Design Guide
2013
Valves
A.
General: The system shall be designed for the provision of isolating valves at all
equipment, fixtures, hydronic circuits, control valves, individual pieces of equipment, and
all branch mains. Isolation valves shall be installed in accessible locations and provided
at sub-mains at take-offs to each floor on multi-story buildings and on branches where
two or more devices are served or where future renovation is anticipated. Control valves
shall be located on the return lines from the equipment being controlled. Generally, the
following valves shall be designated:
B.
Steam Systems:
1.
50.0 PSIG and Above:
a)
Up to 2" - Forged steel body gate valves with rising stem, Class 300
b)
Velan
Stockham
Crane
Bonney
c)
d)
e)
f)
g)
h)
i)
j)
2-1/2 and Above, Distribution (Manholes and 1 st Interior Building Shutoff Valve)
230523 - 1
ROWAN UNIVERSITY
Design Guide
2013
k)
l)
2.
C.
D.
E.
F.
G.
High Performance butterfly valve, ANSI Class 150, lugged body style.
Body: Carbon Steel
230523 - 2
ROWAN UNIVERSITY
3.
4.
5.
6.
7.
8.
Design Guide
2013
H.
I.
230523 - 3