Sunteți pe pagina 1din 4

Supplier Data List

SUPPLIER DOCUMENT COVER SHEET

Dominion Gas Plant

Supplier Name: CLYDEUNION PUMPS

Purchase Order Title: PROPANE PIPELINE PUMPS

Equipment / Tag Number(s): P-803-A/B

Supplier Document No: E001-003

Supplier's Issue Record

CLYDEUNION

PUMPS

21 May 2012

FOR REVIEW

SSU

Date

Issue

By

Rev

MWM

Checked

MW

Approved

Project Document Number

Purchase Order Number

Seq. No.

Data Code

176070-PO-0110-103

N01

Rev. No.

B01

Revision Date

21 May 2012

MOTOR DATA SHEET

DOCUMENT TITLE:

SUPPLIER DOCUMENT REVIEW

Purchasers review of Suppliers documents does not relieve Supplier of the responsibility for correctness under the Purchase Order.

Permission to proceed does not constitute acceptance of design, detail and calculations, test methods or materials developed or

selected by the Supplier and does not relieve the Supplier from full compliance with the Purchase Order or any other obligations, nor

CODE 2

CODE 1

CODE 3

CODE 5

CODE 4

CODE 6

CODE 7

SIGNATURE:

DATE:

CODE 1 -

Final Document

CODE 2 -

No Comments

CODE 3 -

Comments

CODE 4 -

Rejected

CODE 5 -

Superseded

CODE 6 -

Void

CODE 7 -

For Information

CB&I Lummus
Dominion Gas Plant Project No.176070
Engineering Review Status

1 - Final/Certified
Proceed with fabrication. No further
submittal required.

By:

mcuevas

Date: 6/5/2012

These comments do not relieve the supplier of his responsibility to meet the requirements of the PO.

IMPORTANT

Should the Supplier consider that any comments made by the Purchaser change the Scope of Supply, the Supplier shall advise

the price and delivery implications of such changes within five working days of receipt. The Supplier must not incorporate such

changes without prior approval of the Purchaser of the revised price and/or delivery period. RETROSPECTIVE CLAIMS WILL

NOT BE CONSIDERED.

Supplier - Purchaser Interface Data Freeze

CB&I Name:

Signature:

Date:

The document consists of this frontsheet plus X pages.

Doc Number: 176070-DTI-CGP1-DM-PR-00002

Issued for Information 18 Aug 2011 Rev. 1

Page 1 of 1

Document#:176070-PO-0110-103-SD-00011 Revision:A
Tag#:P-803A,P-803B
Supplier#:E001-003
Supplier Rev#:1
PO#:PO-0110-103
Pkg#:176070-CBIR-CBIR-R02723

detract from any of the Purchasers rights.

MODEL NUMBER

Frame

HP

Enclosure

SM857017

V5840

1400

WP II

Voltage

Amps

Duty

Amb / Insul.

4000

179

Continuous

40C / F

Ph / Hz

Type / Form

P / BW

RPM

3 / 60

3561

S.F.

kVA/HP

Stator Res. @ 25C

1.15

0.1888 ohms T-T

AC Motor Performance Data

TYPICAL PERFORMANCE

Load
NO LOAD
1/4

HP

Design Amperes

RPM

% Efficiency

% P. F.

-------

47

3600

7.7 %

-------

350

65

3591

63.4 %

90.2 %

1/2

700

98

3582

81.2 %

93.8 %

3/4

1050

136

3572

86.6 %

94.6 %

1400

179

3561

88.0 %

94.5 %

S. F.

1610

206

3552

88.1 %

94.0 %

5/4

1750

225

3550

87.8 %

94.0 %

RPM

Torque (% FLT)

Torque (N-m)

Amperes

1028

FULL LOAD

SPEED TORQUE

Breakdown
Full Load

60 %

1239

1679

3438

205 %

4232

5738

667

3561

100 %

2065

2799

179

OTHER INFORMATION

1)

Rated temperature rise: 80C x RES at 1.00 S.F.

