Delta Digital Controls

Fire Alarm Products


UL Listed, FM Approved

ANALOG SENSOR BASES


APPLICATION

YBN-NSA-4-DDC

The Delta Digital Controls YBN-NSA-4-DDC and the HSBNSA-6-DDC mounting bases are electronics free and
contain a simple rugged design with screw terminals for
wiring connections. A common mounting base allows
sensor interchange and maintains loop continuity when
sensors are removed. A simple anti-tamper head locking
system is provided which is enabled by removing a small
plastic tab on the back of the sensor. Once locked, the
head can only be removed using a small diameter screw
driver.

OPERATION
The YBN-NSA-4-DDC and HSB-NSA-6-DDC common
mounting bases allows for complete compatibility for all
of the Delta Digital Controls NS Series Analog sensors.
The bases are lightweight and very thin, providing a low
profile once installed. The solder-less screw terminals
enable quick and easy wiring connections.
The YBN-NSA-4-DDC and HSB-NSA-6-DDC are designed
specifically for use with the Delta Digital Controls NS
Analog models AIE-EA-DDC Ionization Smoke Sensor,
ALG-V-DDC Photoelectric Smoke Sensor and ATG-EADDC Heat Sensor.

HSB-NSA-6-DDC
STANDARD FEATURES

UL Listed
Designed for use with all analog sensors.
Available in 4 and 6 inch models.
Contains a security locking tab for tamper
protection.

SPECIFICATIONS
YBN-NSA-4-DDC
HSB-NSA-6-DDC
Security Feature
Color

4 inches
6 inches
Plastic Tamper-Lock
Bone PC / ABS Blend

PRODUCT LISTINGS
Underwriters Laboratories: S1383
CSFM #: 7300-0410:132
FM#: 3022559
MEA Report #: 284-91-E Vol. IV

Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.

F0013

04/2005

ENGINEERING SPECIFICATIONS
The base shall permit direct interchange with the Delta Digital Controls AIE-EA-DDC ionization type smoke sensor,
ALG-V-DDC photoelectric smoke sensor, and the ATG-EA-DDC heat sensor.
The sensitivity of the sensor shall be capable of being measured by the control panel.
The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking
feature shall be optional and can be implemented when required.
It shall be possible to perform a functional test of the sensor without the need of generating smoke. The test method
shall simulate the effects of products of combustion in the chamber to ensure testing of internal circuitry.

TYPICAL WIRING DIAGRAMS

YBN-NSA-4 -DDC
(+)
U.L.
LISTED
COMPATIBLE
DCP
LOOP

(-) 8mA MAX.


OUTPUT

U.L.
LISTED
POWER
LIMITED
SUPPLY

(+)

8mA MAX.
OUTPUT

HSB-NSA-6 -DDC
(+)
U.L.
LISTED
COMPATIBLE
CONTROL
PANEL

U.L.
LISTED
POWER
LIMITED
SUPPLY

(-)

(+)

8mA MAX.
OUTPUT

8mA MAX.
OUTPUT

- OPTIONAL WIRING CONFIGURATIONS FOR REMOTE OUTPUT

NOTE: Fire alarm control panel compatibility is required for DCP products.
State-of-the-art communications protocol, DCP, allows system components (DCP sensors AIE-EA-DDC,
ALG-V-DDC and ATG-EA-DDC, bases and modules), to be used concurrently in a system's signaling line circuit.

Delta Digital Controls Analog Sensor Bases

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed

ASB - ANALOG SOUNDER BASE

SPECIFICATIONS

Shown without sensor

Shown with sensor

STANDARD FEATURES

Programmable evacuation codes -Continuous,


March, ANSI Temporal patterns
Base learns the sensor address and assumes an
upper range address (128-254)
Up to 127 sensors and 127 ASBs can be used on
one SLC loop
Can be alarmed or reset by zone or by individual
address
ASB SLC loop wire resistance = 50 ohms Max.
(total SLC wire run length)
High sound pressure level (85dB SPL at 10 feet)

PRODUCT LISTINGS
Underwriters Laboratories: S1383
CSFM #: 7300-0410:161

Operating Voltage
17 - 41 VDC
SLC Loop Idle Current
110 A
SLC Loop Max. Alarm Current 110 A
Aux. Power Supply Voltage
16 - 31 VDC
Device Aux. Power Min. Voltage 15.0 VDC
Aux. Idle Current
550A
Aux. Max. Alarm Current
18mA
Max. Humidity
93%RH (non-condensing)
Sound Pressure Level at 10 ft
85dB
UL Ambient Installation
Temperature Range
32F (0C) ~ 100F (38C)
Operating Temperature Range
32F (0C) ~ 122F (50C)
Base Diamater
5.9"
Base Height (without sensor)
1.3"
Weight
0.455 lb
Compatible Sensors
ALG-V-DDC, AIE-EA-DDC &
ATG-EA-DDC

DESCRIPTION
The ASB Analog Sounder Base is designed for use
with Delta Digital Controls analog style sensors models
ALG-V-DDC, AIE-EA-DDC, and ATG-EA-DDC. Each
addressable base is to be connected to a Delta Digital
Controls DCP Signaling Line Circuit (SLC). The ASB
provides an audible alarm in the immediate vicinity.
Typical applications are use in hotels, apartments, and
hospitals.
The ASB has a highly configurable programming
algorithm that allows the user to setup groups of bases
for synchronization of modulation tones. Each device
has 16 states that are programmed with the desired
output pattern to be used (e.g., Temporal or March)
for each state.

Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.

F0013

04/2005

WIRING DIAGRAM
FireNET
CONTROL
PANEL

NEXT DEVICE

8mA Max.

LOOP OUT

NEXT DEVICE

(Aux.)

FIGURE A

(+)

TOP VIEW

8mA MAX.
OUTPUT

NOTE: Class A style 7 wire configuration requires the installation of short circuit isolators (SCI).
DO NOT CONNECT FOR CLASS B (STYLE 4)
LOOP IN

CONNECT FOR CLASS A (STYLE 6 OR 7)

CO
A
IC . B
ER
M R EV
B
IA
IK -0 67 AS
C H 08
H O HA-

.
RP
CO
A
IC B
E R EV.
R
I AM 7
IK 06 A SB
C H -08H O HA

RP.
SC

SC
G

TP3

3
TP
SC

1
TP

DET

1
TP

TS
DE

TP

TP2

AUX POWER

2
C-0103
2

RED

RED

2
C-0103
2

RED

BLK
BLK

S56

S5

RED

BLK
BLK

RED
BLACK

RED

RED

BLACK

BLACK

FIGURE B

BOTTOM VIEW

NUMBER OF BASES PERMITTED


# of Bases Maximum Auxiliary 24VDC Power Wire Resistance
In Alarm
(Total Auxiliary Run Length)
127
75
60
50
30
20
15
10

1.4 ohm
2.4 ohm
3.0 ohm
3.6 ohm
6.1 ohm
9.1 ohm
12.2 ohm
18.3 ohm

NOTE: SLC maximum wiring resistance is 50 ohms.

Delta Digital Controls ASB - ANALOG SOUNDER BASE

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
Conventional Detector Bases
NS6 - DDC AND NS4 - DDC SERIES BASE

NS Series Bases

Alarm Current

ID

NS6-224-DDC OR NS4-224-DDC

43mA (70mA @ 33.0V MAX)

HB-5

NS6-220-DDC OR NS4-220-DDC

93mA (136mA @ 33.0V MAX)

HB-3

NS6-221-DDC OR NS4-221-DDC

46mA (77mA @ 33.0V MAX)

HB-4

NS6-100*-DDC OR NS4-100*-DDC

150mA @ 15.0 - 33.0V MAX

HB-55

* Requi res external current li mi ti ng to 150mA maxi mum.

HSC- (X)R-DDC RELAY BASE &


HSC- 4R 4-DDC WIRE BASE

2 Wire Auxilliary
R elay B ases

Alarm C urrent

ID

HSC -224R-D D C

43mA (58mA @ 30.0V MAX)

HB-73

HSC -220R-D D C

88mA (98mA @ 26.5V MAX)

HB-72

HSC -221R-D D C

49mA (62mA @ 30.0V MAX)

HB-71

4 Wire B ase

Alarm C urrent

ID

HSC -4R-D D C

43mA (58mA @ 30.0V MAX)

N/A

HSC -4R12-D D C

47mA (75mA @ 18.0V MAX)

N/A

HSC- (X) L-DDC LATCHING LED BASE

Alarm C urrent

ID

HSC -224L-D D C

2 Wire Latching

35-42mA @ 24V (54mA MAX)

HB-62

HSC -220L-D D C

67-80mA @ 24V
(88.5mA @ 26.5VD C MAX)

HB-64

HSC -221L-D D C

37-45mA @ 24V (57mA MAX)

HB-63

The NS6 - DDC and NS4 - DDC Series is designed specifically


for use with DELTA DIGITAL CONTROLS Conventional Models
SIJ-24 - DDC IONIZATION SMOKE DETECTOR, SLR-24VDDC PHOTOELECTRIC SMOKE DETECTOR, SLR-24H - DDC
Photoelectric with Heat Smoke Detector - DDC, SLR-835 DDC Photoelectric Smoke Detector - DDC, SLR-835H-DDC
Photelectric Smoke Detector w/heat - DDC, or DCD-135-DDC
/190 - DDC Fixed Temperature/Rate-of-Rise Heat Detector DDC. The Base is an electronics free 6" base featuring a
plastic tamper-lock lug. Each base is equipped with a
resistor. Refer to the chart (left) for additional specifications.
The NS4 - DDC base is a 4" version of the NS6 - DDC
base.Models HSC-224R - DDC, HSC-220R - DDC and the
HSC-221R - DDC are designed specifically for use with the
DELTA DIGITAL CONTROLS Conventional Models SIJ-24 DDC, SLR-24V - DDC, SLR-24H - DDC, SLR-835 - DDC, SLR835H-DDC or DCD-135-DDC /190 - DDC. The HSC-(X)R DDC series is a 6" base with two sets of Form "C" relay
contacts.
Models HSC-224R - DDC, HSC-220R - DDC and the HSC221R - DDC are also approved for use with DELTA DIGITAL
CONTROLS previous Conventional Models SIH-24F - DDC DDC, SLK-24 - DDCF, SLK-24 - DDCFH and the DFE 135/
190-DDC.
The HSC-4R - DDC is designed specifically for 24 volt 4
wire applications using DELTA DIGITAL CONTROLS
Conventional Models SIJ-24 - DDC, SLR-24V - DDC, SLR24H - DDC, SLR-835 - DDC, SLR-835H-DDC or DCD-135DDC /190 - DDC. The 6" diameter base is current limited.
Relay contact place a direct short occurs across the loop
when the detector is actuated.
Model HSC-4R - DDC is also approved for use with previous
DELTA DIGITAL CONTROLS Conventional Models SIH-24F
- DDC, SLK-24 - DDCF, SLK-24 - DDCFH and the DFE 135/
190-DDC.The HSC-L-DDC Base Series is designed
specifically for use with the DELTA DIGITAL CONTROLS Fixed
Temperature Heat Detectors Models
DFE-135/ 190-DDC.
The HSC-L-DDC Series is a 6" base featuring a current limiting
resistor, latching annunciator output and a latching circuit so
the alarm LED will remain lit until the control panel has been
reset.
The HSC-4R12-DDC is designed specifically for 12 volt 4
wire applications using DELTA DIGITAL CONTROLS
Conventional Models SLR-835 - DDC, SLR-835H-DDC. The
6" diameter base is current limited. Relay contact place a
direct short occurs across the loop when the detector is
actuated.
Model HSC-4R12-DDC is also approved for use with previous
DELTA DIGITAL CONTROLS Conventional Models SLK-835,
SLR-835 - DDC, and SLR-835H-DDC.

We try to keep our product information up-to-date and accurate. However, we cannot cover all specifications or
anticipate all requirements. For additional information contact your local distributor or Delta Digital Controls.
Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.

F0013

04/2005

Conventional Detector Bases


NS4 - DDC AND NS6 - DDC SERIES BASE
2-WIRE OPERATION
UL LISTED
CONTROL
PANEL

PANEL
POWER
SUPPLY

LISTED
END OF LINE
DEVICE
Resistor shown is for example
only. Not all annunciators
have in line resistance.

NS4 SERIES

NEGATIVE

NS6 SERIES

Annunciation device must be current limited to 20 mA @


24VDC Maximum. Not limiting current could result in
damage to the detector or cause a no alarm condition.

NOTE: - WIRING TERMINALS FOR THE NS4


AND NS6 ARE IDENTICAL
- BASES WITH THE "W" SUFFIX
ARE WHITE IN COLOR

HSC-(X)R - DDC RELAY BASE


2-WIRE OPERATION
UL LISTED
CONTROL
PANEL

LISTED
END OF LINE
DEVICE

GRY
BLU
GRN
YEL
ORN
PUR

HSC- (X) R SERIES

PIGTAIL AUXILLIARY
CONTACTS
TWO FORM "C"

RELAYS SHOWN WITH


POWER OFF.

HSC-4R - DDC FOUR WIRE BASE

4-WIRE OPERATION
LISTED
END OF LINE
DEVICE

INITIATING
CIRCUIT

LISTED
END OF LINE
RELAY
HA-EOLR-12 OR HA-EOLR-24

UL LISTED
POWER
SUPPLY
12VDC OR 24VDC

H1
H2
YEL
ORN
PUR

H1,H2 - TERMINAL
PIGTAIL AUXILLIARY CONTACTS
ONE FORM "C"

HSC-4R OR HSC-4R12

HSC- (X) L-DDC LATCHING LED BASE

2-WIRE OPERATION
COMPATIBLE
UL LISTED
CONTROL
PANEL

PANEL
POWER
SUPPLY
NEGATIVE

HSC-(X) L SERIES

Pig Tail Lead

LISTED
END OF LINE
DEVICE

NS6 SERIES

We try to keep our product information up-to-date and accurate. However, we cannot cover all specifications or anticipate all
requirements. For additional information contact your local distributor or Delta Digital Controls .
Delta Digital Controls Conventional Detector Bases

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed

SBC - CONVENTIONAL SOUNDER BASE


DESCRIPTION

Shown without detector

Shown with detector

STANDARD FEATURES

Wide operating voltage


Selectable Evacuation Codes: continuous or
temporal
Three different configurations: individual, group,
and global modes
High sound pressure level (85 dB at 10 ft)
Can be configured to satisfy a wide variety of
applications
Available with or without relay, 2 and 4 wire
configurations, and bone or white color

The Models SBC-DDC Conventional Sounder Base DDC Series are designed specifically for use with DELTA
DIGITAL CONTROLS NS conventional style smoke
detectors Models SIJ-24 - DDC IONIZATION SMOKE
DETECTOR, SLR-24V- DDC PHOTOELECTRIC
SMOKE DETECTOR and SLR-835 - DDC Wide
Operating Voltage Photoelectric Smoke Detectors. The
SBC-DDC Series will provide an audible evacuation
signal (continuous or temporal Code) upon detector
alarm. Easily configured to 12 or 24-volt applications
through use of a dipswitch, the bases can also be
configured to activate in individual, group, or global
modes. The relay base model SBC-2R - DDC contains
two sets of Form C Relay Contacts rated at 1 Amps
@ 28VDC or 0.5 Amps @ 120VAC. All models come
in 6 diameter size and are available in both bone and
white colored plastic.

SPECIFICATIONS
Model
Operating Voltage Range
Max. Alarm Current

SBC-2 - DDC, 2W
8.7-30VDC
26mA@8.7VDC
35mA@12VDC
65mA@24VDC

GROUP/
GLOBAL MODE
12mA@8.7VDC
18mA@12VDC
45mA@24VDC

SBC-2R - DDC, 2RW


19-30VDC
53mA@19VDC
65mA@24VDC

SBC-4-DDC/12, 4/12W SBC-4-DDC/24, 4/24W


GROUP/
GLOBAL MODE
30mA@19VDC
40mA@24VDC

1234567890123456
123456789012345612345678901
12345678901123456789012345
12345678901234512345678901
12345678901
1234567890123456
12345678901
123456789012345
12345678901
1234567890123456
12345678901
12345678901
1234567890123456
12345678901
12345678901
1A@28VDC
1234567890123456
12345678901
12345678901
OR
Contact Rating of Relay
1234567890123456
12345678901
12345678901
0.5A@120VAC
123456789012345612345678901123456789012345
12345678901
1234567890123456
12345678901
123456789012345
123456789012345612345678901
12345678901234512345678901
12345678901
Alarm Contact Rating
1234567890123456
12345678901
12345678901234512345678901
12345678901
12345678901
93%RH(non-condensing)
93%RH(non-condensing)
Max. Humidity
12345678901
12345678901
12345678901
12345678901
12345678901
12345678901
85
dB
85 dB
Sound Pressure Level at 10ft
12345678901
12345678901
12345678901
12345678901
32F (0C) to
32F (0C) to
12345678901
12345678901
Operating Temperature Range
12345678901 100F (38C)
12345678901
100F (38C)
12345678901
12345678901
12345678901
12345678901
5.94 x 1.34
5.94
x
1.34
Dimensions
12345678901
12345678901
12345678901
12345678901
0.365 lb
12345678901 0.455 lb
12345678901
Weight
12345678901
12345678901
SLR-24V - DDC, SIJ-24 - 12345678901SLR-24V - DDC, SIJ-24 -12345678901
DDC, SLR-835 - DDC/-835W/ 12345678901DDC, SLR-835 - DDC/-835W/12345678901
Compatible Detectors
-835H-DDC/-835HW-DDC 12345678901
12345678901-835H-DDC/-835HW-DDC 12345678901
12345678901
Rated Voltage

PRODUCT LISTINGS
Underwriters Laboratories: S1383
CSFM #: 7300-0410:160

10-18VDC

18-30VDC

75mA@12VDC

65mA@24VDC

24VDC

12VDC

2A@30VDC OR 0.5A@120VAC
2A@30VDC OR 0.5A@120VAC
93%RH(non-condensing)
85 dB
32F( 0C ) to 100F (38C)
5.94 x 1.34
0.455 lb
SLR-835 - DDC
/-835W

SLR-24V - DDC, SLR835H-DDC/-835H-DDCW

Note: W at the end of model designation indicates


white colored plastic.

Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.

F0013

04/2005

GROUP SOUNDER WIRING DIAGRAM (2 WIRE) SBC-2 - DDC AND 2R


NEXT DEVICE

EOL
RESISTOR

INITIATING
LOOP
UL
LISTED
CONTROL
PANEL

NEXT DEVICE

TOP VIEW
OR

CONVENTIONAL SOUNDER BASE 12V/24V WITHOUT RELAY (2 WIRE) SBC-2

P57
20
1

EOL
RELAY

P57
20
1

+12

+12

-12

-12

NEXT

NEXT

J2

J2
J4

J4
S1

8
G

AL

J3

8S

05

S1

CO

VLT

GRY

BRN

GRN
YEL
ORG
RED

8
G

AL

05
8

CO

ON

BLK
WHT

BRN

VLT

GRY

GRN
YEL
ORG
RED
BLK
WHT

ON

J3

12V/24V
AUX

BOTTOM VIEW
CONVENTIONAL SOUNDER BASE 24V WITH RELAY (2 WIRE) SBC-2R

1
20
P 57

20
P57
1

NC
NO
COM
+ 12

J2

J2

24V ONLY
AUX

NC
NO
COM
+ 12

NEXT

J4
S1

J3

8S

6
5
4
CO

AL

DS
G

4
3

O
ALC

2
1

ON

GRY

VLT

BRN

ON

GRY

VLT

BRN

GRN
YEL
ORG
RED
BLK
WHT

GD

5
S0

8S

S1

J3
GRN
YEL
ORG
RED
BLK
WHT

J4

NEXT

05

EOL
RELAY

- 12

- 12

NOTES: FOR ADDITIONAL SOUNDER WIRING DIAGRAM SBC-2 - DDC, AND SBC-2R - DDC INFORMATION, PLEASE REFER TO
INSTALLATION INSTRUCTION HA-06-085-DDC.

INDIVIDUAL SOUNDER WIRING DIAGRAM (4 WIRE) SBC-4-DDC


NEXT DEVICE

UL LISTED
12V/24V

EOL
RELAY

POWER
SUPPLY

12V: SBC-4/12
24V: SBC-4/24

NEXT DEVICE

TOP VIEW

P572

P572

03

03
J2

NEXT

J4

NEXT

J3

J3
ON

4
3
2
1
1

RED
BLK
RED
BLK
GRN
YEL
ORG
RED
BLK
WH
T

S1

S1

RE D
BLK
RE
D
BLK
GRN
YEL
ORG
RE
D
BL K
WHT

ON

J4

RED
BLACK

NC
NO
COM
+ 12
- 12

J2

UL
LISTED
CONTROL
PANEL

NC
NO
COM
+ 12
- 12

INITIATING
LOOP

RED

RED
BLACK

BLACK

EOL
RESISTOR

BOTTOM VIEW

NOTES: FOR ADDITIONAL SOUNDER WIRING DIAGRAM SBC-4-DDC INFORMATION, PLEASE REFER TO INSTALLATION
INSTRUCTION HA-06-086-DDC.

Delta Digital Controls SBC - Conventional Sounder Base

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed

CZM-DDC CONVENTIONAL ZONE MODULE


SPECIFICATIONS

STANDARD FEATURES

Provides an address point for a zone of up to 25


conventional smoke detectors
Blinks green when polled. Latched on red (con
trolled by panel) when activated
Device address can also be programmed with a
handheld programmer. Device address- ranges
from 1 to 127
Compatible with Class B (Style B) and Class A (Style
D) wiring
Auxiliary power source provides power for the zone
of detectors
Compatible with conventional detectors, SLR, SIJ,
SLK and SIH series

PRODUCT LISTINGS
Underwriters Laboratories: S5694
CSFM #: 7300-0410:150

Operating Voltage

17~41 VDC

Auxiliary Supply Voltage Nominal

18.8~27.2 V

Average Current Consumption (From S-SC)


Typical Quiescent
400A
2-Wire Detector Loop Current
Standby Detector Load
1mA Max
From Auxiliary Supply
Alarm (Short across detector line)
60mA Max
Data Transmission Current
22mA 20%
EOL Device
4.7K Ohms
Alarm Threshold Level
<1.5K Ohms
Wiring OK Threshold Level
>2.5K Ohms & <6K Ohms
Open Circuit Threshold Level
>10K Ohms
Max. 2-Wire Conventional Detector
Loop Resistance
50 Ohms (total SLC run length)
Operating Temperature Range
32F (0C) ~ 120F (49C)

DESCRIPTION
The Delta Digital Controls Conventional Zone Module
(CZM-DDC) is designed for use on the FireNET analog
addressable system. Up to 127 devices can be placed
on a single SLC loop. The device address is uniquely
stored on an onboard EEPROM. The module allows the
panel to interface and monitor dry contacts such as twowire conventional detectors or pull stations. Each CZMDDC is addressed through the panel and transmits the
status of one zone of devices (25 maximum per zone)
back to the panel. It supervises the power supply as
well as the entire zone of devices. Status conditions are
reported as normal, open or alarm. All 2-wire smoke
detectors must be UL listed as compatible to be interfaced with the CZM-DDC. The interrupt driven Digital Communication Protocol (DCP) combines maximum communication reliability and fast response to emergency
conditions. The module has a single bi-colored LED to
indicate device status. It fits into a standard 4" square
or double gang electrical back box.

Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.

F0013

04/2005

ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, Conventional Zone Module (CZM-DDC). The
modules shall be UL listed and compatible with the Delta Digital Controls Analog Control Panel Protocol. The device
address shall be electrically programmable and stored in EEPROM. A bi-colored LED shall indicate device status.
The CZM-DDC shall be supplied with a plastic cover and shall be suitable for mounting to a 4" square or double gang
electrical back box. The CZM-DDC shall provide a monitor LED that is visible from outside the cover plate.
LIST OF COMPATIBLE DEVICES
Detector Model

Back side of a CZM-DDC

Base Model

Detector Type

SLK-24F

Photoelectric

HSB-224

SIH-24F

Ionization

HSB-224

SLR-24H

Photoelectric w/heat

NS4-224, NS6-224

SLR-24V

Photoelectric

SLR-835/-835W

Photoelectric (8-35V)

SLR-835H/-835HW

Photoelectric (8-35V)
w/thermal

SLR-835B-2

Photoelectric (8-35V) (baseless)

NS4-224, NS6-224
NS4-224, NS6-224
NS4-224W, NS6-224W
NS4-224, NS6-224
NS4-224W, NS6-224W
N/A

SLR-835BH-2

Photoelectric (8-35V)
w/thermal (baseless)

N/A

SIJ-24

Ionization

NS4-224, NS6-224

DCD-135/-190

Heat Fixed Temp/Rate of Rise

NS4-224, NS6-224

DFE-135/-190

Heat Fixed Temp

HSC-224L

EXPLODED VIEW

NFPA STYLE D WIRING DIAGRAM

3-4: CLASS A
OPTIONAL BRANCH
CIRCUIT TO NEXT
INTERFACE MODULE.
MODULE SUPERVISES
SUPPLY VOLTAGE AND
DETECTOR LOOP.

U.L. LISTED
COMPATIBLE
FIRE CONTROL
PANEL

SC

CLASS A

SER. NO. XXXXXXXXX

TB1

SC

SC

UL LISTED 24VDC POWER LIMITED +


AND REGULATED
POWER SUPPLY,
LISTED FOR FIRE
PROTECTION
WITH BATTERY
BACKUP.

JP2

CZM
Conventional Zone Module

NOTE: ENSURE JUMPER IS IN CORRECT POSITION


FOR WIRING CONFIGURATION. (POSITION 3-4)

TB2

IN+
IN-

24V-

OUT+

24V+

OUT-

MAX. 25 CONVENTIONAL
DETECTORS
24-

24V+

S5694

NEXT DEVICE

ALL WIRING IS SUPERVISED AND POWER LIMTED.


SIGNALING DEVICE
ISSUE NO. AU-6110

EB

DO NOT MIX FIRE ALARM INITIATING, SUPERVISORY, OR


SECURITY DEVICES ON THE SAME MODULE.

NFPA STYLE B WIRING DIAGRAM

EXPLODED VIEW

1-2: CLASS B
OPTIONAL BRANCH
CIRCUIT TO NEXT
INTERFACE MODULE.
MODULE SUPERVISES
SUPPLY VOLTAGE AND
DETECTOR LOOP.

SC

U.L. LISTED
COMPATIBLE SC
FIRE CONTROL S
PANEL
UL LISTED 24VDC POWER LIMITED +
AND REGULATED
POWER SUPPLY,
LISTED FOR FIRE
PROTECTION
WITH BATTERY
BACKUP.

