Cairo at 29th February 2016

To:
Suez Cement Company
Attn.: Eng. Reda AlShahat
Eng. Pola Barsoum

Infrared Thermal Imaging Inspection Report


Customer:

Italcementi Company

Site:

Suez Cement Plant

Lines:

1&2

Rooms:

9, 10, 11, 12, 22, 23, 24 and 25

Equipment:

Electric System

Date:

February 22, 23 - 2016

Reported by

Sherif Mounir Ahmed


"Technical Support / Senior Service Engineer"

Introduction
Infrared Thermographic image is an excellent condition monitoring tool to assist in
the reduction of maintenance costs on the electrical system and mechanical equipment and
detect developing problems. The technique allows for the monitoring of temperatures and
thermal patterns while the electrical system and mechanical equipment are online and
operating under full load. Unlike many other test methods, Infrared Thermal Imaging can be
used on a wide variety of electric components and mechanical equipment. It has been
proven time after time to readily identify reliability and safety concerns, and to provide
excellent short-term. For example, early detection of a single fault in a large transformer can
easily save over one million dollars in maintenance costs.

What is infrared?
Infrared energy is part of the electromagnetic spectrum and behaves similarly to
visible light. It travels through space at the speed of light and can be reflected, refracted,
absorbed, and emitted. Has a wavelength longer than that of visible light. Infrared is usually
divided into 3 spectral regions: near, mid and far-infrared.

Where does infrared energy come from?


All objects emit thermal energy (heat) during normal operation as a function of their
temperature. This means all objects emit infrared radiation. Infrared energy is generated by
the vibration and rotation of atoms and molecules. The higher the temperature of an object,
the more the motion and hence the more infrared energy is emitted. This is the energy
detected by infrared cameras which detect thermal radiation only, not temperature. And the
most important factor that affects radiation emitted form a target is its emissivity. Emissivity
is the ability of a body to emit radiation. Each material has its own emissivity.

What is infrared thermography?


All objects emit infrared radiation in the form of electromagnetic radiation in the
infrared spectrum which allows Infrared thermal imaging to evaluate their operating
condition. The hotter the object is, the more intense the infrared radiation emitted. This
radiation is, however, outside of the human eye range. Infrared thermography is used to
image and measure to detect this radiation. By detecting areas of abnormal temperature,
infrared thermography can diagnose problem areas and their severity.
Infrared Thermography is the technique for producing an image of invisible infrared light
emitted by objects due to their thermal condition.
An image produced by an infrared camera is called a thermogram or sometimes a
thermograph.
Thermography allows one to make non-contact measurements of an objects temperature.
SKF cameras provide detailed photographs indicating each piece of operating component's
"heat signature". The amount of temperature rise over the normal operating temperature
provides a good indicator of the severity of a problem. This thermal profile, correctly
interpreted, can reveal a great deal regarding the operating condition of the equipment
being inspected. A probable cause and recommended action then can be suggested for each
finding.

Page | II

Why does infrared thermography work?


In mechanical and electrical applications, Infrared Thermal Imaging is more useful
for locating a problem area than for indicating the root cause of the overheating. The heat is
usually produced within a component that is not visible directly to the camera. That heat
must conduct up through the material and present itself as a pattern on the surface of the
object in order for the infrared camera to sense it.
Most component or processes are designed to eliminate thermal energy under normal
operation; simply identifying a thermal pattern does not mean a problem has been located.
Once a normal thermal signature is obtained and understood, any deviation from this
normal signature will then provide evidence of a suspect problem developing.

Why infrared thermography surveys are important?


Infrared Thermal Imaging is an electronic technique that quite literally allows us to
see thermal energy. Infrared thermographic imaging has been available for many years as a
troubleshooting tool. With this new capability plant maintenance personnel have recognized
Infrared Thermal Imaging as one of the most versatile and effective condition monitoring
tools available today. Infrared Thermal Imaging enhances a company's ability to predict
equipment and component failure and plan corrective action before a costly shutdown,
component damage, or personal injury occurs.

How infrared thermography is performed?


Performed on operating equipment and machinery, an infrared survey is a
nondestructive test that does not interrupt normal business operations. Measurements are
made:

While the plant is operating.


Without contacting the target object.
With the equipment under full load.
From a safe distance from energized electrical component, rotating equipment or
equipment in hostile environments.
Points in the same target, and compare them.
Real time imaging allows us to do very fast scanning of stationary targets with immediate
results.
The real time character of infrared thermography lets us capture very fast moving target.
After the survey is completed, a report is prepared and can be delivered on-site in either
electronic format.

Electrical Inspection
One of the biggest problems in electrical systems is excessive temperatures. This
excessive heat from distribution and transmission systems for hot spots can be generated by
loose connections, damage, load imbalances and other failure mechanisms. Most electrical
system (such as transformers, Panel Boards, Control Panels, bus bars, transmission lines,
isolation disconnects, , relays, wiring ,Switchboards, Power Cabling, Cable Terminations,
Fuse Disconnects and holders) has allowable operating temperature limits that can be used
as guidelines.

Page | III

Order and scope of work


As a partnership between Company & Industrial Services Center- DATCO, DATCO
submit Infrared Thermal Imaging Inspection on site dated February 22 , 23 - 2016

General Information
Thermographer & Analyst
Infrared thermographic camera
Firmware of the camera
Software Reporter

Page | IV
Sherif Mounir Ahmed
E 50 IR camera
Version 2.23.14
Version 5.4.15351.1001

Description of survey
The inspection covered the components of the electrical system and the electric
insulation systems that were under load at the time of survey. All components of the
electrical systems conform to coding system. The electric insulation systems rated by NEMA,
UL and IEC standards according to as insulation class or thermal classification of each
system.

Coding System
A code is assigned to each of the discovered faults. The purpose behind such procedure is to
classify the faults depending on the degree of seriousness of each fault. The more serious
the fault the more urgent it has to be corrected.
I-

High Voltage

Page | V

Fault

Action

Description

Temperature
Increase ( C)

One

Danger

Immediate repair required

For components temp. exceeding 70c and/or


temperature rise (compared to similar components
under similar load)

> 50

Two

Critical

Repair ASAP

For temp. rise (compared to similar components


under similar load)

30 - 50

Three

Warning Schedule repair

For temp. rise (compared to similar components


under similar load)

20 - 30

Four

Alert

For temp. rise (compared to similar components


under similar load)

< 20

Code

Monitor development and


repair as necessary

II-

Medium & Low Voltage

Fault

Action

Description

Temperature
Increase ( C)

One

Danger

Immediate repair required

For components temp. exceeding 70c and/or


temperature rise (compared to similar components
under similar load)

> 30

Two

Critical

Repair ASAP

For temp. rise (compared to similar components


under similar load)

20 - 30

Three

Warning Schedule repair

For temp. rise (compared to similar components


under similar load)

10 - 20

Four

Alert

For temp. rise (compared to similar components


under similar load)

5 - 10

Code

Monitor development and


repair as necessary

Note: The codes are based on British Engineering Standards BS7671 - Regulation 523-01.

Executive Summary of Inspection:


Part 1: Line 1 Rooms 9 & 10
Ser.

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22

Area

37

Image

K5-1
K5-3

GR0809
GR0811
GR0813
D63-1
GR0815
GR0817
K11-1
GR0967
C9
GR0819
GR0821
C24
GR0823
Line 1
Room 9
GR0825
GR0827
D41-1
Bucket Elevator
GR0829
GR0831
D141 Dust Collector Fan GR0833
GR0963
TS M1 Transfer switch
GR0965
GR0959
TS DIE Transfer switch
GR0961
H725 Coal Feeding Blower "Clinker GR0835
1"
GR0837
GR0775
E 68
GR0777

23
24
25
26
27
28
29
30
31
32
33
34
35
36

Equipment (Unit)

E 69

Line 1
Room 10

GR0779

E47

GR0781
GR0783
GR0785
GR0787
GR0789
GR0791
GR0793
GR0801
GR0795
GR0797
GR0803
GR0805
GR0799

E88-4

GR0807

E30
E7
E55-c
Atlas Copco
E29
Compressor 2
Filter feeder 1& 2
D60 A1
D60 A3

Code

Fault

Action

Normal No Fault
Normal No Fault

No Action Required
No Action Required

Normal No Fault

No Action Required

Normal
Normal
Four
Normal

No Action Required
No Action Required
Monitor development and repair as necessary
No Action Required

No Fault
No Fault
Alert
No Fault

Page | VI

Normal No Fault

No Action Required

Normal No Fault

No Action Required

Normal No Fault

No Action Required

Normal No Fault

No Action Required

Normal
Normal
Three
Normal
Four
Three
Normal
Normal
Normal
Normal
Normal
Normal
One
Normal

No Action Required
No Action Required
Schedule repair
No Action Required
Monitor development and repair as necessary
Schedule repair
No Action Required
No Action Required
No Action Required
No Action Required
No Action Required
No Action Required
Immediate repair required
No Action Required

No Fault
No Fault
Warning
No Fault
Alert
Warning
No Fault
No Fault
No Fault
No Fault
No Fault
No Fault
Danger
No Fault

Normal No Fault

No Action Required

Normal No Fault

No Action Required

Three
Four
Three

Schedule repair
Monitor development and repair as necessary
Schedule repair

Warning
Alert
Warning

Part 2: Line 1 Rooms 11 & 12


Ser.

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40

Area

Equipment (Unit)

E102
E117
Main Breaker MCC E4
Line 1
Room 11

Main Breaker - MCCE5


Main Breaker - MCCFA
F150
FAE
Main Breaker - MCCF
Transfer switch
F19
F18
F16-1
F20
F21
F25A
F23
F25C
F16-2
F16-3
F26
F33-1

Line 1
Room 12

F22
F131-2
F22A
F25
F25B
Main C.B.
Atlas Copco
Compressor
Transfer switch

Image

Code

Fault

GR0749
GR0751
GR0753
GR0755
GR0757
GR0759
GR0761
GR0767
GR0769
GR0953
GR0955
GR0693
GR0691
GR0695
GR0697
GR0699
GR0701
GR0703
GR0705
GR0707
GR0709
GR0711
GR0715
GR0717
GR0719
GR0721
GR0723
GR0727
GR0729
GR0731
GR0733
GR0735
GR0737
GR0747
GR0739
GR0741
GR0743
GR0745
GR0949
GR0951

Normal
Normal
Normal
Three
Normal
Normal
Normal
Normal
Normal

No Fault
No Fault
No Fault
Warning
No Fault
No Fault
No Fault
No Fault
No Fault

No Action Required
No Action Required
No Action Required
Schedule repair
No Action Required
No Action Required
No Action Required
No Action Required
No Action Required

Normal No Fault

No Action Required

Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal

No Fault
No Fault
No Fault
No Fault
No Fault
No Fault
No Fault
No Fault
No Fault
No Fault
No Fault

No Action Required
No Action Required
No Action Required
No Action Required
No Action Required
No Action Required
No Action Required
No Action Required
No Action Required
No Action Required
No Action Required

Three

Warning

Schedule repair

Action

Page | VII

Normal No Fault

No Action Required

Normal No Fault

No Action Required

Normal
Four
Normal
Normal
Normal
Normal
Normal

No Action Required
Monitor development and repair as necessary
No Action Required
No Action Required
No Action Required
No Action Required
No Action Required

No Fault
Alert
No Fault
No Fault
No Fault
No Fault
No Fault

Normal No Fault

No Action Required

Normal No Fault

No Action Required

Part 3: Line 2 Rooms 22 & 23 & 24


Ser.

Area

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43

Equipment (Unit)

E11.24.08.09
E11.25.02.01
Coupling unit
E11.32.10.01
Line 2
Room 22

TB1.02.22.01
E11.32.10.02
E11.32.10.03
F11.10.13.01
F11.10.23.01
F11.10.33.01
F11.12.01.0 Filter Fan
E11.31.03.01
H11.08.33.01
H11.08.43.01
H11.08.53.01

Line 2
Room 23

TB1.02.02.01
K12.01.18.20
TB1.02.12.01
K14.04.21.01
K14.08.10.01 & K14.20.02

Line 2
Room 24

K14.20.02
K14.02.03.01

Image

GR0969
GR0971
GR0973
GR0975
GR0979
GR0977
GR0981
GR0983
GR0993
GR0991
GR0989
GR0985
GR0987
GR0995
GR0997
GR0999
GR1001
GR1005
GR1009
GR1015
GR1017
GR1019
GR1021
GR1023
GR1025
GR1027
GR1029
GR1031
GR1033
GR1035
GR1037
GR1047
GR1049
GR1039
GR1043
GR1045
GR1055
GR1057
GR1059
GR1061
GR1063
GR1065
GR1067

Code

Fault

Action

Normal No Fault

No Action Required

Normal No Fault

No Action Required

Normal No Fault

No Action Required

Normal No Fault

No Action Required

Normal
Four
Three
Normal

No Action Required
Monitor development and repair as necessary
Schedule repair
No Action Required

No Fault
Alert
Warning
No Fault

Normal No Fault

Please, check the load on cables

Normal
Normal
Normal
Three
Normal
One
Three
Normal
Three

No Action Required
No Action Required
No Action Required
Schedule repair
No Action Required
Immediate repair required
Schedule repair
No Action Required
Schedule repair

No Fault
No Fault
No Fault
Warning
No Fault
Danger
Warning
No Fault
Warning

Page | VIII

Normal No Fault

No Action Required

Normal No Fault

No Action Required

Normal No Fault
Four
Alert

No Action Required
Monitor development and repair as necessary

Normal No Fault

No Action Required

Normal No Fault

No Action Required

Three

Schedule repair

Warning

Normal No Fault

No Action Required

Normal No Fault

No Action Required

Normal No Fault
Normal No Fault

No Action Required
No Action Required

One

Danger

Immediate repair required

Three

Warning

Schedule repair

Ser.