2)

Minimum starting voltage: 80 %

3)

Efficiency per IEEE 112 - Method E1 (Stray load loss: 1.2% of output)

4)

Hot stall time:

13 seconds

5)

Cold stall time:

17 seconds

6)

Consecutive starts when motor is at rated ambient or less:

7)

Consecutive starts when motor is at operating temperature: 2

8)
The load inertia is (WK): (not given)

9)

Maximum power factor correction capacitor: 275 KVAR (optional)

10) Hazardous Location: Class I, Division 2, Group D ; Temperature Code: T3 (200C)

11) Altitude: 3300 ft ASL

STRATFORD

SHEET

ONTARIO

CANADA

ISSUE DATE

3/30/12

Document#:176070-PO-0110-103-SD-00011 Revision:A
Tag#:P-803A,P-803B
Supplier#:E001-003
Supplier Rev#:1
PO#:PO-0110-103
Pkg#:176070-CBIR-CBIR-R02723

Locked Rotor

Torque (lb-ft)

MODEL NUMBER

Frame

HP

Enclosure

Type / Form

SM857017

V5840

1400

WP II

P / BW

3 / 60

3561

Amps

Duty

S.F.

kVA/HP

Stator Res. @ 25C

0.1888 ohms T-T

Voltage

Continuous

179

4000

Amb / Insul.

40C / F

Ph / Hz

1.15

RPM

Equivalent Circuit Parameters

1)
Three phase short circuit contribution at 0.5 Hz =

658
amp

2)

205
amp

Three phase short circuit contribution at 5 Hz =

3)

Open circuit AC time constant (T"do) =


0.939
sec.

4)

Short circuit AC time constant (T"d) =


0.049
sec.

5)

Short circuit DC time constant (Ta) =


0.038
sec.

6)

Full Load Slip =

7)

2.596
ohms

Sub Transient Reactance (Locked Rotor) =

9)

X / R ratio =
14.269

Locked rotor power factor =

10)

FULL LOAD

fe

0.00806

0.00892

86.89550

13.2
%

LOCKED ROTOR

0.13033

0.00652

0.12688

0.06022

0.01842

0.04257

3.10208

fe

8.43199

1.92974

(per unit - per phase)

fe

/s
2

1
= stator DC resistance

1
= stator leakage reactance

2
= rotor resistance

2
= rotor leakage reactance

fe
= core loss resistance

M
= magnetizing reactance

STRATFORD

SHEET

ONTARIO

CANADA

ISSUE DATE

3/30/12

Document#:176070-PO-0110-103-SD-00011 Revision:A
Tag#:P-803A,P-803B
Supplier#:E001-003
Supplier Rev#:1
PO#:PO-0110-103
Pkg#:176070-CBIR-CBIR-R02723

8)

1.07
%

Base Ohms =
15.320
ohms

MODEL NUMBER

Frame

HP

SM857017

V5840

1400

Enclosure
WP II

Voltage

Amps

Duty

Amb / Insul.

4000

179

Continuous

Type / Form

Ph / Hz

P / BW

S.F.

40C / F

RPM

3 / 60

3561

kVA/HP

Stator Res. @ 25C

0.1888 ohms T-T

1.15

Recommended Alarm & Trip Settings

Recommended Winding and Bearing Temperatures

Temperature

Maximum Running Total Temperature

155 C

Alarm Total Temperature

160 C

Trip Total Temperature

170 C

Drive End Bearing (DE)

Anti-Friction

( 40 C Ambient )

Grease

Temperature

Typical Running Total Temperature

75 C

Alarm Total Temperature

85 C

Trip Total Temperature

90 C

Opposite Drive End Bearing (ODE)

Anti-Friction

( 40 C Ambient )

Oil

Temperature

Typical Running Total Temperature

70 C

Alarm Total Temperature

80 C

Trip Total Temperature

85 C

Recommended Vibration Settings for Standard Motors

Speed (RPM)

Shaft Vibration (mils)


Alarm

Shutdown

Bracket Vibration (ips)

Alarm

Shutdown

3600

2.50

3.00

0.20

1800

3.00

3.50

0.20

0.30

0.30

1200

3.50

4.00

0.20

0.30

900 & lower

3.50

4.00

0.20

0.30

Recommended Differential Pressure Switch Setting

Switch set to activate at 0.5" w.c. (water column) increasing

differential pressure. ( for motors with air filters only )

STRATFORD

SHEET

ONTARIO

CANADA

ISSUE DATE

3/30/12

Document#:176070-PO-0110-103-SD-00011 Revision:A
Tag#:P-803A,P-803B
Supplier#:E001-003
Supplier Rev#:1
PO#:PO-0110-103
Pkg#:176070-CBIR-CBIR-R02723

Stator Winding

S-ar putea să vă placă și