JP2

CZM

CLASS B

Conventional Zone Module


SER. NO. XXXXXXXXX

TB1

TB2

IN+

SC

NOTE: ENSURE JUMPER IS IN CORRECT POSITION


FOR WIRING CONFIGURATION. (POSITION 1-2)

IN-

S
24V-

OUT+

24V+

OUT-

E.O.L. DEVICE 4.7K


PART NUMBER
0400-01820

MAX. 25 CONVENTIONAL
DETECTORS
24-

24V+

U.L. LISTED
E.O.L. DEVICE 4.7K
PART NUMBER
0400-01820

S5694

NEXT DEVICE
SIGNALING DEVICE
ISSUE NO. AU-6110

EB

ALL WIRING IS SUPERVISED AND POWER LIMTED.


DO NOT MIX FIRE ALARM INITIATING, SUPERVISORY, OR
SECURITY DEVICES ON THE SAME MODULE.

Delta Digital Controls CZM - DDC Conventional Zone Module

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed

DCP-AMS-DDC SERIES ADDRESSABLE MANUAL PULL STATIONS


SPECIFICATIONS
Operating Voltage (SLC)
17~41 VDC
Average Current Consumption 600uA (Typical)
Alarm Current
8mA
Ambient Temperature
32F (0 C) ~ 120F (49C)
Maximum Humidity
90% RH, non-condensing
Dimensions
3.4"W x 4.8"H x 2.0"D
Mounting
Single gang or 4" square
electrical box

MODEL DESCRIPTION
DCP-AMS-DDC

DCP-AMS-KL-DDC

DCP-AMS-DDC
DCP-AMS-LP-DDC
DCP-AMS-KL-DDC
DCP-AMS-KL-LP-DDC

Single Action Hex Key Lock


Dual Action Hex Key Lock
Single Action Key Lock
Dual Action Key Lock

DESCRIPTION
The DCP-AMS-DDC are the Delta Digital Controls series
of addressable manual pull stations that provide a fast
and practical means of manually initiating a fire alarm
signal. Both single action and dual action manual pull
stations are available. Resetting of the pull station
requires either a Cat 211 key or a 1/8" hex key
(depending upon the model used).

DCP-AMS-LP-DDC

DCP-AMS-KL-LP-DDC

STANDARD FEATURES

Addressable integrated design


All metal construction
Single and dual action models available
Extremely easy to operate
Bi-colored status LED indicates Standby and
Alarm conditions
Address is programmable in EEPROM
Address can be programmed when installed
Key lock or hex key lock models available
Terminals accept up to 14AWG wire
Surface mount back box available

An alarm condition is actuated by pulling down on the


handle of the DCP-AMS-DDC and DCP-AMS-KL-DDC
single action models. On the dual action models DCPAMS-LP-DDC and DCP-AMS-KL-LP-DDC the Lift and
Pull cover must be lifted before pulling down on the pull
station handle. Once the pull station is activated, the
handle cannot be put back into a normal standby
condition without using the key operated reset feature.
The DCP-AMS-DDC series is electronically addressable
and includes a bi-colored status LED. The LED blinks
green indicating normal communication with the DCP
compatible SLC loop. When an alarm condition is
actuated by pulling the handle, the LED will latch Red
to indicate the alarm condition.

PRODUCT LISTINGS
California State
Fire Marshal
S6512

Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

7150-0410:169
Continued on back.

F0013

04/2005

ENGINEERING SPECIFICATIONS
Manual pull stations shall be Delta Digital Controls addressable AMS-series single or dual action models, DCPAMS-DDC, DCP-AMS-KL-DDC, DCP-AMS-LP-DDC, or DCP-AMS-KL-LP-DDC. Models shall be made of 14 AWG
CRS and painted with Red enamel. The words Fire Alarm shall be in a contrasting color and be embossed text 1/2" tall.
The electronics shall be fully integrated into the manual pull station requiring only connection to the SLC loop of the
control panel. Programming of the manual pull station address must be possible with the manual pull station fully
installed.
Manual pull stations shall be Underwriters Laboratories Inc. Listed, CSFM Approved, and be installed within the limits
defined in the American Disabilities Act.

WIRING DIAGRAMS
Delta America
Digital Corporation
Controls
Hochiki
DCP-AMS

OUT TO
NEXT
MODULE

Addressable Manual Pull Station

Ser. No.

SC-

S+
S+

SC-

For Proper Installation, see HA-06-135 Rev 12/05

S6512
NON-CODED ALARM BOX
36CC

UL
UL
Listed
LISTED
+ S
Hochiki
DDC
DCP
- SC
Compatible
Compatible
Panel
Panel
TYPICAL WIRING DIAGRAM EXAMPLE, CONNECTED
TO A COMPATIBLE LISTED CONTROL PANEL

Class B (Style 4)
Hochiki America
Delta
Digital Corporation
Controls
DCP-AMS

Hochiki America
Delta
Digital Corporation
Controls
DCP-AMS

Delta
Digital Corporation
Controls
Hochiki America
DCP-AMS

Addressable Manual Pull Station

Addressable Manual Pull Station

Addressable Manual Pull Station

Ser. No.

Ser. No.

Ser. No.

S+

SC-

S6512

+ S

NON-CODED ALARM BOX


36CC

UL
LISTED
Listed
- SC
DDC
Hochiki
DCP
DCP
+ S
Compatible
Compatible
Panel
Panel
-

SC-

S+

For Proper Installation, see HA-06-135 Rev 12/05

S+

SC-

For Proper Installation, see HA-06-135 Rev 12/05

For Proper Installation, see HA-06-135 Rev 12/05

S6512

S6512
NON-CODED ALARM BOX
36CC

NON-CODED ALARM BOX


36CC

SC

Class A Return (Style 6)


Class A (Style 7)
Delta Digital
Hochiki
AmericaControls
Corporation
DCP-AMS

Hochiki
AmericaControls
Corporation
Delta Digital
DCP-AMS

Addressable Manual Pull Station

Addressable Manual Pull Station

For Proper Installation, see HA-06-135 Rev 12/05

(OUT) S

(OUT) SC

S6512

NON-CODED ALARM BOX


36CC

DCP-SCI

SC-

SER. NO. XXXXXXXXX

S+

LISTED
SIGNALING DEVICE
ISSUE NO. AH-9774

(IN) SC

Hochiki America Corporation

(IN) S

S5694

DCP-SCI

SER. NO. XXXXXXXXX

LISTED
SIGNALING DEVICE
ISSUE NO. AH-9774

(OUT) S

(OUT) SC

Hochiki America Corporation

(IN) SC

S5694

NON-CODED ALARM BOX


36CC

(IN) S

For Proper Installation, see HA-06-063 Rev 2/02

S6512

DCP-SCI

For Proper Installation, see HA-06-135 Rev 12/05

(OUT) S

(OUT) SC

SER. NO. XXXXXXXXX

SC-

LISTED
SIGNALING DEVICE
ISSUE NO. AH-9774

S+

Hochiki America Corporation

(IN) SC

S5694

(IN) S

For Proper Installation, see HA-06-063 Rev 2/02

DCP-SCI

SER. NO. XXXXXXXXX

LISTED
SIGNALING DEVICE
ISSUE NO. AH-9774

Hochiki America Corporation

UL
UL
Listed
LISTED
DDC
Hochiki
DCP
DCP
Compatible
Compatible
Panel
Panel - SC

S5694

S
SC

For Proper Installation, see HA-06-063 Rev 2/02

For Proper Installation, see HA-06-063 Rev 2/02

Ser. No.

Ser. No.

(IN) S
(IN) SC
(OUT) S

(OUT) SC

Delta Digital Controls DCP-AMS-DDC SERIES

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed

DIMM - DUAL INPUT MONITOR MODULE

SPECIFICATIONS
Operating Voltage

17~41 VDC

Average Current Consumption

600A(Typical)

Alarm Current

30mA

Dimensons
Ambient Temperature

4.2"W x 4.7"H x 1.4"D


32F (0C) ~ 120F (49C)

Max. Humidity

90% RH, non-condensing

Mounting

4" square electrical box

DESCRIPTION
STANDARD FEATURES

Fast, reliable contact monitoring utilizing the


Delta Digital Controls DCP (Digital
Communications Protocol)
127 devices can be used per DCP loop
Bi-colored indicating LED provides module status
Dual input contact monitor
Can be programmed to monitor Normally Open
(NO) or Normally Closed (NC) contacts
Operates on Class A or Class B SLC loop
Accepts up to 14 AWG wire
Mounts to 4" square gang box

The Delta Digital Controls Dual Monitor Module (DIMM)


is designed for use on the FireNET analog addressable
system. It provides two independent contact monitoring
circuits while only utilizing one address on the SLC
loop. Up to 127 devices can be placed on a single
SLC loop. The device address is uniquely stored on
an onboard EEPROM. The module can be programmed
to monitor Normally Open (NO) or Normally Closed
(NC) contact fire alarm and supervisory devices. The
interrupt driven Digital Communication Protocol (DCP)
combines maximum communication reliability and fast
response to emergency conditions. The module has a
single bi-colored LED to indicate device status. It fits
into a standard 4" square or double gang electrical
back box.

PRODUCT LISTINGS
Underwriters Laboratories: S5694
CSFM #: 7300-0410:150

Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.

F0013

04/2005

ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, addressable contact monitoring modules Delta
Digital Controls DIMM. The modules shall be UL listed and compatible with the Delta Digital Controls FireNET fire alarm
control panel. The device address shall be electrically programmable and stored in EEPROM. A bi-colored LED shall
indicate device status.

Back Side of a DIMM-DDC


WIRING DIAGRAM

U.L. LISTED
E.O.L. DEVICE 22K
PART NUMBER
0400-01000

DCP-DIMM

TB2

TYPICAL WIRING FOR N/O CONTACTS ONLY

OUT TO NEXT MODULE

Dual Input Monitor Module


SER. NO. XXXXXXXXX

TB1

Input A

E.O.L. DEVICE 22K


PART NUMBER
0400-01000

ANY NUMBER OF UL LISTED N/O CONTACT CLOSURE


DEVICES MAY BE USED .

SC

U.L. LISTED

COMPATIBLE
FIRE CONTROL
PANEL

Input B

TYPICAL WIRING FOR N/C CONTACTS ONLY


S5694

U.L. LISTED
E.O.L. DEVICE 22K
PART NUMBER
0400-01000

SIGNALING DEVICE
ISSUE NO. AU-6031

AND INHERENTLY POWER LIMITED.

E.O.L. DEVICE 22K


PART NUMBER
0400-01000

CAUTION!
DO NOT CONNECT MORE
THAN ONE N/C CONTACT
TO AN INPUT!

Delta Digital Controls DIMM - DUAL INPUT MONITOR MODULE

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed

FN-CTM CITY TIE MODULE

SPECIFICATIONS
Operating Voltage
Average Current Consumption
Alarm Current
FN-CTM-DDC
City Tie Module

Ambient Temperature
Maximum Humidity
Dimensions
Weight
Mounting

12 ~ 30 VDC
0mA (Standby)
1A for 0.5 seconds

32F (0 C) ~ 120F (49C)


90% RH, non-condensing
4.2"W X 4.7"H X 1.1"D
Approximately 3.0 ounces
4" square electrical box

DESCRIPTION
STANDARD FEATURES

Interfaces Fire Alarm Control Panels to a Local


Energy type City Tie monitoring circuit
Integrates Fire Alarm Control Panel EOL device
into module for supervision of interface wiring
Wide operating voltage
Power limited operation
Transient protection
Terminals accept up to 14 AWG wire
Mounts to a standard 4" electrical back box

The FN-CTM-DDC City Tie Module is used to connect


a Fire Alarm Control Panel to a Local Energy type City
Tie Monitoring circuit. The FN-CTM-DDC City Tie
Module circuit provides the power necessary to trip
the Master Box Trip Coil when the Fire Alarm Control
Panel goes into alarm.
The City Tie Circuit is capable of providing 1A for 0.5
seconds to operate the Master Box Trip Coil. The wiring
is supervised to the Master Box by placing the Fire
Alarm Control Panel EOL device on the terminals of
the FN-CTM-DDC City Tie Module.

PRODUCT LISTINGS

S8255

Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.

F0013

04/2005

ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, the Delta Digital Controls FN-CTM-DDC City Tie
Module. The module terminal blocks shall be capable of accepting up to 14 AWG wire. The FN-CTM-DDC shall be
configured such that the Fire Alarm Control Panels EOL (end of line) device connects directly with the FN-CTM-DDC to
ensure supervision of the interface wiring. The module shall fit into a standard 4" electrical back box. The FN-CTM-DDC
shall be Underwriters Laboratories Listed for the intended purpose.

FN-CTM-DDC

Rear view of FN-CTM-DDC


City Tie Module
WIRING DIAGRAM
Note: When City Tie wiring leaves
the building, install 26 AWG wire
between the City Tie module and
the Trip Coil. A short length of 24
AWG wire must be used to
interface between the 26 AWG
and the City Tie Module terminal
block. Maximum coil resistance
and wire resistance must not
exceed 30 Ohms.
Ground Wire

Hochiki America Corporation

FN-CTM

City Tie Module


SERIAL NO.XXXXX

Local Energy
City Tie
Trip Coil

E.O.L. DEVICE

City Tie

NAC Input

EOL

NAC Circuit

S8255

U.L. LISTED
E.O.L. DEVICE
FOR FireNET
PART NUMBER
0400-01046
10K OHM 1/4W

For Proper Installation


see HA-06-137 Rev 5/06

Signaling Devices
ISSUE NO. BF-8887

Hochiki FireNET
or
Compatible UL Listed
Fire Alarm Control Panel
NAC Circuit
Wiring Polarity Shown in
Alarm Condition.

All Wiring is Power Limited, Connect only to Power Limited Circuits.


For Use Only With Supervised Circuits.
Delta Digital Controls FN-CTM CITY TIE MODULE

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed, FM Approved

DCP - FRCME - FAST RESPONSE CONTACT MODULE


SPECIFICATIONS
Operating Voltage DCP Powered Loop 17~41 VDC
Average Current Consumption
550 A (Typical)
Alarm Current
8mA
Dimensions
FRCME-4-DDC
4.2"W x 4.7"H x 1.4"D
FRCME-P-DDC
3.0"W x 1.9"H x 0.5"D
FRCME- S-DDC
2.8"W x 1.8"H x 0.7"D
Ambient Temperature
32F (0C) ~ 120F (49C)
Max. Humidity
90% RH, non-condensing
Mounting
FRCME-4-DDC Mounts to double gang/4" square back box
FRCME-S/FRCME-P-DDC Mounts inside a singlegang
back box
FRCME-4-DDC

STANDARD FEATURES
Single input contact monitor
Fast, reliable contact monitoring utilizing the
Delta Digital Controls DCP (Digital Communications
Protocol)
Two different mounting configurations
127 devices can be used per DCP loop
Bi-colored indicating LED provides module status
(FRCME-4-DDC only)
Can be programmed to monitor Normally Open
(NO) or Normally Closed (NC) contacts
Operates on Class A or Class B SLC loop
Accepts up to 14 AWG wire
UL listed UL 864

PRODUCT LISTINGS
Underwriters Laboratories: S5694
CSFM #: 7300 - 0410:150
FM#: 3022559
MEA Report#: 284-91-E Vol. IV (FRCME-4-DDC/
FRCME-S only)

DESCRIPTION
The Delta Digital Controls FRCME-DDC Fast Response
Contact Monitoring Modules are designed to be used with
pull stations, water flow switches, and other applications
requiring the monitoring of dry contact alarm initiating devices.
The interrupt driven Digital Communications Protocol (DCP)
combines maximum communication reliability and fast
response to emergency conditions. Two different mounting
configurations are provided to meet a wide range of
applications. The FRCME-DDC contact monitoring module
does not require a separate 24 VDC power source.
Each addressable contact monitoring module is
programmed with its own unique Signaling Line Circuit
(SLC) loop address. The device address is electrically
programmable and stored in onboard EEPROM. Up to 127
devices can be placed on the Delta Digital Controls DCP
SLC loop. The module supervises the wiring to the contact
with an End Of Line (EOL) resistor. It can be programmed to
monitor Normally Open (NO) or Normally Closed (NC)
contacts. If a fault condition occurs in the wiring, the module
sends a trouble status signal to the fire alarm control panel.
When a change of status (contact changes state) is sensed
by the FRCME-DDC, it sends an interrupt to the FireNET
control panel indicating that an alarm has occurred.
The FRCME-P-DDC and FRCME-S-DDC are small package
designs and are suitable for mounting in a small junction
box behind a pull station or other monitored device.The
FRCME-4-DDC is mounted to a cover plate for a 4" square or
double gang junction box. It contains a visible bi-colored
indicating LED to provide module status.

Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.

F0013

04/2005

ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, addressable contact monitoring modules Delta
Digital Controls DCP-FRCME-4-DDC, DCP-FRCME-S-DDC and FRCME-P-DDC.The modules shall be UL listed and
compatible with the Delta Digital Controls FireNET fire alarm control panel. The device address shall be electrically
programmable and stored in EEPROM.
The FRCME-S-DDC and FRCME-P-DDC shall fit inside a single gang electrical back box. The FRCME-4-DDC shall be
supplied with a plastic face plate and shall be suitable for mounting to a 4" square or double gang electrical back box.
The FRCME-4-DDC shall provide a monitor LED that is visible through the face plate.

FRCME-S-DDC

FRCME-4-DDC

FRCME-P-DDC

OUT TO
NEXT
MODULE

E.O.L. DEVICE
PART NUMBER
0400-01046

IN-B

SIGNALING DEVICE
ISSUE NO. AH-9755

IN-A

S5694

SC-

DCP-FRCME-4

TYPICAL WIRING FOR N/O CONTACTS ONLY


U.L. LISTED
COMPATIBLE
CONTROL
PANEL

S+

FRCME-4-DDC /
FRCME-S-DDC

SER. NO. XXXXXXXXX

WIRING DIAGRAM

ANY NUMBER OF UL LISTED N/O CONTACT CLOSURE


DEVICES MAY BE USED . DO NOT MIX FIRE ALARM
INITIATING OR SUPERVISORY ON THE SAME MODULE

U.L. LISTED
E.O.L. DEVICE
PART NUMBER
0400-01046

ALL WIRING SHOWN IS SUPERVISED


AND INHERENTLY POWER LIMITED.

IN-B

SIGNALING DEVICE
ISSUE NO. AH-9755

IN-A

DCP-FRCME-4

SC-

SER. NO. XXXXXXXXX

U.L. LISTED
COMPATIBLE
CONTROL
PANEL

S+

S5694

OUT TO
NEXT
MODULE

TYPICAL WIRING FOR N/C CONTACTS ONLY

U.L. LISTED
E.O.L. DEVICE
PART NUMBER
0400-01046

E.O.L. DEVICE
PART NUMBER
0400-01046

ALL WIRING SHOWN IS SUPERVISED


AND INHERENTLY POWER LIMITED.

CAUTION!
DO NOT CONNECT MORE THAN ONE N/C CONTACT TO AN INPUT.

FRCME-P-DDC
OUT TO
NEXT
MODULE

E.O.L. DEVICE
PART NUMBER
0400-01046

RED

BLK

IN-A
SC (IN)
WHT

IN-B

SIGNALING DEVICE
ISSUE NO. AH-9765

S (OUT)

SER. NO. XXXXXXXXX

S U.L. LISTED
COMPATIBLE
SC CONTROL
PANEL

SC (OUT)

DCP-FRCME-P

TYPICAL WIRING FOR N/O CONTACTS ONLY


SC

S (IN)

S5694

ANY NUMBER OF UL LISTED N/O CONTACT CLOSURE


DEVICES MAY BE USED . DO NOT MIX FIRE ALARM
INITIATING OR SUPERVISORY ON THE SAME MODULE

ALL WIRING SHOWN IS SUPERVISED


AND INHERENTLY POWER LIMITED.
OUT TO
NEXT
MODULE

S U.L. LISTED
COMPATIBLE
SC CONTROL
PANEL

BLK
WHT

IN-B

SER. NO. XXXXXXXXX

SC

IN-A
SC (IN)

SIGNALING DEVICE
ISSUE NO. AH-9765

RED

SC (OUT)

DCP-FRCME-P

S (OUT)
S (IN)

S5694

U.L. LISTED
E.O.L. DEVICE
PART NUMBER
0400-01046

ALL WIRING SHOWN IS SUPERVISED


AND INHERENTLY POWER LIMITED.

TYPICAL WIRING FOR N/C CONTACTS ONLY

E.O.L. DEVICE
PART NUMBER
0400-01046

U.L. LISTED
E.O.L. DEVICE
PART NUMBER
0400-01046

CAUTION!
DO NOT CONNECT MORE THAN ONE N/C CONTACT TO AN INPUT.

Delta Digital Controls DCP - FRCME - FAST RESPONSE CONTACT MODULE

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed, FM Approved

DCP-R2M - DUAL RELAY MODULE

SPECIFICATIONS
Contacts
2 Independenly Controlled Form C
Contact Rating
1A @ 30 VDC / 0.5A @ 125 VAC
Standby Current
150 A Max.
Alarm Current
150 A Max.
Dimensions
4.2"W x 4.7"H x 1.4"D
Ambient Temperature
32F (0C) ~ 120F (49C)
Humidity
90% RH, Non-Condensing
Mounting
4" square electrical box

DESCRIPTION
STANDARD FEATURES
Provides two independently configurable Form C
contacts per address
Contacts are rated 1.0 Amps @ 30 VDC or 0.5 Amp
@ 125 VAC
Up to127 devices can be used on each SLC loop
Visible Bi-colored LED is software controlled and
can be programmed to blink red or green when
polled. The LED can be latched on when activated
Programming is highly flexible providing 16 priority
states plus zoning capability

The Dual Relay Module (R2M-DDC), has been designed


to provide flexibile and quick response to emergency
conditions. The R2M-DDC allows independent control of
two form C contacts for a variety of normally open and
normally closed contact applications such as fan operation,
elevator recall, door closure, and auxiliary notification.
Each R2M-DDC module provides independent control of
two Form C contacts while utilizing one SLC (Signaling
Line Circuit) address. The R2M-DDC module has a highly
configurable programming algorithm that allows the user
to setup groups of devices (zoning) for simultaneous
operation of multiple R2M-DDC modules. Each module
has 16 priority states that are programmed. The operating
parameters are maintained by the module and do not
require individual communication with the control panel
during the emergency condition to operate. The control
panel broadcasts the control command on the SLC loop
and the R2M-DDC modules do the rest based on their
custom configuration. Since mechanically latching relays
are used within the R2M-DDC module, a separate 24VDC
power source is not required.

PRODUCT LISTINGS
Underwriters Laboratories: S5694
Underwriters Laboratories of Canada: CS943
CSFM #: 7300-0410:150
FM#: 3022559
MEA Report # 284-91-E Vol. IV
Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.

F0013

04/2005

ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, the Delta Digital Controls DCP-R2M-DDC addressable
relay module. The modules shall be UL listed compatible with Delta Digital Controls Digital Communications Protocol
(DCP) supporting control panel loops. The relay module must provide two Form C dry contacts rated at 1A @ 30 VDC
or 0.5A @ 125 VAC. The relay module must be suitable for mounting in a standard 4" square electrical box. The relay
module must provide a bi-colored LED for indication of status.

DCP-R2M-DDC

Back side of a R2M-DDC

WIRING DIAGRAM

DCP-R2M

NO1

S, SC WIRING SERIAL NO. XXXXXXXXX


POWER LIMITED

OUT TO NEXT MODULE

COM1

TB1

U.L. LISTED
COMPATIBLE
FIRE CONTROL
PANEL

SC -

NC1

NON
POWER
LIMITED

S +

(FORM "C" CONTACTS)


(NON-SUPERVISED)

NO2

CROSS OUT
TYPE NOT
USED

SET 2

COM2

S5694
SIGNALING DEVICE
ISSUE NO. AH-9769

Delta Digital Controls DCP-R2M - DUAL RELAY MODULE

SET 1

POWER
LIMITED

NC2

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed

SCI - DDC SHORT CIRCUIT ISOLATOR


OPERATION
* Class A Configuration Wiring:
The DCP-SCI short circuit isolator-DDC should be located
between any devices on the SLC loop. In the event of a
short on the SLC loop, the two adjacent isolators (closest
isolators to the left and right of the shorted section) will
activate and their respective LED indicators will be turned
on. All devices between the active short circuit isolators
will be dead. This will prevent entire loop failure. Upon
removal of the short condition, the DCP-SCIs-DDC will
automatically restore, the entire loop to the normal
operating state.

STANDARD FEATURES

Can be placed at any location on SLC loop.


Checks the line for short circuit at power up. If the
line is normal, the relay will be returned on. If a
line short is detected, the relay remains open.
Indication of short circuit by a yellow LED

SPECIFICATIONS

Absolute Maximum Applied Voltage: S, SC: 41 VDC


Supply Voltage Norminal:
S, SC: 33 VDC
Normal Current Consumption:
270 A (Typical)
Active Current Consumption:
10 mA (Typical)
(Short Circuit Condition)
Dimensions:
4.2"W x 4.7"H x 1.4"D
Weight:
1.4 oz
Visual Indicator (Yellow Status LED):
- No indication in normal condition.
- On steady in active (short) condition.
Maximum Quantity Per Loop:
127
Operation Temperature Range:
0C (32F)~ 49C (120F) Non-condensing
Allowable Ambient Humidity: 90% Non-condensing

* Class B Configuration Wiring:


The DCP-SCI short circuit isolator-DDC should be located
between any devices on the SLC loop. In the event of a
short on SLC loop, an isolator closest to the shorted
section will activate and the LED will be turned on. All
the devices beyond the shorted section will be
disabled. Upon removal of the short condition, the DCPSCI will automatically restore the entire loop to the normal
operating state.
For the best performance of DCP-SCI short circuit, use
class A configuration.
WIRING:
Note: All wiring must conform to local codes, ordinances
and regulations.
1. Install module wiring in accordance with job drawings
and appropriate wiring diagram.
2. Secure the module to an approved electrical box
(supplied by installer).
MOUNTING REQUIREMENTS: 4" SQ Electrical box.

PRODUCT LISTINGS
Underwriters Laboratories: S5694
Underwriters Laboratories of Canada: CS943
CSFM #: 7300-0410:150
MEA Report # 284-91-E Vol. IV

Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.

F0013

04/2005

ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, the Delta Digital Controls DCP-SCI-DDC short
circuit isolator-DDC. The modules shall be UL listed compatible with Delta Digital Controls Digital Communications
Protocol (DCP) supporting control panel loops. The isolator module must be suitable for mounting in a standard 4"
square electrical box. The isolator module must provide a yellow LED for indication of status.

