 Technology and

Protection and Substation Automation


Solutions

UW Goesgen
Protection
Concept

Goesgen / 2003-02-12 /SJ

ABB Switzerland Ltd. - 1

REB500

ABB

REB500 behaviour without CT Remote Station


Current Situation
A
B
Q1

Q2

Q62

Q2

Q1

Q0

Goesgen / 2003-02-12 /SJ

ABB Switzerland Ltd. - 2

Q9

ACA02

ACA0X

ABB

REB500 behaviour without CT Remote Station


ACA02 -Q1 Closed
A
B
Q1

Q2

Q62

Q2

Q1

Q0

Goesgen / 2003-02-12 /SJ

ABB Switzerland Ltd. - 3

Q9

ACA02

ACA0X

ABB

REB500 behaviour without CT Remote Station


ACA02 -Q2 Closed
A
B
Q1

Q2

Q62

Q1

Q2

Q0

Goesgen / 2003-02-12 /SJ

ABB Switzerland Ltd. - 4

Q9

ACA02

ACA0X

ABB

REB500 behaviour without CT Remote Station


ACA02 -Q0 Closed
A
B
Q1

Q2

Q62

Q1

Q2

Q0
Q9

Goesgen / 2003-02-12 /SJ

ABB Switzerland Ltd. - 5

Measurement active for both


zones

ACA02

ACA0X

ABB

REB500 behaviour without CT Remote Station


ACA0X Q62 Closed
A
B
Q1

Q2

Q62

Q2

Q1

Q0
Measurement
blocked because
Q9
of Breaker
Open

Goesgen / 2003-02-12 /SJ

ABB Switzerland Ltd. - 6

Diff. Protection Busbar A is automatically blocked


As feeder current ACA0X is not measured
ACA02

ACA0X

ABB

REB500 behaviour without CT Remote Station


ACA0X Q0 Open
A
B
Q1

Q2

Q62

Q2

Q1

Q0
Q9

Goesgen / 2003-02-12 /SJ

ABB Switzerland Ltd. - 7

Diff. Protection Busbar A is automatically blocked


As feeder current ACA0X is not measured
ACA02

ACA0X

ABB

REB500 behaviour without CT Remote Station


ACA0X Q9 Open
A
B
Q1

Q2

Q62

Q2

Q1

Q0
Q9

Goesgen / 2003-02-12 /SJ

ABB Switzerland Ltd. - 8

Diff. Protection Busbar A is automatically blocked


As feeder current ACA0X is not measured
ACA02

ACA0X

ABB

REB500 behaviour without CT Remote Station


ACA0X Q9 Open
A
B
Q1

Q2

Q62

Q2

Q1

Q0
Q9

Goesgen / 2003-02-12 /SJ

ABB Switzerland Ltd. - 9

Diff. Protection Busbar A is automatically blocked


As feeder current ACA0X is not measured
ACA02

ACA0X

ABB

REB500 behaviour with CT Remote Station


Situation
A
B
Q1

Q2

Q62

Q2

Q1

Q0
Q9

Goesgen / 2003-02-12 /SJ

ABB Switzerland Ltd. - 10

Max. Distance
approx.1.2 km
ACA02
Line protected by
REB500 Diff. Protection

ACA0X

ABB

REB500 behaviour with CT Remote Station


ACA02 -Q1 Closed
A
B
Q1

Q2

Q62

Q2

Q1

Q0

Goesgen / 2003-02-12 /SJ

ABB Switzerland Ltd. - 11

Q9

ACA02

ACA0X

ABB

REB500 behaviour with CT Remote Station


ACA02 -Q2 Closed
A
B
Q1

Q2

Q62

Q1

Q2

Q0
Q9

Goesgen / 2003-02-12 /SJ

ABB Switzerland Ltd. - 12

Measurement is blocked as related breaker is open

ACA02

ACA0X

ABB

REB500 behaviour with CT Remote Station


ACA02 -Q0 Closed
A
B
Q1

Q2

Q62

Q1

Q2

Q0

Goesgen / 2003-02-12 /SJ

ABB Switzerland Ltd. - 13

Measurement is active for both protection


zones

ACA02

Q9

ACA0X

ABB

REB500 behaviour with CT Remote Station


ACA0X Q62 Closed
A
B
Q1

Q2

Q62

Q2

Q1

Q0

Goesgen / 2003-02-12 /SJ

ABB Switzerland Ltd. - 14

Measurement
blocked because
Q9
of Breaker
bypass

ACA02

ACA0X

REB500 Diff. Protection Busbar A active as Feedercurrent is


measured im remote station ACA0X.

ABB

REB500 behaviour with CT Remote Station


ACA0X Q0 Open
A
B
Q1

Q2

Q62

Q2

Q1

Q0

Goesgen / 2003-02-12 /SJ

ABB Switzerland Ltd. - 15

Measurement
blocked because
Q9
of Breaker
Open

ACA02

ACA0X

REB500 Diff. Protection Busbar A active as Feedercurrent is


measured im remote station ACA0X.

ABB

REB500 behaviour with CT Remote Station


ACA0X Q9 Open
A
B
Q1

Q2

Q62

Q2

Q1

Q0

Goesgen / 2003-02-12 /SJ

ABB Switzerland Ltd. - 16

Q9

ACA02

ACA0X

REB500 Diff. Protection Busbar A active as Feedercurrent is


measured im remote station ACA0X.

ABB

REB500 behaviour with CT Remote Station


ACA0X Q1 Open
A
B
Q1

Q2

Q62

Q2

Q1

Q0

Goesgen / 2003-02-12 /SJ

ABB Switzerland Ltd. - 17

Q9

ACA02

ACA0X

REB500 Diff. Protection Busbar A active as Feedercurrent is


measured im remote station ACA0X.

ABB