4008-9101/4008-9121
Fire Alarm Control Panel
Installation,
Programming,
and Operating
Instructions
579-716
Rev A
FCC Information
This equipment complies with Part 68 of the FCC rules and the requirements adopted by the ACTA. On the door of this equipment is a label that contains, among other information, the following product identifier: US:5QWAL01B4008. If requested,
the number must be provided to the telephone company.
In the event of equipment malfunction, all repairs should be performed by an authorized agent. It is the responsibility of users
requiring service to report the need for service to our company or to one of our authorized agents. Service can be arranged
through our office at:
Tyco Safety Products
91 Technology Drive
Westminster, MA 01473
978-731-2500
The Ringer Equivalence Number (REN), which is 01 for the DACT installed in this panel, is used to determine the number of
devices that may be connected to a telephone line. Excessive RENs on a telephone line may result in the devices not ringing in
response to an incoming call. In most, but not all areas, the sum of RENs should not exceed five (5.0). To be certain of the
number of devices that may be connected to a line, as determined by the total number of RENs, contact the local telephone
company. For products approved after July 23, 2001, the REN is part of the product identifier, which uses the format
US:AAAEQ##TXXXX. The digits represented by ## are the REN without a decimal point (e.g. 01 is a REN of 0.1).
If the DACT causes harm to the telephone network, the telephone company will notify you in advance that temporary discontinuance of service may be required. But if advance notice isnt practical, the telephone company will notify you as soon as
possible. If your service is discontinued, you will be advised of your right to file a complaint with the FCC.
The telephone company may make changes to its facilities, equipment, operations, or procedures that could affect the operation of the equipment. If this happens the telephone company will provide advance notice in order for you to make the necessary modifications to maintain uninterrupted service.
If trouble is experienced with the DACT, please contact Tyco Safety Products at the location identified above. If the equipment
is causing harm to the telephone network, the telephone company may request that you disconnect the equipment until the
problem is resolved.
Alarm Dialing Equipment
This equipment must be able to seize the telephone line and place a call in an emergency situation. It must be able to do this
even if other equipment (telephone, answering system, computer modem, etc.) already has the telephone line in use. To do so,
the DACT must be electrically in series with and ahead of all other equipment attached to the same telephone line. Proper
installation is depicted in the figure below. If you have any questions concerning these instructions you should consult your
telephone company or a qualified installer about connecting the alarm dialing equipment for you.
Computer
DACT
Network
Service
Provider's
Facilities
Unused
RJ-11 Jack
Telephone
Line
Telephone
Network
Demarcation
Point
Telephone
Unused
RJ-11 Jack
Fax
Answering
System
Telephone
Connectors for the DACT are terminal blocks on the DACT module. Refer to DACT Wiring in Chapter 2 of this manual for
specific DACT wiring instructions.
ELECTRICAL HAZARD - Disconnect electrical field power when making any internal adjustments or repairs. Servicing
should be performed by qualified Simplex Technical Representatives.
STATIC HAZARD - Static electricity can damage components. Therefore, handle as follows:
RADIO FREQUENCY ENERGY - This equipment generates, uses, and can radiate radio frequency energy and if not installed
and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and
found to comply with the limits for a Class A computing device pursuant to Subpart J of Part 15 of FCC Rules, which are
designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of
this equipment in a residential area may cause interference in which case the user at his own expense will be required to take
whatever measures may be required to correct the interference.
SYSTEM REACCEPTANCE TEST AFTER SOFTWARE CHANGES - To ensure proper system operation, this product must
be tested in accordance with NFPA72-2002 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or
adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In
addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly
affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
Table of Contents
Chapter 1. Overview
The 4008-9101 and 4008-9121 (includes door mounted annunciator) are
addressable fire alarm control panels capable of monitoring and controlling up to 200 initiating devices on an addressable communications circuit (IDNet). The single-board system and cabinet provide a complete
fire alarm for most applications.
In cases where the installation, wiring, or programming procedure is
identical for both panels, the term 4008 is used. If the procedure applies
only to a specific panel, the complete product name (i.e., 4008-9121 is
used).
The 4008 provides audible and visible indications during alarm, supervisory, or trouble conditions. Should any of these conditions occur, the
system activates the applicable notification appliances, LEDs, and the
panels tone-alert. The indications continue until an operator acknowledges the condition.
The 4008 base system includes the Main System Board (MSB) mounted
in a steel enclosure with locking door. The MSB consists of:
IDNet loop
Service port
DACT
The following optional modules mount to the chassis, providing additional capability.
Zone LED Annunciator displays alarm & trouble status for each
logical zone.
1-1
In This Chapter
Optional Modules . . . . . . . . . . . . . . . . . . . . . . .1-2
Initiating Devices . . . . . . . . . . . . . . . . . . . . . . .1-3
Programming Overview . . . . . . . . . . . . . . . . . .1-4
Chapter 1. Overview
9805 provides disconnect switches for each circuit. Model
4006-9805 must be used for Canadian applications. The City
Circuit must be enabled via the panels System Options
before use.
Specification
120 VAC, 60 Hz, 4A;
240 VAC, 50 Hz, 3A
Power Supply
Environmental
ANNUNCIATOR MODULES
Optional Modules
Zone 1
Z one 5
Z one 9
Zone 2
Z one 6
Zone 10
Zone 3
Z one 7
NAC 1
NAC 2
NAC 3
Zone 4
Z one 8
NAC 4
Figure 1-1
1-2
Yellow Trouble
Chapter 1. Overview
-
DETECTOR MODULES
Tone-Alert
Z ONE 9
ZONE 2
ZONE 10
Alarm
S ilence
Z ONE 3
ACK
Alarm
S ilenced
Comm Los t
Z ONE 4
ZONE 5
R eset
T rouble
L amp
T est
Power
CONTROL
ENABLE
Z ONE 6
ZONE 7
Z ONE 8
Figure 1-2
The base version of the NAC Extender is a single-board system consisting of four NACs, a power supply and charger,
and two conventional NAC inputs that connect to the host
panel for hardwired control of the NAC extender.
Initiating Devices
The 4008 is compatible with the following addressable initiating devices. Up to 200 devices (any combination) are
allowed in the system.
1-3
Chapter 1. Overview
-
It is recommended that you use the automatic programming option to perform the following tasks.
MONITOR MODULES
The 4099-9001 (single action) and 4099-9002/40999003 (dual action) addressable pull stations are latching
pull stations that can be reset with a key. They are a linepowered device, consuming one address.
CONTROL MODULES
System Options
System options are pre-defined modes of operation with a
range of settings from which to choose. System Options
define global operations such as the time and date format,
door drop timers, and whether the city circuit is enabled, etc.
System options can be set during either the automatic manual programming process.
Programming Overview
A job refers to the file containing all of the panels programming information. A job (also called a CFIG file) can be programmed in one of two ways.
Alarm Groups
Alarm groups allow you to implement basic selective signalling applications. As you program input (smoke detectors,
monitor zones) and output points (NAC, signal zone, relay),
you are given the opportunity to associate the point with an
alarm group number. The number can range from 1-10 and
each point can be in up to three alarm groups. When programming is complete, an initiating device can only trigger
the output devices (relays, NACs) that share its alarm
group(s).
Single Station Operation
Single Station is a mode of operation that applies to IDNet
devices that use a sounder base (the sensor can be either
photo, heat, or combination photo/heat).
1-4
Chapter 1. Overview
Table 1-1 Operator Keys
Photo and heat sensors mounted on sounder bases can be
installed and programmed to act as single station smoke
detectors. The sounder activates when the smoke or heat
sensor crosses its alarm threshold and turns off when the
smoke level goes below its threshold. (A general alarm fire
condition also occurs when the detector goes into alarm.)
Key
Function
TROUBLE
ACK
ALARM
SILENCE
User Interface
The user interface consists of control keys, LEDs, a 2-line
by 20-character, backlit LCD, and a sounder mounted in the
control panel. The purpose of the Operator and Menu keys is
listed below.
