Sunteți pe pagina 1din 9

5 transformer constructions youre most likely to see inside

buildings
electrical-engineering-portal.com/transformer-constructions

Google+

5 transformer constructions you're most likely to see inside buildings (on photo: General Electric ventilated dry type transformer - 30 KVA, 480 Volt Primary,
208/120 Volt Secondary)

Transformer constructions
Liquid filled, ventilated dry and gas filled dry types
There are several different types of transformer constructions you can see installed in substations inside
commercial and other buildings. This article is generally applicable only to transformers of the liquid filled, ventilated
dry, or gas filled dry types. Liquid insulated and gas filled transformers have their windings brought out to bushings or
to junction boxes on the ends or the top of the transformers.
Ventilated dry type transformers usually have their windings terminated within the enclosure of the transformer to
either stand-off insulators or bus bar terminals.
Ok, these are the five transformer constructions you are most likely to meet in a substation inside buildings:
1. Liquid filled transformers

1/9

2. Ventilated dry type transformers


3. Sealed dry type transformers
4. Cast-coil dry type transformers
5. Totally enclosed, non-ventilated dry type transformers

1. Liquid filled transformers


Are constructed with the windings encased in a liquid-tight tank filled with insulating liquid.
The liquid provides insulation between the various sections of the windings and between the windings and the tank,
and serves as a cooling medium , absorbing heat from the windings and transferring it to the outside of the tank.
Liquid filled transformers should be avoided inside commercial buildings unless non-flammable or less-flammable
liquids are used or unless proper precautions are taken by building a transformer vault that meets the requirements of
the NEC. And of course, then only if all applicable jurisdictional and insurance carrier requirements have been met.
To increase the transfer of heat to the air, tanks are provided with cooling fans (to increase the area of the radiating
surface) or with external cooling tubes or radiators. The hot liquid circulates through the radiators, transferring the
heat picked up in the transformer windings to the radiator and then to the surrounding air.

Liquid filled transformer (photo credit: elektrodekeyser.be)

Fans are sometimes installed to force air over the radiators in order to increase the full load rating by approximately
15% on transformers rated 750-2000 kVA and 25% on transformers rated 2500-10 000 kVA.

2/9

IMPORTANT NOTE! It is essential that the liquid in the transformer be maintained, clean, and free
from moisture! Moisture can enter the transformer through leaks in the tank covers or when moistureladen air is drawn into the transformer.

Transformers can draw air into the tanks through breathing action that results from changes in the volume of liquid,
and air in the tank that occurs with changes in temperature. Most modern transformer constructions are tightly sealed
and do not breathe if they are free from leaks.

Transformer oil tank

Insulating liquid, through the normal aging process, develops a small amount of acid that, if allowed to increase above
well-established limits, can cause damage to insulation in the transformer.
Yearly testing to determine the dielectric breakdown voltage of the liquid (a low dielectric test indicates the
presence of water or other foreign material) and neutralization number (a high neutralization number indicates the
presence of acid in the liquid) by a competent testing laboratory will greatly prolong the life of the transformer.

Liquid samples should be withdrawn under carefully controlled conditions as directed by the group
making the liquid test. In some areas, this service is available from the electric utility.

The classification and handling of existing liquid filled transformers with regard to polychlorinated biphenyl (PCB)
contamination is subject to strict control by environmental agencies.
It is important that any existing liquid filled transformers that have not been evaluated tagged, or otherwise classified
be properly handled. Liquid filled transformers, which contain from 50500 parts per million (ppm) of PCB, have

3/9

successfully been brought into the 050 ppm range , which is within the limits of non-PCB contamination.
Go back to transformer constructions

2. Ventilated dry type transformers


Are constructed in much the same manner as liquid filled transformers, except that the insulating liquid is replaced
with air, and larger clearances and different insulating materials are used to compensate for the lower dielectric
strength of air.
Both ventilated dry type and sealed dry type transformer constructions use a UL component recognized insulation
system that is suitable for operation at an ultimate temperature of 220C. The normal temperature rise of the windings
is 150C by resistance.

