Documente Academic
Documente Profesional
Documente Cultură
for
Tender No - CMM/FTP/75-00-1-1147
Index
S.No.
DESCRIPTION
1.
2.
3.
4.
Page 1 of 1
Volume II
Description of Query
NPCIL's Response
NIT
Volume II
all datasheets
all datasheets
Volume II
Volume II
all datasheets
Volume II
all datasheets
Volume II
7.4 (Welding)
Volume II
7.4 (Welding )
Volume II
A463-000-16-46-DS-4001
10
10
Volume II
A463-000-16-46-DS-4001
11
11
Volume II
all datasheets
Pl. confirm whether Nozzle -IX can be made from two pieces. The
portion of nozzle outside the tank shal be made from forging & the
inside portion shall be made from hollow bar of quality SA 479 Gr.304L
(Refer data sheet no. 6/9).
OD of Nozzle - VI (towards shell side) is not given in detail drg. (Refer
data sheet No. 6/9). NPCIL to confirm..
OD, thk, end details (BW) are specified in datasheet for nozzles and
mentioned to refer GOST Std. . Please confirm GOST std. to be referred
and for what details?
12
12
Volume II
A463-000-16-46-DS-4001
13
13
Volume II
A463-000-16-46-DS-4001
We Propose to use SA 403 Gr. WP 304L for STD Pipe fittings for ex.
ELBOW of Nozzle -VII. Please confirm.
14
14
Volume II
all datasheets
15
15
Volume II
Refer detail ~d' given in Sh. 8. Please furnish Qty. of Rods (Dia. 6 & 12).
16
16
Volume II
Page 1 of 7
Accepted
17
17
Volume II
A463-000-16-46-DS-4002
18
18
Volume II
A463-000-16-46-DS-4002
19
19
Volume II
A463-000-16-46-DS-4003
NPCIL to furnish diatance between tank centre line to end of Nozzle 'I'.
For elbow of Nozzle 'I', WIL proposes to use bend which will be made
from hollow bar of quality SA 479 Or can we use standard pipe &
standard elbow of size 50 NB?
20
20
Volume II
A463-000-16-46-DS-4003
21
21
Volume II
A463-000-16-46-DS-4004
22
22
Volume II
A463-000-16-46-DS-4004
23
23
Volume II
A463-000-16-46-DS-4004
24
24
Volume II
A463-000-16-46-DS-4005
Material quality for shell, roof, bottom plate, nozzle flanges, pipe fitting For material refer table in Technical
nozzle necks are under hold by NPCIL. Please confirm the quality.
specification section 2.0 for the tank
25
25
Volume II
A463-000-16-46-DS-4006
26
26
Volume II
A463-000-16-46-DS-4006
27
27
Volume II
A463-000-16-46-DS-4007
28
28
Volume II
Detail of bottom Support not given in drg. For other tanks such drg. is
provided for e.g. 4007 sheet 9, 10, 11.
Provided in attachment.
29
29
Volume II
all datasheets
Please confirm type & qty. of staircase required for each tank. Also
confirm the design as per API650 and OSHA 29.
30
30
Volume II
all datasheets
31
31
Volume II
all datasheets
32
32
Volume II
OD of Nozzle - VII (towards shell side) is not given in detail drg. NPCIL to
OD-25 mm and length-50 mm
furnish (Refer sh.6/10)
For STD Pipe fitting - ELBOW of Nozzle -IV, We Propose to use SA 403
Acceptable.
Gr.WP 304L.
To be worked out by vender from
Refer detail `H2' given in Sh.7. Please furnish Qty. of Rods (Dia. 6 & 12) sheet no-7 Drawing showing
insulation schematic on tank
Please confirm requirement & no. of platform for each tank. Also
please confirm requirement & no. of walkways for each tank. Also
Tender is not clear for stage of insulation ie. prior to despatch or after
receipt of tank at site. Please confirm.
all datasheets
33
33
Volume II
all datasheets
34
34
Volume II
all datasheets
35
35
Volume II
36
36
Volume II
37
37
Volume I
Payment terms
Page 2 of 7
38
38
Volume I
39
40
40
Volume I
Delivery
41
41
Volume II
Design of components
39
At present Insurance policy is not available and hence, cost of the same
can not be accessed and built in the bid. It may be made available in
Request not acceptable. Tender
near future and Cost of the same will be known at that time. At that
Conditions shall prevail.
time it will be informed to NPCIL to consider it additionally.
Tender involves Design. Analysis, Procurement of raw material, lot of
fabrication & transporatation and hence delivery of KKNPP-3 sholud be Request not acceptable. Tender
Conditions shall prevail.
24 months instead of 13 months and KKNPP should be 30 months
instead of 21 months.
No, complete designing and detail
engineering of the tanks are to be
Are the ASME Sec III, NC / ND Codes to be used only for Nozzle
done as per section III ND
reinforcements and acceptance criteria for stresses, whereas API 650 is
(3300/3200). API 650 to be used only
to be used for the loadings to be considered for calculations of the
for those clauses/calculations not
thicknesses and stresses regarding the parts of the tanks? Kindly clarify.
covered in section III ND or clauses
supeersceeding section ND
Description of Query
NPCIL's Response
42
Delivery
As per Tender: Delivery for Unit III is 13 months and for Unit IV is Request not acceptable. Tender
Conditions shall prevail.
21 months. Is delivery for both units combined for 21 months is
acceptable.
43
44
45
Yes
Request not acceptable. Tender
Conditions shall prevail.
Kindly submit the bid in line with the
terms & conditions of Tender
document
Please refer cl. No. 9.0 of ITT.
Accordingly Prices are to be quoted
in Part-II (Price Bid) exclusive of all
taxes and duties. However Bidders
are required to furnish prevailing
rates of taxes and duties applicable in
Annexure-B of Part-I ( Technical and
Commercial except price)bid being
submitted by them.
46
47
48
49
50
51
10
Power Supply at Plant: What is the rate of Charges for unit power
supply at site?
Water and other resources: What is the rate of Charges for unit power
supply at site?
52
11
53
54
12
13
55
14
56
15
57
16
Page 3 of 7
58
17
Please specify any port near site, incase we transport tanks by sea.
Tuticorin
59
Clause No./Subject
Description Of Query
NPCIL's Response
Charges for Special Type Tests, Seismic Qualification /Testing shall not
be included in the price of the items and shall be quoted/ claimed
separately.
We request NPCIL to modify following payment terms-10% advance against bank guarantee of equivalent amount .
Against submission of Advance Bank Guarantee (ABG) of equivalent
amount valid till CDD plus three months claim period.
5% of PO Value on approval of Design,drawings, and Analysis part of
equipments.
25 % of PO Value against PO placed for procurement of Major Raw
material , receipt of major raw materials as defined and their approval
& Clearance to start fabrication work .
60
61
Billing Breakup
62
63
9.2.
If the vendor dispatches the SS Tanks from his work shop in sections
after payment of Taxes and duties on the full order value and the
sections are assembled at KKNPP 3&4 site , please confirm that the
purchaser will not deduct any tax at source towards income tax OR
Local VAT.
Description Of Query
NPCIL's Response
Tender Section
/Vollume Name
Clause No./Subject
64
Vol II
Yes
65
3.6 Subcontracting
Vol-I
66
Vol 1
Page 4 of 7
67
68
69
70
71
6.12 Foundations
Further, the Bottom plate shall be
supplied with necessary
temporary stiffening arrangement
to take care of Handling &
Erection loads till the final
erection.
Kindly clarify the requirements
The bottom support structure
made of carbon steel shall be
supplied loose.The bottom
support structure shall be welded
to the embedded plates provided
in the floor by the erection
agency of the tanks.
6.14.
All the Storage Tanks except, KPF
13, KPK 10 & GML 10 shall be
supported on Bottom grillage &
the Bottom plate/Annular plate
shall be continuously welded
from outside either to the
Embedded ring in Foundation or Kindly elaborate & clarify.
to I-beam framework.
The supporting details of the
individual equipments have been
provided in Datasheets.
Contractor/Vendor to ensure the
Bottom plate design based on this
provided information.
As per datasheet
7.2
Evener beams may be required
for handling the tanks during
erection stage. The same shall be
designed and supplied by the
We have not considered design and supply of evener beam however if
bidder. If the bidder feels evener
required we can Design , Testing /Analysis , and supply of evener beam
beam is not required, he should
on the basis of additional cost implication.
provide proper justification
supported with documents
related to load lifting/handling
details with calculations for the
approval of the purchaser.
Transportation .
taking necessary permits,
licenses, clearances of
obstruction in roads and any
other foreseen /unforeseen
hindrances faced during
transportation shall be resolved
by the contractor himself
Page 5 of 7
72
73
10
74
11
75
76
Vol 1
12
13
7.5
PWHT/Solution annealing
77
14
78
15
16
Insulation Requirements
Insulation applicability, Material,
& thickness for Tanks shall be as
We consider Insulation fixing will be done by other agency.
per respective Datasheet.
Kindly confirm the same.
Insulation clips/cleats on tanks
shall be provided by the
Contractor/Vendor.
80
17
81
18
79
Vol II section C1
Page 6 of 7
82
19
Description of Query
83
Volume
II/AnnexureB(page no.1/9
A463-000-16-46DS-4001
84
volume-I
Appendix-X Qualification
Requirements for bidders(point2- Can we outsource design & analysis work
b)
85
volume-II
Clause no.10
86
87
88
89
90
91
92
93
94
95
96
97
NPCILs Response
Section C1
Tender
Clause no.2.8 (special instruction
no.CMM\FTP\75to bidder)
00-11147volume II
Section C1
Tender
no.CMM\FTP\7500-11147volume II
Section C1
Tender
no.CMM\FTP\7500-11147volume II
Section C1
Tender
no.CMM\FTP\75- Clause no. 2.9/13.7
00-11147volume II
Section C1
Tender
no.CMM\FTP\7500-11147volume II
for site activity,please confirm tremporary road length ie. How many
kms to be made for approach at site
Please confirm total area of site where the tank will be install
Additional information from NPCIL: Following documents are enclosed with regards to the various technical queries.
1
A-463-000-16-46-DS-4013 Tank bottom support detail
2 Nozzle end details
3
Painting Specification I301.KK34.0.0.TH.TS.WD122
4 Digital seismic response spectra
5
Approved Vendor list
6 Revised datasheet as additional document
7 Additional design requirement for document no A-463-000-16-46-DS-4003
Page 7 of 7
28.02.2003
506
FSUE
"Atomenergoproekt"
Moscow 2002
w{tfls.eaFff{r{
ffiIre*:{KgLAftr}
TECIIHiCAI, SPEC{ffiCAI?ON FON SNOP &
f,{Cg }TS,
***,
i -f
iS
Frffin?*r{filfc
{ffi*d*its
*g$F$#n"pr.Ax:
Hm"ffi 34,S"$.?lt"?s.rA.81.t2
flq|$r 3f Ao#rfitap!