SYSTEM
RESET
Figure 1-3
User Interface
MENU
FUNCTION
DISABLE/
ENABLE
Function
ALARM
ACK
SUPV
ACK
1-5
Chapter 1. Overview
Table 1-1 Operator Keys
Key
Function
EXIT/
CLEAR
ENTER
RIGHT/LEFT
ARROWS
PREVIOUS/
NEXT
4
Passcode =
4000
2.
Press <MENU>
3.
4.
2
Passcode =
2000
Certain operator functions are passcode-protected at different levels. This section describes the operator functions,
their default access level, and the login/logout procedure.
3
Passcode =
3000
Login/Logout Procedure
Access
Level
Operation
Operation
Acknowledge, Silence, System Reset,
View Historical Logs, Lamp Test
View Point Information,
[0]
5.
6.
1-6
In This Chapter
Nine knockouts are provided for conduit connection. Refer to Figure 2-1 for knockout locations.
AC power (non-power limited) wiring must be run in separate conduit from all other wiring, as shown in Figure 2-1. Non-power limited wiring must be separated from power limited wiring by a
minimum of 1/4".
TB1
TB2
TB3
Expansion
Power Supply
City Connect
Module
AC Voltage
Connection
DACT
Battery
Connection
Battery
Battery
2-1
1.5
Figure 2-3
Surface Mounting
Testing Procedure
11.250
1.
2.
13.500
16.000
13.250
15.632
Figure 2-2
Semi-Flush Mounting
Semi-Flush Mounting
Semi-flush mounting involves recessing the cabinet into a
wall and attaching it directly to the wall's studs. At a minimum, 1.5 inches of the cabinet must protrude from the wall
to allow for clearance of the panel door.
2-2
IDNet Wiring
Wire all addressable detectors to B+ and B- terminals. Do not return wiring to A+/A- terminals.
Conductors must test free of all grounds and stray voltages before connection to appliances and panel.
Maximum wiring capacitance is .58uF total. Maximum wiring resistance to any device is 52 ohms.
Refer to installation instructions packed with addressable detectors for information on wiring detectors to
IDNet channel.
10, 000 feet total cable load (max.) allowed. Resistance and capacitance limits must be observed.
To achieve maximum wiring distance, use low capacitance wire, 29 pF/Foot or lower. If shielded wire is used,
be sure to consider shield to conductor capacitance.
Note: If wiring
Class B, do not
return wiring to A+/
A- terminals.
See Ferrite
Bead on next
page for information on looping TB
2-1 and TB 2-2
through Ferrite
bead.
CLSB
4008
OR
UNIMMODEAE
OR
2008
TB1
200DEVICE
12-18AWG
250mA@35V
Compatible Bases:
S
H
I
E
L
D
CLSA
TB2
1 2 3 4 5 6 7 8
TB3
1 2 3 4 5
1 2 3 4 5 6 7 8
MAINSYSTEMBOARD-ADDRESSABLE(MSB-A)
Figure 2-4
IDNet Wiring
2-3
Class A ZAM
Class B ZAM
Supervised IAM
Relay IAM
Figure 2-5
Ferrite Bead
Base(s)
Max. #
Devices
4098-9685
N/A
20
4098-9612 to 9615
4098-9788, -9683,
-9684
20
4098-9601, -9602,
-9605
4098-9788, -9683
20
Base(s)
Max. #
Devices
4098-9612 to 9615
4098-9682 (See
below for wiring.)
20
4098-9601, -9602,
-9605
4098-9682 (See
below for wiring.)
20
24 VDC power
from listed FACP
2098-9735
(RELAY SHO WN
ENERGIZED)
E.O.L. RELAY
RED
4090-9101
ZAM
24VDC
BLACK
Figure 2-6
2-4
YELLO W
YELLO W
END-OF-LINE DEVICE
SELECTED PER ZONE
CIRCUIT
The following guidelines and restrictions apply to notification appliance circuits (NACs) located on either the main
system board (MSB) or on the Expansion Power Supply
(EPS).
Conductors must test free of all grounds and stray voltages before connection to appliances and panel.
When using two-wire audible/visible appliances, maximum wiring capacitance of .22 uF must be considered.
Maximum Wiring Distance in Feet
When using the following SimplexMulti-Candela appliances, each NAC is rated for 2A max.
- 4906-9101
- 4906-9102
- 4906-9103
- 4906-9104
- 4906-9127
- 4906-9128
- 4906-9129
- 4906-9130
- 4906-9151
- 4906-9153
- 4906-9154
Alarm
Current
(Amps)
18
AWG
16
AWG
14
AWG
12
AWG
Line
Resistance
(Ohms)
.25
840
1335
2126
3382
12
.50
420
667
1063
1691
.75
280
445
709
1127
1.0
210
334
532
845
1.25
168
267
425
676
2.4
1.50
140
222
354
564
1.75
120
191
304
483
1.71
2.0
105
167
266
423
1.5
Terminate Class B (Style Y) NACs as shown using Simplex 733-894 (4081-9008) 10K 1/2 W resistor harness.
For Canadian applications, mount end-of-line resistor to
TEPG-US Model 431537 EOL plate in accordance with
ULC-S527.
Main
System
Board
2-5
EPS
NACs
TYPICALAUDIBLE/VISIBLEAPPLIANCES
NAC-
NAC-
NAC-
NAC+
NAC+
NAC+
NAC-
NAC-
NAC+
NAC+
B+
B-
TB2
TB1
1 2 3 4 5 6 7 8
TB3
1 2 3 4 5
1 2 3 4 5 6 7 8
MAINSYSTEMBOARD-ADDRESSABLE(MSB-A)
Figure 2-7
TYPICALAUDIBLE/VISIBLEAPPLIANCES
NAC-
NAC-
NAC-
NAC+
NAC+
NAC+
733-894
10K, 1/2W
EOLR
NAC-
NAC-
NAC+
NAC+
B+
BA+
A-
TYPICALAUDIBLE/VISIBLEAPPLIANCES
B+
B-
733-894
(10K, 1/2W
EOLR
B+
BA+
A-
TYPICALAUDIBLE/VISIBLEAPPLIANCES
TB1
1 2 3 4 5 6 7 8 9 10
EXPANSIONPOWERSUPPLYASSY.
NACMODULE
Figure 2-8
2-6
NAC ratings
The panel is rated Special Application for 2A maximum per
NAC with Simplex 4901 and 4906 TrueAlert & TrueAlert
Multi-Candela Notification Appliances.
30Cd
75Cd
110Cd
4906-
Rated
Current
Max. # per
NAC
Rated
Current
Max. #
per NAC
Rated
Current
Max. # per
NAC
Rated
Current
Max. # per
NAC
9101
0.060
33
0.094
21
0.186
10
0.252
9102
0.075
26
0.125
16
0.233
0.316
9103
0.060
33
0.094
21
0.186
10
0.252
9104
0.075
26
0.125
16
0.233
0.316
9127
0.075
26
0.116
17
0.221
0.285
9128
0.086
23
0.132
15
0.250
0.320
9129
0.075
26
0.116
17
0.221
0.285
9130
0.086
23
0.132
15
0.250
0.320
9151
0.060
33
0.094
21
0.186
10
0.252
9154
0.075
26
0.125
16
0.233
0.316
9153
0.060
33
0.094
21
0.186
10
0.252
2-7
Conductors must test free of all grounds and stray voltages before connection to appliances and panel.
N2COMMS
0VSHIELDCONN
(IFUSED)
TB1
TB3
1 2 3 4 5
1 2 3 4 5 6 7 8
MAINSYSTEMBOARD-ADDRESSABLE(MSB-A)
RAM
MSB
RAM
MSB
RAM
RAM
RAM
RAM
Wiring must pass through a ferrite bead. Wrap the wiring twice through the ferrite bead, as shown in
Figure 2-9.