If transformers are purchased with a 220C insulation system, but are rated for full load use at a lower
temperature (115C or 80C rise), then an improvement in efficiency, overload capability, and life
can be expected.

Consideration should also be given to nonlinear harmonic loads, such as SCRs, UPS, rectifiers, and variable speed
drive applications, since these higher harmonics can cause appreciably higher eddy and stray loss heating in the
windings as well as very high currents in the neutrals of these transformers.

4/9

Ventilated dry type transformer (photo credit: federalpacific.com)

Very often special designs for nonlinear load applications are preferable to just oversizing the unit because of the
skin effect at the higher frequencies.
The ventilated dry type transformer is provided with a sheet metal enclosure that surrounds the winding for
mechanical protection of the windings and the safety of personnel. Ventilating louvers are installed in the enclosure
to permit thermal circulation of air directly over the winding for cooling. Fans are sometimes installed to force air
directly over the windings in order to increase the full load rating by approximately 30-40%.
These types of transformers are normally installed indoors and require the periodic cleaning of the complete core
and coil assembly and an adequate supply of clean ventilating air.
These transformers are gaining acceptance in the 15 kV and 34.5 kV class, and can be built to match the BIL of
liquid immersed transformers and with special enclosures for use outdoors. Meggering before energizing is
recommended after a lengthy shutdown or lengthy periods when the insulation has been subjected to moisture.

5/9

Ventilated dry transformer 45 kVA (photo credit: goding.com)

Go back to transformer constructions

3. Sealed dry type transformers


Sealed dry type transformers are constructed in essentially the same way as ventilated dry type transformers. The
enclosing tank is sealed and operated under positive pressures. It may be filled with nitrogen or other dielectric
gas. Heat is transferred from the winding to the gas within the transformer housing and from there to the tank and to

6/9

the surrounding air.

The sealed dry type (gas filled) transformer can be installed both outdoors and indoors and in areas
where a corrosive or dirty atmosphere would make it impossible to use a ventilated dry type
transformer.

ABBs sealed dry type transformer with complete absence of oil, entirely welded tank assembly,
N2 gas overpressure for tank deterioration monitoring, 2-position ground switch, 70 percent
overloading capability, similar footprint to liquid-filled units with cooling fans and power rating up to
1,000 kVA and 15 kV primary voltages

Go back to transformer constructions

4. Cast-coil, dry type transformers


Are constructed with primary and secondary windings encapsulated (cast) in reinforced epoxy resin. Because of the
cast-coil construction, they are ideal in applications where moisture or airborne contaminants, or both, are a major
concern. This type of construction is available with primary voltage ratings through the 34.5 kV class and BIL ratings
through 200 kV.
These transformers are ideal alternatives for liquid or gas filled units in indoor or rooftop applications. They may be

7/9

forced air cooled to increase their self-cooled ratings by 50%.

Cast-resin dry type transformer (photo credit: mrazik.info)

Go back to transformer constructions

5. Totally enclosed, non-ventilated dry type transformers


Are constructed in essentially the same way as ventilated dry type transformers. The enclosure, while not sealed,
contains air, so the units have the same BIL capabilities as ventilated dry type transformers.
The totally enclosed, non-ventilated dry type transformer can be installed both indoors and outdoors and in areas
where a corrosive or dirty atmosphere would make it impossible to use a ventilated dry type transformer.

8/9

These units are available with fan cooling for a minimum 25% increase in capacity .

Totally enclosed, non-ventilated dry type transformer (on photo: Square D 3-phase 150KVA dry transformer)

Go back to transformer constructions

All above described transformer constructions has various temperature measurement equipment and controls for
determining the winding temperature and for activating cooling, tripping, or alarm devices. To make sure the ultimate
temperature of the insulating system is not exceeded, imbedded detectors should be wound in each low-voltage
winding.
Reference // Recommended Practice for Electric Power Systems in Commercial Buildings IEEE STD 241

9/9

S-ar putea să vă placă și