Sunteți pe pagina 1din 60

CHAPTER 4

SHORT CIRCUIT CALCULATIONS

Chapter 4

Page 1

Short Circuit Calculations

SHORT CIRCUIT CALCULATIONS


PURPOSES OF FAULT CALCULATIONS
TYPES OF FAULT MAGNITUDES

Three Phase Faults

Phase to Phase Faults

Phase to Ground Faults

Arcing Faults

Overloads

MODELING METHODS

Introduction

Ohmic Model

Percent Model

Per-Unit Model

ONE-LINE DIAGRAMS (STEP 1)

One-Line Diagram

SELECT/CALCULATE BASE VALUES (STEP 2)

Base Kilovolt-Amperes (kVAb)

Base Kilovolts (kVb)

Base Current (Ib)

Base Impedance (Zb)

Table of Base Values

DATA COLLECTION AND MODELING (STEP 3)

Utility or Source

Transformers

Conductors (Cables, Busway, Aerial Lines)

Generators

Motors

Chapter 4

Page 2

Short Circuit Calculations

Resistors, Reactors, and Capacitors

PER-UNIT IMPEDANCE CALCULATIONS (STEP 4)

Introduction

Utility or Source

Transformers

Motors and Generators

Conductors

Grounding Resistors, Reactors, and Capacitors

IMPEDANCE DIAGRAMS (STEP 5)

Complex Impedance Diagram (Z = R + jX)

Reactance (X-Only) Diagram (R = 0)

Resistance (R-Only) Diagram (X = 0)

PROBLEM

Problem 3: Per-Unit Modeling

MODIFY MACHINE REACTANCES (STEP 6)

Momentary and Interrupting Duties

Machine Reactance Multipliers

Impedance Diagrams

THEVENIN EQUIVALENT NETWORK (STEP 7)

Thevenin Equivalent Circuit

FAULT CALCULATION PROCEDURES

Problem 5: Bus Fault Calculations

Problem 6: Infinite Bus Calculations

Chapter 4

Page 3

Short Circuit Calculations

PURPOSES OF FAULT CALCULATIONS


INTRODUCTION
No matter how well an electrical power system is designed, it will occasionally
experience short circuits that result in abnormally high current flows. Fault
calculations (short circuit studies) are performed to determine device interrupting and
withstand ratings, and to determine relay pickup and sensitivity settings.
PROTECTIVE DEVICE INTERRUPTING RATINGS
The maximum calculated short circuit current magnitudes are used to select
adequate protective device (e.g., fuses and breakers) interrupting ratings to minimize
the fault damage and the plant downtime.
EQUIPMENT COMPONENT WITHSTAND RATINGS
Other electrical equipment (e.g., buses and cable) must be capable of withstanding
the high thermal and mechanical stresses (I2t) that are associated with the short
circuit current.
PROTECTIVE RELAY PICKUP SETTINGS
The maximum value of the available short circuit current is used to determine the
pickup settings of relays and low voltage breakers. For example, the instantaneous
trip setting of an upstream relay should be set approximately 10 percent above the
maximum available asymmetrical (Iasy) short circuit current that is seen by the
downstream protective device.
MAXIMUM RELAY SETTINGS FOR SENSITIVITY
Minimum values available of short circuit current are required to set maximum relay
settings for sensitivity. For example, the maximum setting for ground fault relays in
medium voltage system is typically selected based on a minimum fault current of
approximately ten percent of the available maximum fault current.

Chapter 4

Page 4

Short Circuit Calculations

TYPES OF FAULTS/MAGNITUDES
THREE-PHASE FAULTS (I3)
Although three-phase faults (Figure 4-1) usually are the least often occurring type of
fault, they are often the worst case in most industrial power systems. Three-phase
bolted faults (I3), which are often called balanced faults, are represented by the
following equations.

I3 = IA = IB = IC = E/Z1

Figure 4-1. Three-Phase Bolted Fault (Balanced)


PHASE-TO-PHASE FAULTS (I-)
Phase-to-phase bolted faults (I-), which are often called line-to line faults (Figure 42), are seldom required for protective equipment fault interrupting duties because
they are not the maximum values. Phase-to-phase fault current magnitudes are
approximately 87% of the three-phase fault values, as represented by the following
equations:

I- = IA = -IB = ( 3 E)/(Z1 + Z2)


= ( 3 E)/2Z1 = .87 E/Z1 = .87 I3

Ic = 0

Figure 4-2. Phase-to-Phase Fault (Unbalanced)

Chapter 4

Page 5

Short Circuit Calculations

PHASE-TO-GROUND FAULTS (I-G)


Phase-to-ground faults (Figure 4-3), which are often called line-to-ground faults, are
the types of faults that most often occur, and their magnitudes range from a few
percentage points to 125% of the three-phase fault values. In industrial systems,
phase-to-ground faults exceeding three-phase fault values are the exception rather
than the rule. Symmetrical components modeling techniques are required to analyze
line-to-ground faults and these techniques are considered beyond the scope of this
course. Phase-to-ground faults are represented by the following equations:

I-G = IA = 3E/[Z1 + Z2 + Z0 + 3(ZN + ZF)]


IB = IC = 0

Figure 4-3. Phase-to-Ground Fault (Unbalanced)


ARCING FAULTS (Iarc)
Many low voltage power systems experience low level arcing faults, and in many
cases they are the most damaging faults, especially at the 480 volt level. Because
of the very high arc impedance, arcing fault current magnitudes tend to be too low
for the protective devices to detect and clear. Arcing fault current magnitudes are
typically estimated as follows:

0.89 at 480 V and 0.12 at 208 V for three-phase arcing.


0.74 at 480 V and 0.02 at 208 for phase-to-phase arcing.
0.38 at 277 V and 0.01 at 120 V for phase-to-neutral arcing.

OVERLOADS (IOL)
Overloads are not technically regarded as faults or short circuits. Very low level
faults (<250% of full load amperes) are often called overloads because they are
detected in the protective device overload (e.g., thermal) ranges rather than in the
fault (e.g., instantaneous or short time) ranges of the protective devices.

Chapter 4

Page 6

Short Circuit Calculations

MODELING METHODS
INTRODUCTION
In order to calculate short circuit currents, line voltage drops, motor starting currents,
etc., the different impedance values for circuit elements (transformers, cables,
motors, generators, etc.) must be determined from nameplates, handbooks, and
catalogs. These impedance values can be modeled in ohms, percent, or per-unit on
a chosen base value. In most calculations, the per-unit modeling of circuit elements
is used because it is easier and more convenient to solve the problems when the
system contains several voltage levels. Impedances that are modeled in per-unit
can be combined in parallel or series regardless of the number of different voltage
levels.
OHMIC MODEL
Modeling an electrical circuit element, for example, a cable in ohms is quite simple;
however, if the power system contains more than one voltage level, which is almost
always the case, the ohmic value will change as the square of the ratio of the voltage
levels. In other words, the ohmic values change from one side of a transformer to
the other. For example, if a power system has three voltage levels, which is not
uncommon, each electrical circuit element (cable, transformer, motor, etc.) will have
three ohmic values (Figure 4-4). For this reason, power system studies are typically
not performed using ohmic models.
Example A: Referring to Figure 4-4, assume that the impedance (Z) of transformer
T1 is 0.2423 at 4.16 kV. What is the impedance of T1 at 13.8 kV? at
0.48 kV?
Answer:

1. Z @ 13.8 kV = Z @ 4.16 kV x a2
= (.2423)(11.004) = 2.666
2. Z @ 0.48 kV = Z @ 4.16 kV a2
= (.2423)/(75.111) = 0.0032

PERCENT MODEL
The percent method of modeling an electrical system differs from the per-unit
method by a factor of 100 (percent value = 100 x p.u. value). It is also not typically
used for power system studies calculations because it leads to simple math errors.
For example, 50% current x 100% impedance = 50% voltage and not 5000% voltage
as the math indicates (50 x 100).