DCP-SCI-DDC

Back side of a DCP-SCI-DDC

TB1

UL LISTED
COMPATIBLE
CONTROL
PANEL

(IN) S
(IN) SC
(OUT) S

(OUT) SC

LISTED

SIGNALING DEVICE
ISSUE NO. AH-9774

DCP-SCI

S5694

SER. NO. XXXXXXXXX

SHORT CIRCUIT ISOLATOR


TB1

(IN) S

(IN) SC
(OUT) S
(OUT) SC

GROUP OF VARIOUS DCP MODULES


GROUP OF VARIOUS DCP SENSORS

OPTIONAL RETURN LINE


(NOT REQUIRED)

(IN) S

(IN) SC

(OUT) S
(OUT) SC

TB1

SHORT CIRCUIT ISOLATOR

-++ +

SIGNALING DEVICE
ISSUE NO. AH-9774

DCP-SCI

SER. NO. XXXXXXXXX

S5694

WIRING DIAGRAM

SER. NO. XXXXXXXXX

DCP-SCI

SIGNALING DEVICE
ISSUE NO. AH-9774

S5694

LISTED

SHORT CIRCUIT ISOLATOR


TYPICAL WIRING DIAGRAM EXAMPLE, CONNECTED
TO A COMPATIBLE LISTED CONTROL PANEL

Delta Digital Controls SCI - DDC SHORT CIRCUIT ISOLATOR

ALL WIRING SHOWN IS SUPERVISED


AND INHERENTLY POWER LIMITED.
ANY COMBINATION OF MODULES
AND/OR SENSORS MAY BE PLACED
BETWEEN ISOLATORS

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed, FM Approved

SOM - SUPERVISED OUTPUT MODULE


SPECIFICATIONS
Supply Voltage (S-SC):

17-41 VDC

Auxiliary Supply Voltage:

18-30 VDC

Average Current Consumption:


(on S-SC Line)
Current Consumption on

Normal 220 A
Maximum 300 A
Typical 150 A

Auxiliary Power Lines:


Dimensions:
Ambient Temperature:
Mounting:

4.2"W x 4.7"H x 1.4"D


32F (0C) ~ 120F (49C)
4" square electrical box

Maximum Output Current: 2A@30VDC power limited


Relative Humidity:

90% RH Non-condensing

STANDARD FEATURES

Flexible application.
Quick response to emergency conditions.
Operation parameters are maintained by the
module, and individual communication with the
control system during emergency conditions
is not required.
Contacts are rated 2.0 Amps @ 30VDC.
Programming is highly flexible providing 16
priority states plus zoning capability.
Program status:
LED will flash red or green.
Programmed device output is turned off, silenced,
or programmed to modulate pattern.

PRODUCT LISTINGS
Underwriters Laboratories: S5694
Underwriters Laboratories of Canada: CS943
CSFM #: 7300-0410:150
FM#: 3022559
MEA Report # 284-91-E Vol. IV

DESCRIPTION
The Supervised Output Module (SOM)-DDC, has been
designed to provide application flexibility and quick
response to emergency conditions. Flexibility is
provided by a wide range of operating modes,
including supporting multi-zone operations, and/or
functions, up to 16 different modulation patterns and
multi-state programming. The operating parameters
for the SOM-DDC are maintained by the module and
do not require individual communication with the
control system during emergency conditions to
operate. The control panel simply broadcasts
system conditions on the Signaling Line Circuit
(SLC) and the SOM-DDCs do the rest based upon
the custom configuration. Each SOM-DDC provides
a Class B Individual Circuit rated for 2.0 Amp @ 30
VDC. Each SOM-DDC also requires a 24 Volt power
source in addition to the SLC. Provide software
controlled LED indication: blinks green or red when
polled, or can be latched on.

Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.

F0013

04/2005

ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, addressable Supervised Output Module (SOM)DDC. The modules shall be UL listed and compatible with Delta Digital Controls FireNET fire alarm control panel. The
device address shall be electrically programmable and stored in EEPROM. A bi-colored LED shall indicate device status.
The SOM-DDC shall be supplied with a plastic cover and shall be suitable for mounting to a 4" square or double gang
electrical back box. The SOM-DDC shall provide a monitor LED that is visible from outside the cover plate.

DCP-SOM-DDC

Back side of a SOM-DDC

WIRING DIAGRAM
U.L. LISTED
E.O.L. DEVICE
PART NUMBER
0400-01046

E.O.L.
DEVICE
0400-01046

NOTIFICATION APPLIANCE CIRCUIT (NAC)


NAC INSTALLATION WIRING SHALL NOT EXCEED
50 OHMS (14-18 AWG.)

OUTPUT TO
COMPATIBLE
U.L. LISTED
DEVICES FOR
FIRE
PROTECTION
SIGNALING
SERVICE

DCP-SOM
OUT TO NEXT MODULE

SER. NO. XXXXXXXXX


2

TB1

TB2

24+

OUT TO

GND

MODULE

NEXT

U.L. LISTED
SC

COMPATIBLE
FIRE CONTROL

PANEL

OUT+
1

ALL WIRING SHOWN ON TB1


IS SUPERVISED AND
INHERENTLY POWER LIMITED

U.L. LISTED REGULATED,


POWER LIMITED SUPPLY FOR
FIRE PROTECTION
SIGNALING SERVICE FOR
AUDIBLE DEVICES. REFER
TO CONTROL PANEL
MANUFACTURER'S
INSTALLATION
INSTRUCTIONS.

OUT S5694

SIGNALING DEVICE
ISSUE NO. AH-9758

ALL WIRING SHOWN ON TB2


IS SUPERVISED AND
INHERENTLY POWER LIMITED

WARNING!!!

USE ONLY FPL, FPLR, OR


FPLP WIRING IN ACCORDANCE
WITH ARTICLE 760 OF THE
NATIONAL ELECTRICAL CODE.

Delta Digital Controls SOM - SUPERVISED OUTPUT MODULE

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed

SRM-SOLENOID RELEASING MODULE


APPLICATION
This module will be connected to a SLC loop utilizing
the Delta Digital Controls DCP (digital communications
protocol). The DCP-SRM-DDC will provide a supervised
24 VDC output to a fire alarm releasing solenoid or squib
agent release supervision circuit.

OPERATION

STANDARD FEATURES

Solenoid output with supervision for open and short


circuit conditions. Check on supervised status
occurs upon receipt of an A-D command
Output relay rate to supply 2A @ 30 VDC for the
solenoid load
Addressable FET switch used to control output for
extra security in releasing functions
Activation pulse time from 1-127seconds in 1
second intervals or 1-127 minutes in 1 minute
intervals.
Visible Bi-colored LED is software controlled and can
be programmed to blink red or green when polled.
The LED can be latched on when activated.
Programmed with DCP expansion mode commands
or with a handheld programmer

There are separate wiring terminals provided for both the


Solenoid and Agent Release Module (ARM-DDC) devices.
Although there are two sets of terminals, this module can
only be used for one type at a time. The ARM-DDC endof-line (EOL) resistor must be removed when used with a
solenoid. A panel command allows the user to choose
which type of device is being controlled and supervised.
In the event of an alarm condition, the module will be
activated to supply up to 2 amps of current to the solenoid
or ARM-DDC devices. The solenoid activation time is
programmable at the DCP control panel.
Solenoid activating pulse time can be programmed from
1 second to 127 second in 1 second intervals or from 1
minute to 127 minutes in 1 minute intervals. The output
can also be latched on until commanded to be turned off
by the control panel.

SPECIFICATIONS
Absolute Max Applied Voltage:

S, SC: 41VDC
AUX+, AUX-: 26VDC
Supply Voltage Nominal:
S, SC : 33VDC
AUX+, AUX-: 24VDC
Normal Current Consumption (S, SC):
220A
Maximum Current Consumption (S, SC):
300A
Normal AUX+, AUX- Consumption:
1.2mA
(Max. 2Amp load)
Maximum Output Current to SOL+, SOL-: 2A @ 30VDC
End Of Line Device:
2.7K Ohm
Dimensions:
4.2"W x 4.7"H x 0.85"D
Ambient Temperature:
32F (0C) ~ 120F (49C)
Humidity:
90% RH, Non-Condensing
Mounting:
4" square electrical box

PRODUCT LISTINGS
Underwriters Laboratories: S5694
Underwriters Laboratories of Canada: CS943
CSFM #: 7300-0410:150
MEA Report # 284-91-E Vol. IV

Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.

F0013

04/2005

ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, the Delta Digital Controls addressable Solenoid
Releasing Module (SRM-DDC). The modules shall be UL listed compatible with the Delta Digital Controls FireNET fire
alarm control panel. The device address shall be electrically programmable and stored in EEPROM. A bi-colored LED
shall indicate device status.
The SRM-DDC shall fit inside a single gang electrical back box. The SRM-DDC shall be supplied with a plastic cover
and shall be suitable for mounting to a 4" square or double gang electrical back box. The SRM-DDC shall provide a
monitor LED that is visible from outside the cover plate.

DCP-SRM-DDC

E.O.L.
DEVICE

Back side of a SRM-DDC

WIRING DIAGRAM

U.L. LISTED
E.O.L. DEVICE
PART # 0400-01057

NOTIFICATION APPLIANCE CIRCUIT (NAC)


NAC INSTALLATION WIRING SHALL NOT EXCEED
50 OHMS (14-18 AWG.)
(6 COMPATIBLE
DEVICES MAXIMUM)

DCP-SRM
TB2

U.L. LISTED REGULATED, POWER


LIMITED SUPPLY FOR FIRE
PROTECTION SIGNALING SERVICE
FOR AUDIBLE DEVICES.
REFER TO CONTROL PANEL
MANUFACTURER'S INSTALLATION
INSTRUCTIONS.

OUT TO NEXT MODULE

SC (OUT)

SC (IN)

ARM-

S (IN)

OUT TO
NEXT
MODULE

24+GND

S (OUT)

24+GND

SIN

U.L. LISTED
COMPATIBLE
FIRE CONTROL
PANEL

SCOUT SOUT SCIN

TB1

SOL-

AUX + (IN)
AUX - (IN)
AUX + (OUT)
AUX - (OUT)
ARM+
ARMSOL+
SOL-

8
EB
ALL WIRING SHOWN
IS SUPERVISED AND
INHERENTLY POWER LIMITED

Delta Digital Controls SRM-DDC SOLENOID RELEASING MODULE

OUTPUT TO A
COMPATIBLE
U.L. LISTED
FIRE ALARM
RELEASING
SOLENOID

WARNING!!!
USE ONLY FPL, FPLR, OR
FPLP WIRING IN ACCORDANCE
WITH ARTICLE 760 OF THE
NATIONAL ELECTRICAL CODE.

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products

HF-24-DDC ULTRAVIOLET FLAME DETECTOR


APPLICATION
The HF-24-DDC is suited for use wherever there is a need
for automatic detection of fires which can develop quickly
or where contents have great value.
Suggested applications include:
Petroleum Storage
Photographic or Film Storage
Computer Rooms
Print Shops
Museums

STANDARD FEATURES

Detects fast flaming fires


Highly reliable, long life UV receptor tube
Low power consumption
HF-24-DDC can be intermixed with other types of
detection on the panel's detection circuitry
Interchangeable with Delta Digital Controls standard
smoke and heat detector bases.
Size and color similar to other Delta Digital Controls
smoke and heat detectors.
Easily Maintained - cleaning can be accomplished
without disassembling the detector.
Not UL Listed

SPECIFICATIONS
Rated Voltage:
Working Voltage:
Normal Current:
Alarm Current:
Response to Ultraviolet:

17.6 - 27.7 VDC


15 - 30 VDC
200 A @ 24 VDC
250mA Maximum
1850 - 3000 Angstrom

Ambient Temperature:
14 to 122 Fahrenheit (-10 C to +50 C)
Mounting:

Color:

The HF-24-DDC is not a substitute for smoke or heat


detectors, but is an added level of protection against fast
flaming fires only.
There is no set area for which the HF-24-DDC Ultraviolet
Detector is able to cover. The reason is that the size of
the fire and the distance from this fire to the detector all
effect how the detector will respond. There is one nonvariable, however, and that is very small fires must have a
duration of at least 7-15 seconds if within 12 feet, 20-30
seconds at 25 feet.

OPERATION
The HF-24-DDC uses an ultraviolet detector tube which
absorbs very weak ultraviolet light such as that emitted
from a flame. This is detected as a train of discharge
pulses creating a current. The electronic circuitry in the
detector body translates this action as an alarm signal.
There is a counter circuit which prevents the alarm from
occurring from one-shot ultraviolet light such as lightning
or cosmic flares. Additionally there are circuit refinements
which limit the detection of only wave lengths from 1850 to
3000 angstroms thus ignoring visible and infrared light.

HSC-4R - DDC , HSB-DDC


series, NS4 - DDC series,
NS6 - DDC series & HSCDDC-xxx L series bases
Ivory ACS

Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

See Reverse Side for


Detection Range Graph
and Wiring Diagram.

Continued on back.

F0013

04/2005

DETECTION RANGE

Ceiling
120

#1

2m
Ceiling Height

3m

#2

4m
5m
6m
7m
8m

Floor
# 1: Flame from a candle or lighter
# 2: Flame from a wad or newspaper, burning flame

WIRING DIAGRAMS
NS Series and HSC Series Base
HSC SERIES

(+)

NS6 SERIES

COMPATIBLE
UL LISTED
CONTROL
PANEL

PANEL
POWER
SUPPLY

NS4 SERIES

LISTED
END OF LINE
DEVICE

(-)

HSB-2 Wire
UL LISTED
CONTROL
PANEL

(+)
LISTED
END OF LINE
DEVICE
3.9K 1/2W

(-)
PANEL
POWER
SUPPLY

16mA MAX.
OUTPUT

(-)

NEGATIVE

Delta Digital Controls HF-24-DDC ULTRAVIOLET FLAME DETECTOR

16mA MAX.
OUTPUT

CURRENT LIMTED AT 24VDC

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed, FM Approved

SPB-24N-DDC PROJECTED BEAM SMOKE DETECTOR


APPLICATION

The Delta Digital Controls SPB-24N-DDC Projected Beam


Smoke Detector consists of an emitter and receiver. The
projected beam smoke detector should be placed so that
smoke generated by a fire will likely rise into the path of
the beam. The receiver is constantly monitoring and
measuring the intensity of the beam transmitted by the
emitter. Should the smoke from a fire cause a decrease
in the signal strength of a magnitude that exceeds the
programmed obscuration setting, an alarm signal is
generated.

STANDARD FEATURES
Microprocessor based for reliability
Simple setup & alignment with signal strength LED's
Provides 60 feet on center linear protection at a

range of 32.8 feet to 328 feet


Automatic compensation for signal drift or dirty lens
Three field adjustable sensitivity settings
Form A alarm and Form B trouble contacts
Calibrated filters available to verify sensitivity
Color-coded emitter and receiver labels for easy
recognition

SPECIFICATIONS
Rated Voltage
Working Voltage
Supervisory Current
Alarm Current
Trouble Current
Ambient Temperature
Range
Sensitivity Test Feature
Dimensions

Mounting

24VDC
19VDC - 33VDC
250A @ 24VDC
20mA @ 24VDC
20mA @ 24VDC
32 F - 122 F
Manufacturers test filters
5.5" Tall
3.2" Wide
4.0" Deep
Wall mount or
Single Gang Box

The SPB-24N-DDC Projected Beam Smoke Detector can


provide vital fire detection in applications where other types
of detectors may not be able to respond quickly, or at all,
to a fire condition. Examples of some applications where
projected beam smoke detectors have been successfully
used include:
atriums, gymnasiums, theatres, museums,
factories, tunnels, churches, stables,
anechoic chambers
and high air velocity areas. The Delta Digital Controls
SPB-24N-DDC Projected Beam Smoke Detector may also
be used in conjunction with more traditional spot type
smoke
detection devices to provide an even more
comprehensive detection system.

For more information on how to install the Delta Digital


Controls SPB-24N-DDC Projected Beam Smoke Detector
consult the SPB-24N-DDC Installation Instruction Guide
and the applicable NFPAStandards for additional
guidance.

OPERATION
The near infrared pulsed beam generated by the emitter
is sensed by the photodiode of the receiver, where it is
converted into an electrical signal. This signal is then
amplified and applied, via an analog to digital converter, to
a microprocessor. The normal state signal (the initial
beam data) once stored in the microprocessor is used as
reference for comparison with subsequent beam signals.
When there is a difference between actual beam strength
and stored reference data that exceeds the programmed
PRODUCT LISTINGS
Underwriters Laboratories: S1383
Factory Mutual: OD8A1.AY
CSFM #: 7260-0410:141

Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.

F0013

04/2005

OPERATION, continued
alarm obscuration reference level, a fire signal is produced. A trouble signal is generated if the beam is more than 90%
obstructed (as opposed to partially obscured by smoke).
The microprocessor also provides compensation for a change in received signal value, with time, caused by contamination
of the optics. Since such a change with time appears as a slow change in the beam signal, the microcomputer
compensates in such a manner that the signal moves closer to the reference data at a rate approximately +1% per
hour. When this compensating capability reaches a limit, the microcomputer automatically generates a trouble signal.
A calibrated test filter is available upon request to test and verify the sensitivity setting of the projected beam smoke
detectors.

ENGINEERING SPECIFICATIONS
The contractor shall furnish and install, where indicated on the plans, Delta Digital Controls SPB-24N-DDC Projected
Beam Smoke Detector. The detector shall have a range of 32.8 feet to 328 feet. The projected beam smoke detector
shall be field adjustable to one of the three obscuration settings of 25%, 50% or 70% per span. These settings shall be
capable of being verified with calibrated filters. Side to side spacing shall be a maximum of 60 feet on center.
The projected beam smoke detector shall posses circuitry that automatically compensates for normal ambient changes
in the intensity of the emitted beam strength. The microprocessor shall provide compensation for a change in received
signal value, with time, caused by contamination of the optics. Since such a change with time appears as a slow change
in the beam signal, the microcomputer compensates in such a manner that the signal moves closer to the reference data
at a rate of approximately +1% per hour. When this compensating capability reaches a limit, the microcomputer
automatically generates a trouble signal.
The projected beam smoke detector(s) shall also signal a trouble condition if the beam has a blockage of 90% or more
than 20 seconds and automatically resets to normal when blockage is removed.
The projected beam smoke detector(s) shall be UL listed for these applications. Voltage and RF transient protection
shall be integral to the internal circuitry of the projected beam smoke detector so as to minimize false alarm potential.
To facilitate easy installation and setup, the projected beam smoke detectors shall employ signal strength indicating
LED's. Alignment shall be facilitated by turning an alignment adjustment wheel and monitoring the relative signal strength
based upon which LED's are illuminated.
The detectors shall also illuminate a red LED, which is visible externally, when an alarm condition is indicated.
The projected beam smoke detector shall provide a Form "A" dry contact for alarm and Form "B" dry contact for trouble.

INSTALLATION
The Delta Digital Controls SPB-24N-DDC Projected Beam Smoke Detector shall be installed in accordance with the
Installation Instruction Guide provided with every unit. Refer to the applicable NFPA Standards for additional guidance on
spacing, irregular ceiling surfaces and other design considerations.

FOUR WIRE CONNECTION TO THE CONTROL PANEL


Emitter
E2

E1

Emitter
E2

E1

EOL-24

24V +
24V Zone +
Zone -

24V
0V
F1
F2
T1

24V
0V
F1
F2
T2

24V
0V
F1
F2
T1

24V
0V
F1
F2
T2

Control
Panel

End of Line
Resistor

NOTE: EOLR-24 required


for power supervision.
NOTE: End of line relay and trouble contacts are closed
when power is applied.

Delta Digital Controls SPB-24N-DDC PROJECTED BEAM SMOKE DETECTOR

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed

SRA-24-DDC REFLECTIVE BEAM DETECTOR


APPLICATION
Delta Digital Controls's Reflective Beam Detector is
designed for smoke detection in large spaces such as
halls, warehouse, museums, theatres etc., where
conventional point detection is impractical or more costly.
The unit is not suitable for applications where strong or
reflected sunlight is present, in these instances the SPB24N-DDC should be considered. The unit detects smoke
linearly over the protected range enabling early detection
before the fire spreads. Compact design, good looks
and flush mounting installation makes this unit ideal for
fitting in areas where architectural considerations are
important.

GENERAL DESCRIPTION
STANDARD FEATURES
Detector spacing from 25ft-100ft.
Pulsed beam to reduce overall consumption and
improve the noise rejection characteristics.
Small flat reflector.
Automatic drift compensation.
Fire detection sensitivity can be set to 20% or
30% obscuration.

SPECIFICATIONS
Operating Voltage
Stand-by Current
Max Current In Alarm
Operating Range
Sensitivity
Compensation
Reflector mounting
angle
Operating Temp. Range
Storage Temp. Range
Maximum Humidity
Color & Case Material
Size: SRA-24-DDC
Reflector
Weight: SRA-24-DDC
Reflector

15-33Vdc
350A at 24Vdc
50mA at 24Vdc
25ft - 100ft
20% or 30%
1% per Hr. 50%
10%
32F to +100F
-22F to +158F
95%RH - Non condensing
(at 104F)
Ivory ABS
6" x 4.8" x 3.1"
7.5" x 7.5" x.1"
1.9 lbs (Including termination module)
1.6 oz.

The Photoelectric reflective beam detector consists of the


SRA-24-DDC unit and a reflector, which face each other
at a distance of between 25ft and 100ft.
In the event of fire the smoke generated will decrease the
amount of near infrared light energy on the
SRA-24-DDC, this decrease is electronically interpreted
to identify the occurrence of fire. An important feature of
the detector is that it monitors the protected space linearly.
This enables the detector to identify a fire before it spreads,
even when the smoke is scattered over a large area.
The fire detection sensitivity is factory set at 20% beam
obscuration and it can be changed to 30% with a sensitivity
switch.
The status of the unit is indicated by three LEDs which
are viewed through a unique lens that allows good visibility
from any viewing angle, particularly from beneath the unit.
The LEDs indicate, Normal, Setup, Fault and Fire
Condition, so the user can verify which unit is in alarm.
The unit indicates a fault on the zone under the
following conditions:

Compensation limit exceeded


Total obscuration of beam
Beam detector unit removed from zone

PRODUCT LISTINGS
Underwriters Laboratories: S1383
Factory Mutual:
CSFM #: 7260-0410:158

Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.

F0013

04/2005

ENGINEERING SPECIFICATIONS
The contractor shall furnish and install, where indicated on the plans, Delta Digital Controls SRA-24-DDC Reflective
Beam Detector. The detector shall have a range of 25 feet to 100 feet. The beam smoke detector shall be field
adjustable to one of the two obscuration settings of 20%, or 30% per span. These settings shall be capable of being
verified with calibrated filters. Side to side spacing shall be a maximum of 60 feet on center.
The reflective beam detector shall posses circuitry that automatically compensates for normal ambient changes in the
intensity of the emitted beam strength. The microprocessor shall provide compensation for a change in received
signal value, with time, caused by contamination of the optics. Since such a change with time appears as a slow
change in the beam signal, the microcomputer compensates in such a manner that the signal moves closer to the
reference data at a rate of approximately +1% per hour. When this compensating capability reaches a limit, the
microcomputer automatically generates a trouble signal.
The reflective beam detector(s) shall also signal a trouble condition if the beam has a blockage of 90% for more than
20 seconds and automatically resets to normal when blockage is removed.
The reflective beam detector(s) shall be UL listed for these applications. Voltage and RF transient protection shall be
integral to the internal circuitry of the reflective beam detector so as to minimize false alarm potential.
To facilitate easy installation and setup, the reflective beam detectors shall employ signal strength indicating LED's.
Alignment shall be facilitated by turning an alignment adjustment screws and monitoring the relative signal strength
based upon which LEDs are illuminated.
The detectors shall also illuminate a red LED, which is visible externally, when an alarm condition is indicated.
The reflective beam detector shall provide a Form "A" dry contact for alarm and Form "B" dry contact for trouble.

INSTALLATION
The Delta Digital Controls SRA-24-DDC Reflective Beam Detector shall be installed in accordance with the Installation
Instruction Guide provided with every unit. Refer to the applicable NFPA Standards for additional guidance on spacing,
irregular ceiling surfaces and other design considerations.

TYPICAL WIRING

Reflector

Reflector

End of Line Relay

24V +
24V Zone +
Zone -

Control
Panel

24V
0V
F1
F2
T1

24V
0V
F1
F2
T2

24V
0V
F1
F2
T1

24V
0V
F1
F2
T2

End of Line
Resistor

NOTE: End of line relay and trouble contacts are closed when power is applied.

Delta Digital Controls SRA-24-DDC REFLECTIVE BEAM DETECTOR

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed

FireNET 4127 - ANALOG ADDRESSABLE FIRE ALARM CONTROL PANEL


STANDARD FEATURES

DESCRIPTION
The FireNET 4127-DDC control panel is an analog
addressable fire alarm panel containing 2 or 4 SLC
loops with each loop supporting 127 devices of any
combination (sensors or modules), and 127 analog
sounder bases, for a possible total of 254 points.
Communication between devices is transferred
through standard cable (shielded or twisted pair is
not required). Each panel includes a 5.25 amp power
supply and has 4 on board NAC circuits. An RS-485
bus provides communication to the panel network,
while the RS-232 interface allows the convenience
of programming via a PC. The system will support
a variety of Delta Digital Controls devices: photo, ion
and heat sensors, which contain a unique, patented
sensor design incorporating automatic drift
compensation and day/night sensitivity mode.
Additional devices include contact monitors, relay
controllers, supervised auxiliary output and short
circuit isolator modules. In addition, interfaces to
conventional detection systems can be established
by using a conventional zone-monitoring module. The
Loop Explorer Windows Software interface provides
the installer with fingertip access to installation
programming and diagnostic tools. An Auto-learn
feature offers the convenience for quick start
applications. Add to this a reputation for high quality
and dedicated service makes this an exceptional
product both in performance and value.

UL 864 9th edition Listed


Analog design using Delta Digital Controlss
advanced DCP
protocol for fast and robust communication
Up to 127 sensors & modules, plus 127 analog
sounder bases, for a total of 254 points possible
per loop
Uses standard wire, no shielded or twisted pair
required on SLC loops
Supports Class B (style 4) and Class A (style 6 or
7) SLC loops
4 on board Class B (style Y) NAC circuits rated at
2.5 Amp each
Programmable sensitivity levels per device &
automatic day/night sensitivity modes
Automatic daily calibration & drift compensation
routine
Large 8-line x 40-character LCD display (320 char.)
2 or 4 loop versions (800 addresses/sub-addr. max.)
Dual RS-485 bus for panel network
2 built-in RS-232 interfaces for programming via a
PC and serial printer interface
5 on board programmable Form C relays rated at 1
amp at 30 VDC (Fire1, Fire2, trouble, supervisory,
aux.)
500mA of auxiliary power available rated at 24 VDC
Loop Explorer Windows configuration utility
*500 network wide software zones
Network Capability of up to 64 panels
RS-485 slave bus for expansion - up to 31 FN-4127DDC IO boards or up to 15 FN-LCD-S-DDC serial
annunciators and up to16 FN-4127-DDC-IO boards
Auto-learn feature
Built in help and alarm information screens
Fire Drill test function
Walk Test function
Alarm Verification feature
FireNET is UL listed for Central Station Service when
used with the Bosch D9068-DDC contact dialer
Operates on 120 VAC or 240 VAC input voltage
Powerful & versatile Cause & Effect programming
(up to 500 maximum, network wide) including:
*Cause & Effect action
*Disable function configuration
*Test mode configuration

PRODUCT LISTINGS

UL 864, Local Signaling Unit.


