

600

mm
mm

2 x 9 x 0.8
9 x 9 x 0.8

2 x 9 x 0.8
10 x 16 x 0.8

6 x 16 x 0.8
(2 x) 10 x 32 x 1.0
(2 x) 10 x 50 x 1.0

1100

mm
mm
mm

6 x 16 x 0.8
10 x 24 x 1.0
+ 5 x 24 x 1.0
(2 x) 8 x 24 x 1.0

6 x 16 x 0.8
10 x 32 x 1.0 + 5
x 32 x 1.0
(2 x) 10 x 50 x 1.0

600

(2 x) 10 x 50 x 1.0
(2 x) 10 x 50 x 1.0

1200

mm
mm

2 x 16 x 0.8
10 x 16 x 0.8

(2 x) 10 x 50 x 1.0
(2 x) 10 x 50 x 1.0

(2 x) 10 x 80 x 1.0

1200

mm

6 x 16 x 0.8
10 x 32 x 1.0 + 5
x 32 x 1.0
(2 x) 10 x 50 x 1.0

M10
20 x 5
30 x 10
+30 x 5

2 x (10 x 50)

600

M10
25 x 5
2 x (50 x 10)

1200

mm
mm

M6
12 x 5
16 x 5

M8
16 x 5
20 x 5

M10
25 x 5
2 x (50 x 10)

600

25 x 5
2 x (50 x 10)
2 x (50 x 10)
60 x 10
2 x (80 x 10)

1200

mm
mm
mm
mm
mm

M10
20 x 5
30 x 10
+30 x 5

2 x (10 x 50)

600

1200

1200

1200
1200

1) The

rated currents In have been determined conform to IEC/EN 60947 (switchgear standard) and generally relate to the max. defined cross-sections and
are intended for the purpose of orientation. The engineering standards which apply in each case must be observed.
2) depending on the cable manufacturer up to 240 mm can be connected.
3) depending on the cable manufacturer up to 95 mmB can be connected.

For Immediate Delivery call KMParts.com at (866) 595-9616

4 x (0 500)

6 x 16 x 0.8
(2 x) 10 x 32 x 1.0
(2 x) 10 x 50 x 1.0

(2 x) 10 x 80 x 1.0

25 x 5
2 x (50 x 10)
2 x (50 x 10)
60 x 10
2 x (80 x 10)

Circuit-breakers, disconnect switches


up to 1200 A

Circuit-breakers, disconnect switches


up to 1200 A

112

SK1157_114_e_G-g.fm Page 114 Thursday, June 8, 2006 10:04 AM

Circuit-breakers, disconnect switches


up to 1200 A

114

Technical data
Auxiliary contact
Moeller SK1230-1157EN-NA

Auxiliary contacts
Rated operational voltage
AC
DC
Conventional thermal current
Rated operational current
AC-15 115 V
230 V
400 V
500 V
DC-13 24 V
42 V
60 V
110 V
220 V
Short-circuit protection
max. fuse
Max. miniature circuit-breaker
Early-make time compared to the main contacts
during switch on and off (switching times with
manual operation)

at AC = 50/60 Hz

M22-K...

XHIV

XHI

Ue
Ue
Ith = Ie

V AC
V DC
A

500
220
4

500
220
4

500
220
4

Ie
Ie
Ie
Ie
Ie
Ie
Ie
Ie
Ie

A
A
A
A
A
A
A
A
A

4
4
2
1
3
1.7
1.2
0.8
0.3

4
4
2
1
3
1.5
0.8
0.5
0.2

4
4
2
1
3

1.2
0.5
0.2

A gG/gL
A
ms

10
PKZM0-10/FAZ-B6

10
FAZ-B6
NZM1, PN1, N1: approx. 20
NZM2, PN2, N2: approx. 20
NZM3, PN3, N3: approx. 20
NZM4, N4: ca. 90
With NZM4/N4 the HIV does
not feature early break.

10
FAZ-B6

mm2

1 x (0.75 2.5)
2 x (0.75 2.5)
1 x (18 14)
2 x (18 14)

1 x (0.75 2.5)
2 x (0.75 2.5)
1 x (18 14)
2 x (18 14)

1 x (0.75 2.5)
2 x (0.75 2.5)
1 x (18 14)
2 x (18 14)

10 A 600 V AC
1 A 250 V DC
A600/P300
above 300 V AC same
polarity

2.5 A 240 V AC
1 A 250 V DC
C300/R300

2.5 A 240 V AC
1 A 250 V DC
C300/R300

Terminal capacities
Solid or flexible conductor with ferrule

AWG
UL/CSA
Rated operational current
Heavy Pilot Duty

Ie

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_115_e_G-m.fm Page 115 Monday, April 24, 2006 10:44 AM

Technical data
Fitted with auxiliary contacts, timer differences

115

Maximum component installation and position of the internal accessories


c
b
-XHIV
or -XA
or -XU
HIA

a
b
c

NZM1
NZM2
NZM3
NZM4

1
1
1
1

Circuit-breakers, disconnect switches


up to 1200 A

Moeller SK1230-1157EN-NA

HIN

1
1
1
2

1
2
3
3

Time differences ON-OFF


Main contact

Auxiliary contact, early-make (HIV)

b
Auxiliary contact, normal (HIN)

Time difference a (ms)


Manual operation
HIV
HIN
K10
K01

Motor operators
HIV
HIN
K10

K01

Time difference b (ms)


Manual operation
HIV
HIN
K10
K01

Motor operators
HIV
HIN
K10

K01

NZM1

202)

2.5

202)

2.5

NZM2

202)

3.5

6.5

NZM3

202)

NZM4

902)

11

Not permissible
Not permissible
Not permissible

2.5

4.5

202)

4.5

202)

3.5

6.5

on request

on request

01)2)

12

15

Not permissible
Not permissible
Not permissible

on request

on request

Notes

1) With

NZM4/N4 the HIV does not feature early break.


value, as it is dependent on the switching speed

2) Minimum

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_116-118_e_G-g.fm Page 116 Thursday, June 8, 2006 10:05 AM

Circuit-breakers, disconnect switches


up to 1200 A

116

Technical data
Undervoltage release, shunt release
Moeller SK1230-1157EN-NA

Undervoltage release
Rated control voltage
Alternating voltage at 50/60 Hz
DC
Operating range
Drop-out voltage
Pick-up voltage
Power consumption
AC
Sealing AC
DC
Sealing DC
Max. opening delay
(response time until the main circuits open)
Minimum command time
Terminal capacities
Solid or flexible conductor with ferrule

Us
Us

NZM1(2/3)-XU...

NZM4-XU...

V AC
V DC

24 600
12 250

24 600
12 250

x Us
x Us

0.35 0.7
0.85 1.1

0.35 0.7
0.85 1.1

VA

1.5

3.6

W
ms

0.8
19

2.5
23

ms

10 15

10 15

mm2

1 x (0.75 2.5)
2 x (0.75 2.5)
1 x (18 14)
2 x (18 14)

1 x (0.75 2.5)
2 x (0.75 2.5)
1 x (18 14)
2 x (18 14)

AWG

UVU-NZM
Undervoltage releases, off-delayed
Rated operational voltage
Alternating voltage at 50/60 Hz
DC
Inrush current (peak value)
Power consumption
Delay time
With additional external capacitor, 90.000 F f 35 V

V AC
V DC
mA
VA
ms
s

24, 220 550


24
< 500
50
70 4000
To 16

With additional external capacitor, 30.000 F f 35 V

To 8

Terminal capacities
Solid or flexible conductor with ferrule

mm2

1 x (0.5 2.5)
2 x (0.5 1.5)

Shunt release
Rated control voltage
AC
DC
Frequency range
Operating range
AC
DC
Power consumption
Sealing AC/DC
Maximum current consumption at 110% Us (230 V 50 Hz)
Maximum opening delay
(response time until opening of the main contacts)
Maximum duty factor
Minimum command time
Terminal capacities
Solid or flexible conductor with ferrule

Ue
Ue
Ie
tsd

Us
Us

NZM1(2/3)-XA...

NZM4-XA...