Chapter 4

Page 7

Short Circuit Calculations

OHMIC MODEL

Figure 4-4. Ohmic Model Impedances

Chapter 4

Page 8

Short Circuit Calculations

PER-UNIT MODEL
When impedances of circuit elements are expressed in per-unit, the problems
mentioned for both the ohmic and percent models are eliminated. Impedances
expressed in per-unit on a defined base are the same on both sides of a transformer.
For example, referring to Figure 4-4, ZT1 = 7% on both the 13.8 kV primary and 4.16
kV secondary sides of the transformer, and ZT2 = 5.5% on both the 4.16 kV primary
and .48 kV secondary sides of the transformer.
In the per-unit model there are four basic quantities: base kilovolt-amperes (kVAb),
base kilovolts (kVb), base amperes (Ib), and base impedance or base ohms (Zb).
The relationship between the base values, per-unit values, and actual values is
defined as follows:

per-unit value = actual value/base value or

per-unit value = percent value/100

For example:
kVApu = kVA actual/kVAb
kWpu = kWactual/kVAb = KWactual/kWb
kVARpu = kVARactual/kVAb = kVARactual/kVARb
kVpu = kVactual/kVb
Ipu = Iactual/Ib
Zpu = Zactual/Zb
Rpu = Ractual/Rb = Ractual/Zb
Xpu = Xactual/Xb = Xactual/Zb
Note: Zb = Rb = Xb
kVAb = kWb = kVARb

Chapter 4

Page 9

Short Circuit Calculations

PER-UNIT MODEL
The five steps that are used to model an electrical power system in per-unit are as
follows:

STEP 1

One-Line Diagram

-- The fault study results are only as accurate as the input data.

STEP 2

Select/Calculate Base Values


kVAb, kVb, Ib, Zb

STEP 3

Data Collection and Modeling

STEP 4

Per-Unit Impedance Calculations

STEP 5

Impedance Diagrams

Note: These five steps are typically the same for per-unit modeling of any
power system, regardless of the type of power study that
is being performed.

Chapter 4

Page 10

Short Circuit Calculations

ONE-LINE DIAGRAMS (STEP 1)


ONE-LINE DIAGRAM
An accurate one-line diagram (system road map) should be prepared that shows all
sources (utility tie, generators, and motors) and significant circuit elements
(transformers, cables, busway, etc.). Note: The study to be performed will only be
as accurate as the one-line diagram. Figure 4-5 is an example one-line diagram of a
electrical power system that will be used throughout the remainder of this Chapter.

Figure 4-5. Example One-Line Diagram

Chapter 4

Page 11

Short Circuit Calculations

SELECT/CALCULATE BASE VALUES (STEP 2)


BASE KILOVOLT-AMPERES (kVAb)
The selection of kVAb is arbitrary; however, a convenient value is usually selected to
make the mathematical calculations somewhat less tedious. For purposes of this
course, select kVAb = 100000 kVA or MVAb = 100 MVA. Note: Per-unit formulas are
often listed in terms of MVAb versus kVAb where 1 MVA = 1000 kVA.
BASE KILOVOLTS (kVb)
Base kilovolt (kVb) is selected to match one of the system transformers rated
voltages and then the base voltages at other voltage levels are established
(calculated) by transformer turns ratios, which also equal the transformer voltage
ratios. For example, referring to Figure 4-5, the base voltages are as follows:

Bus 100: Let kVb = 13.8 kV

Bus 50:

kVb = 13.8 (69.0/13.8) = 69 kV

Bus 250:

kVb = 13.8 (0.48/13.8) = .48 kV

Bus 300:

kVb = 13.8 (4.16/13.8) = 4.16 kV

BASE CURRENT (Ib)


Base current is calculated through the use of the apparent power relationships that
were developed in Chapter 2, as follows:

Ib = kVAb/( 3 x kVb)

Bus 50:

Bus 100: Ib = 100000/( 3 x 13.8) = 4183.7 A

Bus 250: Ib = 100000/( 3 x 0.48) = 120281.3 A

Bus 300: Ib = 100000/( 3 x 4.16) = 13878.6 A

Chapter 4

Ib = 100000/( 3 x 69.0) = 836.8 A

Page 12

Short Circuit Calculations

BASE IMPEDANCE (Zb)


Base impedance is calculated through use of voltage, current, impedance, and
power relationships that also were developed in Chapter 2, as follows:

Zb = (kVb)2/MVAb or Zb = [(kVb)2 x 1000]/kVAb

Bus 50:

Bus 100: Zb = 13.82/100 = 1.9044

Bus 300: Zb = 4.162/100 = 0.173

Bus 250: Zb = 0.482/100 = 0.0023

Zb = 692/100 = 47.61

TABLE OF BASE VALUES


For easier data retrieval, the base values that are selected and calculated for a
particular power system study are usually listed in tabular form. For the one-line
diagram that is shown in Figure 4-5, the base values are listed in Table 4-1.

Bus
Numbers

kVAb

kVb

Ib

Zb

50

100000 kVA

69.0 kV

836.8 A

47.61

100, 150, 200

100000 kVA

13.8 kV

4183.7 A

1.9044

300

100000 kVA

4.16 kV

13878.6 A

0.173

250

100000 kVA

0.480 kV

120281.3 A

0.0023

Table 4-1. Table of Base Values

Chapter 4

Page 13

Short Circuit Calculations

DATA COLLECTION AND MODELING (STEP 3)


UTILITY OR SOURCE
The utility system is modeled as a voltage (Eu) behind an impedance (Zu) as shown
in Figure 4-6. The utility company can provide the data in any of the following forms:

kVASCA or MVASCA and X/R ratio

Amperes (ISCA) and angle (-)

R and X in ohms ()

R and X in per-unit (p.u.) on a given base

Figure 4-6. Utility or Source Model (Zu)


Example B: Figure 4-5 modeled the utility at 950 MVA, X/R = 11.4. What are the
other three possible models?
Answer:

1. |ISCA| = 950000/( 3 x 69) = 7949 A


= tan-1 (11.4) = -85o
ISCA = 7949 -85o A
2. VLN = 69000/ 3 = 39837.2 V
|Z| = VLN/I = 39837.2/7949 = 5.012
Z = 5.012 +85o
= (0.4368 + j 4.9929)
3. |Zpu| = 100/950 = 0.1053 p.u.
Z = 0.1053 +85o p.u.
= (0.0092 + j 0.1049) p.u.

Chapter 4

Page 14

Short Circuit Calculations

TRANSFORMERS
Transformers are modeled as an impedance (ZT) as shown in Figure 4-7.
following data are needed to model power transformers:

The

kVA or MVA self-cooled (OA) rating

Nameplate impedance (e.g., 5.75%, 7.5%)

Voltage ratings (primary and secondary)

X/R ratio (if available, or see Figure 4-8)

Connections (e.g., delta or wye) (L-G calculations only)

Method of grounding (e.g., solid or resistance) (L-G calculations only)

Figure 4-7. Transformer Model (ZT)

Figure 4-8. X/R Ratios of Transformers

Chapter 4

Page 15

Short Circuit Calculations

CONDUCTORS
Cables are modeled as an impedance (ZC) as shown in Figure 4-9. The following
data are needed to model a cable:

Size (e.g., kcmil or AWG) and length (e.g., per 1000 ft.)

