The exhaust rates have been calculated as follows:

BI-25-00002009

TEA

ENGG CERT

JSM

Figure 1 Excerpt from ASHRAE 61.1

APR 2015

REV
NO.

Exhaust System Quantities

The specified kitchen and toilet exhaust quantities are based on AHSRAE 62.1-2013, Table 6.5:

Washrooms
Kitchens

DISCIPLINE
ENGINEER

JSM

5.2

08/06/15

DATE:
PROJECT
ENGINEER

No of units
per room

Operation
(continuous/ intermittent)

Air flow (CFM)

Intermittent

50

N/A

Intermittent

110

Fresh Air System Quantities

The Fresh air supply quantities to the apartments have been calculated using the calculation
method stated in the Saudi Aramco Engineering Standard SAES-K-001, paragraph 4.4.11.1
(figure 2 below):

JSM
DATE:

CALCULATIONS FOR APARTMENT EXHAUST AND FRESH AIR SYSTEMS


5.1

01

BI-25-00002009

JO/EWO

DESCRIPTION

ISSUED FOR 60% REVIEW

08/06/15

CERTIFIED

TEA
DATE:

08/06/15

CONSTRUCTION
AGENCY

DATE:

OPERATIONS

DATE:
(DCC) NO. _____________________

BY:
BY DRAWING COMPLETION CERTIFICATE

CONTROL NUMBER
APPROVAL/CERTIFICATION REQUIREMENTS,

OF THIS DRAWING IS COVERED, FOR ALL

REVISION
REVISIONCERTIFICATION
CERTIFICATE

01
THIS INDICATES THAT REV. NO.__________

EDSD
VERIFICATION

DATE:

Figure 2 Excerpt from SAES-K-001

HVAC CALCULATIONS
NEW STUDENT HOUSING KAUST
SAUDI ARABIA

DWG.TYPE

DOC

PLANT NO.

INDEX

DRAWING NO.

NSH

NSH-K-CAL

JO / EWO:

BI-25-00002-009

SHT.NO.

7
OF
15

REV.NO.

02

EDSD/2616-0399.doc

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.

PMT OPRNS

Saudi Aramco 2616-ENG (03/99)

SAUDI ARABIAN OIL COMPANY


Using the method a) from paragraph 4.4.11 in SAES-K-001:

TEA

TEA

JSM

JSM

ISSUED FOR 60% REVIEW

ISSUED FOR 90% REVIEW

BI-25-00002009

BI-25-00002009

JUN 2015

02

DATE

Associated exhaust systems:

1 x Kitchen @ 110CFM
1 x Washroom @ 50CFM

Total exhaust quantity:

160 CFM

FCU supply air calculation note:

760 CFM

5% of supply air:

38 CFM

Total exhaust + 5% of supply:

160 + 38 = 198 CFM

Fresh air quantity (rounded) =

200 CFM

FCU-02 and FCU-03 serving bedrooms

APR 2015

REV
NO.

FCU-01 serving living rooms and kitchens

01

JO/EWO

DESCRIPTION

ENGG CERT

The fresh air quantity per apartment building is calculated as follows:

DISCIPLINE
ENGINEER

Associated exhaust systems:

1 x Washroom @ 50CFM

Total exhaust quantity:

50 CFM

FCU supply air calculation note:

400 CFM

5% of supply air:

20 CFM

Total exhaust + 5% of supply:

50 + 20 = 70 CFM

Fresh air quantity (rounded) =

70 CFM

Calculation note: FCU supply air figures are based on the highest cooling demand orientation, i.e. west-facing buildings

JSM
DATE: 08/06/15
PROJECT
ENGINEER

AHU-DOAS-01
The total fresh air quantity for (dedicated outside air system) DOAS is calculated as follows:

JSM
DATE:

Per apartment building (22 in total):

08/06/15

CERTIFIED

TEA
DATE:

08/06/15

CONSTRUCTION
AGENCY

Number of FCU-01 systems:

16

Number of FCU-02& 03 systems:

32

Air quantity calculation:

AQ = (16 x 200CFM) + (32 x 70CFM)

DATE:

= 3,200 + 2,240

OPERATIONS

= 5,440 CFM per DOAS unit


= 2,560 L/s (approximately)

DATE:
(DCC) NO. _____________________

BY:
BY DRAWING COMPLETION CERTIFICATE

CONTROL NUMBER
APPROVAL/CERTIFICATION REQUIREMENTS,

OF THIS DRAWING IS COVERED, FOR ALL

REVISION
REVISIONCERTIFICATION
CERTIFICATE

01
THIS INDICATES THAT REV. NO.__________

EDSD
VERIFICATION

DATE:

HVAC CALCULATIONS
NEW STUDENT HOUSING KAUST
SAUDI ARABIA

DWG.TYPE

DOC

PLANT NO.