NZM2/3-XA...-MNS

NZM4-XA...-MNS

V AC
V DC
Hz

12 525
12 525
0 400

12 600
12 600
0 400

230

50/60

230

50/60

x Us
x Us

0.7 1.1
0.7 1.1

0.7 1.1
0.7 1.1

0.1 1.1

0.1 1.1

VA/W
A
ms

2.5

20

2.5

22

0.5
20

1
22

ms
ms

L
10 15

L
10 15

1000
10 15

1000
10 15

mm2

1 x (0.75 2.5)
2 x (0.75 2.5)
1 x (18 14)
2 x (18 14)

1 x (0.75 2.5)
2 x (0.75 2.5)
1 x (18 14)
2 x (18 14)

1 x (0.75 2.5)
2 x (0.75 2.5)
1 x (18 14)
2 x (18 14)

1 x (0.75 2.5)
2 x (0.75 2.5)
1 x (18 14)
2 x (18 14)

AWG

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_116-118_e_G-g.fm Page 117 Thursday, June 8, 2006 10:06 AM

Technical data
Remote operator, capacitor unit

Circuit-breakers, disconnect switches


up to 1200 A

Moeller SK1230-1157EN-NA
NZM-XCM
Capacitor unit for shunt release
Rated operational voltage
Rated operational current
Inrush current (peak value)
Terminal capacities
Solid or flexible conductor with ferrule

Ue
Ie
Ie

V AC
mA
A

230
< 10
3

mm2

1 x (0.5 2.5)
2 x (0.5 1.5)
1 x (20 14)
2 x (20 16)

AWG

Remote operator
Rated control voltage
AC
DC
Operating range
AC
DC
Motor rating
AC

DC

Us
Us

NZM2-XR...

NZM3-XR...

NZM4-XR...

110 440
24 250

110 440
24 250

110 440
24 250

0.85 1.1
0.85 1.1

0.85 1.1
0.85 1.1

0.85 1.1
0.85 1.1

VA
VA
VA
W
W
W
ms
ms

350
350
350
250
250
250
60
300

350
350
350
250
250
250
80
1000

350
350
350
250
250
250
100
3000

ms
ms
Ops./h

30
150
20000
120

30
250
15000
60

30
500
10000
20

mm2
AWG

0.75 2.5
18 14

0.75 2.5
18 14

0.75 2.5
18 14

V AC
V DC

Us
Us
110 V 130 V AC
208 V 240 V AC
380 V 440 V AC
24 V 30 V DC
110 V 130 V DC
220 V 250 V DC

Total make time


Total opening delay
Minimum signal duration
with switch on
with switch off
Lifespan, mechanical
Maximum operating frequency
Terminal capacities
Solid or flexible conductor with ferrule

Operations

117

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_116-118_e_G-g.fm Page 118 Tuesday, April 25, 2006 4:29 PM

Circuit-breakers, disconnect switches


up to 1200 A

118

Technical data
Data Management Interface (DMI Module)
Moeller SK1230-1157EN-NA
DMI

General
Dimensions (W x H x D)
Modular spacing (space units)
Weight
Mounting

mm
kg

Climatic environmental conditions


Operating ambient temperature
Mounting position
Condensation
LCD display (clearly legible)
Storage/Transport
Relative humidity, non-condensing (IEC/EN 60068-2-30)
Air pressure (operation)
Corrosion resistance
IEC/EN 60068-2-42
IEC/EN 60068-2-43
Ambient conditions, mechanical
Pollution degree
Degree of protection (IEC/EN 60529)
Vibrations (IEC/EN 60068-2-6)
Constant amplitude 0.15 mm
Constant acceleration 2 g
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms
Drop to IEC/EN 60068-2-31

4 days
SO2
4 days
H2S

C
C
%
hPa

0 to +55
horizontal, vertical
Prevent condensation by means of suitable measures
0 to +55
-40 to +70
5 95
795 1080

cm3/m3

10

cm3/m3

2
IP20

Drop
height

Free fall, packaged (IEC/EN 60068-2-32)


Power supply
Rated operational voltage
Admissible range
Residual ripple
Input current at 24 V DC
Voltage dips (IEC/EN 61131-2)
Heat dissipation at 24 V DC

107.5 x 90 x 53
6 space units wide
0.3
Top-hat rail IEC/EN 60715, 35 mm

Ue

Hz
Hz
Impacts
mm

10 57
57 150
18
50

V
V DC
%
mA
ms
W

24
20.4 28.8
F5
210
10
5

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_119-120_e_G-m.fm Page 119 Monday, April 24, 2006 10:45 AM

119

Moeller SK1230-1157EN-NA
EASY221-CO
General
Standards
Dimensions (W x H x D)

mm

Weight
Mounting
Terminal capacity
Solid
Flexible with ferrule
Flat-bladed screwdriver
Max. tightening torque
Climatic environmental conditions
Operating ambient temperature
Condensation
Storage
Relative humidity, non-condensing (IEC/EN 60068-2-30)
Atmospheric pressure (operation)
Corrosion resistance
IEC/EN 60947-2-42
IEC/EN 60068-2-43
Mechanical environmental conditions
Pollution degree
Degree of protection (IEC/EN 60529)
Vibrations (IEC/EN 60068-2-6)
Constant amplitude 0.15 mm
Constant acceleration, 2 g
Mechanical shock resistance (IEC/EN 60068-2-27)
semi-sinusoidal 15 g/11 ms
Drop to IEC/EN 60068-2-31
Free fall, packaged (IEC/EN 60068-2-32)
Mounting position
Electromagnetic compatibility (EMC)
Electrostatic discharge (IEC/EN 61000-4-2, Level 3, ESD)
Air discharge
Contact discharge
Electromagnetic fields (IEC/EN 61000-4-3, RFI)
Radio interference suppression (EN 55011)
Burst impulses (IEC/EN 61000-4-4, level 3)
Power lines
Signal cables
Immunity to line-conducted interference (IEC/EN 61000-4-6)

4 days SO2
4 days H2S

Drop height

EASY222-DN

NZM-XDMI-DPV1

EN 55011, EN 55022, EN 61000-4, IEC 60068-2-6, IEC 60068-2-27


35.5 x 90 x 58 (2 SU)
35.5 x 90 x 58 (2 SU)
35.5 x 90 x 58 (2 SU)

kg

0.15
0.15
0.15
Top-hat rail IEC/EN 60715, 35 mm or screw fixing using fixing brackets
ZB4-101-GF1 (accessories)

mm2
mm2
mm
Nm

0.2x4 (AWG 22 12)


0.2x2.5 (AWG 22 12)
3.5 x 0.8
0.6

C
C
%
hPa

-25 to 55, cold as per IEC 60068-2-1, heat as per IEC 60068-2-2
Prevent condensation by means of suitable measures
40 70
40 70
40 70
5 95
5 95
5 95
795 1080
795 1080
795 1080

cmC/mC
cmC/mC

10
1

10
1

10
1

2
IP20

2
IP20

2
IP20

Hz
Hz
Impacts

10 57
57 150
18

10 57
57 150
18

10 57
57 150
18

mm

50

50

50

1
Horizontalxvertical

1
Horizontalxvertical

1
Horizontalxvertical

kV
kV
V/m

8
6
10
EN 55011 class B,
EN 55022 class B

8
6
10

8
6
10
EN 55011 class A,
EN 55022 class A

kV
kV
kV
V

2
2
2
2
0.5 (power line symmetry)
10
10

0.2x4 (AWG 22 12)


0.2x2.5 (AWG 22 12)
3.5 x 0.8
0.6

For Immediate Delivery call KMParts.com at (866) 595-9616

0.2x4 (AWG 22 12)


0.2x2.5 (AWG 22 12)
3.5 x 0.8
0.6

2
2
10

Circuit-breakers, disconnect switches


up to 1200 A

Technical data
Fieldbus connection

SK1157_119-120_e_G-m.fm Page 120 Monday, April 24, 2006 10:45 AM

Circuit-breakers, disconnect switches


up to 1200 A

120

Technical data
Fieldbus connection
Moeller SK1230-1157EN-NA
EASY221-CO

Dielectric strength
Rating of the air and
creepage distance
Dielectric strength
Power supply
Rated operational voltage
Admissible range
Residual ripple
At 24 V DC
Voltage dips (IEC/EN 61131-2)

EASY222-DN

NZM-XDMI-DPV1

EN 50178, UL 508, CSA C22.2, No. 142


EN 50178
Ue

V
V DC
%
mA
ms

24 (-15/+20 %)
20.4 28.8
<5
Averaged 200
10

24 (-15/+20 %)
20.4 28.8
<5
Averaged 200
10

24 (-15/+20 %)
20.4 28.8
<5
Averaged 200
10

4.8

4.8

4.8

Protection against polarity reversal


Power supply

Yes

Yes

Yes

LED displays
Power supply
LED display

LED RUN (RUN): green


LED ERROR (ERR): red

LED module status (MS): green


LED network status (NS):
red/green

LED power (POW): green


LED-PROFIBUS-DP (BUS): red

Network
Connection types

RJ45

5-pole, twin-level terminal block

Potential isolation

Bus to power supply (simple,


bus and power supply to EASY
base unit (safe isolation)