Conductors per phase (e.g., 1, 2, etc.)

Conductor material (e.g., copper or aluminum)

Conductor configuration (3-1/c or 1-3/c)

Shielding (shielded or non-shielded)

Conduit type (e.g., magnetic or non-magnetic) or direct burial cable

Ohmic values of resistance (RC) and reactance (jXC) per unit of length
(Tables 5-2 and 5-3)

Figure 4-9. Conductor or Busway Model (ZC or ZB)


Busway is modeled as an impedance (ZB), also as shown in Figure 4-9.
following data are needed to model busway:

The

Type (e.g., plug-in, feeder, or current limiting) and length (e.g., per
1000 ft.) (Figure 4-10)

Ampacity

Conductor material (e.g., copper or aluminum)

Ohmic values of resistance (RB) and reactance (jXB) per unit of length
(Table 4-4).

Chapter 4

Page 16

Short Circuit Calculations

CONDUCTORS
In Magnetic Duct and Steel Interlock Armor

In Nonmagnetic Duct and Aluminum Armor

600 V & 5 kV

5 kV Shielded &

600 V & 5 kV

5 kV Shielded &

AWG

Non Shielded

15 kV

Nonshielded

15 kV

kcmil

(/1000 ft.)

(/1000 ft.)

(/1000 ft.)

0.811

0.0754

0.814

0.811

0.0860

0.816

(/1000 ft.)

0.811

0.0603

0.813

0.811

0.0688

0.814

*8

0.786

0.0754

0 790

0.786

0.0860

0.791

0.786

0.0603

0.788

0.786

0.0688

0.789

0.510

0.0685

0.515

0.510

0.0796

0.591

0.510

0.0548

0.513

0.510

0.0636

0.514

*6

0.496

0.0685

0.501

0.496

0.0796

0.502

0.496

0.0548

0.499

0.496

0.0636

0.500

0.312

0.0632

0.327

0.312

0.0742

0.329

0.312

0.0506

0.325

0.312

0.0594

0.326

*4

0.312

0.0632

0.318

0.312

0.0742

0.321

0.312

0.0506

0.316

0.312

0.0594

0.318

0.202

0.0585

0.210

0.202

0.0685

0.214

0.202

0.0467

0.207

0.202

0.0547

0.209

0.160

0.0570

0.170

0.160

0.0675

0.174

0.160

0.4560

0.166

0.160

0.0540

0.169

1/0

0.128

0.0540

0.139

0.128

0.0635

0.143

0.127

0.0432

0.134

0.128

0.0507

0.138

2/0

0.102

0.0533

0.115

0.103

0.0630

0.121

0.101

0.0426

0.110

0.102

0.0504

0.114

3.0

0.085

0.0519

0.0958

0.0814

0.0605

0.101

0.0766

0.0415

0.0871

0.0895

0.0484

0.0939

4/0

0.064

0.0497

0.0810

0.0650

0.0583

0.0929

0.0633

0.0396

0.0748

0.0640

0.0466

0.0792

250

0.0552

0.0495

0.0742

0.0557

0.0570

0.0797

0.0541

0.0396

0.0670

0.0547

0.0456

0.0712

300

0.0464

0.0493

0.0677

0.0473

0.0564

0.0736

0.0451

0.0394

0.0599

0.0460

0.0451

0.0644

350

0.0378

0.0491

0.0617

0.0386

0.0562

0.0681

0.0368

0.0393

0.0536

0.0375

0.0450

0.0586

400

0.0356

0.0490

0.0606

0.0362

0.0548

0.0657

0.0342

0.0392

0.0520

0.0348

0.0438

0.0559

450

0.0322

0.0480

0.0578

0.0328

0.0538

0.0630

0.0304

0.0384

0.0490

0.0312

0.0430

0.0531

500

0.0294

0.0466

0.0551

0.0300

0.0526

0.0505

0.0276

0.0373

0.0464

0.0284

0.0421

0.0508

600

0.0257

0.0463

0.0530

0.0264

0.0516

0.0580

0.0237

0.0371

0.0440

0.0246

0.0412

0.0479

750

0.0216

0.0445

0.0495

0.0223

0.0497

0.0545

0.0197

0.0356

0.0405

0.0203

0.0396

0.0445

* Solid Conductor

Source: IEEE Gray Book

Table 4-2. Copper Cable Impedance Data for


Three Single Conductors (3 - 1/c)

Chapter 4

Page 17

Short Circuit Calculations

CONDUCTORS
In Magnetic Duct and Steel Interlock Armor

In Nonmagnetic Duct and Aluminum Armor

600 V & 5 kV

5 kV Shielded &

600 V & 5 kV

5 kV Shielded &

AWG

Non Shielded

15 kV

Nonshielded

15 kV

kcmil

(/1000 ft.)

(/1000 ft.)

(/1000 ft.)

(/1000 ft.)

0.811

0.0577

0.813

0.811

0.0658

0.814

0.811

0.0503

0.812

0.811

0.0574

0.813

*8

0.786

0.0577

0 788

0.786

0.0658

0.789

0.786

0.0503

0.787

0.786

0.0574

0.788

0.510

0.0525

0.513

0.510

0.0610

0.500

0.496

0.0457

0.512

0.510

0.0531

0.513

*6

0.496

0.0525

0.499

0.496

0.0610

0.500

0.496

0.0547

0.498

0.496

0.0531

0.499

0.312

0.0483

0.325

0.312

0.0568

0.326

0.312

0.0422

0.324

0.312

0.0495

0.325

*4

0.312

0.0483

0.316

0.312

0.0508

0.317

0.312

0.0422

0.315

0.312

0.0495

0.316

0.202

0.0448

0.207

0.202

0.0524

0.209

0.202

0.0390

0.206

0.202

0.0457

0.207

0.160

0.0436

0.166

0.160

0.0516

0.168

0.160

0.3800

0.164

0.160

0.0450

0.166

1/0

0.128

0.0414

0.135

0.128

0.0486

0.137

0.127

0.0360

0.132

0.128

0.0423

0.135

2/0

0.102

0.0407

0.110

0.103

0.0482

0.114

0.101

0.0355

0.107

0.102

0.0420

0.110

3.0

0.085

0.0397

0.0898

0.0814

0.0463

0.0936

0.0766

0.0346

0.0841

0.0805

0.0403

0.090

4/0

0.064

0.0381

0.0745

0.0650

0.0446

0.0788

0.0633

0.0332

0.0715

0.0640

0.0389

0.0749

250

0.0552

0.0379

0.0670

0.0557

0.0436

0.0707

0.0541

0.0330

0.0634

0.0547

0.0380

0.0666

300

0.0464

0.0377

0.0598

0.0473

0.0431

0.0640

0.0451

0.0329

0.0328

0.0492

0.0375

0.0530

350

0.0376

0.0373

0.0539

0.0386

0.0427

0.0576

0.0368

0.0328

0.0492

0.0375

0.0375

0.0530

400

0.0356

0.0371

0.0514

0.0362

0.0415

0.0551

0.0342

0.0327

0.0475

0.0348

0.0366

0.0505

450

0.0322

0.0361

0.0484

0.0328

0.0404

0.0520

0.0304

0.0320

0.0441

0.0312

0.0359

0.0476

500

0.0294

0.0349

0.0456

0.0300

0.0394

0.0495

0.0276

0.0311

0.0416

0.0284

0.0351

0.0453

600

0.0257

0.0343

0.0429

0.0264

0.0382

0.0464

0.0237

0.0309

0.0389

0.0246

0.0344

0.0422

750

0.0216

0.0326

0.0391

0.0223

0.0364

0.0427

0.0197

0.0297

0.0355

0.0203

0.0332

0.0389

* Solid Conductor

Source: IEEE Gray Book

Table 4-3. Copper Cable Impedance Data for


Single Three-Conductor Cable (1 - 3/c)