Types: Automatic, manual, waterflow,
sprinkler supervisory,
Auxiliary Service(local energy),
S8255
and Central Station Service (DACT)
Non-coded signaling. NFPA 70, 72 &13 Compliant

Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.

F0013

04/2005

SPECIFICATIONS
Primary AC
Output DC
Power Supply
Charger Current
Dimensions
Weight
Color
Material
Display
Network
Zones
SLC loops
Devices per loop
Addresses per panel
NAC Outputs
Relay Outputs
Voltage Outputs
Aux. Power
Aux. Inputs
PC Port
Printer Port

120VAC @ 2.1 Amps 60hz or 220VAC @ 1.1Amps 60hz


24VDC @ 5.25 Amps (4 Amps availble for system power)
5.25 Amp integrated
1.5 Amps max.
14.5" W x 24" H x 5" D
31 lbs. (without batteries)
Red (optional charcoal)
ABS/steel enclosure
8 line x 40 character LCD (320 characters total)
Dual RS485 ports (64 panels max.)
500 network wide software zones per system
2 or 4 (class A, "style 6 or 7" or class B, "style 4")
127 sensors & modules, plus 127 analog sounder bases, 254 total
(800 addresses+sub-addresses max. per panel)
(4) 2.5 Amp @ 24VDC (class B)
(5) Form C 1 Amp @ 30VDC
FireNET ORDERING MODELS
(3) 500mA @ 24VDC
500mA @ 24VDC
MODEL
DESCRIPTION
(8) digital pull downs
FN-2127-DDC
FACP (2 Loop/5.25 Amp)
RS232
FN-2127N-DDC FACP (2 Loop/5.25 Amp) (w/Network)
RS232
FN-4127-DDC
FACP (4 Loop/5.25 Amp)
FN-4127N-DDC

FACP (4 Loop/5.25 Amp) (w/Network)

SLC COMPATIBLE DEVICES & SYSTEM ACCESSORIES


MODEL
FN-4127-SLC -DDC
FN-4127-NIC-DDC
FN-4127-DDC-IO
FN-CTM-DDC

DESCRIPTION
CONTROL PANEL EXPANDERS
Dual SLC Loop Expansion Card
Network Interface Card
16 Channel Input/Output Board
City-Tie Module (Local Energy Type)

FN-LCD-N-DDC
FN-LCD-S-DDC

Network LCD Annunciator


Serial LCD Annunciator

ALG-V-DDC
AIE-EA-DDC
ATG-EA-DDC
NSA-6-DDC
NSA-4-DDC
ASB-DDC
DH-98A-DDC
DH-98AR-DDC
MS-RA-DDC, MS-RA/R
-DDC,MS-KA/R-DDC
FRCME-S-DDC
FRCME-P-DDC
FRCME-4-DDC
DIMM-DDC
CZM-DDC
R2M-DDC
SOM-DDC
SCI-DDC
AMS-DDC Series
TCH-B100-DDC
FN-ACC-DDC
FN-ETR-DDC
Delta Digital Controls FireNET 4127 - AA FCP

ANNUNCIATORS

SLC LOOP DEVICES


Analog Addressable Photoelectric Sensor
Analog Addressable Ionization Sensor
Analog Addressable Heat Sensor
Six inch Sensor Base
Four inch Sensor Base
Analog Sounder Base
Anaolg Addressable Duct Detector Unit
Analog Addressable Duct Detector Unit (with relays)
Remote Test Station for DH98A & DH98AR
Contact Monitoring Module (mini w/terminal blocks)
Contact Monitoring Module (mini w/pigtail leads)
Contact Monitoring Module (with faceplate/indicating LED)
Dual Input Monitor Module (with faceplate/indicating LED)
Conventional Zone Module
Dual Relay Module
Supervised Output Module
Short Circuit Isolator Module
Addressable Manual Pull Station

ACCESSORIES
Hand Held Programmer (portable device addresser)
Battery/Accessory Enclosure (houses up to 33AH size
Enclosure Trim Ring for Panel Flush Mount

batteries)

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed

FN-4127-DDC-IO 16 CHANNEL INPUT/OUTPUT BOARD


(RS-485 BUS DEVICE)
SPECIFICATIONS
Supply Voltage:

24 VDC Nominal

Channels:

(16) total per I/O board (each


configurable as input or output)
I/O Comms Bus: Up to (32) expansion boards
Quiescent Current:
20mA
Current per input:
3mA max.
Current per output:
100mA max. (*within overall
limits)
*Current per bank of 500mA max. (for banks 1-8 & 9-16)
8 outputs:
*Current per I/O board:
1A max.

STANDARD FEATURES

16 channels of input/output points.


32 I/O boards per FireNET panel (512 channels of
input/output points).
Each channel configurable as input or output point.
Inputs are opto-isolated non-supervised pulldown
type triggered by dry contact from input source.
Outputs are open collector transistor pulldown
type (100mA max each) that provide wet voltage
output.
Simple 4 wire connection to control panel (2 for
power, 2 for data).
All inputs/outputs can be assigned to global
functions, any event category, and used in network
wide Cause & Effect logic.
Can be mounted locally within control panel
enclosure or remotely via FN-ACC accessory
enclosure up to 4000ft from the panel.
Each I/O board has a unique address 1-32 (set via
DIP switch) on the I/O Comms Bus.
Input/Outputs are for secondary use, not for
primary fire initiation inputs or notification outputs.
Two LEDs are provided for communication status.
PRODUCT LISTINGS
UL 864 Category UOJZ CNN: Signal System Control
Unit Sub-Assembly S8255 Vol. 1 Sec. 2
NFPA72 compliant
CSFM #: 7165-0410:159

Specifications subject to change without notice.

Communications:
Max Distance from
panel:
Cable Capacity:

RS485 two wire


4,000 ft. (depends on method &
wire size used for input power).
12 AWG max.

Indicators:

(2) LED's for communication


status

Size:

7.5" L x 2.4" W

DESCRIPTION
The FireNET FN-4127-DDC-IO is a 16 channel Input/
Output board that provides powerful input/output
expansion & addition to the FireNET system allowing up
to thirty two I/O boards to be connected to each FireNET
panel within the FireNET network. Every I/O board
connected to any panel is available to the entire network,
which allows for network wide input/output mapping.
Typical uses include graphical LED map displays/
annunciators, tabular LED zone display/annunciators,
input/output logic to & from the fire system for secondary
use (I/O board points cannot be used for primary fire
initiation inputs or notification outputs) such as access
control, burglar, CCTV, intercom, voice, or other 3rd party
systems. Each channel can be configured to produce a
variety of input actions or respond to a variety of output
categories or logic. All channels can trigger, or react from,
network wide cause and effect logic depending on their
configuration. The flexibility of these boards is further
enhanced by the fact that each of the channels is
configurable as either an input or an output. Connection
can be achieved through a simple two wire RS485
communications protocol and two wire power input. I/O
boards can be mounted locally in the control panel or
distributed on a bus up to 4,000ft from the panel when
using the FN-ACC accessory enclosure.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.

F0013

04/2005

Delta Digital Controls FN-4127-DDC-IO 16 CHANNEL INPUT/OUTPUT BOARD

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed

FN-4127-NIC-DDC NETWORK INTERFACE CARD


SPECIFICATIONS
Supply Voltage:

24 VDC Nominal

Quiescent Current Consumption:

20mA

Cable Length:

4,000ft Max.

Cable Type:

Belden 9271, Belden 9860

Protocol:

RS-485

Address Setting:

Dipswitch

Operating Temperature:
Operating Humidity:

32F~120F
90%RH

STANDARD FEATURES

DESCRIPTION

The FN-4127-NIC-DDC Network Interface Card allows


for the expansion of up to 64 nodes (combination of
FACPs or annuciators) on a single FireNET network wide
system. Using the Loop Explorer configuration software
up to 64 nodes can be programmed to respond to in a
variety ways-independently or system wide. The flexibility
extends the comprehensive cause and effect
programming capability to the entire network allowing
actions to be started from any point. The network
communication protocol has been designed to be
extremely tolerant to interference and data corruption.
The simple 2 wire loop connection makes for ease during
installation.

Allows for the expansion of up to 64 panels on a


FireNET system.
Enables information to be transmitted between
control panels.
Network protocol designed for tolerance to
interference and data corruption.
Each card configured to a unique address
through use of a dipswitch.
Transmission distance of up to 4,000 ft.
Uses standard type Belden cable suitable for
RS-485 applications.
Simple 2-wire loop connection.
Flexible configuration options.
Network wide Cause & Effect logic.
Fully secure against short or open conditions.

ENGINEERING SPECIFICATIONS

PRODUCT LISTINGS
UL 864, NFPA 72: Local Signaling Unit. S8255
Types: Automatic, manual, waterflow and sprinkler
supervisory
CSFM #: Pending

The FN-4127-NIC-DDC Network interface card shall be


compatible for use with a FireNET 4127-DDC analog
addressable control panel. The NIC shall be mounted on
the inside of the FACP and is connected used a standard
RS-485 type 2 wire connection. Up to a maximum of 64
network cards can be installed per one complete
networked system. The network card shall be addressed
by use of a dipswitch.

Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.

F0013

04/2005

Delta Digital Controls FN-4127-NIC-DDC NETWORK INTERFACE CARD

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed

FN-4127-SLC DUAL SLC LOOP EXPANDER


SPECIFICATIONS
Operating Voltage: 24 - 40VDC
Board Current:

100mA (+ loop current)

Loop Current:

400mA max. each

System Capacity:

One expander per FireNET


control panel

Loops per
expander:

2 SLC (Class A or B)

Devices per loop:

STANDARD FEATURES

Adds two SLC loops to a two loop FireNET


control panel.
Each SLC loop is capable of 127 sensors/
modules, plus 127 analog sounder bases,
for a potential total of 254 addresses per
loop (127+127 per loop).
FN-4127-SLC-DDC can be added at the
factory or installed in the field.
Supports Class A and B wiring methods per
NFPA72 Styles 4, 6, and 7 (with isolators).
Fully supervised & power limited SLC loops.
Supports Delta Digital Controlss DCP
(Digital. Communication Protocol) loop
protocol.
Same functionality as built-in SLC loops of
FireNET control panel.
One SLC expander (maximum) may be
added per FireNET control panel.
Each SLC loop is completely independent
and autonomous.
Uses standard wire, no shielded or twisted
pair required on SLC loops.

127 sensors/modules +
127 analog sounder bases,
254 total

Loop Load
impedance:

50 ohms, 1uF, 1mH max.

Size:

6.3" L x 4.5" W

DESCRIPTION
The model FN-4127-SLC-DDC Dual SLC Loop Expander
is a two loop expander board that increases the standard
FireNET loop capacity from 2 to 4 loops. The FN-4127SLC-DDC can be added at the factory or installed in the
field, and mounts within the main control board location
as a piggy-back board. By adding the FN-4127-SLC-DDC,
the FireNET capacity is increased from 254+254 to
508+508 analog addressable points within the overall 800
address/sub-address limit. The FN-4127-SLC-DDC has
the same functionality as the built-in SLC loops. The FN4127-SLC-DDC utilizes Delta Digital Controlss robust
DCP loop protocol for highly reliable and fast alarm
reporting without the need for shielded or twisted pair
wiring for the SLC loops.

PRODUCT LISTINGS
UL 864 Category UOJZ CNN: Signal System Control
Unit Sub-Assembly S8255 Vol. 1
NFPA72 compliant
CSFM #: 7165-0410:159
Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.

F0013

04/2005

Delta Digital Controls FN-4127-SLC DUAL SLC LOOP EXPANDER

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed

FN-LCD-N LCD NETWORK ANNUNCIATOR


STANDARD FEATURES
UL 864 9th edition Listed
320 character liquid crystal display (8 line x 40

DESCRIPTION
The FN-LCD-N-DDC type LCD network annunciator is
designed to be used with the FireNET analog addressable
system. It allows for remote access, monitoring & control
of the FireNET system throughout the building.
The FN-LCD-N-DDC is a true network annunciator that
can access, monitor & control any or all FireNET panels
in the network. Each FN-LCD-N-DDC is completely
independent. The highly intuitive user interface and 320
character LCD display of the FN-LCD-N-DDC is exactly
the same as the FireNET panel. In addition to routing
any panel in the network to the FN-LCD-N-DDC, every
event category within each panel can also be individually
routed, as well as routing of all remote control functions
(reset, alarm silence, re-sound alarm) from individual
panels. The FN-LCD-N-DDC supports the same RS485
expansion port as the FireNET panel, allowing for FireNET
expansion boards and accessories to be connected to
the network annunciator.
The FN-LCD-N-DDC also has (4) output relays for fire,
supervisory, trouble & auxiliary. The relays are
programmable (except supervisory).
Security is established by the use of a password or
firefighters enable key. Designed to be aesthetically
pleasing, the FN-LCD-N-DDC is available in charcoal grey
or red and can be surface or flush mounted using a
standard trim ring kit.

PRODUCT LISTINGS
UL 864, NFPA 70 & 72:
Signaling Device

character)
LED indicators for Fire, Supervisory Alarm, Pre-Alarm,
Fire Output Active, Power On, On Test, Panel
Sounder Silenced, Delay Active, More Events, Point
Bypassed, General Trouble, Power Trouble, System
Trouble & NAC Trouble
Dual RS485 ports for primary fire network
RS 485 slave bus for expansion - up to 31 FN-4127DDC-IO boards or up to 15 FN-LCD-S-DDC serial
annunciators and up to16 FN-4127-DDC-IO boards
2 built-in RS-232 interfaces for programming via a PC
and serial printer interface
4 on board programmable Form C relays rated at 1
Amp at 30VDC (Fire, Supervisory, Trouble & Auxiliary)
Same controls as the FireNET fire panel (Reset, Panel
Sounder Silence, Lamp Test, Alarm Silence, Resound Alarm, Fire Drill, Programmable Function,
More Events, More Fire Events, Enter & Exit)
Local piezo sounder for event notification
Supports user codes & firefighter key to enable
access & controls
Powered by FireNET Aux 24VDC or UL fire listed
Aux. 24VDC supply
Available in red or charcoal, and can be surface or
flush mounted (using trim ring)
True network annunciator, any or all panels can be
routed to the FN -LCD-N-DDC. In addition, each event
category can be individually routed to the FN-LCD-NDDC
Up to (64) FireNET panels & FN-LCD-N-DDC can be
networked together in any combination
500mA of auxiliary power available rated at 24VDC
Auto-learn feature
Built-in help & alarm information screens
Fire drill function
Each FN-LCD-N-DDC is completely independent
Supports up to (31) FN-4127-DDC-IO boards on
RS 485 expansion port
The FN-LCD-N-DDC can be configured to remote
reset, silence, resound, any or all panels on the
network in any combination

S8255 Vol. 2
Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.

F0013

04/2005

SPECIFICATIONS
Input DC
Aux. Output DC
Dimensions
Weight
Color
Material
Display
Network
Relay Outputs
PC Port
Printer Port
Expansion Port

24VDC @ 270mA Max. ( + Aux. Power Load)


24VDC @ 500mA
14.5" W x 10" H x 3.3" D
9.4 lbs
Red (optional charcoal)
ABS/steel enclosure
8 line x 40 character LCD (320 characters total)
Dual RS485 ports (64 nodes max.)
(4) Form C 1amp@30VDC
RS232
RS232
RS485 (for optional expansion boards)

ENGINEERING SPECIFICATION
The contractor shall furnish and install where indicated on the plans, the network annunciator model
FN-LCD-N-DDC. The FN-LCD-N-DDC shall connect to the FireNET fire alarm control panel (FACP) network. The
network annunciator shall be capable of annunciating on its 320 character display and local buzzer, the condition of
any FireNET FACP or network annunciator on the network. Up to 64 FN-LCD-N-DDC network annunciators or
FireNET FACP's may be connected together on the network. The FN-LCD-N-DDC shall be UL listed, and have
surface or flush mount capability.

WIRING DIAGRAM

Delta Digital Controls FN-LCD-N LCD NETWORK ANNUNCIATOR

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed

FN-LCD-S SERIAL LCD ANNUNCIATOR


STANDARD FEATURES

DESCRIPTION
The FN-LCD-S-DDC serial annunciator provides a
convenient and cost effective remote annunciator solution.
Up to 15 FN-LCD-S-DDC annunciators can be connected
to the slave RS-485 port of the FireNET control panel or
network annunciator. The FN-LCD-S-DDC large 320
character display and navigation buttons are a complete
mimic of the FireNET control panel display. The use of a
common interface allows the user to easily operate the
FN-LCD-S-DDC as if he were operating the FireNET
control panel directly.
Security is established by the use of a password or
firefighters enable key. Designed to be aesthetically
pleasing, the FN-LCD-S-DDC is available in charcoal grey
or red enclosures. The FN-LCD-S-DDC can be surface
or flush mounted without the need for a trim ring.

PRODUCT LISTINGS
UL 864, NFPA 70 & 72:
Signaling Device

UL 864 9th edition Listed


Large 320 character liquid crystal display (8 line
x 40 character) allows viewing of system status
LED indicators for Fire, Supervisory Alarm, PreAlarm, Fire Output Active, AC Power On, On Test,
Panel Sounder Silenced, Delay Active, More
Events, Point Bypassed, General Trouble, Power
Trouble, System Trouble & NAC Trouble
Same controls as the FireNET fire panel (Reset,
Panel Sounder Silence, Lamp Test, Alarm Silence,
Re-sound Alarm, Fire Drill, Programmable Function,
More Events, More Fire Events, Enter & Exit)
Up to 15 FN-LCD-S-DDC serial annunicators may
be connected to a FireNET control panel or network
annunciator
Resides on the FireNET slave RS-485 line
Local piezo sounder for event notification
Supports user codes & firefighter key to enable
access & controls
Powered by FireNET Aux 24 VDC or UL fire listed
Aux. 24 VDC supply
Available in red or charcoal, and can be surface or
flush mounted
Built-in help & alarm information screens
Fire drill function

SPECIFICATIONS
Current Draw
Standby:
Alarm:
Dimensions
FN-LCD-S-DDC
Back Box
Weight

20mA @ 24VDC
110mA @ 24VDC
10.88" W x 8.00" H x 1.38" D
10.38" W x 7.38" H x 1.25" D
3.5 lbs

Color

Red (optional charcoal)

Material
Display

ABS/steel enclosure
8 line x 40 character LCD
(320 characters total)

Network

RS485 port

S8255 Vol. 2

Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.

F0013

04/2005

ENGINEERING SPECIFICATION
The contractor shall furnish and install where indicated on the plans, the serial remote annunciator model FN-LCD-SDDC. The FN-LCD-S-DDC shall connect to the FireNET fire alarm control panel (FACP) or network annunciator
(FN-LCD-N-DDC) RS485 slave bus. The serial remote annunciator shall annunciate on its 320 character display and
local buzzer, the condition of its master FireNET FACP. Up to 15 FN-LCD-S-DDC serial annunciators may be connected
together on a single RS-485 FireNET slave bus. The FN-LCD-S-DDC shall be UL listed and compatible with the Delta
Digital Controls FireNET control panel, and have surface or flush mount capability.

WIRING DIAGRAM

1522RO @

ADDRESS

COMM1

COMM2

+24V

K S
2

ON
1

0V

RESET

RESET W / DOG

FIT JUMPER
FOR END OF LINE
COMM1 COMM2
COMMS
ACTIVE

Reset
Switch

Not Used
Not Used
DIP Switch used to set
the FN-LCD-S address
between 1 -15

RS485 End-of-line jumper . Put


jumper in place when FN-LCD-S
is the last device on the RS485
buss I/O Comm.

7. PR2

COMMS

l +

8. PR3

ADDITIONAL
I/O BOARDS

( +)

NETWORK
IN

l +

24 VDC
(- )
(+)

l +

AUX
24X

NETWORK
OUT

RS-485

l +

(- )

To next
serial
FN-LCDS or
other
RS485
Buss
Device

FireNET Control Panel


(section)

Delta Digital Controls FN-LCD-S SERIAL LCD ANNUNCIATOR

To AUX 24VDC of control


panel (as shown) or to UL
864/1481 listed AUX
24VDC Power Supply

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed

HCP-202-DDC FIRE ALARM CONTROL PANEL


DESCRIPTION
Delta Digital Controlss HCP-202-DDC Fire Alarm Control
Panel is a microprocessor based unit designed for small
to medium commercial, institutional and industrial
occupancies. Fully configurable using DIP switches, it
enables the user to configure the system to meet their
specific requirements.

STANDARD FEATURES

2 Class B (Style B) Initiating Circuits which may


be configured as 1 Class A (Style D) circuits.
2 Class A/B (Style Z/Y) Indicating Circuits with
individual trouble indicators (1.25 Amps max. per
circuit.)
Each Indicating Circuit can be configured as
Silenceable or Non-Silenceable. Audibles may be
configured as Steady, Temporal Code, California Code
or March Time
Selectable Alarm Verification on Initiating Circuits
Output for 4-wire resettable regulated smoke power
supply of 24 VDC 100mA maximum
Output for RTI or Remote Annunciators of 24VDC,
300 mA max, unfiltered
Built-in Walk Test operation
Auxiliary relay contacts for Common Alarm, Common
Trouble and Common Supervisory. If no Supervisory
circuits are enabled, the Supervisory relay becomes
a second Alarm relay.
2.75 Amp Power Supply
Easy configuration via DIP switches

The HCP-202-DDC comes standard with 2 Class B (Style


B) Initiating Circuits which may be configured as 1 Class
A (Style D) circuits. In addition it comes equipped with 2
Class A/B (Style Z/Y) indicating circuits which are each
rated at 1.25 amps. The panel also includes a 2.75 Amp
Power Supply which powers the system and supplies a
4-wire resettable regulated smoke power supply of 24
VDC 100mA maximum.
The HCP-202-DDC utilizes a simple DIP switch
configuration for programming initiating and indicating
circuits as well as the enabling and disabling of system
functions such as Signal Silence, Fire Drill and Auxiliary
Disconnect. In addition the HCP-202-DDC allows for
Alarm Verification on the Initiating circuits. The Indicating
circuits may be configured as Silenceable or NonSilenceable with the audibles configured for Steady,
March-Time, Temporal Code, or California Code.
The cabinet is available in a beige color for the Canadian
market and a red exterior for the U.S. and International
markets. A Fire Retardant Lexan Window in the hinged
door allows for viewing of the status LEDs. It comes with
a durable CAT-30 lock and key. Space is provided for up
to 10 AH batteries.

SPECIFICATIONS
Primary Input Power
Indicating Current
Standby Power
Charging Capability
Dimensions:

120 volts, 60 Hz, 1 Amps


24VDC unfiltered, 2.5Amps
24VDC Standby Batteries
4 6.5 AH Batteries
12 3/4H x 13 3/4W x 3 1/8D

PRODUCT LISTINGS
Underwriters Laboratories: S6468
CSFM #: 7165-0410:152

Specifications subject to change without notice.


Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.
Continued on back.

F0013

04/2005

ORDERING INFORMATION
Model

Description

Fire Alarm Control Panel


HCP-202-DDC Two Zone Microprocessor Based Fire Alarm Control Panel comes with 2 Class B (Style B) or 1 Class
A (Style D) Initiating Circuits, 2 Class A/B (Style Z/Y) Indicating Circuits and a 2.75 Amp Power Supply.
Allows for one HDACT-100-DDC Digital Communicator or one HPR-100-DDC Polarity Reversal Module
or one HRM-204-DDC or HRM-208-DDC Auxiliary Relay Module. Red enclosure comes with keylock
door.
HRTI-1-DDC

Remote Trouble Indicator

Adder Modules
HDACT-100-DDC
Digital Alarm Communication Transmitter/Dialer Module
HPR-100-DDC
Polarity Reversal/City Tie Module
HRM-204-DDC
Auxiliary Relay Module comes with 4 configurable relays
HRM-208-DDC
Auxiliary Relay Module comes with 8 configurable relays
(Note: Only one of the above modules can be used with the HCP-202-DDC)

Delta Digital Controls HCP-202-DDC FIRE ALARM CONTROL PANEL

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed

HCP-204 FIRE ALARM CONTROL PANEL


DESCRIPTION
Delta Digital Controlss HCP-204-DDC Fire Alarm Control
Panel is a microprocessor based unit designed for small
to medium commercial, institutional and industrial
occupancies. Fully configurable using DIP switches, it
enables the user to configure the system to meet their
specific requirements.

STANDARD FEATURES

4 Class B (Style B) Initiating Circuits which may


be configured as 2 Class A (Style D) circuits
2 Class A/B (Style Z/Y) Indicating Circuits with
individual trouble indicators (1.25 Amps max. per
circuit)
Each Indicating Circuit can be configured as
Silenceable or Non-Silenceable. Audibles may be
configured as Steady, Temporal Code, California
Code or March Time
Selectable Alarm Verification on Initiating Circuits
Output for 4-wire resettable regulated smoke
power supply of 24 VDC 100mA maximum
Output for RTI or Remote Annunciators of 24VDC,
300 mA max. unfiltered
Built-in Walk Test operation
Auxiliary relay contacts for Common Alarm,
Common Trouble and Common Supervisory. If no
Supervisory circuits are enabled, the Supervisory
relay becomes a second Alarm relay
2.75 Amp Power Supply
Easy configuration via DIP switches

SPECIFICATIONS
Primary Input Power
Indicating Current
Standby Power
Charging Capability
Dimensions

120 volts, 60 Hz, 1 Amps


24VDC unfiltered, 2.5Amps
24VDC Standby Batteries
4 6.5 AH Batteries
12 3/4"H x 13 3/4"W x 3 1/8"D

The HCP-204-DDC comes standard with 4 Class B (Style


B) Initiating Circuits which may be configured as 2 Class
A (Style D) circuits. In addition, it comes equipped with 2
Class A/B (Style Z/Y) Indicating circuits which are each
rated at 1.25 Amps. The panel also includes a 2.75 Amp
Power Supply which powers the system and supplies a
4-wire resettable regulated smoke power supply of 24 VDC
100mA maximum.
The HCP-204-DDC utilizes a simple DIP switch
configuration for programming initiating and indicating
circuits as well as the enabling and disabling of system
functions such as Signal Silence, Fire Drill and Auxiliary
Disconnect. Some predefined Initiating circuits can
optionally be configured as Waterflow or Latching/NonLatching Supervisory. In addition the HCP-204-DDC allows
for Alarm Verification on the initiating circuits. The
Indicating circuits may be configured as Silenceable or
Non-Silenceable with the audibles configured for Steady,
March-Time, Temporal Code, or California Code. The HCP204-DDC is equipped with auxiliary relay contacts for
Common Alarm, Trouble and Supervisory. If no Supervisory
circuits are enabled, the Supervisory relay becomes a
second Alarm relay.
The cabinet is available in a beige color for the Canadian
market and a red exterior for the U.S. and International
markets. A Fire Retardant Lexan Window in the hinged
door allows for viewing of the status LEDs. It comes with
a durable CAT-30 lock and key. Space is provided for up
to 10 AH batteries.
PRODUCT LISTINGS
Underwriters Laboratories: S6468
CSFM #: 7165-0410:152

Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.