"atrfrrlt{G
ilh{rl*stWark
lvt*+$**ris* Srrrr*{*s
*dBJ
^f
g(*tBg - ag,,
-w'E &?tn'*vK tr{b sa*n w:ttwffi in {{tf *ltlil sli{l l84rftd 6fi*t*t{ttitls ta tl*
Eesf4sfion I rpknafi* MrF *rd h{er** ;imupfxd,
g*srs{r*tb'nHs:t{F#t
/*xHpF.a:&d/4$&}gxlW,frf
ryCgkeff*E.}t of
T::4M
*f*i
}a/p//t
Fercrilptlcn
vw
$f,gns
Wl#'#fif;,n
BSf
Ctpctedb
*{q
I5ffSJB/nGUS$ryl{
rE{cst
l-$-,a3{3
fi*
MTS$gMf;ff
A{E{$
3?,S3'lg
py{**-,**
^ewn#r$
A{r {#r5}
l6'3-i3
Site
ACE{CS
as&
fr!a*#rb
Slc
F*i*npsdby
Y
grds*a&#Afix?*rltAlt
ew$Ed!ry
$ir*
g SA}fiFNJE
Approwdfu
l?*
{,*see{
pF
{axi3&4}
r*{rwait)
13
u'&br.
tb-3.\1
#'8"t'rg
--@Xla.n'{L
HFCTL PRCIPRIETARY
T&i* d*a$na$r
$*
*, *y *d fuf#;6;;;y;;
februs{y. ZSl3
fitr
: ii of iii
: R0
: 25-03-2013
PAINTING
DATE OF ISSUE
R0
25.03.13
48
Dhananjay
25-03-2013
CHECKED BY
Satya Sridhar
25-03-2013
APPROVED BY
R Chaudhury
25-03-2013
Name
Sign
Date
Issued by
File Name
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
: iii of iii
: R0
: 25-03-2013
PAINTING
I301.KK34.0.0.TH.TS.WD122
TITLE
Description of Revision
R0/25.03.13
Checked By
Approved By
SATYA SRIDHAR
R CHAUDHURY
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: Page 1 of 45
REV. NO.
: R0
CONTENTS
SL.
NO
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
13.0
14.0
15.0
16.0
17.0
18.0
19.0
20.0
21.0
22.0
23.0
24.0
DESCRIPTION
PAGE
NO.
General.
Scope
Reference Codes & Standards....
Equipment
Surface Preparation, Shop Primer, Coating Application & Repair And
Documentation.
Paint Materials..
Shop & Field Painting System For Oil And Water Treatment Plant...............................
Coating System For Indoor Cs Pipes, Equipments & Supports Etc In Areas Other
Than Radio Active Zones.
Coating System For Indoor Metal Structures, Framed Pillers, Hand Rails, Ladders
And Crane Girders Etc In Areas Other Than Radio Active Zones..
Coating System For Indoor Cs Pipes, Equipments, Supports Etc. In Areas Of Radio
Active Zone.....................................................................................................................
Indoor Coating Systems For Metal Structures Of Roof Covering & Wall And Wall
Enclosures
Coating System For Outdoor Cs Pipes, Equipments & Supports Etc..............................
Internal & External Coating System For Embedded CS Ventilation Ducts in Both
Radioactive and Non-Radioactive Zones.........................................................................
Coating System For Roof & Roof Structures Exposed To Outdoor Climate..
External Coating Systems For Cs & Low Alloy Steel Storage Tanks.............................
Internal Coating Systems For Carbon Steel And Low Alloy Steel Storage Tanks..........
External Coating Systems Of Underground Carbon Steel Plant Piping And
Underground Vessels...
External Painting - Under Insulation for both Radioactive And Non-Radio Active
Areas...........................................................................................................
Storage.
Colour Code.
Inspection And Testing
Guarantee.
Qualification Criteria Of Painting Contractor/Sub-Contractor
Vendor Data Requirement
3
3
5
6
36
QC/001
6
16
24
25
25
26
26
26
27
27
28
29
30
31
32
32
32
33
33
34
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 2 OF 45
REV. NO.
: R0
ABBREVIATION:
CS
MS
SS
RCC
ETP
FRP
GRP
ASTM
ANSI
ISO
NACE
SSPC
DFT
WFT
DM
TSAC
ASME
BS
AWS
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
Carbon Steel
Mild Steel
Stainless Steel
Reinforced Cement Concrete
Effluent Treatment Plant
Fibre Reinforced Plastic
Glass Reinforced Plastic
American Society for Testing and Materials
American National Standard Institution
International Organization for Standardization
National Association of Corrosion Engineers
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 3 OF 45
REV. NO.
: R0
1.0
GENERAL
1.1
This technical specifications shall be applicable for the work covered by the contract, and
without prejudice to the provisions of various codes of practice, standard specifications etc.
It is understood that contractor shall carry out the work in all respects with the best quality
of materials and workmanship and in accordance with the best engineering practice and
instructions of Engineer-In-Charge.
1.2
2.0
SCOPE
This specification defines the requirements for surface preparation, selection and
application of primers and paints on external surfaces of equipment, vessels, machinery,
piping, ducts, steel structures, external & internal protection of storage tanks for all services
and chimneys if any. The items listed in the heading of tables of paint systems is indicative
only, however, the contractor is fully responsible for carrying out all the necessary
painting, coating and lining on external and internal surfaces as per the tender and technical
requirement.
2.2
2.2.1
Extent of Work
The following surfaces and materials shall require shop, pre-erection and field painting:
A
All un insulated Carbon Steel, Alloy Steel, Stainless Steel Equipments, vessels,
Columns, Storage Tanks and Exchangers (if any) and parts of boilers etc.
All uninsulated Carbon Steel, Alloy Steel and Stainless Steel plant and related
piping, fittings and valves (including painting of identification marks), furnace
ducts and stacks etc.
All insulated parts of vessels, boilers, chimneys, stacks, piping and steam piping
and if any other insulated items present
All items contained in a package units, desalination plant, chiller package and Oil
& Water treatment package etc as necessary.
All structural steel work, pipe, structural steel supports, walkways, handrails,
ladders, platforms etc.
Flare lines, external surfaces of MS chimney with or without refractory lining and
internal surfaces of MS chimney without refractory lining. (If present)
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 4 OF 45
REV. NO.
: R0
2.2.2
H.
Supply of all primers, paints and all other materials required for painting
Painting under insulation for carbon steel, alloy steel and stainless steel as
specified.
Repair work of damaged pre-erection/ fabrication and shop primer and weld
joints in the field/site before and after erection as required.
All CS Piping, equipments, storage tanks and internal surfaces of RCC tanks in
ETP/ water and oil treatment plants.
The following surfaces and materials shall not require painting in general. However, if
there is any specific requirement by the NPCIL, the same shall be painted as per the
relevant specifications:
A
Plastic and/or Plastic coated materials colour of plastic shall be as per the colour
code. If not matching painting/ tapping may be required for identification.
FRP/GRP piping and tanks colour shall be as per the applicable colour coding. If not
matching painting/ tapping may be required for identification
2.3
Documents
2.3.1
The contractor shall perform the work in accordance with the following documents
developed by him and accepted by the Purchaser.
a.
b.
c.
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 5 OF 45
REV. NO.
: R0
2.4
Unless otherwise instructed, final painting on pre-erection/ shop primed pipes and
equipments shall be painted in the field, only after the mechanical completion, testing on
systems are completed as well as after completion of steam purging wherever required.
2.5
Changes and deviations required for any specific job due to Purchasers requirement or
otherwise shall be referred to Purchaser for deviation permit.
3.0
3.1
Without prejudice to the provision of Clause 1.1 above and the detailed specifications of
the contract, latest editions of the following codes and standards are applicable for the work
covered by this contract.
IS-5
RAL DUTCH
IS-101
IS-2379
ASTM-Vol 6.01 & 6.03
ASA A 13.1-1981
Colour coding.
International Standard for colour shade (Dutch Standard)
Methods of test for ready mixed paints and enamels.
Indian Standard for Pipe line identification-colour code.
American standard test methods for Paints and Coatings.
Scheme for identification of piping systems: American
National Standards Institution.
IO1.KK.0.0.QA.QAD.WD009: NORMs for Piping & equipment identification and colour
coding
3.2
:
:
:
:
:
:
3.2.1
ISO 8501-1/SIS-05 59 00: ISO standard for Preparation of steel substrates before application
of paints and related products. This standard contains photographs of the various standards
on four different degrees of rusted steel and as such is preferable for inspection purpose by
the Engineer-In-Charge.
3.2.2
3.2.3
3.2.4
Various International Standards equivalent to Swedish Standard for surface preparations are
given in Table-I.
3.3
The contractor shall arrange, at his own cost, to keep a set of latest edition of above
standards and codes at site.
3.4
The paint manufacturer's instructions shall be followed as far as practicable at all times for
best results. Particular attention shall be paid to the following:
a.
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 6 OF 45
REV. NO.
: R0
b.
Surface preparation prior to painting shall be followed as per Table 8.0 to 16.0 of
this standard shall be followed.
c.
d.
4.0
EQUIPMENT
4.1
All tools, brushes, rollers, spray guns, blast material, hand power tools for cleaning and all
equipments, scaffolding materials, shot & grit blasting equipments & air compressors etc.
required to be used shall be suitable for the work and all in good order and shall be
arranged by the contractor at site and in sufficient quantity. The manufacturers test
certificates / data sheets for all the above items shall be reviewed by Engineer-in-charge at
site before start of work.
4.2
Mechanical mixer shall be used for paint mixing operations in case of two pack systems
except that the Engineer-In-Charge may allow the hand mixing of small quantities at his
discretion in case of specific requirement for touch up work only.
5.0
5.1
General
5.1.1
In order to achieve the maximum durability, one or more of following methods of surface
preparation shall be followed, depending on condition of surface to be painted and as
instructed by Engineer-In-Charge. Adhesion of the paint film to surface depends largely on
the degree of cleanliness of the metal surface. Proper surface preparation contributes more
to the success of the paint protective system.
5.1.2
a.
b.
c.
Blast cleaning.
Mill scale, rust, rust scale and foreign matter shall be removed fully to ensure that a clean
and dry surface is obtained. Unless otherwise specified, surface preparation shall be done
as per provisions of relevant tables given elsewhere in this specification. The minimum
acceptable standard in case of manual or hand tool cleaning shall be St. 2 or equivalent, in
case of mechanical or power tool cleaning it shall be St. 3 or equivalent, in case of blast
cleaning it shall be Sa 2-1/2 as per Swedish Standard SIS-055900 (latest edition) or SSPCSP or ISO 8501-01. Blast cleaning shall be Sa 3 as per Swedish Standard in case of highly
corrosive environment.
Remove all other contaminants, oil, grease etc. by use of an aromatic solvent prior to
surface cleaning.
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 7 OF 45
REV. NO.
: R0
5.1.3
Irrespective of whether external or internal surface to be coated, blast cleaning shall not be
performed where dust can contaminate surfaces undergoing such cleaning or during humid
weather conditions having humidity exceed 85%. Desiccant type de-humidifiers shall be
used to maintain the RH during abrasive blast cleaning and the application of coating
materials. For internal coating of storage tanks the RH shall be maintained less than 60%
and air temperature inside the tank shall be maintained at 25-40 deg C. Dehumidifier
should depress the dew point of air in the enclosed space, sufficient enough so as to
maintain it 3C below the metal substrate temperature during centre period of blasting and
coating application. During the interval time between application of primer coat and
subsequent intermediate and top coats or between blast cleaning completion and start of
application of primer coat, dehumidifier unit should be in continuous operation to ensure
that no condensation occurs on substrate.
Dehumidifier should be able to maintain grain drop (moisture removal) at the rate of 25
grains per pound of air per hour. Dehumidifier should have capacity of at least 2 air
changes per hour of the enclosed space. All necessary psychometric data should be
collected by contractor for the given site conditions before starting operation of
dehumidifier to ensure that desired values of dew point, moisture content in enclosed scope
is achieved.