Chapter 4

Page 18

Short Circuit Calculations

CONDUCTORS

Figure 4-10. Busway Types


Plug-in Busway
Current
Copper Bus Bars
Rating
R
X
Z
(amperes)
(ohms/1000 ft)
225
0.0836
0.0800
0.1157
400
0.0437
0.0232
0.0495
600
0.0350
0.0179
0.0393
800
0.0218
0.0136
0.0384
1000
0.0145
0.0135
0.0198
Low-Impedance Feeder Busway (Copper)
Current
Rating
R
X
Z
(amperes)
(ohms/1000 ft)
800
1000
1350
1600
2000
2500
4000

0.0219
0.0190
0.0126
0.0116
0.0075
0.0057
0.0037

0.0085
0.0050
0.0044
0.0035
0.0031
0.0025
0.0016

0.0235
0.0196
0.0134
0.0121
0.0081
0.0062
0.0040

Aluminum Bus Bars


X
Z
(ohms/1000 ft)
0.1090
0.0720
0.1313
0.0550
0.0222
0.0592
0.0304
0.0121
0.0327
0.0243
0.0154
0.0288
Current Limiting Busway (Copper)
Current
Rating
R
X
Z
X/R
(ohms/1000 ft)
(amperes
)
1000
0.013
0.063
0.064
4.85
1350
0.012
0.061
0.062
5.08
1600
0.009
0.056
0.057
6.22
2000
0.007
0.052
0.052
7.45
2500
0.006
0.049
0.049
8.15
3000
0.005
0.046
0.046
9.20
4000
0.004
0.042
0.042
10.50
R

Source: *IEEE Red Book

Table 4-4. Busway Impedance

Chapter 4

Page 19

Short Circuit Calculations

CONDUCTORS
Aerial (overhead) lines are modeled as an impedance (ZOHL), as shown in Figure 411. Although the resistance (ROHL) of an aerial line is modeled exactly the same as
other conductors, the reactance (XOHL) consists of two components (Xa and Xd). Xa
is found in a cable handbook, like most other cable data; however, Xd is a function of
the overhead line configuration and spacing and it (Xd) must be calculated. The
following data are needed to model an aerial line:

Size (e.g., kcmil or AWG) and length (e.g., per mile)

Conductor material (e.g., Cu, Al, ACSR)

Conductors per phase

Conductor configuration and spacing

Resistance (ROHL) per unit of length @ t oC (per mile) (Tables 4-5 and
4-6)

Operating temperature (t oC)

Reactance (Xa) per unit of length (per mile) (Tables 4-5 and 4-6)

Reactance (Xd) per unit of length (per mile) based on the conductor
configuration and spacing.

Figure 4-11. Aerial Line Model (ZOHL)

Chapter 4

Page 20

Short Circuit Calculations

CONDUCTORS
Size
Approx.
Resistance (R)
cmil
Ampacity
DC
AC
or
250C 500C
250C 500C
AWG*
amps**
ohms/mile
ohms/mile
4(1)
170
1.374 1.053 1.374 1.503
4(3)
180
1.388 1.518 1.388 1.518
2(1)
220
.864
.945
.864
.945
2(3)
240
.873
.955
.873
.955
2(7)
230
.881
.964
.882
.964
1/0(7)
310
.555
.606
.555
.606
2/0(7)
360
.440
.481
.440
.481
3/0(7)
420
.349
.381
.350
.382
4/0(7)
480
.276
.302
.278
.303
* number of strands as indicated by (x)
** for conductor at 750C, air at 250C, wind 1.4 mi/hr

Reactance (Xa)
60 Hz
1 ft spacing
ohms/mile
.609
.599
.581
.571
.574
.546
.532
.518
.503

Table 4-5. Copper Aerial Line Impedance Data


Resistance (R)
Size
cmil
or
AWG*
6
4
2
1
1/0
2/0
3/0
4/0

Approx.
Ampacity

DC
25 C 500C
ohms/mile
3.560 3.920
2.240 2.470
1.410 1.550
1.120 1.230
.885
.974
.702
.773
.556
.612
.441
.485
0

amps**
100
140
180
200
230
270
300
340

AC
25 C 500C
ohms/mile
3.560 3.980
2.240 2.570
1.410 1.690
1.120 1.380
.888 1.120
.706
.895
.560
.723
.445
.592
0

Reactance (Xa)
60 Hz
1 ft spacing
ohms/mile
.673
.659
.665
.665
.656
.641
.621
.581

* Conductor at 750C, air at 250C, wind at 1.4 mi/hr


** Current approx. 75% capacity which will produce 500C conductor
temperature (250C rise) with 250C ambient, wind at 1.4 mi/hr
Table 4-6. ACSR Aerial Line Impedance Data

Chapter 4

Page 21

Short Circuit Calculations

GENERATORS
Generators, similar to the utility, are modeled as a voltage (Eg) behind an impedance
(Zg), as shown in Figure 4-12. The following data are required to model a generator.

kVA or MVA ratings or kW and power factor

Subtransient reactance (Xd)

Assume Xd = 15% if unknown for 4 pole generators and Xd = 9% for 2


pole generators.

Voltage rating

X/R ratio (if available, or see Figure 4-13)

Figure 4-12. Generator Model (Eg)

Figure 4-13. X/R Ratios for Generators and Synchronous Motors

Chapter 4

Page 22

Short Circuit Calculations

MOTORS
Motor impedance models are modeled the same as utility and generators, as shown
in Figure 4-14; however, the impedance data (Zm = Rm + jXm) that are required to
model a motor depends on the system and motor voltages.

Figure 4-14. Motor Model (Zm)


Less Than 1000 Volts: For system studies less than 1000 volts, low voltage motors
are modeled as follows:

Lump sum (for motors applied at 480 V and below, each less than 50
hp).

Individual motors (all other motors). Note: Induction motors 50 to 250


hp are also often treated as lump sum motors.

Assume Xd = 25%, Rd = 2.5%, X/R = 10

Over 1000 Volts: For system studies over 1000 volts (multivoltage studies), low
voltage motors are modeled using both a 1st-cycle and an interrupting network.
Mutlivoltage system studies motors (1st cycle network) are modeled as follows:

For LV induction motors <50 hp, neglect reactance, or assume that X =


1.67Xd, or assume that 1.67 Xd = 28% on the motors rating. Note:
For purposes of this Tab use X = 1.67Xd = 28% and an X/R ratio of 10.

For LV induction motors that are greater than 50 hp, assume that X =
1.2Xd, or assume that 1.2Xd = 20% on the motors rating. Use an X/R
ratio of the largest motor. Note: For purposes of this Tab use X =
1.2Xd = 20% and an X/R ratio of 10.