44
45
46
47
48

Area

Equipment (Unit)

K14.08.10.02
Line 2
Room 24

K14.01.09.01
K14.08.10.3

Image

GR1071
GR1075
GR1079
GR1083
GR1085

Code

Fault

Action

Normal No Fault

No Action Required

Normal No Fault

No Action Required

One
Danger
Normal No Fault

Immediate repair required


No Action Required

Page | IX

Part 4: Line 2 Room 25


Ser.

Area

1
2
3
4
5

L11.03.04.01
L11.01.14.01
K13.01.23.02
S21.01.51.01

6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33

Equipment (Unit)

K13.01.23.03
K13.02.11.01
ER25
K13.05.10.02
K13.05.10.03
Line 2
Room 25

K13.01.23.01
K13.03.06.19
K13.03.10.19
K13.03.07.19
K13.03.14.19
K13.03.08.19
K13.03.12.19
K13.03.15.19
K13.03.09.19
K13.03.13.19

Image

GR0839
GR0841
GR0843
GR0847
GR0849
GR0851
GR0853
GR0855
GR0857
GR0861
GR0863
GR0859
GR0865
GR0867
GR0869
GR0871
GR0913
GR0915
GR0917
GR0919
GR0921
GR0923
GR0925
GR0927
GR0893
GR0897
GR0899
GR0901
GR0905
GR0907
GR0903
GR0909
GR0911

Code

Fault

Action

Normal No Fault

No Action Required

Normal
Three
Normal
Four
Three
Normal

No Action Required
Schedule repair
No Action Required
Monitor development and repair as necessary
Schedule repair
No Action Required

No Fault
Warning
No Fault
Alert
Warning
No Fault

Normal No Fault

No Action Required

Normal No Fault

No Action Required

Normal No Fault

No Action Required

Normal No Fault

No Action Required

Normal No Fault

No Action Required

Four
Three
Four
Normal

Monitor development and repair as necessary


Schedule repair
Monitor development and repair as necessary
No Action Required

Alert
Warning
Alert
No Fault

Normal No Fault

No Action Required

Normal No Fault

No Action Required

One

Immediate repair required

Danger

Normal No Fault

No Action Required

Normal No Fault

No Action Required

Normal No Fault

No Action Required

Normal No Fault

No Action Required

Ser.

34
35
36
37
38
39
40
41
42
43
44
45
46
47

Area

Equipment (Unit)

K13.03.02.19
K13.03.03.19
K13.03.04.19
Line 2
Room 25

K13.03.05.19
K13.03.01.19
TA1.02.02.01
TA1.02.02.02

Image

GR0873
GR0875
GR0877
GR0879
GR0881
GR0883
GR0885
GR0887
GR0889
GR0891
GR0939
GR0941
GR0943
GR0945

Code

Fault

Action

Normal No Fault

No Action Required

Normal No Fault
One
Danger

No Action Required
Immediate repair required

Normal No Fault

No Action Required

Normal No Fault

No Action Required

Normal No Fault

No Action Required

Normal No Fault

No Action Required

Normal No Fault

No Action Required

For any further information, please do not hesitate to contact us.

Page | X

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com

Infrared Thermal Imaging


Inspection Report - Part 1

1/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

35.4

Sp2

39.2

Sp3

40.4

Li1

Li2

Li3

Max

43.9

Min

36.4

Average

39.8

Max

40.4

Min

27.8

Average

33.9

Max

43.7

Min

29.8

Average

36.6

21/02/2016 01:45:21 PM

C
51.7
Li1

Li2

Sp3

Sp1

Li3

Parameters
Emissivity
Refl. temp.

Sp2

0.95
20 C

Note
K5-1 Water Pump

IR_0809.jpg

FLIR E50

23.0
49025354

21/02/2016 01:45:21 PM

DC_0810.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which is
an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

2/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Li3

Li4

Max

39.8

Min

33.3

Average

36.2

Max

41.3

Min

29.4

Average

36.6

Max

42.6

Min

26.9

Average

33.7

Max

40.3

Min

27.2

Average

33.7

21/02/2016 01:46:05 PM
Li1

Li3

Li4

Li2

Parameters
Emissivity
Refl. temp.

C
52.5

0.95
20 C

Note
K5-3 Water Pump

IR_0811.jpg

FLIR E50

21.3
49025354

21/02/2016 01:46:05 PM

DC_0812.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which is
an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

3/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

45.7

Sp2

42.0

Sp3

42.3

Sp4

46.6

Sp5

42.5

Sp6

42.3

21/02/2016 01:52:08 PM

C
46.8

Sp4

Sp5

Parameters
Emissivity
Refl. temp.

0.95
20 C

Sp1

Sp2

Sp6

Sp3

Note
D63-1 Filter Fan

IR_0813.jpg

FLIR E50

26.3
49025354

21/02/2016 01:52:08 PM

DC_0814.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which is
an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

4/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

43.5

Sp2

41.4

Sp3

38.6

Dt1

Sp1 - Sp3

21/02/2016 01:52:28 PM

C
43.2

4.9

Parameters
Emissivity
Refl. temp.

0.95
20 C

Sp1

Sp2

Sp3

Note
D63-1 Filter Fan

IR_0815.jpg

FLIR E50

26.0
49025354

21/02/2016 01:52:28 PM

DC_0816.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed as the temp. diff. on the left phase is more loaded
thanrightphase, otherwise temp. diff. for each phase is an acceptable.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

5/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Sp1
Li1

Li2

Li3

21/02/2016 01:52:45 PM

45.0
Max

31.8

Min

25.3

Average

28.8

Max

36.0

Min

28.7

Average

32.6

Max

32.7

Min

25.1

Average

27.5

C
45.2

Li1
Li2

Sp1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Li3

Note
D63-1 Filter Fan

IR_0817.jpg

FLIR E50

23.7
49025354

21/02/2016 01:52:45 PM

DC_0818.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

6/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

45.7

Sp2

47.2

Sp3

45.1

Li1

Li2

Max

42.9

Min

29.3

Average

37.2

Max

38.7

Min

31.2

Average

34.6

22/02/2016 11:21:58 AM

C
45.8

Sp1 Sp2
Sp3

Li1

Parameters
Emissivity
Refl. temp.

0.95
20 C
Li2

Note
K11-1 Water pump

IR_0967.jpg

FLIR E50

25.0
49025354

22/02/2016 11:21:58 AM

DC_0968.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which is
an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

7/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

28.7

Sp2

25.3

Sp3

24.8

Li1

Max

28.1

Min

23.4

Average

26.7

21/02/2016 01:55:59 PM

C
32.8

Sp1

Li1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
C9 Belt Conv.

Sp2

Sp3

IR_0819.jpg

FLIR E50

22.0
49025354

21/02/2016 01:55:59 PM

DC_0820.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which is
an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

8/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

31.1

Sp2

28.4

Sp3

25.0

Li1

Dt1

Max

26.6

Min

23.3

Average

24.7

Sp1 - Sp3

21/02/2016 01:59:35 PM

Li1

Sp1

Sp2

6.2

Parameters
Emissivity
Refl. temp.

C
31.8

Sp3

0.95
20 C

Note
C24 Belt Conv.

IR_0821.jpg
21/02/2016 01:59:35 PM

Text annotations

FLIR E50

22.3
49025354

DC_0822.jpg

Description of analysis & observation

Raised temperature are observed on spot (1), the temp. diff. is within the range 5 - 10 C as
shown in the above mentioned measurements table between the max. and the min. spots.

Action / Severity

Monitor development and repair as necessary required for the Sp (1). / low severity

Code / Fault

Four / Alert

Potential impact upon severity

Occur arcing/short circuiting/turn-to-turn faults.

Conditions Found/Deviation

Loose connections/poor contacts/bad lug/rust/unbalanced loads/deteriorated internal contact/


overloading/overheating is of concern.

Physical inspection/Electrical testing/Remedy

The source of the raised temperature shall be investigated and eliminated by cleaning/tighten the
connection/inspect cable and insulation/check the load/inspection the internal component, if
possible.

9/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

22.8

Sp2

22.4

Sp3

23.0

21/02/2016 02:00:59 PM

Parameters
Emissivity
Refl. temp.

C
28.3

Sp1

0.95
20 C

Note
C24 Belt Conv.
Sp2
Sp3

IR_0823.jpg

FLIR E50

20.0
49025354

21/02/2016 02:00:59 PM

DC_0824.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

10/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

25.3

Sp2

29.4

Sp3

28.6

Dt1

Sp2 - Sp1

21/02/2016 02:03:42 PM

C
32.4

4.1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Sp3

Sp2

Sp1

Note
D41-1 Bucket Elevator

IR_0825.jpg

FLIR E50

21.8
49025354

21/02/2016 02:03:42 PM

DC_0826.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which is
an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

11/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

28.5

Sp2

28.7

Sp3

26.7

Li1

Max

27.7

Min

23.2

Average

24.8

21/02/2016 02:03:58 PM

C
29.0
Sp1

Sp2

Sp3

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
D41-1 Bucket Elevator
Li1

IR_0827.jpg

FLIR E50

20.7
49025354

21/02/2016 02:03:58 PM

DC_0828.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

12/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

26.7

Sp2

26.2

Sp3

26.4

Sp4

27.9

Sp5

26.2

Sp6

28.5

21/02/2016 02:04:27
PM
Sp1

Sp2

Sp3

C
46.8

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
D41-1 Bucket Elevator
Sp4
Sp5
Sp6

IR_0829.jpg

FLIR E50

20.9
49025354

21/02/2016 02:04:27 PM

DC_0830.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

13/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Max

25.2

Min

21.3

Average

22.8

21/02/2016 02:04:37 PM

C
28.0

Parameters
Emissivity
Refl. temp.

0.95
20 C

Li1

Note
D41-1 Bucket Elevator

IR_0831.jpg

FLIR E50

19.6
49025354

21/02/2016 02:04:37 PM

DC_0832.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

14/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

41.5

Sp2

43.9

Sp3

41.4

Li1

Li2

Li3

Li4

Max

44.5

Min

39.4

Average

41.8

Max

38.6

Min

32.3

Average

35.5

Max

30.1

Min

26.8

Average

28.7

Max

30.8

Min

28.4

Average

29.3

C
69.2

Li1

Sp1

Sp2

0.95
20 C

Sp3

Li2
Li3

IR_0833.jpg

Parameters
Emissivity
Refl. temp.

21/02/2016 02:07:35 PM

FLIR E50

Li4

26.1
49025354

21/02/2016 02:07:35 PM

Note
D141 Dust Collector Fan

DC_0834.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

15/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

38.6

Sp2

40.2

Sp3

37.5

Li1

Max

30.4

Min

28.5

Average

29.4

22/02/2016 11:18:49 AM

C
39.9
Sp1

Sp2

Sp3

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
TS M1 Transfer switch
Li1

IR_0963.jpg

FLIR E50

23.6
49025354

22/02/2016 11:18:49 AM

DC_0964.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

16/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Max

25.4

Min

24.0

Average

24.7

22/02/2016 11:18:59 AM

C
31.2

Parameters
Emissivity
Refl. temp.

0.95
20 C

Li1

Note
TS M1 Transfer switch

IR_0965.jpg

FLIR E50

22.4
49025354

22/02/2016 11:18:59 AM

DC_0966.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

17/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Max

26.7

Min

22.5

Average

24.8

22/02/2016 11:17:10 AM

C
27.7

Li1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
TS DIE Transfer switch

IR_0959.jpg

FLIR E50

20.8
49025354

22/02/2016 11:17:10 AM

DC_0960.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

18/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Max

24.8

Min

23.0

Average

23.9

22/02/2016 11:17:18 AM

C
27.7

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
TS DIE Transfer switch

Li1

IR_0961.jpg

FLIR E50

22.4
49025354

22/02/2016 11:17:18 AM

DC_0962.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which is
an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

19/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Max

26.9

Min

24.8

Average

25.8

21/02/2016 02:20:01 PM

C
31.3

Parameters
Emissivity
Refl. temp.

0.95
20 C

Li1

Note
H725 Coal Feeding Blower "Clinker 1"

IR_0835.jpg

FLIR E50

23.0
49025354

21/02/2016 02:20:01 PM

DC_0836.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

20/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Max

29.5

Min

26.2

Average

27.7

21/02/2016 02:20:25 PM

C
33.4

Parameters
Emissivity
Refl. temp.

0.95
20 C

Li1

Note
H725 Coal Feeding Blower "Clinker 1"

IR_0837.jpg

FLIR E50

25.1
49025354

21/02/2016 02:20:25 PM

DC_0838.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

21/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

26.6

Sp2

38.2

Sp3

27.6

Sp4

29.0

Sp5

31.6

Sp6

28.0

Dt2

Sp5 - Sp6

3.6

Dt1

Sp2 - Sp1

11.6

21/02/2016 01:06:04 PM
Sp3

Sp2

Sp1

Sp6

Sp5

Sp4

C
40.9

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
E 68 New Bucket elevator

21/02/2016 01:06:04 PM
IR_0775.jpg

Text annotations

FLIR E50

18.3
49025354

DC_0776.jpg

Description of analysis & observation

Raised temperature are observed on spot (2), the temp. diff. is within the range 10 - 20 C as
shown in the above mentioned measurements table between the max. and the min. spots.

Action / Severity

Schedule repair required for the Sp (2). / Potential severity

Code / Fault

Three / Warning

Potential impact upon severity

Occur arcing/short circuiting/turn-to-turn faults.