Dehumidification to be maintained round the clock for surface preparation and painting till
the total coating application is over.
Dehumidifier shall not be stopped under any condition till the entire blasted surface is
primed to the satisfaction of the technical representative of the paint manufacturer
interested with quality assurance for the work. In case the dehumidifier breaks down in
middle of the job, the same shall be replaced at the risk and the cost of the contractor and
the entire unfinished work shall be repeated.
The Engineer in-charge shall have the right to disallow usage of dehumidifier if the
performance is not meeting the specified requirements. Under such circumstances the
contractor shall remove the equipment and replace the same with another equipment to
provide satisfactory results without any additional cost to the owner.
5.1.4
Irrespective of the method of surface preparation, the first coat of primer must be applied
by airless spray/ air assisted conventional spray if recommended by the paint manufacturer
on dry surface. This should be done immediately and in any case within 4 hours of cleaning
of surface. However, at times of unfavourable weather conditions, the Engineer-In-Charge
shall have the liberty to control the time period, at his sole discretion and/or to insist on recleaning, as may be required, before primer application is taken up. In general, during
unfavourable weather conditions, blasting and painting shall be avoided as far as
practicable.
5.1.5
The external surface of R.C.C. chimney to be painted shall be dry and clean. Any loose
particle of sand, cement, aggregate etc. shall be removed by scrubbing with soft wire brush.
Acid etching with 10-15% HCL solution for about 15 minutes shall be carried and surface
must be thoroughly washed with water to remove acid & loose particles and then dried
completely before application of paint.
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 8 OF 45
REV. NO.
: R0
5.2
5.2.1
5.2.2
5.2.3
b.
Hand scraping
c.
Rust, mill scale spatters, old coatings and other foreign matter, shall be removed by
hammering, scrapping tools, emery paper cleaning, wire brushing or combination of the
above methods. On completion of cleaning, loose material shall be removed from the
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 9 OF 45
REV. NO.
: R0
surface by clean rags and the surface shall be bushed, swept, dusted and blow off with
compressed air/steam to remove all loose matter. Finally the surface may be washed with
water and dried for effective cleaning.
5.3
5.4
Shop coated (coated with Primer & finishing coat) equipment should not be repainted
unless paint is damaged. Repair shall be carried out as per Table 7.1 of paint systems
depending upon compatibility of paint.
5.5
Shop primed equipment and surfaces will only be 'spot cleaned' in damaged areas by means
of power tool brush cleaning or hand tool cleaning and then spot primed before applying
one coat of field primer unless otherwise specified. If shop primer is not compatible with
field primer then shop coated primer should be completely removed before application of
selected paint system for particular environment.
5.6
For Package units/equipment, shop primer should be as per the paint system given in this
specification. However, manufacturers standard can be followed after review.
5.7
5.7.1
Surface shall not be coated in rain, wind or in environment where injurious airborne
elements exists, when the steel surface temperature is less than 5 oF above dew point when
the relative humidity is greater than 85% or when the temperature is below 40oF and when
the ambient/substrate temp is below the paint manufacturers recommended temperature of
application and curing. De-humidifier equipment shall be used to control RH and Dew
point. The paint application shall not be done when the wind speed exceeds 20KM per
hour.
5.7.2
Blast cleaned surface shall be coated with one complete application of primer as soon as
practicable but in no case later than 4 hrs the same day.
5.7.3
To the maximum extent practicable, each coat of material shall be applied as a continuous
film uniform thickness free of probes. Any spots or areas missed in application shall be
recoated and permitted to dry before the next coat is applied. Applied paint should have
the desired wet film thickness.
5.7.4
Each coat shall be in proper state of cure or dryness before the application of succeeding
coat. Material shall be considered dry for recoating when an additional coat can be applied
without the development of any detrimental film irregularities, such as lifting or loss of
adhesion of the under coat. Manufacturer instruction shall be followed for inter coat
interval.
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 10 OF 45
REV. NO.
: R0
5.7.5
When the successive coat of the same colour have been specified, alternate coat shall be
tinted, when practical, sufficiently to produce enough contrast to indicate complete
coverage of the surface. The tinting material shall be compatible with the material and not
detrimental to its service life and shall be recommended by the original paint manufacturer.
5.7.6
The equipment used shall be suitable for the intended purpose, shall be capable of
properly atomizing the paint to be applied, and shall be equipped with suitable
pressure regulators and gauges. The air caps, nozzles, and needles shall be those
recommended by the manufacturer of the equipment for the material being
sprayed. The equipment shall be kept in satisfactory condition to permit proper
paint application.
b.
Traps or separators shall be provided to remove oil and condensed water from the
air. These traps or separators must be of adequate size and must be drained
periodically during operations. The air from the spray gun impinging against the
surface shall show no condensed water or oil.
c.
Ingredients shall be kept properly mixed in the spray pots or containers during
application by continuous mechanical agitation.
d.
The pressure on the material in the pot and of the air at the gun shall be adjusted
for optimum spraying effectiveness. The pressure on the material in the pot shall
be adjusted when necessary for changes in elevation of the gun above the pot.
The atomizing air pressure at the gun shall be high enough to properly atomize
the paint but not so high as to cause excessive fogging of paint, excessive
evaporation of solvent, or less by over spray
e.
Spray equipment shall be kept sufficiently clean so that dirt, dried paint, and other
foreign materials are not deposited in the paint film.
Any solvents left in the equipment shall be completely removed before applying
paint to the surface being painted.
f.
Paint shall be applied in a uniform layer, with overlapping at the edge of the spray
pattern. The spray patterns shall be adjusted so that the paint is deposited
uniformly. During application, the gun shall be held perpendicular to the surface
and at a distance which will ensure that a wet layer of paint is deposited on the
surface. The trigger of the gun should be released at the end of each stroke.
g.
All runs and sags shall be brushed out immediately or the paint shall be removed
and the surface repainted.
h.
Areas inaccessible to the spray gun shall be painted by brush; if not accessible by
brush, daubers or sheepskins shall be used.
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 11 OF 45
REV. NO.
: R0
5.7.7
i.
j.
Edges of structural shapes and irregular coated surfaces shall be coated first and
an extra pass made later.
k.
Airless spray application shall be in accordance with the following procedure: as per steel
structure paint Manual Vol.1 & Vol.2 by SSPC, USA, Air less spray relies on hydraulic
pressure rather than air atomization to produce the desired spray. An air compressor or
electric motor is used to operate a pump to produce pressures of 1000 to 6000 psi. paint is
delivered to the spray gun at this pressure through a single hose within the gun, a single
paint stream is divided into separate streams, which are forced through a small orifice
resulting in automization of paint without the use of air. This results in more rapid
coverage with less over spray. Airless spray usually is faster, cleaner, more economical
and easier to use than conventional air spray.
Airless spray equipment is mounted on wheels, and paint is aspirated in a hose that sucks
paint from any container, including drums. The unit shall have in built agitator that keep
the paint uniformly mixed during the spraying. The unit shall consist of in built strainer.
Usually very small quantity of thinning is required before spray. In case of high build
epoxy coating (two pack). 30:1 pump ratio and 0.020-0.023 tip size will provide a good
spray pattern. Ideally fluid hoses should not be less than 3/8 ID and not longer than 50 ft
to obtain optimum results.
In case of gun choking, de-choking steps shall be followed immediately.
5.7.8
Brushes shall be of a style and quality that will enable proper application of paint.
b.
Round or oval brushes are most suitable for rivets, bolts, irregular surface, and rough
or pitted steel. Wide flat brushes are suitable for large flat areas, but they shall not
have width over five inches.
c.
d.
e.
f.
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 12 OF 45
REV. NO.
: R0
5.7.9
5.7.10
For each coat the painter should know the WFT corresponding to the specified DFT and
standardize the paint application technique to achieve the desired WFT. This has to be
ensured in the qualification trial.
5.8
5.8.1
No coat shall be applied until the preceding coat has dried. The material shall be
considered dry for re-coating when another coat can be applied without the development of
any film irregularities such as lifting or loss of adhesion of undercoats. Drying time of the
applied coat should not exceed maximum specified for it as a first coat; if it exceeds the
paint material has possibly deteriorated or making is faulty.
5.8.2
No paint shall be force dried under conditions which will cause chalking, wrinkling,
blistering formation of pores, or detrimentally affect the conditions of the paint.
5.8.3
No drier shall be added to a paint on the job unless specifically called for in the
manufacturers specification for the paint.
5.8.4
Paint shall be protected from rain, condensation, contamination, snow and freezing until
dry to the fullest extent practicable.
5.9
5.9.1
Where paint has been damaged in handling and in transportation, the repair of damaged
coating of pre-erection / fabrication and Shop primer shall be done as given below and as
per the Table 7.1 of this specification.
5.9.2
Repair of damaged inorganic zinc silicate primer after erection / welding in the design
temperature of -90oC to 550oC.
Surface Preparation: Quickly remove the primer from damaged area by mechanical
scraping and emery paper conforming to SSPC-SP-3 to expose the white metal. Blast clean
the surface, if possible. Feather the primed surface over the intact adjacent surface
surrounding the damaged area by emery paper.
Primer coating: One coat of F-9 shall be applied wherever damaged was observed on preerection pre fabrication / shop primer of inorganic zinc silicate coating (F-9). F-9 shall not
be applied if damaged area is not more than 5x5 cm.
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 13 OF 45
REV. NO.
: R0
5.10
Paint Application
5.10.1
Shop priming/pre-erection priming with F9 or F12 shall be done only on blasted surface
(SSPC-SP-10)
5.10.2
Shop priming/ pre-erection priming with F9 or F12 shall be done only with airless spray.
5.10.3
For large flat surface field painting shall be done by airless spray otherwise brush can be
used.
5.10.4
5.11
Documentation
5.11.1 A written quality plan with procedure for qualification trials and for the actual work.
5.11.2 Daily progress report with details of weather conditions, particular of applications, no of
coats and type of materials applied, anomalies, progress of work versus program.
5.11.3 Results of measurement of temperatures relative humidity, surface profile, film thickness,
holiday detection, adhesion tests with signature of appropriate authority.
5.11.4 Particulars of surface preparation and paint application during trials and during the work.
5.11.5 Details of non-compliance, rejects and repairs.
5.11.6 Type of testing equipments and calibration.
5.11.7 Code and batch numbers of paint materials used.
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 14 OF 45
REV. NO.
: R0
SL.
NO. DESCRIPTION
1
Manual or
cleaning
hand
ISO 8501-1/
SIS-05 59 00
SSPC-SP, USA
REMARKS
NACE, USA
tool
SSPC-SP-2
--
SSPC-SP-3
--
This
method
is
applied when the
surface is exposed to
normal atmospheric
conditions
when
other
methods
cannot be adopted
and also for spot
cleaning
during
maintenance
painting.
3.1
SSPC-SP-5
NACE#1
3.2
Where extremely
clean surface can be
expected for prolong
life of paint system.
SSPC-SP-10
NACE#2
The
minimum
requirement
for
chemically resistant
paint systems such
as epoxy, vinyl,
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 15 OF 45
REV. NO.
: R0
SL.
NO. DESCRIPTION
SSPC-SP, USA
REMARKS
NACE, USA
3.3
Commercial Blast
SA 2
SSPC-SP-6
NO.3
3.4
SSPC-SP-7
NO.4
polyurethane based
and inorganic zinc
silicate paints, also
for
conventional
paint systems used
under
fairly
corrosive conditions
to obtain desired life
of paint system.