Figure 2-9
TB2
1 2 3 4 5 6 7 8
Figure 2-11
Ferrite Bead
2-8
TB1
TB2
1 2 3 4 5 6 7 8
TB3
1 2 3 4 5
1 2 3 4 5 6 7 8
MAINSYSTEMBOARD-ADDRESSABLE(MSB-A)
DANGER
HIGHVOLTAGE
INTHISAREA
DACTTELEPHONE
CONNECTIONS
1 2 3 4 5 6 7 8
TB5
R T R T R T R T
I I I I I I I I
N P N P N P N P
G
G
G
G
LINE2TELCOSERVICEIN
WIRETOMODULARJACK
TOUSELINE1FOR
OTHERTELCOEQUIP.
WIRETOMODULARJACK
TOUSELINE1FOR
OTHERTELCOEQUIP.
LINE1TELCOSERVICEIN
Figure 2-12
DACT Wiring
2-9
Communication Format
FBII
CP220FB
Note 2, 3
Osbourne/
Hoffman
QuickAlert
II
ADEMCO
685
Note 1, 3
Surgard
MLR2-DG
Contact ID
Preferred
3/1 Standard
1800/2300 Hz
10 and 20PPS
3/1 Standard
1900/1400 Hz
10 and 20PPS
4/2 Standard
1800/2300 Hz
10 and 20PPS
4/2 Standard
1900/1400 Hz
10 and 20PPS
Radionics BFSK
1800/2300 Hz
Radionics BFSK
1900/1400 Hz
SIA
Radionics
D6600
Silent
Knight
9000
Silent
Knight
9500
Surgard
MLR2000
With 9032
Line Card
With 9032
Line Card
With 9032
Line Card
With 9032
Line Card
With 9032
Line Card
With 9032
Line Card
With 9004
Line Card
Notes:
1.
2.
3.
2-10
Conductors must test free of all grounds and stray voltages before connection to appliances and panel.
MSBAUX24V
1/2MAX.
TB1
TB3
TB2
1 2 3 4 5 6 7 8
1 2 3 4 5
1 2 3 4 5 6 7 8
MSBAUX24V
1/2MAX.
MAINSYSTEMBOARD-ADDRESSABLE(MSB-A)
EPS
POWERSUPPLYMODULE
Figure 2-13
2-11
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8
TB5
TB1
DACTTELEPHONE
CONNECTIONS
EXPANSIONPOWERSUPPLYASSY.
NACMODULE
DANGER
HIGHVOLTAGE
INTHISAREA
City module consists of two circuits that are jumperconfigured. Circuits may be configured for reversepolarity or local energy operation. See jumper setting
table for details. Modules must also be added to the system configuration. See System Options later in this
manual.
REVERSEPOLARITY
TB1
LOCALENERGY
TB3
TB2
1 2 3 4 5 6 7 8
1 2 3 4 5
1 2 3 4 5 6 7 8
MAINSYSTEMBOARD-ADDRESSABLE(MSB-A)
24VDCNORMAL
4mASUPERVISIONCURRENT
500mAMAX.ALARMCURRENT(PULSED)
15mAMAX.AT24VDC
INTENDEDFORCONNECTIONTOAPOLARITY
REVERSALCIRCUITOFAREMOTESTATION
RECEIVINGUNITHAVINGCOMPATIBLERATINGS
20.4V-28VDC,1/2p-pRIPPLE(MAX.)
CITYCONNECT
MODULE
INTENDEDFORCONNECTIONTOA14.5OHM
TRIPCOIL.
DACTTELEPHONE
CONNECTIONS
DANGER
HIGHVOLTAGE
INTHISAREA
MAXIMUMWIRINGRESISTANCE:4000OHMS
WITH2200OHMTRIPCOIL(6200OHMTOTAL)
POLARITYMARKEDONTERMINALSREFLECTS
THEALARMSTATE.
3A
FUSE
SW
3A
FUSE
SW
3 4
SEEDETAILA
P3
CKT1 CKT2
P5
10
LE 6
RP 4
P2
LE
RP
10
LE 6
RP 4
CITYCONNECT
MODULE
P4
P6
LE
RP
1
2
3
4
P6
1
2
3
4
P6SELECTSCITYCIRCUIT2OPERATION.
POS.1-2AND3-4FORCITY2TO
ACTIVATEONSUPERVISORYCONDITION
P5
P3
LE
RP
JUMPERPOSITIONS
REVERSEPOLARITY LOCALENERGY
CITY1
CITY2
P3:1-2,3-4,5-6
P2:2-3
P5:1-2,3-4,5-6
P4:2-3
P3:7-8,9-10
P2:1-2
P5:7-8,9-10
P4:1-2
LE
RP
P2
LE
RP
P4
LE
RP
POS.1-3FORCITY2TO
ACTIVATEONTROUBLECONDITION
3A
FUSE
3A
FUSE
SW
SW
1
DETAILA
Figure 2-14
2-12
P6
1
2
3
4
Conductors must test free of all grounds and stray voltages before connection to appliances, devices, and
panel.
Each relay is selected for normally-closed or normallyopen operation. Shunt jumper setting selects desired
contact.
AUX. TBL.
RELAY RELAY
J
U
M
P
E
R
TB1
TB3
TB2
1 2 3 4 5 6 7 8
C
E
N
T
E
R
1 2 3 4 5
1 2 3 4 5 6 7 8
JUMPER
CENTER
MAINSYSTEMBOARD-ADDRESSABLE(MSB-A)
JUMPERSTOSELECTNORMALLYOPEN
ORCLOSEDRELAYCONTACTS.
NORMALLYOPEN(JMPRLEFT)
NORMALLYCLOSED(JMPRRIGHT)
Figure 2-15
2-13
AC Supply Wiring
Wire LINE to the left terminal of TB4. Wire Neutral to the right terminal of TB4.
TB1
TB3
TB2
1 2 3 4 5
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
THEPOWERSUPPLYMODULE,PARTOFTHEEPS
ASSEMBLY,ISMOUNTEDBENEATHTHENACMODULE
PORTIONOFTHEEPSASSEMBLY.
MAINSYSTEMBOARD-ADDRESSABLE(MSB-A)
EPS
POWERSUPPLYMODULE
B+ B- A+ A-
NEUTRAL
B+ B-
LINE
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8
TB5
TB1
DACTTELEPHONE
CONNECTIONS
EXPANSIONPOWERSUPPLYASSY.
NACMODULE
DANGER
HIGHVOLTAGE
INTHISAREA
734-179
WIREACLINEANDNEUTRALASSHOWN.
HOTTOLEFTTERMINAL,NEUTRALTORIGHTTERMINAL.
WHITE
BLACK
WHITE/BLACKHARNESS734-179
FROMEPS(LOWERMODULES)
TOMAINSYSTEMBOARD.
Figure 2-16
AC Supply Wiring
2-14
Battery Wiring
The main battery harness connects the MSB to the battery set in the same cabinet.
The EPS connects to the battery header next to the battery harness described in the previous bullet. Install the
EPS red/black harness right-justified to the battery
header, with the black wire to the right.
1.
For 18 Ah batteries, the 4009-9801 external battery cabinet must be used. Mount the battery box within 20 feet
of the control panel, in accordance with the mounting
instruction label in the box. All interconnecting wiring
must be enclosed in conduit.
2.
3.
TB1
TB2
TB3
1 2 3 4 5
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
THEPOWERSUPPLYMODULE,PARTOFTHEEPS
ASSEMBLY,ISMOUNTEDBENEATHTHENACMODULE
PORTIONOFTHEEPSASSEMBLY.
MAINSYSTEMBOARD-ADDRESSABLE(MSB-A)
EPS
POWERSUPPLYMODULE
1 2 3 4 5 6 7 8
TB5
R B
E L
D K
1 2 3 4 5 6 7 8 9 10
DACTTELEPHONE
CONNECTIONS
TB1
EXPANSIONPOWERSUPPLYASSY.