Conditions Found/Deviation

Loose connections/poor contacts/bad lug/rust/unbalanced loads/deteriorated internal contact/


overloading/overheating is of concern.

Physical inspection/Electrical testing/Remedy

The source of the raised temperature shall be investigated and eliminated by cleaning/tighten the
connection/inspect cable and insulation/check the load/inspection the internal component/
change the component, if possible.

22/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

27.0

Sp2

27.0

Sp3

27.2

Li1

Max

28.7

Min

23.3

Average

26.1

21/02/2016 01:06:27 PM

C
31.1
Li1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Sp3

Sp2

Note

Sp1

E 68 New Bucket elevator

IR_0777.jpg

FLIR E50

18.7
49025354

21/02/2016 01:06:27 PM

DC_0778.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

23/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

38.1

Sp2

41.5

Sp3

45.5

Sp4

47.0

Sp5

42.9

Sp6

31.0

Sp7

29.0

Sp8

32.8

Sp9
Li1

21/02/2016 01:07:09 PM
Sp5

Sp4

Sp2

Sp3

Sp6

C
44.9

Sp1

29.9
Max

33.4

Min

26.6

Average

30.2

Dt3

Sp5 - Sp6

11.9

Dt1

Sp3 - Sp1

7.4

Dt2

Sp4 - Sp6

16.0

0.95
20 C

Sp8

Sp7

Li1

IR_0779.jpg

Parameters
Emissivity
Refl. temp.

Sp9

FLIR E50

19.4
49025354

21/02/2016 01:07:09 PM

Note
E 69 New Bucket elevator

Text annotations

DC_0780.jpg

Description of analysis & observation

Raised temperature are observed on spot (3) the temp. diff. is within the range 5 - 10 C and on
spot (4&5), the temp. diff. is within the range 10 - 20 C as shown in the above mentioned
measurements table between the max. and the min. spots.

Action / Severity

Monitor development and repair as necessary required for the Sp (3). / low severity. Schedule
repair required for the Sp (4&5). / Potential severity

Code / Fault

Four / Alert on spot (3). Three / Warning on the spots (4&5).

Potential impact upon severity

Occur arcing/short circuiting/turn-to-turn faults/burning component.

Conditions Found/Deviation

Loose connections/poor contacts/bad lug/rust/unbalanced loads/deteriorated internal contact/


overloading/overheating is of concern.

Physical inspection/Electrical testing/Remedy

The source of the raised temperature shall be investigated and eliminated by cleaning/tighten the
connection/check the load/change the component, if possible.

24/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

27.0

Sp2

29.0

Sp3

30.2

21/02/2016 01:07:28 PM

C
43.6
Sp3

Sp2

Sp1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
E 69 New Bucket elevator

IR_0781.jpg

FLIR E50

18.6
49025354

21/02/2016 01:07:28 PM

DC_0782.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

25/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Li3

Max

21.9

Min

18.1

Average

20.2

Max

27.4

Min

20.2

Average

23.6

Max

23.0

Min

18.7

Average

21.0

21/02/2016 01:09:39 PM

Li1

Parameters
Emissivity
Refl. temp.

C
32.1

Li2

0.95
20 C
Li3

Note
E30 Aeration blower

IR_0783.jpg

FLIR E50

16.3
49025354

21/02/2016 01:09:39 PM

DC_0784.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which is
an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

26/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Max

20.8

Min

19.7

Average

20.2

Max

23.8

Min

20.3

Average

21.9

21/02/2016 01:10:23 PM

C
34.6

Li1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
E7 Dust collector

Li2

IR_0785.jpg

FLIR E50

15.7
49025354

21/02/2016 01:10:23 PM

DC_0786.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

27/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Li3

Max

25.9

Min

20.3

Average

23.1

Max

30.6

Min

20.3

Average

25.4

Max

25.9

Min

18.3

Average

21.7

21/02/2016 01:11:38 PM

C
35.1
Li3

Li2

Li1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
E55-c Aeration blower

IR_0787.jpg

FLIR E50

10.9
49025354

21/02/2016 01:11:38 PM

DC_0788.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

28/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Sp1
Li1

Li2

21/02/2016 01:12:59 PM

C
31.6

27.9
Max

27.3

Min

25.3

Average

26.0

Max

32.3

Min

25.4

Average

27.2

Li1

Sp1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
Li2

Atlas Copco Compressor

IR_0789.jpg

FLIR E50

19.4
49025354

21/02/2016 01:12:59 PM

DC_0790.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

29/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Li3

Li4

Max

22.4

Min

19.5

Average

20.8

Max

27.2

Min

18.0

Average

22.6

Max

25.8

Min

19.7

Average

22.3

Max

27.5

Min

16.4

Average

22.7

21/02/2016 01:13:34 PM

C
34.5

Li4

Li3

Li2

Li1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
E29 Aeration blower

IR_0791.jpg

FLIR E50

13.5
49025354

21/02/2016 01:13:34 PM

DC_0792.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which is
an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

30/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

119.7

Sp2

116.9

Sp3

80.2

Sp4

65.6

Li1

Li2

Max

119.0

Min

108.9

Average

114.3

Max

65.5

Min

40.2

Average

55.4

21/02/2016 01:20:52 PM

C
119.1

Sp4

Sp3

Sp1
Sp2
Li1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Li2

Note
Compressor 2 - Spray tower Comp.

IR_0793.jpg01:20:52 PM
21/02/2016

Text annotations

FLIR E50

20.7
49025354

DC_0794.jpg

Description of analysis & observation

Dangerously high temperature are observed on spots (1&2&3). The temp. exceeding 100C while
reference temp. is 70C. The temp. diff. between the spot and the reference temp. is shown in the
above mentioned measurements table.

Action / Severity

Immediate repair required for the Sp (1&2&3). / Severity is high. This is strongly recommended as
result of this suffered temp. will lead to fault immediately.

Code / Fault

One / Danger

Potential impact upon severity

Occur arcing/short circuiting/turn-to-turn faults/burning component/fire.

Conditions Found/Deviation

Loose connections/poor contacts/rust/unbalanced loads/deteriorated internal contact/overloading/


overheating is of concern.

Physical inspection/Electrical testing/Remedy

The source of the raised temperature shall be investigated and eliminated by cleaning/tighten the
connection/inspect cable and insulation/check the load/inspection the internal component/change
the component, if possible.

31/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Li3

Max

34.5

Min

28.2

Average

31.5

Max

30.0

Min

29.3

Average

29.7

Max

35.4

Min

29.7

Average

31.8

21/02/2016 01:29:51 PM

C
35.9
Li2

Li3

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note

Li1

Filter feeder 1& 2

IR_0801.jpg

FLIR E50

19.1
49025354

21/02/2016 01:29:51 PM

DC_0802.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which is
an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

32/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Li3

Li4

Max

25.8

Min

22.5

Average

24.6

Max

27.4

Min

22.7

Average

25.1

Max

30.3

Min

22.1

Average

25.7

Max

32.6

Min

29.2

Average

31.2

21/02/2016 01:23:51 PM

C
64.1

Li4

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
D60 A1 Air lift blower

Li1

IR_0795.jpg

Li3

Li2

FLIR E50

21.1
49025354

21/02/2016 01:23:51 PM

DC_0796.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

33/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Li3

Li4

Max

26.9

Min

22.5

Average

24.4

Max

26.4

Min

21.7

Average

23.8

Max

24.9

Min

22.4

Average

24.2

Max

31.5

Min

22.5

Average

24.9

21/02/2016 01:23:57
Li4PM

C
97.7

Li3

Li2

Li1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
D60 A1 Air lift blower

IR_0797.jpg

FLIR E50

19.1
49025354

21/02/2016 01:23:57 PM

DC_0798.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

34/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Li3

Li4

Max

32.4

Min

29.0

Average

30.9

Max

27.5

Min

23.2

Average

24.9

Max

28.0

Min

23.4

Average

26.5

Max

28.4

Min

23.4

Average

26.0

21/02/2016 01:32:43 PM

C
35.4

Li1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
D60 A3 Air lift blower

Li2

IR_0803.jpg

Li3

Li4

FLIR E50

21.1
49025354

21/02/2016 01:32:43 PM

DC_0804.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

35/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Li3

Max

24.1

Min

21.8

Average

22.8

Max

27.6

Min

22.0

Average

24.5

Max

24.6

Min

21.3

Average

23.4

21/02/2016 01:32:54 PM

Li1

Parameters
Emissivity
Refl. temp.

C
54.5

Li2

Li3

0.95
20 C

Note
D60 A3 Air lift blower

IR_0805.jpg

FLIR E50

18.9
49025354

21/02/2016 01:32:54 PM

DC_0806.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

36/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

40.6

Sp2

53.2

Sp3

43.1

Sp4

34.8

Sp5

33.1

Sp6

37.5

Dt1

Sp2 - Sp1

21/02/2016 01:28:42 PM

C
52.5

Sp3

Sp2

Sp1

12.6

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
E47 Dust collector fan
Sp6

IR_0799.jpg

Sp5

FLIR E50

Sp4

24.4
49025354

Text annotations
Description of analysis & observation

Raised temperature are observed on spot (2), the temp. diff. is within the range 10 - 20 C as
shown in the above mentioned measurements table between the max. and the min. spots.

Action / Severity

Schedule repair required for the Sp (2). / Potential severity

Code / Fault

Three / Warning

Potential impact upon severity

Occur arcing/short circuiting/turn-to-turn faults.

Conditions Found/Deviation

Loose connections/poor contacts/bad lug/rust/unbalanced loads/deteriorated internal contact/


overloading/overheating is of concern.

Physical inspection/Electrical testing/Remedy

The source of the raised temperature shall be investigated and eliminated by cleaning/tighten the
connection/crimp-on lug/replace with new lug/inspect cable and insulation/check the load/
inspection the internal component/change the component, if possible.

37/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

62.1

Sp2

57.4

Sp3

50.5

Li1

Li2

Li3

Max

45.5

Min

31.9

Average

35.4

Max

53.0

Min

36.5

Average

44.0

Max

54.6

Min

38.1

Average

46.0

Dt1

Sp1 - Sp3

11.6

Dt2

Sp2 - Sp3

7.0

21/02/2016 01:34:37 PM
Sp3Sp2Sp1

Li3

Li2

Li1

Parameters
Emissivity
Refl. temp.

0.95
20 C

C
56.1

IR_0807.jpg
21/02/2016 01:34:37 PM

FLIR E50

19.5
49025354

Note
E88-4 Atlas compressor

Text annotations
Description of analysis & observation

DC_0808.jpg
Raised temperature are observed on spot (2), the temp. diff. is within the range 5 - 10 C and on
spot (1), the temp. diff. is within the range 5 - 10 C as shown in the above mentioned
measurements table between the max. and the min. spots.

Action / Severity

Monitor development and repair as necessary required for the Sp (1) / low severity. Schedule
repair required for the Sp (2) / Potential severity.

Code / Fault

Four / Alert on Sp (2). Three / Warning on Sp (1).

Potential impact upon severity

Occur arcing/short circuiting/turn-to-turn faults.

Conditions Found/Deviation

Loose connections/poor contacts/rust/unbalanced loads/deteriorated internal contact/overloading/


overheating is of concern.

Physical inspection/Electrical testing/Remedy

The source of the raised temperature shall be investigated and eliminated by cleaning/tighten the
connection/inspect cable and insulation/check the load/inspection the internal component/change
the component, if possible.

38/38

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com

Infrared Thermal Imaging


Inspection Report - Part 2

1/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Max

32.5

Min

32.0

Average

32.2

Max

33.6

Min

32.2

Average

32.9

21/02/2016 12:31:04 PM

C
34.0
Li2

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
E102 Fan
Li1

IR_0749.jpg

FLIR E50

30.0
49025354

21/02/2016 12:31:04 PM

DC_0750.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which is
an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

2/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Sp1
Li1

21/02/2016 12:32:48 PM

C
38.3

38.4
Max

38.1

Min

35.1

Average

36.8

Parameters
Emissivity
Refl. temp.

0.95
20 C

Sp1

Note
E117 Fan

Li1

IR_0751.jpg

FLIR E50

32.4
49025354

21/02/2016 12:32:48 PM

DC_0752.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

3/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Li3

Max

38.7

Min

35.4

Average

37.1

Max

38.7

Min

36.1

Average

37.7

Max

43.5

Min

37.5

Average

40.9

21/02/2016 12:34:20 PM

C
48.1

Li3

Li2

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note

Li1

Main Breaker MCC E4

IR_0753.jpg

FLIR E50

32.9
49025354

21/02/2016 12:34:20 PM

DC_0754.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

4/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

39.2

Sp2

37.7

Sp3

41.0

Sp4

37.9

Sp5

54.9

Sp6

52.5

Dt1

Sp5 - Sp1

15.7

Dt2

Sp6 - Sp2

14.7

21/02/2016 12:34:42 PM

Sp5

Sp6

C
55.1

Sp3

Sp4

Sp1

Sp2

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
Main Breaker MCC E4

IR_0755.jpg
21/02/2016 12:34:42 PM

Text annotations

FLIR E50

30.5
49025354

DC_0756.jpg

Description of analysis & observation

Raised temperature are observed on spot (5&6), the temp. diff. is within the range 10 - 20 C as
shown in the above mentioned measurements table between the max. and the min. spots.

Action / Severity

Schedule repair required for the Sp (5&6). / Potential severity

Code / Fault

Three / Warning

Potential impact upon severity

Occur arcing/short circuiting/turn-to-turn faults.

Conditions Found/Deviation

Loose connections/poor contacts/rust/unbalanced loads/deteriorated internal contact/overloading/


overheating is of concern.