Bus to power supply (simple,


bus and power supply to EASY
base unit (safe isolation)

Function
Interface
Bus protocol
Baud rates

CANopen slave
CAN
CANopen
Automatic detection up to 1
MBitxs
Separate, external bus connection
necessary (120 O)
1 127 via EASY base unit with
display or EASY-SOFT addressable

DeviceNet slave
CAN
DeviceNet
Automatic detection up to 500
kBitxs
Separate, external bus connection
necessary (120 O)
0 63 via EASY base unit with
display or EASY-SOFT addressable

All data R1 R16, S1 S8


Readxwrite, time, day,
summer-xwinter time, all
parameters of the EASY function

All data R1 R16, S1 S8


Readxwrite, time, day,
summer-xwinter time, all
parameters of the EASY function

PROFIBUS-DP
Connection types
Potential isolation

Sub-D 9 pole, socket


Bus to power supply (simple),
bus and power supply to DMI base
unit (safe isolation)

Function
Interface
Bus protocol
Baud rates

Bus termination resistors


Bus addresses

PROFIBUS-DP slave
RS 485
PROFIBUS-DP
Automatic detection up to
12 MBitxs
Switch-in via connector
1 126 via DMI

Heat dissipation at 24 V DC

Bus termination resistors


Bus addresses

Services
Cyclic
Acyclic

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_121_e_G-m.fm Page 121 Thursday, June 8, 2006 10:09 AM

Technical data
Direction of blow-out, minimum clearances, pipe cable lugs

121

Circuit-breakers, disconnect switches


up to 1200 A

Moeller SK1230-1157EN-NA
Direction of blow-out

NZM1
NZM2
NZM3
NZM4

Top
Front
X
X
X
X

Bottom
Rear

X
X

Minimum clearance

Between two switches mounted side-by-side


Minimum clearance a in mm

NZM1
NZM2
NZM3
NZM4

NZM1
0
5
5
15

NZM2
5
5
5
15

NZM3
5
5
5
15

NZM4
15
15
15
15

1000 V

35
60
200

d
F 690 V
0
35
60
0

Between switch and other components


Minimum clearance in mm

NZM1
NZM2
NZM3
NZM4

b
F 690 V
0
5
5
15

c
F 690 V
60
35
60
100

Dimensions

Cable lug

KS95-NZM7
KS120-NZM7
KS150-NZM7
NZM2-XKS185
NZM3-XKS185
NZM3-XKS240

For use with

Nominal
cross-section
mm2
NZM2
95
NZM2
120
NZM2
150
NZM2
185
NZM3, NZM4 185
NZM3, NZM4 240

Terminal bolts
o
M8
M8
M8
M8
M10
M10

Dimensions
in mm
a
b
23g0.5
53+2
23g0.5
56+2
61+2
23g0.5
22g1
65g1.5
65
24,5
72
31

c
18g0.2
19.5g0.2
21g0.2
24g0.3
24
26

d
10g1
10g1
10g1
9+1
0,5
11,5
11,5

e
19
19
19
19+2,5
0,5
18
19

f
8,5
8,5
8,5
8,5+0,05
0,1
10,5
10,5

g
25
26
30
30g2
30
35

For Immediate Delivery call KMParts.com at (866) 595-9616

h
13,5
15
16,5
19g0.4
19
21

i
4,4
4,4
4,4
7
7.0g0.8
5.0g0.8

SK1157_122_h_G-g.fm Page 122 Tuesday, April 25, 2006 4:32 PM

Circuit-breakers, disconnect switches


up to 1200 A

122

Engeneering
Mechanical interlock
Moeller SK1230-1157EN-NA

Interlocking variants combination options

x4P

NZM1
NZM2
NZM3
NZM4

3 pole
3 pole
3 pole
3 pole

NZM-XBZ600
Max. switch clearance

NZM1
NZM2
NZM3
NZM4

3 pole
3 pole
3 pole
3 pole

NZM-XBZ1000
Max. switch clearance

NZM1
NZM2
NZM3
NZM4

3 pole
3 pole
3 pole
3 pole

OFF
ON/TRIP
ON

OFF
ON
ON/TRIP

OFF
ON
ON/TRIP

OFF
ON/TRIP
ON

OFF
ON
ON/TRIP

OFF
ON/TRIP
ON
ON

OFF
ON
ON/TRIP
ON

OFF
ON
ON
ON/TRIP

OFF
ON/TRIP
ON

OFF
ON
ON/TRIP

OFF
ON/TRIP
ON

OFF
ON
ON/TRIP

X3p = 3 pole switch clearance

x4P
x3P

x3P

NZM-XBZ225
Max. switch clearance

NZM1
X3P
mm
135
135
90
50

NZM2
X3P
mm
120
120
75
40

NZM3
X3P
mm
135
135
85
25

NZM4
X3P
mm
125
125
80
15

NZM1
X3P
mm
510
510
460
400

NZM2
X3P
mm
495
495
450
380

NZM3
X3P
mm
510
510
460
400

NZM4
X3P
mm
475
475
460
390

NZM1
X3P
mm
910
910
820
750

NZM2
X3P
mm
895
895
850
730

NZM3
X3P
mm
910
910
860
800

NZM4
X3P
mm
865
865
860
790

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_123-124_h_G-m.fm Page 123 Thursday, May 4, 2006 6:47 PM

Engineering
Mechanical interlock for remote operator

Circuit-breakers, disconnect switches


up to 1200 A

Moeller SK1230-1157EN-NA

x4P
x3P

Mechanical interlock, XMVR


(mounting side-by-side)
NZM...-XMVR
Max. switch clearance

NZM2
NZM3
NZM4

3 pole
3 pole
3 pole

NZM2
3 pole

NZM3
3 pole

NZM3
3 pole

NZM4
3 pole

NZM4
3 pole

130
95

135

135

200
160

200
160

NZM3
3 pole

NZM4
3 pole

NZM4
3 pole

on request

on request
on request

on request
on request

Mechanical interlock, XMVRL


(mounting in adjacent control panel sections)
NZM...-XMVRL
Max. switch clearance
NZM2
NZM3
3 pole
3 pole
NZM2
NZM3
NZM4

3 pole
3 pole
3 pole

123

on request
on request

on request

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_123-124_h_G-m.fm Page 124 Thursday, May 4, 2006 6:48 PM

Notes

Moeller SK1230-1157EN-NA

Circuit-breakers, disconnect switches


up to 1200 A

124

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_125-133_f_G.fm Page 125 Thursday, May 4, 2006 6:50 PM

Dimensions
Circuit-breakers, disconnect switches

Circuit-breakers, disconnect switches


up to 1200 A

Moeller SK1230-1157EN-NA
Circuit-breaker, disconnect switch, 3-pole
NZMB1, NZMN1, NZMH1, N1, NS1
84.5
NZM...1-...-(C)NA

21

57

41.5

04
R1

45

145

126

112

64

9.5

16

10.2

30

68

f 60

m
ax
.9

63

F
90

162
M4 x 50/10

SW4

30
90

125

44.6

a Blow out area, minimum clearance to other partsf 60 mm

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_125-133_f_G.fm Page 126 Thursday, May 4, 2006 6:50 PM

Dimensions
Circuit-breakers, disconnect switches
Moeller SK1230-1157EN-NA

Cover for screw terminals


NZM1-XKSA
Screw connection
NZM1-XKS
IP2X protection against contact with a finger
NZM1-XIPA
21
4

16
IP2X

M6 x 14

34

158

296

64

26

SW 4

80
90 a

59

120 b

a 3-pole
b 4-pole
NZM1 tunnel terminal
NZM1-XKA
20

20

SW 5
M6 x 14

64

SW 4

32

48

Circuit-breakers, disconnect switches


up to 1200 A

126

90 a
b
120

a 3-pole
b 4-pole

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_125-133_f_G.fm Page 127 Thursday, May 4, 2006 6:50 PM