NACMODULE
DANGER
HIGHVOLTAGE
INTHISAREA
3B+
3B3A+
3A4B+
4B4A4A24V
0V
734-180
ATTACHTOBATTERYCONNECTOR
RIGHT-JUSTIFIED,BLACKWIRETOTHERIGHT
BLACK
RED
R B
E L
D K
HARNESS734-180
FROMEPS(LOWERMODULES)
TOMAINSYSTEMBOARD
BATTERYCONNECTOR
CONNECTTO
BATTERYTERMINALS
(FUSEDONPCB)
Figure 2-17
Battery Wiring
2-15
Remove this
Jumper
NEUTRAL
Figure 2-18
+ BATT
+ EPS
FIRE
SUPV
TRBL
00
00
02
Figure 2-19
2-16
Batteries should be tested by discharging them with a suitable tester and verifying that battery voltage is at least 21V
when fully discharged. Battery discharge tests should be performed annually, and batteries should be replaced no longer
than 4 years from date of installation.
Corresponding LEDs
To create an open:
2-17
Temp
(C)
Temp
(F)
V/cell
(min)
V/cell
(max)
Min.
Battery
Voltage
Max.
Battery
Voltage
32
2.294
2.367
27.53
28.40
41
2.284
2.352
27.41
28.22
10
50
2.274
2.337
27.29
28.04
15
59
2.264
2.322
27.17
27.86
22.2
72
2.250
2.300
27.00
27.60
25
77
2.244
2.292
26.93
27.50
30
86
2.234
2.277
26.81
27.32
35
95
2.224
2.262
26.69
27.14
40
104
2.214
2.247
26.57
26.96
45
113
2.204
2.232
26.45
26.78
49
120.2
2.196
2.220
26.36
26.64
Chapter 3. Auto-Programming
The Auto-Program option provides the ability to quickly and automatically program the panels components and features for general alarm
operation. It automatically scans the serial communication channel, adding any annunciators found, polls the IDNet channel and configures any
IDNet devices found, and adds any option cards found.
Auto-Program can perform the following:
The panel does not operate as a fire alarm system during Auto-Programming.
Auto-Program performs a IDNet duplicate address search and terminates if duplicate addresses are found.
Configure ALL
This option starts the panel with a new configuration. If a previous configuration is present and this option is selected, it erases the previous
configuration and creates a new one with the currently connected hardware.
1.
2.
3-1
In This Chapter
Configure ALL . . . . . . . . . . . . . . . . . . . . . . . . .3-1
Detect New Hardware . . . . . . . . . . . . . . . . . . .3-2
Restore Factory Defaults . . . . . . . . . . . . . . . . .3-2
Edit System Options. . . . . . . . . . . . . . . . . . . . .3-2
Restore Default System Options . . . . . . . . . . .3-3
Saving the Configuration . . . . . . . . . . . . . . . . .3-3
Default Programming Assignments . . . . . . . . .3-3
Chapter 3. Auto-Programming
3.
4.
FIRE ALARM
SUSPENDED
2.
3.
AutoProgram Complete
Total Devices: 200
RESTORING DEFAULT
5.
1.
This option adds newly found devices and cards to the existing configuration. It will also change any devices in the configuration that have changed (e.g. photo device changed to a
sounder base photo).
1.
FIRE ALARM
SUSPENDED
2.
FIRE ALARM
SUSPENDED
2.
3.
3.
The display will indicate the progress of the Auto Program operation. When the process is complete, the total
number of IDNet devices found during the Auto Program is displayed:
AutoProgram Complete
Total Devices: 200
4.
Option
Settings
Time/Date Format
Active Status
Reminder
Choose:
1.
Alarm Silence/Reset
Inhibit
3-2
Chapter 3. Auto-Programming
Table 3-1 System Options
Option
When the configuration is saved, the panel will automatically restart and run through its self-test procedure.
Settings
Detector Output
Enable Expansion
Power
Single Station
Cross Zone
Function
Type
PHOTO
SMOKE
Smoke Detector
SPHOTO
SMOKE
RPHOTO
SMOKE
IPHOTO
SMOKE
HEAT
HEAT
Heat Detector
SHEAT
HEAT
RHEAT
HEAT
IHEAT
HEAT
OHEAT
HEAT
OSHEAT
HEAT
ORHEAT
HEAT
OIHEAT
HEAT
AZONE
FIRE
BZONE
FIRE
MON
FIRE
PULL
PULL
RELAY
OTR
3-3
Description
Chapter 3. Auto-Programming
Table 3-2 Default Function Type Assignments,
IDNet Devices, NACs, and Relays
Function
Type
Device
Description
SIGNAL
OTS
ISOL
ISOL
SIG1-2
OTS
SIG3-4
OTR
AUX1
OTR
AUX2
TRBL
SIG1-2 (NAC)
SIG3-4 (NAC
Synchronized. Used with visual NACs. Programs all visuals to flash simultaneously.
Steady on
RELAY Modules
Steady on
SIGNAL Modules
Steady on
Annunciator Defaults
Annunciator cards found during the Auto-Program process
are added into the default configuration.
LED Annunciators and 24-I/O modules are not programmed for default operation.
Circuit
DACT Defaults
The defaults for the DACT are listed below. Refer to Chapter 5for information on manually programming the DACT.
3-4
Function Type
Default CID
Event Code
SMOKE
111
VSMOKE
111
PULL
115
FIRE
110
STYLEC
110
SUPV
200
LATSUPV
200
WSO
113
WATER
113
TROUBLE
330
Possible Settings
In This Chapter
In most cases, it is recommended that you use the panels auto programming feature (see Chapter 3) when initially programming the panel, or
when adding devices to an existing job. Auto programming scans the
IDNet channel and automatically adds devices that it finds to the job.
Once the devices are added, use the manual programming procedures
described in this chapter to adjust the point attributes listed below to
your site-specific needs.
Hardware Type. Identifies the specific type of device. If auto programming was used, the hardware type was automatically set and
does not need to be changed.
Function Type. Determines the operation of the device by specifying the way in which the system responds when changes occur to
the electrical state of the device. For example, one function type
might define a fire alarm as a current-limited state and another
might define a fire alarm as a short.
To manually add, edit, or delete a IDNet point, you must first login at
Access Level 4. Refer to Chapter 1 for information on doing this.
4-1
Note: Make sure the address shown on the display corresponds to the physical address, set via dip switches, of the
device.
FIRE ALARM
SUSPENDED
1.
<ENTER>=Accept
Prg:[Points]
3.
IDNet: 1
Pull
<ENTER>=Accept
Prg: [IDNet]
4.
2.
Press <ENTER>.
<ENTER>=Accept
IDNet: [Add]
5.
Lobby Door
Follow the steps outlined in Accessing IDNet Programming Menus earlier in this chapter. Select Edit
and then press <ENTER>. The display shows the first
point in the list. For example:
3.
4.
Select the operation you want to perform and see the appropriate section in this chapter.
<ENTER>= Confirm
[ADRPUL]
5.
<ENTER>=Accept
IDNet: 2
Use the <NEXT> and <PREV> keys to scroll through the
list of device addresses. When the appropriate address is displayed, press <ENTER>.
4-2
.
Table 4-1 Hardware Types for Sensors/Bases
Sensor
Models
Base
Models
Use this
Hardware
Type
4098-9755
4098-9755C
Two-wire duct base w/o relay
4098-9792
4098-9792C
Detector base w/o remote LED
4098-9714
40989714C
PhotoElectric
Smoke
Detector
Sensor
4098-9789
4098-9789C
Detector base with remote LED
RPHOTO
4098-9791
4098-9791C
Detector base with relay
RPHOTO
4098-9793
4098-9793C
Isolator base
IPHOTO
4098-9794
4098-9794C
Sounder base
See Note1 below
SPHOTO
4098-9792
4098-9792C
Detector base w/o remote LED
4098-9733
40989733C
Heat
Detector
Sensor
4098-9789
4098-9789C
Detector base with remote LED
HEAT
OHEAT
4098-9791
4098-9791C
Detector base with relay
RHEAT
ROHEAT
4098-9793
4098-9793C
Isolator base
IHEAT
IOHEAT
4098-9794
4098-9794C
Sounder base
See Note 1 below.