Physical inspection/Electrical testing/Remedy

The source of the raised temperature shall be investigated and eliminated by cleaning/tighten the
connection/check the load/check the electric supply/inspection the internal component/change the
component, if possible.

5/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Max

32.2

Min

31.7

Average

31.9

21/02/2016 12:37:55 PM

C
33.7

Parameters
Emissivity
Refl. temp.

Li1

0.95
20 C

Note
Main Breaker - MCCE5

IR_0757.jpg

FLIR E50

29.6
49025354

21/02/2016 12:37:55 PM

DC_0758.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

6/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Li3

Max

31.3

Min

30.7

Average

30.9

Max

31.3

Min

30.7

Average

31.0

Max

31.4

Min

30.5

Average

30.9

21/02/2016 12:39:32 PM

C
32.6

Li1

Li2

Li3

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
Main Breaker - MCCFA

IR_0759.jpg

FLIR E50

28.5
49025354

21/02/2016 12:39:32 PM

DC_0760.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

7/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Max

31.9

Min

31.4

Average

31.6

21/02/2016 12:41:29 PM

C
33.4

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
F150 Calciner control

Li1

IR_0761.jpg

FLIR E50

29.3
49025354

21/02/2016 12:41:29 PM

DC_0762.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

8/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Max

32.8

Min

32.1

Average

32.5

Max

32.9

Min

31.8

Average

32.3

21/02/2016 12:44:57 PM

C
33.5

Li2

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
FAE - FAE main feeder

Li1

IR_0767.jpg

FLIR E50

29.3
49025354

21/02/2016 12:44:57 PM

DC_0768.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

9/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Sp1
Li1

Li2

21/02/2016 12:47:53 PM

C
31.8

31.1
Max

31.7

Min

30.4

Average

31.1

Max

32.3

Min

28.4

Average

30.9

Li1

Parameters
Emissivity
Refl. temp.

Sp1

0.95
20 C

Note
Main Breaker - MCCF

Li2

IR_0769.jpg

FLIR E50

21.2
49025354

21/02/2016 12:47:53 PM

DC_0770.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

10/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Max

29.6

Min

28.4

Average

29.1

Max

29.4

Min

28.4

Average

29.1

22/02/2016 11:07:34 AM

C
31.2

Li2
Li1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
Transfer switch

IR_0953.jpg

FLIR E50

27.1
49025354

22/02/2016 11:07:34 AM

DC_0954.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

11/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Max

28.4

Min

27.1

Average

27.6

22/02/2016 11:07:45 AM

C
30.3

Parameters
Emissivity
Refl. temp.

0.95
20 C

Li1

Note
Transfer switch

IR_0955.jpg

FLIR E50

26.2
49025354

22/02/2016 11:07:45 AM

DC_0956.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

12/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Max

25.9

Min

25.5

Average

25.7

Max

26.0

Min

25.5

Average

25.7

21/02/2016 11:36:52 AM

C
28.0

Li2

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
F19 Cooler fan
Li1

IR_0693.jpg

FLIR E50

23.9
49025354

21/02/2016 11:36:52 AM

DC_0694.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

13/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Sp1
Li1

Li2

21/02/2016 11:35:55 AM

C
28.5

27.4
Max

28.2

Min

26.8

Average

27.6

Max

27.5

Min

26.5

Average

26.9

Li2

Sp1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note

Li1

F18 Cooler fan

IR_0691.jpg

FLIR E50

24.5
49025354

21/02/2016 11:35:55 AM

DC_0692.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

14/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Max

25.8

Min

25.6

Average

25.8

Max

25.8

Min

25.6

Average

25.7

21/02/2016 11:38:06 AM

C
28.4
Li1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
F16-1 Cooler Drive 1

Li2

IR_0695.jpg

FLIR E50

24.3
49025354

21/02/2016 11:38:06 AM

DC_0696.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

15/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Max

27.7

Min

27.0

Average

27.3

21/02/2016 11:39:06 AM

C
29.2

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
F20 Cooler fan

Li1

IR_0697.jpg

FLIR E50

25.1
49025354

21/02/2016 11:39:06 AM

DC_0698.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

16/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Max

27.7

Min

26.2

Average

26.6

21/02/2016 11:40:26 AM

C
28.5

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
F21 Cooler fan
Li1

IR_0699.jpg

FLIR E50

24.4
49025354

21/02/2016 11:40:26 AM

DC_0700.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

17/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Max

27.5

Min

26.8

Average

27.3

Max

28.9

Min

27.6

Average

28.1

21/02/2016 11:41:19 AM

C
30.0

Li2

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
F25A Cooler fan
Li1

IR_0701.jpg

FLIR E50

25.9
49025354

21/02/2016 11:41:19 AM

DC_0702.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

18/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Max

31.5

Min

30.5

Average

31.0

Max

35.0

Min

30.7

Average

32.1

21/02/2016 11:42:41 AM

C
37.3
Li2

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
F23 Cooler fan
Li1

IR_0703.jpg

FLIR E50

27.6
49025354

21/02/2016 11:42:41 AM

DC_0704.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

19/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Li3

Max

32.9

Min

28.4

Average

30.5

Max

32.4

Min

28.5

Average

30.2

Max

38.7

Min

29.4

Average

32.9

21/02/2016 11:43:32 AM

C
40.0
Li3

Parameters
Emissivity
Refl. temp.

0.95
20 C

Li1
Li2

Note
F25C Cooler fan

IR_0705.jpg

FLIR E50

26.9
49025354

21/02/2016 11:43:32 AM

DC_0706.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

20/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Max

27.7

Min

26.9

Average

27.2

Max

27.8

Min

27.2

Average

27.5

21/02/2016 11:44:36 AM

C
29.4

Li2

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
F16-2 Cooler Drive 2
Li1

IR_0707.jpg

FLIR E50

25.4
49025354

21/02/2016 11:44:36 AM

DC_0708.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

21/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Max

27.4

Min

26.7

Average

27.0

Max

28.8

Min

27.2

Average

27.9

21/02/2016 11:44:52 AM

C
30.9

Li2

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
F16-3 Cooler Drive 3

Li1

IR_0709.jpg

FLIR E50

25.4
49025354

21/02/2016 11:44:52 AM

DC_0710.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

22/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

29.4

Sp2

33.2

Sp3

29.6

Sp4

32.0

Sp5

32.3

Sp6

29.8

21/02/2016 11:47:19 AM

C
54.1

Sp4

Sp5

Sp6

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
F26 Crusher
Sp1

IR_0711.jpg

Sp2

FLIR E50

Sp3

25.4
49025354

21/02/2016 11:47:19 AM

DC_0712.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

23/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

32.1

Sp2

47.1

Sp3

35.0

Dt1

Sp2 - Sp1

21/02/2016 11:52:16 AM

C
50.0

15.0

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
F33-1 Belt Conv.

Sp1

IR_0715.jpg

Sp2

Sp3

FLIR E50

26.5
49025354

21/02/2016 11:52:16 AM

Text annotations

DC_0716.jpg

Description of analysis & observation

Raised temperature are observed on spot (2), the temp. diff. is within the range 10 - 20 C as
shown in the above mentioned measurements table between the max. and the min. spots.

Action / Severity

Schedule repair required for the Sp (2). / Potential severity

Code / Fault

Three / Warning

Potential impact upon severity

Occur arcing/short circuiting/turn-to-turn faults.

Conditions Found/Deviation

Loose connections/poor contacts/rust/unbalanced loads/deteriorated internal contact/overloading/


overheating is of concern.

Physical inspection/Electrical testing/Remedy

The source of the raised temperature shall be investigated and eliminated by cleaning/tighten the
connection/inspect cable and insulation/check the load/inspection the internal component/change
the component, if possible.

24/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

31.8

Sp2

47.6

Sp3

34.1

Li1

Li2

Dt1

Max

34.7

Min

28.6

Average

30.9

Max

38.5

Min

29.9

Average

32.3

Sp2 - Sp1

15.8

21/02/2016 11:52:36 AM

Sp1

C
47.6
Sp2

Sp3

Li2

Parameters
Emissivity
Refl. temp.

Li1

0.95
20 C

Note
F33-1 Belt Conv.

IR_0717.jpg

FLIR E50

25.7
49025354

21/02/2016 11:52:36 AM

Text annotations
Description of analysis & observation

DC_0718.jpg
Raised temperature are observed on spot (2), the temp. diff. is within the range 10 - 20 C as
shown in the above mentioned measurements table between the max. and the min. spots.

Action / Severity

Schedule repair required for the Sp (2). / Potential severity

Code / Fault

Three / Warning

Potential impact upon severity

Occur arcing/short circuiting/turn-to-turn faults.

Conditions Found/Deviation

Loose connections/poor contacts/rust/unbalanced loads/deteriorated internal contact/overloading/


overheating is of concern.

Physical inspection/Electrical testing/Remedy

The source of the raised temperature shall be investigated and eliminated by cleaning/tighten the
connection/inspect cable and insulation/check the load/inspection the internal component/change
the component, if possible.

25/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Li3

Li4

Li5

Max

30.4

Min

28.5

Average

29.3

Max

28.6

Min

27.7

Average

28.1

Max

28.4

Min

27.0

Average

27.6

Max

27.3

Min

26.4

Average

26.8

Max

27.0

Min

26.4

Average

26.7

C
32.0

Li3

Li4
Li1

Li2

IR_0719.jpg

Parameters
Emissivity
Refl. temp.

21/02/2016 11:52:58 AM

0.95
20 C

Li5

FLIR E50

25.7
49025354

21/02/2016 11:52:58 AM

Note
F33-1 Belt Conv.

DC_0720.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

26/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Max

29.8

Min

27.1

Average

28.2

Max

29.6

Min

27.6

Average

28.3

21/02/2016 11:54:51 AM

C
29.9

Li2

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
F22 Cooler fan
Li1

IR_0721.jpg

FLIR E50

25.9
49025354

21/02/2016 11:54:51 AM

DC_0722.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

27/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Max

28.4

Min

26.9

Average

27.7

21/02/2016 11:55:19 AM

C
29.6

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
F22 Cooler fan

Li1

IR_0723.jpg

FLIR E50

25.5
49025354

21/02/2016 11:55:19 AM

DC_0724.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

28/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Max

31.6

Min

26.9

Average

29.6

21/02/2016 11:59:10 AM

C
36.3

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
F131-2 Oil Pump

Li1

IR_0727.jpg

FLIR E50

26.9
49025354

21/02/2016 11:59:10 AM

DC_0728.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

29/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

31.7

Sp2

35.0

Sp3

38.6

Sp4

32.6

Sp5

34.3

Sp6

35.0

Dt1

Sp3 - Sp1

21/02/2016 11:59:21 AM

C
40.6

Sp3

Sp2

Sp1

6.9

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note

Sp4

F131-2 Oil Pump

IR_0729.jpg

Sp5

FLIR E50

Sp6

26.7
49025354

21/02/2016 11:59:21 AM

Text annotations
Description of analysis & observation

DC_0730.jpg
Raised temperature are observed on spot (3), the temp. diff. is within the range 5 - 10 C as
shown in the above mentioned measurements table between the max. and the min. spots.

Action / Severity

Monitor development and repair as necessary required for the Sp (3). / low severity

Code / Fault

Four / Alert

Potential impact upon severity

Occur arcing/short circuiting/turn-to-turn faults.

Conditions Found/Deviation

Loose connections/poor contacts/bad lug/rust/unbalanced loads/deteriorated internal contact/


overloading/overheating is of concern.

Physical inspection/Electrical testing/Remedy

The source of the raised temperature shall be investigated and eliminated by cleaning/tighten the
connection/crimp-on lug/replace with new lug/inspect cable and insulation/check the load/
inspection the internal component/change the component, if possible.

30/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

29.9

Sp2

32.4

Sp3

29.9

21/02/2016 11:59:39 AM

C
44.3

Parameters
Emissivity
Refl. temp.

0.95
20 C

Sp1

Sp2

Sp3

Note
F131-2 Oil Pump

IR_0731.jpg

FLIR E50

25.9
49025354

21/02/2016 11:59:39 AM

DC_0732.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

31/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Sp1

21/02/2016 12:04:28 PM

C
41.9

42.6

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
F22A Cooler fan
Sp1

IR_0733.jpg

FLIR E50

26.1
49025354

21/02/2016 12:04:28 PM

DC_0734.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

32/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Max

29.2

Min

24.9

Average

26.2

Max

27.8

Min

24.8

Average

26.2

21/02/2016 12:05:25 PM

C
28.5
Li2

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
F25 Cooler fan

Li1

IR_0735.jpg

FLIR E50

24.4
49025354

21/02/2016 12:05:25 PM

DC_0736.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

33/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Sp1

21/02/2016 12:06:09 PM

C
29.9

30.1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
F25B Cooler fan
Sp1

IR_0737.jpg

FLIR E50

24.6
49025354

21/02/2016 12:06:09 PM

DC_0738.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

34/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Max

28.7

Min

26.2

Average

26.8

21/02/2016 12:16:03 PM

C
28.6

Li1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
Main C.B.