For steel required to
be painted with
conventional paints
for exposure to
mildly corrosive
atmosphere for
longer life of the
paint systems.
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 16 OF 45
REV. NO.
: R0
6.0
PAINT MATERIALS
Paint manufacturers shall furnish the characteristics of all paints materials on original printed
literature, along with the test certificate for all specified characteristics given in this
specification. All the paint materials shall be of first quality and suitable for the service life
of about 15 years. They shall conform to the following general characteristics as per the
tables 6.1, 6.2, 6.3, 6.4 and 6.5.
CARBOZINC
11 SG
Solvent
base
Inorganic Zinc
Primer
INTERGARD
251
Two Pack Zinc
Phosphate
Primer
An
inorganic
zinc
basecoat
that
protects
steel
galvanically.
This is the first
self
curing
inorganic zinc
primer
Two pack
primers,
anticorrosive
primer/undercoat
pigmented with
Zinc Phosphate
79 2
63 2
50-75
50-75
8.2
8.40
45 minutes
20 minutes
3 hrs.
18 hrs
Min.: 8 hrs
8 hrs
6 hrs
399 Deg C
(Continuous)
427 Deg C
(Intermittent)
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 17 OF 45
REV. NO.
: R0
INTERZINC
42
Two
component
metallic zinc
primer
Type and
composition
A
two
component
metallic zinc
primer,
designed for
use
in
maintenance
situations and
as a primer at
new
construction.
Volume Solids
(minimum.) %
DFT (Dry Film
thickness) per
coat (minimum)
microns
Theoretical
covering
capacity in
M2/coat/litre
(minimum)
Weight per litre
in kg/litre
(minimum)
Touch dry at
30oC
Hard dry at 30oC
(max)
Full cure at 30oC
(for immersion/
high temperature
service)
Over-coating
interval at 30 oC
Pot life (approx.)
at 30oC for two
component
60 2
7
8
9
10
INTERTHANE
-990
Two component
acrylic
polyurethane
INTERTHERM
- 50
High temperature
Silicone
Aluminium Paint
A
two
component
acrylic
polyurethane
finish
giving
excellent
durability and
long
term
recoatability
A
single
component, high
temperature
coating, based on
a moisture curing
silicone
binder
and
pigmented
with aluminium
flake.
55
INTERLINE
850
Two
component
high
build
epoxy
phenolic lining
A
two
component,
chemically
resistant, high
solids,
high
build
epoxy
lining
to
provide
corrosion
protection for
the internals of
steel storage
tanks.
76
57 3
45
50
50-75
100-150
50-75
25
12
7.303
6.1
11.40
18.0
2.0
1.6
1.2
1.1
30 min .
45 minutes
5 hours
90 minutes.
30 minutes
60 minutes
150 minutes
8 hours
6 hrs
2 hours
2 hrs (min.)
8 hrs (min.)
6 hrs
12 hours (min.)
10 hrs.
10 hrs
1 hour
2 hrs
NA
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
11
PAGE NO.
: 18 OF 45
REV. NO.
: R0
paints
(minimum)
Temperature
Resistance
(minimum)
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 19 OF 45
REV. NO.
: R0
EPILUX 155
EPILUX 13
HB MIO
Two pack high Two pack high
build epoxy
build
epoxy
resin cured with primer
amine adduct
Volume Solids
(minimum) %
DFT (Dry Film
thickness) per coat
(minimum)
Theoretical covering
capacity in M2/coat/
litre (minimum)
Weight per litre in
kg/litre (minimum)
Touch dry at 30oC
(maximum)
Hard dry at 30oC
(maximum)
Full cure 30oC (for
immersion /high
temperature service)
Over-coating
interval
Pot life at 30oC for
two component
paints (minimum.)
Temperature
Resistance (min)
6
7
8
9
10
11
EPILUX 4 CR
Two pack high
performance
epoxy top coat
EPILUX 78
HBTL
Two pack high
build
epoxy
primer
cured
with
amine
adduct
A self priming
high build high
performance
tank
liner
specially
designed
for
sustained
immersion
service.
50-60
50-75
25-35
100-150
7.8-9.4
6.7-10
11.7-16.4
3.7-5.5
3-4 hrs
1-2 hrs
2-3 hrs
2-3 hrs
overnight
overnight
Overnight
overnight
Min.: overnight
Max.: 5 days
4-6 Hrs
Min.:Overnight Min.:Overnight
Max.: Indefinite Max.: 5 days
6-8 hrs.
4-6 hrs
Min.: Overnight
Max.: 5 days
6-8 hrs.
93 Deg C
(Continuous)
120 Deg C
(Intermittent)
93 Deg C
(Continuous)
120 Deg C
(Intermittent)
93 Deg C
(Continuous)
120 Deg C
(Intermittent)
93 Deg C
(Continuous)
120 Deg C
(Intermittent)
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 20 OF 45
REV. NO.
: R0
Volume Solids
(minimum.) %
DFT (Dry Film
thickness) per coat
(minimum) microns
Theoretical covering
capacity in m2/coat/litre
(minimum)
Weight per litre in
kg/litre (minimum)
Touch dry at 30oC
Hard dry at 30oC (max)
Full cure at 30oC (for
immersion/ high
temperature service)
Over-coating interval at
30 oC
Pot life (approx.) at 30oC
for two component
paints (minimum)
Temperature Resistance
(minimum)
6
7
8
9
10
11
INTERGARD
475 HS
High
solids,
high build, two
component
epoxy coating
A low VOC,
high solids, high
build, two
component
epoxy coating.
Available with
conventional
pigmentation, or
alternatively can
be pigmented
with micaceous
iron oxide to
provide
enhanced
overcoating
properties.
INTERGARD
740
Two component
epoxy
finish
coat
PROTECTOMASTIC
Two pack high
build
epoxy
resin
EPILUX 4 Z88
High
performance
epoxy primer
A tough twocomponent,
epoxy based
finish with good
abrasion and
chemical
resistance.
Intergard 740 is
suited to interior
surfaces needing
a hard, easily
cleaned surface
High
performance
epoxy
primer
heavily loaded
with
metallic
zinc,
imparts
excellent
cathodic
protection when
applied
over
blast
cleaned
steel.
80
523
A low VOC,
two component,
flexible high
build surface
tolerant coating
with reinforced
with Aluminium
and special
MicaciousIron-Oxide
pigments
for
improved
corrosion
resistance and
extended
temperature
resistance
-
100 - 200
50
100-150
35-50
6.40
10.4
5.7-8.5
9.0-12.8
2.1
1.2-1.5
60 minutes.
5 hrs
2 hrs
8 hrs
2-3 hrs
overnight
15-30 minutes
4-6 hrs
5 hrs
Min.: 16 hrs.
60 minutes.
3 hrs
120 Deg C
(Continuous)
150 Deg C
(Intermittent)
200 Deg C
(Continuous)
300 Deg C
(Intermittent)
March 2013
PAGE NO.
: 21 OF 45
REV. NO.
: R0
Volume Solids
(minimum.) %
DFT (Dry Film
thickness) per coat
(minimum) microns
Theoretical covering
capacity in m2/coat/litre
(minimum)
Weight per litre in
kg/litre (minimum)
Touch dry at 30oC
Hard dry at 30oC (max)
Full cure at 30oC (for
immersion/ high
temperature service)
Over-coating interval at
30 oC
Pot life (approx.) at 30oC
for two component
paints (minimum)
Temperature Resistance
(minimum)
6
7
8
9
10
11
EPILUX 4
100-150
100-150
125-150
6.0
7.2
30 minutes
4 hrs
1.5 hrs
4 hrs
4 hrs
6 hrs
24 hrs
Min.: 8hrs.
Max.: 3 days
3 Hrs.
24 hrs
2 hrs.
3 hrs
4 hrs
150oC
Dry service
121 Deg C
(Continuous)
149 Deg C
(Intermittent)
82 Deg C
(Continuous)
121 Deg C
(Intermittent)
5 days
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 22 OF 45
REV. NO.
: R0
TABLE NO. 6.6: Summary of Painting systems elaborated later in this document:
Sr.
No.
1
Item description
Painting system
Up to 80
DFT/coat +
EPILUX 4 CR @75 DFT/coat
(Berger)
81 to 400
INTERZINC 42@
50-75 DFT/coat + 2 coats of
INTERTHERM 50 @ 25
DFT/coat
Indoor coating system for Metal
2 coats of EPILUX 78 HBTL
structures of roof covering &
@100 DFT/coat
wall and wall enclosures
Outdoor CS pipes, equipments & INTERGARD 475 HS @150
supports etc
DFT/coat +
INTERTHANE 990 @ 50
DFT/coat
Internal & external coating High build Epoxy @ 125
system for Embedded CS DFT/coat
Reference
Table 7
Table 8
Table 9
Table 10
Table 11
Table 12
Table 13
March 2013
PAGE NO.
: 23 OF 45
REV. NO.
: R0
Sr.
No.
Item description
Painting system
Reference
ventilation
ducts
in
both Recommended products
radioactive and non-radioactive Protectomastic HB (Berger)
zones
Amercoat-90 (Goodlass Nerolac)
Carbo Line-890 (CDC Carboline )
OR
CARBOMASTIC
CARBOLINE-890
(CDC Carboline)
10
11
12
13
15/AL
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 24 OF 45
REV. NO.
: R0
Table 7.0
Sl.
No.
7.1
7.2
SYSTEM
FOR
OIL
AND
WATER
Total
DFT in
Surface Preparation
Remarks
Intermediate/F Microns
Primer
(min.)
inish Coat
For External Surfaces of C.S./M.S. items: Screens, Walk way bridges, Baffles, Dual media filters,
Vertical pumps, piping in treated effluent sump, bio sludge pump, Screw pump and pump house, CS
tanks, sumps and vessels etc.
INTERGARD4
Equivalent
75 HS @150
INTERZINC-42
systems from
DFT/coat
@ 65-75
Berger, CDC
+
-14 to 80
SSPS-SP-10
DFT/coat
Carboline,
INTERTHANE
Good lasss-990@50
(akzo nobel)
Nerolac are
DFT/coat
acceptable
(akzo nobel)
Coating System
Design Temp.
in oC
For Internal Surfaces of CS/MS Items: Bio-sludge sump, Filter feed sump, Process sump, Sanitary
sump, Transfer sump, Sludge, oil tanks, scrapping mechanism in Clarifier etc
-14 to 80
SSPS-SP-10
ZINC ANODE
304 @ 65-75
DFT/coat.
Equivalent
systems from
Berger, CDC
3 coats of
EPILUX 155
Carboline,
HB MIO
365-375 Good lasss@125
Nerolac are
DFT/coat
acceptable
Note:1
7.3
All R.C.C./concrete surfaces exposed to effluent water / liquid such as tanks, structures, drains etc. in
Process sump, TPI separator (Process and Oil), Aeration Tank and Transfer sump etc.
-14 to 80
7.4
Blast
cleaning
to
SSPC-SP guide lines
and Acid etching with
10-15% HCl acid
followed by thorough
water washing.
3mm
Epoxy screed
lining shall be
applied as per
manufacturer
and Engineerin-Charge
instructions
4.5mm
Natural
Rubber lining
shall be
applied as per
specific
manufacturer
and Engineerin-Charge
instructions
Up to 60
SSPC-SP-10
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 25 OF 45
REV. NO.
: R0
Note 1: The paint /coating manufacturers shall provide their Quality control test certificate of coating
materials for immersion service of the exposed effluents
TABLE 8.0
Sl.