Dimensions
Circuit-breakers, disconnect switches

127

Circuit-breakers, disconnect switches


up to 1200 A

Moeller SK1230-1157EN-NA
Connection on rear
NZM1-XKR
30

30
30

30

15
o 22

M6 x 14

63

64

SW 4

50

128

10

126

102

18

10

o 6.6
120

M4

30

25

90

30
M6 x 20

15

15

Control circuit terminal


NZM-XSTK, NZM1-XSTS

128

126

63

o 22

M4

IP2X protection against contact with a finger


NZM1-XIPK

64

76

91

108
89
90 a
120 b

10

13

46

90 a
120 b

a 3-pole
b 4-pole

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_125-133_f_G.fm Page 128 Thursday, June 8, 2006 10:10 AM

Dimensions
Circuit-breakers, disconnect switches
Moeller SK1230-1157EN-NA

Rotary handle for circuit-breaker


NZM1-XDV(R)

NZM1-XDTV

36

54

45

F 43

80.3

90

45
90
120

d=48
b f 34

a Up to 3 padlocks
Door coupling rotary handle
NZM1-XT(V)D(V)(R)
73.5
27.5
8

71

40

85

23

o8

ZFS...-NZM7

6
R4
71
85

25

35

Circuit-breakers, disconnect switches


up to 1200 A

128

d=48
b f 34

a Up to 3 padlocks

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_125-133_f_G.fm Page 129 Thursday, May 4, 2006 6:50 PM

Moeller SK1230-1157EN-NA
Door coupling rotary handle with extension shaft
NZM1-XT(V)D(V)(R)(-NA)
NZM1/2-XV4(6)
73

25
27

X
8

o 45

55

NZM1/2-XV4(6)

NZM1/2-XV4
NZM1/2-XV6

23g0.5

36

x
210 400
400 600

NZM1-XT(V)D(V)(R)-60(-NA)

NZM1-XT(V)D(V)(R)-0(-NA)
41 75

16 60

a
NZM1/2-XV...
167 210

23g0.5

128 167

a Special tip
Minimum door coupling rotary handle clearance from door pivot point

NZM...1-... f 130

For Immediate Delivery call KMParts.com at (866) 595-9616

23g0.5

129

Circuit-breakers, disconnect switches


up to 1200 A

Dimensions
Circuit-breakers, disconnect switches

SK1157_125-133_f_G.fm Page 130 Thursday, June 8, 2006 10:11 AM

Dimensions
Circuit-breakers, disconnect switches
Moeller SK1230-1157EN-NA

Main switch assembly kit for side wall installation


NZM1-XS(R)-L

2-5

129

12

73.5

95-310

90

NZM1-XS(R)-R

51.5

41

12
95-310

15

129

2-5

90

73.5

Main switch assembly kit for side panel mounting with mounting bracket
NZM1-XS(R)M-L

145

NZM1/2-XZB

2-5

12

73.5

131.4

57.2

176
163

178.5

195.5

NZM1-XS(R)M-R

145

Circuit-breakers, disconnect switches


up to 1200 A

130

NZM1/2-XZB

12

2-5
57.2

163

131.4
73.5

176
178.5

195.5

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_125-133_f_G.fm Page 131 Thursday, June 8, 2006 10:12 AM

Moeller SK1230-1157EN-NA
Undervoltage release, shunt release, early-make auxiliary contact
a NZM1-XA(HIV)
NZM1-XU(HIV)(20)
NZM1-XHIV
b NZM1-XA(HIV)(L)
NZM1-XU(V)(HIV)(L)(20)
NZM1-XHIV(L)
c NZM1-XHIVR

23.2

38.6

39.3

20

39.3

20

Spacers
NZM1/2-XAB

Clip plates
NZM1-XC35
9.5

103
35

157

126

30

145

17.5

8.4

90

For Immediate Delivery call KMParts.com at (866) 595-9616

131

Circuit-breakers, disconnect switches


up to 1200 A

Dimensions
Circuit-breakers, disconnect switches

SK1157_125-133_f_G.fm Page 132 Thursday, May 4, 2006 6:50 PM

Dimensions
Circuit-breakers, disconnect switches
Moeller SK1230-1157EN-NA

Insulating surround
NZM1-XBR

Mounting aperture
9.5
1.5 5

53

82

64

ZFS...-NZM7

132
23

117

11.5

148.5

19

Rotary handle on switch with door interlock


NZM1-XDTV(R)

Mounting aperture
32
9.5
1.5 5
14.4
9

53

40

11

o4

132

11.5
19

45

Toggle lever interlock device


NZM1-XKAV

d=48
b f 34

a Up to 3 padlocks

46.3

Circuit-breakers, disconnect switches


up to 1200 A

132

32

F 80

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_125-133_f_G.fm Page 133 Thursday, June 8, 2006 10:14 AM

Dimensions
Circuit-breakers, disconnect switches

Circuit-breakers, disconnect switches


up to 1200 A

Moeller SK1230-1157EN-NA
Mechanical interlock
NZM1-XMV with NZM1-XDV(R)

133

R1

40

31

22.5

45

27

51

80.3

29.2

7
5

45

40

90
143

120

40

NZM1-XMV with NZM1-XT(V)D(V)(R)


NZM1/2-XV4(6)

NZM1/2-XV4
NZM1/2-XV6

NZM1-XMV with NZM1-XT(V)D(V)(R)-60

NZM1-XMV with NZM1-XT(V)D(V)(R)-0

NZM1/2-XV...

202 245

163 202

a Special tip

For Immediate Delivery call KMParts.com at (866) 595-9616

x
245 400
400 600

SK1157_134-147_f_G.fm Page 134 Thursday, June 8, 2006 10:15 AM

Dimensions
Circuit-breakers, disconnect switches
Moeller SK1230-1157EN-NA

Circuit-breaker, disconnect switch, 3-pole


NZMB2, NZMN2, NZMH2, NS2
149
NZM...2-...(C)NA

103

35

25

M8 x 22

90

184

145

95

R1

24

80

24.5

19.5

11

f 35

ba

135

72.5

100

F
90

a
f5

35

SW5
105

f 35

Circuit-breakers, disconnect switches


up to 1200 A

134

M4 x 85/20

64

78.7

f5

a Blow out area, minimum clearance to other partsf 35 mm


b Minimum clearance from adjacent parts f 5 mm

For Immediate Delivery call KMParts.com at (866) 595-9616

217

SK1157_134-147_f_G.fm Page 135 Thursday, June 8, 2006 10:16 AM

135

Moeller SK1230-1157EN-NA
Box terminal
(+)NZM2-...-XKC(O)(U)
IP2X protection against contact with a finger
NZM2-XIPK

Tunnel terminal
NZM2-XKA

30

25

65
25
19

F 22.1

M10

80

80

111

SW 5

37

20

55

SW 8

SW 5
105 a
140 b

a
b

105
140

a 3-pole
b 4-pole
Cover for screw terminals
NZM2-XKSA
Cable lug
NZM2-XKS185
IP2X protection against contact with a finger for shroud
NZM2-XIPA

M8 x 22

81

175

337

80

SW 5

105

87

140

For Immediate Delivery call KMParts.com at (866) 595-9616

M8 x 22

Circuit-breakers, disconnect switches


up to 1200 A

Dimensions
Circuit-breakers, disconnect switches

SK1157_134-147_f_G.fm Page 136 Thursday, May 4, 2006 6:57 PM

Dimensions
Circuit-breakers, disconnect switches
Moeller SK1230-1157EN-NA

Connection on rear
(+)NZM2-XKR(O)(U)
35

35

35
o 22

100
48

10

18

10

o 8.6

105

M4

17.5

35
70

140
35

35

M8 x 30

18
35

For Immediate Delivery call KMParts.com at (866) 595-9616

M4

160

145

72

80

o 30

160

145

72

80

80

SW 4

o 20

Circuit-breakers, disconnect switches


up to 1200 A

136

SK1157_134-147_f_G.fm Page 137 Thursday, June 8, 2006 3:26 PM

Dimensions
Circuit-breakers, disconnect switches

Circuit-breakers, disconnect switches


up to 1200 A

Moeller SK1230-1157EN-NA
Control circuit terminal
NZM2-XSTS, NZM-XSTK

105

100

a 3-pole
b 4-pole

105 a
140 b

Rotary handle for circuit-breaker


NZM2-XDV(R)

NZM2-XDTV(R)

59

100

95

75

F67

R4

52
104

d=48
b f 34

140

Door coupling rotary handle


NZM2-XT(V)D(V)(R)
d

73.5
27.5

d=48
b f 34

ZFS...-NZM7

71

40

85

23

o8

a Up to 3 padlocks

6
R4
71
85

137

35

25

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_134-147_f_G.fm Page 138 Thursday, May 4, 2006 6:57 PM

Dimensions
Circuit-breakers, disconnect switches
Moeller SK1230-1157EN-NA

Door coupling rotary handle with extension shaft


NZM2-XT(V)D(V)(R)(-NA)
NZM1/2-XV4(6)
73

25

NZM1/2-XV4
NZM1/2-XV6

x
245 400
400 600

27
8

o 45

55

17

Circuit-breakers, disconnect switches


up to 1200 A

138

NZM1/2-XV4(6)

NZM2-XT(V)D(V)(R)-60(-NA)

36

23g0.5

NZM2-XT(V)D(V)(R)-0(-NA)
41 75

16 60

NZM1/2-XV...