IR_0747.jpg

FLIR E50

24.6
49025354

21/02/2016 12:16:03 PM

DC_0748.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

35/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

41.4

Sp2

39.5

Sp3

39.0

Sp4

41.4

Sp5

42.3

Sp6

40.2

Sp7

38.2

Sp8

38.9

Sp9

35.7

Sp10

39.5

Sp11

41.4

Sp12
Li1

Li2

21/02/2016 12:10:08 PM

Li1

C
44.2
Sp1

Sp2

Sp3

Sp7

Sp8

Sp9

38.5
Max

32.9

Min

28.2

Average

30.6

Max

35.4

Min

31.6

Average

33.1

Li2
Sp4

IR_0739.jpg

Sp5

FLIR E50

Sp6

Sp10 Sp11

Sp12

26.7
49025354

21/02/2016 12:10:08 PM

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
Atlas Copco Compressor

DC_0740.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

36/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Li3

Max

37.2

Min

34.4

Average

36.3

Max

37.6

Min

32.0

Average

35.8

Max

35.8

Min

33.0

Average

34.9

21/02/2016 12:10:31 PM

C
41.6

Li1

Li2

Parameters
Emissivity
Refl. temp.

0.95
20 C

Li3

Note
Atlas Copco Compressor

IR_0741.jpg

FLIR E50

28.5
49025354

21/02/2016 12:10:31 PM

DC_0742.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

37/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

37.3

Sp2

38.1

Sp3

38.6

21/02/2016 12:10:48 PM

C
41.8

Parameters
Emissivity
Refl. temp.

Sp3

0.95
20 C

Sp1

Sp2

Note
Atlas Copco Compressor

IR_0743.jpg

FLIR E50

26.3
49025354

21/02/2016 12:10:48 PM

DC_0744.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

38/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Max

29.2

Min

27.4

Average

28.0

21/02/2016 12:11:06 PM

C
40.1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
Atlas Copco Compressor

Li1

IR_0745.jpg

FLIR E50

26.3
49025354

21/02/2016 12:11:06 PM

DC_0746.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

39/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

25.1

Sp2

25.2

Sp3

24.8

22/02/2016 10:58:12 AM

Parameters
Emissivity
Refl. temp.

C
30.9

Sp3 Sp2 Sp1

0.95
20 C

Note
Transfer switch

IR_0949.jpg

FLIR E50

22.0
49025354

22/02/2016 10:58:12 AM

DC_0950.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

40/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

22.8

Sp2

23.0

Sp3

22.8

22/02/2016 10:58:50 AM

C
30.3

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
Transfer switch

Sp3

IR_0951.jpg

Sp2

Sp1

FLIR E50

22.0
49025354

22/02/2016 10:58:50 AM

DC_0952.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

41/41

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com

Infrared Thermal Imaging


Inspection Report - Part 3

1/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Max

24.1

Min

21.8

Average

22.0

22/02/2016 11:33:44 AM

C
24.6
Li1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
E11.24.08.09 Separeator Electrical

IR_0969.jpg

FLIR E50

20.5
49025354

22/02/2016 11:33:44 AM

DC_0970.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

2/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Max

23.5

Min

22.2

Average

22.6

Max

23.0

Min

21.9

Average

22.5

22/02/2016 11:34:08 AM

C
24.7

Li1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Li2

Note
E11.24.08.09 Separeator Electrical

IR_0971.jpg

FLIR E50

20.7
49025354

22/02/2016 11:34:08 AM

DC_0972.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

3/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Max

30.8

Min

25.6

Average

27.8

Max

35.2

Min

24.5

Average

28.0

22/02/2016 11:36:39 AM

C
38.9

Li2

Li1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
E11.25.02.01 Air Slide Fan

IR_0973.jpg

FLIR E50

22.2
49025354

22/02/2016 11:36:39 AM

DC_0974.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

4/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Max

29.2

Min

22.7

Average

24.8

22/02/2016 11:37:07 AM

C
31.6

Li1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
E11.25.02.01 Air Slide Fan

IR_0975.jpg

FLIR E50

21.5
49025354

22/02/2016 11:37:07 AM

DC_0976.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

5/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

22.7

Sp2

22.8

Sp3

24.7

Sp4

23.8

Sp5

22.3

Sp6

22.3

C
25.3
Sp1

Sp4

Sp2

Sp5

Sp3

Parameters
Emissivity
Refl. temp.

22/02/2016 11:41:51 AM

0.95
20 C

Sp6

Note
Coupling unit

IR_0979.jpg

FLIR E50

20.5
49025354

22/02/2016 11:41:51 AM

DC_0980.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

6/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

21.1

Sp2

21.2

Sp3

23.6

22/02/2016 11:41:10 AM

C
27.6

Parameters
Emissivity
Refl. temp.

Sp1

0.95
20 C

Note
Coupling unit
Sp3

Sp2

IR_0977.jpg

FLIR E50

20.0
49025354

22/02/2016 11:41:10 AM

DC_0978.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

7/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

23.7

Sp2

23.9

Sp3

23.6

22/02/2016 11:47:45 AM
Sp1

C
49.2

Parameters
Emissivity
Refl. temp.

0.95
20 C
Sp2

Note
E11.32.10.01 HV Rectifier 1

Sp3

IR_0981.jpg

FLIR E50

21.9
49025354

22/02/2016 11:47:45 AM

DC_0982.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

8/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

23.4

Sp2

23.9

Sp3

22.0

22/02/2016 11:48:23 AM

C
31.9

Sp1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note

Sp2

E11.32.10.01 HV Rectifier 1

Sp3

IR_0983.jpg

FLIR E50

20.8
49025354

22/02/2016 11:48:23 AM

DC_0984.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

9/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

37.6

Sp2

40.7

Sp3

37.1

22/02/2016 11:57:57 AM

C
40.7

Parameters
Emissivity
Refl. temp.

0.95
20 C

Sp1
Sp2

Note
TB1.02.22.01 Compressor B

Sp3

IR_0993.jpg

FLIR E50

21.7
49025354

22/02/2016 11:57:57 AM

DC_0994.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

10/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

37.8

Sp2

48.6

Sp3

35.3

Sp4

42.6

Sp5

49.6

Sp6

43.0

Dt2

Sp5 - Sp4

7.0

Dt1

Sp2 - Sp3

13.3

22/02/2016 11:57:41 AM

Sp1

Sp4

C
51.5

Sp2
Sp5
Sp3

Sp6

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
TB1.02.22.01 Compressor B

IR_0991.jpg
22/02/2016 11:57:41 AM

Text annotations

FLIR E50

23.9
49025354

DC_0992.jpg

Description of analysis & observation

Raised temperature are observed on spot (5), the temp. diff. is within the range 5 - 10 C and on
spot (2), the temp. diff. is within the range 5 - 10 C as shown in the above
mentionedmeasurements table between the max. and the min. spots.

Action / Severity

Monitor development and repair as necessary required for the Sp (5) / low severity. Schedulerepair
required for the Sp (2) / Potential severity.

Code / Fault

Four / Alert on Sp (5). Three / Warning on Sp (2).

Potential impact upon severity

Occur arcing/short circuiting/turn-to-turn faults.

Conditions Found/Deviation

Loose connections/poor contacts/bad lug/rust/unbalanced loads/deteriorated internal contact/


overloading/overheating is of concern.

Physical inspection/Electrical testing/Remedy

The source of the raised temperature shall be investigated and eliminated by cleaning/tighten the
connection/crimp-on lug/replace with new lug/inspect cable and insulation/check the load/
inspection the internal component/change the component, if possible.

11/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

32.1

Sp2

32.2

Sp3

29.9

22/02/2016 11:55:47 AM

C
34.7
Sp1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
Sp2

E11.32.10.02 HV Rectifier 2

Sp3

IR_0989.jpg

FLIR E50

25.5
49025354

22/02/2016 11:55:47 AM

DC_0990.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

12/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Bx1

Max

69.4

Min

28.0

Average

47.8

Bx1

22/02/2016 11:52:24 AM

C
68.9

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
E11.32.10.03 HV Rectifier 3

IR_0985.jpg

FLIR E50

28.6
49025354

22/02/2016 11:52:24 AM

DC_0986.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

13/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

39.7

Sp2

38.5

Sp3

42.9

22/02/2016 11:54:40 AM

C
68.7

Sp1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note

Sp2

E11.32.10.03 HV Rectifier 3

Sp3

IR_0987.jpg

FLIR E50

32.3
49025354

22/02/2016 11:54:40 AM

DC_0988.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

14/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Li3

Li4

Max

48.4

Min

24.5

Average

30.9

Max

48.8

Min

23.8

Average

33.9

Max

48.5

Min

25.4

Average

35.0

Max

39.5

Min

27.6

Average

32.6

22/02/2016 12:00:08 PM
Li1

Li2

Li3

Li4

C
55.6

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
F11.10.13.01 Blower F

IR_0995.jpg

FLIR E50

21.2
49025354

22/02/2016 12:00:08 PM

DC_0996.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

15/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

30.3

Sp2

29.3

22/02/2016 12:02:06 PM

C
31.5

Parameters
Emissivity
Refl. temp.

0.95
20 C

Sp1

Note
F11.10.13.01 Blower F

Sp2

IR_0997.jpg

FLIR E50

22.4
49025354

22/02/2016 12:02:06 PM

DC_0998.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

16/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Li3

Li4

Max

43.2

Min

25.5

Average

29.9

Max

45.1

Min

23.9

Average

31.6

Max

46.7

Min

25.2

Average

35.4

Max

45.8

Min

27.9

Average

33.4

22/02/2016Li112:03:16 PM

Li2

Li3

Li4

C
52.1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
F11.10.23.01 Blower F

IR_0999.jpg

FLIR E50

22.0
49025354

22/02/2016 12:03:16 PM

DC_1000.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

17/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

37.1

Sp2

51.7

Sp3

39.2

Dt1

Sp2 - Sp1

22/02/2016 12:04:38 PM
Sp1

14.7

Parameters
Emissivity
Refl. temp.

C
52.1

Sp2

0.95
20 C

Note
F11.10.23.01 Blower F
Sp3

IR_1001.jpg

FLIR E50

27.6
49025354

22/02/2016 12:04:38 PM

Text annotations

DC_1002.jpg

Description of analysis & observation

Raised temperature are observed on spot (2), the temp. diff. is within the range 10 - 20 C as
shown in the above mentioned measurements table between the max. and the min. spots.

Action / Severity

Schedule repair required for the Sp (2). / Potential severity

Code / Fault

Three / Warning

Potential impact upon severity

Occur arcing/short circuiting/turn-to-turn faults.

Conditions Found/Deviation

Loose connections/poor contacts/rust/unbalanced loads/deteriorated internal contact/overloading/


overheating is of concern.

Physical inspection/Electrical testing/Remedy

The source of the raised temperature shall be investigated and eliminated by cleaning/tighten the
connection/check the load, if possible.

18/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Li3

Li4

Max

37.5

Min

25.8

Average

29.8

Max

47.6

Min

25.6

Average

32.8

Max

41.7

Min

26.5

Average

33.8

Max

36.6

Min

26.9

Average

31.2

22/02/2016 12:06:22 PM

C
54.7

Li2
Li1

Li3

Li4

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
F11.10.33.01 Blower F

IR_1005.jpg

FLIR E50

22.6
49025354

22/02/2016 12:06:22 PM

DC_1006.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

19/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Sp1

22/02/2016 12:09:37 PM

C
98.4

99.9

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
F11.12.01.0 Filter Fan
Sp1

IR_1009.jpg
22/02/2016 12:09:37 PM

Text annotations
Description of analysis & observation

FLIR E50

31.2
49025354

DC_1010.jpg
Elevated temperature are observed on spot (1). The temp. exceeding reference temperature 70
C. The temp. diff. between the spot and the reference temperature is shown in the above
mentioned measurements table.

Action / Severity

Immediate repair required for the Sp (1). / Severity is high. This is strongly recommended as a
result of this suffered temp. will lead to fault immediately.

Code / Fault

One / Danger

Potential impact upon severity

Occur arcing/short circuiting/turn-to-turn faults/burning component/fire.

Conditions Found/Deviation

Loose connections/poor contacts/bad lug/rust/unbalanced loads/deteriorated internal contact/


overloading/overheating is of concern.

Physical inspection/Electrical testing/Remedy

The source of the raised temperature shall be investigated and eliminated by cleaning/tighten the
connection/inspect cable and insulation/check the load/check the electric supply/inspection the
internal component/change the component, if possible.

20/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

26.5

Sp2

26.6

Sp3

25.1

Sp4

32.1

Sp5

36.3

Sp6

46.3

Sp7

41.1

Sp8

43.9

Sp9

39.6

Dt1

Sp6 - Sp4

22/02/2016 12:23:00 PM
Sp4
Sp5

Sp6

Sp1

Sp2

Sp3

Sp7
Sp8

14.2

Sp9

Parameters
Emissivity
Refl. temp.

C
48.5

0.95
20 C

Note
E11.31.03.01 Tower water pump

IR_1015.jpg
22/02/2016 12:23:00 PM

Text annotations

FLIR E50

20.3
49025354

DC_1016.jpg

Description of analysis & observation

Raised temperature are observed on spot (6), the temp. diff. is within the range 10 - 20 C as
shown in the above mentioned measurements table between the max. and the min. spots.

Action / Severity

Schedule repair required for the Sp (6). / Potential severity

Code / Fault

Three / Warning

Potential impact upon severity

Occur arcing/short circuiting/turn-to-turn faults.

Conditions Found/Deviation

Loose connections/poor contacts/bad lug/rust/unbalanced loads/deteriorated internal contact/


overloading/overheating is of concern.

Physical inspection/Electrical testing/Remedy

The source of the raised temperature shall be investigated and eliminated by cleaning/tighten the
connection/crimp-on lug/replace with new lug/inspect cable and insulation/check the load/
inspection the internal component/change the component, if possible.

21/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

29.9

Sp2

31.2

Sp3

31.0

22/02/2016 12:23:21 PM

C
31.8

Parameters
Emissivity
Refl. temp.