No.
8.1
Design
Temperature.
in oC
Up to 80
TABLE 9.0
Sl.
No.
Surface
Preparation/
Primer
remarks
Total DFT
in Microns
(min.)
SSPC-SP-10
Equivalent
systems from
Akzo
nobel,
CDC
Carboline,
Good
lasssNerolac
are
acceptable
Design
Temperature.
in oC
Surface
preparation
/ Primer
Remarks
Total DFT
in Microns
(min.)
9.1
Alter
nate
Up to 80
SSPC-SP-10
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 26 OF 45
REV. NO.
: R0
TABLE 10.0
Sl.
No.
10.1
10.2
Design
Temperature.
in oC
Up to 80
11.1
Sl.
No.
12.1
Up to 80
SSPC-SP-10;
INTERZINC
42@
50-75 DFT/coat
(International)
Surface
Preparation
SSPC-SP-10
Equivalent
systems
from
Akzo nobel, CDC
Carboline, Good
lasss- Nerolac are
acceptable
Primer
Total DFT
in Microns (min.)
ZINC
ANODE 2 coats of EPILUX 78 HBTL 265
304@65
@100 DFT/coat
DFT/coat
Design
Temperature.
in oC
Up to 80
Remarks
Total DFT
in Microns (min.)
Design
Temperature.
in oC
TABLE 12.0
Surface
preparation/
Primer
ZINC
ANODE
304@65
DFT/coat
(Berger)
81 to 400
TABLE 11.0
Sl.
No.
Surface
Preparation
SSPC-SP-10
Primer
Total DFT
in Microns (min.)
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 27 OF 45
REV. NO.
: R0
TABLE 13.0
Design
Temperat
ure. in oC
Surface
Preparation
Primer
13.1
Up to 80
SSPC-SP-10
Inorganic
Zinc
Silicate@65-75
DFT/coat
Recommended
Prodcuts
Zinc
Anode304(Berger)
Dimet
coat
-6
(Goodlass Nerolac)
Carbo Zinc -11 SG
(CDC Carboline)
13.2
Up to 80
SSPC-SP-3
CARBOMASTIC
15/AL
(CDC Carboline)
Sl.
No.
Intermediate + Finish
coat
Total
DFT
in
Microns
(min.)
Remark
TABLE 14.0
Sl.
No.
14.1
CARBOLINE-890
(CDC Carboline)
For
wire
brush cleaned
surfaces
Design
Temperature.
in oC
Up to 80
Surface
Preparation
SSPC-SP-10
Primer
Total DFT
in Microns (min.)
NOTES:
1.
The list of items given in the heading of the above table is not exhaustive. There may be more
items for a particular contract where these specifications are used. The Contractor is fully
responsible for completing painting including prefabrication primer for all the items supplied
and fabricated through his scope of work as per tender document.
2.
If the Pre-erection/Pre-fabrication & Shop Primer has already been completed, the same shall
not be repeated again in the field. In case the damages of primer are severe and spread over
large areas, the engineer-in-charge may decide & advise re-blasting and priming again.
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 28 OF 45
REV. NO.
: R0
3.
In case of shop Primer is not applicable, the same shall be applied as field primer without
altering subsequent coating systems
TABLE 15.0
Design
Temperature
in deg. C
Sl.
No.
Surface
Preparati
on
Finish paint
Total Final
DFT
in Microns
(min.)
Remarks
15.1
All external surfaces of shell, wind girders, appurtenances, roof tops of all above ground tanks
including top side of floating roof of open tank as well as covered floating roof tank and associated
structural works of DM water, firewater, raw water, potable water, acids, alkalis, solvents and
chemicals etc.
15.1.1
-14 to 80
SSPC-SP10
INTERZINC-42 @ 6575
DFT/coat
+
INTERGARD
251@
50 DFT/ coat
2 coats of INTERGARD
475 HS @ 100 DFT
/coat + INTERTHANE
990 @ 50 DFT/ coat;
(Akzo Nobel)
(Akzo Nobel)
INTERLINE 850 @
75 DFT/ coat
2 coats of INTERLINE
850 @ 75 DFT/ coat +
INTERTHANE 990 @
50 DFT/ coat;
(Akzo nobel)
(Akzo nobel)
15.1.2
Note 1
280
81 to 100
SSPC-SP10
(Note 2)
15.2
External surfaces of bottom plate (soil side) for all storage tanks.
15.2.1
-14 to 80
15.2.2
345-355
81 to100
SSPC-SP10
SSPC-SP10
(Note 2 )
Note 1
INTERZINC-42 @
65-75 DFT/ coat
3
coats
of 365-375
INTERGARD 475 HS
@ 125 DFT /coat
Note 1
(Akzo nobel)
INTERLINE 850 @ 75
DFT/ coat
(Akzo nobel)
2 coat of INTERLINE
850@75 DFT/coat
Note 1
(Akzo nobel)
(Akzo nobel)
225
NOTES
1. Equivalent coating systems from M/s Berger, M/s CDC Carboline, M/s Goodlass- Nerolac
are acceptable
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 29 OF 45
REV. NO.
: R0
TABLE 16.0
Sl.
No.
16.1
Design
Temperature
in oC
Surface
Preparation
Finish paint
Total
Final DFT
in Microns
(min.)
Remarks
16.3
Internal surfaces of Diesel oil tanks including underside of floating roof, internal surface of cone roof,
bottom plate, oil side surfaces of deck plates, oil side surfaces of pontoons, roof structures, structural steel,
ladders and supports etc.
-14 to 80
SSPC-SP-10 INTERLINE-850 @ 2 coats of
225-250
Equivalent
75 DFT/coat
INTERLINE 850@
system from
75 DFT /coat
Berger, CDC
carboline,
(Akzo Nobel)
(Akzo Nobel)
goodlassnerolac are
acceptable
Internal surfaces of fixed roof type storage tanks of Potable water
-14 to 80
SSPC-SP-10 EPILUX 13 @50
2 coats of
300-325
Equivalent
DFT/coat;
PROTECTMASTC @
system from
(Berger)
125 DFT/ Coat;
Akzonobel,
(Berger)
CDC
carboline,
Note : test certificate is
goodlassrequired for potable
nerolac are
water application
acceptable
De-mineralized water (DM) Internal shell, bottom plate & all accessories
INTERLINE-850 @ 2 coats of
225-250
Up to 80
SSPC-SP-10 75 DFT/ coat
INTERLINE-850 @
75 DFT/coat
(Akzo Nobel)
(Akzo Nobel)
10 % Hydrochloric acid (HCl) Internal shell, bottom plate & all accessories
16.3.1
-14 to 60
16.4
16.4.1
Aggressive Solvents
16.1.1
16.1
16.1.1
16.2
16.2.2
-14 to 65
SSPC-SP-10
SSPC-SP-10
None
INTERLINE-850 @
75 DFT/ coat
2 coats of
INTERLINE-850 @
75 DFT/coat
(Akzo Nobel)
4.5 mm
225-250
(Akzo Nobel)
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 30 OF 45
REV. NO.
: R0
TABLE 17.0
17.1
Total Final
DFT
in Microns
Primer
Finish paint
(min.)
Underground carbon steel plant piping ( Yard/ Over the Ditch Corrosion protection Coating)
17.1.1
25 to 65
17.2
17.2.1
Sl.
No.
Design
Temperature
in oC
Surface
Preparation
SSPC-SP-10
1 coat of synthetic
fast drying primer
25 @ DFT/ coat
Remarks
375
Products
form
AkzoNobel
,
Berger,
Jotun are
acceptable
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 31 OF 45
REV. NO.
: R0
TABLE 18.0
FOR
BOTH
For insulated Piping, Storage Tanks/vessels, Equipments etc (Note-1) of Carbon Steel, LTCS, Low
Alloy Steel & Stainless Steel
Sl.
No.
18.1
18.1.1
18.2
18.2.1
18.3
18.3.1
18.3.2
18.4
Surface
Total
design
Preparation & PreFinal DFT
Paint
system
(Field)
Temperature
Remarks
erection/Shop
in Microns
in oC
Primer
Finish
paint
Primer
(min.)
Insulated Carbon steel, LTCS and low allow steel Piping, Stainless Steel Piping, Storage Tanks and
Equipment etc
-45 to 150
SSPC-SP-10
2 coats of
225 - 250
Equivalent
INTERLINE-850
systems
INTERLINE-850
@ 75 DFT/coat;
from Berger
@75 DFT/coat
are
also
(Akzo Nobel )
(Akzo Nobel)
acceptable
Insulated low alloy steel piping, C Steel piping and Stainless Steel Piping with intermittent cyclic service.
Sealer coat ; Refer
TSAC shall be
150 to 4000C SSPC-SP-5
Thermally
flame spray or
ANNEXURE-I
sprayed
arc
spray;
Aluminium
Refer
coating (TSAC)
ANNEXURE; Refer
I)
ANNEXURE-I
Insulated stainless steel including Alloy-20 piping (Note:1)
Below 0oC to
Aluminium sheeting with aluminium foil and Chloride free mineral
If the piping
all minus
sealant coating barium chromate shall be applied.
&
temperature
equipments
are already
400 to 500
SSPC-SP-10
None
TSAC shall be
250
erected than
(15-25 surface
flame spray or arc
surface shall
profile)
spray
be prepared
Refer
by cleaning
ANNEXURE I
with emery
paper
and
wash/flush
Alternate to
SSPC-SP-10
None
1 coat of
240
with chloride
14.3.2
1 coat of
AMERCOAT 738
free
DM
AMERCOAT 738
@ 125 DFT
water
400-600
@ 125 DFT
/coat
followed by
/coat
wiping with
SS
organic
SSPC-SP-1
solvent
With non-chloride
solvent
No painting is required for insulated monel, Incoloy and Nickel lines.
NOTES
1. The blast cleaning abrasives for SS and Alloy steel surfaces shall be SS grits/shots or
Aluminium oxide grits/shots.
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 32 OF 45
REV. NO.
: R0
19.0
STORAGE
All paints and painting materials shall be stored only in rooms to be arranged by contractor
and approved by Engineer-in-charge for the purpose. All necessary precautions shall be
taken to prevent fire. The storage building shall preferably be separate from adjacent
building. A signboard bearing the word PAINT STORAGE NO NAKED LIGHT
HIGHLY INFLAMABLE shall be clearly displayed outside. Manufacturers
recommendation shall be followed for storage of paint materials.
20.0
COLOUR CODE
NPCIL norms and guidelines are applicable for colour coding of Piping, Equipments and
vessels etc and for the special requirements like camouflaging
21.0
21.1
All painting materials including primers and thinners brought to site by contractor for
application shall be procured directly from manufactures as per specifications and shall be
accompanied by manufacturer's test certificates. Paint formulations without certificates are
not acceptable.
21.2
Engineer-In-Charge at his discretion may call for tests for paint formulations. Contractor
shall arrange to have such tests performed including batch-wise test of wet paints for
physical & chemical analysis as per clause 24.4 of relevant ASTM test method. All costs
there shall be borne by the contractor.
The contractor shall produce test reports from manufacturer regarding the quality of the
particular batch of paint supplied. The Engineer-in-Charge shall have the right to test wet
samples of paint at random for quality of same. Batch test reports of the manufacturer's for
each batch of paints supplied shall be made available by the contractor.
21.3
PAGE NO.
: 33 OF 45
REV. NO.
: R0
contract. Dry film thickness (DFT) shall be checked and recorded after application of each
coat and extra coat of paint should be applied to make-up the DFT specified without any
extra cost to owner, the extra coat should have prior approval of Engineer-in-charge.