Base
Models
Use this
Hardware
Type
4098-9754
40989754C
4098-9795
4098-9795C
Multi-detector sounder base
See Note 1 and Note 2 below.
SPHOTO &
SHEAT
4098-9796
4098-9796C
Multi-detector base with LED
See Note 2 below.
PHOTO &
HEAT
Combination Photo
Electric
Smoke
Detector
and Heat
Detector
PHOTO
4098-9756
4098-9756C
Four-wire duct base with relay
Sensor
Models
Note 1.
Note 2.
A multi-detector base, coupled with a combination photo/heat sensor, uses two addresses. Make
sure to set the address on the base to an even
number, and do not set any other device to the
address that you set plus one. The even number
represents the Photo portion of the combination
sensor. The address plus one represents the heat
portion of the sensor.
Note 3.
The HEAT, RHEAT, IHEAT, and SHEAT function types set the heat detector to a fixed sensitivity of 135F. An alarm is initiated when the
temperature rises beyond this temperature.
The OHEAT, ROHEAT, IOHEAT, and SOHEAT
function types set the heat detector for rate-of-rise
operation. With this hardware type, if the temperature rises beyond 135F or if the temperature
rises at a rate of 15F per minute, an alarm is initiated.
4-3
Module
Use this
Hardware
Type
4090-9007
Zone Individual Addressable Module (IAM) for
Class A or B Signal Circuits
SIGNAL
4090-9001
Supervised Individual Addressable Module (IAM)
IAM
4090-9002
Indiv. Addressable Module with Relay
RIAM
Use this
Hardware
Type
4090-9116
Addressable Isolator
ISOL
4090-9101
Class B Zone Addressable Module for monitor
devices
MBZAM
4090-9106
Class A Zone Addressable Module (ZAM) for
monitor devices
MAZAM
IDNet: 1
F: [Hardware Type]
3.
IDNet: 1
[PULL]
4.
5.
ADRPUL
<ENTER>= Confirm
[PULL]
6.
SMOKE
HEAT
Follow the steps outlined in Accessing IDNet Programming Menus earlier in this chapter. Select Edit
and then press <ENTER>. The display shows the first
point in the list. For example:
IDNet: 1
Pull
2.
Normal = NORMAL
Current-Limited = FIRE
Short = FIRE
Open = TROUBLE
Use with heat detectors.
PULL
Lobby Door
Normal = NORMAL
Current-Limited = FIRE
Short = FIRE
Open = TROUBLE
Use with pull stations.
4-4
DUCT
STYLEC
SUPV
Normal = NORMAL
Current-Limited = SUPERVISORY
Short = SUPERVISORY
Open = TROUBLE
Used to monitor any supervisory type device
where operator acknowledgment is required.
LATSUPV
Normal = NORMAL
Current-Limited = SUPERVISORY
Short = SUPERVISORY
Open = TROUBLE
Generic supervisory monitor - latches until a system reset occurs.
Normal = NORMAL
Current-Limited = SUPERVISORY
Short = SUPERVISORY
Open = TROUBLE
SO
Used to indicate abnormal sprinkler conditions,
such as the opening of a PIV or OS&Y tamperswitch. Must be used with normally open contacts
only.
Normal = NORMAL
Current-Limited = SUPERVISORY
Short = FIRE (water flow)
Open = TROUBLE
FIRE
Normal = NORMAL
Current-Limited = FIRE
Short = TROUBLE
Open = TROUBLE
Style-C Fire Alarm Monitor. Used when only current limited devices are connected to the zone. A
short circuit is reported as a Trouble.
Normal = NORMAL
Current-Limited = VERIFY
Short = FIRE
Open = TROUBLE
VSMOKE
WSO
WATER
4-5
TROUBLE
DHOLDER
Description
Relay typically provides 24V power to larger door
holder relay with separate power source. Relay
activates on general alarm and signals door holder
relay to cut power to door holder magnets.
Normal = OFF
Current-Limited = ON
Short = ON
Open = TROUBLE
QALERT
A utility initiating device requires the following
programming:
UTIL
RSIG
Description
RRELAY
SUPV
TRBL
AUXPWR
PRIMARY
ALTERN
DRESET
SUPV
NAC activates when there is a supervisory condition active in the system. NAC is on until supervisory condition is acknowledged.
TRBL
AUXPWR
AVS44
MDL
The relay must have a function type of Primary or Alternate and must be wired to the appropriate elevator control contact.
4-6
Default of blanks
5th
Floor
North
Flr_1
Garage
South
Flr_2
Hallway
East
Flr_3
HVAC_Room
West
Flr_4
Kitchen
Front
Flr_5
Lobby
Centr
RM __
Office
rear
Basement
Patient
upper
Boiler_RM
Restroom
lower
Classroom
Room
main
Closet__
Stairway
first
Corridor
Storeroom
2nd
Elect_RM
Wing
3rd
Elevator
Zone
4th
Entrance
<ENTER>=Accept
Prg: [IDNet]
2.
3.
4.
Using the Keypad. Press the alphanumeric key corresponding to the letter you want. For example, for
the letter C, press the 2 key on the keypad three
times. Use the left and right arrow keys to move to
the next letter in the label.
5.
Use the Word Library, which is a stored list of common words sorted alphabetically. Press the
<FUNCTION> key on the front panel. A prompt
similar to the following appears.
Alarm Group
The Alarm Group programming choice allows you to perform input-output (selective signaling) programming in a
fast, flexible manner. The Alarm Group concept allows the
activation of a particular input to control a specific set of
outputs. An IDC can be in up to three different Alarm
Groups. For additional details on Alarm Groups and their
operation, refer to Programming Overview in Chapter 1.
IDNet1
<FUNC> = Word Library
To jump to a word, press the alphanumeric key corresponding to the first letter in the word. For example, to use the word Floor, press the 3 key
repeatedly until Floor appears.
4-7
4-8
Possible Settings
To manually add, edit, or delete a point, you must first login at Access
Level 4. Refer to Chapter 1 for information on doing this.
If an Expansion Power Supply Module is installed in the system, you
must first set the Expansion Power Supply system option to ON before
5-1
In This Chapter
Accessing Menus . . . . . . . . . . . . . . . . . . . . . . 5-2
Programming NACs . . . . . . . . . . . . . . . . . . . . 5-2
Programming AUX Relays . . . . . . . . . . . . . . . 5-4
Programming DACT. . . . . . . . . . . . . . . . . . . . 5-6
Accessing DACT Menu . . . . . . . . . . . . . . . . . 5-6
Programming DACT Options . . . . . . . . . . . . . 5-7
Programming Contact ID (CID) Points . . . . . . 5-9
Programming Event Codes . . . . . . . . . . . . . 5-10
Saving Changes. . . . . . . . . . . . . . . . . . . . . . 5-11
programming NACs. Refer to Chapter 7 - Manually Programming System Options for information on doing this.
Alarm Group
Accessing Menus
Use the following steps to gain access to the NAC and relay
menus.
1.
1.
<ENTER>=Accept
Prg: [NAC]
FIRE ALARM
SUSPENDED
2.
<ENTER> to Program
<EXIT> to resume
2.
3.
4.
NAC
Programming NACs
Use the following procedure to edit the programming of the
two Notification Appliance Circuits (NACs) on the base
panel, or the two optional NACs on the expansion power
supply. NACs cannot be added or deleted, only edited.