0.95
20 C

Sp1

Note
E11.31.03.01 Tower water pump
Sp2

Sp3

IR_1017.jpg

FLIR E50

21.4
49025354

22/02/2016 12:23:21 PM

DC_1018.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

22/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

39.6

Sp2

47.3

Sp3

36.8

Dt1

Sp2 - Sp3

22/02/2016 12:24:59 PM

C
48.1

Sp1

10.5

Parameters
Emissivity
Refl. temp.

0.95
20 C

Sp2

Note
E11.31.03.01 Tower water pump

Sp3

IR_1019.jpg

FLIR E50

24.4
49025354

22/02/2016 12:24:59 PM

Text annotations

DC_1020.jpg

Description of analysis & observation

Raised temperature are observed on spot (2), the temp. diff. is within the range 10 - 20 C as
shown in the above mentioned measurements table between the max. and the min. spots.

Action / Severity

Schedule repair required for the Sp (2). / Potential severity

Code / Fault

Three / Warning

Potential impact upon severity

Occur arcing/short circuiting/turn-to-turn faults.

Conditions Found/Deviation

Loose connections/poor contacts/bad lug/rust/unbalanced loads/deteriorated internal contact/


overloading/overheating is of concern.

Physical inspection/Electrical testing/Remedy

The source of the raised temperature shall be investigated and eliminated by cleaning/tighten the
connection/inspect cable and insulation/check the load/check the electric supply/inspection the
internal component/change the component, if possible.

23/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp2

51.3

Sp1

49.6

Sp3

47.8

22/02/2016 12:26:53 PM

C
51.1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
H11.08.33.01 Blower F
Sp3

Sp2
Sp1

IR_1021.jpg

FLIR E50

22.2
49025354

22/02/2016 12:26:53 PM

DC_1022.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

24/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

34.1

Sp2

34.1

22/02/2016 12:27:28 PM

C
34.6

Parameters
Emissivity
Refl. temp.

0.95
20 C

Sp1

Note
H11.08.33.01 Blower F

Sp2

IR_1023.jpg

FLIR E50

23.8
49025354

22/02/2016 12:27:28 PM

DC_1024.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

25/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Li3

Max

47.4

Min

29.9

Average

35.8

Max

44.7

Min

28.4

Average

35.0

Max

41.4

Min

25.7

Average

33.0

22/02/2016 12:28:45 PM
Li1

Li2

Li3

C
55.1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
H11.08.43.01 Blower F

IR_1025.jpg

FLIR E50

22.8
49025354

22/02/2016 12:28:45 PM

DC_1026.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

26/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

49.7

Sp2

51.1

Sp3

47.8

22/02/2016 12:29:30 PM

C
51.2

Sp1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Sp2

Note
H11.08.43.01 Blower F

Sp3

IR_1027.jpg

FLIR E50

22.9
49025354

22/02/2016 12:29:30 PM

DC_1028.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

27/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Li3

Max

47.4

Min

27.1

Average

35.1

Max

53.4

Min

27.0

Average

36.9

Max

49.1

Min

26.5

Average

35.0

22/02/2016 12:30:35 PM
Li1

Li2

Li3

C
54.2

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
H11.08.53.01 Blower F

IR_1029.jpg

FLIR E50

20.6
49025354

22/02/2016 12:30:35 PM

DC_1030.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

28/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

53.2

Sp2

55.3

Sp3

49.3

Dt1

Sp2 - Sp3

22/02/2016 12:31:10 PM

Sp1

5.9

Parameters
Emissivity
Refl. temp.

C
55.4

Sp2

0.95
20 C

Note

Sp3

H11.08.53.01 Blower F

IR_1031.jpg

FLIR E50

23.1
49025354

22/02/2016 12:31:10 PM

Text annotations

DC_1032.jpg

Description of analysis & observation

Raised temperature are observed on spot (2), the temp. diff. is within the range 5 - 10 C as
shown in the above mentioned measurements table between the max. and the min. spots.

Action / Severity

Monitor development and repair as necessary required for the Sp (2). / low severity

Code / Fault

Four / Alert

Potential impact upon severity

Occur arcing/short circuiting/turn-to-turn faults.

Conditions Found/Deviation

Loose connections/poor contacts/bad lug/rust/unbalanced loads/deteriorated internal contact/


overloading/overheating is of concern.

Physical inspection/Electrical testing/Remedy

The source of the raised temperature shall be investigated and eliminated by cleaning/tighten the
connection/inspect cable and insulation/check the load/inspection the internal component/
change the component, if possible.

29/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

44.6

Sp2

43.8

Sp3

42.2

Li1

Li2

Max

40.6

Min

25.6

Average

33.1

Max

41.9

Min

27.5

Average

34.3

22/02/2016 12:32:27 PM
Sp1

Li1

Li2

C
46.1

Sp2
Sp3

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
TB1.02.02.01 Compressor B

IR_1033.jpg

FLIR E50

20.5
49025354

22/02/2016 12:32:27 PM

DC_1034.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

30/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

32.2

Sp2

31.2

Sp3

31.9

22/02/2016 12:32:53 PM

Parameters
Emissivity
Refl. temp.

C
32.4

Sp1

0.95
20 C

Note
TB1.02.02.01 Compressor B

Sp2
Sp3

IR_1035.jpg

FLIR E50

24.0
49025354

22/02/2016 12:32:53 PM

DC_1036.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

31/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

44.1

Sp2

46.5

22/02/2016 12:33:36 PM

C
46.8

Parameters
Emissivity
Refl. temp.

0.95
20 C

Sp2

Note
TB1.02.02.01 Compressor B
Sp1

IR_1037.jpg

FLIR E50

24.7
49025354

22/02/2016 12:33:36 PM

DC_1038.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

32/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Max

32.2

Min

29.1

Average

30.9

Max

32.4

Min

31.7

Average

32.1

22/02/2016 12:38:41 PM

C
32.8

Li1

Li2

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
K12.01.18.20 VVVF Feeder

IR_1047.jpg

FLIR E50

23.4
49025354

22/02/2016 12:38:41 PM

DC_1048.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

33/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Max

27.9

Min

26.3

Average

27.1

22/02/2016 12:39:15 PM

C
28.1

Li1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
K12.01.18.20 VVVF Feeder

IR_1049.jpg

FLIR E50

24.0
49025354

22/02/2016 12:39:15 PM

DC_1050.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

34/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

56.6

Sp2

42.0

Sp3

42.6

Sp4
Dt1

22/02/2016 12:35:39 PM

C
63.8

66.1
Sp1 - Sp2

Sp1

14.6

Sp4

Parameters
Emissivity
Refl. temp.

0.95
20 C

Sp2

Note
TB1.02.12.01 Compressor B

Sp3

IR_1039.jpg
22/02/2016 12:35:39 PM

Text annotations

FLIR E50

22.8
49025354

DC_1040.jpg

Description of analysis & observation

Raised temperature are observed on spot (1), the temp. diff. is within the range 10 - 20 C as
shown in the above mentioned measurements table between the max. and the min. spots.

Action / Severity

Schedule repair required for the Sp (1). / Potential severity

Code / Fault

Three / Warning

Potential impact upon severity

Occur arcing/short circuiting/turn-to-turn faults/burning component/fire.

Conditions Found/Deviation

Loose connections/poor contacts/bad lug/rust/unbalanced loads/deteriorated internal contact/


overloading/overheating is of concern.

Physical inspection/Electrical testing/Remedy

The source of the raised temperature shall be investigated and eliminated by cleaning/tighten the
connection/crimp-on lug/replace with new lug/inspect wire and cable and insulation/check the load
if possible.

35/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

45.0

Sp2

42.5

22/02/2016 12:36:52 PM

C
46.4

Parameters
Emissivity
Refl. temp.

0.95
20 C

Sp1

Note

Sp2

TB1.02.12.01 Compressor B

IR_1043.jpg

FLIR E50

22.2
49025354

22/02/2016 12:36:52 PM

DC_1044.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

36/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp2

45.2

Sp3

43.3

Sp1

41.3
Sp1

Parameters
Emissivity
Refl. temp.

22/02/2016 12:37:25 PM

C
50.4

Sp2

0.95
20 C

Sp3

Note
TB1.02.12.01 Compressor B

IR_1045.jpg

FLIR E50

25.7
49025354

22/02/2016 12:37:25 PM

DC_1046.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

37/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

34.7

Sp2

35.4

Sp3

32.0

Li1

Max

31.5

Min

22.6

Average

28.6

22/02/2016 12:41:02 PM

C
35.3

Li1

Sp1
Sp2

Sp3

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
K14.04.21.01 Primary air fan

IR_1055.jpg

FLIR E50

20.4
49025354

22/02/2016 12:41:02 PM

DC_1056.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which is
an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

38/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

27.2

Sp2

25.5

22/02/2016 12:41:19 PM

C
27.7

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
K14.04.21.01 Primary air fan
Sp1

Sp2

IR_1057.jpg

FLIR E50

21.3
49025354

22/02/2016 12:41:19 PM

DC_1058.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

39/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Max

37.4

Min

31.5

Average

34.6

Max

30.7

Min

28.3

Average

29.3

22/02/2016 12:46:41 PM
Li1

C
44.1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
K14.08.10.01 HV rectifier 1
K14.20.02 Granulator

Li2

IR_1059.jpg

FLIR E50

21.0
49025354

22/02/2016 12:46:41 PM

DC_1060.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

40/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Max

27.4

Min

24.7

Average

25.9

22/02/2016 12:47:20 PM

C
28.7

Li1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
K14.20.02 Granulator

IR_1061.jpg

FLIR E50

24.6
49025354

22/02/2016 12:47:20 PM

DC_1062.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

41/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Bx1

Max

123.8

Min

23.4

Average

83.3

Sp1

37.7

Sp2

70.5

Sp3

34.5

Li1

Li2

Max

42.8

Min

26.8

Average

33.7

Max

45.6

Min

25.2

Average

38.3

Dt2 Bx1.Max - Ref. temp.

53.8

Dt1

0.5

Sp2 - Ref. temp.

22/02/2016 12:49:24 PM

C
118.4

Sp1

Li1

Bx1
Sp2

Sp3

Li2

Parameters
Emissivity
Refl. temp.

0.95
20 C

IR_1063.jpg
22/02/2016 12:49:24 PM

FLIR E50

23.2
49025354

Note
K14.02.03.01 Tower water pump

Text annotations

DC_1064.jpg

Description of analysis & observation

Elevated temperature are observed on spot (2). The temp. exceeding reference temperature 70
C. The temp. diff. between the spot and the reference temperature is shown in the above
mentioned measurements table.

Action / Severity

Immediate repair required for the Sp (2). / Severity is high. This is strongly recommended as a
result of this suffered temp. will lead to fault immediately.

Code / Fault

One / Danger

Potential impact upon severity

Occur arcing/short circuiting/turn-to-turn faults/burning component/fire.

Conditions Found/Deviation

Loose connections/poor contacts/bad lug/rust/unbalanced loads/deteriorated internal contact/


overloading/overheating is of concern.

Physical inspection/Electrical testing/Remedy

The source of the raised temperature shall be investigated and eliminated by cleaning/tighten the
connection/crimp-on lug/replace with new lug/inspect cable and insulation/check the load/
inspection the internal component/change the component, if possible.

42/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Bx1

Max

127.2

Min

29.1

Average

69.9

22/02/2016 12:49:40 PM

Parameters
Emissivity
Refl. temp.

C
125.7

Bx1

0.95
20 C

Note
K14.02.03.01 Tower water pump

IR_1065.jpg
22/02/2016 12:49:40 PM

Text annotations

FLIR E50

25.8
49025354

DC_1066.jpg

Description of analysis & observation

Dangerously high temperature are observed on Bx(1). The temp. exceeding 100C while
reference temp. is 70C. The temp. diff. between the spot and the reference temp. is shown in the
above mentioned measurements table.

Action / Severity

Immediate repair required for the Bx(1). / Severity is high. This is strongly recommended as a
result of this suffered temp. will lead to fault immediately.

Code / Fault

One / Danger

Potential impact upon severity

Occur arcing/short circuiting/turn-to-turn faults/burning component/fire.

Conditions Found/Deviation

Loose connections/poor contacts/bad lug/rust/unbalanced loads/deteriorated internal contact/


overloading/overheating is of concern.

Physical inspection/Electrical testing/Remedy

The source of the raised temperature shall be investigated and eliminated by cleaning/tighten the
connection/crimp-on lug/replace with new lug/inspect cable and insulation/check the load/
inspection the internal component/change the component, if possible.

43/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

31.7

Sp2

47.4

Sp3

32.2

Dt1

Sp2 - Sp1

22/02/2016 12:50:04 PM

15.7

C
49.5

Sp1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Sp2

Note
K14.02.03.01 Tower water pump

Sp3

IR_1067.jpg
22/02/2016 12:50:04 PM

Text annotations

FLIR E50

23.7
49025354

DC_1068.jpg

Description of analysis & observation

Raised temperature are observed on spot (2), the temp. diff. is within the range 10 - 20 C as
shown in the above mentioned measurements table between the max. and the min. spots.

Action / Severity

Schedule repair required for the Sp (2). / Potential severity

Code / Fault

Three / Warning

Potential impact upon severity

Occur arcing/short circuiting/turn-to-turn faults.

Conditions Found/Deviation

Loose connections/poor contacts/bad lug/rust/unbalanced loads/deteriorated internal contact/


overloading/overheating is of concern.

Physical inspection/Electrical testing/Remedy

The source of the raised temperature shall be investigated and eliminated by cleaning/tighten the
connection/crimp-on lug/replace with new lug/inspect cable and insulation/check the load/
inspection the internal component/change the component, if possible.