Chapter 4

Page 23

Short Circuit Calculations

MOTORS
Multivoltage system studies motors (interrupting network) are modeled as follows:

For LV induction motors < 50 hp, neglect reactance.

For LV induction motors that are greater than 50 hp, assume that X =
3.0 Xd or assume that 3.0 Xd = 50% on the motors rating. Note: For
purposes of this Tab use X = 3.0 Xd = 50% and an X/R ratio of 10.

Large motors over 1000 volts (medium voltage) are modeled as follows:

Type: synchronous or induction

Horsepower (hp) and speed (rpm)

Subtransient reactance (Xd) and transient reactance (Xd)

FLA and LRA: Xd = FLA/LRA

Assume that Xd = 17% if the actual data are not available for induction
motors, and assume that Xd = 20% for synchronous motors. Assume
that Xd 1.5Xd.

Power factor: kVA = hp rating if p.f. = 80% or kVA = 0.8 x hp rating if


p.f. = 100%.

X/R ratio (if available), or see Figure 4-15 for induction motors and
Figure 4-13 for synchronous motors.

Figure 4-15. X/R Ratios for Induction Motors

Chapter 4

Page 24

Short Circuit Calculations

RESISTORS, REACTORS, AND CAPACITORS


Grounding resistors are modeled as shown in Figure 4-16a. Data for a grounding
resistor (RR) are limited to the following:

Voltage

Current ratings (e.g., 200 A, 400 A)

Resistance (e.g., 40 , 6 )

Time (e.g., 10 sec)

Reactors (grounding, current limiting, or tuning) are modeled as shown in Figure 416b. The following data are needed to model reactors (jXL):

Grounding reactors: voltage, percent impedance, amperes, ohms, and


time

Current limiting reactors: voltage, kVA, or amperes

Tuning (harmonic filter) reactors: amperes, ohms, or millihenries

Capacitors are modeled as shown in Figure 4-16c. The following data are needed to
model capacitors (-jXc): Note: Capacitors are not modeled for short circuit studies.

voltage (e.g., 4.16 kV, 600 V)

kVAR or MVAR (e.g., 300 kVAR, 150 MVAR)

Figure 4-16. Resistor, Reactor, and Capacitor Models

Chapter 4

Page 25

Short Circuit Calculations

PER-UNIT IMPEDANCE CALCULATIONS (STEP 4)


INTRODUCTION
The per-unit impedance calculation depends on whether the data that are provided
(modeled) is in kVAR, MVA or kVA, current, ohms, or percent. Note: In practice,
steps 3 and 4 are usually accomplished concurrently.
UTILITY OR SOURCE
The per-unit impedance calculation of the utility (Zu) depends on whether the data
are provided as kVA (or MVA), current, or ohms, as represented by the following
formulas:

Zu = kVAb/KVASCA or
= MVAb/MVASCA or
= Ib/ISCA or
= Z/Zb

Ru = Zu cos[tan-1(X/R)]

Xu = Zu sin[tan-1(X/R)] or
= (Ru)(X/R ratio)

Example C: What is the per-unit impedance (R + jX) of the utility system that is
shown in Figure 4-5?
Answer:

1. Zu = MVAb/MVASCA
= 100/950 = 0.1053 p.u.
2. Ru = Zu cos [tan-1(X/R)]
= 0.1053 cos [tan-1 (11.4)] = 0.0092 p.u.
3. Xu = Ru (X/R ratio)
= (0.0092)(11.4) = j0.1049 p.u. or
4. Xu = Zu sin [tan-1(X/R)]
= .1053 sin [tan-1 (11.4)] = j0.1049 p.u.

Chapter 4

Page 26

Short Circuit Calculations

TRANSFORMERS
The nameplate impedance of a transformer is provided in per-unit (Zpu(old)) on the
transformers kVA (kVAb(old)) and voltage (kVb(old)) ratings. Calculating the per-unit
impedance values of the transformer to the new kVA (kVAb(new)) and voltage
(kVb(new)) base ratings requires use of the change-of-base formula, as follows:

Zpu(new) = Zpu(old) (kVAb(new)/kVAb(old))(kVb(old)/kVb(new))2 = ZT or

Zpu(new) = Zpu(old) (kVAb(new)/kVAb(old)) (Assumes kVb(old) = kVb(new))

RT = ZT cos[tan-1(X/R)]

XT = (Rpu) (X/R ratio) or


XT = ZT sin[(tan-1(X/R)]

Example D: What are the per-unit impedances of the three transformers that are
shown in Figure 4-5?
Answer:

1. ZT = Zpu(old) (kVAb(new)/kVAb(old))(kVb(old)/kVb(new))2
ZT1 = (0.070)(100000/5000)(69/69)2 = 1.40 p.u. or
ZT1 = (0.070)(100/5)(13.8/13.8)2 = 1.40 p.u.
RT1 = 1.4 cos[tan-1(14)] = 0.0997 p.u.
XT1 = (0.0997)(14) = j1.3958 p.u.
2. ZT2 = (0.0550)(100/0.75)(0.48/0.48)2 = 7.333 p.u.
RT2 = 7.333 cos[tan-1(6)] = 1.2056 p.u.
XT2 = (6)(1.2056) = j7.2336 p.u.
3. ZT3 = (0.05)(100/2)(4.16/4.16)2 = 2.500 p.u.
RT3 = 2.500 cos[tan-1(8)] = 0.3101 p.u.
XT3 = (8)(0.3101) = j2.4808 p.u.

Chapter 4

Page 27

Short Circuit Calculations

MOTORS AND GENERATORS


Motor and generator reactance data are also provided in per-unit (Xpu(old)) on the
nameplate base kVA and voltage ratings. Calculating the reactance values also
requires use of the change-of-base formula as presented below:

Xpu(new) = (Xpu(old))(kVAb(new)/kVAb(old))(kVb(old)/kVb(new))2 or

Xpu(new) = (Xpu(old))(kVAb(new)/kVAb(old)) (Assumes kVb(old) = kVb(new))

Rpu = (Xpu)/(X/R ratio)

Example E: What are the per-unit impedances of the three motors that are shown
in Figure 4-5?
Answer:

1. XM1 = Xpu(new) = (Xpu(old))(kVAb(new)/kVAb(old))(kVb(old)/kVb(new))2


= (j.20)(100000/500)(.46/.48)2 = j36.7361 p.u.
RM1 = (Xpu)/(X/R ratio) = 36.7361/10 = 3.6736 p.u.
2. XM2 = (j.28)(100000/250)(.46/.48)2 = j102.8611 p.u.
RM2 = 102.8611/10 = 10.2861 p.u.
3. XM3 = (j.17)(100000/1000)(4/4.16)2 = j15.7174 p.u.
RM3 = 15.7174/20 = 0.7859 p.u.

Example F: Assuming that kVb(old) = kVb(new), repeat the per-unit calculations of


Example E.
Answer:

1. XM1 = (.20)(100/.5) = j40 p.u.


RM1 = 40/10 = 4.0 p.u.
2. XM2 = (.28)(100/.25) = j112.0 p.u.
RM2 = 112/10 = 11.2000 p.u.
3. XM3 = (.17)(100/1) = j17.00 p.u.
RM3 = 17/20 = 0.8500 p.u.

