The Magnetic Balance test is conducted on Transformers to


identify inter turn faults and magnetic imbalance. The magnetic
balancetestisusuallydoneonthestarsideofatransformer.A
twophasesupply440Visappliedacrosstwophases,say,1Uand
1V.ThephaseWiskeptopen.Thevoltageisthenmeasured
between UV and UW. The sum of these two voltages should
givetheappliedvoltage.Thatis,1U1W+1V1Wwillbeequalto
1U1V.
For instance, if the voltage applied is 440V between 1U1V, then
thevoltagesobtainedcanbe
1U1V=1U1W+1V1W
440V=260V+180V
Thevoltagesobtainedinthesecondarywillalsobeproportionaltothevoltagesabove.
This indicates that the transformer is magnetically balanced. If there is any interturn short
circuitthatmayresultinthesumofthetwovoltagesnotbeingequaltotheappliedvoltage.
The Magnetic balance test is only an indicative test for the transformer. Its results are not
absolute.Itneedstobeusedinconjunctionwithothertests.
2013FormNYDTFRP5217
PDFINS

Adsby Google

Test&Balance
PowerTransformerTest
TransformerMagneticCore
FillNow!

Blog Archive

2015(257)
2014(117)
2013(36)

Youmightalsolike:

2012(85)
2011(84)
2010(86)
December(5)

CoreBalance
Current
Transformers

TrefoilFormation
forArranging
Cables

AcceptanceTestfor
Automobiles

ThermalMagnetic
TripAnOverview

November(10)

Balancingthe
PumpRotors

October(10)
September(18)

Linkwithin

August(9)
ReactiveLoadandPower
factor

Labels:balance,magnetic,test,transformers

NewerPost

Home

http://www.electrotechnik.net/2010/08/magneticbalancetestontransformers.html

OlderPost

Part2PowerFactor
ImprovementandWhyit
is...

1/3

8/10/2016

MagneticBalanceTestonTransformers

ResourcePages

UnderstandingPower
FactorPart1

Batteries

Cables

Motors

Capacitors

BatteryExplosions
CausesandPrevention

Transformers

Alternators

RotorVoltageDropTest

Earthing

Fuses

FormationofBulgesin
Batteries

Forum
ListofArticles

WhatismeantbyaDi
electricAbsorptionTest
MagneticBalanceTeston
Transformers

Popular Posts

VoltageClassificationLV,MVandEHV
ACvoltageshavebeenclassifiedinvariousmanners.Inearliertimes,therewerejusttwo
categoriesLVandHV.Asthelevelofvoltages...

RotorEarthFaultRelay
July(2)
June(3)

StaticandDynamicResistance
StaticResistanceisthenormalohmicresistanceinaccordancewithOhm'sLaw.Itisthe
ratioofvoltageandcurrentandisaconstant...

May(6)
April(4)
March(2)

CalculatingthepercentageimpedanceofaTransformer
Theimpedanceofatransformerisdefinedasthepercentageofthedropinvoltagetothe
atfullloadtotheratedvoltageofthetransform...

February(4)
January(13)
2009(108)

ReversePowerRelayFunctionandOperation
Areversepowerrelayisadirectionalpowerrelaythatisusedtomonitorthepowerfroma
generatorrunninginparallelwithanothergener...

2008(3)
2006(5)
Follow Us On

WhatisthefunctionoftheConservatorinaTransformer
TheConservatorisacylindricalcomponentofthetransformer.Theconservatorislocatedatthetopof
thetransformer.TheConservatori...

Twitter
Facebook
LinkedIn
GooglePlus
Adsby Google

MagneticTest
HowtoTestaTransformer
ElectricalTest

www.boilertechnik.com

Recommendedforyou

http://www.electrotechnik.net/2010/08/magneticbalancetestontransformers.html

2/3

8/10/2016

MagneticBalanceTestonTransformers

AdvantagesofThree
PhasePoweroversingle
Phasepower

VoltageClassification
LV,MVandEHV

FreewheelingorFlyback
diodesandtheirfunction

www.electrotechnik.net

www.electrotechnik.net

www.electrotechnik.net

Calculatingthe
percentageimpedance
ofaTransformer

Whyisthesinglephase
motornotselfstarting?

Whatisthedifference
betweenaVariac,
variableautotransform...

www.electrotechnik.net

www.electrotechnik.net

www.electrotechnik.net

AddThis

http://www.electrotechnik.net/2010/08/magneticbalancetestontransformers.html

3/3

S-ar putea să vă placă și