44/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Max

56.9

Min

31.1

Average

35.2

22/02/2016 12:54:45 PM

C
54.0
Li1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
K14.08.10.02 HV rectifier 2

IR_1071.jpg

FLIR E50

22.1
49025354

22/02/2016 12:54:45 PM

DC_1072.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

45/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Max

35.4

Min

23.6

Average

30.1

Max

32.9

Min

25.5

Average

28.3

22/02/2016 12:55:52 PM

C
42.3
Li2

Li1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
K14.01.09.01 Fresh air fan

IR_1075.jpg

FLIR E50

20.9
49025354

22/02/2016 12:55:52 PM

DC_1076.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

46/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

28.7

Sp2

26.2

Sp3

26.6

22/02/2016 12:56:32 PM

C
29.3

Parameters
Emissivity
Refl. temp.

0.95
20 C
Sp3

Note
K14.01.09.01 Fresh air fan

Sp1

Sp2

IR_1079.jpg

FLIR E50

21.1
49025354

22/02/2016 12:56:32 PM

DC_1080.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

47/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Sp1
Dt1

22/02/2016 12:59:23 PM

C
79.2

84.0
Sp1 - Ref. temp.

14.0

Parameters
Emissivity
Refl. temp.

0.95
20 C
Sp1

Note
K14.08.10.3 HV rectifier 3

IR_1083.jpg
22/02/2016 12:59:23 PM

Text annotations
Description of analysis & observation

FLIR E50

24.1
49025354

DC_1084.jpg
Elevated temperature are observed on spot (1). The temp. exceeding reference temperature 70
C. The temp. diff. between the spot and the reference temperature is shown in the above
mentioned measurements table.

Action / Severity

Immediate repair required for the Sp (1). / Severity is high. This is strongly recommended as a
result of this suffered temp. will lead to fault immediately.

Code / Fault

One / Danger

Potential impact upon severity

Occur arcing/short circuiting/turn-to-turn faults/burning component/fire.

Conditions Found/Deviation

Loose connections/poor contacts/bad lug/rust/unbalanced loads/deteriorated internal contact/


overloading/overheating is of concern.

Physical inspection/Electrical testing/Remedy

The source of the raised temperature shall be investigated and eliminated by cleaning/tighten the
connection/crimp-on lug/replace with new lug/inspect cable and insulation/check the load/
inspection the internal component/change the component, if possible.

48/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Sp1

22/02/2016 12:59:32 PM

C
43.6

39.8

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
K14.08.10.3 HV rectifier 3
Sp1

IR_1085.jpg

FLIR E50

24.4
49025354

22/02/2016 12:59:32 PM

DC_1086.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

49/49

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com

Infrared Thermal Imaging


Inspection Report-Part 4

1/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Max

36.6

Min

28.3

Average

31.2

Max

38.2

Min

27.6

Average

32.4

21/02/2016 03:10:46 PM

Li1

C
47.4

Li2

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
L11.03.04.01 Conveyor

IR_0839.jpg

FLIR E50

25.3
49025354

21/02/2016 03:10:46 PM

DC_0840.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

2/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Sp1

21/02/2016 03:11:08 PM

C
31.3

28.9

Parameters
Emissivity
Refl. temp.

0.95
20 C

Sp1

Note
L11.03.04.01 Conveyor

IR_0841.jpg

FLIR E50

23.0
49025354

21/02/2016 03:11:08 PM

DC_0842.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

3/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Max

34.9

Min

28.8

Average

31.9

Max

38.7

Min

28.3

Average

34.1

21/02/2016 03:13:24 PM
Li1

Li2

C
49.5

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
L11.01.14.01 Conveyor

IR_0843.jpg

FLIR E50

25.6
49025354

21/02/2016 03:13:24 PM

DC_0844.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

4/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp4

34.5

Sp5

47.9

Sp6

32.0

Li1

Li2

Dt1

Max

37.6

Min

27.8

Average

30.8

Max

40.0

Min

26.5

Average

32.3

Sp5 - Sp6

15.8

21/02/2016 03:16:14 PM
Li1

Li2

Sp4
Sp5

Parameters
Emissivity
Refl. temp.

C
46.2

Sp6

0.95
20 C

Note
K13.01.23.02 Grate 02

IR_0847.jpg
21/02/2016 03:16:14 PM

Text annotations

FLIR E50

25.3
49025354

DC_0848.jpg

Description of analysis & observation

Raised temperature are observed on spot (5), the temp. diff. is within the range 10 - 20 C as
shown in the above mentioned measurements table between the max. and the min. spots.

Action / Severity

Schedule repair required for the Sp (5). / Potential severity

Code / Fault

Three / Warning

Potential impact upon severity

Occur arcing/short circuiting/turn-to-turn faults.

Conditions Found/Deviation

Loose connections/poor contacts/bad lug/rust/unbalanced loads/deteriorated internal contact/


overloading/overheating is of concern.

Physical inspection/Electrical testing/Remedy

The source of the raised temperature shall be investigated and eliminated by cleaning/tighten the
connection/inspect cable and insulation/check the load/inspection the internal component/change
the component, if possible.

5/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Max

37.9

Min

27.5

Average

31.0

Max

30.8

Min

26.9

Average

29.1

21/02/2016 03:18:35 PM
Li2

C
42.7
Li1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
S21.01.51.01 Heavy oil HP Pump

IR_0849.jpg

FLIR E50

24.8
49025354

21/02/2016 03:18:35 PM

DC_0850.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

6/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

51.6

Sp2

39.1

Sp3

47.4

Sp4

39.1

Sp5

36.6

Sp6

37.8

Dt2

Sp3 - Sp2

8.3

Dt1

Sp1 - Sp2

12.4

21/02/2016 03:21:08 PM

C
52.0

Sp4

Sp1

Sp2

Sp5

Sp3

Sp6

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
K13.01.23.03 Grate 03

IR_0851.jpg

FLIR E50

25.3
49025354

21/02/2016 03:21:08 PM

Text annotations

DC_0852.jpg

Description of analysis & observation

Raised temperature are observed on spot (3), the temp. diff. is within the range 5 - 10 C and on
spot (1), the temp. diff. is within the range 10 - 20 C as shown in the above mentioned
measurements table between the max. and the min. spots.

Action / Severity

Monitor development and repair as necessary required for the Sp (3)/ low severity. Schedule repair
required for the Sp (1) / Potential severity.

Code / Fault

Four / Alert on Sp (3). Three / Warning on Sp (1).

Potential impact upon severity

Occur arcing/short circuiting/turn-to-turn faults.

Conditions Found/Deviation

Loose connections/poor contacts/bad lug/rust/unbalanced loads/deteriorated internal contact/


overloading/overheating is of concern.

Physical inspection/Electrical testing/Remedy

The source of the raised temperature shall be investigated and eliminated by cleaning/tighten the
connection/crimp-on lug/replace with new lug/inspect cable and insulation/check the load/
inspection the internal component/change the component, if possible.
Infrared Thermal Imaging Inspection Report
Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

7/48

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

32.1

Sp2

29.4

Sp3

28.4

21/02/2016 03:21:44 PM

C
33.1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note

Sp1

K13.01.23.03 Grate 03

Sp2

Sp3

IR_0853.jpg

FLIR E50

24.8
49025354

21/02/2016 03:21:44 PM

DC_0854.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

8/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Li3

Max

36.5

Min

27.3

Average

30.4

Max

36.1

Min

26.1

Average

30.4

Max

36.3

Min

28.2

Average

31.4

21/02/2016 03:25:45 PM

C
46.2
Li2

Li1

Li3

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
K13.02.11.01 Crusher

IR_0855.jpg

FLIR E50

25.3
49025354

21/02/2016 03:25:45 PM

DC_0856.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

9/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Max

27.8

Min

27.1

Average

27.4

21/02/2016 03:26:19 PM

C
30.3

Parameters
Emissivity
Refl. temp.

0.95
20 C

Li1

Note
K13.02.11.01 Crusher

IR_0857.jpg

FLIR E50

22.1
49025354

21/02/2016 03:26:19 PM

DC_0858.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

10/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

34.1

Sp2

33.7

Sp3

32.7

Sp4

37.1

Sp5

37.3

Sp6

36.1

21/02/2016 03:35:08 PM

Sp4
Sp1
Sp5
Sp2
Sp6

Parameters
Emissivity
Refl. temp.

C
37.3

0.95
20 C

Sp3

Note
ER25 Air condition

IR_0861.jpg

FLIR E50

25.3
49025354

21/02/2016 03:35:08 PM

DC_0862.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

11/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Max

29.7

Min

25.8

Average

28.0

21/02/2016 03:35:26 PM

C
31.5
Li1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
ER25 Air condition

IR_0863.jpg

FLIR E50

23.2
49025354

21/02/2016 03:35:26 PM

DC_0864.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

12/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Max

28.0

Min

27.3

Average

27.6

21/02/2016 03:28:38 PM

C
34.3
Li1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
K13.05.10.02 HV Rectifier 2

IR_0859.jpg

FLIR E50

25.1
49025354

21/02/2016 03:28:38 PM

DC_0860.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

13/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Max

28.2

Min

27.5

Average

27.8

21/02/2016 03:37:54 PM

C
31.5
Li1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
K13.05.10.03 HV Rectifier3

IR_0865.jpg

FLIR E50

23.2
49025354

21/02/2016 03:37:54 PM

DC_0866.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

14/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Bx1

Max

27.5

Min

25.5

Average

26.6

21/02/2016 03:38:46 PM

Bx1

Parameters
Emissivity
Refl. temp.

C
30.3

0.95
20 C

Note
K13.05.10.03 HV Rectifier3

IR_0867.jpg

FLIR E50

22.1
49025354

21/02/2016 03:38:46 PM

DC_0868.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

15/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

31.4

Sp2

30.8

Sp3

29.5

Li1

Max

36.5

Min

26.9

Average

30.4

21/02/2016 03:40:23 PM

C
49.3
Sp1

Li1

Sp2

Sp3

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
K13.01.23.01 Grate 01

IR_0869.jpg

FLIR E50

25.1
49025354

21/02/2016 03:40:23 PM

DC_0870.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

16/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

33.7

Sp2

33.0

21/02/2016 03:41:18 PM

C
40.7

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
K13.01.23.01 Grate 01

Sp1

Sp2

IR_0871.jpg

FLIR E50

26.3
49025354

21/02/2016 03:41:18 PM

DC_0872.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

17/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

42.8

Sp2

49.7

Sp3

43.1

Dt1

Sp2 - Sp1

21/02/2016 04:05:01 PM

C
48.4

6.9

Parameters
Emissivity
Refl. temp.

Sp1

0.95
20 C

Note

Sp2

K13.03.06.19 VVVF FAN 3A


Sp3

IR_0913.jpg

FLIR E50

26.3
49025354

21/02/2016 04:05:01 PM

Text annotations

DC_0914.jpg

Description of analysis & observation

Raised temperature are observed on spot (2), the temp. diff. is within the range 5 - 10 C as
shown in the above mentioned measurements table between the max. and the min. spots.

Action / Severity

Monitor development and repair as necessary required for the Sp (2). / low severity

Code / Fault

Four / Alert

Potential impact upon severity

Occur arcing/short circuiting/turn-to-turn faults.

Conditions Found/Deviation

Loose connections/poor contacts/rust/unbalanced loads/deteriorated internal contact/


overloading/overheating is of concern.

Physical inspection/Electrical testing/Remedy

The source of the raised temperature shall be investigated and eliminated by cleaning/tighten the
connection/inspect cable and insulation/check the load/check the electric supply/inspection the
internal component, if possible.

18/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

36.9

Sp2

50.7

Sp3

36.3

Dt1

Sp2 - Sp3

21/02/2016 04:05:16 PM

C
55.9

Sp1

14.4

Parameters
Emissivity
Refl. temp.

0.95
20 C

Sp2

Note
K13.03.06.19 VVVF FAN 3A

Sp3

IR_0915.jpg
21/02/2016 04:05:16 PM

Text annotations

FLIR E50

26.7
49025354

DC_0916.jpg

Description of analysis & observation

Raised temperature are observed on spot (2), the temp. diff. is within the range 10 - 20 C as
shown in the above mentioned measurements table between the max. and the min. spots.

Action / Severity

Schedule repair required for the Sp (2). / Potential severity

Code / Fault

Three / Warning

Potential impact upon severity

Occur arcing/short circuiting/turn-to-turn faults/burning component/fire.

Conditions Found/Deviation

Loose connections/poor contacts/bad lug/rust/unbalanced loads/deteriorated internal contact/


overloading/overheating is of concern.

Physical inspection/Electrical testing/Remedy

The source of the raised temperature shall be investigated and eliminated by cleaning/tighten the
connection/crimp-on lug/replace with new lug/inspect cable and insulation/check the load/check
the electric supply/inspection the internal component, if possible.

19/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp2

45.6

Sp3

52.8

Sp1

43.3

Li1

Dt1

Max

21/02/2016 04:06:03 PM

Li1

48.6

Min

32.6

Average

42.3

Sp1 - Sp2

-2.3

Sp1
Sp2

Parameters
Emissivity
Refl. temp.

C
52.4

Sp3

0.95
20 C

Note
K13.03.10.19 VVVF FAN 4A

IR_0917.jpg04:06:03 PM
21/02/2016

Text annotations

FLIR E50

25.3
49025354

DC_0918.jpg

Description of analysis & observation

Raised temperature are observed on spot (3), the temp. diff. is within the range 5 - 10 C as
shown in the above mentioned measurements table between the max. and the min. spots.