Chapter 4

Page 28

Short Circuit Calculations

CONDUCTORS
Conductor impedance data are provided in ohms (R + jX) per unit of length (e.g.,
1000 ft). Calculating the per-unit impedance of the conductors requires dividing the
given ohmic value by the base ohms (Zb) at the given voltage, as represented by the
following formulas:

Z = (R + jX) /1000 ft (Note: See Tables 4-2, 4-3, or 44).

Z = [(R + jX) /1000 ft](number of feet)

ZC = Z/Zb = (R/Rb) + j(X/Xb) = (R/Zb) + j(X/Zb)

Example G: What is the per-unit impedance of the cable (C2) that is shown in Figure
4-5?
Answer:

1. Z = (R + jX) /1000 ft (Note: See Table 4-3)


= (0.2020 + j0.0524) /1000 ft
2. Z = [(R + jX) /1000 ft](number of feet)
= [(0.2020 + j0.0524)/1000](500) = (0.1010 + j 0.0262)
3. ZC2 = Z/Zb = (0.1010 + j0.0262)/(1.9044)
= (0.0530 + j0.0138) p.u.

AERIAL LINES
Aerial line resistance data are provided in ohms (R1) per unit of length, for example,
1 mile, at a given temperature (t1 oC). If the operating temperature (t2oC) is different,
the resistance must be changed to a value (R2) for the operating temperature.
Aerial line reactance (Xa) that is based on the type of material is also provided in
ohms per unit of length, for example, 1 mile. Aerial line reactance (Xd) must be
calculated based on the configuration and spacing of the overhead lines (Figure 417).

Chapter 4

Page 29

Short Circuit Calculations

AERIAL LINES
The per-unit calculations for aerial line conductors are represented by the following
formulas:

R1 @ t1 oC (Note: See Tables 4-5 or 4-6.)

R2 @ t2 oC = R1[(T + t2oC)/(T + t1oC)] = R

where: T = 234.5 for annealed copper - 100% conductivity


= 241.0 for hard drawn copper - 97.3% conductivity
= 228.0 for hard drawn aluminum - 61% conductivity

R1, R2 = resistance of conductor at temperatures t1, t2 in 0C

X = Xa + Xd

where: Xa
Xd

= reactance of conductor per mile


(Note: See Tables 4-5 or 4-6.)
= 0.2794 log10 deq

deq = (dab x dbc x dca)1/3 (See Figure 4-17.)

Z = [(R + jX)/mile](number of miles)

ZOHL = Z/Zb = [(R/Zb) + j(X/Zb)] = Zpu

Figure 4-17. Aerial Lines Configuration and Spacing

Chapter 4

Page 30

Short Circuit Calculations

AERIAL LINES
Example H: What is the per-unit impedance of the overhead aerial line (C1) that is
shown in Figure 4-5? Assume an ambient temperature of 40oC.
Answer:

1. RC1 @ t1 oC = RC1 @ 25 oC = .888 /mi (Table 4-6)


2. RC1 @ 40 oC = .888 [(228 + 40)/(228 + 25)] = .9406 /mi
3. XaC1 = j.656 /mi (Table 4-6)
4. deq = (dab x dbc x dca)1/3 (Figure 4-18)
= (3.5 x 3.5 x 7.0)1/3 = 4.41 ft.

Figure 4-18. Aerial Line Configuration (Example H)


5. XdC1 = 0.2794 log10 deq
= 0.2794 log10 (4.41) = .180 /mi
6. ZC1 = [R + j (Xa + Xd)] (number of miles)
= [.9406 + j(.656 + .180)] (1.25)
= (1.1758 + j1.045)
7. ZC1 = Z/Zb
= (1.1758 + j1.045)/(1.9044)
= (0.6174 + j0.5487) p.u.

Chapter 4

Page 31

Short Circuit Calculations

GROUNDING RESISTORS, REACTORS, AND CAPACITORS


Grounding resistor and reactor data is typically provided in ohms, amperes, and
time. The per-unit impedance calculation of a grounding resistor or a reactor is
represented by the following formulas:

Zpu = Z/Zb or Zpu = Ib/Iamps

Note: Resistors are modeled as resistive ohms (R) and reactors are modeled as
reactive ohms (jX).
Example I: What is the per-unit impedance of the 6 , 400-ampere grounding
resistor (ZR) that is shown in Figure 4-5?
Answer:

1. ZR = Z/Zb = 6/.173 = 34.6821 p.u. or


2. ZR = Ib/Iamps = 13878.6/400 = 34.6965 p.u.

Capacitor data is typically provided in kVARs, MVARs, and voltage. The per-unit
impedance calculation of a capacitor is represented by the following formulas:

Z = kV2/MVAR or Z = [kV2 x 1000]/kVAR

Zcap = Z/Zb

Example J: What is the per-unit impedance (Zcap) of the capacitor bank (1200
kVAR) that is shown in Figure 4-5?
Answer:

1. Z = (13.8)2/(1.2) = 158.7
2. Zcap = 158.7/1.9044 = - j83.3333 p.u.

Chapter 4

Page 32

Short Circuit Calculations

IMPEDANCE DIAGRAMS (STEP 5)


COMPLEX IMPEDANCE DIAGRAM (R + jX)
The final step in per-unit modeling of an electrical power system is to draw and label
the series/parallel network of resistances and reactances, which is called the
complex impedance diagram.
Example K: Draw and label the complex impedance diagram for the power system
(one-line diagram) that is shown in Figure 4-5. Ignore the grounding
resistor and the capacitor bank.
Answer:

See Figure 4-19.

Figure 4-19. Complex Impedance Diagram (Example K)

Chapter 4

Page 33

Short Circuit Calculations

REACTANCE (X-ONLY) DIAGRAM (R = 0)


The X-only reactance diagram requires redrawing and labeling the complex
impedance diagram with the resistances omitted (R = 0).
Example L: Draw and label the X-only reactance diagram.
Answer:

See Figure 4-20.

Figure 4-20. X-Only Diagram (Example L)


RESISTANCE (R-ONLY) DIAGRAM (X = 0)
The R-only resistance diagram requires redrawing and labeling the complex
impedance diagram with the reactances omitted (X = 0).
Example M: Draw and label the R-only resistance diagram.
Answer:

See Figure 4-21.

Figure 4-21. R-Only Diagram (Example M)

Chapter 4

Page 34

Short Circuit Calculations

PROBLEM
PROBLEM 3: ONE-LINE DIAGRAM
Model the following power system (Figure 4-22) in per-unit on a 100 MVA base.

Figure 4-22. One-Line Diagram (Problem 3)

Chapter 4

Page 35

Short Circuit Calculations

PROBLEM 3: ONE-LINE DIAGRAM


Note: This page left intentionally blank for the answer to Problem 3.
Answer:

Chapter 4

Page 36

Short Circuit Calculations

MODIFY MACHINE REACTANCES (STEP 6)


MOMENTARY AND INTERRUPTING DUTIES
For multivoltage calculations, the reactances of machines must be modified to reflect
the momentary duty and interrupting duty of medium voltage breakers (Figure 4-23).

Figure 4-23. Medium Voltage Breaker Duties


Momentary Duty Network: Motors and generators are modeled for the momentary
duty network (first-cycle) as follows: Note: See Table 4-7.

Induction motors less than 50 hp:


X = 1.67 Xd or X = 28% on motor rating or neglect

Induction motors greater than 50 hp:


X = 1.2 Xd or X = 20% on motor rating

Interrupting Duty Network: Motors and generators are modeled for the interrupting
network as follows: Note: See Table 4-7.