The "output method" used by the NAC when it activates (coded, steady, etc.)
TEMPRL
5.
6.
Note: Refer to the table located at the top of Page 5-1 for UL
864 compliant options.
Press <ENTER> when the appropriate NAC is displayed. A prompt appears, asking you to specify the
NAC function type.
NAC1
[SSIG]
Select the operation you want to perform and see the appropriate section in this chapter.
1/4
NAC1
Fn: [Function]
4.
3.
5-2
.
Table 5-1 NAC Function Types
Function
Type
Function
Type
Description
UTILITY
Operation
Description
Temporal
Description
Synch
Steady
Steady On
20 BPM
SUPV
NAC activates when there is a supervisory condition active in the system. NAC is on until supervisory condition is cleared.
TRBL
1.
2.
3.
5-3
1/4
Press <ENTER> when the appropriate NAC is displayed. A prompt appears, asking you to specify the
NAC function type.
NAC1
Fn: [Alarm Groups]
NAC1
FN: [Function Type]
4.
5.
NAC1
Fn: [Edit Label]
5.
6.
6.
00
Use the <NEXT> and <PREV> keys to scroll the number in the brackets. Use the right and left arrow keys to
move between the alarm groups. Press <ENTER> when
all the values are set correctly.
Edit or Clear Point Label. Allows you to set a 40 character label for the relay point.
1.
<ENTER>=Accept
Prg: [Relay]
<ENTER>=Accept
Prg: [NAC]
2.
3.
AUX1
Alarm
3.
1/4
1/2
Press <ENTER> when the appropriate relay is displayed. A prompt appears, asking you to specify the
relay function type.
AUX1
FN: [Function]
Press <ENTER> when the appropriate NAC is displayed. A prompt appears, asking you to specify the
NAC function type.
4.
NAC1
FN: [Function Type]
4.
Press <ENTER>. The display appears similar to the following. As shown in the example below, the function
type is comprised of two parts -- the function (On Till
Trouble Relay, On Till Reset, etc.) and the coding pattern (Steady, 120 BPM, etc.)
AUX1
[OTR]
5-4
STEADY
5.
6.
Operation
Description
Temporal
Note: Refer to the table located at the top of Page 5-1 for UL
864 compliant options.
Table 5-3 Relay Function Types
Function
Type
Description
SRELAY
RRELAY
SUPV
Utility
PRIMARY
See Note
Below
ALTERN
See Note
Below
DRESET
Steady On
SYNCH
20 Bpm
TRBL
Steady
The relay must have a function type of Primary or Alternate and must be wired to the appropriate elevator control contact.
DHOLDER
2.
3.
Press <ENTER> when the appropriate relay is displayed. A prompt appears, asking you to specify the
relays hardware type.
AUX1
FN: [Hardware Type]
5-5
1/2
4.
2.
<ENTER>=Accept
Prg:[Points]
AUX1
Fn: [Edit Label]
5.
3.
4.
Pressing the <ENTER> key will save the current label, and
<EXIT/CLEAR> will quit label editing without saving.
5.
Programming DACT
The panels DACT (Digital Alarm Communicator Transmitter) allows the panel to use one or two telephone lines to call
a supervising station and report a local alarm, trouble, or
supervisory condition.
Event Codes. The 3/1, 4/2, BFSK, and SIA communication formats support per-event reporting of
fire alarms, trouble conditions, etc. With these formats, the supervising station receives a general
code for an event type that does not specify the
activated point.
Use this choice to verify and edit the codes for each
event type. Refer to Programming Event Codes,
below for more information.
5-6
CID Points. The Contact ID communication format supports per-point reporting of system events.
The supervising station receives a code identifying
the point and the event type (alarm, trouble, etc.).
With this format, the DACT can also send a restoral code to the supervising station after the device
experiencing the alarm, trouble, or supervisory
condition is restored to a normal state. Use this
choice to verify and edit the activation and restoral
codes for each point. Refer to Programming Contact ID (CID) Event Codes, below for more information.
1.
B -- Use if it is necessary to input a DTMF (touchtone) asterisk (*) into the phone number.
Enabling/Disabling DACT
1.
2.
3.
4.
5.
3.
4.
Pri Account #
[0] 000
1.
Use the arrow keys to move the cursor from one number
to another. Use the NEXT and PREV keys or the keypad to enter each number.
2.
3.
4.
<ENTER>=Accept
Opt: [Pri Phone #]
1.
2.
Use the arrow keys to move the cursor from one digit to
another. Use the keypad numbers, or use the NEXT and
PREV keys to enter each number. Press <ENTER>
when the number is correctly entered. A prompt appears
asking you to confirm the number that you entered.
5-7
and tone else pulse (attempt to dial with a touchtone format and if that fails, use a pulse format).
description of these characters in the section Setting Primary Phone Number above.
<ENTER>=Accept
Opt: [Sec Phone #]
1.
2.
Use the arrow keys to move the cursor from one digit to
another. Use the keypad numbers, or use the NEXT and
PREV keys to enter each number. Press <ENTER>
when the number is correctly entered. A prompt appears
asking you to confirm the number that you entered.
3.
4.
3.
4.
5.
Press the <NEXT> key. The prompt for the Pulse Rate
appears.
Pulse Rate
[20 PPS]
2.
3.
4.
5.
Press the <NEXT> key. The prompt for the Pulse Frequency appears.
Sec Account #
[0] 000
1.
Use the arrow keys to move the cursor from one number
to another. Use the NEXT and PREV keys or the keypad to enter each number.
2.
3.
4.
Press the <NEXT> key. The prompt for setting the dialing mode appears.
<ENTER> = Accept
Opt: [Pulse Freq]
1.
2.
Press <ENTER>.
Dialing Mode
[Tone else Pulse]
2.
Press <ENTER>.
Pulse Freq
[1.9KHz Data]
<ENTER> = Accept
Dialing Mode
1.
Press <ENTER>.
3.
5-8
4.
5.
AC Fail Delay
Reporting Format
Before you select the Communications Format Code, determine, from an authorized person at the supervising station,
the required reporting format.
AC Fail Delay
[06] Hrs
<ENTER> = Accept
Opt: [Report Format]
1.
1.
2.
3.
4.
Press the <NEXT> key. The prompt for the Test Report
Time appears.
<ENTER> = Accept
Opt: [Test Rpt Time]
1.
Press <ENTER>.
Test Rpt Time
[02] : 00
2.
Use the NEXT and PREV keys to increment or decrement the hour setting (two digits on left). Use the right
arrow key to move the cursor to the minutes (two digits
on right). Use the NEXT and PREV keys to increment
or decrement the minutes setting.
3.
2.
4.
3.
5.
4.
5.
5-9
<ENTER>=Accept
DACT: [Event Codes]
2.
[FIRE ALARM]
Code: A1
2.
3.
For each code, use the right arrow key to move between
the letter/digit of the Code field. Use the <NEXT> and
<PREV> keys to increment or decrement the value of a
letter or digit. See Table 5-5 for a list of Event types and
their corresponding codes.
4.
5.
IDC1]
ID: 001
3.
4.
5.
Point Custom Label. The top line of the prompt displays the custom label assigned to the point.
<ENTER>=Confirm
Code: A1
6.
For each point, use the right arrow key to move between
the digits of the GRP and ID fields. Use the <NEXT>
and <PREV> keys to increment or decrement the value
of a digit.
Event
<ENTER>=Confirm
GRP: [01]
ID:001
6.
5-10
3/1
BFSK
4/2
SIA
Fire Alarm
11
A1
FA1
Supervisory
33
A3
SS3
Trouble
F4
A4
FT4
Fire Restoral
E1
71
FR1
Supervisory
Restoral
E3
73
SJ3
Trouble Restoral
E4
74
FJ4
Phone Line 1
Trouble
FB
31
LT1
Phone Line 1
Restoral
EB
35
LR1
Phone Line 2
Trouble
FC
32
LT2
Phone Line 2
Restoral
EC
36
LR2
AC Failure
FA
6A
AT0
AC Restoral
EA
7A
AR0
EE
3A
RP0
3/1
BFSK
4/2
SIA
Manual Test
Report
EE
3A
RX0
Off-normal at
test
F8
33
YX0
Saving Changes
When DACT programming is complete, press the EXIT/
CLEAR key until the following prompt is shown.