21.4
Primer Application
After surface preparation, the primer should be applied to cover the crevices, corners, sharp
edges etc. in the presence of inspector nominated by Engineer-In-Charge.
21.5
The shades of successive coats should be slightly different in colour in order to ensure
application of individual coats, the thickness of each coat and complete coverage should be
checked as per provision of this specification. This should be approved by Engineer-InCharge before application of successive coats.
21.6
The contractor shall provide standard thickness measurement instrument with appropriate
range(s) for measuring.
Dry film thickness of each coat, surface profile gauge for checking of surface profile in case
of sand blasting. Holiday detectors and pinhole detector and protector whenever required for
checking in case of immersion conditions.
21.7
Prior to application of paints on surfaces of chimneys, the thickness of the individual coat
shall be checked by application of each coat of same paint on M.S.test panel. The thickness
of paint on test panels shall be determined by using gauge such as 'Elkometer'. The thickness
of each coat shall be checked as per provision of this specification. This shall be approved by
Engineer-In-Charge before application of paints on surface of chimney.
21.8
At the discretion of Engineer-In-Charge, the paint manufacturer must provide the expert
technical service at site as and when required. This service should be free of cost and without
any obligation to the owner, as it would be in the interest of the manufacturer to ensure that
both surface preparation and application are carried out as per their recommendations. The
contractor is responsible to arrange the same.
21.9
Final inspection shall include measurement of paint dry film thickness, Adhesion, Holiday
detection check of finish and workmanship. The thickness should be measured at as many
points/ locations as decided by Engineer-In-Charge and shall be within + 10% of the dry film
thickness, specified in the specifications.
21.10
The contractor shall arrange for spot checking of paint materials for Sp.gr., glow time (ford
cup) and spreading rate.
22.0
GUARANTEE
22.1
The contractor shall guarantee that the chemical and physical properties of paint materials
used are in accordance with the specifications contained herein/to be provided during
execution of work.
23.0
QUALIFICATION
CONTRACTOR
CRITERIA
OF
PAINTING
CONTRACTOR/SUB-
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 34 OF 45
REV. NO.
: R0
Painting contractor must have necessary equipments, machinery, tools and tackles for
surface preparation, paint application and inspection. The contractor mush have qualified,
trained and experienced surface preparator, paint applicator, inspector and supervisors. The
contractor supervisor, inspector, surface preparator and paint applicator must be conversant
with the standards referred in this specification.
24.0
24.1
The manufacturer should arrange testing of the coating materials as per the list of tests given
above from one of the following reputed Government laboratories:
IICT, Hyderabad
HBTI, Kanpur
DMSRDE, Kanpur
BIS Laboratories
UICT, Matunga, Mumbai
RITES, Kolkata
PDIL, Sindri
NTH, Kolkata
24.2
PAGE NO.
: 35 OF 45
REV. NO.
: R0
24.3
All test panels should be prepared by Govt. testing agency coloured photographs of test
panels should be taken before and after the test and should be enclosed along with test
report.
Sample batch no. and manufacturers test certificate should be enclosed along with the
report. Test report must contain details of observation and rusting if any, as per the testing
code.
24.4
Manufacturers should intimate the company, details of sample submitted for testing, name of
Govt. testing agency, date, contact personnel of the govt. testing agency. At the end of the
test the manufacturer should submit the test reports to the company for approval. The
manufacturer(s) shall be approved based on the results of these tests and other assessment
and the companys decision in this regard shall be final and binding on the manufacturer.
24.4
Coating systems for panel test shall be decided after discussion with NPCIL/EIL
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 36 OF 45
REV. NO.
: R0
ANNEXURE-I
SPECIFICATION FOR THERMALLY SPRAYED ALUMINIUM (TSA) COATING
1.0
SCOPE
The following sections outlines the requirement of supply, application and testing of
thermally sprayed Aluminium coatings (TSAC) for corrosion protection of steel structures as
referred elsewhere
2.0
GENERAL
Structures, components thermally sprayed shall not have any uncoated area or shall not be in
mechanically connected by flanges etc to any uncoated bare steel work. Such adjacent areas
to TSA coated areas, if not coated by TSA shall have suitable paint coating system
3.0
TSAC REQUIREMENTS
3.1
Surface Preparation
All the parts to be sprayed shall be degreased according to SSPC-SP 1. The absence of oil
and grease after degreasing shall be tested by method given elsewhere in the specification
(Refer Sec. 6.7). Thereafter the surface to be abrasive blasted to white metal finish as per
NACE 1/SSPC-SP 5 for marine and immersion service. Using SSPC VIS 1, it is to be
visually assessed that the blast cleaned surface meets requirement of SSPC-SP 5. Thereafter
clear cellophane tape test as per ISO 8502-3 shall be used to confirm absence of dust on the
blasted surface. Finally blasted surface shall be tested for presence of soluble salts as per
method ISO 8502-9. Maximum allowable salt content shall be considered 50mg/M2. (5
micrograms/cm2) .In case salt content exceeds specified limit. The contaminated surface
shall be cleaned by method as per Annex C of IS 12944-4 (Water Cleaning). After cleaning
the surface shall be retested for salt content after drying.
The blasting media shall be either chilled iron or angular steel grit as per SSPC-AB-3 of
mesh size G-16 to G-40. Copper or Nickel slag or Garret as abrasive will also be suitable
having mesh size in the range of G16 to G24, conforming to SSPC-AB-1. Mesh size shall be
required as appropriate to the anchor tooth depth profile requirement and blasting equipment
used. The blasted surface should be having angular profile depth not less than 75 microns
with sharp angular shape.
The profile depth shall be measured according to NACE
standard RP 0287 (Replica Tape) or ASTM D 4417 method B (Profile depth gauge).
For manual blasting one profile depth measurement shall be taken every 10-20 m2 of blasted
surface.
Surface preparation shall be completed in one abrasive blast cleaning operation wherever
possible.
If rust bloom (visual appearance of rust) appears on the blast cleaned surface before thermal
spraying, the affected area shall be re blasted to achieve specified degree of cleanliness after
which only thermal spraying shall commence.
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 37 OF 45
REV. NO.
: R0
Air blasting pressure at nozzle shall be normally maintained at 100 psi. Air pressure and
media size should be reduced and adjusted to preclude damage/distortion to thin gauge
materials. Blasting time on work piece should be adjusted to only clean the surface and cut
required anchor tooth with minimum loss of metal. Blast angle should be as close to
perpendicular as possible but in no case greater than 30 0 from perpendicular to work
surface. Blasting media must be free of debris, excessive fines, contaminants such as Nacl
and sulphur salts (Ref. SEC 6.0 of this Spec).
3.1.1
Blasting Equipment
The TSAC applicator shall use mechanical (centrifugal wheel) or pressure pot blast cleaning
equipment and procedures. Suction blasting equipment shall not be used. Sec 6.6.2 shall
be used to validate clean and dry air
3.1.2
Feed Stock
The feed stock shall be in the form of wire. The feed stock shall be 99.5% aluminium of
commercial purity grade, its composition shall be in accordance with requirement of BS
1475or ASTM B833 (wrought aluminium and aluminium alloys, wire).
3.1.3
Thickness Requirement
The nominal thickness of finished TSAC shall be 250 microns having minimum value of
225 microns at low thickness areas (valleys) and not more than 275 microns at peak areas.
The finished thickness shall be measured using SSPC-PA 2 type 2 fixed probe gauge
(Magnetic Gauge).
3.1.4
3.1.5
Porosity
All thermally sprayed metallic coatings will have porosity. For thermally sprayed aluminium
coatings porosity shall not exceed 15% of total surface area for flame sprayed coating and
8% for arc spray coating.
4.0
4.1
4.1.1
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 38 OF 45
REV. NO.
: R0
4.1.2
Spray parameters
Spray parameters (see 4.1.3 below) and thickness of each crossing pass shall be set and shall
be validated with bend test (See 6.5 of this Spec).
4.1.3
Spray Parameters
Spray Parameters
Arc voltage
Air pressure
Steel surface cleanliness
Method of Application
Arc wire Spray
27 V
80 psi
NACE-1 white metal
The above parameters to be validated with a bend test by the contractor before start of work
(for details of bend test see Sec 6.5 of this Spec).
4.2
4.2.1
The steel surface temperature shall be at least 50C above dew point of ambient air
temperature.
Steel substrate surface temperature shall be recorded by with a contact pyrometer.
Thermal spraying should commence within 15 minutes from the time of completion of
blasting
4.2.2
Holding Period
Time between the completion of final anchor tooth blasting and completion of thermal
spraying of blasted surface should be no more than four hours. If within this period rust
bloom appears Sec 4.4.1of this specification will apply.
4.3
Pre-Heating
For flame spraying, the initial starting area of 1-2 square feet to be preheated to
approx.1200C to prevent condensation of moisture in the flame on the substrate. For arc
spraying the preheating is not required.
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 39 OF 45
REV. NO.
: R0
4.4
Thermal spraying
Spraying should commence only after validation of equipment set up by procedure
qualification test
and spray parameter validation tests described in Sec 7.0 and 6.5
respectively. Thermal spraying must commence within 15 minutes from the time of
completion of blast cleaning
The specified coating thickness shall be applied in several crossing passes. The coating bond
strength is greater when the spray passes are kept thin. Laying down an excessively thick
spray pass increases the internal stresses in TSAC and decreases the bond strength of total
TSAC. The suitable thickness for crossing passes shall be determined by procedure
qualification test described in Sec 7.0 of this specification.
For manual spraying, spraying to be done in perpendicular crossing passes to minimize thin
spots in coating. Approx. 75-100 microns of TSAC shall be laid down in each pass.
The surface geometry of the item or area to be sprayed should be inspected before
application. The spraying pass and sequence shall be planned according to following.
-
4.4.1
Standoff (Inches)
6-8
5-7
Spray
pass
width
(Inches)
1 ( 40mm )
( 20mm )
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 40 OF 45
REV. NO.
: R0
4.4.2
Masking
Masking all those parts and surfaces which are not required to be thermally sprayed as
instructed by purchaser should be inspected by applicator to ensure that they are properly
marked and covered by purchaser.
Complex geometries (flanges, valve manifolds, intersections) shall be masked by applicator
to minimize overspray i.e. TSAC applied outside spray parameters (primarily gun to
substrate distance and spray angle).
4.4.3
TSAC Finish
The deposited TSAC shall be uniform without blisters, cracks, loose particles, or exposed
steel as examined with 10 X magnification.
5.0
SEALER
Sealant shall be applied after satisfactory application of TSAC and completion of all testing
and
measurements of the finished TSAC as per Sec 6.0 of this specification.
For shop work Sealer shall be applied immediately after thermal spraying and for field work
sealer shall be applied within 8 hours. The sealcoat shall be thin enough to penetrate into the
body of TSAC.
The sealant shall be Silicone Alkyd Aluminium paint having DFT not more than 35-40
micron. Typically seal coat shall be applied at a spreading rate resulting in theoretical 38
microns DFT. The seal coat shall be applied in accordance with SSPC-PA 1 and the paint
manufacturer instruction for sealing.
During application of seal coat, complete coverage shall be ensured by visual observation.
6.0
6.1
Surface Finish
That the blasted cleaned surface meets the required criteria (NACE 1/SSPC-SP 5 ) shall be
visually inspected using SSPC-VIS 1. The clear cellophane-tape test shall be used to
confirm absence of dust or foreign debris on the cleaned surface.