INDEX

DRAWING NO.

NSH

NSH-K-CAL

JO / EWO:

BI-25-00002-009

SHT.NO.

8
OF
15

REV.NO.

02

EDSD/2616-0399.doc

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.

PMT OPRNS

Saudi Aramco 2616-ENG (03/99)

SAUDI ARABIAN OIL COMPANY

TEA
JSM
ISSUED FOR 90% REVIEW
BI-25-00002009

JUN 2015

02

JO/EWO

BI-25-00002009

01

REV
NO.

DATE

APR 2015

ISSUED FOR 60% REVIEW

DESCRIPTION

JSM

TEA

ENGG CERT

Using method b) from paragraph 4.4.11.2 in SAES-K-001, ASHRAE STD 62.1:

DISCIPLINE
ENGINEER

JSM

08/06/15

DATE:
PROJECT
ENGINEER

JSM
DATE:

Figure 3 Excerpt from ASHRAE 62.1

08/06/15

CERTIFIED

The required ventilation rate for the apartment building is calculated as follows:

TEA
DATE:

08/06/15

CONSTRUCTION
AGENCY

DATE:

OPERATIONS

DATE:
(DCC) NO. _____________________

BY:

Ra, Outdoor airflow rate required per unit area = 0.06 cfm/ft2

BY DRAWING COMPLETION CERTIFICATE

CONTROL NUMBER
APPROVAL/CERTIFICATION REQUIREMENTS,

OF THIS DRAWING IS COVERED, FOR ALL

EDSD
VERIFICATION

REVISION
REVISIONCERTIFICATION
CERTIFICATE

Pz, Total number of people for a 2 bedroom apartment = 3 people


(AHSRAE states 2 person per 1 bedroom plus 1 additional person per bedroom)
Rp, Outdoor airflow rate per person is = 5 cfm/person

DATE:

01
THIS INDICATES THAT REV. NO.__________

Az, Total area per apartment = 1,030 ft2

Total ventilation rate per apartment is calculated


Vbz = 5 x 3 + 0.06 x 1,030
= 15 + 61.8
= 76.8 cfm/apartment
Therefore total ventilation per apartment building is:
16 apartments x 76.8 cfm/apartment = 1,229 cfm
HVAC CALCULATIONS
NEW STUDENT HOUSING KAUST
SAUDI ARABIA

DWG.TYPE

DOC

PLANT NO.

INDEX

DRAWING NO.

NSH

NSH-K-CAL

JO / EWO:

BI-25-00002-009

SHT.NO.

9
OF
15

REV.NO.

02

EDSD/2616-0399.doc

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.

PMT OPRNS

Saudi Aramco 2616-ENG (03/99)

SAUDI ARABIAN OIL COMPANY

TEA

Calculation method

JSM

JSM

TEA

ENGG CERT

The DOAS unit would be sized for the greater of the above calculation methods. These figures
are summarized below:
DOAS unit airflow

5% of supply air plus exhaust

5,440 cfm

ASHRAE 62.1, paragraph 6.2.2.1

1,229 cfm

ISSUED FOR 90% REVIEW


BI-25-00002009

JUN 2015

02

01

REV
NO.

DATE

APR 2015

BI-25-00002009

JO/EWO

ISSUED FOR 60% REVIEW

DESCRIPTION

The DOAS unit design flow rates for the New Student Housing is based upon the calculation
method of 5% of supply air plus exhaust air.

DISCIPLINE
ENGINEER

JSM

08/06/15

DATE:
PROJECT
ENGINEER

JSM
DATE:

08/06/15

CERTIFIED

TEA
DATE:

08/06/15

CONSTRUCTION
AGENCY

DATE:

OPERATIONS

DATE:
(DCC) NO. _____________________

BY:
BY DRAWING COMPLETION CERTIFICATE

CONTROL NUMBER
APPROVAL/CERTIFICATION REQUIREMENTS,

OF THIS DRAWING IS COVERED, FOR ALL

REVISION
REVISIONCERTIFICATION
CERTIFICATE

01
THIS INDICATES THAT REV. NO.__________

EDSD
VERIFICATION

DATE:

HVAC CALCULATIONS
NEW STUDENT HOUSING KAUST
SAUDI ARABIA

DWG.TYPE

DOC

PLANT NO.

INDEX

DRAWING NO.

NSH

NSH-K-CAL

JO / EWO:

BI-25-00002-009

SHT.NO.

10
OF
15

REV.NO.

02

EDSD/2616-0399.doc

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.

PMT OPRNS

Saudi Aramco 2616-ENG (03/99)

S-ar putea să vă placă și