Action / Severity

Monitor development and repair as necessary required for the Sp (3). / low severity

Code / Fault

Four / Alert

Potential impact upon severity

Occur arcing/short circuiting/turn-to-turn faults.

Conditions Found/Deviation

Loose connections/poor contacts/rust/unbalanced loads/deteriorated internal contact/overloading/


overheating is of concern.

Physical inspection/Electrical testing/Remedy

The source of the raised temperature shall be investigated and eliminated by cleaning/tighten the
connection/inspect cable and insulation/check the load/inspection the internal component/change
the component, if possible.

20/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

40.6

Sp2

38.5

21/02/2016 04:06:27 PM

C
39.7
Sp1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
K13.03.10.19 VVVF FAN 4A

Sp2

IR_0919.jpg

FLIR E50

25.5
49025354

21/02/2016 04:06:27 PM

DC_0920.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

21/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Max

38.5

Min

31.8

Average

35.0

Max

39.8

Min

32.0

Average

35.8

21/02/2016 04:07:06 PM

C
40.1

Li2

Li1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
K13.03.07.19 VVVF FAN 3B

IR_0921.jpg

FLIR E50

24.7
49025354

21/02/2016 04:07:06 PM

DC_0922.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

22/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

30.7

Sp2

30.0

Sp3

30.2

21/02/2016 04:07:24 PM

C
31.8

Sp1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
K13.03.07.19 VVVF FAN 3B
Sp3
Sp2

IR_0923.jpg

FLIR E50

25.0
49025354

21/02/2016 04:07:24 PM

DC_0924.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

23/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Max

27.7

Min

25.4

Average

26.8

Max

32.5

Min

26.0

Average

28.3

21/02/2016 04:08:01 PM

C
32.3

Li2

Li1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
K13.03.14.19 VVVF FAN 5

IR_0925.jpg

FLIR E50

23.4
49025354

21/02/2016 04:08:01 PM

DC_0926.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

24/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Max

28.6

Min

26.2

Average

27.3

21/02/2016 04:08:18 PM

C
32.2

Li1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
K13.03.14.19 VVVF FAN 5

IR_0927.jpg

FLIR E50

24.7
49025354

21/02/2016 04:08:18 PM

DC_0928.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

25/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

78.2

Sp2

52.5

Sp3

49.1

Li1

Dt1

Max

42.5

Min

34.0

Average

39.1

Sp1 - Ref. temp.

21/02/2016 03:52:31 PM

C
76.3

Sp2

Li1

Sp1

8.2
Sp3

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
K13.03.08.19 VVVF FAN 3C

IR_0893.jpg

FLIR E50

27.2
49025354

21/02/2016 03:52:31 PM

Text annotations

DC_0894.jpg

Description of analysis & observation

Elevated temperature are observed on spot (1). The temp. exceeding reference temperature 70
C. The temp. diff. between the spot and the reference temperature is shown in the above
mentioned measurements table.

Action / Severity

Immediate repair required for the Sp (1). / Severity is high. This is strongly recommended as a
result of this suffered temp. will lead to fault immediately.

Code / Fault

One / Danger

Potential impact upon severity

Occur arcing/short circuiting/turn-to-turn faults/burning component/fire.

Conditions Found/Deviation

Loose connections/poor contacts/rust/unbalanced loads/deteriorated internal contact/overloading/


overheating is of concern.

Physical inspection/Electrical testing/Remedy

The source of the raised temperature shall be investigated and eliminated by cleaning/tighten the
connection/inspect cable and insulation/check the load/inspection the internal component/change
the component, if possible.
Infrared Thermal Imaging Inspection Report
Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

26/48

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

40.5

Sp2

44.7

Sp3

40.4

Li1

Max

39.2

Min

32.0

Average

35.2

21/02/2016 03:55:52 PM

C
43.7

Li1

Sp1
Sp2

Parameters
Emissivity
Refl. temp.

Sp3

0.95
20 C

Note
K13.03.12.19 VVVF FAN 4C

IR_0897.jpg

FLIR E50

25.7
49025354

21/02/2016 03:55:52 PM

DC_0898.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

27/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

46.2

Sp2

48.5

21/02/2016 03:56:20 PM

C
50.1

Parameters
Emissivity
Refl. temp.

Sp1

0.95
20 C

Note
K13.03.12.19 VVVF FAN 4C

Sp2

IR_0899.jpg

FLIR E50

27.1
49025354

21/02/2016 03:56:20 PM

DC_0900.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

28/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Max

42.1

Min

29.6

Average

36.2

Max

41.0

Min

30.6

Average

36.0

21/02/2016 03:57:13 PM

C
43.3

Li2

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note

Li1

K13.03.15.19 VVVF FAN 6

IR_0901.jpg

FLIR E50

25.1
49025354

21/02/2016 03:57:13 PM

DC_0902.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

29/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

35.3

Sp2

39.2

Sp3

34.2

21/02/2016 03:58:42 PM

Sp1

Parameters
Emissivity
Refl. temp.

C
39.2

0.95
20 C

Note
K13.03.15.19 VVVF FAN 6
Sp2
Sp3

IR_0905.jpg

FLIR E50

26.7
49025354

21/02/2016 03:58:42 PM

DC_0906.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

30/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

43.9

Sp2

40.4

Sp3

39.4

Li1

Dt1

Max

38.8

Min

30.7

Average

34.3

Sp1 - Sp3

21/02/2016 03:59:21 PM

C
43.1

Sp1

Sp2

4.5

Parameters
Emissivity
Refl. temp.

0.95
20 C

Sp3
Li1

Note
K13.03.09.19 VVVF FAN SP3

IR_0907.jpg

FLIR E50

25.7
49025354

21/02/2016 03:59:21 PM

DC_0908.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

31/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Sp1

21/02/2016 03:57:56 PM

C
39.4

39.3

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
K13.03.09.19 VVVF FAN SP3
Sp1

IR_0903.jpg

FLIR E50

26.1
49025354

21/02/2016 03:57:56 PM

DC_0904.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

32/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Max

42.0

Min

26.5

Average

36.7

Max

41.5

Min

28.6

Average

34.4

21/02/2016 04:00:07 PM

C
41.6

Li1

Li2

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
K13.03.13.19 VVVF FAN SP4

IR_0909.jpg

FLIR E50

25.0
49025354

21/02/2016 04:00:07 PM

DC_0910.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

33/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Sp1

21/02/2016 04:00:26 PM

C
35.0

25.6

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
K13.03.13.19 VVVF FAN SP4
Sp1

IR_0911.jpg

FLIR E50

24.6
49025354

21/02/2016 04:00:26 PM

DC_0912.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

34/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

42.1

Sp2

46.1

Sp3

44.1

Li1

Max

46.6

Min

33.5

Average

39.4

21/02/2016 03:46:06 PM

C
45.6

Sp1

Li1

Sp2

Sp3

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
K13.03.02.19 VVVF FAN 2A

IR_0873.jpg

FLIR E50

25.1
49025354

21/02/2016 03:46:06 PM

DC_0874.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

35/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

38.5

Sp2

40.6

Sp3

41.4

21/02/2016 03:46:24 PM

C
41.4

Sp1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Sp2

Note
K13.03.02.19 VVVF FAN 2A

Sp3

IR_0875.jpg

FLIR E50

28.0
49025354

21/02/2016 03:46:24 PM

DC_0876.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

36/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

53.5

Sp2

49.5

Sp3

51.1

Li1

Dt1

Max

46.9

Min

37.4

Average

42.7

Sp1 - Sp2

21/02/2016 03:47:14 PM

C
53.2

Sp1
Sp2

4.0

Li1

Sp3

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
K13.03.03.19 VVVF FAN 2B

IR_0877.jpg

FLIR E50

24.8
49025354

21/02/2016 03:47:14 PM

DC_0878.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

37/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

70.5

Sp2

42.4

Sp3

73.4

Li1

Li2

Max

72.9

Min

53.9

Average

70.2

Max

70.3

Min

46.1

Average

65.8

21/02/2016 03:47:28 PM

C
72.4

Sp1
Li2

Sp2

Parameters
Emissivity
Refl. temp.

Li1
Sp3

0.95
20 C

Note
K13.03.03.19 VVVF FAN 2B

IR_0879.jpg

FLIR E50

28.0
49025354

21/02/2016 03:47:28 PM

Text annotations
Description of analysis & observation

DC_0880.jpg
Elevated temperature are observed on spot (1&3). The temp. exceeding reference temperature
70C. The temp. diff. between the spot and the reference temperature is shown in the above
mentioned measurements table.

Action / Severity

Immediate repair required for the Sp (1&3). / Severity is high. This is strongly recommended as a
result of this suffered temp. will lead to fault immediately.

Code / Fault

One / Danger

Potential impact upon severity

Occur arcing/short circuiting/turn-to-turn faults/burning component/fire.

Conditions Found/Deviation

Loose connections/poor contacts/bad lug/rust/unbalanced loads/deteriorated internal contact/


overloading/overheating is of concern.

Physical inspection/Electrical testing/Remedy

The source of the raised temperature shall be investigated and eliminated by cleaning/tighten the
connection/crimp-on lug/replace with new lug/inspect cable and insulation/check the load/
inspection the internal component/change the component, if possible.

38/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Max

37.6

Min

29.9

Average

33.4

Max

37.7

Min

28.4

Average

33.8

21/02/2016 03:48:17 PM

C
37.6

Li1

Parameters
Emissivity
Refl. temp.

Li2

0.95
20 C

Note
K13.03.04.19 VVVF FAN 2C

IR_0881.jpg

FLIR E50

24.8
49025354

21/02/2016 03:48:17 PM

DC_0882.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

39/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

32.5

Sp2

34.0

Sp3

34.7

21/02/2016 03:48:34 PM

C
35.0
Sp1

Parameters
Emissivity
Refl. temp.

0.95
20 C
Sp2

Note
K13.03.04.19 VVVF FAN 2C

Sp3

IR_0883.jpg

FLIR E50

26.3
49025354

21/02/2016 03:48:34 PM

DC_0884.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

40/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Max

37.0

Min

31.1

Average

34.2

Max

36.4

Min

30.9

Average

33.6

21/02/2016 03:49:37 PM

Li1

Parameters
Emissivity
Refl. temp.

C
36.4

Li2

0.95
20 C

Note
K13.03.05.19 VVVF FAN SP2

IR_0885.jpg

FLIR E50

23.6
49025354

21/02/2016 03:49:37 PM

DC_0886.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

41/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

32.3

Sp2

32.1

Sp3

31.4

21/02/2016 03:49:59 PM

C
37.0

Sp1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
K13.03.05.19 VVVF FAN SP2
Sp2
Sp3

IR_0887.jpg

FLIR E50

26.0
49025354

21/02/2016 03:49:59 PM

DC_0888.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

42/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements

Sp1

44.5

Sp2

41.8

21/02/2016 03:51:03 PM

C
44.2

Parameters
Emissivity
Refl. temp.

0.95
20 C

Sp1

Note
K13.03.01.19 VVVF FAN 1
Sp2

IR_0889.jpg

FLIR E50

24.9
49025354

21/02/2016 03:51:03 PM

DC_0890.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

43/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Sp1

21/02/2016 03:51:21 PM

C
45.1

40.6

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
K13.03.01.19 VVVF FAN 1
Sp1

IR_0891.jpg

FLIR E50

25.1
49025354

21/02/2016 03:51:21 PM

DC_0892.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

44/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Max

37.7

Min

31.6

Average

35.1

Max

42.7

Min

36.0

Average

39.7

21/02/2016 04:22:04 PM

C
45.2

Li2

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
TA1.02.02.01 Water pump

Li1

IR_0939.jpg

FLIR E50

25.4
49025354

21/02/2016 04:22:04 PM

DC_0940.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which is
an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

45/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Li3

Max

29.5

Min

26.5

Average

27.6

Max

33.2

Min

28.1

Average

30.0

Max

36.0

Min

28.7

Average

31.3

21/02/2016 04:22:17 PM

C
42.6
Li3

Li2

Parameters
Emissivity
Refl. temp.

0.95
20 C
Li1

Note
TA1.02.02.01 Water pump

IR_0941.jpg

FLIR E50

24.8
49025354

21/02/2016 04:22:17 PM

DC_0942.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

46/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Max

39.9

Min

33.5

Average

36.6

Max

40.7

Min

30.0

Average

37.7

21/02/2016 04:22:46 PM

C
45.2

Li1

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note
TA1.02.02.02 Water pump
Li2

IR_0943.jpg

FLIR E50

27.4
49025354

21/02/2016 04:22:46 PM

DC_0944.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

47/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

Industrial Services Center - Datco


78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - Egypt
Web Site: http://www.datcoegypt.com
Measurements
Li1

Li2

Li3

Max

37.5

Min

29.6

Average

34.3

Max

30.9

Min

28.5

Average

29.7

Max

31.4

Min

26.1

Average

29.0

21/02/2016 04:23:06 PM

C
39.1
Li1

Li2

Parameters
Emissivity
Refl. temp.

0.95
20 C

Note

Li3

TA1.02.02.02 Water pump

IR_0945.jpg

FLIR E50

25.0
49025354

21/02/2016 04:23:06 PM

DC_0946.jpg

Text annotations
Description of analysis & observation

Normal conditions are observed, the temp. diff. is less than 5C as shown in the
above mentioned measurements table between the max. and the min. spots, which
is an acceptable diff.

Action / Severity

No Action required / No severity

Code / Fault

Normal condition / No fault

48/48

Infrared Thermal Imaging Inspection Report


Report Author: Sherif Mounir Ahmed
Mobile: +2 012 - 85 711 000
Email: sherif.mounir@datcoegypt.com

S-ar putea să vă placă și