F0013

04/2005

ORDERING INFORMATION
Model

Description

Fire Alarm Control Panel


HCP-204-DDC Four Zone Microprocessor Based Fire Alarm Control Panel comes with 4 Class B (Style B) or 2 Class
A (Style D) Initiating Circuits, 2 Class A/B (Style Z/Y) Indicating Circuits and a 2.75 Amp Power Supply.
Allows for one HDACT-100-DDC Digital Communicator or one HPR-100-DDC Polarity Reversal Module
or one HRM-204-DDC or HRM-208-DDC Auxiliary Relay Module. Red enclosure comes with keylock
door.
HRTI-1-DDC

Remote Trouble Indicator

Adder Modules
HDACT-100-DDC
Digital Alarm Communication Transmitter/Dialer Module
HPR-100-DDC
Polarity Reversal/City Tie Module
HRM-204-DDC
Auxiliary Relay Module comes with 4 configurable relays
HRM-208-DDC
Auxiliary Relay Module comes with 8 configurable relays
(Note: Only one of the above modules can be used with the HCP-204-DDC)
Remote Annunciator
HRAM-208-DDC

Remote Multiplex Annunciator comes with Common Control Features, Indicators and
8 Bi-Colored LEDs
Controls: Signal Silence, Buzzer Silence, Lamp Test & System Reset
Indicators: A.C. On, Common Trouble & Signal Silence

Delta Digital Controls HCP-204 FIRE ALARM CONTROL PANEL

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed

HCP-204E FIRE ALARM CONTROL PANEL


DESCRIPTION
Delta Digital Controlss HCP-204E-DDC Fire Alarm
Control Panel is a microprocessor based unit designed
for small to medium commercial, institutional and
industrial occupancies. Fully configurable using DIP
switches, it enables the user to configure the system to
meet their specific requirements.

STANDARD FEATURES

4 Class B (Style B) Initiating Circuits which may


be configured as 2 Class A (Style D) circuits.
Expandable up to 8 Class B (Style B) or 4 Class A
(Style D) Initiating Circuits
2 Class A/B (Style Z/Y) Indicating Circuits with
individual trouble indicators (1.7 amps max. per
circuit.) Expandable up to 4 Class A/B (Style Z/Y)
Indicating Circuits
Each Indicating Circuit can be configured as
Silenceable or Non-Silenceable. Audibles may be
configured as Steady, Temporal Code, California
Code or March Time
Output for RTI or Remote Annunciators of 24VDC,
300 mA max, unfiltered
Built-in Walk Test operation
Auxiliary relay contacts for Common Alarm,
Common Trouble and Common Supervisory. If no
Supervisory circuits are enabled, the Supervisory
relay becomes a second Alarm relay
6 Amp Power Supply
Easy configuration via DIP switches

SPECIFICATIONS
Primary Input Power
Indicating Current
Standby Power
Charging Capability
Dimensions:

120 volts, 60 Hz, 2 amps


24VDC unfiltered, 5 amps
24VDC standby batteries
10 24 AH batteries
14 7/8H x 14 1/2W x 5D

The HCP-204E-DDC comes standard with 4 Class B


(Style B) Initiating Circuits which may be configured as
2 Class A (Style D) circuits. In addition it comes equipped
with 2 Class A/B (Style Z/Y) Indicating Circuits which
are each rated at 1.7 amps. The HCP-204E-DDC can
be expanded up to 8 Class B (Style B) or 4 Class A
(Style D) Initiating Circuits and 4 Class A/B (Style Z/Y)
Indicating Circuits with the addition of an HDM-204-DDC
Adder Zone Module. The panel also includes a 6 amp
power supply which powers the system and supplies a
4-wire resettable regulated smoke power supply of 24
VDC 100mA maximum.
The HCP-204E-DDC utilizes a simple DIP switch
configuration for programming initiating and indicating
circuits as well as the enabling and disabling of system
functions such as Signal Silence, Fire Drill and Auxiliary
Disconnect. Some predefined Initiating Circuits can
optionally be configured as Waterflow or Latching/NonLatching Supervisory. In addition the HCP-204E-DDC
allows for alarm verification on the Initiating Circuits. The
Indicating Circuits may be configured as Silenceable or
Non-Silenceable with audibles configured for Steady,
March-Time, Temporal Code, or California Code.
The HCP-204E-DDC is equipped with auxiliary relay
contacts for Common Alarm, Trouble and Supervisory. If
no Supervisory circuits are enabled, the Supervisory relay
becomes a second Alarm relay. The cabinet is available
in a beige color for the Canadian market and a red exterior
for the U.S. and International markets. A Fire Retardant
Lexan Window in hinged door allows for viewing of the
status LEDs. It comes with a durable CAT-30 lock and
key. Space is provided for up to 10 AH batteries.

PRODUCT LISTINGS
Underwriters Laboratories: S6468
CSFM #: 7165-410:152

Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.

F0013

04/2005

ORDERING INFORMATION
Model

Description

Fire Alarm Control Panel


HCP-204E-DDC Four expandable to Eight Zone Microprocessor Based Fire Alarm Control Panel comes with 4 Class B
(Style B) or 2 Class A (Style D) Initiating Circuits, 2 Class A/B (Style Z/Y) Indicating Circuits and a 6 amp
power supply. Expandable up to 8 Class B (Style B) Initiating Circuits or 4 Class A (Style D) and 4 Class
A/B (Style Z/Y) Indicating Circuits. Allows for one HDACT-100-DDC Digital Communicator or one HPR100-DDC Polarity Reversal Module. Also allows for one HRM-204-DDC or HRM-208-DDC Auxiliary
Relay Module. Red enclosure comes with keylock door.
HRTI-1-DDC

Remote Trouble Indicator

Adder Modules
HDM-204-DDC
HDACT-100-DDC
HPR-100-DDC
HRM-204-DDC
HRM-208-DDC
Remote Annunciator
HRAM-208-DDC

Four Class B (Style B) or Two Class A (Style D) Initiating Circuit and 2 Class A/B (Style Z/Y)
Indicating Circuit Module
Digital Alarm Communication Transmitter/Dialer Module
Polarity Reversal/City Tie Module
Auxiliary Relay Module comes with 4 configurable relays
Auxiliary Relay Module comes with 8 configurable relays
Remote Multiplex Annunciator comes with Common Control Features, Indicators and
8 Bi-Colored LEDs
Controls: Signal Silence, Buzzer Silence, Lamp Test & System Reset
Indicators: A.C. On, Common Trouble & Signal Silence

Delta Digital Controls HCP-204E FIRE ALARM CONTROL PANEL

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed

HCP-1008E FIRE ALARM CONTROL PANEL


DESCRIPTION
Delta Digital Controlss HCP-1008E-DDC Fire Alarm
Control Panel is a microprocessor based unit designed
for maximum flexibility and easy installation. Fully
configurable from the front panel using the push buttons
and DIP switches, it enables the user to configure the
system to meet their specific requirements.

STANDARD FEATURES

8 Class B (Style B) initiating circuits which may


be configured as 4 Class A (Style D) circuits
Expandable up to 24 Class B or 12 Class A
initiating circuits
4 Class A/B (Style Z/Y) indicating circuits with
individual trouble indicators (1.7 Amps max. per
circuit)
Each indicating circuit can be configured as
silenceable or non-silenceable. Audibles may be
configured as Steady, Temporal Code, California
Code or March Time
Each initiating circuit can be configured as alarm,
supervisory, waterflow or trouble
Two outputs for 4 wire resettable smoke power
supply (200 mA Max. each)
Alarm verification on initiating circuits
Easy configuration via push buttons and DIP
switches on the front panel

SPECIFICATIONS
Primary Input Power 120 volts, 60 Hz, 1 Amps
(Optional 220VAC)
Indicating Current
24VDC unfiltered, 5Amps
Standby Power
24VDC standby batteries
Charging Capability 10 24 AH batteries
Dimensions
26"H x 14 1/2"W x 4 1/2" D

The HCP-1008E-DDC consists of one HMCC-1024-6-DDC


main Chassis in an HBB-1024-DDC Enclosure. The
HMCC1024-6-DDC main Chassis comes complete with
8 Class B (Style B) initiating circuits which may be
configured as 4 Class A (Style D) circuits. It can be
expanded up to 24 Class B or 12 Class A circuits with
the addition of two HDM-1008-DDC Initiating Circuit
Modules. In addition it comes equipped with 4 Class A/
B (Style Z/Y) indicating circuits which are each rated at
1.7 Amps. The main Chassis also includes a 6 amp
power supply which powers the system and supplies two
4-wire resettable regulated smoke power supply of 24
VDC 200mA maximum each. The HMCC-1024-6-DDC
also allows for the addition of two HSGM-1004-DDC Signal
Modules or two HRM-1008-DDC Relay Modules in place
of the HDM-1008-DDC Initiating Circuit Adder Modules.
(Maximum of 2 adder modules and 1 communication
module).
The cabinet is available in a beige color for the Canadian
market and a red exterior for the U.S. and international
markets. A Fire Retardant Lexan Window in the hinged
door allows for viewing of the status LEDs. It comes with
a durable CAT-30 lock and key. Space is provided for up
to 17 AH Gel Cell batteries.
Delta Digital Controls's HCP-1008E-DDC is designed as
an economical Microprocessor Based Fire Alarm Control
Panel which is expandable up to 24 display points. Its
modular design suits various applications. Ideal for
applications such as small institutional and commercial
buildings, shopping malls, offices and public
establishments, the HCP-1008E-DDC is configurable to
meet virtually all requirements. The panel is designed to
be easy in its installation, operation and maintenance.
This makes the system cost effective and very reliable
for its intended applications.

Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

PRODUCT LISTINGS
California
State
S6468

7165Continued on back.

F0013

04/2005

ORDERING INFORMATION
Model

Description
Fire Alarm Control Panel

HCP-1008E-DDC

Microprocessor Based Fire Alarm Control Panel expandable up to 24 display points.


Includes HMCC-1024-6-DDC main Chassis complete with 8 Class B (Style B) initiating circuits
or 4 Class A (Style D) initiating circuits, 4 Class A/B (Style Z/Y) indicating circuits, 6 amp power
supply and one HBB-1024-DDC Red Enclosure. (DIP switches)

HCP-1008ES-DDC

Microprocessor Based Fire Alarm Control Panel expandable up to 24 display points.


Includes HMCC-1024-6S-DDC main Chassis complete with 8 Class B (Style B) initiating
circuits or 4 Class A (Style D) initiating circuits, 4 Class A/B (Style Z/Y) indicating circuits,
6 amp power supply and one HBB-1024-DDC Red Enclosure. (Slide switch version)

HFA-1024TR-DDC

Semi-Flush Trim Ring

HRTI-1-DDC

Remote Trouble Indicator

Adder Modules
HDM-1008-DDC

Eight Class B (Style B) or 4 Class A (Style D) Initiating Circuit Module

HSGM-1004-DDC

Four Class A/B (Style Z/Y) Indicating Circuit Module (Rated at 1.7 Amps per circuit).

HRM-1008-DDC

Eight Relay Circuit Module comes with eight Form C relays (Rated for 28 VDC @ 1 Amp.
max. per relay)

Auxiliary Modules
HDACT-100U-DDC

Universal Digital Alarm CommunicationTransmitter/Dialer Module

HDACT-100-DDC

Digital Alarm Communication Transmitter/Dialer Module

HPR-100-DDC

Polarity Reversal and City Tie Module

Remote Annunciator
HRAM-1032-DDC

Main Annunciator Chassis comes with common control features, indicators and 32
bi-colored LEDs

HBB-1001-DDC

Annunciator backbox with keylock door

Delta Digital Controls HCP-1008E FIRE ALARM CONTROL PANEL

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed

HCP-1008ES FIRE ALARM CONTROL PANEL


DESCRIPTION
Delta Digital Controlss HCP-1008ES-DDC Fire Alarm
Control Panel is a microprocessor based unit designed
for maximum flexibility and easy installation. Fully
configurable from the front panel using the push buttons
and SLIDE switches, it enables the user to configure the
system to meet their specific requirements.

STANDARD FEATURES

8 Class B (Style B) Initiating Circuits which may


be configured as 4 Class A (Style D) Circuits.
Expandable up to 24 Class B or 12 Class A
Initiating Circuits
4 Class A/B (Style Z/Y) Indicating Circuits with
individual trouble indicators (1.7 Amps max. per
circuit)
Each Indicating Circuit can be configured as
Silenceable or Non-Silenceable. Audibles may be
configured as Steady, Temporal Code, California
Code or March Time
Each Initiating Circuit can be configured as Alarm,
Supervisory, Waterflow or Trouble
Two outputs for 4 wire resettable smoke power
supply (200 mA Max. each)
Alarm Verification on Initiating Circuits
Easy configuration via push buttons and SLIDE
switches on the front panel

SPECIFICATIONS
Primary Input Power
Indicating Current
Standby Power
Charging Capability
Dimensions:

120 Volts, 60 Hz, 2 Amps


24VDC Unfiltered, 5 Amps
24VDC Standby Batteries
10 24 AH Batteries
26 H x 14 1/2 W x 4 1/2 D

The HCP-1008ES-DDC consists of one HMCC-1024-6SDDC Main Chassis in an HBB-1024-DDC Enclosure. The
HMCC1024-6-DDC Main Chassis comes complete with
8 Class B (Style B) Initiating Circuits which may be
configured as 4 Class A (Style D) Circuits. It can be
expanded up to 24 Class B or 12 Class A circuits with the
addition of two HDM-1008-DDC Initiating Circuit Modules.
In addition it comes equipped with 4 Class A/B (Style Z/
Y) Indicating circuits which are each rated at 1.7 Amps.
The Main Chassis also includes a 6 Amp Power Supply
which powers the system and supplies two 4-wire
resettable regulated smoke power supply of 24 VDC
200mA maximum each. The HMCC-1024-6S-DDC also
allows for the addition of two HSGM-1004-DDC Signal
Modules or two HRM-1008-DDC Relay modules in place
of the HDM-1008-DDC Initiating Circuit Adder Modules.
(Maximum of 2 Adder modules and 1 communication
module).
The cabinet is available in a beige color for the Canadian
market and a red exterior for the U.S. and international
markets. A Fire Retardant Lexan Window in the hinged
door allows for viewing of the status LEDs. It comes with
a durable CAT-30 lock and key. Space is provided for up
to 17 AH Gel Cell batteries.
Delta Digital Controls's HCP-1008ES-DDC is designed
as an economical Microprocessor Based Fire Alarm
Control Panel which is expandable up to 24 display points.
Its modular design suits various applications. Ideal for
applications such as small institutional and commercial
buildings, shopping malls, offices and public
establishments, the HCP-1008ES-DDC is configurable to
meet virtually all requirements. The panel is designed to
be easy in its installation, operation and maintenance.
This makes the system cost effective and very reliable for
its intended applications.

PRODUCT LISTINGS
Underwriters Laboratories: S6468
CSFM #: 7165-0410:154

Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.

F0013

04/2005

ORDERING INFORMATION
Model

Description
Fire Alarm Control Panel

HCP-1008ES-DDC

Microprocessor Based Fire Alarm Control Panel expandable up to 24 display points.


Includes HMCC-1024-6S-DDC Main Chassis complete with 8 Class B (Style B) Initiating Circuits
or 4 Class A (Style D) Initiating Circuits, 4 Class A/B (Style Z/Y) Indicating Circuits, 6 Amp
Power Supply and one HBB-1024-DDC Red Enclosure.

HFA-1024TR-DDC

Semi-Flush Trim Ring

Adder Modules
HDM-1008-DDC
HSGM-1004-DDC
HRM-1008-DDC

Auxiliary Modules
HDACT-100U-DDC
HDACT-100-DDC
HPR-100-DDC

Eight Class B (Style B) or 4 Class A (Style D) Initiating Circuit Module


Four Class A/B (Style Z/Y) Indicating Circuit Module (Rated at 1.7 Amps per circuit)
Eight Relay Circuit Module comes with eight Form C relays (Rated for 28 VDC @ 1 Amp.
max. per relay)
Universal Digital Alarm Communication Transmitter/Dialer Module
Digital Alarm Communication Transmitter/Dialer Module
Polarity Reversal and City Tie Module

Remote Annunciators
HRAM-1032-DDC
Main Annunciator Chassis comes with Common Control Features, Indicators and
32 Bi-Colored LEDs
HBB-1001-DDC
Annunciator backbox with keylock door

Delta Digital Controls HCP-1008ES FIRE ALARM CONTROL PANEL

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed

HPS-CP CALL POINT BREAK GLASS STATIONS


SPECIFICATIONS
Contacts

Normally Open

Contact Current Rating 3A @ 120 VAC


Dimensions (WxHxD)

3.5" x 5 1/4" x 3/4"

DESCRIPTION
Delta Digital Controls Models HPS-CP-DDC series pull
stations are available in two models:

HPS-CP-DDC

HPS-CP-DDC call point/break glass


HPS-CP/S-DDC call point/break glass
(Spanish)
The Delta Digital Controls HPS-CP-DDC series is very
dependable break glass station intended for simple yet
failsafe operation. The actuating switch is a heavy duty
plunger type, with a Glass plate covering (2.5" x 2.5")
which is a Factrolite single strength (obscured) type.
Design of this station is such that it seems to inhibit the
"false alarm" factor that is so prevalent in public schools
and places of public assembly. The steel rod attached to
the station is not necessary to break the glass. A slight
blow of the hand, coin, key, pencil, etc. is sufficient to
break the glass and initiate the alarm. The HPS-CP-DDC
is intended for mounting in a standard electrical outlet
box.

WIRING DIAGRAM
TOP REAR VIEW

HPS-CP-DDC/S
STANDARD FEATURES
Actuating switch, a heavy duty plunger type
Glass plate (2.5" x 2.5"), a Factrolite single
strength (obscured) type.
Steel rod attached
Mounts in a standard electrical outlet box
Available in English & Spanish
UL listed
Made in USA

L1
IN
L2
CIRCUIT
L2 OUT
L1

PRODUCT LISTING
Underwriter Laboratories: S6512
CSFM #: 7150-0410:164

Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.

F0013

04/2005

Delta Digital Controls HPS-CP CALL POINT BREAK GLASS STATIONS

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed

HPS-SA-EX/WP Explosion Proof Manual Pull Stations


DESCRIPTION
The Delta Digital Controls HPS-SA-EX/WP-DDC
Explosion Proof Manual Pull Station is a single action,
UL listed fire alarm initiating device. With a UL rating
of class I groups B (hydrogen), C and D; class II
groups E, F and G; class III and an outdoor rating of
type 4X, this station offers unmatched placement
flexibility. The 2 sets of Form "C" (NO/C/NC) contacts
are rated for 10 Amps at 120/240 VAC. The HPS-SAEX/WP-DDC has an easily identifiable pull down lever
and contains an integral break glass rod carrier.

STANDARD FEATURES
Compatible with all Delta Digital Controls
Control Panels
Rugged die-cast housing
Rated class I group B (hydrogen) C&D, class II
groups E,F,G, class III, 4X outdoor
Weather Proof
Corrosion-resistant construction
Latching alarm levers
Screw Terminals 12-22 AWG
Key-locked reset
Optional glass break rod
DPDT Contacts

SPECIFICATIONS
Contacts

DPDT Form "C" (NO/C/NC)

The unit is a high quality manual fire alarm box


constructed entirely of a high strength metal die-cast
alloy with a low profile and rounded edges to fit most
design applications. All components are prepainted
or have plated surfaces to inhibit corrosion. Noncorroding screw terminals are provided for wire
connections to the HPS-SA-EX/WP-DDC.
The HPS-SA-EX/WP-DDC is manufactured in
conformance with the standards set forth in the
Americans with Disabilities Act (ADA).
The HPS-SA-EX/WP-DDC has a white pull down lever
in its center. Pulling down the lever latches it into
place. The HPS-SA-EX/WP-DDC's normally open
contact switch is shorted causing an alarm on the
fire initiating loop. The pull down lever can not be
reset unless the correct key is inserted into the
manual fire alarm box lock and the unit is opened.
The latching lever can then be restored to its normal
position.
When the HPS-SA-EX/WP-DDC is being reset and
has a glass break rod installed, all debris must be
removed prior to installing another rod to ensure the
unit will close and lock securely.

Contact Current Rating 10 Amps @ 120/240 VAC


Dimensions (HxWxD)

4.75 in. x 3.125 in. x


3.375 in. (12.1 cm x 7.9
cm x 8.6 cm)

PRODUCT LISTING
Underwriter Laboratories: E154860
CSFM #: 7151-0410:163

Specifications subject to change without notice


Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.

F0013

04/2005

Delta Digital Controls HPS-SA-EX/WP Explosion Proof Manual Pull Stations

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed, FM Approved

Series HPS-SAH, HPS-SAK, HPS-DAHC, HPS-DAH/S, HPS-DAK, HPS-DAK/S


Manual Non-Coded Pull Station

STANDARD FEATURES

Metal Construction
Enclosed switch with glass rod (included)
10 Amps @ 120 VAC
Available in: Single Action, Dual Action and
Dual Action in Spanish (HPS-DAH/S-DDC)
UL, FM, CSFM Listed
Made in USA

HPS-SAH-DDC

HPS-SAK-DDC
DESCRIPTION
Delta Digital Controls Americas Models HPS series
pull stations are available in six models:

HPS-DAH-DDC

HPS-SAH-DDC single action


HPS-SAK-DDC single action with key lock
HPS-DAH-DDC dual action
HPS-DAH/S-DDC dual action (Spanish)
HPS-DAK-DDC dual action with key lock
HPS-DAK/S-DDC dual action with key lock
(Spanish)

HPS-DAH/S-DDC
Each model is constructed of a solid die cast housing
and comes in glossy red. The back switch plate is plated
steel. The electrical switch is rated for 10 Amps @ 120
VDC normally open contact rating. All models are connected via terminal block connections.

PRODUCT LISTING
Underwriters Laboratories: S2984
CSFM #: 7150-0410:162

HPS-DAK-DDC

HPS-DAK/S-DDC

Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.

F0013

04/2005

Rear View

Front View

PULL DOWN

SPECIFICATION

ELECTRICAL WIRING

Delta Digital Controls Manual Non-Coded Pull Station

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed

HPS-SAH-DDC-WP Weather Proof Manual Pull Stations


DESCRIPTION
The Delta Digital Controls HPS-SAH-DDC-WP
Weatherproof Manual Pull Station is a UL Listed fire
alarm initiating device suitable for applications requiring
outdoor mounting of the manual fire alarm pull station.
The HPS-SAH-DDC-WP is appropriate for applications
where the manual pull station may be subject to wet
conditions.
The HPS-SAH-DDC-WP consists of a die-cast aluminum
back box, Neoprene sealing gasket and a special manual
fire alarm box. The unit is a high quality pull station
constructed entirely of nontoxic materials with a low
profile and rounded edges to fit most design requirements.
All components are pre-painted, or have plated surfaces
to inhibit corrosion.

STANDARD FEATURES

Weatherproof Manual Pull Station


10 A, 120 VAC contacts
Rugged die-cast aluminum housing
Neoprene sealing gasket
Corrosion-resistant construction
Hex reset
Latching pull-down lever
Screw terminal connections

The latching pull-down lever on the HPS-SAH-DDC-WP


requires a hex key to reset it. This allows only authorized
personnel to reset the manual pull station so that the
origin of the alarm can be determined easily.
The HPS-SAH-DDC-WP has one set of Normally Open
contacts rated for 10A @ 120 VAC, making the device
suitable for installations involving large current loads.
The HPS-SAH-DDC-WP conforms with the Americans
with Disabilities Act (ADA).
Manual Station

SPECIFICATIONS
Contact Current Rating 10A @ 120 VAC
To Fire Alarm
Control/Communicator
zone or point

1
N/O

Switch

PRODUCT LISTING
Underwriter Laboratories: S2984
CSFM #: 7150-0410:162
Wire Connections
Specifications subject to change without notice
Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.

F0013

04/2005

Delta Digital Controls HPS-SAH-DDC-WP Weather Proof Manual Pull Stations

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed, FM Approved

AIE-EA-DDC IONIZATION SMOKE SENSOR


APPLICATION
The Delta Digital Controls AIE-EA-DDC Ionization smoke
sensor has a responsive and highly stable operation that
gives it an extremely wide range of uses. The AIE-EADDC can be used in areas where early warning of trouble
from superheated or flaming combustibles is expected.
The AIE-EA-DDC is also constructed to be effectively
used where outside RFI (Radio Frequency Interference)
and other electrical interference is expected to be encountered.

OPERATION
Shown without base

STANDARD FEATURES.
Low Profile - Only 2.22" high, including base.
Simple and reliable device addressing method.
Very low current consumption using the unique
"Low Power Mode".
Automatic compensation for sensor
contamination.
Built in fire test feature.
Uses the noise immune Digital Communication
Protocol (DCP), which utilizes interrupts for fast
response to fires.