6.2
production before
The angular profile depth measurement shall be done by profile tape as per method NACE
Standard RP 0287 or ASTM D 4417 method B (Profile depth gauge micrometer). Spot
measurement shall be carried out every 15m2 of blasted surface. At each spot three
measurements shall be taken over an area of 10 cm2 and average of measurements to be
recorded and reported.
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 41 OF 45
REV. NO.
: R0
If profile is <75 microns blasting shall continue till grater than 75 microns depth profile is
achieved.
6.3
TSAC Thickness (In-Process Testing For finished coating during regular production)
6.3.1
TSAC finished thickness shall be measured using SSPC-PA 2 type 2 fixed probe gauge.
6.3.2
For flat surfaces, measurements shall be taken along a straight measurement line, one
measurement line for every 15 m2 of applied TSAC shall be selected along which 5
measurements to be taken at 25 mm internal and average to be reported.
6.3.3
For curved surface or complex geometry, 5 measurements shall be taken at a spot measuring
10 cm2 in area. One spot to be taken for every 15 m2 of applied TSAC area.
6.3.4
The TSAC thickness in surface changes or contour changes, welds and attachments shall be
also measured and reported.
6.3.5
If TSAC is less than specified minimum thickness, apply additional TSAC until specified
thickness range is achieved.
6.3.6
All locations and values of TSAC thickness measurements shall be recorded in Job Record
(JR).
6.4
Tensile Bond Testing (In-Process testing for finished coating during regular production)
6.5
Tensile Bond strength of the TSAC finish coat shall be determined according to
ASTM D 4541 using a self-aligning adhesion tester.
One measurement shall be made every 50 m2. If tensile bond at any individual spot is
less than 1000 psi for flame sprayed coating and 1500 psi for arc sprayed coating the
degraded TSAC shall completely removed and reapplied.
The tensile bond portable test instrument to be calibrated according to ASTM C 633
Bend Tests
Bend test shall be carried out at beginning of each work shift. Bend tests shall also be
conducted on sample coupons before start of thermal spraying work to qualify the following
as mentioned earlier in this specification.
-
6.5.1
Test Procedure
a)
b)
Surface shall be prepared by dry abrasive blast cleaning as per this specification.
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 42 OF 45
REV. NO.
: R0
c)
TSAC shall be applied as per specified thickness range. TSAC should be sprayed
in crossing passes laying down approx. 75-100 microns in each pass.
d)
e)
f)
Only minor cracking that cannot be lifted from substrate with a knife blade.
6.6
6.6.1
Blasting Media (For every fresh batch of media and one random test during blasting)
Blasting Media shall be visually inspected for absence of contamination and debris using 10
X magnification.
a)
6.6.2
Inspection for the absence of oil contamination shall be conducted using following
procedure :
-
Fill the bottle with potable water, cap and shake the bottle.
Inspect water for oil film/slick.If present, the blasting media is not to be used.
b)
c)
Clean blasting equipment, especially pot and hoses, then replace blasting media and
retest.
Test for Blasting Air ( Once Daily before start of blasting and once at random during
blasting)
The air for blasting shall be free from moisture and oil. The compressor air shall be checked
for oil and water contamination per ASTM D 4285.
6.7
a)
Visual inspection - Continue degreasing until all visible signs of contamination are removed.
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 43 OF 45
REV. NO.
: R0
b)
Conduct a solvent evaporation test by applying several drops or a small splash of residuefree trichloromethane on the suspect area especially pitting, crevice corrosion areas or
depressed
areas. An evaporation ring formation is indicative of oil and grease
contamination.
Continue degreasing and inspection till test is passed.
7.0
7.1
Four each quadrant five in-line thickness measurements at 1 interval shall be done
using SSPC-PA 2 type 2 fixed probe gauge. Thus a total of four five in line
thickness measurements to be done for the whole sample.
One tensile bond measurement using ASTM D 4541 type III or IV portable self
aligning test instrument to be done at centre of each quadrant. Total of 4 measurements
for the sample.
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 44 OF 45
REV. NO.
: R0
7.2
The procedure shall be considered qualified if thickness and tensile-bond strength and
porosity values meet the specification requirement.
Bend test: Bend test shall be carried out as detailed at sec. 6.5 of this specification.
Applicators thermal spray equipment set-up, operation and procedure of application
including in-process QC checkpoints adopted during procedure qualification as described
above should be always subsequently followed during entire duration of work.
8.0
DOCUMENTATION
The following information shall be provided by TSAC applicator before award of work.
9.0
10.0
Detailed application procedure and in-process quality control check points for (a)
surface preparation (b) thermal spraying (c) seal coats.
Paint manufacturer data sheet for the selected sealing coat to be applied.
RECORDS
-
The TSAC applicator shall maintain a job record to record production and QC
information. All the results of the tests and quality control checks shall be entered
in the record for each component/part thermally sprayed. All the result of tests
(thickness, tensile bond, bend tests) and other validation tests (e.g. procedure
qualification test, test for surface cleanliness after abrasive blasting, test for
cleanliness of abrasives and air) shall also be recorded and duly signed by owner.
All the information mentioned in Sec 8.0 above should also form part of the Job
record.
Any modification affected after procedure qualification in the procedure, QC, spray
parameter, equipment spec to the original information (submitted before award of
the work) must also form part of Job record.
WARRANTY
The TSAC applicator shall warrant the quality of material used by providing the purchaser
with a certificate of materials used to include
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
PAGE NO.
: 45 OF 45
REV. NO.
: R0
11.0
Spray feed stock: Alloy type/designation, Lot Number, wire diameter, chemical
analysis, name of supplier, manufacturer.
12.0
March 2013
NOT FOR PUBLICATION / PRESENTATION OUTSIDE NPCIL & EIL
Z ZPA= 1.17
25
1%
2%
3%
4%
5%
7%
10%
20%
Acceleration,m/s2
20
15
10
0
0
10
15
20
25
30
35
40
45
50
55
Frequency, Hz
60
65
70
75
80
85
90
95
100
Z ZPA= 0.80
9
1%
2%
3%
4%
5%
7%
10%
20%
Acceleration,m/s2
0
0
10
15
20
25
30
35
40
45
50
55
Frequency, Hz
60
65
70
75
80
85
90
95
100
Z ZPA= 0.67
8
1%
2%
3%
4%
5%
7%
10%
20%
Acceleration,m/s2
0
0
10
15
20
25
30
35
40
45
50
55
Frequency, Hz
60
65
70
75
80
85
90
95
100
Z ZPA= 0.68
7
1%
2%
3%
4%
5%
7%
10%
20%
Acceleration,m/s2
0
0
10
15
20
25
30
35
40
45
50
55
Frequency, Hz
60
65
70
75
80
85
90
95
100
Z ZPA= 2.16
25
1%
2%
3%
4%
5%
7%
10%
20%
Acceleration,m/s2
20
15
10
0
0
10
15
20
25
30
35
40
45
50
55
Frequency, Hz
60
65
70
75
80
85
90
95
100
Z ZPA= 2.65
30
1%
2%
3%
4%
5%
7%
10%
20%
25
Acceleration,m/s2
20
15
10
0
0
10
15
20
25
30
35
40
45
50
55
Frequency, Hz
60
65
70
75
80
85
90
95
100
2.
SS Tubes
3.
Welded
CS pipes
IS-3589
ERW 410
4.
SS Pipes
A-312 TP 304L
ERW / SML
INDIAN VENDOR
FOREIGN VENDOR
1. M/s. SAIL
2. M/s. Mann Indus., Indore
3. M/s. Deccan Metal Industries, Rajpura,
Punjab
4. M/s. Lalit Profiles, Navi Mumbai
5. M/s. MSL, Raigad
6. M/s. PSL Limited, Chennai
1. M/s. Ratnamani Metals and Tubes Ltd,
Ahmedabad
2. M/s. NFC, Hyderabad
3. M/s. REMI, Mumbai
1. M/s. AB Sandvik,
Sweden
2. M/s. Fine Tubes, UK
3. M/s. Vallourec &
Mannesman,Germany
4. M/s. Dalmine, Italy
5. M/s. Salzgitter
Mannesmann, France
6. M/s. Productos
Tubulares, Spain
-
1. M/s. AB Sandvik,
Sweden
2. M/s. Dalmine
Tenaris, Italy
3. M/s. Salzgitter
Mannesmann,
France
4. M/s. Vallourec &
Mannesman,
5.
Seamless
Elbows, Tees,
Bends,
Reducers, Caps,
Sockolet,
Threadolet,
Couplings,
Flanges, Weldolets
etc.
CS/ASTM-A-105,
A234WPB/P22, SSA182/A403
304L/316L,
6.
Hangers, Supports,
Snubbers and Sway
Braces
7.
Bearing pads /
Lubrite Pads
Fasteners
8.
Germany
5. M/s. Productos
Tubulares, Spain
6. M/s. Schoeller
Blackmann
1. M/s. Sungkwang
Bend Co., Korea
2. M/s. Techtube, Italy
3. M/s. Union Piping,
Italy
4. M/s. ERNE, Austria
5. M/s. Petrol
Raccordi, Italy
6. M/s. M.E.G.A, SPA
Italy
7. M/s. Bassi Luigi, Italy
8. M/s. Schultz, Germany
9. M/s. B.K.L. Fittings Ltd,
UK
10. M/s. Raccordi
Forgeati, Italy
11. M/s. Myong
KWANG Metal Co., Korea
12. M/s. TEE Kwang,
Korea
13. M/s. Fino, Germany
9.
Gasket
10.
Structural
Steel(CS&SS)
1. M/s. Flexitallic,UK
Purpose
Connecting pipeline
size, ODThickness,
mm
Grooving
diameter dgr, mm
Quantity,
psc.
Air vent
322.5
28+0.21
II
21911
200+0.46
III
27311
255+0.52
IV
Inlet from
recirculation line
1596
150+0.40
Overflow
1596
150+0.40
VI
Level metering
connecting pipe
142
10.5+0.18
VII
Drainage
895
80+0.30
VIII
Manhole
800
VIII
Manhole
800
IX
122
NO,
,
kNm
NO,
,
kNm
NO,
F,
kN
NO
F,
kN
NO+DBE
DBE,
kNm
NO+DBE
FDBE,
kN
25
0.175
0.384
1.44
3.16
0.218
1.76
80
2.33
3.45
4.00
5.94
2.87
4.90
150
7.12
10.20
7.16
10.30
8.76
8.74
200
26.80
37.30
9.90
13.70
33.00
12.00
250
37.20
49.30
12.30
16.30
45.70
15.00
Note - , F moment and force by the weight of pipeline. , F range of moment and
force by pipeline temperature compensation. DBE, FDBE - moment and force by joint effect
of pipeline weight and DBE.
3.0 Page 4 & 5 of 9: Tank outline drawing for 3 FAL51BB001, 3 FAL52BB001, 4 FAL51BB001, 4
FAL52BB001
Purpose
ODxThickness, mm
Bore
diameter Db
Number, pcs.
573
52 +0.3
II
Tank filling
108x5
99 +0.35
III
Tank filling
573
52 +0.3
IV
Blowoff
573
52 +0.3
Recirculation
573
52 +0.3
VI
Compressed air
32x2.5
28 +0.21
VII
Caustic soda
32x2.5
28 +0,21
VIII
Tank filling
1085
99 +0.35
IX
219x11
200 +0.46
142
10,5 +0.18
XI
573
52 +0.3
XII
Manhole
820x10
XIII
18x2.5
13.5 +0.18
XIV
18x2.5
13.5 +0.18
2.0 Page 4 of 8: Outline drawing and fastening of embedded parts for tanks 3KPF13BB001,
3KPF13BB002, 4KPF13BB001 and 4KPF13BB002.