[Cont]
Dscrd
Save
Use the right arrow key to move the cursor to one of the following options and press <ENTER>.
5-11
In This Chapter
6-1
Adding an Annunciator
4.
<ENTER>=Accept
Annuns: [Add]
5.
<ENTER>=Accept
Add: [LCD]
6.
FIRE ALARM
SUSPENDED
<ENTER> to Program
<EXIT> to resume
2.
Use the <NEXT> key to select [Detect New]. The following prompt appears.
<ENTER> to Continue
*May CHANGE Setting*
4.
Zone Ann
Remote LED/SW
7.
8.
9.
<ENTER>=Accept
AP: [Reconfig All]
3.
Press <ENTER>. A prompt appears, asking you to identify the specific type of annunciator.
Use the following procedure to manually add the annunciator module to the job.
1.
1.
FIRE ALARM
SUSPENDED
FIRE ALARM
SUSPENDED
<ENTER> to Program
<EXIT> to resume
<ENTER> to Program
<EXIT> to resume
2.
2.
3.
3.
<ENTER>=Accept
Prg: [Annuns]
6-2
<ENTER>=Accept
Prg:[IDC
4.
Point 3
Point 10
Point 18
Point 22
Point 11
Point 19
Point 4
Point 12
Point 1
Point 5
Point 13
Point 21
Point 6
Point 14
Point 2
Point 7
Point 15
Point 23
Point 8
Point 16
Point 24
Point 9
Point 20
Point 9
Point 10
Point 11
Point 12
Point 13
Point 14
Point 15
Point 16
Point 17
Point 20
Point 22
Point 4
Point 5
Point 6
Point 7
Point 8
Point 17
Figure 6-1
Alarm
Silence
ACK
Reset
Lamp
Test
Alarm
Silenced
Comm Lost
Trouble
CONTROL
ENABLE
Power
Programming Overview
Programming an LED consists of performing the following
tasks
Note: The three LEDs on the front of the display are programmed in a different manner. Refer to Programming
Panel LEDs at the end of this chapter for information.
Mapping LEDs to Software Points
Figure 6-1 identifies the way in which the software points
map to the LEDs on the annunciators. For example, to control the LED in the upper left corner of the Local Zone LED
Annunciator, you need to program Point 17.
Identify which point state (fire alarm, trouble, etc.) triggers the LED to turn on. This is called the mode.
6-3
Default Function
Default Reference
Point
TROUBLE
Alarm Group 9
TROUBLE
NAC2
FIRE
Alarm Group 8
TROUBLE
Alarm Group 1
FIRE
Alarm Group 2
TROUBLE
Alarm Group 2
FIRE
Alarm Group 3
TROUBLE
Alarm Group 3
FIRE
Alarm Group 4
10
TROUBLE
Alarm Group
11
FIRE
Alarm Group 5
12
TROUBLE
Alarm Group 5
13
FIRE
Alarm Group 6
14
TROUBLE
Alarm Group 6
15
FIRE
Alarm Group 7
16
TROUBLE
Alarm Group 7
17
FIRE
Alarm Group 99
18
TROUBLE
Alarm Group 8
19
FIRE
Alarm Group 9
20
TROUBLE
Alarm Group 99
21
TROUBLE
NAC 1
22
FIRE
Alarm Group 1
23
TRBL
NAC 3
24
TRBL
NAC 4
Point
Type
Default
Function
Default
Reference
Point
Tone-Alert
none
Yellow LED
none
Red LED
FIRE
Alarm
Group 3
Red LED
FIRE
Alarm
Group 4
Red LED
FIRE
Alarm
Group 5
Point
Type
Default
Function
Default
Reference
Point
Red LED
FIRE
Alarm
Group 6
Red LED
FIRE
Alarm
Group 7
Red LED
FIRE
Alarm
Group 8
10
Red LED
FIRE
Alarm
Group 9
11
Yellow LED
TROUBLE.
Alarm
Group 99
12
Yellow LED
TROUBLE
Alarm
Group 1
13
Yellow LED
TROUBLE
Alarm
Group 2
14
Yellow LED
TROUBLE
Alarm
Group 3
15
Yellow LED -
TROUBLE
Alarm
Group 4
16
Yellow LED -
TROUBLE
Alarm
Group 5
17
Red LED -
FIRE
Alarm
Group 99
18
Yellow LED -
none
none
20
Red LED -
FIRE
Alarm
Group 1
22
Red LED -
FIRE
Alarm
Group 2
6-4
<ENTER>=Accept
Prg: [LED]
Mode
2.
3.
4.
5.
6.
SUPV
TRBL
DISA
8.
9.
OFF
LF
LS
LT
Reference
Point
IDNet 1-200
City/DACT
Disconnect
Separate reference point (18-14) for disconnect and trouble. Typical use is to
monitor the ON state of either point.
Elevator
Bypass
Door Bypass
Description
Output activates when referenced
point is in an Alarm condition.
6-5
Control
Bypass
Description
Aux Relays 1
and 2
City Trouble
FIRE
Fire
7.
Mode
ON
Description
List - General
Alarm Points
List - Sprinkler
Zones
<ENTER>=Accept
Prg: [User SW/LED]
Description
2.
User LED 1
Y LED
3.
Alarm Group
1 -99
NACs 1 - 4
4.
5.
6.
1/5
User LED 1
Fn: [Function]
6-6
Function
Color
Alarm Inputs
Red
Alarm Signal
Yellow
Inhibit
Yellow
Supervisory Inputs
Power - ON
Green
Trouble Signal
Yellow
Yellow
2.
3.
1/5
User LED 1
Fn: [Mode]
4.
5.
6.
8.
9.
Fire
7.
6-7
1.
After selecting <NEXT>, as described in Step 6 of the previous section, you are prompted to specify whether you want
to annunciate Fire events on the LCD.
FIRE ALARM
SUSPENDED
<ENTER>=Accept
Send FIRE Events: [Yes]
<ENTER> to Program
<EXIT> to resume
2.
1.
<ENTER>=Accept
Send SUPV Events: [Yes]
<ENTER>=Accept
Prg:[Points]
3.
2.
4.
3.
4.
<ENTER>=ALL Events
<NEXT> = Select Events
Card=[11]
LCD
6.
<ENTER>=Accept
Cards:[Add]
5.
1.
6-8
2.
4.
5.
6.
Dscrd
Save
Use the right arrow key to move the cursor to one of the following options and press <ENTER>.
6-9
System options are pre-defined modes of operation with a range of settings from which to choose. System Options define global operations
such as the time and date format, door drop timers, and whether the city
circuit is enabled, etc. System options can be set during either the automatic (Chapter 3) or manual programming process.
3.
4.
5.
Programming Options
Refer to the appropriate section in the table below for details on each
option. In each case, programming the option involves using the
<NEXT> and <PREV> keys to scroll through the choices and using the
<ENTER> key to set the option to the value you choose.
To back out of an option without setting it, use the <EXIT/CLEAR>
key.
7-1
In This Chapter
Accessing System Options Menu . . . . . . . . . .7-1
Programming Options . . . . . . . . . . . . . . . . . . .7-1
Option
Option
Time/Date
Format
Reminder
Choose 12 (am/pm) or 24-hour (military) format. Use <NEXT> and <PREV> to scroll
between options and <ENTER> to set.