SPECIFICATIONS
Operating Voltage
Current Consumption
Standby:

17-41 VDC

Normal: 350A (typical)


Low Power Mode:
140A (@ 0.75 sec)
Average when polled: 2mA
Alarm:
8mA
Transmission Method
DCP - Digital
Communication Protocol
Maximum Humidity
95% RH Non Condensing
UL Ambient Installation 32F to 100F
Temperature Range
(0C to 37.8C)
Operating Temperature
14F to 122F
Range
(-10C to 50C)
Radiation Source
Americium 241 (0.98Ci)
Color & Case Material Bone PC / ABS Blend
Weight
4.2oz (5.9 oz. w/ 4" base)
Base
4" YBN-NSA-4-DDC
6" HSB-NSA-6-DDC

A single radioactive source ionizes two chambers which


causes a small DC current to flow between the electrodes in each chamber. Smoke can freely enter the
outer chamber while the inner chamber is virtually sealed
to smoke. Smoke entering the outer chamber causes a
reduction in the DC current, the imbalance between the
two chambers is proportional to the smoke density. The
two chamber design is utilized to compensate for changes
in atmospheric and environmental conditions. When the
sensed input value exceeds a predetermined threshold,
an interrupt is issued to the control panel indicating a
fire alarm.
The fire alarm control panel can adjust the sensor threshold to compensate for contamination. Up to 127 devices are permitted on each loop. A sensor address can
be set by a hand held programming unit. The sensor
mounts to an electronics free base and incorporates a
locking mechanism for secure installation. The base
provides mounting slots, terminals for field wiring and a
third contact for a remote indicator/LED. The sensor incorporates dual LED's for easy viewing of sensor status.

ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated
on the plans, dual-chamber, ionization smoke sensor
Delta Digital Controls AIE-EA-DDC. The combination
sensor head and twist-lock base shall be UL listed compatible with a UL listed fire alarm control panel.

PRODUCT LISTINGS
Underwriters Laboratories: S1383
CSFM #: 7271-0410:148
FM#: 3022559
MEA Report#: 284-91-E Vol. IV

Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.

F0013

04/2005

ENGINEERING SPECIFICATIONS, continued


The base shall permit direct interchange with the Delta Digital Controls ALG-V-DDC photoelectric sensor and the
ATG-EA-DDC heat sensor.
The sensitivity of the sensor shall be capable of being measured by the control panel.
The vandal-resistant, security locking feature shall be used in those areas indicated on the drawing. The locking feature
shall be optional and can be implemented when required.

BASES
The Delta Digital Controls HSB-NSA-6-DDC and the YBN-NSA-4-DDC mounting bases are electronics free and are a
simple rugged design with screw terminals for wiring connections. A common mounting base allows
sensor interchange and maintains loop continuity when sensors are removed. A simple anti-tamper head locking
system is provided which is enabled by removing a small plastic tab on the back of the sensor.
Once locked, the head can be removed using a small diameter screw driver.

HSB-NSA-6-DDC Base

YBN-NSA-4-DDC Base

TYPICAL WIRING DIAGRAMS

NOTE: Fire alarm control panel compatibility is required for DCP products.
State-of-the-art communications protocol, DCP, allows system components (DCP sensors AIE-EA-DDC,
ALG-V-DDC and ATG-EA-DDC, bases and modules), to be used concurrently in a system's signal conditioning
loop.
Delta Digital Controls AIE-EA-DDC IONIZATION SMOKE SENSOR

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed, FM Approved

ALG-V-DDC PHOTOELECTRIC SMOKE SENSOR


APPLICATION
The Delta Digital Controls ALG-V-DDC Photoelectric
Smoke Sensor is particularly suited to detecting optically
dense smoke typical of fires involving materials such as
soft furnishings, plastic, foam or other similar materials
which tend to smoulder and produce large visible smoke
particles. Delta Digital Controls's unique design allows
fast response to flaming fires as well as smoldering fires
while eliminating false alarms.

OPERATION

Shown without base

STANDARD FEATURES
Low Profile - Only 1.97" high, including base.
Simple and reliable device addressing method.
Very low current consumption using the unique
"Low Power Mode".
Automatic compensation for sensor contamination.
Built-in optical fire test feature.
Uses the noise immune Digital Communication
Protocol (DCP), which utilizes interrupts for fast
response to fires.

SPECIFICATIONS
Operating Voltage
Current Consumption
Standby:

17-41 VDC

Normal: 390A (typical)


Low Power Mode:
120A (@ 0.75 sec.)
Average when Polled:
2mA
Alarm:
8mA
Transmission Method
DCP - Digital
Communication Protocol
Maximum Humidity
95% RH Non-Condensing
UL Ambient Installation 32F to 100 F
Temperature Range (0 C to 37.8 C)
Operating Temperature
14F to 122 F
Range
(-10 C to 50 C)
Air Velocity Range
0-4000 fpm
Color & Case Material Bone PC / ABS Blend
Weight
3.4oz
(5.1 oz. with 4" base)
Bases
4"
YBN-NSA-4-DDC
6"
HSB-NSA-6-DDC

The detection chamber consists of a light emitting diode


(LED) and photodiode arrangement. The chamber is
designed such that light emitted by the LED cannot
normally reach the photo diode. In the event of fire, particles
of smoke enter the chamber and scatter the light. As the
smoke level increases, the scattering effect increases,
causing more light to hit the photo- diode. The chamber
contains a unique baffle design which allows smoke to
enter the chamber while preventing external light from
affecting the photodiode. The photodiode input level is
sampled to sense smoke density.
When the smoke density exceeds a preset threshold the
sensor transmits an interrupt to the fire control panel
indicating a fire condition. The fire alarm control panel
can adjust the sensor threshold to compensate for
contamination.
Up to 127 devices are permitted on each loop. A sensor
address can be set by a hand held programming unit. The
sensor mounts to an electronics free base and incorporates
a locking mechanism for secure installation. The base
provides mounting slots, terminals for field wiring and a
third contact for a remote indicator/LED. The sensor
incorporates dual LED's for easy viewing of sensor status.

ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, photoelectric sensors Delta Digital Controls Model ALG-V-DDC. The combination
sensor head and twist lock base shall be UL listed
compatible with a UL listed fire alarm control panel.

PRODUCT LISTINGS
Underwriters Laboratories: S1383
CSFM #: 7272-0410:149
FM#: 3022559
MEA Report #: 284-91-E Vol. IV

Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.

F0013

04/2005

ENGINEERING SPECIFICATIONS, continued


The base shall permit direct interchange with the Delta Digital Controls AIE-EA-DDC ionization type smoke sensor,
and the ATG-EA-DDC heat sensor.
The sensitivity of the sensor shall be capable of being measured by the control panel.
The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking
feature shall be optional and can be implemented when required.

BASES
The Delta Digital Controls YBN-NSA-4-DDC and the HSB-NSA-6-DDC mounting bases are electronics free and are a
simple rugged design with screw terminals for wiring connections. A common mounting base allows sensor interchange
and maintains loop continuity when sensors are removed. A simple anti-tamper head locking system is provided which
is enabled by removing a small plastic tab on the back of the sensor. Once locked, the head can be removed using a
small diameter screw driver.

YBN-NSA-4-DDC Base

HSB-NSA-6-DDC Base

TYPICAL WIRING DIAGRAMS

NOTE: Fire alarm control panel compatibility is required for DCP products.
State-of-the-art communications protocol, DCP, allows system components (DCP sensors AIE-EA-DDC,
ALG-V-DDC and ATG-EA-DDC, bases and modules), to be used concurrently in a system's signal conditioning loop.

Delta Digital Controls ALG-V-DDC PHOTOELECTRIC SMOKE SENSOR

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed, FM Approved

ATG-EA-DDC HEAT SENSOR


APPLICATION
The Delta Digital Controls ATG-EA-DDC Sensor provides
accurate temperature measurement data to the fire alarm
control panel. This sensor is particularly suited to
environments where smoke detectors are unsuitable
because of the precense of system or cooking fumes
such as in a kitchen.

OPERATION

STANDARD FEATURES
Low Profile - Only 2.0" high, including base
Simple and reliable device addressing method
Very low current consumption using the unique
"Low Power Mode"
Built-in optical fire test feature
Uses the noise immune Digital Communication
Protocol (DCP), which utilizes interrupts for fast
response to fires
Adjustable threshold temperature 135F - 150F
(determined by panel)

SPECIFICATIONS
Operating Voltage
Current Consumption
Standby

17-41 VDC

Normal: 350A (typical)


Low Power Mode:
110A (@ 0.75 sec.)
Average when Polled
2mA
Alarm
8mA
Transmission Method
DCP - Digital
Communication Protocol
Maximum Humidity
95% RH Non-Condensing
UL Ambient Installation 32F to 115 F
Temperature Range (0 C to 47 C)
Operating Temperature
135F to 150 F
Range
(57.2 C to 65.6 C)
Color & Case Material Bone PC / ABS blend
Weight
3.2oz
(4.9 oz. with 4" base)
Bases
4"
YBN-NSA-4-DDC
6"
HSB-NSA-6-DDC

The ATG-EA-DDC Heat sensor incorporates a highly


linear thermistor circuit, with the thermistor mounted
externally. The specially designed cover protects the
thermistor while allowing maximum air flow. The
thermistor circuit produces a voltage proportional to
temperature which is scaled, and transmitted as a
digitally encoded value to the control panel. When the
ambient temperature exceeds a pre-programmed
threshold (fixed temperature), the sensor transmits an
interrupt to the control panel indicating a fire alarm. The
fire alarm control panel can adjust the sensor threshold
for different Standard's requirements. The rate of rise
function is calculated within the fire alarm control panel,
which can also initiate a fire test which functionally
tests the sensor.
Up to 127 devices are permitted on each loop. A sensor
address can be set by a hand-held programming unit.
The sensor mounts to an electronics free base and incorporates a locking mechanism secure installation. The
base provides mounting slots, terminals for field wiring,
and a third contact for a remote indicator/LED. The sensor incorporates dual LED's for easy viewing of sensor
status.

ENGINEERING SPECIFICATIONS
Heat sensors are installed in accordance with NFPA
(National Fire Pretection Association) 72, the UL Listed
Spacing Requirements and the rules and regulations set
forth by the local authorities having

PRODUCT LISTINGS
Underwriters Laboratories: S2966
CSFM #: 7272-0410:147
FM#: 3022559
MEA Report#: 284-91-E Vol. IV

Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.

F0013

04/2005

ENGINEERING SPECIFICATIONS, continued


jurisdiction. Automatic heat sensors shall be Underwriters Laboratories listed.
The base shall permit direct interchange with the Delta Digital Controls AIE-EA-DDC ionization type smoke sensor,
and the ALG-V-DDC photoelectric smoke sensor.
The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking
feature shall be optional and can be implemented when required.
It shall be possible to perform a functional test of the sensor without generating heat. The test method shall simulate

BASES
The Delta Digital Controls HSB-NSA-6-DDC and the YBN-NSA-4-DDC mounting bases are electronic free and are a
simple rugged design with screw terminals for wiring connections. A common mounting base allows sensor interchange and maintains loop continuity when sensors are removed. A simple anti-tamper head locking system is
provided which is enabled by removing a small plastic tab on the back of the sensor. Once locked, the head can be
removed using a small diameter screw driver.

(DIAGRAM OF 2 BASES HERE)

HSB-NSA-6-DDC Base

YBN-NSA-4-DDC Base

TYPICAL WIRING DIAGRAMS

NOTE: Fire alarm control panel compatibility is required for DCP products.
State-of-the-art communications protocol, DCP, allows system components (DCP sensors AIE-EA-DDC,
ALG-V-DDC and ATG-EA-DDC, bases and modules), to be used concurrently in a system's signal conditioning loop.
Delta Digital Controls ATG-EA-DDC HEAT SENSOR

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed, FM Approved

DCD 135/190 FIXED TEMPERATURE/RATE OF RISE HEAT DETECTOR


APPLICATION
The DCD-135-DDC /-190-DDC fixed temperature/rateof-rise heat detector are suited for installation where high
heat output fires are expected or in areas where ambient
conditions would not allow use of other detection
methods. Heat detectors are intended for protection of
property. Do not rely on heat detectors for life safety
protection. Where life safety is a concern, smoke
detectors must also be used. A UL listed fire alarm
panel must electronically supervise the DCD-135-DDC /
-190-DDC heat detectors.

Shown without base

STANDARD FEATURES
Choice of fixed temperature/rate-of-rise
135F or 190F heat detector
UL Listed spacing up to 60' by 60'
2 or 4 wire base compatibility, relay bases available
Highly stable operation, RF/Transient protection
Low standby current, 35A nominal
Two built-in power/alarm LED's for 360 viewing
Fully electronic operation
Power/alarm LED's confirm detector status
Compatible with Delta Digital Controls SLR-24V DDC and SIJ-24 - DDC
detectors
and their bases

Response

SPECIFICATIONS
Temperature
135 7.5F
Temperature
190 7.5F

Rated Voltage
Working Voltage
Maximum Voltage
Supervisory Current
Surge Current
Alarm Current
Ambient Temperature
Contact Rating
Color & Case Material
Mounting

17.7 - 30.0 VDC


15.0 - 33.0 VDC
42 VDC
40A @ 24 VDC
160A max. @ 24 VDC
150mA max. @ 24 VDC
32F to 120F
(0C to 49C)
N/O Contacts
150mA max. @ 24 V
Bone PC/ABS blend
Refer to the NS Conventional
Detector Base Data Sheet

All NS conventional devices are mechanically compatible


with Delta Digital Controls HSB, HSC and YBA type
bases. Please check individual panel listings for
appropriate listed bases.

OPERATION
The DCD-135-DDC /-190-DDC fixed temperature/rate-ofrise heat detectors are suited to detect in the presence
of slow or fast rising temperatures due to burning
combustibles. The construction of these models
incorporate a thermistor heat element protected from
damage by the built-in, durable plastic guard. These
electronic heat detectors incorporate two power/alarm
LED's for 360 indication of status. In standby condition
the power LED's flash Green. In an alarm condition the
LED's latch on Red. The DCD-135-DDC /-190-DDC
electronic heat detection circuitry performs the same
function as a Mechanical Device but with Electronic
Precision. If the heat rise is less than 12/minute the
DCD will not alarm until it reaches its alarm temperature
(135 or 190 7.5F). If the heat rise is greater than
12/minute the DCD will alarm immediately giving an
early warning signal and latching the Red alarm LED's
on.

PRODUCT LISTINGS

MEA

284-91E Vol. IV
S2966

Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

1D5A1.AY
California
State Fire
Marshal
7270-0410:151
Continued on back.

F0013

04/2005

ENGINEERING SPECIFICATIONS
Automatic heat detectors where ambient temperatures do not exceed 120F shall be the DCD-135-DDC fixed
temperature/rate-of-rise heat detector rated at 135F. For areas where ambient temperatures exceed 120F, but not
160F, the DCD-190-DDC fixed temperature/rate-of-rise heat detector rated at 190F shall be used. Electrical contacts
shall be normally open, rated at 150mA @ 24VDC.
Heat detectors shall be installed in accordance with National Fire Protection Association Standard 72, the spacing
assigned by Underwriters Laboratories and in accordance with the rules and regulations set forth by the local authorities
having jurisdiction. Automatic heat detectors shall be Underwriters Laboratories listed.

4-WIRE OPERATION
(+)
INITIATING
CIRCUIT

LISTED
END OF LINE
DEVICE
HSC-4R
CONTACTS

(-)

H1
H2
YEL
ORN
PUR

UL LISTED
POWER
SUPPLY
12VDC OR 24VDC

(+)

LISTED
END OF LINE
RELAY
HA-EOLR-12 OR HA-EOLR-24

(-)

HSC-4R

HSC-4R

2-WIRE OPERATION

UL LISTED
CONTROL
PANEL

(+)

LISTED
END OF LINE
DEVICE

(-)
PANEL
POWER
SUPPLY

Resistor shown is for example


only. Not all annunciators have
in line resistance.

(-)

NEGATIVE

NS4 SERIES

NS6 SERIES

Annunciation device must be current limited to 20 mA @


24VDC Maximum. Not limiting current could result in
damage to the detector or cause a no alarm condition.

2-WIRE RELAY OPERATION


(+)
UL LISTED
CONTROL
PANEL

LISTED
END OF LINE
DEVICE
TERMINAL BLOCK USED ON
HSC-224RA/RST VERSION ONLY
HSC-(XXX)R (2-WIRE)

(-)
COM

N/C

5
4
3

N/O

HSC-RELAY SERIES

N/O
N/C
COM

Delta Digital Controls DCD 135/190 FIXED TEMPERATURE/RATE OF RISE HEAT DETECTOR

2
1

GRY
BLU
GRN
YEL
ORN
PUR

2 AND 4 WIRE BASE


RELAYS SHOWN WITH
POWER OFF.

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed

DFE 135/190-DDC FIXED TEMPERATURE HEAT DETECTOR


APPLICATION
The DFE 135/190-DDC fixed temperature heat detector
is suited for installation where high heat output fires are
expected or in areas where ambient conditions would
not allow use of other detection methods.
Heat detectors are used for property protection. Do not
rely on heat detectors for life safety protection. Where
life safety is involved, smoke detectors must also be
used.
Heat detectors should be electronically supervised from
a UL listed alarm panel.

OPERATION
STANDARD FEATURES

Choice of fixed temperature - 135F or 190F


UL Listed ceiling spacing of 50' by 50'
(2,500 square feet)

Self-Restoring
Heat element protected by a built-in guard
Contact Rating of 100 mA
Highly Dependable

The DFE 135/190-DDC fixed temperature heat detector


is suited to alarm in the presence of slowly rising
temperatures. The construction of this model
incorporates an oversized heat collector protected from
damage by the built-in, durable plastic guard. The DFE
135/190-DDC fixed temperature heat detector used the
proven snap-disc principle of operation. This bi-metal
disc deflects when temperature reaches a predetermined
value. The disc deflection then causes a push-rod to
close the internal contact resulting in an alarm condition.
The bi-metal disc returns to its normal shape when the
heat subsides causing internal contacts to return to their
normally open position. A standby condition is restored.

Latching LED base available

ENGINEERING SPECIFICATIONS
SPECIFICATIONS
Temperature
135 7.5F
Temperature
190 7.5F
Contact Rating
N/O Contacts
100mA @ 60 V
Color & Case Material
Ivory ACS
Mounting
Refer to back of this sheet
Response

PRODUCT LISTINGS
Underwriters Laboratories: S2966
CSFM #: 7270-0410:119
MEA Report #: 284-91-E Vol. II

Automatic heat detectors shall be fixed temperature rated


at 135F for areas where ambient temperatures do not
exceed 120F and 190F where ambient temperatures
exceed 120F but not 160F. The fixed temperature element shall consist of a bi-metallic disc and actuator
shaft. Electrical contacts shall be normally open, rated
at 100mA @ 60VDC.
Heat detectors shall be installed in accordance with
National Fire Protection Association Standard 72, the
spacing assigned by Underwriters Laboratories, and in
accordance with the rules and regulations set forth by
the local authorities having jurisdiction. Automatic heat
detectors shall be Underwriters Laboratories listed.

Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.

F0013

04/2005

COMPATIBLE BASES
HSC-(XXX)L-DDC HEAT DETECTOR BASE
The HSC-DDC xxx L Series is a 6" base featuring a current limiting resistor, latching annunciator
output and a latching circuit so the alarm LED will remain lit until the control panel has been reset.
Heat detectors are not recognized as proper detection for life safety protection, therefore they
should be utilized only for the protection of property.

COMPATIBLE

(+)

UL LISTED

LISTED
END OF LINE
DEVICE
3.9K 1/2W

CONTROL
PANEL

(-)

Pig Tail Lead

PANEL
POWER
SUPPLY

(-)

HSC-(XXX)L SERIES

NEGATIVE

Nominal alarm current shown at 24V. Polarized with annunciator output.


HSC-21L-DDC 24mA
HSC-224L-DDC 38mA

HSC-221L-DDC 41mA
HSC-220L-DDC 73mA

NS6 -100- DDC DETECTOR BASE


The NS6 -100- DDC is a 6" diameter base that has no current limiting nor annunciator output
features. A direct short occurs across the loop when the detector is actuated. Heat detectors are
not recognized as proper detection for life safety protection, therefore they should be utilized only
for the protection of property.

(+)
COMPATIBLE
UL LISTED
CONTROL
PANEL

LISTED
DEVICE

(-)
6

NS6-100
NS6-100-DDC
Non polarized, not current limited. No annunciator output.

We try to keep our product information up-to-date and accurate. However, we cannot cover
all specifications or anticipate all requirements. For additional information contact
your local distributor or call or write Delta Digital Controls.
Delta Digital Controls DFE 135/190-DDC FIXED TEMPERATURE HEAT DETECTOR

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed

DSC-EA-DDC RATE OF RISE THERMAL DETECTOR


STANDARD FEATURES

SPECIFICATIONS
Rated Voltage:
24VDC
Working Voltage:
15 - 30VDC
Maximum Switching Current: 100mA max.
Heat Sensing Element: Air chamber composed with
the diaphragm.
Operating Temp. Range:
-10 C - +50 C
(14F - 122 F)
Storage Temp. Range: -30 C - +70 C
(-22 F - 158 F)
Relative Humidity
(at 40 C):
95% RH Non-Condensing
3.9 " D x 1.3" H
Dimensions:
Weight:
3 oz.
Color:
Bone
Applicable Standard:
UL-521
Response Grade:
Ordinary

1. The DSC-DDC features a slim design which combines


visual appeal with a high standard of reliability.
2. The design of the DSC-DDC enables the detector to
operate in locations where the temperature is likely
to increase suddenly should a fire develop.
3. The operating characteristics of DSC-DDC is a key
feature of the product enabling a very cost effective
solution for the use of heat detectors. This detector
consumes no current in standby, which enables an
unlimited number of detectors to be connected on
the same detection wires.
4. With connection to the standard Delta Digital Controls
range of conventional bases, the DSC-DDC heat
detector can be connected or disconnected very
easily, allowing simple interchangeability with other
members of the Delta Digital Controls conventional
detectors.

APPLICATION
The DSC-DDC rate of rise heat detector is suitable for
use in most applications that require heat detection.
Please note that special attention should be given to avoid
installation in direct line with hot air heaters, above stoves,
ovens or other heat generating objects.

OPERATION
The DSC-DDC rate of rise heat detectors are composed
of an air chamber, vent and a flexible metal diaphragm.
When the DSC-DDC is heated, the air in the chamber
expands. The vent permits the chamber to breathe and
slowly release the expanded air. If a fire occurs, the air
in the chamber will expand more rapidly than it can be
vented. This causes the diagram to close a set of precious
metal contacts (nornally open) to trigger the alarm signal.

PRODUCT LISTINGS
Underwriters Laboratories: S2966

Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.

F0013

04/2005

COMPATIBLE BASES
HSC-(XXX)L-DDC HEAT DETECTOR BASE
The HSC-(XXX)L-DDC Series is a 6" base featuring a current limiting resistor, latching annunciator output and a latching circuit so the alarm LED will remain lit until the control panel has been
reset. Heat detectors are not recognized as proper detection for life safety protection, therefore
they should be utilized only for the protection of property.

COMPATIBLE

(+)

UL LISTED

LISTED
END OF LINE
DEVICE
3.9K 1/2W

CONTROL
PANEL

(-)
PANEL
POWER
SUPPLY

Pig Tail Lead


(-)

HSC-(XXX)L SERIES

NEGATIVE

Nominal alarm current shown at 24V. Polarized with annunciator output.


HSC-220L-DDC 73mA
HSC-221L-DDC 41mA
HSC-224L-DDC 38mA

NS6 -100- DDC DETECTOR BASE


The NS6 -100- DDC is a 6" diameter base that has no current limiting nor annunciator output
features. A direct short occurs across the loop when the detector is actuated. Heat detectors
are not recognized as proper detection for life safety protection, therefore they should be utilized
only for the protection of property.

(+)
COMPATIBLE
UL LISTED
CONTROL
PANEL

LISTED
END OF LINE
DEVICE

(-)
6

NS6-100
NS6-100-DDC
Non polarized, not current limited. No annunciator output.

We try to keep our product information up-to-date and accurate. However, we cannot cover
all specifications or anticipate all requirements. For additional information contact
your local distributor or call or write Delta Digital Controls.
Delta Digital Controls DSC-EA-DDC RATE OF RISE THERMAL DETECTOR

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed, FM Approved

SIJ-24 - DDC IONIZATION SMOKE DETECTOR


APPLICATION
The SIJ-24 - DDC can be used in all areas where Ionization
Smoke Detectors are required. The responsive yet highly
stabile operation allows the SIJ-24 - DDC to fit in a wide
range of uses. The SIJ-24 - DDC can be used in areas
where early warning of superheated or flaming
combustibles is expected.
NS-4 - DDC Series, NS-6 - DDC Series, HSC-4R - DDC
or HSC-(X)R - DDC Style bases may be used with the
SIJ-24 - DDC. Current compatible devices are the SLR24V - DDC Photoelectric detector, the SLR-24H - DDC
photoelectric detector with heat sensor and the DCD135-DDC /190 - DDC heat detectors.

Shown without base.

STANDARD FEATURES

Low profile, 1.8" high (with base)


2 or 4 wire base compatibility, relay bases available
Highly stable operation, RF/Transient protection
Low standby current, 40A at 24 VDC
Two built-in power/alarm LEDs for 360 viewing
Non-directional smoke chamber
Vandal resistant security locking feature
Built-in magnetic detector sensitivity test feature.
Meets NFPA 72, Chapter 2 & 7, Inspection, Testing
and Maintenance requirements.
Compatible with SLR-24V - DDC photoelectric
detectors
Backwards compatible with Delta Digital Controls
SLK and SIH smoke detectors.

SPECIFICATIONS
Radioactive Source
Rated Voltage
Working Voltage
Maximum Voltage
Supervisory Current
Surge Current
Alarm Current
Ambient Temperature

AM-241 0.5Ci
17.7 - 30.0 VDC
15.0 - 33.0 VDC
42 VDC
40A @ 24 VDC
200A max. @ 24 VDC
150mA max. @ 24 VDC
32F to 120F
(0C to 49C)
Color & Case Material Bone PC/ABS Blend
Sensitivity Test Feature Magnetically activated
dual reed switch test
Mounting
Refer to the NS Conventional
Detector Base Data Sheet

All conventional devices are mechanically compatible


with Delta Digital Controls HSB, HSC and YBA type
bases which may have been used in previous
installations. Please check individual panel listings for
compatible bases.

OPERATION
The SIJ-24 - DDC IONIZATION SMOKE DETECTOR
utilizes two bi-colored LEDs for status indication
purposes. In a normal standby condition the LEDs flash
green approximately once each second. When the
detector senses smoke and goes into alarm the status
LEDs will latch on red.
A single radioactive source of Americium-241 ionizes two
chambers within the detector, a reference chamber, and
the smoke sensing chamber. The air is ionized by this
source and a small DC current flows between the
electrodes of each chamber. Smoke can freely enter
the sensing chamber while the inner chamber is virtually
sealed to smoke. Smoke entering the sensing chamber
causes a reduction in the DC current flow, the voltage
imbalance between the two chambers is proportional to
the smoke density. When the voltage differences become
great enough it causes the detector to go into alarm.
The two chamber design is utilized to compensate for
changes in atmospheric and environmental conditions.

PRODUCT LISTCalifornia
State
S1383

Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

1D5A1.AY

7271Continued on back.