Induction motors less than 50 hp: - neglect

Induction motors greater than 50 hp:


X = 3.0 Xd or X = 50% on motor rating

Synchronous motors and induction motors > 250 hp:


X = 1.5 Xd

Chapter 4

Page 37

Short Circuit Calculations

MACHINE REACTANCE MULTIPLIERS


Type of
Rotating Machine

Interrupting Duty
(Per Unit)

Momentary Duty
(Per Unit)

All turbo-generators, all hydrogenerators with amortisseur windings,


and all condensers

1.0Xd

1.0Xd

Hydro-generators without
amortisseur windings

0.75Xd

0.75Xd

All synchronous motors

1.5Xd

1.0Xd

1.5Xd

1.0Xd

3.0Xd

1.2Xd

Neglect

Neglect

3.0Xd (Note 5)
Neglect

1.2Xd (Note 3)
1.67Xd (Note 4)

Induction Motors
Above 1000 hp at 1800 r/min or less
Above 250 hp at 3600 r/min
All others, 50 hp and above
All smaller than 50 hp
(a)
Induction Motors (Note 2)
All others, 50 hp and above
All smaller than 50 hp

(b)
Notes: 1. Resistance values should also use same multipliers.
2. For comprehensive multivoltage calculations.
3. Or X = .20 p.u. based on motor rating.
4. Or X = .28 p.u. based on motor rating.
5. Or X = .50 p.u. based on motor rating.
* Source IEEE Red Book

Table 4-7. Rotating Machine Reactance Multipliers


Example N: Referring to the one-line diagram that is shown in Figure 4-5 and the
machine reactance multipliers that are listed in Table 4-7, model the
interrupting duty reactances of motors M1, M2, and M3. Draw the
modified X-only and R-only impedance diagrams.

Chapter 4

Page 38

Short Circuit Calculations

IMPEDANCE DIAGRAMS
Answer:

1. XM1 = (.50)(100/.500) = j100.0 p.u.


RM1 = 100/10 = 10.0 p.u.
2. Neglect XM2 and RM2 (<50 hp).
3. XM3 = (1.5 x .17)(100/1) = j25.5 p.u.
RM3 = 25.5/20 = 1.275 p.u.
4. See Figure 4-24.

Figure 4-24. Interrupting Network Diagrams

Chapter 4

Page 39

Short Circuit Calculations

THEVENIN EQUIVALENT NETWORK (STEP 7)


THEVENIN EQUIVALENT CIRCUIT
The Thevenin equivalent network (Figure 4-25) involves combining the series/parallel
network of impedances into a single Thevenin equivalent impedance (reactance).

Figure 4-25. Thevenin Equivalent Circuit


The interrupting duty of low and medium voltage fuses and low voltage circuit
breakers (MCCBs and LVPCBs), and the closing and latching capability (momentary
duty) of medium voltage circuit breakers must be calculated by using the momentary
duty reactances of all machines. The interrupting duty of medium voltage circuit
breakers is calculated exactly the same way except that the interrupting duty
reactances, as modified in Table 4-7, are used to model the machines.
The IEEE Red Book admits that reduction of the complex network is more accurate,
but that reduction of the separate R and X networks is simpler. The IEEE Red Book
also states that the separate network reductions are more conservative and that the
X/R ratios are the best approximation.

Chapter 4

Page 40

Short Circuit Calculations

SUMMARY OF SHORT CIRCUIT PROCEDURE


Objectives of Short Circuit Calculations
1. Determine if protective devices (fuses, breakers) are properly
applied or overdutied
2. Help determine settings for the breakers and relays.
Procedure for calculating Fault Levels

Construct accurate and up-to-date single line diagram.

Change all impedances to per unit impedances

Utility
Zpu (new) = (MVAbase / MVAavail)
determine Rpu and Xpu from given X/R ratio from utility

Transformers
Zpu(new)

= Zpu(old) *(100 / MVAtxmr)

Refer to Figure 4-8 of the notes and estimate the X/R ratio
Break down Zpu into Rpu and Xpu

Chapter 4

Page 41

Short Circuit Calculations

Cables
Find R(ohms) and X(ohms) from cable manufacturer,
If not available, refer to Tables 4-2 and 4-3 of the notes to
estimate the cables R and X per 1000 feet
Calculate R and X (in ohms) by multiplying by the length of the
cable
Rp.u =

R(ohms) / Zbase

Xp.u. =

X(ohms) / Zbase

Where Zbase depends on the voltage of the cable,


Zbase

is given in Table 4-1 of the notes

Induction Motors
Xpu (new)

= Xpu(old) * (100,000 / HP),


because we assume 1 HP = 1 KVA

Refer to Figure 4-15 of the notes to estimate the X/R ratio


Rpu(new)

= Xpu(new) / (X/R) ratio

Synchronous Motors
If the motor has 0.8 P.F.

1 Hp = 1 KVA

If the motor has 1.0 P.F

1 KVA = 0.8 HP

Xpu(new)

= Xpu(old) * (100,000/KVA)

Refer to Figure 4-13 of the notes to estimate the X/R ratio


Rpu(new)

= Xpu(new) / (X/R) ratio

Now you can construct the per unit impedance diagram

Chapter 4

Page 42

Short Circuit Calculations

Next, have to do half cycle (momentary calculations)

Keep impedances of utility, transformers, cables unchanged

Generators
Their per unit impedances stay the same (as per Table 4-7)

Synchronous motors
Their per unit impedance stays the same (as per Table 4-7)

Induction Motors
Above 1000 Hp motors: Their per unit impedance stays the same (as
per Table 4-7)
50-1000 Hp motors: Multiply their per unit impedance by a factor of 1.2
(as per Table 4-7)
Individual motors, each less than 50 HP motors:
neglect, or lump
together as one big induction motor, and also use a multiplying factor of
1.2

Chapter 4

Page 43

Short Circuit Calculations

Construct a momentary per unit impedance diagram


Find the symmetric half cycle fault at every bus

Find the X/R of the fault at every bus

Calculate Mm and Ma at every bus (from page 3-20 of notes)

If the faulted bus has low voltage breakers


Ifault asym=

Ifault sym (just calculated) * Ma

Compare Symm interr. rating of breaker with Ifault sym


Compare Asymm interr. rating of breaker with Ifault asymm

(Symmetric and asymmetric ratings of low voltage breakers are


provided by manufacturer)
This will determine, whether or not, breaker is properly applied

If the faulted bus has Low Voltage Fuses


Ifault asym=

Ifault sym (just calculated) * Mm

Compare Symm interr. Rating of fuse with Ifault sym


Compare Asymm interr. rating of fuse with Ifault asymm

This will determine, whether or not, fuse is properly applied

Chapter 4

Page 44

Short Circuit Calculations

If the faulted bus has Medium Voltage Fuses


Ifault asym=

Ifault sym (just calculated) * Mm

Compare Symm interr. Rating of fuse with Ifault sym


Compare Asymm interr. rating of fuse with Ifault Asymm

This will determine, whether or not, fuse is properly applied

If the faulted bus has Medium (high) voltage breakers


Ifault asym=

Ifault sym (just calculated) * Mm

Compare Close and latch rating of breaker with Ifault Asym


(not done yet, have to do 5 cycle calculations too)