3.0 Page 5 of 8: Outline drawing and fastening of embedded parts for tank 3KPF13BB003,
4KPF13BB003
NO,
Mw,
kN x m
NO,
Mr,
kN x m
NO,
Fw,
kN
NO
Fr,
kN
NO+DBE
DBE,
kN x m
NO+DBE
FDBE,
kN
10
0.0248
0.0534
0.63
1.35
0.0307
0.77
15
0.0535
0.115
0.81
1.75
0.0661
0.99
25
0.175
0.384
1.44
3.16
0.218
1.76
50
0.727
1.61
2.57
5.68
0.907
3.14
100
2.80
3.98
4.86
6.81
3.44
5.94
Note - w, Fw moment and force from pipeline weight. r, Fr ranges of moment and
force from pipeline temperature compensation. DBE, FDBE moment and force by joint
impact of pipeline weight and DBE.
Bore diameter
Db
52 +0,3
Number,
pcs.
1
573
52 +0.3
573
52 +0.3
32x2.5
28 +0.21
Blowoff
895
80 +0.3
573
52 +0.3
VII
820x10
VIII
219x11
200 +0.46
IX
201.5
573
52 +0.3
XI
Nitrogen supply
182.5
13.5 +0.18
XII
Supply of sorbents
573
52 +0.3
XIII
Overflow
895
80 +0.3
XIV
142
10.5 +0.18
XV
18x2.5
13.5 +0.18
XVI
18x2.5
13.5 +0.18
Mark
Purpose
I
II
III
Medium return
IV
V
VI
Dnom,
mm
NO,
Mw,
kN x
m
NO,
Mr,
kN x m
NO,
Fw,
kN
NO
NO+DB NO+DB
Fr,
E
E
kN
DBE,
FDBE,
kNm
kN
NO+SSE
MWE,
kNm
NO+SSE
FWE,
kN
0.0248 0.0534
0.63
1.35
0.0307
0.77
0.0346
0.882
10
0.0535
0.115
0.81
1.75
0.0661
0.99
0.0745
1.13
15
0.175
0.384
1.44
3.16
0.218
1.76
0.247
2.02
25
0.727
1.61
2.57
5.68
0.907
3.14
1.03
3.59
50
2.33
3.45
4.00
5.94
2.87
4.90
3.23
5.61
80
Note - w, Fw moment and force from pipeline weight. r, Fr ranges of moment and force
from pipeline temperature compensation. DBE, FDBE moment and force from joint action of
pipeline weight and DBE. MWE, FWE moment and force from joint action of pipeline weight
and SSE.
3.0 Page No. 4 of 7: Outline drawing of vat residue tanks 3KPK10BB001, 3KPK10BB002,
3KPK10BB003, 4KPK10BB001, 4KPK10BB002, 4KPK10BB003
Purpose
ODThickness, mm
Grooving
diameter
dgr, mm
Quantity,
psc.
Distillate inlet
1085
99+0.35
II
Recirculation
573
52+0.3
III
1596
150+0.40
+0.30
IV
Tank unloading
895
80
Overflow
1596
150+0.40
VI
Air vent
322.5
28+0.21
VII
142
10.5+0.18
VIII
Manhole
800
IX
1085
99+0.35
NO,
,
kNm
NO,
,
kNm
NO,
F,
kN
NO
F,
kN
NO+DBE
DBE,
kNm
NO+DBE
FDBE,
kN
25
0.175
0.384
1.44
3.16
0.218
1.76
50
0.727
1.61
2.57
5.68
0.907
3.14
80
2.33
3.45
4.00
5.94
2.87
4.90
100
2.80
3.98
4.86
6.81
3.44
5.94
150
7.12
10.20
7.16
10.30
8.76
8.74
Note - , F moment and force by the weight of pipeline. , F range of moment and
force by pipeline temperature compensation. DBE, FDBE - moment and force by joint effect
of pipeline weight and DBE.
3.0 Page No. 4 & 5 of 10: Tank outline drawing for 3 KBC16BB001, 3 KBC17BB001, 4 KBC16BB001, 4
KBC17BB001
Purpose
OD x Thickness,
mm
Bore
diameter Db
Number, pcs.
573
52 +0.3
II
89x5
80 +0.3
III
895
80 +0.3
IV
573
52 +0.3
1085
99 +0.35
VI
14x2
10,5 +0.18
VII
Blowoff
89x5
80 +0.3
VIII
820x10
IX
820x10
140
NO,
Mw,
kN x m
NO,
w,
kN x m
NO,
Mw,
kN x m
NO
Fr,
kN
NO,
Mw,
kN x m
NO+DBE
FDBE,
kN
10
0.0248
0.0534
0.63
1.35
0.0307
0.77
50
0.727
1.61
2.57
5.68
0.907
3.14
80
2.33
3.45
4.00
5.94
2.87
4.90
100
2.80
3.98
4.86
6.81
3.44
5.94
Note - w, Fw moment and force from pipeline weight. r, Fr ranges of moment and
force from pipeline temperature compensation. DBE, FDBE moment and force by joint
impact of pipeline weight and DBE.
3.0 Page no. 4 of 5: Outline drawing of purified boron concentrate tank 3KBC40BB001,
3KBC40BB002,4 KBC40BB001, 4KBC40BB002.
4.0 Changes made to note no. 14: The tank shall withstand loading cycles
Operation
modes
Temperature
variation range,
Temperature
variation
duration, s
Pressure
variation
range, MPa
Pressure
variation
duration, s
Loading
cycles for 30
years
NO modes
20 60
not limited
0 0.067
not limited
3000
Purpose
Coolant inlet from Volume and
ODxthickness,
Bore diameter
Number,
mm
Db
pcs.
1596
150 +0.4
108x5
99 +0.35
III
219x11
200 +0.46
IV
573
52 +0.3
Nitrogen inlet
383
33 +0.25
VI
Blowoff
57x3
52 +0.3
VII
57x3
52 +0.3
VIII
142
10.5 +0.18
IX
220x7
209 +0.46
201.5
XI
820x10
XII
18x2.5
13.5 +0.18
XIII
18x2.5
13.5 +0.18
NO,
Mw,
kN x m
NO,
Mr,
kN x m
NO,
Fw,
kN
NO
Fr,
kN
NO+DBE
DBE,
kN x m
NO+DBE
FDBE,
kN
10
0.0248
0.0534
0.63
1.35
0.0307
0.77
15
0.0535
0.115
0.81
1.75
0.0661
0.99
32
0.31
0.68
1.71
3.75
0.386
2.09
50
0.727
1.61
2.57
5.68
0.907
3.14
100
2.80
3.98
4.86
6.81
3.44
5.94
150
7.12
10.20
7.16
10.30
8.76
8.74
200
13.65
18.69
9.90
13.60
16.80
12.10
Note - w, Fw moment and force of pipeline weight. r, Fr ranges of moment and force
from pipeline temperature compensation. DBE, FDBE moment and force by joint impact of
pipeline weight and DBE.
3.0 Page no. 4 of 9: Outline drawing of operational grade coolant storage tank 3KBB10BB001,
3KBB10BB002, 4KBB10BB001, 4KBB10BB002
ODxThickness,
Purpose
Bore diameter Db
mm
Number, pcs.
Coolant inlet
1596
150 +0.4
II
573
52 +0.3
III
219x11
200 +0.46
IV
Distillate inlet
573
52 +0.3
Nitrogen inlet
383
33 +0.25
VI
Blowoff
57x3
52 +0.3
VII
57x3
52 +0.3
VIII
142
10.5 +0.18
IX
201.5
Manhole
820x10
XI
18x2.5
13.5 +0.18
XII
18x2.5
13.5 +0.18
NO,
Mw,
kN x m
NO,
Mr,
kN x m
NO,
Fw,
kN
NO
Fr,
kN
NO+DBE
DBE,
kN x m
NO+DBE
FDBE,
kN
10
0.0248
0.0534
0.63
1.35
0.0307
0.77
15
0.0535
0.115
0.81
1.75
0.0661
0.99
32
0.31
0.68
1.71
3.75
0.386
2.09
50
0.727
1.61
2.57
5.68
0.907
3.14
150
7.12
10.20
7.16
10.30
8.76
8.74
Note - w, Fw moment and force from pipeline weight. r, Fr ranges of moment and
force from pipeline temperature compensation. DBE, FDBE moment and force by joint
impact of pipeline weight and DBE.
3.0 Page no. 4 of 11: Outline drawing of operational grade coolant storage tank 3KBB10BB003,
4KBB10BB003
4.0 Page no. 5 of 11: Outline drawing of operational grade coolant storage tank 3KBB10BB004,
4KBB10BB004
Purpose
ODxThicknes
Bore diameter
s, mm
Db
Number, pcs.
Filling
573
52 +0.3
II
Overflow
573
52 +0.3
III
Draining
573
52 +0.3
IV
Hatch (manhole)
820x10
383
33 +0.25
VI
Air duct
573
52 +0.3
VII
108x5
99 +0.35
VIII
142
10,5 +0.18
NO,
Mw,
kN x m
NO,
Mr,
kN x m
NO,
Fw,
kN
NO
Fr,
kN
NO+DBE
DBE,
kN x m
NO+DBE
FDBE,
kN
10
0.0248
0.0534
0.63
1.35
0.0307
0.77
32
0.31
0.68
1.71
3.75
0.386
2.09
50
0.727
1.61
2.57
5.68
0.907
3.14
100
2.80
3.98
4.86
6.81
3.44
5.94
Note - w, Fw moment and force from pipeline weight. r, Fr ranges of moment and
force from pipeline temperature compensation. DBE, FDBE moment and force by joint
impact of pipeline weight and DBE.
3.0 Changes made in note 12 of datasheet :The tank shall withstand loading cycles
Operation
modes
Temperature
variation range,
Temperature
variation
duration, s
Pressure
variation
range, MPa
Pressure
variation
duration, s
Loading
cycles for 30
years
NO modes
20 40
not limited
0 0.036
not limited
2800
Qty,
Purpose
S, mm
Medium input
573,0
II
Overflow
1085,0
III
Emptying
573,0
IV
Air vent
573,0
Manhole
800
designation
pcs.
F
X
UC
Acceleration, m/s2
, /2
10
8
6
4
2
0
0
50
100
,
Frequency,
150
200
Hz
7%
Acceleration, m/s2
, /2
5%
10%
3
2
1
0
50
100
150
200
, Hz
Frequency,
30
Acceleration, m/s
, / 2
25
20
15
10
5
0
0
50
100
150
200
Frequency,
, Hz
Figure .7 - Response spectra from ASW for UKC building along axis X.
Walls and slabs at elevation minus 3.600 m
2%
5%
Acceleration, m/s2
7%
10%
4
3
2
1
0
50
100
150
200
,
Frequency,
Hz
10
5%
, /2
Acceleration, m/s2
7%
10%
6
4
2
0
20
40
60
80
100
120
140
160
180
200
, Hz
Frequency,
, /
Acceleration, m/s2
6
5
4
3
2
1
0
0
50
100
150
200
,
Frequency,
Hz
Figure .8 - Response spectra from ASW for UKC building along axis Y.
Walls and slabs at elevation minus 3.600 m