F0013

04/2005

ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, Delta Digital Controls Model SIJ-24 - DDC Ionization
Smoke Detector - DDCs. The combination detector head and twist-lock base shall be UL listed compatible with a UL
listed fire alarm panel.
The base shall permit direct interchange with Delta Digital Controls America, SLR-24V - DDC photoelectric type smoke
detector, SLR-24H - DDC combination photoelectric/heat detector, and/or DCD-135-DDC /190 - DDC Fixed Temperature/
Rate-of-Rise Heat Detector - DDCs. The base shall be appropriate twistlock base NS-4 - DDC Series, NS-6 - DDC Series,
HSC-4R - DDC or HSC-(X)R - DDC. In the event of partial or complete retrofit, the SIJ-24 - DDC maybe used in
conjunction with, or as a replacement for, Delta Digital Controls detectors (SLK-24 - DDC, SLK-24 - DDCFH and the SIH24F - DDC) on most HSB-DDC and HSC-DDC base applications.
The smoke detector shall have two flashing status LEDs for visual supervision. When the detector is in standby condition
the LEDs will flash Green. When the detector is actuated, the flashing LEDs will latch on Red. The detector may be reset
by actuating the control panel reset switch.
The sensitivity of the detector shall be capable of being measured. It shall be possible to perform a functional test of the
detector without the need of generating smoke. The test method shall simulate effects of products of combustion in the
chamber to ensure testing of the detector electronics.
To facilitate installation, the detector shall be non-polarized. Voltage and RF transient suppression techniques shall be
employed to minimize false alarm potential. Auxiliary SPDT relays shall be installed where indicated.
The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking
feature shall be field removable when not required.

SIJ-24 - DDC SENSITIVITY TEST FEATURE


TEST PROCEDURE
1. With detector wired to appropriate initiating circuit or current limited power source and with normal applied power,
place a magnet as shown in Figure 1.
2. Wait at least six seconds. Detector SHOULD NOT alarm and LED should not light.
3. Place magnet on detector as shown in Figure 2 (opposite side).
4. Wait at least six seconds. Detector SHOULD alarm.
5. If detector does alarm when magnet is positioned as in Figure 1 or does not produce an alarm when magnet
is positioned as in Figure 2, detector is not within specified sensitivity limits and may require service. See
Technical Bulletin HA-97 for more information and for additional sensitivity test devices.
WARNING: Conduct testing only under Normal Standby conditions. Abnormal or Low Power conditions may
affect sensitivity. Always reset power prior to testing of next unit.

Figure 1

Delta Digital Controls SIJ-24 - DDC IONIZATION SMOKE DETECTOR

LED's

Figure 2

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed, FM Approved

SLR-24H - DDC PHOTOELECTRIC/ HEAT SMOKE DETECTOR


APPLICATION
The SLR-24H - DDC can be used in all areas where
Photoelectric Smoke Detectors are required. The wide
range smoke chamber makes the SLR-24H - DDC well
suited for fires ranging from smoldering to flaming fires.
NS-4 - DDC Series, NS-6 - DDC Series, HSC-4R - DDC
or HSC-xxx R - DDC Style bases may be used with the
SLR-24H - DDC. Current interchangeable/compatible
devices are the SIJ-24 - DDC ionization detector, SLR24V - DDC photoelectric detector and the DCD-135-DDC
/190 - DDC heat detectors.

Shown without base.

STANDARD FEATURES

Low profile, 2.2" high (with base)


2 or 4 wire base compatibility, relay bases available
135F latching heat sensor
Heat sensor protected by a built-in guard
Highly stable operation, RF/Transient protection
Low standby current, 45A at 24VDC
Two built-in power/sensitivity supervision/alarm LED's
Non-directional smoke chamber
Vandal resistant security locking feature
Removable smoke labyrinth for cleaning or replacement
Automatic Sensitivity window verification function
meets outlined requirements in NFPA 72, Chapter 2 & 7,
Inspection, Testing and Maintenance

SPECIFICATIONS
Light Source
Heat Sensor
Rated Voltage
Working Voltage
Maximum Voltage
Supervisory Current
Surge Current
Alarm Current
Ambient Temperature
Color & Case Material
Sensitivity Test Feature
Mounting

GaAlAs Infrared
Emitting Diode
135F
17.7 - 30.0 VDC
15.0 - 33.0 VDC
42 VDC
45A @ 24 VDC
160A max. @ 24 VDC
150mA max. @ 24 VDC
32F to 120F
(0C to 49C)
Bone PC/ABS Blend
Automatic Sensitivity
window verification test
Refer to NS Conventional
Detector Base Data Sheet

All NS conventional devices are mechanically compatible


with Delta Digital Controls HSB, HSC and YBA type
bases which may have been used in previous
installations. Please check individual panel listings for
compatible bases.

OPERATION
The SLR-24H - DDC photoelectric smoke detector utilizes
two bicolored LED's for indication of status. In a normal
standby condition the LED's flash Green every 3
seconds. When the detector senses that its sensitivity
has drifted outside the UL listed sensitivity window the
LED's will flash Red every 3 seconds. When the detector
senses smoke and goes into alarm the status LED's will
latch on Red.
The detector utilizes an infrared LED light source and
silicon photo diode receiving element in the smoke
chamber. In a normal standby condition, the receiving
element receives no light from the pulsing LED light
source. In the event of a fire, smoke enters the detector
smoke chamber and light is reflected from the smoke
particles to the receiving element. The light received is
converted into an electronic signal.
Signals are processed and compared to a reference level,
and when two consecutive signals exceeding the
reference level are received within a specified period of
time, the time delay circuit triggers the SCR switch to
activate the alarm signal. The status LED's light
continuously during the alarm period.

PRODUCT LISTINGS
Underwriters Laboratories: S1383
CSFM #: 7272-0410:107
Factory Mutual: 3006185

Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.

F0013

04/2005

ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, Delta Digital Controls Model SLR-24H - DDC
photoelectric smoke detectors. The combination detector head and twist-lock base shall be UL listed compatible with
a UL listed fire alarm panel.
The base shall permit direct interchange with Delta Digital Controls SLR-24V - DDC photoelectric detector, SIJ-24 - DDC
ionization type smoke detector and/or DCD-135-DDC /190 - DDC Fixed Temperature/Rate-of-Rise Heat Detector - DDCs.
The base shall be appropriate twist-lock base NS-4 - DDC Series, NS-6 - DDC Series, HSC-4R - DDC , or HSC-xxx R DDC . In the event of partial or complete retrofit, the SLR-24-DDC maybe used in conjunction with, or as a replacement
for, Delta Digital Controls detectors (SLK-24 - DDC, SLK-24 - DDC,FH and the SIH-24-DDC) on most HSB and HSC
base applications.
The smoke detector shall have two flashing status LED's for visual supervision. When the detector is in standby
condition the LED's will flash Green. When the detector is outside the UL listed sensitivity window the LED's will flash
Red. When the detector is actuated, the flashing LED's will latch on Red. The detector may be reset by actuating the
control panel reset switch.
The sensitivity of the detector shall be capable of being measured. It shall be possible to perform a functional test of the
detector without the need of generating smoke. The sensitivity of the detector shall be monitored automatically and
continuously to verify that it is operating within the listed sensitivity range.
To facilitate installation, the detector shall be non-polarized. Voltage and RF transient suppression techniques shall be
employed to minimize false alarm potential. Auxiliary SPDT relays shall be installed where indicated.
The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking
feature shall be field removable when not required.

SLR-24H - DDC SENSITIVITY TEST FEATURE


The SLR-24H - DDC Photoelectric Smoke Detector has a built-in automatic sensitivity test feature.
1. In normal condition, both LED's flash green.
2. When the sensitivity drifts outside of its sensitivity limits, both LED's flash red.
3. In the alarm state both LED's are red continuously.
4. When the sensitivity drifts outside of its sensitivity limits and both LED's flash red, the device needs to be cleaned
or returned to the factory for cleaning. Refer to HA Technical Bulletin HA-97 for cleaning information.

4-WIRE OPERATION

(+)
INITIATING
CIRCUIT

LISTED
END OF LINE
DEVICE
HSC-4R
CONTACTS

(-)

H1
H2
YEL
ORN
PUR

UL LISTED
POWER
SUPPLY
12VDC OR 24VDC

(+)

LISTED
END OF LINE
RELAY

(-)

HSC-4R-DDC
HSC-4R

HSC-4R-DDC
HSC-4R

2-WIRE OPERATION
UL LISTED
CONTROL
PANEL

(+)

LISTED
END OF LINE
DEVICE

(-)
PANEL
POWER
SUPPLY

Resistor shown is for example


only. Not all annunciators have
in line resistance.

(-)

NEGATIVE

NS4 SERIES

NS6

Annunciation device must be current limited to 20 mA @


24VDC Maximum. Not limiting current could result in
damage to the detector or cause a no alarm condition.

NOTE: - WIRING TERMINALS FOR THE NS4


AND NS6 ARE IDENTICAL
SERIES
- BASES WITH THE "W" SUFFIX
ARE WHITE IN COLOR

2-wire relay wiring diagram is also available


Delta Digital Controls SLR-24H - DDC PHOTOELECTRIC/ HEAT SMOKE DETECTOR

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed, FM Approved

SLR-24V- DDC PHOTOELECTRIC SMOKE DETECTOR


APPLICATION
The SLR-24V - DDC can be used in all areas where
Photoelectric Smoke Detectors are required. The wide
range smoke chamber makes the SLR-24V - DDC well
suited for fires ranging from smoldering to flaming fires.

Shown without base.

STANDARD FEATURES
Low profile, 1.8" high (with base)
2 or 4 wire base compatibility, relay bases available
Highly stable operation, RF/Transient protection
Low standby current, 45A at 24VDC
Two built-in power/sensitivity supervision/alarm LEDs
Non-directional smoke chamber
Vandal resistant security locking feature
Built-in magnetic go/no go detector test feature
Removable smoke labyrinth for cleaning or
replacement

Automatic Sensitivity window verification function

meets outlined requirements in NFPA 72, Chapter 2


& 7, Inspection, Testing and Maintenance
Compatible with SIJ-24 - DDC ionization detectors
Backwards compatible with Delta Digital Controls
SLK and SIH detectors

SPECIFICATIONS
Light Source

GaAlAs Infrared
Emitting Diode
Rated Voltage
17.7 - 30.0 VDC
Working Voltage
15.0 - 33.0 VDC
Maximum Voltage
42 VDC
Supervisory Current
45A @ 24 VDC
Surge Current
160A max. @ 24VDC
Alarm Current
150mA max. @ 24 VDC
Air Velocity Range
0-4000 fpm
Ambient Temperature
32F to 120F (0C to 49C)
Color & Case Material Bone PC/ABS Blend
Sensitivity Test Feature Automatic Sensitivity
window verification test
Mounting
Refer to NS Conventional
Detector Base Data Sheet

NS-4 - DDC Series, NS-6 - DDC Series, HSC-4R - DDC


or HSC-xxx R - DDC Style bases may be used with the
SLR-24V - DDC. Current interchangeable/compatible
devices are the SIJ-24 - DDC ionization detector, the
SLR-24H - DDC photoelectric detector with heat sensor,
and the DCD-135-DDC /190 - DDC heat detectors.All
NS conventional devices are mechanically compatible
with Delta Digital Controls HSB, HSC and YBA type
bases which may have been used in previous installations. Please check individual panel listings for compatible bases.

OPERATION
The SLR-24V- DDC PHOTOELECTRIC SMOKE DETECTOR utilizes two bicolored LEDs for indication of status.
In a normal standby condition the LEDs flash Green every 3 seconds. When the detector senses that its sensitivity has drifted outside the UL listed sensitivity window the LEDs will flash Red every 3 seconds. When the
detector senses smoke and goes into alarm the status
LEDs will latch on Red.
The detector utilizes an infrared LED light source and
silicon photo diode receiving element in the smoke chamber. In a normal standby condition, the receiving element receives no light from the pulsing LED light source.
In the event of a fire, smoke enters the detector smoke
chamber and light is reflected from the smoke particles
to the receiving element. The light received is converted
into an electronic signal.
Signals are processed and compared to a reference level,
and when two consecutive signals exceeding the reference level are received within a specified period of time,
the time delay circuit triggers the SCR switch to activate
the alarm signal. The status LEDs light continuously
during the alarm period.

PRODUCT LISTINGS

S1383

Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

1D5A1.AY

California
State Fire
Marshal
7272-0410:107
Continued on back.

F0013

04/2005

ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, Delta Digital Controls Model SLR-24V - DDC
Photoelectric Smoke Detector - DDCs. The combination detector head and twist-lock base shall be UL listed compatible
with a UL listed fire alarm panel.
The base shall permit direct interchange with Delta Digital Controls SLR-24H - DDC combination photoelectric/heat
detector, SIJ-24 - DDC ionization type smoke detector and/or DCD-135-DDC /190 - DDC Fixed Temperature/Rate-of-Rise
Heat Detector - DDCs. The base shall be appropriate twist-lock base NS-4 - DDC Series, NS-6 - DDC Series, HSC-4R
- DDC , or HSC-xxx R - DDC . In the event of partial or complete retrofit, the SLR-24V - DDC maybe used in conjunction
with, or as a replacement for, Delta Digital Controls detectors (SLK-24 - DDC, SLK-24 - DDCFH and the SIH-24-DDC) on
most HSB and HSC base applications.
The smoke detector shall have two flashing status LEDs for visual supervision. When the detector is in standby condition
the LEDs will flash Green. When the detector is outside the UL listed sensitivity window the LEDs will flash Red. When
the detector is actuated, the flashing LEDs will latch on Red. The detector may be reset by actuating the control panel
reset switch.
The sensitivity of the detector shall be capable of being measured. It shall be possible to perform a functional test of the
detector without the need of generating smoke. The sensitivity of the detector shall be monitored automatically and
continuously to verify that it is operating within the listed sensitivity range.
To facilitate installation, the detector shall be non-polarized. Voltage and RF transient suppression techniques shall be
employed to minimize false alarm potential. Auxiliary SPDT relays shall be installed where indicated.

SLR-24V - DDC SENSITIVITY TEST FEATURE


The SLR-24V- DDC PHOTOELECTRIC SMOKE DETECTOR has a built-in automatic sensitivity test feature.
1. In normal condition, both LED's flash green.
2. When the sensitivity drifts outside of its sensitivity limits, both LED's flash red.
3. In the alarm state both LED's are red continuously.
4. When the sensitivity drifts outside of its sensitivity limits and both LED's flash red, the device needs to be cleaned
or returned to the factory for cleaning. Refer to HA Technical Bulletin HA-97 for cleaning information.
2-WIRE OPERATION
UL LISTED
CONTROL
PANEL

PANEL
POWER
SUPPLY
NEGATIVE

LISTED
END OF LINE
DEVICE
Resistor shown is for
example only. Not all
annunciators have in
line resistance.

NS4 SERIES

NS6 SERIES

Annunciation device must be current limited to 20 mA @


24VDC Maximum. Not limiting current could result in
damage to the detector or cause a no alarm condition.

NOTE: - WIRING TERMINALS FOR THE NS4


AND NS6 ARE IDENTICAL
- BASES WITH THE "W" SUFFIX
ARE WHITE IN COLOR

2-WIRE RELAY OPERATION


UL LISTED
CONTROL
PANEL

LISTED
END OF LINE
DEVICE

COM
N/C
N/O

HSC-RELAY SERIES

N/O
N/C

4-WIRE OPERATION

COM

INITIATING
CIRCUIT

6
5
4
3
2
1

TERMINAL BLOCK USED ON


HSC-224RA/RST VERSION ONLY
HSC-(XXX)R (2-WIRE)
GRY
BLU
GRN
YEL
ORN
PUR

2 AND 4 WIRE BASE


RELAYS SHOWN WITH
POWER OFF.

LISTED
END OF LINE
DEVICE
HSC-4R
CONTACTS
H1
H2
YEL
ORN
PUR

UL LISTED
POWER
SUPPLY
12VDC OR 24VDC

LISTED
END OF LINE
RELAY
HA-EOLR-12 OR HA-EOLR-24

HSC-4R-DDC
HSC-4R

Delta Digital Controls SLR-24V - DDC PHOTOELECTRIC SMOKE DETECTOR

HSC-4R
HSC-4R-DDC

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed, FM Approved

SLR-835/SLR-835H PHOTOELECTRIC SMOKE DETECTOR

SLR-835 - DDC

Shown without a base

STANDARD FEATURES

Low Profile - Only 1.8" high (2.2" 835H-DDC)


2 or 4 wire base compatibility, relay bases available
135F latching heat sensor (835H-DDC only)
Heat sensor protected by a built-in guard (835H-DDC only)
Highly stable operation, RF/Transient protection
Low standby current
Two built-in power/sensitivity supervision/alarm LEDs
Non-directional smoke chamber
Vandal resistant security locking feature
Removable smoke labyrinth for cleaning or replacement
Backwards compatible with Delta Digital Controls SLK
and SIH detectors
Automatic Sensitivity window verification function meets
outline requirements in the NFPA 72 Inspection Testing
and Maintenance.

SPECIFICATIONS
Light Source
Operating Voltage
Working Voaltage
Wave Form
Heat Sensor
Supervisory Current
Surge Current
Alarm Current
Ambient Temperature
Compatibility Identifier
Color & Case Material
Sensitivity Test Feature
Ordering Codes White
Dimensions
Mounting

GaAl AS infrared L.E.D.


Nominal 12 VDC or 24 VDC
8.0-35.0 VDC
Filtered DC 15% Ripple Max
135 F (835H-DDC only)
38A AVG @12 VDC
55A AVG @24 VDC
70A AVG @35 VDC
200A Max @24 VDC
150mA Max
32 F - 120 F (0C - 49C)
HD-3
Bone/White PC/ABS Blend
Automatic Sensitivity
window verification Test
SLR-835 - DDCW/SLR-835 DDCHW BoneSLR-835
- DDC/SLR-835H-DDC
1.8" (2.2" 835H-DDC) H x 3.94" W
Refer to NS Conventional
Detector Base Data Sheet

SLR-835H-DDC

Shown without a base

APPLICATION
The Delta Digital Controls SLR-835 - DDC/-835H-DDC can
be used in all areas where photoelectric smoke detectors
are required. It is suited for fires ranging from smoldering to
flaming fires. NS4 - DDC Series, NS6 - DDC Series, HSC4R - DDC or HSC-(X)R - DDC Style bases may be used
with the SLR-835 - DDC/-835H-DDC.

OPERATION
The SLR-835 - DDC/-835H-DDC Photoelectric Smoke
Detector utilizes two bicolored LEDs for indication of
status. In a normal standby condition the LEDs flash
green every 3 seconds. When the detector senses that
its sensitivity has drifted outside the UL listed sensitivity
window the LEDs will flash Red every 3 seconds. When
the detector senses smoke and goes into alarm the status
LEDs will latch on Red.
The detector utilizes an infrared LED light source and
silicon photo diode receiving element in the smoke
chamber. In a normal standby condition, the receiving
element receives no light from the pulsing LED light
source. In the event of a fire, smoke enters the detector
smoke chamber and light is reflected from the smoke
particles to the receiving element. The light received is
converted into an electronic signal.
Signals are processed and compared to a reference level,
and when two consecutive signals exceeding the reference
level are received within a specified period of time, the
time delay circuit triggers the SCR switch to activate the
alarm signal. The status LEDs light continuously during
the alarm period.

PRODUCT LISTCalifornia
State
S1383

Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

3007144

7272Continued on back.

F0013

04/2005

ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, Delta Digital Controls Model SLR-835 - DDC
Photoelectric Smoke Detector - DDCs. The combination detector head and twist-lock base shall be UL listed compatible with a UL listed fire alarm panel.
When the supply power is 24VDC, the base shall permit direct interchange with Delta Digital Controls SLR-24H - DDC
combination photoelectric/heat detector, SLR-24-DDC photoelectric smoke detector, SIJ-24 - DDC ionization type
smoke detector and DCD-135-DDC /190 - DDC heat detector.
The base shall be the appropriate twist-lock base NS4 - DDC Series, NS6 - DDC Series, HSC-4R - DDC , or HSC-(X)R
- DDC Series. In the event of partial or complete retrofit, the SLR-835 - DDC, SLR-835H-DDC may be used in conjunction with, or as a replacement for, Delta Digital Controls detectors ( SLK-835H-DDC, SLK-24 - DDC, SLK-24 - DDC,FH
and the SIH-24F - DDC) on most HSB and HSC base application.
The smoke detector shall have two flashing status LEDs for visual supervision. When the detector is in standby
condition the LEDs will flash Green. When the detector is outside the UL listed sensitivity window the LEDs will flash
Red. When the detector is actuated, the flashing LEDs will latch on Red. The detector may be reset by actuating the
control panel reset switch.
The sensitivity of the detector shall be capable of being measured. It shall be possible to perform a functional test of the
detector without the need of generating smoke. The sensitivity of the detector shall be monitored automatically and
continuously to verify that it is operating within the listed sensitivity range.
To facilitate installation, the detector shall be non-polarized. Voltage and RF transient suppression techniques shall be
employed to minimize false alarm potential. Auxiliary SPDT relays shall be installed where indicated on the drawing.
The locking feature shall be field removable when not required.

SLR-835 - DDC/-835H-DDC SENSITIVITY TEST FEATURE


The SLR-835 - DDC/-835H-DDC Photoelectric Smoke Detector has a built-in automatic sensitivity test feature.
1.
2.
3.
4.

In normal condition, both LEDs flash Green.


When the sensitivity drifts outside of its sensitivity limits, both LEDs flash Red.
In the alarm state both LEDs are Red continuously.
When the sensitivity drifts outside of its sensitivity limits and both LED's flash Red, the device needs to be cleaned
or returned to the factory for cleaning. Refer to HA Technical Bulletin HA-97 for cleaning information.

4-WIRE OPERATION
INITIATING
CIRCUIT

LISTED
END OF LINE
DEVICE
HSC-4R
CONTACTS
H1
H2
YEL
ORN
PUR

UL LISTED
POWER
SUPPLY
24VDC

LISTED
END OF LINE
RELAY
HA-EOLR-24

HSC-4R-DDC
HSC-4R

HSC-4R-DDC
HSC-4R

2-WIRE OPERATION
UL LISTED
CONTROL
PANEL

PANEL
POWER
SUPPLY
NEGATIVE

LISTED
END OF LINE
DEVICE
Resistor shown is for example
only. Not all annunciators have
in line resistance.

NS4 SERIES

NS6 SERIES

Annunciation device must be current limited to 20 mA @


24VDC Maximum. Not limiting current could result in
damage to the detector or cause a no alarm condition.

NOTE: - WIRING TERMINALS FOR THE NS4


AND NS6 ARE IDENTICAL
BASES WITH THE "W" SUFFIX
ARE WHITE IN COLOR

2-WIRE RELAY OPERATION


UL LISTED
CONTROL
PANEL

LISTED
END OF LINE
DEVICE
TERMINAL BLOCK USED ON

COM
N/C
N/O

HSC-RELAY SERIES

N/O
N/C
COM

Delta Digital Controls SLR-835/SLR-835H PHOTOELECTRIC SMOKE DETECTOR

6
5
4
3
2
1

HSC-(XXX)R (2-WIRE)
GRY
BLU
GRN
YEL
ORN
PUR

2 AND 4 WIRE BASE


RELAYS SHOWN WITH
POWER OFF.

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed, FM Approved

SLR-835B-DDC DIRECT-WIRE PHOTOELECTRIC


SMOKE DETECTOR
STANDARD FEATURES

Low Profile - Only 2.0" High


2 or 4 Wire Models
Highly Stable Operation, RF/Transient Protection
Two built-in power/sensitivity supervision/alarm LED's
Non-Directional Smoke Chamber
Vandal Resistant Security Locking Feature
Removable smoke labyrinth for cleaning or
replacement
Automatic Sensitivity window verification function
meets outlined requirements in NFPA 72,
Inspection,Testing and Maintenance
Shown with Trim Ring

APPLICATION

SPECIFICATIONS

The Delta Digital Controls SLR-835B-DDC Series can be


used in all areas where Photoelectric Smoke Detectors
are required. It is suited for smoldering or flaming fires.

Light Source
Operating Voltage
Working Voltage

OPERATION

GaAlAs Infrared LED


Nominal: 12 VDC or 24 VDC
8.0 - 35.0 VDC
(35.0 VDC Max)
Wave Form
Filtered DC 15% Ripple Max.
Alarm Current
150mA Maximum
Surge Current
200A Maximum (2 wire)
Average Stand-By
38A AVG @12 VDC
Current
55A AVG @24 VDC
70A AVG @35 VDC
Ambient Temperature
32 F - 120 F (0 C - 49 C)
Sensitivity Test Feature Automatic Sensitivity
Window Verification Test
Compatibility Identifier HD-6
Order Codes
2-Wire Detector & Trim Ring
Bone SLR-835B-DDC-2
White SLR-835B-DDC-2W
4-Wire Detector & Trim Ring
Bone SLR-835B-DDC-4
White SLR-835B-DDC-4W

The SLR-835B-DDC Series photoelectric smoke detector


utilizes two bicolored LED's for indication of status. In a
normal standby condition the LED's flash Green every 3
seconds. When the detector senses that its sensitivity
has drifted outside the UL listed sensitivity window the
LED's will flash Red every 3 seconds. When the detector
senses smoke and goes into alarm the status LED's will
latch on Red.
The unit is comprised of an LED light source and silicon
photo diode receiving element. In a normal standby
condition, the receiving element receives no light from
pulsing light source. In the event of fire, smoke enters
the detector and light is reflected from the smoke particles
to the receiving element. The light received is converted
to an electronic signal. Signals are processed in the

PRODUCT LISTINGS
Underwriters Laboratories: S1383
Factory Mutual: 3007144
CSFM #: 7272-0410:107

Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.

F0013

04/2005

OPERATION,

continued

comparator, and when two consecutive signals exceeding the basic level are received within a specific period of time, the
time delay circuit triggers the SCR switch to activate the alarm signal. The status LED lights continuously during alarm
period.

ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans Delta Digital Controls SLR-835B-DDC direct-wire
photoelectric smoke detectors. The detector shall be UL listed compatible (2-wire model) with a UL listed fire alarm
panel.
The smoke detector shall have green flashing status LED's for visual supervision. When the detector is actuated, the
flashing LED's will turn red and latch on steady. The detector may be reset by actuating the control panel reset switch.
The detector shall have a sensitivity window verification feature. If the sensitivity of the detector drifts outside its approved
window the LED's will flash red to indicate an out of sensitivity condition.
The vandal resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking
feature shall be field selectable.
It shall be possible to perform a functional test of the detector without the need of generating smoke. The method shall
simulate effects of products of combustion in the chamber to ensure testing of detector circuits.
Voltage and RF transient suppression techniques shall be employed to minimize false alarm potential.

