6

General Purpose Transformers


Electrical Connections (Three Phase)
208 D Volt Primary 208Y/120 Volt Secondary
Taps: 2, 2% FCAN;
4, 2% FCBN

17

Primary
@ Tap

H1-H2-H3
Voltage

Secondary Voltage
X 1, X 2, X 3

X0-X1, X2, X3

240 D Volt Primary, 208Y/120 Volt Secondary


Taps: 2, 5% FCBN

18

Primary
Voltage

C o n n ect
Lines To

Connect Taps

240 D Volt Primary, 208Y/120 Volt Secondary


Taps: 2, 2% FCAN; 4, 2% FCBN

19

Primary

H1-H2-H3

@ Tap

Voltage

252

246

240

218

240

1-H1 & 2-H2 & 3-H3

H1, H2, H3

213

228

4-H1 & 5-H2 & 6-H3

H1, H2, H3

208

216

7-H1 & 8-H2 & 9-H3

H1, H2, H3

234

203

228

198

C o n n ect
Lines To

Secondary
Voltage

222

192

208

X 1, X 2, & X 3

216

187

120

X 0, X 1, X 2, X 3

208

120

480 D Volt Primary, 208Y/120 Volt Secondary


Taps: 2, 5%% FCBN

20

480 D Volt Primary 208Y/120 Volt Secondary


Taps: 2, 2% FCAN; 4, 2% FCBN

Primary
@ Tap

H1-H2-H3
Voltage

Primary
Voltage

Interconnect

Connect Lines to

504

480

1-H1 & 2-H2 & 3- H3

H1, H2, H3

492

456

4-H1 & 5-H2 & 6- H3

H1, H2, H3

480

432

7-H1 & 8-H2 & 9- H3

H1, H2, H3

468

Secondary
Voltage

Connect Lines to

456

208

X 1, X 2, & X 3

444

120

X 0, X 1, X 2, X 3

432

Secondary Voltage
X 1, X 2, X 3

X0-X1, X2, X3

208

120

21

Secondary Voltage
X 1, X 2, X 3

X0-X1, X2, X3

208

120

Notes:
Connect the electrostatic shield to the equipment ground (green) or to
both the equipment ground and the system ground (white). Specifications
are subject to change without notice.

Visit our website at www.solaheviduty.com or


contact Technical Services at (800) 377-4384 with any questions.

159

General Purpose Transformers

Electrical Connections (Three Phase)


480 D Volt Primary 240 D w/120 CT Volt Secondary
Taps: 2, 5% FCBN

22

480 D Volt Primary 240 D w/120 CT Volt Secondary


Taps: 2, 2% FCAN; 4, 2% FCBN

Primary

H 1-H 2-H 3

23

Secondary Voltage
X1-X6-X3

Primary
Voltage

Connect Lines To

480

1-H1 & 2-H2 & 3-H3

H1, H2, H3

4-H1 & 5-H2 & 6-H3

H1, H2, H3

Secondary
Voltage

7-H1 & 8-H2 & 9-H3

H1, H2, H3

Interconnect

Connect Lines To

240
120-0-120

X 1, X 2, X 3
X6 to

504

492

480

468

456

X 1, X 2, X 3

444

432

240

120-0-120

X1-X6-X3

480 D Volt Primary 480Y/277 Volt Secondary


Taps: 2, 2% FCAN; 4, 2% FCBN

Primary
@ Tap

160

Voltage

X6 to

Connect Taps

456
432

@ Tap

24

H1-H2-H3

Secondary Voltage

Voltage

X 1, X 2, X 3 X 0- X 1, X 2, X 3

600 D Volt Primary 208Y/120 Volt Secondary


Taps: 2, 5% FCBN

25

Primary
Voltage

Connect Taps

Line Leads
H1, H2, H3

504

600

1-H1 & 2-H2 & 3-H3

492

570

4-H1 & 5-H2 & 6-H3

H1, H2, H3

480

540

7-H1 & 8-H2 & 9-H3

H1, H2, H3

468
456

Secondary
Voltage

Line Leads

5
6

444

208

X 1, X 2, X 3

432

120

X 0, X 1, X 2, X 3

480

277

Visit our website at www.solaheviduty.com or


contact Technical Services at (800) 377-4384 with any questions.

General Purpose Transformers


Electrical Connections (Three Phase)
600 D Volt Primary 208Y/120 Volt Secondary
Taps: 2, 2% FCAN; 4, 2% FCBN

Primary

H1-H2-H3

Secondary Voltage

@ Tap

Voltage

X 1, X 2, X 3 X 0- X 1, X 2, X 3

630

615

600

585

26

480 D Volt Primary 380Y/220 Volt Secondary


Taps: 2, 5% FCBN

Primary
Voltage

Interconnect

27

Connect Lines to

480

1-H1 & 2-H2 & 3-H3

H1, H2 & H3

456

4-H1 & 5-H2 & 6-H3

H1, H2 & H3

570

432

7-H1 & 8-H2 & 9-H3

H1, H2 & H3

555

Secondary
Voltage

Interconnect

Connect Lines to

540

208

120

480 D Volt Primary 380Y/220 Volt Secondary


Taps: 2, 2% FCAN; 4, 2% FCBN

Primary
@ Tap

H1-H2-H3

Secondary Voltage

Voltage

X 1, X 2, X 3 X 0- X 1, X 2, X 3

504

492

480

468

456

444

432

380

380

X 1, X 2, X 3

220

X 0, X 1, X 2, X 3