205 249

23g0.5

172 205

a Special tip
Minimum door coupling rotary handle clearance from door pivot point

NZM...2-... f 130

For Immediate Delivery call KMParts.com at (866) 595-9616

23g0.5

SK1157_134-147_f_G.fm Page 139 Thursday, June 8, 2006 10:19 AM

Dimensions
Circuit-breakers, disconnect switches

Circuit-breakers, disconnect switches


up to 1200 A

Moeller SK1230-1157EN-NA
Main switch assembly kit for side wall installation
NZM2-XS(R)-L

2-5
73.5

0.5
95-310

105

170.5

NZM2-XS(R)-R

51.5

41

0.5
105

15

2-5
95-310

139

73.5

170.5

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_134-147_f_G.fm Page 140 Thursday, May 4, 2006 6:57 PM

Dimensions
Circuit-breakers, disconnect switches
Moeller SK1230-1157EN-NA

Main switch assembly kit for side panel mounting with mounting bracket
NZM2-XS(R)M-L

185

NZM1/2-XZB

2-5
73.5

172.1

0.5

216

47.2

218.5

168
200.5

NZM2-XS(R)M-R

185

Circuit-breakers, disconnect switches


up to 1200 A

140

NZM1/2-XZB
0.5
47.2
168

172.1

2-5
73.5

216
218.5

200.5

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_134-147_f_G.fm Page 141 Thursday, May 4, 2006 6:57 PM

Dimensions
Circuit-breakers, disconnect switches

141

Spacers
NZM1/2-XAB

Circuit-breakers, disconnect switches


up to 1200 A

Moeller SK1230-1157EN-NA
Clip plates
NZM2-XC75

17.5

130
169

17.5

120.5

35

NZM1/2-XAB

105

NZM1/2-XAB

120.5

Insulating surround
NZM2-XBR

Mounting aperture
ZFS...-NZM7

9.5

103

64

132

1.5 5

142
127

23

158.5

10
17.5

Rotary handle on switch with door interlock


NZM2-XDTV(R)

Mounting aperture
32
10.4

9.5
9

1.5 5

o4

103

63

NZM2-XDTV(R)

142
10
17.5

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_134-147_f_G.fm Page 142 Thursday, May 4, 2006 6:57 PM

Dimensions
Circuit-breakers, disconnect switches
Moeller SK1230-1157EN-NA

Toggle lever interlock device


NZM2/3-XKAV
50

1.3

d=48
b f 34
92.5

a Up to 3 padlocks

F 88

NZM2, PN2, N2
NZM3, PN3, N3

a
52,5
70

Capacitor unit
NZM-XCM

60

78

50

M5 X 16

M4 X 16
115

100

85

Remote operator
NZM2-XR...
322.8
235.5
35

135
NZM2-XAVPR
21.5

7.2

105

F 13.7

250

105

52.5
105

140

a Up to 3 padlocks
b Remote operator folded

Circuit-breakers, disconnect switches


up to 1200 A

142

d=48
b f 34

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_134-147_f_G.fm Page 143 Thursday, June 8, 2006 10:20 AM

Dimensions
Circuit-breakers, disconnect switches

Circuit-breakers, disconnect switches


up to 1200 A

Moeller SK1230-1157EN-NA
Mechanical interlock
NZM2-XMV with NZM2-XDV(R)

143

R1

40

50

47.5

95

50

73

75

36

9.6

50
6

52.5

41

105
140

180

46

NZM2-XMV with NZM2-XT(V)D(V)(R)


NZM1/2-XV4(6)

NZM1/2-XV4
NZM1/2-XV6

For Immediate Delivery call KMParts.com at (866) 595-9616

x
280 400
400 600

SK1157_134-147_f_G.fm Page 144 Thursday, May 4, 2006 6:57 PM

Circuit-breakers, disconnect switches


up to 1200 A

144

Dimensions
Circuit-breakers, disconnect switches
Moeller SK1230-1157EN-NA

NZM2-XMV with NZM2-XT(V)D(V)(R)-60


NZM1/2-XV...

240 284

NZM2-XMV with NZM2-XT(V)D(V)(R)-0


a Special tip

207 240

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_134-147_f_G.fm Page 145 Thursday, May 4, 2006 6:57 PM

Dimensions
Circuit-breakers, disconnect switches

Circuit-breakers, disconnect switches


up to 1200 A

Moeller SK1230-1157EN-NA
Plug-in adapter elements
+NZM2-XSV
190.5
92.3
87.5

148.3

25

15.7

35

67.1

M8 x 22

NZM2(-4)-XSVE

M4 x 93
SW5
M4 x 85

78.7
105

140

For Immediate Delivery call KMParts.com at (866) 595-9616

241

184

237

396

205

109.7

57.5

NZM2(-4)-XSVS

35

145

SK1157_134-147_f_G.fm Page 146 Thursday, May 4, 2006 6:57 PM

Dimensions
Circuit-breakers, disconnect switches
Moeller SK1230-1157EN-NA

Data Management Interface (DMI Module)


NZM-XDMI612
75

16.25

16.25

45

110

90

102

M4

4.5
107.5

47.5
56.5
58

Undervoltage release, delayed


UVU-NZM

60

50

M5 X 16

78

Circuit-breakers, disconnect switches


up to 1200 A

146

M4 X 16
100

112

85

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_134-147_f_G.fm Page 147 Thursday, May 4, 2006 6:57 PM

Notes

Circuit-breakers, disconnect switches


up to 1200 A

Moeller SK1230-1157EN-NA

147

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_148-157_f_G.fm Page 148 Thursday, June 8, 2006 10:21 AM

Dimensions
Circuit-breakers, disconnect switches
Moeller SK1230-1157EN-NA

Circuit-breaker, disconnect switches, 3-pole


NZMN3, NZMH3, N3, NS3
166
NZM...3-...-4(C)NA

31

f 60

45

120.5

M10 x 30

29.5

20.5

11

275

234

95

123.5

R 205

28

135

216

117

90

F
90

45

SW5

a
f5

140

f 60

Circuit-breakers, disconnect switches


up to 1200 A

148

69.7

M5 x 75

315.5

f5

a Blow out area, minimum clearance to other partsf 60 mm


b Minimum clearance from adjacent parts f 5 mm

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_148-157_f_G.fm Page 149 Thursday, June 8, 2006 10:23 AM

149

Moeller SK1230-1157EN-NA
Box terminal
(+)NZM3-XKC(O)(U)
IP2X protection against contact with
NZM3-XIPK

Tunnel terminal
NZM3-XKA1(2)

54
25

32

27

75
26.5

31

F 18.7

124

124

172

25

35

SW 8

25

SW 8

M12

80

SW 8

SW 5

140
185
140
185

Cover for screw terminals


NZM3-XKSA
Cable lug
NZM3-XKS185
IP2X protection against contact with
NZM3-XIPA

M10 x 30

96

253

459

124

SW 8

140

103

185

For Immediate Delivery call KMParts.com at (866) 595-9616

M10 x 30

Circuit-breakers, disconnect switches


up to 1200 A

Dimensions
Circuit-breakers, disconnect switches

SK1157_148-157_f_G.fm Page 150 Thursday, May 4, 2006 7:28 PM

Dimensions
Circuit-breakers, disconnect switches
Moeller SK1230-1157EN-NA

Connection width extension


NZM3-XKV70
Terminals
NZM3-XK22X21
NZM3-XK300
70

70

45

26.5

37

33

70
o 13

43

70

20 50 18

24
6

70

50

M10 x 30

o 6.4

401

433

295

616

401

433

295

123.5

5.75

11.5

28

200

49

45 45

45 45 45

140

Note:

185

24

188

258

255

325

a NZM3(-4)-XK22X21
b NZM3(-4)-XK300

36.5

Length with phase isolators approx. 599 mm

Connection on rear
(+)NZM3-XKR(O)(U)
45

SW 8

45

45

112

247

234

124

117

123.5

o 30

57
11

22

11

o 11
35

140

90

M5

185
M10 x 35

45

45
o 30

247

234

124

117

10

o28

Circuit-breakers, disconnect switches


up to 1200 A

150

22

M5
45

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_148-157_f_G.fm Page 151 Thursday, May 4, 2006 7:28 PM

Dimensions
Circuit-breakers, disconnect switches

Circuit-breakers, disconnect switches


up to 1200 A

Moeller SK1230-1157EN-NA

599
161.6

200

616

Phase isolator
NZM3-XKP

100

3.5
45
90
210
255

Control circuit terminal


NZM3/4-XSTS
NZM-XSTK

149

148

a 3-pole
b 4-pole

185

140
b

151

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_148-157_f_G.fm Page 152 Thursday, June 8, 2006 10:31 AM

Dimensions
Circuit-breakers, disconnect switches
Moeller SK1230-1157EN-NA

Rotary handle on circuit-breaker


NZM3-XDV(R)

7
95
30

124

30

R8

F82.6

105

140

185

d=48
b f 34

a Up to 3 padlocks

Door coupling rotary handle


NZM3-XT(V)D(V)(R)
95
27.5
8

o
R87

71
85

35

25

d=48
b f 34

a Up to 3 padlocks

For Immediate Delivery call KMParts.com at (866) 595-9616

71

40

23

o8

ZFS...-NZM7

85

Circuit-breakers, disconnect switches


up to 1200 A

152

SK1157_148-157_f_G.fm Page 153 Thursday, May 4, 2006 7:28 PM

Dimensions
Circuit-breakers, disconnect switches

Circuit-breakers, disconnect switches


up to 1200 A

Moeller SK1230-1157EN-NA
Door coupling rotary handle with extension shaft
NZM3-XT(V)D(V)(R)(-NA)
NZM3/4-XV4(6)
95

25
X

27
8

o 60

32.5

59

36

23g0.5

NZM3/4-XV4(6)
29

NZM3/4-XV4
NZM3/4-XV6

x
270 400
400 600

NZM3-XT(V)D(V)(R)-60(-NA)

NZM3-XT(V)D(V)(R)-0(-NA)
42 77.5
18 60

NZM3/4-XV...

235 277

a
199.5 235

23g0.5

a Special tip
Minimum door coupling rotary handle clearance from door pivot point

NZM...3-... f 180

For Immediate Delivery call KMParts.com at (866) 595-9616

153

23g0.5

SK1157_148-157_f_G.fm Page 154 Thursday, June 8, 2006 10:32 AM

Dimensions
Circuit-breakers, disconnect switches
Moeller SK1230-1157EN-NA

105

Main switch assembly kit for side wall installation


NZM3-XS(R)-L

86 433

25

195

95

25

NZM3-XS(R)-R

105

Circuit-breakers, disconnect switches


up to 1200 A

154

39.1

86 433

25

195
95

25

Spacers
NZM3-XAB
138
17.5

NZM3-XAB

For Immediate Delivery call KMParts.com at (866) 595-9616

24.1

SK1157_148-157_f_G.fm Page 155 Thursday, June 8, 2006 10:33 AM

Dimensions
Circuit-breakers, disconnect switches

155

Circuit-breakers, disconnect switches


up to 1200 A

Moeller SK1230-1157EN-NA
Insulating surround
NZM3-XBR
9.5
ZFS...-NZM7

110

64

132

1.5 5

177
162

23

193.5

10
17.5

Mechanical interlock
NZM3-XMV with NZM3-XDV(R)

R1

40

50

47.5

95
96.5

20
5

99

40

140
185

196

For Immediate Delivery call KMParts.com at (866) 595-9616

69

73.2

50

105

34.5

SK1157_148-157_f_G.fm Page 156 Thursday, May 4, 2006 7:28 PM

Circuit-breakers, disconnect switches


up to 1200 A

156

Dimensions
Circuit-breakers, disconnect switches
Moeller SK1230-1157EN-NA

NZM3-XMV with NZM3-XT(V)D(V)(R)

NZM3/4-XV4
NZM3/4-XV6

NZM3/4-XV4(6)

NZM3-XMV with NZM3-XT(V)D(V)(R)-60

NZM3/4-XV...

270 312

NZM3-XMV with NZM3-XT(V)D(V)(R)-0


a Special tip

235 270

For Immediate Delivery call KMParts.com at (866) 595-9616

x
305 400
400 600

SK1157_148-157_f_G.fm Page 157 Thursday, May 4, 2006 7:28 PM

Dimensions
Circuit-breakers, disconnect switches

157

Circuit-breakers, disconnect switches


up to 1200 A

Moeller SK1230-1157EN-NA
Remote operator
NZM3-XR...
358
260.5
143.5

60.5
NZM3-XAVPR

28

17

5.5

10

291.5

95

140

F 13

140

70
140
185

d=48
b f 34

a Up to 3 padlocks
b Remote operator folded
Withdrawable unit
+NZM3-XAV
309 d
299 e
271 f
5

171

175.8

25

91

225.5

30

25

313.5

130

170.8

151.8

341.6

200

R1

SW 8

45

31

96

M10 x 30
400

200 a

520

227 a
250 b
272 b

c Up to 3 padlocks
d

a 3-pole
b 4-pole

d=48
b f 34

d disconnected
e test
f connected

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_158-172_f_G.fm Page 158 Thursday, June 8, 2006 10:35 AM

Dimensions
Circuit-breakers, disconnect switches
Moeller SK1230-1157EN-NA

Circuit-breaker, switch-disconnector, 3-pole


NZMN4, NZMH4, N4, NS4
207
204

138

70

33

21
87.5

117

401

313

180

171.5

119

108

44

f 100

ba

15

o 10.5

M5 x 110

b
15

Circuit-breakers, disconnect switches


up to 1200 A

158

45
f 15

25

100

100

f 15

70
210

a Blow out area, minimum clearance to other parts f 100 mm up to 690 V; f 200 mm up to 1000 V
b Minimum clearance from adjacent parts f 15 mm

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_156-170_f_G.fm Page 159 Tuesday, April 25, 2006 5:28 PM

Dimensions
Circuit-breakers, disconnect switches

Circuit-breakers, disconnect switches


up to 1200 A

Moeller SK1230-1157EN-NA
Cover
NZM4-XKSA

f 100

108.5

128

531
210
280

a 3-pole
b 4-pole
c Clearance from conductive parts f 100 mm up to
690 V; f 200 mm up to 1000 V

Tunnel terminal
NZM4-XKA
60
53

32

30.5

25

73.5

f 100

4 x SW8

M10 x 60

171.5

2 x SW16

210 a
280 b

159

a 3-pole
b 4-pole
c Clearance from conductive parts f 100 mm up to
690 V; f 200 mm up to 1000 V

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_158-172_f_G.fm Page 160 Thursday, June 8, 2006 10:36 AM

Dimensions
Circuit-breakers, disconnect switches
Moeller SK1230-1157EN-NA

Screw connection
Module plate 1-hole
NZM4-XKM1
Module plate 2-hole
NZM4-XKM2
Flat cable terminal
NZM4-XKB
43

40

a 3-pole
b 4-pole
c Clearance from conductive parts f 100 mm up to
690 V

50
43

25

NZM4-XKM2
o 11

NZM4(-4)-XKB
SW5
SW16

NZM4(-4)-XKM1
NZM4(-4)-XKM2
NZM4(-4)-XKB

M10 50

NZM4(-4)-XKB

36
32

171.5

NZM4-XKM1

210 a
280 b

Module plate 2-hole vertical


NZM4-XKM2S
33
70

o 13

70

70

o 13

16

70

M 10 x 50

32

16

70

32
50

518

486

518

171.5

SW16

486

Circuit-breakers, disconnect switches


up to 1200 A

160

50
210

NZM4-XKM2S-1250
NZM4-XKM2S-1600

280

x
12
20

For Immediate Delivery call KMParts.com at (866) 595-9616

b
47
40
47

SK1157_156-170_f_G.fm Page 161 Tuesday, April 25, 2006 5:28 PM

Dimensions
Circuit-breakers, disconnect switches

Connection width extension


NZM4-XKV95
77

107.5

48

107.5
77

50

o 11

18

15

o 11

30.5

15

50

NZM4-XKV110

95

15

95

Circuit-breakers, disconnect switches


up to 1200 A

Moeller SK1230-1157EN-NA

M10 x 50

30

30
28.5

292

NZM4-4-XKV95

NZM4-4-XKV120

95

47.5

47.5

18

95
18

80

122
42

122
42

48

122
42

15

50

77

o 11

15

o 11

M10 x 50

30

18
362

41

625

595

573

543

171.5

15

50
30

41

210

267

18

573

543

573

543

171.5

SW16

210

30
280

161

83

446

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_156-170_f_G.fm Page 162 Tuesday, April 25, 2006 5:29 PM