WIRING DIAGRAMS
2-Wire Wiring Diagram
U.L. Listed
Compatible
Control
Panel

Listed
End-of-Line
Device

4-Wire Wiring Diagram

Listed
End-of-Line
Device

U.L. Listed
Control
Panel
U.L. Listed
Power
Supply
*24VDC

Listed
End-of-Line
Relay
12 or 24VDC

U.L. Listed
Power
Supply
*12VDC

* Use either 12 OR 24VDC . They cannot be used simultaneously.


Delta Digital Controls SLR-835B-DDC DIRECT-WIRE PHOTOELECTRIC SMOKE DETECTOR

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed, FM Approved

SLR-835BH-DDC DIRECT-WIRE PHOTOELECTRIC


HEAT SMOKE DETECTOR
STANDARD FEATURES

Shown With Trim Ring

Low Profile - Only 2.375" High.


2 or 4 Wire Models
135 F Latching Heat Sensor
Highly Stable Operation, RF/Transient Protection
Two built-in power/sensitivity supervision/alarm LED's
Non-Directional Smoke Chamber
Vandal Resistant Security Locking Feature
Removable smoke labyrinth for cleaning or
replacement
Automatic Sensitivity window verification function
meets outlined requirements in NFPA 72,
Inspection,Testing and Maintenance.

DESCRIPTION
SPECIFICATIONS
Light Source
Voltage
Nominal
Working
Wave Form
Alarm Current
Surge Current
Average Stand-By
Current

GaAl AS Infrared LED


12 VDC or 24 VDC
8.0 - 35.0 VDC (35.0 VDC Max)
Filtered DC
15% Ripple Max.
150mA Maximum
200A Maximum (2 wire)
38A AVG @12 VDC
55A AVG @24 VDC
70A AVG @35 VDC
32 F - 120 F (0 C - 49 C)

Ambient Temperature
Sensitivity Test Feature
Automatic Sensitivity Window Verification Test
Compatibility Identifier HD-6
Heat Sensor
135 F
Order Codes
2-Wire Detector & Trim Ring
White
Bone
4-Wire Detector & Trim Ring
White
Bone

The SLR-835BH-DDC Series photoelectric smoke


detector utilizes two bicolored LEDs for indication of
status. In a normal standby condition the LEDs flash
Green every 3 seconds. When the detector senses that
its sensitivity has drifted outside the UL listed sensitivity
window the LEDs will flash Red every 3 seconds. When
the detector senses smoke and goes into alarm the
status LEDs will latch on Red.
The unit is comprised of an LED light source and silicon
photo diode receiving element. In a normal standby
condition, the receiving element receives no light from
pulsing light source. In the event of fire, smoke enters
the detector and light is reflected from the smoke particles
to the receiving element. The light received is converted
to an electronic signal. Signals are processed in the
comparator, and when two consecutive signals exceeding
the basic level are received within a specific period of
time, the time delay circuit triggers the SCR switch to
activate the alarm signal. The Status LED lights
continuously during alarm period.

SLR-835BH-DDC-2W
SLR-835BH-DDC-2
SLR-835BH-DDC-4W
SLR-835BH-DDC-4

PRODUCT LISTINGS

S1383

Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

3012444

California
State Fire
Marshal
7272-0410:107
Continued on back.

F0013

04/2005

ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans Delta Digital Controls SLR-835BH-DDC baseless
photoelectric smoke detectors. The combination detector head shall be UL listed compatible with an UL listed fire alarm
panel.
The smoke detector shall have flashing status LED for visual supervision. When the detector is actuated, the flashing
LED will latch on steady at full brilliance. The detector may be reset by actuating the control panel reset switch.
The detector shall have a sensitivity window verification feature.
The vandal resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking
feature shall be field selectable.
It shall be possible to perform a functional test of the detector without the need of generating smoke. The method shall
simulate effects of products of combustion in the chamber to ensure testing of detector circuits.
Voltage and RF transient suppression techniques shall be employed to minimize false alarm potential.

WIRING DIAGRAMS
2-Wire Wiring Diagram

U.L. Listed
Compatible
Control
Panel

Listed
End-of-Line
Device

4-Wire Wiring Diagram


Listed
End-of-Line
Device

U.L. Listed
Control
Panel

U.L. Listed
Power
Supply
*24VDC

24VDC 12VDC

NO

24VDC 12VDC

NO

Listed
End-of-Line
Relay
12 or 24VDC

U.L. Listed
Power
Supply
*12VDC

* Use either 12 OR 24VDC . They cannot be used simultaneously.

Delta Digital Controls SLR-835B-DDC DIRECT-WIRE PHOTOELECTRIC HEAT SMOKE DETECTOR

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
FM Approved

SZA-NA(FM)-DDC HIGH SENSITIVITY SMOKE DETECTION


SYSTEM
DESCRIPTION
The Delta Digital Controls SZA-NA(FM)-DDC high sensitivity
smoke detection system is capable of detecting minute
particles of smoke. The SZA-NA(FM)-DDC is ideal for
applications where response time is critical. It provides the
earliest response to fires available. The SZA-NA(FM)-DDC
provides a detection solution for rooms with high air flow,
and rooms with large open spaces.

SPECIFICATIONS
STANDARD FEATURES
Detects very low density smoke
200 m2 detection area (2150 ft2)
No filter necessary
N/O or N/C alarm contacts form A, form B
Automatic and manual laser tests
Four selectable sensitivity ranges:
*Sensitivity 1: 0.005 to 0.1%/m (0.002 to 0.03%/ft)
*Sensitivity 2: 0.01 to 0.2%/m (0.003 to 0.06%/ft)
*Sensitivity 3: 0.025 to 0.5%/m (0.008 to 0.15%/ft)
*Sensitivity 4: 0.25 to 5.0%/m (0.08 to 1.55%/ft)
3 alarm levels:
*Alarm 1 (low)
*Alarm 2 (medium)
*Alarm 3 (high)

Power Supply
24 VDC 10% 0.5A or less
Current Output
4-20mA DC output (Receiving resistance: 100 ohm or less)
Contact Output
Alarm 1 output, Alarm 2 output , Alarm 3 output,
& System Fault output
Contact Capacity
24 VDC, 0.5A or less (each contact output)
Contact Output Logic
NO (form A) or NC (form B) selectable
by a jumper pin
AC Power Supply Monitoring Input
NO (form A) or NC (form B) selectable
by system setting
Internal Wiring
Heat-resistance shielded wires
Materials
Body & panel: Steel plate of 0.8 mm thick, baked painting
Display operating panel: Steel plate of 1.0 mm thick
Colors
Body & panel:
Munsell 2.5Y9/1 or equivalent
Display operating panel: Munsell 5Y6/0.5 or equivalent
Weight
Approximately 8.2 lbs. (3.7kg.)
Dimensions
12.48" W x 8.86" H x 4.00" D
317mm x 225mm x 102mm

Exploded View of Front Panel

PRODUCT LISTINGS

Operating Temperature 14F to 122F


(-10 C to +50 C)

Installation
Accessory

Indoor (Non-condensing)
Dedicated flexible pipe

3026973
Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.

F0013

04/2005

OPERATION
An aspirating smoke detection system continuously draws air from the monitored area into the sampling pipes. The air
is drawn from the sampling pipes into the main sampling unit. In the main sampling unit, the air is analyzed by very
sensitive laser detection components. The laser detection components constantly monitor for the presence of smoke
particles.
If smoke particles are detected, the unit will activate the alarm output relays in accordance with the sensitivity selected
and the alarm level reached. The SZA-NA(FM)-DDC High Sensitivity Smoke Detector is between 20 and 1000 times
more sensitive than spot-type smoke detectors. The SZA-NA(FM)-DDC has three alarm stages. Alarm 1 is the lowest
obscuration alarm (high sensitivity), activating when very small amounts of smoke are detected. The Orange Alarm 1
LED will light, and the Alarm 1 relay will activate. As the smoke density reaches alarm level 2, the Red Alarm 2 LED will
light and Alarm 2 relay will activate. As the smoke density reaches alarm level 3, the Red Alarm 3 LED will flash and the
Alarm 3 relay will activate.
The SZA-NA(FM)-DDC is ideal for use in areas such as computer server rooms, clean rooms, telecommunication
equipment rooms, medical equipment/operating rooms, power generation plants, and many other applications. By
continuously sampling the area, the SZA-NA(FM)-DDC can provide the earliest warning of the presence of smoke, even
before the smoke is visible to the human eye.

1
2
3
1 Relay Connections 2 Jumpers (N/O or N/C)
4 Fan Unit
5 Laser Unit and Air Flow Sensor

TERMINAL BLOCK

Delta Digital Controls SZA-NA(FM)-DDC HIGH SENSITIVITY SMOKE DETECTION SYSTEM

4
3 Programming Display
6 24 VDC Fuse

MOUNTING

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed, FM Approved

DH-98-DDC CONVENTIONAL DUCT DETECTOR


STANDARD FEATURES

Duct housing is available with either a conventional


photoelectric or ionization detector.

SPECIFICATIONS
Duct Detector Model #

DH-98-I-DDC

DH-98-P-DDC DH-98-HVI-DDC DH-98-HVP-DDC

Operating Voltage

115V AC,
24V AC/DC

115V AC,
24V AC/DC

230V AC,
24V AC/DC

230V AC,
24V AC/DC

Detector Head Model

SIJ-24DH-DDC

SLR-24DH

SIJ-24DH-DDC

SLR-24DH

Detector Head Type

Conventional
Ionization

Conventional
Photoelectric

Conventional
Ionization

Conventional
Photoelectric

Power Requirements
Standby

8mA

230 VAC
115 VAC

14mA

8mA

14mA

24 VAC

20mA

20mA

20mA

20mA

24 VDC

13mA

13mA

13mA

13mA

15mA

15mA

115 VAC

28mA

28mA

24 VAC

95mA

95mA

95mA

95mA

24 VDC

60mA

60mA

60mA

60mA

Alarm Contacts

1 form "C" and


1 form "A" rated
at 10 amps @
115 V.A.C.

1 form "C" and


1 form "A" rated
at 10 amps @
115 V.A.C.

1 form "C" and


1 form "A" rated
at 10 amps @
115 V.A.C.

1 form "C" and


1 form "A" rated
at 10 amps @
115 V.A.C.

Detection Loop

1 Form A (1A)

1 Form A (1A) 1 Form A (1A)

Power Requirements
Alarm

230 VAC

Trouble Contacts
Sensitivity Test Method

1 Form "C"

1 Form "C"

1 Form "C"

Dual Reed
Switch Test

Self Diagnostic
Test

Dual Reed
Switch Test

Self Diagnostic
Test

Remote Indication Capability


Power, Alarm, Power, Alarm, Power, Alarm,
(Refer to DH-98-DDC
Horn/Piezo,
Horn/Piezo,
Horn/Piezo,
Accessories Data Sheet for
Test
Test
Test
Specifications)
Air Velocity

1 Form A (1A)

1 Form "C"

Power, Alarm,
Horn/Piezo,
Test

300 to 4000 ft./min

Ambient Temperature

32F to 120F (0C to 49C)

Humidity

10% to 85% Relative Humidity (non-condensing)

Housing Material

18 G.A. steel backbox, clear plastic cover

Finish

Grey Paint

Dimensions

9 1/8"L X 7 1/4"W X 2 1/4"H

Maximum Net Weight

3 lbs.

Sampling Tubes

2.5 ft., 5 ft. or 10 ft.

Radioactive Element

DH-98-I-DDC and DH-98-HVI-DDC Only:Americum 241 0.5 Mirco-Curie

Detects and limits the spread of smoke throughout


building HVAC ducts
Ability to interconnect (all relays operate wth a single
alarm) up to 30 units using the same independent
power supply
Compatible with building automation and fire
alarm systems
Installs quickly and easily
Interchangeable Plug-In photoelectric or
ionization heads
No screens or filters to clean
Cover provides magnet window and
placement guide for operational testing without
disassembly
Rugged gray steel back box with clear cover
Accessories - Remote power, remote alarm
indication capability and remote, horn/piezo
capability
Meets UL 268A Requirements

DESCRIPTION
The DELTA DIGITAL CONTROLS DH-98-DDC Duct Smoke
Detector provides early detection of smoke and products of
combustion present in air moving through HVAC ducts in
Commercial, Industrial and Residential applications. The DH98-DDC is designed to prevent the recirculation of smoke
in areas by the air handling systems, fans and blowers.
Complete systems may be shut down in the event of smoke
detection. The DELTA DIGITAL CONTROLS DH-98-I-DDC
and the DH-98-P-DDC operate on 115 VAC, 24 VAC and
24 VDC and the DH-98-HVI-DDC and the DH-98-HVP-DDC
operate on 230 VAC, 24 VAC and 24 VDC.
The DH-98-DDC is designed and built to meet all local
requirements, as well as the NFPA regulations regarding
duct smoke detectors. Output terminals are provided for
remote accessories such as a horn, strobe, remote status
indicators and reset key switches or push buttons.

PRODUCT LISTINGS
Underwriters Laboratories: S1383
CSFM #: 3240-0410:155
FM #: 3005751

Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.

F0013

04/2005

PRODUCT DESCRIPTION,

continued

Air sampling is accomplished by two tubes which protrude into the duct. An exhaust tube of one standard length (7.5")
is supplied in the installation kit with the smoke duct unit. Once the duct width has been determined the air intake
sampling tubes must be ordered. Sampling tubes are supplied in three standard lengths 2.5 ft., 5 ft. and 10 ft. and cut to
size to fit the duct. Mounting the duct smoke unit is accomplished by the use of a template and 4 sheet metal screws,
which are provided. Mounting can be achieved without the removal of the clear cover which is secured by 4 capture
screws.
The compact DH-98-DDC contains 3 sets of alarm contacts, 1 set of form C contacts rated at 10 amps, 1 set of form
A contacts rated at 10 amps, 1 set of form A contacts rated at 1 amp. There is also 1 set of form C 10 amp trouble
contacts for monitoring detector head removal, and the failure of the input supply voltage.
The pilot and alarm visual indicators provided on the front of the DH-98-DDC duct unit, signal the operating status of the
device. A manual test/reset switch is located along side the visual indicators. This switch can be defeated by cutting a
jumper on the PCB.

ENGINEERING SPECIFICATIONS
Air duct smoke detectors shall be DELTA DIGITAL CONTROLS DH-98-DDC Series. The detectors shall be listed by
Underwriters Laboratories per UL 268A. The detectors shall operate at air velocities from 300 feet per minute to 4000 feet
per minute.
The detectors shall have the ability to interconnect up to 30 units using the same independent power supply.
The duct detector housings shall be of metal construction and complete mechanical installation may be performed
without removal of detector cover. Visual indication of alarm and power must be provided on detector front. A manual
reset switch shall be located on front of the device. Detector heads shall not require additional filters or screens which
must be maintained. The housing shall contain a detector base which will accept photoelectric or ionization detector
heads. Terminal connections shall be of the screw type and be a minimum of # 6 screw. Terminals shall be provided for
remote pilot, remote alarm indication, strobe/horn and remote key switch. All wiring must comply with local codes and
regulations.
See
Power
Connections

WIRING DIAGRAMS
1

ALARM
CONTACTS
10.0A @ 115VAC

ALARM
CONTACTS
1A @ 24VDC

10

11

12

*TROUBLE
CONTACTS
10.0A @ 115VAC

13

14

15

17

18

19

20

24 VDC 60 Hz INPUT
@ 0.1 AMP MAX.(Detector only).
UP TO 1.9 AMPS FOR AUXILIARY
OUTPUTS (HORNS/STROBES).

24 VAC 60 Hz INPUT
@ 0.1 AMP MAX.(Detector only).
UP TO 1.9 AMPS FOR AUXILIARY
OUTPUTS (HORNS/STROBES).

16

*Trouble contacts are shown in non-energized


condition. Trouble contacts monitor power
connected and head removed.

DH-98 DUCT SMOKE DETECTOR

REMOTE
ACCESSORIES

DH-98-I
DH-98-P

DH-98-I
DH-98-P

24 V.A.C. OPERATION

24 V.D.C. OPERATION

115 VAC 60 Hz INPUT


@ 0.1 AMP MAX.

230 VAC 60 Hz INPUT


@ 0.1 AMP MAX.

DH-98-I
DH-98-P

DH-98-HVI
DH-98-HVP

115 V.A.C. OPERATION

230 V.A.C. OPERATION

INTERCONNECT WIRING DIAGRAMS


DUCT UNIT #1

INPUT
POWER

Input Power Source


Will Be Either
24V, 115V or 230V

DUCT UNIT #2

DUCT UNIT #3

P
P

16

16

16

18

18

18

Delta Digital Controls DH-98-DDC CONVENTIONAL DUCT DETECTOR

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products

DH-98-DDC DUCT DETECTOR REMOTE ACCESSORIES


APPLICATION

SPECIFICATIONS

The DH-98-DDC Duct Detector Remote Accessories


are designed to be used with the DH-98-DDC
Conventional and DH-98-DDC Analog Duct Detectors
to provide audible and visual indication as well as
remote test/reset functions.

Power Requirements
Alarm LED
Pilot LED
Horn
Sound Pressure
Horn
Dimensions
Single Gang

These devices are contructed of brushed stainless


steel and mount on a standard single or double gang
backbox.

Double Gang

ALARM

ALARM

TEST/RESET

ALARM

PILOT

MS-RA
Functions:
Remote Alarm LED (red)
For Use with:
DH-98-DDC-I, DH-98-DDCP
DH-98-DDC-HVI, DH-98DDC-HVP
DH-98-A-DDC, DH-98-ARDDC

MS-KA/R
Functions:
Remote Alarm LED (red)
Key-Operated Test/Reset
Switch
For Use with:
DH-98-DDC-I, DH-98-DDC-P
DH-98-DDC-HVI, DH-98DDC-HVP
DH-98-AR-DDC
MS-RA/P
Functions:
Remote Alarm LED (red)
Pilot LED (green)
For Use with:
DH-98-DDC-I, DH-98-DDC-P
DH-98-DDC-HVI, DH-98DDC-HVP

ALARM

PILOT

TEST/RESET

ALARM

TEST/RESET

ALARM

PILOT

TEST/RESET

Specifications subject to change without notice.

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

15 mA
15 mA
20 mA @ 24 VDC
78 db @ 10 feet
2.75" (69.85mm) W
4.5" (114.3mm) H
4.5" (114.3mm) W
4.5" (114.3mm) H

MS-KA/P/R
Functions:
Remote Alarm LED (red)
Pilot LED (green)
Key-Operated Test/Reset
Switch
For Use with:
DH-98-I-DDC ,
DH-98- DDC-P,
DH-98-DDC-HVI,
DH-98-DDC-HVP
MS-RA/R
Functions:
Remote Alarm LED (red)
Push-button Test/Reset
Switch
For Use with:
DH-98-DDC-I,
DH-98-DDC-P
DH-98-DDC-HVI,
DH-98-DDC-HVP
DH-98-AR-DDC
MS-RA/P/R
Functions:
Remote Alarm LED (red)
Pilot LED (green)
Push-button Test/Reset
Switch
For Use with:
DH-98-DDC-I,
DH-98-DDC-P
DH-98-DDC-HVI,
DH-98-DDC-HVP

Continued on back.

F0013

04/2005

MS-RH/KA/P/R
Functions:
Remote Alarm Horn
Remote Alarm LED (red)
Pilot LED (green)
Key-Operated Test/Reset
Switch
For Use with:
DH-98-DDC-I, DH-98-DDC-P
DH-98-DDC-HVI, DH-98-DDC-HVP

ALARM

PILOT

TEST/RESET

WIRING DIAGRAM
RED
RED
RED
24VDC

ALARM

ALARM

GREEN
24VDC

HORN

PILOT
LED

LED
BLACK

BLACK

ALARM

PILOT

BLACK

KEY OR
24VDC

PUSH BUTTON
"TEST/RESET"
SWITCH

BLACK

TEST/RESET

PRODUCT SPECIFICATIONS
PUSH
KEY
PILOT ALARM BUTTON OPERATED
TEST/
TEST/
LED
LED
RESET
RESET
(GREEN) (RED)

HORN

SINGLE
GANG

DOUBLE
GANG

MODEL #
MS-RA
MS-RA/P
MS-RA/R
MS-RA/P/R
MS-KA/R
MS-KA/P/R
MS-RH/KA/P/R

Delta Digital Controls DH-98-DDC DUCT DETECTOR REMOTE ACCESSORIES

Specifications subject to change without notice.

Delta Digital Controls


Fire Alarm Products
UL Listed, FM Approved

DH-98-DDC ANALOG DUCT DETECTOR


STANDARD FEATURES
Detects and limits the spread of smoke
throughout building HVAC ducts.

Compatible with building automation and fire

alarm systems.
Installs quickly and easily.
No screens or filters to clean.
Rugged gray steel back box with clear cover.
Accessories - Remote LED alarm
indication capability.
Meets UL 268A Requirements.

APPLICATION
Duct housing with an ALG-DH analog
photoelectric sensor.

SPECIFICATIONS
D uct Detector Model #

DH-98-A-DDC

DH-98-AR-DDC

ALG-DH

Detector Head model


Detector Head Type

Analog Photoelectric

Communication

DCP Powered Loop

DCP Powered Loop

DCP Powered Loop/


24V DC

2mAAVG

10mA

Alarm Current

8mA

55mA

Alarm Contacts

N/A

Input Voltage
Standby Current

2 form C rated at
10A@250V AC
Control Panel

Sensitivity Test Method


Remote Indication Compatibility
(Refer to DH-98-DDC Accessories)

Alarm

Power,Alarm,
Horn/Piezo
Test

Air Velocity

300 to 4000 ft/min.

Ambient Temperature

32F to 120F (0C to 49C)

Humidity

10% to 85% Relative Humidity


(non-condensing)

Housing Material

18 G.A. steel backbox, clear plastic cover

Finish

Grey Paint

Dimensions

91/8"L x 71/4"W x 21/4"H

Maximum Net Weight

3lbs.

Sampling Tubes

3ft., 5ft. or 10ft.

Specifications subject to change without notice.


Specifications subject to change without notice.

The DELTA DIGITAL CONTROLS DH-98-DDC Analog


duct smoke detector provides early detection of smoke
and products of combustion present in air moving through
HVAC ducts in Commercial, Industrial and Residential
applications. The DH-98-DDC is designed to prevent the
recirculation of smoke in areas by the air handling
systems, fans and blowers. Complete systems may be
shut down in the event of smoke detection. The DELTA
DIGITAL CONTROLS DH-98-A-DDC and the DH-98-ARDDC operate on a DCP powered loop (24 VDC source
required for DH-98-AR-DDC)

PRODUCT DESCRIPTION
The DH-98-DDC is designed and built to meet all local
requirements, as well as the NFPA regulations regarding duct smoke detectors. Output terminals are provided for remote accessories such as a horn, strobe,
remote status indicators and reset key switches or
push buttons. Air sampling is accomplished by two
tubes which protrude into the duct. An exhaust tube
of one standard length (7.5") is supplied in the installation kit with the smoke duct unit. Once the duct
width has been determined the air intake sampling
tubes must be ordered. Sampling tubes are supplied
in three standard lengths 3 ft., 5 ft. and 10 ft. and cut
to size to fit the duct.

PRODUCT LISTINGS
Underwriters Laboratories: S1383
CSFM #: 3240-0410:155
FM #: 3022559
MEA Report#: 284-91-E Vol. V

Delta Digital Controls


1291 W. State Fair, Suite B200 Detroit, MI 48203
Phone: +1 586 884 6993 Fax : +1 586 323 0182
E-mail : info@deltadigitalcontrols.com, Web:www.deltadigitalcontrols.com

Continued on back.
Continued on back.

F0013

04/2005

PRODUCT DESCRIPTION,

continued

Mounting the duct smoke unit is accomplished by the used of a template and 4 sheet metal screws, which are provided.
Mounting can be achieved without the removal of the clear cover which is secured by 4 capture screws.
The compact DH-98-AR-DDC contains 2 sets of form "C" contacts rated at 10 amps.
The pilot and alarm visual indicators, provided on the front of the DH-98-AR-DDC duct unit, signal the operating status of
the device. A manual test/ reset switch is located along side the visual indicators.

ENGINEERING SPECIFICATIONS
Air duct smoke detectors shall be DELTA DIGITAL CONTROLS DH-98-DDC Series. The detectors shall be listed by
Underwriters Laboratories per UL 268A. The detectors shall operate at air velocities from 300 feet per minute to 4000 feet
per minute.
The duct detector housings shall be of metal construction and complete mechanical installation may be performed
without removal of detector cover. The duct detector shall not require additional filters or screens which must be maintained.
The housing shall contain a base which will accept an analog photoelectric sensor head. Terminal connections shall be
of the screw type and be a minimum of #6 screw. For installations requiring relay function, terminals shall be provided for
remote pilot, remote alarm indication, strobe/ horn and remote key switch. For installation not requiring relay function,
visual indication of alarm and power must be provided on detector front. A manual reset switch shall be located on front
of the device. All wiring must comply with local codes and regulations.

WIRING DIAGRAMS
DH-98-A-DDC

ALG-DH ANALOG
SENSOR
1

3
(-)

LOOP INTERFACE

UL LISTED
CONTROL PANEL

Note

4
(+) REMOTE ALARM LED WIRING MUST
HAVE POLARITY AS SHOWN
24 VDC (8mA MAX.)

S (+)

The DH-98-A-DDC and


DH-98-AR-DDC are not
self-contained sensors. This
product is compatible only
with fire alarm control panels that utilize Delta Digital
Controls's Digital Communications Protocol, DCP. For example the FireNET Control
Panel.

TO NEXT
SENSOR

SC (-)

FAN SHUT DOWN EXAMPLE

DH-98-AR-DDC

OBSERVE POLARITY
INPUT VOLTAGE
24 V.D.C.
10 mA Standby
55mA Alarm

ADDRESSABLE
LOOP

4
-

REMOTE
ALARM
LED
+
5
6
+

REMOTE
PILOT LED

LOOP INTERFACE

UL LISTED
CONTROL PANEL

FAN

SUPPLY VOLTAGE

8
NC

9
NO

ALARM CONTACTS
10.0A @ 250VAC

11

10
NC

12
NO

ALARM CONTACTS
10.0A @ 250VAC

REMOTE TEST
SWITCH

(Test function only. does not reset.)

S (+)
ANALOG ADDRESSABLE
FIELD LOOP WIRING

SC (-)

TO NEXT SENSOR
OR RETURN
TO CONTROL PANEL

Terminate Remote Accessories as indicated above (if required).


This is not a self-contained stand alone detector.
A U.L. Listed Analog Addressable Fire System is required.

Delta Digital Controls DH-98-DDC ANALOG DUCT DETECTOR

Specifications subject to change without notice.