AC Doors
Inhibit
Alarm Cutout
Alarm Doors
Settings
Settings
7-2
Option
Settings
This option activates the 4008 Expansion
Power Supply Module and its associated
NACs. If the expansion power is used in the
system this option must be selected or a trouble will be reported. If this option is selected
and the EPS is not connected, the trouble will
also report.
Activation of this module allows the two
expansion NACs to be edited in the Point programming menu.
7-3
Chapter 8. Operating
Normal Operation
In This Chapter
The 4008 operator interface shows the following under normal conditions:
SYSTEM NORMAL
1:45:07 pm 3/10/03
LAMP Test
Lamp Test is accomplished during normal monitoring (Access Level 1)
by pressing the Function key, then pressing ENTER. All LEDs energize
and all LED segments are written to.
Abnormal Conditions
Abnormal conditions are indicated on the 4008 by flashing the alarm,
supervisory, or trouble LED and sounding the tone-alert. The tone-alert
pulses for an alarm condition, and is on steady for a trouble or supervisory. If the "Display First Alarm" option is selected, the display provides information about the first, highest-priority alarm in the system
without operator intervention. If "Display First Alarm" is not selected, a
screen showing the overall system status is shown:
FIRE
SUPV
TRBL
02
00
00
CORE 1 MEZZANINE
FIRE
1/2
8-1
Chapter 8. Operating
Historical Logs
The electrical state of the point (open, short circuit, normal, abnormal)
Silencing Alarms
The "Alarm Silence" key allows the operator to silence
active Notification Appliance Circuits that are programmed
for "on-til-silence" operation.
SLOG
Supervisory
Log
100 Entries
TLOG
Trouble Log
300 Entries
CLOG
Combined Log
Stored Events
Alarms
Alarm Acknowledge
Log Cleared
Alarm Silence
System Reset
Supervisory Conditions
Supervisory Acknowledge
Log Cleared
Trouble Events
Login/Logout for Level 2 or higher
Log Cleared
WALKTEST Events
All Events in Chronological Order
Viewing Logs
1.
Press <MENU>.
System Reset
2.
<ENTER>=Accept
Menu: [History Logs]
3.
If a device remains in alarm during the reset period, the system reset is aborted, and the system remains in the alarm
state. The display will continue to show the device(s) that
remain in alarm.
4.
5.
Clearing Logs
The logs may be viewed at Access Level 1, however they
may not be cleared unless you are at Access Level 2 or
8-2
Chapter 8. Operating
7.
SMOKE
a.
IDNet1
PHOTO
Press <MENU>.
2.
a.
IDNet
SMOKE
Enable/Disable status
<ENTER>=Accept
Menu: [Control/View]
3.
<ENTER>=Accept
Ctrl/View: [IDNet]
a.
4.
5.
IDNet
Relay
NAC
Output (LED)
Relay or
NAC
IDNet1
Fire
6.
NAC1
NAC
Input
NORMAL
8-3
N/A
a.
Enable/Disable status
Chapter 8. Operating
System
Point
a.
a.
2.
3.
4.
5.
IDNet1
FN: [Enable]
6.
Press <MENU>.
2.
3.
4.
5.
6.
Function
User control functions, such as Drill, City Disconnect, Control Point Bypass, and Elevator Recall Bypass are available
by pressing the <FUNCTION> key.
ENTER = Accept
FN: ON
8.
Control Functions
Press <MENU>.
8-4
Description
Drill
Manual Evacuation
City/DACT
Disconnect
Chapter 8. Operating
a.
a.
a.
Configure the application to capture the information coming in on the serial port. (Choose Capture
Text in the Hyperterminal Transfer menu.)
Description
Bypasses the following control points
(causes a trouble):
On-til-Silence NACs
On-til-Reset NACs/relays
Elevator
Bypass
Doorholder
Bypass
Lamp Test
Earth Fault
Latch
Display Time
Send DACT
Test
Press <MENU>.
2.
3.
4.
<ENTER>=Accept
ALOG
[11]:23 pm 11/12/03
SLOG
TLOG
CLOG
CONFIG
The Right/Left arrow keys allow you to move the focus from
field-to-field for editing. The <NEXT/PREV> keys allow
you to change the currently selected fields. The am/pm field
and the day-of-week field are not editable.
Reports
5.
Description
Diagnostics
8-5
1.
Press <MENU>.
2.
Chapter 8. Operating
<ENTER>=Accept
Menu: [Diagnostics]
3.
Option
Description
BAT CHGR
METER
Battery Meter
HW Reset
WalkTest
WalkTest allows one person to test the functionality of the
panels devices. Once the panel is placed into WalkTest
mode, you can test the following:
5.
4.
8-6
Chapter 8. Operating
1.
<ENTER>=Accept
[Off]
Lg
2.
Sil
NoPr
1.
Press <MENU>.
2.
Press <NEXT> and <PREV> and choose one of the following options.
Cold. Clears the Access Level 4 trouble and re-initializes the panels non-volatile memory, clearing
all time/date information, historical logs, and disabled points.
LG/NL. Controls whether alarms and troubles generated by WalkTest are sent to the alarm or trouble
log. Lg enables logging; NL disables logging.
3.
3.
1.
Press <MENU>.
2.
When the options are set, press the <ENTER> key. The
system prompts you to confirm the settings. Press
<ENTER> again to confirm.
Rev 1.00.11
<NEXT> = View Job Info
Advanced Operations
Upload/Download
3.
Press <MENU>.
2.
3.
<ENTER>=Accept
XFER: [Start XFER]
8-7
04/09/04
Module
Standby Current
Alarm Current
175mA
200 mA
1 mA
1 mA
50 mA
60 mA
100 mA
150 mA
100 mA
100 mA
30 mA
60 mA
0 mA
1.
2.
3.
4.
Using the values in Steps 1-4, perform an Initial Battery Calculation per the following:
5.
6.
Select a battery size LARGER than the number from the Initial Battery Calculation from the following list of batteries
using the 20 Hour Rating value:
B = ______
A-1
7.
20 Hour Rating
C/20 (Amps)
20 Hour Rating
C/20 (Amps)
1.3 Ah
0.065
6.2 Ah
0.31
2.2 Ah
0.11
7.0 Ah
0.35
3.0 Ah
0.15
7.2 Ah
0.36
3.4 Ah
0.17
10 Ah
0.50
4.0 Ah
0.20
12 Ah
0.60
4.5 Ah
0.225
12.7 Ah
0.635
5.0 Ah
0.25
18 Ah
0.90
If either the Standby Current or the Alarm Current is greater than the C/20 current for the initial battery size selected, a
Discharge Factor (DF) must be applied. For example, 1 A load on a 10 Ah battery requires a Discharge Factor of 1.08 (10
Ah / 1 A gives discharge time of 10 hours; DF = 1.08). Use the following table to determine Discharge Factor (use the 20
hr value for 24 hr standby):
Discharge
Time
Discharge
Factor
Discharge
Time
Discharge
Factor
Discharge
Time
Discharge
Factor
Discharge
Factor
0.083 hr
5 min
3.85
2 hr
1.43
8 hr
1.10
14 hr
1.03
0.166 hr
10 min
2.78
3 hr
1.30
9 hr
1.09
16 hr
1.02
0.249 hr
15 min
2.27
4 hr
1.22
10 hr
1.08
18 hr
1.01
0.332 hr
20 min
2.08
5 hr
1.18
11 hr
1.06
20 hr
1.00
0.5 hr
30 min
1.96
6 hr
1.14
12 hr
1.05
48 hr
1.00
1 hr
60 min
1.67
7 hr
1.11
13 hr
1.04
60 hr
1.00
8.
9.
Minimum Required Battery Capacity Calculation. (to account for battery aging, a 1.17 multiplier is included)
Minimum battery capacity in Ah =
1.17 x [(A x C x SDF) + (0.0167 x B x D x ADF)] = _______
10. If the battery size initially selected is smaller than the result of step 9 above, repeat the calculations using a larger battery
size.
A-2
579-716
Rev. A