Dimensions
Circuit-breakers, disconnect switches
Moeller SK1230-1157EN-NA

Connection on rear
NZM4-XKR

Fitting on mounting plate


278
139
SW16

30

206

88
M5

9.5

15

280

210
b

16
70

3-5
140
o 11

208

205.5

87.5
M5

35
70

Rear connection possible also with rotation by 90.


a 3-pole
b 4-pole

For Immediate Delivery call KMParts.com at (866) 595-9616

411

180

72

45

104

411

180

172

72

M10 x 30

25

Circuit-breakers, disconnect switches


up to 1200 A

162

SK1157_156-170_f_G.fm Page 163 Tuesday, April 25, 2006 5:29 PM

Dimensions
Circuit-breakers, disconnect switches

Circuit-breakers, disconnect switches


up to 1200 A

Moeller SK1230-1157EN-NA

190

Phase isolator
NZM4-XKP

3.5

163

114

70
140

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_156-170_f_G.fm Page 164 Tuesday, April 25, 2006 5:29 PM

Dimensions
Circuit-breakers, disconnect switches
Moeller SK1230-1157EN-NA

Drilling template NZM12-1000 (1250) conversion to NZM4


a
b
c
d

50
60
100

Module plate NZM4-XAS12-1000(1250)


Drilling dimensions for mounting bracket NZM4-XAS12(M5)
Mounting bracket NZM4-XAS12
DIN rail NZM12

98

4.5

19 64.5

93.5

536.5

218

343

180

95.5

Circuit-breakers, disconnect switches


up to 1200 A

164

d
70
79

79
210
276

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_156-170_f_G.fm Page 165 Tuesday, April 25, 2006 5:29 PM

Moeller SK1230-1157EN-NA
Exchange of NZM12-1000(1250) by NZM4 with module plate,
fixed mounted on mounting plate
NZM4-XAS12-1000(1250)

Exchange of NZM12-1600() by NZM4 with module plate,


fixed mounted on mounting plate
NZM4-XAS12-1600

184

79

79
39.5

93.5
79
39.5

96.5

22

15

68.5
599

578.5

536.5

141.5

141.5

22

68.5

55

14

184

50

10 (NZM12-1250)
8 (NZM12-1000)

25

79

10 (NZM12-1000)

98.5

98.5

15 (NZM12-1250)

248

59

248

276

59

15
215.8

276
215.8
96.5

50

15

60
22

48.5

14

93.5

23

10 (NZM12-1250)

50

22

48.5

128

578.5

536.5

55.5

192.5

599

55.5

98

192.5

34

128

8 (NZM12-1000)

60

95.5

39.5
57
79
10 (NZM12-1000)

39.5

79
210

15 (NZM12-1250)

57
79

79
210

15
59

59
186.5
243.7
264.1

For Immediate Delivery call KMParts.com at (866) 595-9616

186.5
243.7
264.1

165

Circuit-breakers, disconnect switches


up to 1200 A

Dimensions
Circuit-breakers, disconnect switches

SK1157_158-172_f_G.fm Page 166 Thursday, June 8, 2006 10:37 AM

Dimensions
Circuit-breakers, disconnect switches
Moeller SK1230-1157EN-NA

Rotary handle on circuit-breaker


NZM4-XDV(R)
57
204

69

221.5

33

117

73.5

f 89.5

60.5

58.5

R 137

162
210

280

d=48
b f 34

a Up to 3 padlocks
Door coupling rotary handle
NZM4-XT(V)D(V)(R)
ZFS...-NZM7
70

40
o
85

71

R1

37

d=48
b f 34

a Up to 3 padlocks

For Immediate Delivery call KMParts.com at (866) 595-9616

71

23

o8

18

85

Circuit-breakers, disconnect switches


up to 1200 A

166

SK1157_156-170_f_G.fm Page 167 Tuesday, April 25, 2006 5:31 PM

Dimensions
Circuit-breakers, disconnect switches

Circuit-breakers, disconnect switches


up to 1200 A

Moeller SK1230-1157EN-NA
Door coupling rotary handle with extension shaft
NZM4-XT(V)D(V)(R)(-NA)
NZM3/4-XV4(6)
X

95

25
27
8
5

21

60

59

36

23g0.5

NZM3/4-XV4(6)
57

NZM3/4-XV4
NZM3/4-XV6

NZM4-XT(V)D(V)(R)-60(-NA)

NZM4-XT(V)D(V)(R)-0(-NA)

42 77.5

18 60

NZM3/4-XV...

270 312

a
23g0.5

234.5 270

a Special tip
Minimum door coupling rotary handle clearance from door pivot point

NZM...4-... f 180

For Immediate Delivery call KMParts.com at (866) 595-9616

167

23g0.5

x
300 400
400 600

SK1157_156-170_f_G.fm Page 168 Tuesday, April 25, 2006 5:31 PM

Dimensions
Circuit-breakers, disconnect switches
Moeller SK1230-1157EN-NA

Main switch assembly kit for side wall installation


NZM4-XS(R)(F)-L
NZM4-XS(R)(F)-R
229

86 433
25

34.1
24.1

100

221.5

Circuit-breakers, disconnect switches


up to 1200 A

168

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_158-172_f_G.fm Page 169 Thursday, June 8, 2006 10:38 AM

Dimensions
Circuit-breakers, disconnect switches

169

Circuit-breakers, disconnect switches


up to 1200 A

Moeller SK1230-1157EN-NA
Insulating surround
NZM4-XBR
9.5
1.5 5

125

154

64

ZFS...-NZM7

246
231

23

262.5

10
17.5

Mechanical interlock
NZM4-XMV with NZM4-XDV(R)
34.5

R1

40

50

47.5

95

20
5
162
210

40
230

280

For Immediate Delivery call KMParts.com at (866) 595-9616

69

73.2

50

221.5

SK1157_156-170_f_G.fm Page 170 Tuesday, April 25, 2006 5:31 PM

Circuit-breakers, disconnect switches


up to 1200 A

170

Dimensions
Circuit-breakers, disconnect switches
Moeller SK1230-1157EN-NA

NZM4-XMV with NZM4-XT(V)D(V)(R)


NZM3/4-XV4
NZM3/4-XV6

x
335 400
400 600

NZM3/4-XV4(6)

NZM4-XMV with NZM4-XT(V)D(V)(R)-60

NZM3/4-XV...

305 347

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_156-170_f_G.fm Page 171 Tuesday, April 25, 2006 5:31 PM

Dimensions
Circuit-breakers, disconnect switches

171

Circuit-breakers, disconnect switches


up to 1200 A

Moeller SK1230-1157EN-NA
NZM4-XMV with NZM4-XT(V)D(V)(R)-0
a Special tip

270 305

Remote operator
NZM4-XR...
435.2
313.4
175.4
12.5
204

84.4

b
189.5

189.5

208

208
280
d

210

d=48
b f 34

a Up to 3 padlocks
b Remote operator folded

For Immediate Delivery call KMParts.com at (866) 595-9616

454.4

189

117

55.6

45.5

306.4

19.4

F13.4

SK1157_156-170_f_G.fm Page 172 Tuesday, April 25, 2006 5:31 PM

Dimensions
Circuit-breakers, disconnect switches
Moeller SK1230-1157EN-NA

Withdrawable unit
+NZM4-XAV
353.5

e
f

341
313
243

274.5

217

25 25

M6 x 12

451

300

509

30

R1

c
25 25

70

131

33

275
297

560

680

350
367

a 3-pole
b 4-pole

c Up to 3 padlocks

Circuit-breakers, disconnect switches


up to 1200 A

172

d=48
b f 34

d disconnected
e test
f connected

For Immediate Delivery call KMParts.com at (866) 595-9616

SK1157_222-223_i_G.fm Page 173 Monday, May 22, 2006 11:38 AM

173

Moeller SK1230-1157EN-NA

+
+NZM...-XAV...
+NZM...-XKC
+NZM...-XKR...
+NZM...-XSV...