Chapter 4

Page 45

Short Circuit Calculations

Construct interrupting per unit impedance diagram

Keep impedances of utility, transformers, cables in generic diagram


impedance unchanged

Generators
Their per unit impedances stay the same (as per Table 4-7)

Synchronous motors
Their per unit impedance is multiplied by 1.5 (as per Table 4-7)

Induction Motors
Above 1000 Hp motors: Their per unit impedance is multiplied by 1.5 (as
per Table 4-7)
50-1000 Hp motors: Multiply their per unit impedance by a factor of 3.0
(as per Table 4-7)
Individual motors, each less than 50 HP motors:
neglect, or lump
together as one big induction motor, and also use a multiplying factor of
3.0

Find the symmetric half cycle fault at every bus

Chapter 4

Page 46

Short Circuit Calculations

If the faulted bus has Medium (high) voltage breakers

Compare interrupting rating of breaker (after correction for voltage)


with Ifault sym

M.V. Breaker is properly applied if:

Close and Latch rating greater than Ifault asymm.( at half cycle),
and
Interrupting rating (corrected for voltage) is greater than Ifault
symm (at 5 cycles)

Chapter 4

Page 47

Short Circuit Calculations

APPLICATION PROBLEM

For the utility, MVA SC = 500 MVA, (X/R) = 10


The transformer is 5 MVA, with Z% = 6%
The motor is 2000 HP induction motor, with Xd = 0.17
Determine if a 5 kv, 250 MVA breaker can be used at the bus

Chapter 4

Page 48

Short Circuit Calculations

Solution
For the utility
Zpu = 100/500 = 0.2 PU

X/R = 10

R = Z/(1+(X/R)2) = 0.0199 PU
X = R * (X/R) = 0.199 PU

For the 5 MVA Transformer


Zpu = 0.06 * (100/5) = 1.2 PU,

assume (X/R) = 12

R = Z/(1+(X/R)2) = 0.0996545 PU
X = R * (X/R) = 1.195854 PU

For the Motor


XPU = 0.17 * (100000,2000) = 8.5, assume (X/R) = 31
RPU = X / (X/R) = 0.2741935

Chapter 4

Page 49

Short Circuit Calculations

Generic Impedance Diagram

R = 0.0199
Utility
X = 0.199

R = 0.0997
Transformer
X = 1.196

R = 0.274
Motor
X = 8.50

Chapter 4

Page 50

Short Circuit Calculations

Momentary Impedance Diagram

No need to modify the impedances of utility or transformer or induction


motor
Momentary impedance diagram equals generic impedance diagram

R = 0.0199
Utility
X = 0.199

R = 0.0997
Transformer
X = 1.196

R = 0.274
Motor
X = 8.50

Chapter 4

Page 51

Short Circuit Calculations

Using the R-only, X- only method


R only Diagram will look as follows:

R = 0.0199
Utility
R = .1196

R = 0.0997
Transformer

R = 0.274

R = .0.274

Motor

Rth = (R1*R2) / (R1 + R2)

= (.1196*.274) / (.1196 + .274)

= 0.08326 P.U.

Chapter 4

Page 52

Short Circuit Calculations

The X only Impedance diagram will look as follows:

Utility
X = 0.199
X1 = 1.395

Transformer
X = 1.196

Motor

X2 = 8.50
X = 8.50

Xth = (X1 * X2) / (X1 + X2)


= (1.395 * 8.50) / (1.395 + 8.50)
= 1.198
Zpu = (Rpu2 + Xpu2)

= 1.2009

Ipu = 1 / (Zpu)
Ipu = 0.8327
Ibase = 13,878.6 (base voltage on a 4160 volt system)

Chapter 4

Page 53

Short Circuit Calculations

Therfore, Ifault

= Ipu * Ibase
= 0.8327 * 13,878.6 = 11,556.93 amps

And (X/R) ratio = 14.38862 therefore


Ifault asym

Mm = 1.512

= 1.512 * 11,556.93 = 17,474 amps

Comparing that number with the close and latch breaker of the breaker
(58,000 amps), the breaker can close in on such a fault (58,000 greater
than 17,474)

Chapter 4

Page 54

Short Circuit Calculations

Interrupting Duty
Only thing that changes are the Rpu and Xpu for the motor
They get multiplied by as factor of 1.5
The interrupting impedance diagram looks as follows:

R = 0.0199
Utility
X = 0.199

R = 0.0997
Transformer
X = 1.196

R = 0.274

0.411

Motor
X = 8.50

Chapter 4

Page 55

12.75

Short Circuit Calculations

Repeating all calculations as before, we get


Rth = 0.09264
Xth = 1.2574
Zpu = 1.260831
Ipu = 0.7884507
Ifault = (0.7884507) * (13,878.6)
= 10,942.6 amps
For the interrupting rating o the breaker

At 4.16 kv, the breaker can interrupt


29,000 * (4.76/4.16)

33,183 amps

And 33,183 greater than 10,942.6

Since breaker meets half cycle and 5 cycle criteria, it is properly applied

Transformer FLA = 5000/(* 4.16) = 693 amps


Therefore should use a breaker rated for 1200 amps

Chapter 4

Page 56

Short Circuit Calculations

Chapter 4

Page 57

Short Circuit Calculations

270 VCP-W 25

13.8

150 VCP-W 1000

13.8

150 VCP-W 500

13.8

7.2

75 VCP-W 500

150 VCP-W 750

4.16

50 VCP-W 350

Class

4.16

Type

50 VCP-W 250

kV

Circuit

1000

750

500

500

350

250

Class

MVA

Voltage

Class

Breaker

Maximum

MVA

Class

27

15

15

15

8.25

4.76

4.76

kV rms

Rated

3-Phase

Voltage

Rated

1.0

1.30

1.30

1.30

1.25

1.19

1.24

60

36

36

36

36

19

19

kV rms

quency

125

95

95

95

95

60

60

kV Crest

1200
2000
3000
1200
2000
3000
1200
2000
3000
1200
2000
3000
1200
2000
3000
1200
2000
3000
1200

Amperes

25

37

28

18

33

41

29

kA rms

Cycles

V/K

Sec.

27

11.5

11.5

11.5

6.6

4.0

3.85

kV rms

25

48

36

23

41

49

36

kA rms

KI

Fre-

Short Circuit
Current

kV)

Capability

Carrying

Current

Time

Short-

kA rms

25

48

36

23

41

49

36

40

77

58
77

37
58

66

78

58
78

kA rms

Current

Circuit

Rated Short

67.5

130

97
130

62
97

111

132

97
132

kA Crest

Current

Circuit

Rated Short

2.7 K Times

(Momentary)

Capability

Latching

and

Closing

1.6 K Times

Current Values
3 Sec

K Times Rated

Low
Impulse

Capability

Max.

Inter-

rated

By K
rupting

Delay

Sym.

mum

(at

Divided

Voltage

Maxi-

Current

Tripping

sible

Max.

Related Required Capabilities

Current

Time

rupting

Permis-

Rated

at 60 Hz

Circuit

Short

Inter-

Rated

Factor

Contin-

Rated

Rated

uous

Test Voltage

Rated Withstand

Current
Rated

Rated Values
Insulation Level

Range

Voltage

Voltage

Nominal

Nominal

Identification

Chapter 4

Page 58

Short Circuit Calculations

Chapter 4

Page 59

Short Circuit Calculations

Chapter 4

Page 60

Short Circuit Calculations

S-ar putea să vă placă și