Withdrawable unit with auxiliary plug-in adapter


Box terminal
Connection on rear
Plug-in units

65
71, 75
71, 77
64

A
B
BPF-NZM...

Lightning symbol

59

Expansion unit CANopen


Expansion unit DeviceNet
Switched-mode power supply unit

88
88
88

FDT frame software for field device operation

89

insulated additional terminal


insulated additional terminal
Cable lug

90
90
73

Auxiliary contacts
Telescopic adapters

24
88

E
EASY221-CO
EASY222-DN
EASY400-POW

F
FDT-NAVIGATOR

K
K.../1
K.../BR
KS...-NZM7

M
M22-...
M22-TA

N
N1-...-NA
N2-...-NA
N3-...-NA
N4-...-NA
NS1-...-NA
NS2-...-NA
NS3-...-NA
NS4-...-NA
NZM...1-...-CNA
NZM...1-...-NA
NZM...2-...-CNA
NZM...2-...-NA
NZM...3-...-CNA
NZM...3-...-NA
NZM...4-...-NA
NZM...-XA...
NZM...-XA...MNS
NZM...-XAB
NZM...-XBR

Disconnect switches for North America


21
Disconnect switches for North America
21
Disconnect switches for North America
21
Disconnect switches for North America
21
Molded case switches for North America
20
Molded case switches for North America
20
Molded case switches for North America
20
Molded case switches for North America
20
Circuit-breakers for North America
10
Circuit-breakers for North America
6, 8
Circuit-breakers for North America
12
Circuit-breakers for North America
6, 8, 16, 18
Circuit-breakers for North America
18
Circuit-breakers for North America
14, 16, 18
Circuit-breakers for North America
14, 16, 18
Shunt releases
38, 40, 42, 44, 46, 48
Shunt releases for mesh network circuit-breakers 42, 48
Spacers
60
Insulating surround
60

NZM...-XC...
NZM...-XD...
NZM...-XDTV...
NZM...-XDTV...-NA
NZM...-XDZ
NZM...-XHB...
NZM...XHI...
NZM...-XHIV...
NZM...-XIP...
NZM...-XKA
NZM...-XKAV
NZM...-XKB
NZM...-XKC
NZM...-XKM...
NZM...-XKP
NZM...-XKR
NZM...-XKS
NZM...-XKS...
NZM...-XKSA
NZM...-XKSFA
NZM...-XKV...
NZM...-XMV
NZM...-XMVR
NZM...-XMVRL
NZM...-XRC
NZM...-XS...
NZM...-XST
NZM...-XSV...
NZM...-XT...
NZM...-XT...-NA
NZM...-XU...
NZM...-XUV...
NZM...-XV...
NZM1/2-XZB
NZM4-XAS...
NZM-XBZ...
NZM-XCM
NZM-XDMI612
NZM-XDMI-DPV1
NZM-XPC-DTM
NZM-XPC-KIT

Clip plate
60
Rotary handle
54
Rotary handle with door interlock
55
Rotary handle with door interlock for NA breakers
55
Additional handle
60
Main switch assembly kit
56
Auxiliary contact
24
Auxiliary contacts, early-make
24
IP2X protection against contact with a finger 69, 73, 79
Tunnel terminal
67, 71, 77, 83
Toggle lever interlock device
60
Flat cable terminal
83
Box terminal
67, 71, 75
Module plate
81
Phase isolator
79, 87
Connection on rear
67, 69, 77, 83
Bolt connection
67, 71, 75
Cable lug
73, 79, 87
Cover
69, 73, 79, 87
Terminal cover, knockout
69, 73, 79, 87
Connection width extension
75, 81
Mechanical interlock for rotary door handle
61
Mechanical interlock for remote operator
61
Mechanical interlock for remote operator
61
Clamp terminal springloaded clamp
62
Main switch assembly kit
56, 57, 58
for side panel mounting
Control circuit terminal
69, 73, 87
Plug-in units
64
Door coupling rotary handle
50, 51
Door coupling rotary handle for NA breakers
52, 53
Undervoltage releases
26, 28, 30, 34, 35, 36
Undervoltage releases
37
for combination with separate delay unit
Extension shaft
50, 52
Additional plate
58
Adapter set
83, 85
Bowden cables
61
Capacitor unit
40
Data management interface (DMI module)
88
Expansion unit PROFIBUS-DPV1 slave
88
DTM software module to FTD standard
89
Diagnostics and configuration software
88
for NZM and DMI

P
S
U
UVU-NZM

Undervoltage releases, off-delayed

37

External warning plate

59

Z
ZFS...-NZM...

For Immediate Delivery call KMParts.com at (866) 595-9616

Circuit-breakers, disconnect switches


up to 1200 A

Part number list

SK1157_222-223_i_G.fm Page 174 Monday, May 22, 2006 11:38 AM

Circuit-breakers, disconnect switches


up to 1200 A

174

Alphabetical index

Moeller SK1230-1157EN-NA
Part number

Device

Page

Part number

Device

Page

Adapter set
Additional handle
Additional plate
Auxiliary contact
Auxiliary contact, early-make

83, 85
60
58
24, 25
24, 25

B
Bolt connection
Bowden cables
Box terminal

67, 71, 75
61
67, 71, 75

C
Cable lug
Capacitor unit
Circuit-breakers for North America
Clamp terminal springloaded clamp
Clip plate
Connection on rear
Connection width extension
Control circuit terminal

73, 79, 87
40
6 18
62
60
67, 71, 77, 83
75, 81
69, 73, 87

D
Data management interface (DMI module)
Diagnostic and configurator software for NZM and DMI
Door coupling rotary handle
Door coupling rotary handle for UL/CSA approved breakers
DTM software module to FTD standard

88
88
50 53
52, 53
89

E
Expansion unit CANopen
Expansion unit DeviceNet
Expansion unit PROFIBUS-DPV1 slave
Extension shaft
External warning plate

88
88
88
50, 52
59

F
FDT frame software for operating field devices
Flat cable terminal

89
83

Lightning symbol

M
Main switch assembly kit
Main switch assembly kit for side panel mounting
Mechanical interlock for remote operator
Mechanical interlocking of (door coupling) rotary handles
Module plate
Molded case switches for North America

Insulating surround
IP2X protection against contact with a finger
Iusulated additional terminal

56
56, 57, 58
61
61
81
20

P
Phase isolator
Plug-in units

79, 87
64

R
Rotary handle
Rotary handle with door interlock

54
55

S
Shroud
Shunt release
Shunt release for mesh network circuit-breaker
Spacer
Disconnect switches for North America
Switched-mode power supply unit

69, 73, 79, 87


38 49
42, 48
60
21
88

T
Telescopic adapter
Terminal cover, knockout
Toggle lever interlock device
Tunnel terminal

88
69, 73, 79, 87
60
67, 71, 77, 83

U
Undervoltage release
Undervoltage release, for combination with separate delay unit
Undervoltage releases, off-delayed

26 36
37
37

W
Withdrawable unit with auxiliary plug-in adapter

59

60
69, 73, 79
90

For Immediate Delivery call KMParts.com at (866) 595-9616

65

SK1230+1157_D_D-INT_GB-INT3.qxp

27/07/2006

20.31

Pagina 1

www.moellerusa.com
www.moeller.ca
Moeller Corporate Headquarters
4140 World Houston Parkway, N 100
Houston, Texas USA 77032
Tel 713.933.0999
Fax 832.613.6255

Moeller Canadian Head Office


7275 Rapistan Court
Mississauga, Ontario CANADA
L5N 5Z4
Tel 905.542.2323
Fax 905.542.2321

2006 by Moeller, Inc.


Technical and other changes reserved.
Publication: NZM-CAT-0806
Printed in Germany
08/06
Article No: 695010

Think future. Switch to green.


green

For Immediate Delivery call KMParts.com at (866) 595-9616

NZM1-4 circuit-breaker series up to 1200 A

Product Range Catalogue | 2006


Switching, protection, communication
the new NZM1-4 circuit-breaker series
up to 1200 A

Reliable and safely controlling,


switching and managing
power. In industry, in buildings
and in machine construction.
Innovative protection concepts.
With built-in diagnostics and
communication functions.

Circuit-breaker NZM

Think future. Switch to green.


green